S30. 2024 Annual Medical Gas Inspection - G.V. Sonny Montgomery VAMC.pdf

PDF 4 MB Posted

Attached to
J043--Medical Air/Vacuum- Inspection and Repair Service
Solicitation number
36C25625Q0790
Issued by

About this file

This document is a comprehensive annual medical gas inspection report for the G. V. (Sonny) Montgomery VA Medical Center in Jackson, Mississippi, conducted on October 15-18, 2024, by Environmental & Medical Gas Services. The inspection covered multiple medical gas systems, including oxygen, medical air, medical vacuum, nitrous oxide, and nitrogen across various hospital areas such as ambulatory surgery, emergency department, ICU, cardiology, dialysis, and patient rooms.

The report details extensive testing of medical gas infrastructure, including zone valves, area alarms, master alarms, outlet testing, and manifold systems. Several deficiencies were identified, including leaking oxygen outlets in the ENT Clinic, improperly labeled nitrogen manifold pipelines, and a zone valve located inside the area it serves in the Ambulatory Surgery area. Recommendations include replacing outlets, adding proper signage, replacing pigtails, and relocating zone valves to comply with medical gas system safety standards. The inspection was performed in accordance with NFPA 99 standards and covered 368 oxygen outlets, 360 medical air outlets, 448 medical vacuum outlets, and various other medical gas system components.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G. V. (SONNY) MONTGOMERY VA MEDICAL CENTER

Location: Jackson, MS

2024 ANNUAL MEDICAL

GAS INSPECTION

Date: 10/15/2024 - 10/18/2024

Medical Gas Survey & Inspection Performed by:

Report ID: BTM24289-1

ENVIRONMENTAL & MEDICAL GAS SERVICES

218 W Lorenz Blvd. - Jackson, MS 39213 Ph: (601)981-1861 • Fax: (601)981-1869 www.emgsi.com • testing@emgsi.com

Index Title:

Index:

Affidavit:

Credentials:

Inventory:

Summary of Findings:

Detail Report on Findings:

Summary of Corrections Detail Report on Corrections:

Master Alarms Testing:

Area Alarms Testing:

Zone Valves Testing:

Outlet Purity Testing:

Outlet Testing:

Manifold Testing:

Compressor Testing:

Vacuum Testing:

Bulk Gas Testing:

EOSC Testing:

Page 4 - 6 Page 7 - 8 Page 9 - 13 Page 14 - 23 Page 24 - 26 Page 27 - 34 Page 35 - 41 Page 42 - 75 Page 76 - 125 Page 126 - 128 Page 129 - 186 Page 187 - 193 Page 194 - 199 Page 200 - 204 Page 205 - 210 Page 211 - 213

FINAL FIELD AFFIDAVIT

ANNUAL INSPECTION/TESTING SERVICES

MEDICAL GAS SYSTEMS & EQUIPMENT

Company - CONFIDENTIAL

Repairs were made to the medical gas system(s) at G. V. (Sonny) Montgomery VA Medical Center by a qualified ASSE 6040 Technician (see name above). These repairs occurred during the same time period as the testing so documentation is included as applicable to any repairs made.

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Ph: (601)981-1861 Fax: (601)981-1869 www.emgsi.com

Bryan Teasley Environmental & Medical Gas Services Representative

10/15/2024 - 10/18/2024

Field Affidavit # BTM24289-1

Stephen Bishop G. V. (Sonny) Montgomery VA Medical Center Jackson, MS

Primary Med Gas Authorized Person:

To Whom It May Concern:

In accordance with the terms of the contract documents and NFPA 99 - 2012 edition, I the undersigned, as a duly appointed representative of Capitol Medical Supply, Inc., have conducted the following:

Annual Inspection Completed per the requirements of NFPA 99

SEE ATTACHED DATA SHEETS: DATA SHEETS MUST BE ATTACHED

The Contractor verifies that he is responsible for identification of all the equipment to be certified in the system as of this date. Any equipment not listed on the attached worksheets is the responsibility of the Contractor

HOLD HARMLESS CLAUSE:

The above certification applies to the condition of the detailed, itemized list of equipment as of date noted. Capitol Medical Supply, Inc. will be held harmless from any liability caused by any modification of the piping system including but not limited to the gas outlets, alarms, zone valves, manifolds or supply gases at a later date.

