nLight IECC 2018 Applications Guide.pdf

PDF 7 MB Posted

Attached to
Z2DA--PROJECT NO: 598-18-103 DEVELOP PRIVATE/ SEMI-PRIVATEBED SPACES FOR 4B AND 4C PODS
Solicitation number
36C25621R0145
Issued by

About this file

This document contains an applications guide for nLight digital lighting controls and a solicitation for a construction project at a Veterans hospital.

The applications guide provides layout examples and product information for nLight wireless and wired lighting control solutions that comply with IECC 2018 lighting control requirements for various common building space types. It includes bill of materials, wiring diagrams and control options for enclosed offices up to 250 square feet with windows. The solicitation is a 100% small business set-aside to develop private and semi-private bed spaces at the John L. McClellan Veterans Memorial Hospital in Little Rock, Arkansas. The construction cost range is $5-10 million and responses are due around September 1, 2021 with an anticipated award date within 30 days thereafter. The recommended contract performance period is 485 calendar days from notice to proceed.

View the file

Other files

File Type Posted
RFI 79 DRAWING 4.pdf PDF
PRE-BID RFIS COMPLETE.docx DOCX document
RFI 79 DRAWING 3.pdf PDF
RFI 79 DRAWING 1.pdf PDF
RFI 79 DRAWING 2.pdf PDF
AMENDMENT 36C25621R0145 0002.docx DOCX document
SITE VISIT SIGN IN SHEET.pdf PDF
AMENDMENT 36C25621R0145 0001.docx DOCX document
081121_PRE-BID RFIs_PARTIAL RESPONSES.docx DOCX document
P07 WAGE DETERMINATION AR20210032 04-02-2021.pdf PDF
59818103 Specifications.pdf PDF
EXHIBIT C CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY v2.docx DOCX document
SOW - revised.docx DOCX document
EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.docx DOCX document
598918103 Drawings 2 of 2.pdf PDF
36C25621R0145.docx DOCX document
59818103 BOD.pdf PDF
598918103 Drawings 1 of 2.pdf PDF
EXHIBIT B Past and Present Performance Questionnaire.docx DOCX document
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

nLight® Applications Guide

IECC 2018

www.nlightcontrols.com www.nlightcontrols.com • 800-535-2465

Intro nLight Lighting Controls Platform

It’s not just smarter. It’s easier.

nLight is a digital lighting controls solution that offers wired and wireless lighting controls that easily connect luminaires, sensors, and other control devices to create a digital network.

The nLight platform of products enables ease in specification, installation, and ownership, making it the go-to digital lighting controls platform for specifiers, contractors, and building owners.

IECC 2018: nLight Applications Guide

Table of Contents

Code Requirements for Common Building Spaces

How to Use This Guide

Enclosed Office Solutions

Open Plan Office Solutions

Conference Room Solutions

Classroom Solutions

Lobby Solutions

Corridor Solutions

Restroom Solutions

Stairwell Solutions

Warehouse Storage Solutions

Gymnasium Solutions

Parking Garage

Site Lighting nLight Hybrid Networked Lighting Control

Requirements Overview

Emergency Lighting nLight Enabled Luminaires

TABLE OF CONTENTS

Title 24 Lighting Control

About

About IECC 2018 The International Energy Conservation Code (IECC)

2018 is a residential and commercial building energy code. The IECC has been adopted by many states and municipalities. The intention of this code is to reduce energy consumption by outlining design and construction requirements which include specific constraints for lighting controls. The use of lighting controls to synchronize light levels with daylight, occupancy, and scheduled/manual inputs are required in order to be compliant.

About This Guide Acuity Brands® offers the nLight® IECC Applications

Guide as a reference of typical nLight layouts that help make code compliance quicker and easier.

The Acuity Brands Design Services Team is also available to support engineers and contractors with detailed design, submittal, and installation.

For additional information, please contact your

Acuity Brands Sales Representative.

About nLight nLight® is a sensor-based digital lighting controls solution that offers wired and wireless lighting controls that easily connect luminaires, sensors, and other control devices to create one digital lighting controls platform to aid in code compliance, reduce energy, and enable advanced networked capabilities. Ideal for practically any application, small to large, indoor to outdoor, nLight offers lighting controls that scale from one room to an entire floor, from one floor to an entire building, from one building to an entire campus.

ABOUT

Code Requirements for Common Building Spaces

The chart below is an overview of the Code Requirements for Common Building Spaces. Please use this information as a guide.

For specific code requirements please refer to the IECC code.

