nLight IECC 2018 Applications Guide.pdf
PDF 7 MB Posted
- Solicitation number
- 36C25621R0145
About this file
This document contains an applications guide for nLight digital lighting controls and a solicitation for a construction project at a Veterans hospital.
The applications guide provides layout examples and product information for nLight wireless and wired lighting control solutions that comply with IECC 2018 lighting control requirements for various common building space types. It includes bill of materials, wiring diagrams and control options for enclosed offices up to 250 square feet with windows. The solicitation is a 100% small business set-aside to develop private and semi-private bed spaces at the John L. McClellan Veterans Memorial Hospital in Little Rock, Arkansas. The construction cost range is $5-10 million and responses are due around September 1, 2021 with an anticipated award date within 30 days thereafter. The recommended contract performance period is 485 calendar days from notice to proceed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI 79 DRAWING 4.pdf | ||
| PRE-BID RFIS COMPLETE.docx | DOCX document | |
| RFI 79 DRAWING 3.pdf | ||
| RFI 79 DRAWING 1.pdf | ||
| RFI 79 DRAWING 2.pdf | ||
| AMENDMENT 36C25621R0145 0002.docx | DOCX document | |
| SITE VISIT SIGN IN SHEET.pdf | ||
| AMENDMENT 36C25621R0145 0001.docx | DOCX document | |
| 081121_PRE-BID RFIs_PARTIAL RESPONSES.docx | DOCX document | |
| P07 WAGE DETERMINATION AR20210032 04-02-2021.pdf | ||
| 59818103 Specifications.pdf | ||
| EXHIBIT C CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY v2.docx | DOCX document | |
| SOW - revised.docx | DOCX document | |
| EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.docx | DOCX document | |
| 598918103 Drawings 2 of 2.pdf | ||
| 36C25621R0145.docx | DOCX document | |
| 59818103 BOD.pdf | ||
| 598918103 Drawings 1 of 2.pdf | ||
| EXHIBIT B Past and Present Performance Questionnaire.docx | DOCX document |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
nLight® Applications Guide
IECC 2018
www.nlightcontrols.com www.nlightcontrols.com • 800-535-2465
Intro nLight Lighting Controls Platform
It’s not just smarter. It’s easier.
nLight is a digital lighting controls solution that offers wired and wireless lighting controls that easily connect luminaires, sensors, and other control devices to create a digital network.
The nLight platform of products enables ease in specification, installation, and ownership, making it the go-to digital lighting controls platform for specifiers, contractors, and building owners.
IECC 2018: nLight Applications Guide
Table of Contents
Code Requirements for Common Building Spaces
How to Use This Guide
Enclosed Office Solutions
Open Plan Office Solutions
Conference Room Solutions
Classroom Solutions
Lobby Solutions
Corridor Solutions
Restroom Solutions
Stairwell Solutions
Warehouse Storage Solutions
Gymnasium Solutions
Parking Garage
Site Lighting nLight Hybrid Networked Lighting Control
Requirements Overview
Emergency Lighting nLight Enabled Luminaires
TABLE OF CONTENTS
Title 24 Lighting Control
About
About IECC 2018 The International Energy Conservation Code (IECC)
2018 is a residential and commercial building energy code. The IECC has been adopted by many states and municipalities. The intention of this code is to reduce energy consumption by outlining design and construction requirements which include specific constraints for lighting controls. The use of lighting controls to synchronize light levels with daylight, occupancy, and scheduled/manual inputs are required in order to be compliant.
About This Guide Acuity Brands® offers the nLight® IECC Applications
Guide as a reference of typical nLight layouts that help make code compliance quicker and easier.
The Acuity Brands Design Services Team is also available to support engineers and contractors with detailed design, submittal, and installation.
For additional information, please contact your
Acuity Brands Sales Representative.
About nLight nLight® is a sensor-based digital lighting controls solution that offers wired and wireless lighting controls that easily connect luminaires, sensors, and other control devices to create one digital lighting controls platform to aid in code compliance, reduce energy, and enable advanced networked capabilities. Ideal for practically any application, small to large, indoor to outdoor, nLight offers lighting controls that scale from one room to an entire floor, from one floor to an entire building, from one building to an entire campus.
ABOUT
Code Requirements for Common Building Spaces
The chart below is an overview of the Code Requirements for Common Building Spaces. Please use this information as a guide.