Representative Credentials

Page: 4COMPANY Confidential

Page: 5

Representative Credentials

Page: 6

Representative Credentials

Inventory Totals

Page: 7COMPANY Confidential

Medical Gas Inventory Totals

Page: 8

G. V. (Sonny) Montgomery VA Medical Center

Outlets Oxygen - 368 Med Air - 360 Med Vac - 448 Nitrous Oxide - 7 Nitrogen - 9

WAGD - 4

Zone Valves Oxygen - 47 Med Air - 49 Med Vac - 49 Nitrous Oxide - 7 Nitrogen - 7

Area Alarms Oxygen - 33 Med Air - 33 Med Vac - 33 Nitrous Oxide - 1 Nitrogen - 1

Master Alarms Oxygen - 12 Med Air - 16 Med Vac - 10 Nitrous Oxide - 6 Nitrogen - 6

1196 159

101 50

Findings

Page: 9COMPANY Confidential

Deficiency List G. V. (Sonny) Montgomery VA Medical Center

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description DateRecommendationID#

Summary of Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

25116 Manifold Room Behind Shipping Nitrogen Amico

M2HD-D-HH-U-NIT

Medical gas cylinders need to have proper signage and segragation, indicating which cylinders are full/empty.

Recommend adding signage as to which cylinders are empty/full. 10/18/2024

25118 Manifold Room Behind Shipping Nitrogen Amico

M2HD-D-HH-U-NIT

Pigtails are to be replaced every 5 years per the manufacturer's recommendation.

Recommend replacing the pigtails.

8x Nitrogen

10/18/2024

25163 Manifold Room Behind Shipping Nitrogen Amico

M2HD-D-HH-U-NIT

Pipingtypepropertlylabeled = FAIL Recommend installing proper Nitrogen labels on the pipeline 10/21/2024

25119 Manifold Room loading Dock N2O Amico M2HD-

D-HH-U-N2O

Pigtails are to be replaced every 5 years per the manufacturer's recommendation.

Recommend replacing the pigtails.

8x N2O

10/18/2024

25120 Manifold Room loading Dock N2O Amico M2HD-

D-HH-U-N2O

Pipingtypepropertlylabeled = FAIL 10/18/2024

25165 Medical Vacuum Exhaust Exhaust for the Medical Vacuum system is not turned down with a non corrosive screen installed.

Install a 90 degree turn down with a non corrosive screen. 10/18/2024

25171 Zone Valve serving Neurology Lab gas turrets.

MGZV02-06

The lab is being used as a break room now. Recommend removing handles from zone valve and draining the line pressures.

10/18/2024

Deficiency List for G. V. (Sonny) Montgomery VA Medical Center10/21/2024 Page: 10

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description DateRecommendationID#

Summary of Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

25182 Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C331 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Horizon

Leaking from front body Recommend replacing the outlet. 10/21/2024

25185 Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C334 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Horizon

Leaking from front body Recommend replacing the outlet. 10/21/2024

25186 Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C334 Gas Type: Oxygen Outlet Number: 2 Outlet Model: Horizon

Leaking from front body Recommend replacing the outlet. 10/21/2024

25183 Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C335 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Horizon

Leaking from front body Recommend replacing the outlet. 10/21/2024

25184 Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C335 Gas Type: Oxygen Outlet Number: 2 Outlet Model: Horizon

Leaking from front body Recommend replacing the outlet. 10/21/2024

Deficiency List for G. V. (Sonny) Montgomery VA Medical Center10/21/2024 Page: 11

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description DateRecommendationID#

Summary of Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

25187 Floor 4 Area Served: Cardiology

(MGZV04-06)

Room Number: K-429 Gas Type: Med Vac Outlet Number: 3 Outlet Model: Diamond 3

Inlet is being used with a WAGD hose Recommend replacing the vacuum ceiling inlet with a WAGD inlet.