Notes:

* This summary is for general information purposes only and is provided without any warranty as to accuracy, completeness, or otherwise. The user should read the applicable code sections for more complete and detailed descriptions of code requirements and exceptions and should consult with a professional engineer or other competent advisor before making any decision or taking any action based on this summary.

** While energy code is required, safety may preclude the use of a manual controls in these spaces.

Control Requirement*

Code Provision

Code Summary*

Space Type

Enclosed Office

Open Plan

Office

Conference, Meeting, Multipurpose Room

Classroom, Lecture Hall, Training Room

Lobby Corridor Public Restroom

Private Restroom

Non-Exit Stairwell Gymasium Warehouse Parking

Garage Site

Lighting

Manual-On or AutoOn

≤ 50% C405.2.1.1.1

Automatically controlled spaces must be controlled to automatically turn the lighting on to not more than 50% power.

Full Automatic-On C405.2.1.1.2

Automatically controlled spaces are allowed to turn on to full.

Auto-Off ≤ 50% C405.2.1.2

Occupancy sensors shall automatically reduce lighting in ware-house storage aisle-ways and open areas by ≤ 50%

Full Auto-Off via Occupancy

Sensor

C405.2.1.1.1

C405.2.1.3

Fixtures must automatically turn off within 20 minutes of all occupants leaving the space.

Time-Switch Controls

(via System Controller)

C405.2.2.1

Each area of the building not provided with occupant sensor controls shall be provided with time switch controls. These areas must also be provided with a manual override switch.

Light Reduction Controls

C405.2.2.2

Spaces shall have a manual control that allows the occupant to reduce the connected lighting load uniformly by not less than 50%.

Manual Control

(Local Switch) C405.2.5

Areas shall incorporate a manual control to allow occupants to turn fixtures off.

Daylight- Responsive

Controls

C405.2.3.1

C405.2.3.2

Daylight-responsive controls shall be provided within each space with sidelight and toplight daylight zones totaling > 150W.

Exterior Lighting Controls

C405.2.6

C405.2.6.1 Daylight shutoff C405.2.6.2 Decorative lighting shutoff C405.2.6.3 Lighting setback C405.2.6.4 Exterior time-switch control function

On -O f Co nt ro l Da yli gh t C on tro l

Ex te rio r C on tro l

(or)

(or) (or)

(or) (or)

(or) (or)

How to Use This Guide www.acuitybrands.com/nLight • 800-535-2465

ENCLOSED OFFICE: < 250 sq. ft., Windows, nLight Enabled Fixtures

Bill of Materials Symbol Qty Product # Description

2 See Note nLight AIR Enabled Troffer with Sensor Option

1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod®

Line Voltage Wires

Line Power Feed

WirelessWired

Bill of Materials Symbol Qty Product # Description

2 See Note nLight Wired Enabled Troffer

1 nWSXA PDT LV DX Wall Switch Occupancy Sensor with On/Off, Raise/Lower nWSXA PDT LV DX

CAT-5e Cable

Line Voltage Wires

Line Power Feed

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE® controller

¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

ADDITIONAL OPTIONS:

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures can be controlled together or independently

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures turn off automatically when room becomes vacant

Daylight Control:

¡ Not required for offices without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise/lower control of fixtures

OPERATIONAL DETAILS:

rPODBA DX

For each space type there will be a wired solution on the left and wireless solution on the right.

Wire type legend

Required list of devices in order to implement room layout design above

Additional options that add control capacity beyond code requirements

Operational details describe the functionality provided by the equipment specified in the solution

Room description

Control Requirement*

Code Provision

Code Summary*

Space Type

Enclosed Office

Open Plan

Office

Conference, Meeting, Multipurpose Room

Classroom, Lecture Hall, Training Room

Lobby Corridor Public Restroom

Private Restroom

Non-Exit Stairwell Gymasium Warehouse Parking

Garage Site

Lighting

Manual-On or AutoOn

≤ 50% C405.2.1.1.1

Automatically controlled spaces must be controlled to automatically turn the lighting on to not more than 50% power.

Full Automatic-On C405.2.1.1.2

Automatically controlled spaces are allowed to turn on to full.

Auto-Off ≤ 50% C405.2.1.2

Occupancy sensors shall automatically reduce lighting in ware-house storage aisle-ways and open areas by ≤ 50%

Full Auto-Off via Occupancy

Sensor

C405.2.1.1.1

C405.2.1.3

Fixtures must automatically turn off within 20 minutes of all occupants leaving the space.

Time-Switch Controls

(via System Controller)

C405.2.2.1

Each area of the building not provided with occupant sensor controls shall be provided with time switch controls. These areas must also be provided with a manual override switch.

Light Reduction Controls

C405.2.2.2

Spaces shall have a manual control that allows the occupant to reduce the connected lighting load uniformly by not less than 50%.

