36C25625Q0838 0004_1 SAM POSTING.pdf

PDF 278 KB Posted

Attached to
N063--Building 37 Med Gas Master Alarm Panel Installation
Solicitation number
36C25625Q0838
Issued by

About this file

This document is an Amendment to a Previous Combined Solicitation for the Department of Veterans Affairs (VA) medical gas master alarm panel installation project. The amendment extends the solicitation response date to 06/06/2025 at 3:00 PM Central Standard Time and provides responses to contractor questions. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB) under NAICS code 238290, with the project located at the G.V. (Sonny) Montgomery VAMC in Jackson, MS.

Key technical details include the requirement to install a new medical gas master alarm panel in Building 37, with new wiring required and an estimated cable routing distance of approximately 900 feet. The VA will accept the panel without emergency power, and contractors are instructed to use the Amico Alert-2 series master alarm panel as specified in the Statement of Work. The amendment includes clarifications about existing conduit, building interconnections, and provides additional documentation such as building floor plans and site maps to assist potential bidders in preparing their quotes.

View the file

Other files

File Type Posted
Med gas panel points of interest.pdf PDF
building 37.pdf PDF
IMG_0403.jpg JPG image
Building 1 basement blue print.pdf PDF
building 1 floor plan Med gas alarm panel bld 37.pdf PDF
36C25625Q0838 0003_1.pdf PDF
36C25625Q0838 0002_1.docx DOCX document
Building Floor Plan.pdf PDF
36C25625Q0838 0001_1.docx DOCX document
Panel Photo.pdf PDF
36C25625Q0838_1.docx DOCX document
Wage Determination No. 2015-5109 Revision 26.pdf PDF
Attachment D.4 Past Performance References.pdf PDF
S02. Attachment D.1 Final Invoice Memo.pdf PDF
Solicitation 36C25625Q0838.pdf PDF
Attachment D. 2 Drawing Engineering Shops.pdf PDF
Attachment D. 3 Campus Map.pdf PDF
Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Amendment to a Previous Combined Solicitation

*= Required Field Amendment to a Previous Combined Solicitation

SUBJECT* Building 37 Med Gas Master Alarm Panel Installation

GENERAL INFORMATION

CONTRACTING OFFICE’S ZIP CODE* 39216

SOLICITATION NUMBER* 36C25625Q0838

RESPONSE DATE/TIME/ZONE 06-06-2025 3 PM CENTRAL TIME, CHICAGO, USA

ARCHIVE 60 DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS N

SET-ASIDE SDVOSBC

PRODUCT SERVICE CODE* N063

NAICS CODE* 238290

CONTRACTING OFFICE ADDRESS Department of Veterans Affairs

G.V. (Sonny) Montgomery VAMC

1500 E. Woodrow Wilson Dr.

Jackson MS 39216

POINT OF CONTACT*

DIYONNE WILLIAMS

DIYONNE.WILLIAMS@VA.GOV

PLACE OF PERFORMANCE

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

AGENCY’S URL

URL DESCRIPTION

AGENCY CONTACT’S EMAIL ADDRESS

EMAIL DESCRIPTION

DESCRIPTION

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR

ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES

SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 3

0004 05-30-2025

10N16

Department of Veterans Affairs

Network Contracting Office 16

715 S Pear Orchard

Plaza 1

Ridgeland MS 39157

10N16

Department of Veterans Affairs

G.V. (Sonny) Montgomery VAMC

A&MM Service (90C)

715 South Pear Orchard Road

Ridgeland MS 39157

To all Offerors/Bidders

36C25625Q0838

05-20-2025

X

X X

X (1) One

The purpose of this amendment is to "extend" the solicitation due date for submission of quotes and to provide responses to questions that were received.

A. The updated hour and date specified for receipt of offers is extended to 06/06/2025 at 3:00 PM (CST).

B. Questions and Answers (Q&A) are provided on the following pages.

Note: Contractor must acknowledge this amendment by signing in box 15b and submit with quote before the solicitation due date. If not acknowledged, contractor may be ineligible for award at the discretion of the Contracting Officer.

End of Document

Medical Gas Panel Installation Questions and Answers Pt 2.

• Can you provide floor plans of the adjoining buildings between Bldg1 and Bldg 37 so we can attempt to identify a path of travel? The floor plan provided is not sufficient. We are requesting

1st floor and basement drawings.

• Prints for building 1 first floor, building 1 basement, building 37, and a sitemap have been provided.

• The new master alarm panel is required to be 120VAC e-power. NFPA chapter 5: 5.1.9.1(9) refers to power from the Life safety branch of the essential electrical system chapter 6:

6.7.5.1.2.3. If there is no e-power in this building, the new Master alarm panel will not pass final verification. Is the VA accepting a panel that will not meet code or can we propose a new location? Possible chiller plant, boiler plant, or an office in the building where maintenance personnel sit?

• VA will accept panel with no emergency power.

• Is there a chase, tunnel, or anything connecting the hospital to Bldg 37? If not, this would require digging to install conduit connecting the two buildings. There is not a chase or tunnel. There is buried conduit connecting building 1 to building 37. There is no drawing of the path of the conduit. Do you know the size of the buried conduit? Is there space to pull additional wire? Is there a pull string on both ends of the conduit?

• A pull string in building 37 was not found. In building 37 the conduit appears to be 2 inch. Pipe size has not been verified after it leaves building 37.

• Could you confirm the approximate distance from the source building to the new panel location in Building 37 where alarm wiring will need to be routed?

• An approximate distance of 900ft was estimated using google earth for a route of the cable. This estimate does not account for any deviations that may be required to route the cable around obstacles. This route is a guess and may differ from the route you choose to take.

• Recommend field verifying route for cables and distances.

• Please see attachment med gas points of interest

• How many alarm source wires will be required for proper functionality?

• It will need to be the amount of wires required to provide the same functions as the Master alarm panel in the picture provided previously. Please reference manufacturer’s specifications for wiring requirements.

• Is there existing alarm wiring in Building 37, or will new wiring be required entirely?

• New wiring will be required.

• If new wiring is needed, is there existing underground conduit available for use to pull the wiring? Yes, but you will need to verify if it is sufficient.

• If so, can you provide the conduit size and path layout to assist in determining capacity and compatibility? I can not confirm the path.

• In building 37 the conduit appears to be 2 inch. Pipe size has not been verified after it leaves building 37

• Lastly, we’d like to note that the Amico Alert-2 system is now obsolete. The current model is the

Amico Alert-3. Please confirm whether the VA intends to proceed with the Alert-3 model or has an alternative requirement. The Amico Alert-2series Master alarm panel is what is stated in the

SOW. Please proceed with what is stated in the SOW.

See attached document: IMG_0403.

See attached document: Med gas panel points of interest.

See attached document: building 37.

See attached document: Building 1 basement blue print.

See attached document: building 1 floor plan Med gas alarm panel bld 37 02.

End of Document