Hose Vac DISS fitting to be replaced with a WAGD Female DISS as well

10/21/2024

Deficiency List for G. V. (Sonny) Montgomery VA Medical Center10/21/2024 Page: 12

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description DateRecommendationID#

Summary of Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

25193 Basement Ambulatory Surgery 1-10 Oxygen, MedAir,MedVac Zone Valve MGZVB-11

Intervening wall exists = FAIL

Zone Valve is inside the area it serves.

Recommend relocating the zone valve to a place where a wall intervenes it from the outlets it serves.

Deficiency List for G. V. (Sonny) Montgomery VA Medical Center10/21/2024 Page: 13

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

General Medical Gas Issues

Manifold Room Behind Shipping Nitrogen Amico

M2HD-D-HH-U-NIT

Medical gas cylinders need to have proper signage and segragation, indicating which cylinders are full/empty.

Medium 10/18/2024Recommend adding signage as to which cylinders are empty/full.

25116

Page: 14

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Manifold Room Behind Shipping Nitrogen Amico

M2HD-D-HH-U-NIT

Pigtails are to be replaced every 5 years per the manufacturer's recommendation.

Medium 10/18/2024Recommend replacing the pigtails.

8x Nitrogen25118

Page: 15

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Manifold Room Behind Shipping Nitrogen Amico

M2HD-D-HH-U-NIT

Pipingtypepropertlylabeled = FAIL Medium 10/21/2024Recommend installing proper Nitrogen labels on the pipeline25163

Manifold Room loading Dock N2O Amico M2HD-D-

HH-U-N2O

Pigtails are to be replaced every 5 years per the manufacturer's recommendation.

Medium 10/18/2024Recommend replacing the pigtails.

8x N2O25119

Page: 16

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Manifold Room loading Dock N2O Amico M2HD-D-

HH-U-N2O

Pipingtypepropertlylabeled = FAIL Medium 10/18/2024

25120

Page: 17

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Medical Vacuum Exhaust Exhaust for the Medical Vacuum system is not turned down with a non corrosive screen installed.

Medium 10/18/2024Install a 90 degree turn down with a non corrosive screen.

25165

Page: 18

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Zone Valve serving Neurology Lab gas turrets.

MGZV02-06

The lab is being used as a break room now. Medium 10/18/2024Recommend removing handles from zone valve and draining the line pressures.

25171

Page: 19

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Medical Gas Outlet / Inlet Issues

Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C331 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Horizon

Leaking from front body Medium 10/21/2024Recommend replacing the outlet.

25182

Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C334 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Horizon

Leaking from front body Medium 10/21/2024Recommend replacing the outlet.

25185

Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C334 Gas Type: Oxygen Outlet Number: 2 Outlet Model: Horizon

Leaking from front body Medium 10/21/2024Recommend replacing the outlet.

25186

Page: 20

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C335 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Horizon

Leaking from front body Medium 10/21/2024Recommend replacing the outlet.

25183

Floor 3 Area Served: ENT Clinic

(MGZV03-04)

Room Number: C335 Gas Type: Oxygen Outlet Number: 2 Outlet Model: Horizon

Leaking from front body Medium 10/21/2024Recommend replacing the outlet.

25184

Page: 21

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Floor 4 Area Served: Cardiology

(MGZV04-06)

Room Number: K-429 Gas Type: Med Vac Outlet Number: 3 Outlet Model: Diamond 3

Inlet is being used with a WAGD hose Medium 10/21/2024Recommend replacing the vacuum ceiling inlet with a WAGD inlet.

Hose Vac DISS fitting to be replaced with a WAGD Female DISS as well

25187

Page: 22

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Deficiency Description Priority DateRecommended SolutionID#

Detail Report on Findings

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

Medical Gas Zone Valve Issues

Basement Ambulatory Surgery 1-10 Oxygen, MedAir,MedVac Zone Valve

MGZVB-11

Intervening wall exists = FAIL

Zone Valve is inside the area it serves.