Manual Control

(Local Switch) C405.2.5

Areas shall incorporate a manual control to allow occupants to turn fixtures off.

Daylight- Responsive

Controls

C405.2.3.1

C405.2.3.2

Daylight-responsive controls shall be provided within each space with sidelight and toplight daylight zones totaling > 150W.

Exterior Lighting Controls

C405.2.6

C405.2.6.1 Daylight shutoff C405.2.6.2 Decorative lighting shutoff C405.2.6.3 Lighting setback C405.2.6.4 Exterior time-switch control function

(or)

Room layout diagram with controls, fixtures, and wiring

ENCLOSED OFFICE: < 250 sq. ft., Windows, nLight Enabled Fixtures

Bill of Materials Symbol Qty Product # Description

2 See Note nLight AIR Enabled Troffer with Sensor Option

1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod®

Line Voltage Wires

Line Power Feed

WirelessWired

Bill of Materials Symbol Qty Product # Description

2 See Note nLight Wired Enabled Troffer

1 nWSXA PDT LV DX Wall Switch Occupancy Sensor with On/Off, Raise/Lower nWSXA PDT LV DX

CAT-5e Cable

Line Voltage Wires

Line Power Feed

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE® controller

¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

ADDITIONAL OPTIONS:

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures can be controlled together or independently

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures turn off automatically when room becomes vacant

Daylight Control:

¡ Not required for offices without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise/lower control of fixtures

OPERATIONAL DETAILS:

rPODBA DX

ENCLOSED OFFICE: < 250 sq. ft., Windows, 0-10V Dimming Fixtures

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE® controller

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

ADDITIONAL OPTIONS:

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures are controlled together

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures turn off automatically when room becomes vacant

Daylight Control:

¡ Not required for offices without windows or that have loads <150W in sidelit zone

Manual Control:

¡ On/off & raise/lower control of fixtures

OPERATIONAL DETAILS:

Bill of Materials Symbol Qty Product # Description

1 nPP16 D EFP Relay Pack with 0-10V Dimming Output

1 nWSXA PDT LV DX Wall Switch Occupancy Sensor with On/Off, Raise/Lower

CAT-5e Cable

Line Voltage Wires

0-10V Wires

Line Power Feed

Line Voltage Wires

0-10V Wires

Line Power Feed nWSXA PDT LV DX nPP16 D

Wired Wireless

Bill of Materials Symbol Qty Product # Description rPP20 D 24V EFP G2

Relay Pack with 0-10V Dimming Output

1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod

1 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor rPP20 D 24V rCMSB PDT 7

OPEN PLAN OFFICE: > 300 sq. ft., nLight Enabled Fixtures

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ Occupant sensor controls in open plan office spaces less than 300 sq. ft. in area shall comply with Section C405.2.1.1

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures are controlled together or independently

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures turn off automatically when room becomes vacant

¡ General lighting must be controlled in zones not greater than 600 sq. ft.

Daylight Control:

¡ Smooth continuous dimming

¡ Custom grouping of fixtures into separate daylight zones (max.

number zones = number of fixtures)

¡ Not required for offices without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise/lower control of fixtures

ADDITIONAL OPTIONS: OPERATIONAL DETAILS:

Bill of Materials Symbol Qty Product # Description

14 See Note nLight Wired Enabled Troffer

2 See Note nLight Wired Enabled Troffer with Battery Option (typical)

2 nPODMA DX On/Off, Raise/Lower WallPod

4 nCM PDT 9 RJB Occupancy Sensor

1 nCM ADCX RJB Daylight Sensor

Bill of Materials Symbol Qty Product # Description

14 See Note nLight AIR Enabled Troffer with Sensor Option

2 See Note nLight AIR Enabled Troffer with Sensor and EM Option

2 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod

CAT-5e Cable

Line Voltage Wires

Line Power Feed

EM Power Feed

Line Voltage Wires

Line Power Feed

Wired Wireless

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

D Z

EM

EM

rPODBA DX rPODBA DX

1 Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

D Z

EM

EM

nPODMA DX nPODMA DX nCM ADCX nCM PDT 9 nCM PDT 9 nCM PDT 9 nCM PDT 9

1 Some nLight enabled EM fixtures require a normal sense line connection.

Wiring shown assumes battery backup emergency option. See fixture spec sheets for details.

OPEN PLAN OFFICE: > 300 sq. ft., 0-10V Dimming Fixtures

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Occupant sensor controls in open plan office spaces less than 300 sq. ft. in area shall comply with Section C405.2.1.1

Light Fixtures:

¡ All fixtures are dimmable

¡ Each row controlled independently

¡ Maximum level can be task tuned to any per-centage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures turn off automatically when room becomes vacant

¡ General lighting must be controlled in zones not greater than 600 sq. ft.