For specific code requirements please refer to the IECC code.
Notes:
* This summary is for general information purposes only and is provided without any warranty as to accuracy, completeness, or otherwise. The user should read the applicable code sections for more complete and detailed descriptions of code requirements and exceptions and should consult with a professional engineer or other competent advisor before making any decision or taking any action based on this summary.
** While energy code is required, safety may preclude the use of a manual controls in these spaces.
Control Requirement*
Code Provision
Code Summary*
Space Type
Enclosed Office
Open Plan
Office
Conference, Meeting, Multipurpose Room
Classroom, Lecture Hall, Training Room
Lobby Corridor Public Restroom
Private Restroom
Non-Exit Stairwell Gymasium Warehouse Parking
Garage Site
Lighting
Manual-On or AutoOn
≤ 50% C405.2.1.1.1
Automatically controlled spaces must be controlled to automatically turn the lighting on to not more than 50% power.
Full Automatic-On C405.2.1.1.2
Automatically controlled spaces are allowed to turn on to full.
Auto-Off ≤ 50% C405.2.1.2
Occupancy sensors shall automatically reduce lighting in ware-house storage aisle-ways and open areas by ≤ 50%
Full Auto-Off via Occupancy
Sensor
C405.2.1.1.1
C405.2.1.3
Fixtures must automatically turn off within 20 minutes of all occupants leaving the space.
Time-Switch Controls
(via System Controller)
C405.2.2.1
Each area of the building not provided with occupant sensor controls shall be provided with time switch controls. These areas must also be provided with a manual override switch.
Light Reduction Controls
C405.2.2.2
Spaces shall have a manual control that allows the occupant to reduce the connected lighting load uniformly by not less than 50%.
Manual Control
(Local Switch) C405.2.5
Areas shall incorporate a manual control to allow occupants to turn fixtures off.
Daylight- Responsive
Controls
C405.2.3.1
C405.2.3.2
Daylight-responsive controls shall be provided within each space with sidelight and toplight daylight zones totaling > 150W.
Exterior Lighting Controls
C405.2.6
C405.2.6.1 Daylight shutoff C405.2.6.2 Decorative lighting shutoff C405.2.6.3 Lighting setback C405.2.6.4 Exterior time-switch control function
On -O f Co nt ro l Da yli gh t C on tro l
Ex te rio r C on tro l
(or)
(or) (or)
(or) (or)
(or) (or)
How to Use This Guide www.acuitybrands.com/nLight • 800-535-2465
ENCLOSED OFFICE: < 250 sq. ft., Windows, nLight Enabled Fixtures
Bill of Materials Symbol Qty Product # Description
2 See Note nLight AIR Enabled Troffer with Sensor Option
1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod®
Line Voltage Wires
Line Power Feed
WirelessWired
Bill of Materials Symbol Qty Product # Description
2 See Note nLight Wired Enabled Troffer
1 nWSXA PDT LV DX Wall Switch Occupancy Sensor with On/Off, Raise/Lower nWSXA PDT LV DX
CAT-5e Cable
Line Voltage Wires
Line Power Feed
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE® controller
¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
ADDITIONAL OPTIONS:
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures can be controlled together or independently
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures turn off automatically when room becomes vacant
Daylight Control:
¡ Not required for offices without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise/lower control of fixtures
OPERATIONAL DETAILS:
rPODBA DX
For each space type there will be a wired solution on the left and wireless solution on the right.
Wire type legend
Required list of devices in order to implement room layout design above
Additional options that add control capacity beyond code requirements
Operational details describe the functionality provided by the equipment specified in the solution
Room description
Control Requirement*
Code Provision
Code Summary*
Space Type
Enclosed Office
Open Plan
Office
Conference, Meeting, Multipurpose Room
Classroom, Lecture Hall, Training Room
Lobby Corridor Public Restroom
Private Restroom
Non-Exit Stairwell Gymasium Warehouse Parking
Garage Site
Lighting
Manual-On or AutoOn
≤ 50% C405.2.1.1.1
Automatically controlled spaces must be controlled to automatically turn the lighting on to not more than 50% power.
Full Automatic-On C405.2.1.1.2
Automatically controlled spaces are allowed to turn on to full.