Medium 10/21/2024Recommend relocating the zone valve to a place where a wall intervenes it from the outlets it serves.25193

Page: 23

Corrections

Page: 24COMPANY Confidential

Corrections List

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description DateCorrective ActionID#

Summary of Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

25179 Bulk Oxygen Valve Tag There were no tags identifying areas served. Tag had become discolored from the elements.

Replaced tag with a new metal source valve tag. Date found:

10/21/2024

Date repaired:

10/21/2024

25178 Medical Air Source Valve Tag

There were no tags identifying areas served. Added Source Valve Tag Date found:

10/21/2024

Date repaired:

10/21/2024

25177 Medical Vacuum Source Valve Tag

There were no tags identifying areas served. Replaced Source Valve Tag with correct labeling and color. Date found:

10/21/2024

Date repaired:

Correction List for G. V. (Sonny) Montgomery VA Medical Center10/21/2024 Page: 25

Corrections List

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description DateCorrective ActionID#

Summary of Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

25189 Basement Area Served: Radiology

(MGZVB-03)

Room Number: B07 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Diamond 3

Leaking from back body Outlet repaired with repair kit Date found:

10/17/2024

Date repaired:

10/17/2024

25192 Floor 2 Area Served: Module C

(MGZV02-03)

Room Number: C-221 Gas Type: Oxygen Outlet Number: 1 Outlet Model: O-QDWAL

Leaking from front body Outlet repaired with repair kit Date found:

10/21/2024

Date repaired:

10/21/2024

25191 Floor 3 Area Served: PMRS

(MGZV03-01)

Room Number: 3049 Gas Type: Oxygen Outlet Number: 1 Outlet Model: O-QDWAL

Leaking from front body Outlet repaired with repair kit Date found:

10/15/2024

Date repaired:

10/15/2024

25033 Floor 4 Area Served: Dialysis

(MGZV04-05)

Room Number: 6 Gas Type: Med Air Outlet Number: 1 Outlet Model: O-QDWAL

Leaking from front body Outlet repaired with repair kit Date found:

10/15/2024

Date repaired:

10/15/2024

25188 Floor 4 Area Served: Patient

(MGZV04-03)

Room Number: 4130 Gas Type: Med Air Outlet Number: 1 Outlet Model: O-QDCON

Leaking from front body Outlet repaired with repair kit Date found:

10/15/2024

Date repaired:

10/15/2024

Correction List for G. V. (Sonny) Montgomery VA Medical Center10/21/2024 Page: 26

Closed / Resolved Issue List

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

There were no tags identifying areas served. Tag had become discolored from the elements.

Replaced tag with a new metal source valve tag.

10/21/2024Bulk Oxygen Valve Tag

25179

Page: 27

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

There were no tags identifying areas served. Added Source Valve Tag 10/21/2024Medical Air Source Valve Tag

25178

Page: 28

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

There were no tags identifying areas served. Replaced Source Valve Tag with correct labeling and color.

10/21/2024Medical Vacuum Source Valve Tag

25177

Page: 29

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

Leaking from back body Outlet repaired with repair kit 10/17/2024Basement Area Served: Radiology (MGZVB -03) Room Number: B07 Gas Type: Oxygen Outlet Number: 1 Outlet Model: Diamond 3

25189

Page: 30

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

Leaking from front body Outlet repaired with repair kit 10/21/2024Floor 2 Area Served: Module C (MGZV02 -03) Room Number: C-221 Gas Type: Oxygen Outlet Number: 1 Outlet Model: O-QDWAL

25192

Page: 31

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

Leaking from front body Outlet repaired with repair kit 10/15/2024Floor 3 Area Served: PMRS (MGZV03-01) Room Number: 3049 Gas Type: Oxygen Outlet Number: 1 Outlet Model: O-QDWAL