Daylight Control:

¡ Smooth continuous dimming

¡ Daylight zones defined by rows

¡ Not required for offices without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise/lower control of fixtures

ADDITIONAL OPTIONS: OPERATIONAL DETAILS:

Bill of Materials Symbol Qty Product # Description

4 nPP16 D EFP Relay Pack with 0-10V Dimming Output

1 nPP16 D ER EFP Emergency Relay Pack with 0-10V Dimming Output

2 nPODMA DX On/Off, Raise/Lower WallPod

4 nCM PDT 9 RJB Occupancy Sensor

1 nCM ADCX RJB Daylight Sensor

CAT-5e Cable

Line Voltage Wires

Line Power Feed

0-10V Wires

EM Power Feed

Line Voltage Wires

Line Power Feed

0-10V Wires

EM Power Feed

Wired Wireless

Bill of Materials Symbol Qty Product # Description rPP20 D 24V

EFP G2

Relay Pack with 0-10V Dimming Output rPP20 D 24V EM

EFP G2

Emergency Relay Pack with 0-10V Dimming Output

2 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod

5 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor nPP16 D nPP16 D nPP16 D nCM ADCX nCM PDT 9 nCM PDT 9 nCM PDT 9 nCM PDT 9 nPP16 D nPP16 D ER

D Z nPODMA DX

EM

EM

nPODMA DX rPP20 D 24V rPP20 D 24V rPP20 D 24V rCMSB PDT 7 rCMSB PDT 7 rCMSB PDT 7 rCMSB PDT 7 rPP20 D 24V rPP20 D 24V EM

D Z rPODBA DX

EM

EM

CONFERENCE ROOM with nLight Enabled Fixtures

OPERATIONAL DETAILS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

¡ A/V zone can be programmed to control two fixtures in front of the whiteboard

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures turn off automatically when room becomes vacant

Daylight Control:

¡ Smooth continuous dimming

¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)

¡ Not required for areas without windows or that have loads <150w in sidelit zones

Manual Control:

¡ On/off & raise lower control of two zones of fixtures

ADDITIONAL OPTIONS:

nCM PDT 9 nCM ADCX nPODMA 2P DX

CAT-5e Cable Line Voltage Wires Line Power Feed Line Voltage Wires Line Power Feed

Bill of Materials Symbol Qty Product # Description

1 See Note nLight Wired Enabled Linear Fixture

6 See Note nLight Wired Enabled Downlight Fixture

1 nPODMA 2P DX 2-Pole, On/Off, Raise/Lower WallPod

1 nCM PDT 9 RJB Occupancy Sensor

1 nCM ADCX RJB Daylight Sensor

Bill of Materials Symbol Qty Product # Description

1 See Note nLight AIR Enabled Linear Fixture with Sensor Option

6 See Note nLight AIR Enabled Downlight Fixture

1 rPODBA 2P DX G2 Battery Powered, 2-Pole, On/ Off, Raise/Lower WallPod

Wired Wireless

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

rPODBA 2P DX

CONFERENCE ROOM with 0-10V Dimming Fixtures

OPERATIONAL DETAILS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures turn off automatically when room becomes vacant

Daylight Control:

¡ Smooth continuous dimming

¡ Daylight zones defined by rows

¡ Not required for areas without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise lower control of two zones of fixtures

ADDITIONAL OPTIONS:

nCM ADCX nPODMA 2P DX nCM PDT 9 nPP16 D nPP16 D

Bill of Materials Symbol Qty Product # Description

2 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output

1 rPODBA 2P DX G2 Battery Powered, 2-Pole, On/ Off, Raise/Lower WallPod

1 rCMSB PDT 7 G2 Battery Powered Occupancy and Daylight Sensor

Bill of Materials Symbol Qty Product # Description

2 nPP16 D EFP Relay Pack with 0-10V Dimming Output

1 nPODMA 2P DX 2-Pole, On/Off, Raise/ Lower WallPod

1 nCM PDT 9 RJB Occupancy Sensor

1 nCM ADCX RJB Daylight Sensor

Wired Wireless

CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires Line Voltage Wires Line Power Feed 0-10V Wires rCMSB PDT 7 rPP20 D 24V rPODBA 2P DX rPP20 D 24V

CLASSROOM with nLight Enabled Fixtures

OPERATIONAL DETAILS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures are controlled together or independently

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)

¡ Fixtures automatically turn off when room becomes vacant

Daylight Control:

¡ Smooth continuous dimming

¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)

¡ Not required for areas without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise/lower control of entire room

¡ Teacher station with 4 preset scenes

ADDITIONAL OPTIONS:

nWV PDT 16 nCM ADCX nPODMA 4S DX

DZ

Bill of Materials Symbol Qty Product # Description

9 See Note nLight Wired Enabled Troffer

1 nPODMA DX On/Off, Raise/Lower WallPod

1 nWV PDT 16 Dual Technology Wide View Occupancy Sensor

1 nPODMA 4S DX Teacher Station — 4 Scene Control with Master On/Off & Raise/Lower

1 nCM ADCX RJB Daylight Sensor

Bill of Materials Symbol Qty Product # Description

9 See Note nLight AIR Enabled Troffer with Sensor Option

1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod

1 rPODBA 4S DX G2 Teacher Station — Battery Powered 4 Scene Control with Master On/Off & Raise/Lower

Wired Wireless

CAT-5e Cable Line Voltage Wires Line Power Feed Line Voltage Wires Line Power Feed

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

DZ

rPODBA 4S DX rPODBA DX

CLASSROOM with 0-10V Dimming Fixtures

OPERATIONAL DETAILS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Light Fixtures:

¡ All fixtures are dimmable

¡ Each row can be controlled independently

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)

¡ Fixtures automatically turn off when room becomes vacant

Daylight Control:

¡ Smooth continuous dimming

¡ Daylight zones defined by rows

¡ Not required for areas without windows or that have loads <150W in sidelit zones

Manual Control:

¡ Master on/off & raise/ lower control of entire room

¡ Teacher station with 4 preset scenes

ADDITIONAL OPTIONS:

nPP16 D nPP16 D nPP16 D

DZ

nWV PDT 16 nCM ADCX nPODMA 4S DX

Bill of Materials Symbol Qty Product # Description

3 nPP16 D EFP Relay Module with 0-10V Dimming Output

1 nPODMA DX On/Off, Raise/Lower WallPod

1 nWV PDT 16 Dual Technology Wide View Occupancy Sensor

1 nPODMA 4S DX Teacher Station — 4 Scene Control with Master On/Off & Raise/Lower

1 nCM ADCX RJB Daylight Sensor

Bill of Materials Symbol Qty Product # Description

3 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output

1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod

2 rCMSB PDT 7 G2 Battery Powered Occupancy and Daylight Sensor

1 rPODBA 4S DX G2 Teacher Station — Battery Powered 4 Scene Control with Master On/Off & Raise/Lower

Wired Wireless

CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires Line Voltage Wires Line Power Feed 0-10V Wires rPP20 D 24V rPP20 D 24V rPP20 D 24V

DZ

rPODBA DX rCMSB PDT 7 rPODBA 4S DX

LOBBY with nLight Enabled Fixtures

DZ

nPODMA DX

Bill of Materials Symbol Qty Product # Description

4 See Notes nLight Wired Enabled Downlight

DZ

nPODM DX

1 See Notes nLight Wired Enabled Troffer with Sensor Option

1 nPODMA DX On/Off, Raise/Lower WallPod

Bill of Materials Symbol Qty Product # Description

4 See Notes nLight AIR Enabled Downlight

DZ

nPODM DX

1 See Notes nLight AIR Enabled Troffer with Sensor Option

1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod

Wired Wireless

CAT-5e Cable Line Voltage Wires Line Power Feed Line Voltage Wires Line Power Feed

OPERATIONAL DETAILS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off when room becomes vacant

Daylight Control:

¡ Smooth continuous dimming

¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)

¡ Not required for areas without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise/lower control of fixtures

ADDITIONAL OPTIONS:

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

DZ

CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires Line Voltage Wires Line Power Feed 0-10V Wires

LOBBY with 0-10V Dimming Fixtures nPP16 D nPP16 D

DZ

nPODMA DX nCM PDT 9 ADCX

Bill of Materials Symbol Qty Product # Description

2 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output

1 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod

1 rCMSB PDT 7 G2 Battery Powered Occupancy and Daylight Sensor

Bill of Materials Symbol Qty Product # Description

2 nPP16 D EFP Relay Pack with 0-10V Dimming Output

1 nPODMA DX On/Off, Raise/Lower WallPod

1 nCM PDT 9 ADCX Occupancy and Daylight Sensor

Wired Wireless

OPERATIONAL DETAILS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off when room becomes vacant

Daylight Control:

¡ Smooth continuous dimming

¡ Daylight zones defined by relay module wiring

¡ Not required for areas without windows or that have loads <150W in sidelit zones