Auto-Off ≤ 50% C405.2.1.2
Occupancy sensors shall automatically reduce lighting in ware-house storage aisle-ways and open areas by ≤ 50%
Full Auto-Off via Occupancy
Sensor
C405.2.1.1.1
C405.2.1.3
Fixtures must automatically turn off within 20 minutes of all occupants leaving the space.
Time-Switch Controls
(via System Controller)
C405.2.2.1
Each area of the building not provided with occupant sensor controls shall be provided with time switch controls. These areas must also be provided with a manual override switch.
Light Reduction Controls
C405.2.2.2
Spaces shall have a manual control that allows the occupant to reduce the connected lighting load uniformly by not less than 50%.
Manual Control
(Local Switch) C405.2.5
Areas shall incorporate a manual control to allow occupants to turn fixtures off.
Daylight- Responsive
Controls
C405.2.3.1
C405.2.3.2
Daylight-responsive controls shall be provided within each space with sidelight and toplight daylight zones totaling > 150W.
Exterior Lighting Controls
C405.2.6
C405.2.6.1 Daylight shutoff C405.2.6.2 Decorative lighting shutoff C405.2.6.3 Lighting setback C405.2.6.4 Exterior time-switch control function
(or)
Room layout diagram with controls, fixtures, and wiring
ENCLOSED OFFICE: < 250 sq. ft., Windows, nLight Enabled Fixtures
Bill of Materials Symbol Qty Product # Description
2 See Note nLight AIR Enabled Troffer with Sensor Option
1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod®
Line Voltage Wires
Line Power Feed
WirelessWired
Bill of Materials Symbol Qty Product # Description
2 See Note nLight Wired Enabled Troffer
1 nWSXA PDT LV DX Wall Switch Occupancy Sensor with On/Off, Raise/Lower nWSXA PDT LV DX
CAT-5e Cable
Line Voltage Wires
Line Power Feed
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE® controller
¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
ADDITIONAL OPTIONS:
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures can be controlled together or independently
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures turn off automatically when room becomes vacant
Daylight Control:
¡ Not required for offices without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise/lower control of fixtures
OPERATIONAL DETAILS:
rPODBA DX
ENCLOSED OFFICE: < 250 sq. ft., Windows, 0-10V Dimming Fixtures
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE® controller
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
ADDITIONAL OPTIONS:
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures turn off automatically when room becomes vacant
Daylight Control:
¡ Not required for offices without windows or that have loads <150W in sidelit zone
Manual Control:
¡ On/off & raise/lower control of fixtures
OPERATIONAL DETAILS:
Bill of Materials Symbol Qty Product # Description
1 nPP16 D EFP Relay Pack with 0-10V Dimming Output
1 nWSXA PDT LV DX Wall Switch Occupancy Sensor with On/Off, Raise/Lower
CAT-5e Cable
Line Voltage Wires
0-10V Wires
Line Power Feed
Line Voltage Wires
0-10V Wires
Line Power Feed nWSXA PDT LV DX nPP16 D
Wired Wireless
Bill of Materials Symbol Qty Product # Description rPP20 D 24V EFP G2
Relay Pack with 0-10V Dimming Output
1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod
1 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor rPP20 D 24V rCMSB PDT 7
OPEN PLAN OFFICE: > 300 sq. ft., nLight Enabled Fixtures
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ Occupant sensor controls in open plan office spaces less than 300 sq. ft. in area shall comply with Section C405.2.1.1
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures turn off automatically when room becomes vacant
¡ General lighting must be controlled in zones not greater than 600 sq. ft.
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max.
number zones = number of fixtures)
¡ Not required for offices without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise/lower control of fixtures
ADDITIONAL OPTIONS: OPERATIONAL DETAILS:
Bill of Materials Symbol Qty Product # Description
14 See Note nLight Wired Enabled Troffer
2 See Note nLight Wired Enabled Troffer with Battery Option (typical)
2 nPODMA DX On/Off, Raise/Lower WallPod
4 nCM PDT 9 RJB Occupancy Sensor
1 nCM ADCX RJB Daylight Sensor
Bill of Materials Symbol Qty Product # Description
14 See Note nLight AIR Enabled Troffer with Sensor Option
2 See Note nLight AIR Enabled Troffer with Sensor and EM Option
2 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod
CAT-5e Cable
Line Voltage Wires
Line Power Feed
EM Power Feed
Line Voltage Wires
Line Power Feed
Wired Wireless
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
D Z
EM
EM
rPODBA DX rPODBA DX
1 Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
D Z
EM
EM
nPODMA DX nPODMA DX nCM ADCX nCM PDT 9 nCM PDT 9 nCM PDT 9 nCM PDT 9
1 Some nLight enabled EM fixtures require a normal sense line connection.
Wiring shown assumes battery backup emergency option. See fixture spec sheets for details.