25191

Page: 32

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

Leaking from front body Outlet repaired with repair kit 10/15/2024Floor 4 Area Served: Dialysis (MGZV04-05) Room Number: 6 Gas Type: Med Air Outlet Number: 1 Outlet Model: O-QDWAL

25033

Page: 33

BTM24289-1 -- 2024 Annual Medical Gas Inspection

Item Description Resolution Date

Completed

Detail Report on Corrections

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

(601)981-1861 (601)981-1869 www.emgsi.com

ID#

Leaking from front body Outlet repaired with repair kit 10/15/2024Floor 4 Area Served: Patient (MGZV04-03) Room Number: 4130 Gas Type: Med Air Outlet Number: 1 Outlet Model: O-QDCON

25188

Page: 34

Master Alarms

Page: 35COMPANY Confidential

Master Alarm Report G. V. (Sonny) Montgomery VA Medical CenterFacility 10/18/2024Date Stephen BishopJob Contact Bryan TeasleyInspector

Alarm Visual Test

EngineeringPanel Location Alert-2 AreaModel AmicoManufacturer MGMA01-01Label

Master Alarm Panel Verification Audible TestSensor Location

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 Fax: (601)981-1869 www.emgsi.com

PASSPASSBoiler RoomOxygen High Line Pressure

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSBoiler RoomOxygen Low Line Pressure

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Reserve Supply in Use

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Main Tank Liquid Level Low

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Reserve Tank Liquid Level Low

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Reserve Low Pressure

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSBoiler RoomMed Air High Line Pressure

Med Air Air Compressor - Boiler Room

PASSPASSBoiler RoomMed Air Low Line Pressure

Med Air Air Compressor - Boiler Room

PASSPASSASEMed Air Dew Point High Med Air Air Compressor -

Boiler Room

COMPANY Confidential Page: 36

Alarm Visual Test

EngineeringPanel Location Alert-2 AreaModel AmicoManufacturer MGMA01-01Label

Master Alarm Panel Verification Audible TestSensor Location

PASSPASSASEMed Air Carbon Monoxide High

Med Air Air Compressor - Boiler Room

PASSPASSASEMed Air Lag Compressor in Use

Med Air Air Compressor - Boiler Room

PASSPASSASEMed Air Compressor High Temp Unit 1

Med Air Air Compressor - Boiler Room

PASSPASSASEMed Air Compressor High Temp Unit 2

Med Air Air Compressor - Boiler Room

PASSPASSASEMed Air Compressor High Temp Unit 3

Med Air Air Compressor - Boiler Room

PASSPASSBoiler RoomMed Vac Low Vacuum Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Lag Pump in

Use Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Pump High

Temp Unit 1 Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Pump High

Temp Unit 2 Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Pump High

Temp Unit 3 Med Vac Vacuum Pump -

Boiler Room PASSPASSASEN2O High Line Pressure

N2O Manifold - Manifold Room loading Dock

PASSPASSASEN2O Low Line Pressure N2O Manifold - Manifold

Room loading Dock PASSPASSASEN2O Cylinder Bank

Changeover N2O Manifold - Manifold

Room loading Dock COMPANY Confidential Page: 37

EngineeringPanel Location Alert-2 AreaModel AmicoManufacturer MGMA01-01Label

Master Alarm Panel Verification Audible TestSensor Location

PASSPASSASENitrogen High Line Pressure

Nitrogen Manifold - Manifold Room Behind

Shipping PASSPASSASENitrogen Low Line

Pressure Nitrogen Manifold -

Manifold Room Behind Shipping

PASSPASSASENitrogen Cylinder Bank Changeover

Nitrogen Manifold - Manifold Room Behind

Shipping Inspection Items

The following items were inspected as part of the verification in accordance with NFPA 99:

PASSItem 1: Functional test passed with no failures detected

Item 2: All low voltage wiring is supervised Item 3: Means to test for visual or audible alarm failure (i.e. test switch) Item 4: Provision for automatic restart in the event of a power outage Item 5: Visual and audible indication that wiring to an alarm initiating device is disconnected Item 6: Alarm panel is powered from the Life Safety Branch of the Emergency Power Circuit

