This document is a Load Shed Priority list that appears to be related to a federal contract opportunity for troubleshooting and repair of Automatic Transfer Switches (ATS) for the Southeast Louisiana Veterans Healthcare System.

The key details are:

  • The Load Shed Priority list assigns priority levels from 1-7 to various electrical equipment and systems, including elevators, fire pumps, and UPS systems.
  • The related federal contract opportunity is Solicitation Number 36C25624Q1131, issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 as a SDVOSB set-aside. The contract is for a base period of 09/15/2024 - 11/14/2024 to provide troubleshooting and repair services for ATS located at the Southeast Louisiana Veterans Healthcare System in New Orleans, LA. Quotes are due by 10:00 AM CST on 08/29/2024.

View the file

Other files

File Type Posted
Load Shed pg 2.pdf PDF
7ES611 bldg control single line Diagram.pdf PDF
36C25624Q1131 0003.docx DOCX document
RFI for ATS Troubleshooting.docx DOCX document
36C25624Q1131 0002.docx DOCX document
ATS Troubleshoot walk through sign in 1.pdf PDF
36C25624Q1131 A0001.docx DOCX document
36C25624Q1131 F.docx DOCX document
36C25624Q1131.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

From Sheet 7E5611

ATS Priority from 7E5713 LS BT DT TP EL ES ASCO Type Correct function confirmed Notes

EL8-1 Priority 1 X X . This ATS not shown on 7ES611, on Research dwg.

EQ8-1 Priority 2 X X X x X Elevators, but not assigning the lower priority

ELS8-1 Priority 1 X X

ELS9-1 Priority 1 X X "RI" on dwg. Thought to be BT. Not correct.

EI19-1 Priority 1 X X

EQ9-1 Priority 2 X X X X

Fire Pump Priority 1 X X Need to confirm remote test feature

Fire Pump Priority 1 X No remote test

Fire Pump Priority 1 X No remote test

1J5502-1A Priority 3

USS02-16 . Priority 3

USS02-2A Priority 3

USS02-26 Priority 3

USS01-A Priority 3

USS01-B Priority 3

USS07-A Priority 4

USS07-13 Priority 4

USS03-A Priority 5

USS03-13 Priority 5

USSO4 Priority 5

USSO6 Priority 5

USS08-A Priority 5

USS08-8 Priority 5

USSO9 Priority 5

UPS07-B CH 1 , Priority 6

UPS07-8 CH 2 Priority 6

UPS07-6 CH 3 Priority 6

UPS07-A CH 4 Priority 7

UPS07-A CH 5 , Priority 7

UPS07-A CH 6 Priority 7 Not shown on the list on 7E5713