This document contains the results of a lead-based paint investigation conducted at the Veterans Healthcare System of the Ozarks Building 10 Boiler Plant in Fayetteville, Arkansas. Lead-based paint was found on all surfaces tested, with an average reading of 11.32 mg/cm2. Positive readings ranged from 4.9 to 17.1 mg/cm2. The solicitation requests proposals for installing catwalks and upgrading the piping system at the same Boiler Plant. Interested Service-Disabled Veteran-Owned Small Businesses are asked to review the forthcoming request for proposals, with a tentative issue date of January 12, 2021 and proposal due date of February 15, 2021. The contract award is anticipated within 30 days of receipt of proposals. The recommended contract period is 365 days from notice to proceed. The location of work is the Veterans Healthcare System of the Ozarks facility in Fayetteville. NAICS code 238220 applies with a $16.5 million size standard. The construction cost range is $2-5 million.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25621R0020 0004 .docx | DOCX document | |
| COMPLETE RFI RESPONSES.docx | DOCX document | |
| 36C25621R0020 0003.docx | DOCX document | |
| VA-Soils Report.pdf | ||
| Parking Plan Visual with Boiler laydown.pdf | ||
| GC101 Updated.pdf | ||
| E-601 Updated.pdf | ||
| Asbestos Report.pdf | ||
| SITE VISIT SIGN IN SHEET.pdf | ||
| RFI RESPONSES.docx.doc | DOC document | |
| AMENDMENT TO RESCHEDULE SITE VISIT - 36C25621R0020 0002.docx | DOCX document | |
| AMENDMENT TO RESCHEDULE SITE VISIT - 36C25621R0020 0001.docx | DOCX document | |
| 36C25621R0020 0001.docx | DOCX document | |
| 564-14-124 - Construction Specifications.pdf | ||
| 564-14-124 Construction Drawings.pdf | ||
| EXHIBIT C CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY v2.docx | DOCX document | |
| SOLICITATION 36C25621R0020_1.docx | DOCX document | |
| Current Parking Plan.pdf | ||
| WAGE DETERMINATION AR20210035 01-01-2021.pdf | ||
| EXHIBIT A PERFORMANCE RELEVANCY SURVEY v2.docx | DOCX document | |
| EXHIBIT B Past and Present Performance Questionnaire.docx | DOCX document | |
| 36C25621R0020.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
220 North Knoxville Russellville, Arkansas 72801 Phone (479) 968-6767 Fax (479) 968-1956
(800) 530-7968 www.eegonline.com
2213 Hawks Landing Fayetteville, Arkansas 72704
Phone (479) 444-0438 Fax (479) 444-6767
December 14, 2010
Mr. Terry Blaylock Environmental Protection Associates #9 Remington Cove Little Rock, Arkansas 72204
RE: Work Area Lead Investigation Veterans Healthcare System of the Ozarks ♦ Building 10 Boiler Plant ♦ Fayetteville, Arkansas ♦
EEG Project #10-0117-066
Dear Mr. Blaylock:
ENVIRONMENTAL ENTERPRISE GROUP, INC. (EEG) has conducted a work area lead-based paint investigation at the Veterans Healthcares System of the Ozarks, which was limited to painted surfaces in Building 10 Boiler Plant, located in Fayetteville, Arkansas under the direction of Mr. Kenneth Morrow of Tri- Systems, Incorporated. The work area investigation was conducted by Mr. Mike Cole, Certified Inspector/Risk Assessor, Arkansas Department of Environmental Quality (ADEQ) certification #000248.
Positive Lead Based Paint identified by XRF measurements are documented by multiple readings of greater than 1.0 milligram per square centimeter. Negative Lead Based Paint readings are documented by multiple readings of less than 1.0 milligram per square centimeter. Surfaces that are consistently below detection levels are considered to have a minimal hazard for work activities relating to lead exposure. Surfaces that are consistently above detection levels but are not at Lead Based Paint levels, may pose potential risks while performing job tasks such as scraping, grinding or sanding. The OSHA Lead Standard does not define lead-paint based on the amount of lead present in a material. That is, the standard does not specify a minimum amount or concentration of lead that triggers a determination that lead is present and the potential for occupational exposure exists. OSHA requires analytical data from personal air samples as proof of no, or limited exposure, to lead-containing materials if any lead is present in a material. OSHA's permissible exposure limit is 50 µg/m3 and OSHA's action level is 30 µg/m3 for an 8-hour time-weighted average.