PASS

PASS

PASS

PASS

PASS

COMPANY Confidential Page: 38

PBXPanel Location Tan FaceModel MedaesManufacturer MGMA01-02Label

Master Alarm Panel Verification Audible TestSensor Location

PASSPASSBoiler RoomOxygen High Line Pressure

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSBoiler RoomOxygen Low Line Pressure

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Reserve Supply in Use

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Main Tank Liquid Level Low

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Reserve Tank Liquid Level Low

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSASEOxygen Reserve Low Pressure

Oxygen Bulk Tank - Outside Plant Ops.

PASSPASSBoiler RoomMed Air High Line Pressure

Med Air Air Compressor - Boiler Room

PASSPASSBoiler RoomMed Air Low Line Pressure

Med Air Air Compressor - Boiler Room

PASSPASSASEMed Air Dew Point High Med Air Air Compressor -

Boiler Room PASSPASSASEMed Air Carbon Monoxide

High Med Air Air Compressor -

Boiler Room PASSPASSASEMed Air Lag Compressor in Use Med Air Air Compressor -

Boiler Room PASSPASSASEMed Air Compressor High

Temp Unit 1 Med Air Air Compressor -

Boiler Room

COMPANY Confidential Page: 39

MedaesManufacturer MGMA01-02Label

Master Alarm Panel Verification Audible TestSensor Location

PASSPASSASEMed Air Compressor High Temp Unit 2

Med Air Air Compressor - Boiler Room

PASSPASSASEMed Air Compressor High Temp Unit 3

Med Air Air Compressor - Boiler Room

PASSPASSBoiler RoomMed Vac Low Vacuum Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Lag Pump in

Use Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Pump High

Temp Unit 1 Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Pump High

Temp Unit 2 Med Vac Vacuum Pump -

Boiler Room PASSPASSASEMed Vac Pump High

Temp Unit 3 Med Vac Vacuum Pump -

Boiler Room PASSPASSASEN2O High Line Pressure

N2O Manifold - Manifold Room loading Dock

PASSPASSASEN2O Low Line Pressure N2O Manifold - Manifold

Room loading Dock PASSPASSASEN2O Cylinder Bank

Changeover N2O Manifold - Manifold

Room loading Dock PASSPASSASENitrogen High Line

Pressure Nitrogen Manifold -

Manifold Room Behind Shipping

PASSPASSASENitrogen Low Line Pressure

Nitrogen Manifold - Manifold Room Behind

Shipping

COMPANY Confidential Page: 40

MedaesManufacturer MGMA01-02Label

Master Alarm Panel Verification Audible TestSensor Location

PASSPASSASENitrogen Cylinder Bank Changeover

Nitrogen Manifold - Manifold Room Behind

Shipping Inspection Items

The following items were inspected as part of the verification in accordance with NFPA 99:

PASSItem 1: Functional test passed with no failures detected

Item 2: All low voltage wiring is supervised Item 3: Means to test for visual or audible alarm failure (i.e. test switch) Item 4: Provision for automatic restart in the event of a power outage Item 5: Visual and audible indication that wiring to an alarm initiating device is disconnected Item 6: Alarm panel is powered from the Life Safety Branch of the Emergency Power Circuit

PASS

PASS

PASS

PASS

PASS

COMPANY Confidential Page: 41

Area Alarms

Page: 42COMPANY Confidential

Area Alarm Report - Ohmeda - Tan Face

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-06Label 1-10Room Numbers

Sen Loc to

ZVB

Sensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSAmbulatory Surgery PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS Med Vac 12” Hg N/A PASS PASS

COMPANY Confidential Page: 43

Area Alarm Report - Amico - Alert-2 Area

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-08Label A-19-22, A-26-29Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSBiomed PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 44

Area Alarm Report - Medaes - Tan Face

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-04Label F11, F13, F17,F19, B08A-B08FRoom Numbers