Manual Control:

¡ On/off & raise/lower control of fixtures

ADDITIONAL OPTIONS:

rPP20 D 24V rPP20 D 24V

DZ

Bill of Materials Symbol Qty Product # Description

7 See Note nLight Wired Enabled Troffer with Sensor Option

2 See Note nLight Wired Enabled Troffer with Battery Option

3 nPODMA On/Off WallPod

4 nCM 10 RJB Occupancy Sensor

Bill of Materials Symbol Qty Product # Description

7 See Note nLight AIR Enabled Troffer with Sensor Option

2 See Note nLight AIR Enabled Troffer with Sensor and EM Option

3 rPODBA G2 Battery Powered, On/Off, Raise/Lower WallPod

CAT-5e Cable

Line Voltage Wires

Line Power Feed

EM Power Feed

Line Voltage Wires

Line Power Feed

EM Power Feed

Wired Wireless nCM 10 nCM 10 nCM 10 nCM 10

EM

EM

nPODMA nPODMA nPODMA

1 Some nLight enabled EM fixtures require a normal sense line connection.

Wiring shown assumes battery backup emergency option. See fixture spec sheets for details.

CORRIDOR with nLight Enabled Fixtures

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures are controlled together or independently

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Manual Control:

¡ On/off control of fixtures

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

Some nLight enabled EM fixtures require a normal sense line connection. Wiring shown assumes battery backup emergency option. See fixture spec sheets for details.

EM

EM

rPODBA rPODBA rPODBA

1 Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

Line Voltage Wires

Line Power Feed

0-10V Wires

EM Power Feed

CAT-5e Cable

Line Voltage Wires

Line Power Feed

0-10V Wires

EM Power Feed

Wired Wireless nCM 10 nCM 10 nCM 10 nPP16 D nCM 10 nPP16 D ER

EM

EM

nPODMA nPODMA nPODMA

CORRIDOR with 0-10V Dimming Fixtures

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Manual Control:

¡ On/off control of fixtures

Bill of Materials Symbol Qty Product # Description

1 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output rPP20 D 24V EM

EFP G2

Emergency Relay Pack with 0-10V Dimming Output

4 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor

3 rPODBA G2 Battery Powered, On/Off, Raise/Lower WallPod

Bill of Materials Symbol Qty Product # Description

1 nPP16 D EFP Relay Pack with 0-10V Dimming Output

1 nPP16 D ER EFP Emergency Relay Pack with 0-10V Dimming Output

4 nCM 10 RJB Occupancy Sensor

3 nPODMA On/Off WallPod rCMSB PDT 7 rCMSB PDT 7 rCMSB PDT 7 rPP20 D 24V rCMSB PDT 7 rPP20 D 24V EM

EM

EM

rPODBA rPODBA rPODBA

PUBLIC RESTROOM with nLight Enabled Fixtures

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures are controlled together or independently (per room)

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied (or optionally can be configured to come on automatically to 50%)

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Manual Control:

¡ On/off & raise/lower control of fixtures

¡ If switch poses safety concerns, optionally can be programmed for “on only”

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

Bill of Materials Symbol Qty Product # Description

2 See Note nLight Wired Enabled Troffer

2 See Note nLight Wired Enabled Troffer with Battery Option

2 nPODMA DX On/Off, Raise/Lower WallPod

Bill of Materials Symbol Qty Product # Description

2 See Note nLight AIR Enabled Troffer with Sensor Option

2 See Note nLight AIR Enabled Troffer with Sensor and EM Option

2 rPODBA DX G2 Battery Powered, On/Off, Raise/Lower WallPod

Wired Wireless

Line Voltage Wires Line Power FeedCAT-5e Cable

Line Voltage Wires Line Power Feed

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

EM

rPODBA DX rPODBA DX

EM

1 1

1 Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

EM

rPODBA DX rPODBA DX

EM

1 1

1 Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

EM

1 1 nPODMA DX nPODMA DX

EM

1 Some nLight enabled EM fixtures require a normal sense line connection.

nCM PDT 9 nCM PDT 9

PUBLIC RESTROOM with 0-10V Dimming Fixtures

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures are controlled together or independently (per room)

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied (or optionally can be configured to come on automatically to 50%)

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Manual Control:

¡ On/off & raise/lower control of fixtures

¡ If switch poses safety concerns, optionally can be programmed for “on only”

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Bill of Materials Symbol Qty Product # Description