OPEN PLAN OFFICE: > 300 sq. ft., 0-10V Dimming Fixtures
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Occupant sensor controls in open plan office spaces less than 300 sq. ft. in area shall comply with Section C405.2.1.1
Light Fixtures:
¡ All fixtures are dimmable
¡ Each row controlled independently
¡ Maximum level can be task tuned to any per-centage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures turn off automatically when room becomes vacant
¡ General lighting must be controlled in zones not greater than 600 sq. ft.
Daylight Control:
¡ Smooth continuous dimming
¡ Daylight zones defined by rows
¡ Not required for offices without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise/lower control of fixtures
ADDITIONAL OPTIONS: OPERATIONAL DETAILS:
Bill of Materials Symbol Qty Product # Description
4 nPP16 D EFP Relay Pack with 0-10V Dimming Output
1 nPP16 D ER EFP Emergency Relay Pack with 0-10V Dimming Output
2 nPODMA DX On/Off, Raise/Lower WallPod
4 nCM PDT 9 RJB Occupancy Sensor
1 nCM ADCX RJB Daylight Sensor
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
EM Power Feed
Line Voltage Wires
Line Power Feed
0-10V Wires
EM Power Feed
Wired Wireless
Bill of Materials Symbol Qty Product # Description rPP20 D 24V
EFP G2
Relay Pack with 0-10V Dimming Output rPP20 D 24V EM
EFP G2
Emergency Relay Pack with 0-10V Dimming Output
2 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod
5 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor nPP16 D nPP16 D nPP16 D nCM ADCX nCM PDT 9 nCM PDT 9 nCM PDT 9 nCM PDT 9 nPP16 D nPP16 D ER
D Z nPODMA DX
EM
EM
nPODMA DX rPP20 D 24V rPP20 D 24V rPP20 D 24V rCMSB PDT 7 rCMSB PDT 7 rCMSB PDT 7 rCMSB PDT 7 rPP20 D 24V rPP20 D 24V EM
D Z rPODBA DX
EM
EM
CONFERENCE ROOM with nLight Enabled Fixtures
OPERATIONAL DETAILS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
¡ A/V zone can be programmed to control two fixtures in front of the whiteboard
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures turn off automatically when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or that have loads <150w in sidelit zones
Manual Control:
¡ On/off & raise lower control of two zones of fixtures
ADDITIONAL OPTIONS:
nCM PDT 9 nCM ADCX nPODMA 2P DX
CAT-5e Cable Line Voltage Wires Line Power Feed Line Voltage Wires Line Power Feed
Bill of Materials Symbol Qty Product # Description
1 See Note nLight Wired Enabled Linear Fixture
6 See Note nLight Wired Enabled Downlight Fixture
1 nPODMA 2P DX 2-Pole, On/Off, Raise/Lower WallPod
1 nCM PDT 9 RJB Occupancy Sensor
1 nCM ADCX RJB Daylight Sensor
Bill of Materials Symbol Qty Product # Description
1 See Note nLight AIR Enabled Linear Fixture with Sensor Option
6 See Note nLight AIR Enabled Downlight Fixture
1 rPODBA 2P DX G2 Battery Powered, 2-Pole, On/ Off, Raise/Lower WallPod
Wired Wireless
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
rPODBA 2P DX
CONFERENCE ROOM with 0-10V Dimming Fixtures
OPERATIONAL DETAILS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures turn off automatically when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Daylight zones defined by rows
¡ Not required for areas without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise lower control of two zones of fixtures
ADDITIONAL OPTIONS:
nCM ADCX nPODMA 2P DX nCM PDT 9 nPP16 D nPP16 D
Bill of Materials Symbol Qty Product # Description
2 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output
1 rPODBA 2P DX G2 Battery Powered, 2-Pole, On/ Off, Raise/Lower WallPod
1 rCMSB PDT 7 G2 Battery Powered Occupancy and Daylight Sensor