Sen Loc to

ZVB

Sensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSCAT SCAN PASS PASS

Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 45

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-07Label K-3Room Numbers

Sen Loc to

ZVB

Sensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSEKG/LAB PASS PASS

Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 46

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-09Label K-20B,C,E,F,GRoom Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSEndo PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 47

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-03Label 1-16Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSInfusion PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 48

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-02Label D-21 - D-38Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSOncology PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 49

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-10Label 1-8, isolationRoom Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSP.A.C.U PASS PASS

Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 50

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-01Label Bo6,B09Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSRadiology PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 51

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor Label F11,F13,F17,B08A, B08F, F19Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSRadiology PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 52

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGAAB-05Label OR1-7, AnesthesiaRoom Numbers

Sen Loc to

ZVB

Sensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSSurgery PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS Med Vac 12” Hg N/A PASS PASS

N2O 40 PSI 60 PSI PASS PASS

Nitrogen 135 PSI 205 PSI PASS PASS

COMPANY Confidential Page: 53

Stephen BishopJob Contact Bryan TeasleyInspector Floor 1Floor MGAA01-01Label 1121A-H, 1104-1106, 1109-1114, 1119,, 1121A-H, E-139, E-143Room Numbers

Sen Loc to

ZVB

Sensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSEmergency Department PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 54

Area Alarm Report - Amico - Alert-3 LCD

Stephen BishopJob Contact Bryan TeasleyInspector Floor 2Floor MGAA02-06Label H130-H146,H150-H160Room Numbers

Remote (in Zone Valve)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSCLC Patients PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 55

Stephen BishopJob Contact Bryan TeasleyInspector Floor 2Floor MGAA02-02Label 215,216,218,222,224,227Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSH.A.C PASS PASS

Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 56

Stephen BishopJob Contact Bryan TeasleyInspector Floor 2Floor MGAA02-03Label C203-C221Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSModule C PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 57

Stephen BishopJob Contact Bryan TeasleyInspector Floor 2Floor MGAA02-04Label C234-240Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSModule D PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 58

Stephen BishopJob Contact Bryan TeasleyInspector Floor 2Floor MGAA03-03Label 316,319Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSModule F PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 59

Stephen BishopJob Contact Bryan TeasleyInspector Floor 2Floor MGAA02-05Label C252,253,255,257,261,262,264,265,255,268-281Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSModule G PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 60

Stephen BishopJob Contact Bryan TeasleyInspector Floor 3Floor MGAA03-04Label C326,329,331,332,334,335,336Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSENT Clinic PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 61

Stephen BishopJob Contact Bryan TeasleyInspector Floor 3Floor MGAA03-01Label 3048, 3049Room Numbers

Remote (in Zone Valve)Sen Loc to

ZVB

Upstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPMRS PASS PASS

Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 62

Stephen BishopJob Contact Bryan TeasleyInspector Floor 3Floor MGAA02-01Label L231-252Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSSleep Lab PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 63

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-06Label K419,422,424,426,429Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSCardiology PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 64

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-05Label 1-15Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSDialysis PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 65

Area Alarm Report - Amico - AVU-202A4V (Alarm Valve Combo)

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-08Label L421,423,425,427,429,431Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSICU PASS PASS

Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 66

Area Alarm Report - Amico - AVU-202A4V (Alarm Valve Combo)

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-07Label L442,444,446,448Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSICU PASS PASS

Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 67

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-09Label 4235,4239,4240,4243,4245,4247Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients 4C PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 68

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-11Label 4254,4255,4260,4263,4266,4267,4269,4270Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients 4C PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 69

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-12Label 4272,4274,4275,4277,4280,4284,4285Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients 4C PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 70

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-10Label 4287,4289,4292,4293,4296,4298,4301Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients 4C PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 71

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-02Label 4104,4110,4112,4116Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 72

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-01Label 4120,4121,4125Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 73

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-03Label 4129-4134Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 74

Stephen BishopJob Contact Bryan TeasleyInspector Floor 4Floor MGAA04-04Label 4136,4137,4138,4144Room Numbers