2 nPP16 D EFP Relay Pack with 0-10V Dimming Output

2 nPP16 D ER EFP Emergency Module with 0-10V Dimming Output

2 nPODMA DX On/Off & Raise/Lower WallPod

2 nCM PDT 9 RJB Occupancy Sensor

Bill of Materials Symbol Qty Product # Description

2 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output rPP20 D 24V EM

EFP G2

Emergency Relay Pack with 0-10V Dimming Output

2 rPODBA DX G2 Battery Powered, On/Off & Raise/Lower WallPod

2 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor

Wired Wireless

CAT-5e Cable 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed nCM PDT 9 nCM PDT 9 nPP16 D nPP16 D

EM EM

nPP16 D ERnPP16 D ER nPODMA DX nPODMA DX

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

rCMSB PDT 7 rPP20 D 24VrPP20 D 24V

EM EM

rPP20 D 24V EM rPP20 D 24V EM rPODBA DX rPODBA DX

PRIVATE / SINGLE RESTROOM with nLight Enabled Fixture

OPERATIONAL DETAILS:

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via progrmamming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied (or optionally can be configured to come on automatically to 50%)

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Manual Control:

¡ On/off & raise/lower control of fixtures

¡ If switch poses safety concerns, optionally can be programmed for “on only”

ADDITIONAL OPTIONS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option nWSXA LV DX

Bill of Materials Symbol Qty Product # Description

1 See Note nLight Wired Enabled Troffer

1 nWSXA PDT LV DX Occupancy Wall Switch, On/Off, Raise/Lower

Bill of Materials Symbol Qty Product # Description

1 See Notes nLight AIR Enabled Troffer with Sensor Option

1 rPODBA DX G2 Battery Powered, On/Off, Raise/ Lower WallPod

Wired Wireless

Line Voltage Wires Line Power FeedCAT-5e Cable Line Voltage Wires Line Power Feed

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

NON-EXIT STAIRWELL with nLight Enabled Fixtures/0-10V Dimming Fixtures

OPERATIONAL DETAILS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

¡ For emergency lighting control use a power pack with ER/EM option or nLight Enabled Fixture with emergency option

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Manual Control:

¡ Safety may preclude the use of a manual control in these areas

ADDITIONAL OPTIONS:

Line Power Feed

EM Power Feed

Wireless with nLight Enabled Fixtures

Bill of Materials Symbol Qty Product # Description

1 See Note nLight AIR Enabled Fixture with Sensor Option

1 See Note nLight AIR Enabled Fixture with Sensor and EM Option

Line Voltage Wires

Line Power Feed

0-10V Wires

EM Power Feed

Wireless with 0-10V Dimming Fixtures

Bill of Materials Symbol Qty Product # Description rPP20 D 24V

EFP G2

Relay Pack with 0-10V Dimming Output rPP20 D 24V EM

EFP G2

Emergency Relay Pack with 0-10V Dimming Output

2 rCMSB PDT 7 G2 Battery Powered Occupancy Sensor

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

rPP20 D 24V rCMSB 7 rCMSB 7 rPP20 D 24V EM

EM

EM

1 Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

WAREHOUSE STORAGE Wireless Enabled Fixtures/0-10V Dimming Fixtures

Bill of Materials Symbol Qty Product # Description

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

rPODB 2P rPODB 2P rPODB 2P

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

20 See Note nLight AIR Enabled High Bay Fixture with Sensor Option

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

rPODB 2P rPODB 2P rPODB 2P

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

EMG

15 See Note nLight AIR Enabled High Bay Fixture with Sensor and EM Option

3 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod

Wireless with nLight Enabled Fixtures

Line Voltage Wires Line Power Feed EM Power Feed

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/ daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Daylight Control:

¡ Daylight responsive controls lights to full off when adequate daylight present

¡ Not required for spaces without skylights or that have loads <150W in toplit zones

Wireless with 0-10V Dimming Fixtures

Bill of Materials Symbol Qty Product # Description

6 rPP20 D 24V EFP G2 Relay Pack with 0-10V Dimming Output rPP20 D 24V EM

EFP G2

Emergency Relay Pack with 0-10V Dimming Output

3 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod

12 rCMS 6 G2 Occupancy Sensor

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

Low Voltage Wires 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

rCMS 6 rCMS 6

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

rPP20 D 24V EM rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rPP20 D 24V rPODBA 2P rPODB 2P rPODBA 2P

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

STORAGE RACKS

rPODBA 2P rPODBA 2P rPODBA 2P

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

EM

1 Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

GYMNASIUM with nLight Enabled Fixtures/0-10V Dimming Fixtures

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1 - Time-Switch Controls), and also qualify for Enhanced Digital Lighting Controls (C406.4)

¡ HVAC control available through system-wide BACnet® interface option on the ECLYPSE controller

¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

Light Fixtures:

¡ All fixtures are dimmable

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Daylight Control:

¡ Daylight responsive controls lights to full off when adequate daylight present

¡ Not required for spaces without skylights or that have loads <150W in toplit zones

Bill of Materials Symbol Qty Product # Description rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6

M E

M E

M

EM

E

M E

M E rPODB 2P rPODB 2P n n n n n nnn n n n n nn nn n nn n rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn

18 See Notes nLight AIR Enabled Fixture with Sensor Option rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6rLSXR 6 rLSXR 6 rLSXR 6 rLSXR 6

M E

M E

M

EM

E

M E

M E rPODB 2P rPODB 2P n n n n n nnn n n n n nn nn n nn n rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn rLSXR 6 EMn6 See Notes nLight AIR Enabled Fixture with Sensor and EM Option

2 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod

Bill of Materials Symbol Qty Product # Description rPP20 D 24V

EFP G2

Relay Pack with 0-10V Dimming Output rPP20 D 24V EM

EFP G2

Emergency Relay Pack with 0-10V Dimming Output

2 rPODBA 2P G2 Battery Powered, 2-Pole, On/Off WallPod

6 rCMS 6 G2 High Bay Occupancy Sensor

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

Line Voltage Wires Line Power Feed EM Power Feed

Wireless with nLight Enabled Fixtures Wireless with 0-10V Dimming Fixtures

Low Voltage Wires 0-10V Wires Line Voltage Wires Line Power Feed EM Power Feed

M E

M E

M

EM

E

M E

M E rPODBA 2P rPODBA 2P

1 1

1 1

Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

M E

M E

M

EM

E

M E

M E rPODBA 2P rPODBA 2P rPP20 D 24V EM rPP20 D 24V rPP20 D 24V EM rPP20 D 24V rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6 rCMS 6

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

¡ Devices can be connected to nLight backbone to enabled network control or time schedules, including astronomical time schedules for shutoff (C405.2.6.2), lighting setback (C405.2.6.3), & exterior time-switch control (C405.2.6.4). GFXK option can be added to nLight ECLYPSE to provide manual override (C405.2.5).

¡ Wireless fixture embedded control and occupancy/daylighting sensor options available, please see the fixture specification sheet

¡ nLight enabled fixtures comply with monitoring and configuration requirements of Luminaire Level Lighting Controls (LLLC) (C405.2.1, C405.2.4, C405.2.5)

Light Fixtures:

¡ All fixtures are dimmable

¡ All fixtures can be controlled together or independently

¡ Maximum level can be task tuned to any percentage via programming

Occupancy Control:

¡ Fixtures automatically go to full bright when occupied

¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant

Daylight Control:

¡ Daylight responsive controls lights to full off when adequate daylight present

Note: Contact your local lighting agent for more information on nLight enabled fixtures.

nLight enabled fixtures provide Luminaire Level Lighting Controls (LLLC), as specified in the IECC 2018 CODE.

PARKING GARAGE with nLight AIR Enabled Fixtures

Wireless Parking Garage

Bill of Materials Symbol Qty Product # Description

ELEVATOR LOBBY

STAIRS

IN

OUT

DWN

UP

ELEC/MECH/DATA

n n n n n n n n n n

NECYD

NLTAIR

n rPODB n

13 See Note nLight AIR Enabled Canopy Fixture with Sensor Option

ELEVATOR LOBBY

STAIRS

IN

OUT

DWN

UP

ELEC/MECH/DATA

n n n n n n n n n n

NECYD

NLTAIR

n rPODB n

2 See Note nLight AIR Enabled Canopy Fixture with Sensor and EM Option

ECLYPSE™ECLYPSE™ ECLYPSE™ 1 nECY nLight ECLYPSE Network System Controller

Bridge nLight ECLYPSE

LAN

nPP20 nCM nWSX

1 nECYD NLTAIR G2 nLight AIR Adapter

ELEVATOR LOBBY

STAIRS

IN

OUT

DWN

UP

ELEC/MECH/DATA

n

NECYD NLTAIR

NECY MVOLT ENC GFXK

PS 150

EM

EM

Fixture(s) assumed to include power interruption detection emergency option.

For battery backup option, no dedicated EM circuit necessary.

Low Voltage Wires

USB Cable

Line Voltage Wires

Line Power Feed

EM Power Feed

OPERATIONAL DETAILS: ADDITIONAL OPTIONS:

¡ Devices can be connected to nLight backbone to enabled network control or time schedules, including astronomical time schedules for shutoff (C405.2.6.2), lighting setback (C405.2.6.3), & exterior time-switch control (C405.2.6.4).

This is the start of the file's text. The full file is on GovTribe.