Bill of Materials Symbol Qty Product # Description
2 nPP16 D EFP Relay Pack with 0-10V Dimming Output
1 nPODMA 2P DX 2-Pole, On/Off, Raise/ Lower WallPod
1 nCM PDT 9 RJB Occupancy Sensor
1 nCM ADCX RJB Daylight Sensor
Wired Wireless
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires Line Voltage Wires Line Power Feed 0-10V Wires rCMSB PDT 7 rPP20 D 24V rPODBA 2P DX rPP20 D 24V
CLASSROOM with nLight Enabled Fixtures
OPERATIONAL DETAILS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)
¡ Fixtures automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise/lower control of entire room
¡ Teacher station with 4 preset scenes
ADDITIONAL OPTIONS:
nWV PDT 16 nCM ADCX nPODMA 4S DX
DZ
Bill of Materials Symbol Qty Product # Description
9 See Note nLight Wired Enabled Troffer
1 nPODMA DX On/Off, Raise/Lower WallPod
1 nWV PDT 16 Dual Technology Wide View Occupancy Sensor
1 nPODMA 4S DX Teacher Station — 4 Scene Control with Master On/Off & Raise/Lower
1 nCM ADCX RJB Daylight Sensor
Bill of Materials Symbol Qty Product # Description
9 See Note nLight AIR Enabled Troffer with Sensor Option
1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod
1 rPODBA 4S DX G2 Teacher Station — Battery Powered 4 Scene Control with Master On/Off & Raise/Lower
Wired Wireless
CAT-5e Cable Line Voltage Wires Line Power Feed Line Voltage Wires Line Power Feed
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
DZ
rPODBA 4S DX rPODBA DX
CLASSROOM with 0-10V Dimming Fixtures
OPERATIONAL DETAILS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Light Fixtures:
¡ All fixtures are dimmable
¡ Each row can be controlled independently
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Daylight zones defined by rows
¡ Not required for areas without windows or that have loads <150W in sidelit zones
Manual Control:
¡ Master on/off & raise/ lower control of entire room
¡ Teacher station with 4 preset scenes
ADDITIONAL OPTIONS:
nPP16 D nPP16 D nPP16 D
DZ
nWV PDT 16 nCM ADCX nPODMA 4S DX
Bill of Materials Symbol Qty Product # Description
3 nPP16 D EFP Relay Module with 0-10V Dimming Output
1 nPODMA DX On/Off, Raise/Lower WallPod
1 nWV PDT 16 Dual Technology Wide View Occupancy Sensor
1 nPODMA 4S DX Teacher Station — 4 Scene Control with Master On/Off & Raise/Lower
1 nCM ADCX RJB Daylight Sensor
Bill of Materials Symbol Qty Product # Description
3 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output
1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod
2 rCMSB PDT 7 G2 Battery Powered Occupancy and Daylight Sensor
1 rPODBA 4S DX G2 Teacher Station — Battery Powered 4 Scene Control with Master On/Off & Raise/Lower
Wired Wireless
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires Line Voltage Wires Line Power Feed 0-10V Wires rPP20 D 24V rPP20 D 24V rPP20 D 24V
DZ
rPODBA DX rCMSB PDT 7 rPODBA 4S DX
LOBBY with nLight Enabled Fixtures
DZ
nPODMA DX
Bill of Materials Symbol Qty Product # Description
4 See Notes nLight Wired Enabled Downlight
DZ
nPODM DX
1 See Notes nLight Wired Enabled Troffer with Sensor Option
1 nPODMA DX On/Off, Raise/Lower WallPod
Bill of Materials Symbol Qty Product # Description
4 See Notes nLight AIR Enabled Downlight
DZ
nPODM DX
1 See Notes nLight AIR Enabled Troffer with Sensor Option
1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod
Wired Wireless
CAT-5e Cable Line Voltage Wires Line Power Feed Line Voltage Wires Line Power Feed
OPERATIONAL DETAILS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise/lower control of fixtures
ADDITIONAL OPTIONS:
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