Local (in Alarm Box)Sen Loc to

ZVB

Downstream of ZVBSensor Type

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

PASSPASSPASSPatients PASS PASS Area(s) Served

Ability for automatic restart

Area Alarm Verification

VIS and AUD indication wiring disc

Means to test VIS and AUD failure

Alarm panel powered from emerg pwr Test Switch

Alarm Type Low Alarm High Alarm Visual Test Audible Test

Oxygen 40 PSI 60 PSI PASS PASS Med Air 40 PSI 60 PSI PASS PASS

COMPANY Confidential Page: 75

Zone Valves

Page: 76COMPANY Confidential

Zone Valve Box Report

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGZVB-11Label

Room Numbers Hill RomManufacturer1-10

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

Gas Type Valve Size

Area(s) Served Leak Test

PASS

Zone Valve Box Verification

Not behind doors or hidden

PASSAmbulatory Surgery

Cover plate Accessible

PASS PASS

Intervening wall exist between zone valve and the outlets served

FAIL

1"Oxygen 1"Med Air

1-3/4"Med Vac

COMPANY Confidential Page: 77

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGZVB-13Label

Room Numbers AmicoManufacturerA-19-22 - A-26-29

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

Gas Type Valve Size

Area(s) Served Leak Test

PASS

Zone Valve Box Verification

Not behind doors or hidden

PASSBiomed

Cover plate Accessible

PASS PASS

Intervening wall exist between zone valve and the outlets served

PASS

1"Oxygen 1"Med Air

1-1/2"Med Vac

COMPANY Confidential Page: 78

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGZVB-06Label

Room Numbers OhmedaManufacturerB-14

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

Gas Type Valve Size

Area(s) Served Leak Test

PASS

Zone Valve Box Verification

Not behind doors or hidden

PASSBioMed

Cover plate Accessible

PASS PASS

Intervening wall exist between zone valve and the outlets served

PASS

1"Med Air

COMPANY Confidential Page: 79

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGZVB-08Label

Room Numbers Medical Gas SystemsManufacturerF11, F13, F17,F19, B08A-B08F

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

Gas Type Valve Size

Area(s) Served Leak Test

PASS

Zone Valve Box Verification

Not behind doors or hidden

PASSCAT SCAN

Cover plate Accessible

PASS PASS

Intervening wall exist between zone valve and the outlets served

PASS

1"Oxygen 1"Med Air

COMPANY Confidential Page: 80

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGZVB-01Label

Room Numbers MedaesManufacturerE-5

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

Gas Type Valve Size

Area(s) Served Leak Test

PASS

Zone Valve Box Verification

Not behind doors or hidden

PASSE-5

Cover plate Accessible

PASS PASS

Intervening wall exist between zone valve and the outlets served

PASS

1/2"Oxygen 1/2"Med Air 1/2"Med Vac

COMPANY Confidential Page: 81

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGZVB-02Label

Room Numbers MedaesManufacturerE-5A

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

Gas Type Valve Size

Area(s) Served Leak Test

PASS

Zone Valve Box Verification

Not behind doors or hidden

PASSE-5

Cover plate Accessible

PASS PASS

Intervening wall exist between zone valve and the outlets served

PASS

1/2"Oxygen 1/2"Med Air 3/4"Med Vac

COMPANY Confidential Page: 82

Stephen BishopJob Contact Bryan TeasleyInspector BasementFloor MGZVB-12Label

Room Numbers OhmedaManufacturerK-3

Environmental & Medical Gas Services 218 W Lorenz Blvd.

Jackson, MS 39213

Phone: (601)981-1861 | Fax: (601)981-1869 www.emgsi.com

Gas Type Valve Size

Area(s) Served Leak Test

PASS

Zone Valve Box Verification

Not behind doors or hidden

PASSEKG/LAB

Cover plate Accessible

PASS PASS

Intervening wall exist between zone valve and the outlets served

PASS

3/4"Oxygen 3/4"Med Air

COMPANY Confidential Page: 83

Stephen BishopJob…