This document is a Load Shed Priority list that appears to be related to a federal contract opportunity for troubleshooting and repair of Automatic Transfer Switches (ATS) for the Southeast Louisiana Veterans Healthcare System.
The key details are:
- The Load Shed Priority list assigns priority levels from 1-7 to various electrical equipment and systems, including elevators, fire pumps, and UPS systems.
- The related federal contract opportunity is Solicitation Number 36C25624Q1131, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 as a SDVOSB set-aside. The contract is for a base period of 09/15/2024 - 11/14/2024 to provide troubleshooting and repair services for ATS located at the Southeast Louisiana Veterans Healthcare System in New Orleans, LA. Quotes are due by 10:00 AM CST on 08/29/2024.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Load Shed pg 2.pdf | ||
| 7ES611 bldg control single line Diagram.pdf | ||
| 36C25624Q1131 0003.docx | DOCX document | |
| RFI for ATS Troubleshooting.docx | DOCX document | |
| 36C25624Q1131 0002.docx | DOCX document | |
| ATS Troubleshoot walk through sign in 1.pdf | ||
| 36C25624Q1131 A0001.docx | DOCX document | |
| 36C25624Q1131 F.docx | DOCX document | |
| 36C25624Q1131.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
From Sheet 7E5611
ATS Priority from 7E5713 LS BT DT TP EL ES ASCO Type Correct function confirmed Notes
EL8-1 Priority 1 X X . This ATS not shown on 7ES611, on Research dwg.
EQ8-1 Priority 2 X X X x X Elevators, but not assigning the lower priority
ELS8-1 Priority 1 X X
ELS9-1 Priority 1 X X "RI" on dwg. Thought to be BT. Not correct.
EI19-1 Priority 1 X X
EQ9-1 Priority 2 X X X X
Fire Pump Priority 1 X X Need to confirm remote test feature
Fire Pump Priority 1 X No remote test
Fire Pump Priority 1 X No remote test
1J5502-1A Priority 3
USS02-16 . Priority 3
USS02-2A Priority 3
USS02-26 Priority 3
USS01-A Priority 3
USS01-B Priority 3
USS07-A Priority 4
USS07-13 Priority 4
USS03-A Priority 5
USS03-13 Priority 5
USSO4 Priority 5
USSO6 Priority 5
USS08-A Priority 5
USS08-8 Priority 5
USSO9 Priority 5
UPS07-B CH 1 , Priority 6
UPS07-8 CH 2 Priority 6
UPS07-6 CH 3 Priority 6
UPS07-A CH 4 Priority 7
UPS07-A CH 5 , Priority 7
UPS07-A CH 6 Priority 7 Not shown on the list on 7E5713