DZ
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires Line Voltage Wires Line Power Feed 0-10V Wires
LOBBY with 0-10V Dimming Fixtures nPP16 D nPP16 D
DZ
nPODMA DX nCM PDT 9 ADCX
Bill of Materials Symbol Qty Product # Description
2 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output
1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod
1 rCMSB PDT 7 G2 Battery Powered Occupancy and Daylight Sensor
Bill of Materials Symbol Qty Product # Description
2 nPP16 D EFP Relay Pack with 0-10V Dimming Output
1 nPODMA DX On/Off, Raise/Lower WallPod
1 nCM PDT 9 ADCX Occupancy and Daylight Sensor
Wired Wireless
OPERATIONAL DETAILS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Daylight zones defined by relay module wiring
¡ Not required for areas without windows or that have loads <150W in sidelit zones
Manual Control:
¡ On/off & raise/lower control of fixtures
ADDITIONAL OPTIONS:
rPP20 D 24V rPP20 D 24V
DZ
Bill of Materials Symbol Qty Product # Description
7 See Note nLight Wired Enabled Troffer with Sensor Option
2 See Note nLight Wired Enabled Troffer with Battery Option
3 nPODMA On/Off WallPod
4 nCM 10 RJB Occupancy Sensor
Bill of Materials Symbol Qty Product # Description
7 See Note nLight AIR Enabled Troffer with Sensor Option
2 See Note nLight AIR Enabled Troffer with Sensor and EM Option
3 rPODBA G2 Battery Powered, On/Off, Raise/Lower WallPod
CAT-5e Cable
Line Voltage Wires
Line Power Feed
EM Power Feed
Line Voltage Wires
Line Power Feed
EM Power Feed
Wired Wireless nCM 10 nCM 10 nCM 10 nCM 10
EM
EM
nPODMA nPODMA nPODMA
1 Some nLight enabled EM fixtures require a normal sense line connection.
Wiring shown assumes battery backup emergency option. See fixture spec sheets for details.
CORRIDOR with nLight Enabled Fixtures
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Manual Control:
¡ On/off control of fixtures
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
Some nLight enabled EM fixtures require a normal sense line connection. Wiring shown assumes battery backup emergency option. See fixture spec sheets for details.
EM
EM
rPODBA rPODBA rPODBA
1 Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
Line Voltage Wires
Line Power Feed
0-10V Wires
EM Power Feed
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
EM Power Feed
Wired Wireless nCM 10 nCM 10 nCM 10 nPP16 D nCM 10 nPP16 D ER
EM
EM
nPODMA nPODMA nPODMA
CORRIDOR with 0-10V Dimming Fixtures
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Manual Control:
¡ On/off control of fixtures
Bill of Materials Symbol Qty Product # Description
1 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output rPP20 D 24V EM
EFP G2
Emergency Relay Pack with 0-10V Dimming Output
4 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor
3 rPODBA G2 Battery Powered, On/Off, Raise/Lower WallPod
Bill of Materials Symbol Qty Product # Description
1 nPP16 D EFP Relay Pack with 0-10V Dimming Output
1 nPP16 D ER EFP Emergency Relay Pack with 0-10V Dimming Output
4 nCM 10 RJB Occupancy Sensor
3 nPODMA On/Off WallPod rCMSB PDT 7 rCMSB PDT 7 rCMSB PDT 7 rPP20 D 24V rCMSB PDT 7 rPP20 D 24V EM
EM
EM
rPODBA rPODBA rPODBA
PUBLIC RESTROOM with nLight Enabled Fixtures
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently (per room)
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied (or optionally can be configured to come on automatically to 50%)
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Manual Control:
¡ On/off & raise/lower control of fixtures
¡ If switch poses safety concerns, optionally can be programmed for “on only”
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
Bill of Materials Symbol Qty Product # Description
2 See Note nLight Wired Enabled Troffer
2 See Note nLight Wired Enabled Troffer with Battery Option
2 nPODMA DX On/Off, Raise/Lower WallPod
Bill of Materials Symbol Qty Product # Description
2 See Note nLight AIR Enabled Troffer with Sensor Option
2 See Note nLight AIR Enabled Troffer with Sensor and EM Option
2 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod
Wired Wireless
Line Voltage Wires Line Power FeedCAT-5e Cable
Line Voltage Wires Line Power Feed
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
EM
rPODBA DX rPODBA DX
EM
1 1
1 Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
EM
rPODBA DX rPODBA DX
EM
1 1
1 Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
EM
1 1 nPODMA DX nPODMA DX
EM
1 Some nLight enabled EM fixtures require a normal sense line connection.
nCM PDT 9 nCM PDT 9
PUBLIC RESTROOM with 0-10V Dimming Fixtures
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently (per room)
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied (or optionally can be configured to come on automatically to 50%)
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Manual Control:
¡ On/off & raise/lower control of fixtures
¡ If switch poses safety concerns, optionally can be programmed for “on only”
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Bill of Materials Symbol Qty Product # Description
2 nPP16 D EFP Relay Pack with 0-10V Dimming Output
2 nPP16 D ER EFP Emergency Module with 0-10V Dimming Output
2 nPODMA DX On/Off & Raise/Lower WallPod
2 nCM PDT 9 RJB Occupancy Sensor
Bill of Materials Symbol Qty Product # Description
2 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output rPP20 D 24V EM
EFP G2
Emergency Relay Pack with 0-10V Dimming Output
2 rPODBA DX G2 Battery Powered, On/Off & Raise/Lower WallPod
2 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor
Wired Wireless
CAT-5e Cable 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed nCM PDT 9 nCM PDT 9 nPP16 D nPP16 D
EM EM
nPP16 D ERnPP16 D ER nPODMA DX nPODMA DX
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
rCMSB PDT 7 rPP20 D 24VrPP20 D 24V
EM EM
rPP20 D 24V EM rPP20 D 24V EM rPODBA DX rPODBA DX
PRIVATE / SINGLE RESTROOM with nLight Enabled Fixture
OPERATIONAL DETAILS:
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via progrmamming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied (or optionally can be configured to come on automatically to 50%)
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Manual Control:
¡ On/off & raise/lower control of fixtures
¡ If switch poses safety concerns, optionally can be programmed for “on only”
ADDITIONAL OPTIONS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option nWSXA LV DX
Bill of Materials Symbol Qty Product # Description
1 See Note nLight Wired Enabled Troffer
1 nWSXA PDT LV DX Occupancy Wall Switch, On/Off, Raise/Lower
Bill of Materials Symbol Qty Product # Description
1 See Notes nLight AIR Enabled Troffer with Sensor Option
1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod
Wired Wireless
Line Voltage Wires Line Power FeedCAT-5e Cable Line Voltage Wires Line Power Feed
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
NON-EXIT STAIRWELL with nLight Enabled Fixtures/0-10V Dimming Fixtures
OPERATIONAL DETAILS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Manual Control:
¡ Safety may preclude the use of a manual control in these areas
ADDITIONAL OPTIONS:
Line Power Feed
EM Power Feed
Wireless with nLight Enabled Fixtures
Bill of Materials Symbol Qty Product # Description
1 See Note nLight AIR Enabled Fixture with Sensor Option
1 See Note nLight AIR Enabled Fixture with Sensor and EM Option
Line Voltage Wires
Line Power Feed
0-10V Wires
EM Power Feed
Wireless with 0-10V Dimming Fixtures
Bill of Materials Symbol Qty Product # Description rPP20 D 24V
EFP G2
Relay Pack with 0-10V Dimming Output rPP20 D 24V EM
EFP G2
Emergency Relay Pack with 0-10V Dimming Output
2 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
rPP20 D 24V rCMSB 7 rCMSB 7 rPP20 D 24V EM
EM
EM
1 Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
WAREHOUSE STORAGE Wireless Enabled Fixtures/0-10V Dimming Fixtures
Bill of Materials Symbol Qty Product # Description
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
rPODB 2P rPODB 2P rPODB 2P
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
20 See Note nLight AIR Enabled High Bay Fixture with Sensor Option
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
rPODB 2P rPODB 2P rPODB 2P
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
EMG
15 See Note nLight AIR Enabled High Bay Fixture with Sensor and EM Option
3 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod
Wireless with nLight Enabled Fixtures
Line Voltage Wires Line Power Feed EM Power Feed
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Daylight Control:
¡ Daylight responsive controls lights to full off when adequate daylight present
¡ Not required for spaces without skylights or that have loads <150W in toplit zones
Wireless with 0-10V Dimming Fixtures
Bill of Materials Symbol Qty Product # Description
6 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output rPP20 D 24V EM
EFP G2
Emergency Relay Pack with 0-10V Dimming Output
3 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod
12 rCMS 6 G2 Occupancy Sensor
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
Low Voltage Wires 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
rCMS 6 rCMS 6
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
rPP20 D 24V EM rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V rPODBA 2P rPODB 2P rPODBA 2P
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
rPODBA 2P rPODBA 2P rPODBA 2P
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
1 Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
GYMNASIUM with nLight Enabled Fixtures/0-10V Dimming Fixtures
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)
¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller
¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
Light Fixtures:
¡ All fixtures are dimmable
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Daylight Control:
¡ Daylight responsive controls lights to full off when adequate daylight present
¡ Not required for spaces without skylights or that have loads <150W in toplit zones
Bill of Materials Symbol Qty Product # Description rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6
M E
M E
M
EM
E
M E
M E rPODB 2P rPODB 2P n n n n n nnn n n n n nn nn n nn n rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn
18 See Notes nLight AIR Enabled Fixture with Sensor Option rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6
M E
M E
M
EM
E
M E
M E rPODB 2P rPODB 2P n n n n n nnn n n n n nn nn n nn n rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn6 See Notes nLight AIR Enabled Fixture with Sensor and EM Option
2 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod
Bill of Materials Symbol Qty Product # Description rPP20 D 24V
EFP G2
Relay Pack with 0-10V Dimming Output rPP20 D 24V EM
EFP G2
Emergency Relay Pack with 0-10V Dimming Output
2 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod
6 rCMS 6 G2 High Bay Occupancy Sensor
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
Line Voltage Wires Line Power Feed EM Power Feed
Wireless with nLight Enabled Fixtures Wireless with 0-10V Dimming Fixtures
Low Voltage Wires 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed
M E
M E
M
EM
E
M E
M E rPODBA 2P rPODBA 2P
1 1
1 1
Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
M E
M E
M
EM
E
M E
M E rPODBA 2P rPODBA 2P rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
¡ Devices can be connected to nLight backbone to enabled network control or time schedules, including astronomical time schedules for shutoff (C405.2.6.2), lighting setback (C405.2.6.3), & exterior time-switch control (C405.2.6.4). GFXK option can be added to nLight ECLYPSE to provide manual override (C405.2.5).
¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet
¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)
Light Fixtures:
¡ All fixtures are dimmable
¡ All fixtures can be controlled together or independently
¡ Maximum level can be task tuned to any percentage via programming
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
Daylight Control:
¡ Daylight responsive controls lights to full off when adequate daylight present
Note: Contact your local lighting agent for more information on nLight enabled fixtures.
nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.
PARKING GARAGE with nLight AIR Enabled Fixtures
Wireless Parking Garage
Bill of Materials Symbol Qty Product # Description
ELEVATOR LOBBY
STAIRS
IN
OUT
DWN
UP
ELEC/MECH/DATA
n n n n n n n n n n
NECYD
NLTAIR
n rPODB n
13 See Note nLight AIR Enabled Canopy Fixture with Sensor Option
ELEVATOR LOBBY
STAIRS
IN
OUT
DWN
UP
ELEC/MECH/DATA
n n n n n n n n n n
NECYD
NLTAIR
n rPODB n
2 See Note nLight AIR Enabled Canopy Fixture with Sensor and EM Option
ECLYPSE™ECLYPSE™ ECLYPSE™ 1 nECY nLight ECLYPSE Network System Controller
Bridge nLight ECLYPSE
LAN
nPP20 nCM nWSX
1 nECYD NLTAIR G2 nLight AIR Adapter
ELEVATOR LOBBY
STAIRS
IN
OUT
DWN
UP
ELEC/MECH/DATA
n
NECYD NLTAIR
NECY MVOLT ENC GFXK
PS 150
EM
EM
Fixture(s) assumed to include power interruption detection emergency option.
For battery backup option, no dedicated EM circuit necessary.
Low Voltage Wires
USB Cable
Line Voltage Wires
Line Power Feed
EM Power Feed
OPERATIONAL DETAILS: ADDITIONAL OPTIONS:
¡ Devices can be connected to nLight backbone to enabled network control or time schedules, including astronomical time schedules for shutoff (C405.2.6.2), lighting setback (C405.2.6.3), & exterior time-switch control (C405.2.6.4).