Lead based paint was detected on every surface analyzed. The average lead concentration was 11.32 milligram per square centimeter. A listing of results is included in the data tables below.
A surface-by-surface style investigation for lead-based paint was conducted on December 10, 2010 by Mr. Mike Cole of EEG. Testing was performed using a Niton X-Ray Fluorescence Spectrometer (XRF) model XLp 300, serial number 25752. The investigation was limited to only painted surfaces in Building 10 Boiler Plant. The work area investigation indicated that lead-based paint is present on the following substrates/areas:
EPA
Work Area Lead Investigation ♦ EEG Project #10-0117-066 December 14, 2010
220 North Knoxville Russellville, Arkansas 72801 Phone (479) 968-6767 Fax (479) 968-1956
(800) 530-7968 www.eegonline.com
2213 Hawks Landing Fayetteville, Arkansas 72704
Phone (479) 444-0438 Fax (479) 444-6767
XRF
Reading
XRF
Reading in mg/cm² Material Description
4 15.3 White Metal Lower I Beam Near Ceiling 5 13.6 White Metal Lower I Beam Near Ceiling 6 16.6 White Metal Angle Brace Near Ceiling 7 11.9 White Metal Angle Brace Near Ceiling 8 10.9 White Metal Tension Rods Near Ceiling 9 7.3 White Metal Tension Rods Near Ceiling
10 9.0 White Metal Upright I Beam Near Ceiling 11 11.8 White Metal Upright I Beam Near Ceiling 12 12.2 White Metal Upper I Beam Near Ceiling 13 12.5 White Metal Upper I Beam Near Ceiling 14 12.4 White Metal Upper I Beam Near Ceiling 15 5.1 White Concrete Ceiling Deck Near Ceiling 16 5.2 White Concrete Ceiling Deck Near Ceiling 17 7.2 White Brick South Wall Main Floor 18 8.7 White Brick South Wall Main Floor 19 10.5 White Brick East Wall Column Main Floor 20 4.9 White Brick East Wall Column Main Floor 21 13.2 White Brick West Wall Column Main Floor 22 17.1 White Brick West Wall Column Main Floor 23 15.4 White Brick West Wall Main Floor 24 15.8 White Brick West Wall Main Floor 25 14.3 White Brick West Wall Main Floor 26 9.8 White Brick North Wall Column Near Ceiling 27 11.2 White Brick North Wall Column Near Ceiling 28 12.3 White Brick North Wall Lower I Beam Near Ceiling 29 10.2 White Brick North Wall Lower I Beam Near Ceiling
Enclosed please find a copy of the XRF data sheet for this project. EEG appreciates the opportunity to have been of service to EPA. Please feel free to contact me with any questions you may have or if I can be of further assistance. I can be reached at 968-6767 extension 2131 or via e-mail at mcole@eegonline.com. We look forward to working with you again soon.
Respectfully, Mike Cole Certified Inspector/Risk Assessor Arkansas Department of Environmental Quality #000248
Attachments
Building 10 Boiler Plant
Boiler Plant Main Floor Near Ceiling
VETERANS HEALTHCARE SYSTEM
BUILDING 10 BOILER PLANT
FAYETTEVILLE, ARKANSAS
www.eegonline.com
Boiler Plant South Wall
Boiler Plant East Wall Column
Boiler Plant West Wall Column
Boiler Plant North Wall Column and I Beam
CLIENT PROPERTY INSPECTOR
Environmental Protection Associates Veterans Healthcare System of the Ozarks Name: Mike Cole
#9 Remington Cove Boiler Plant Signature:
Little Rock, Arkansas 72204 Fayetteville, Arkansas Inspection Date:
TEST
NO. AREA OR FLOOR ROOM EQUIV. OR
NAME COMPONENT COLOR SUBSTRATE
XRF READING
(MG/CM2)
RESULT
(POS., NEG.,
INC.)
QUANTITY CORRECTION
(YES/NO)
1 NIST SRM 2573 Red 1.1 No 2 NIST SRM 2573 Red 1.1 No 3 NIST SRM 2573 Red 1.0 No 4 Building 10 Near Ceiling Lower I Beam White Metal 15.3 Positive No 5 Building 10 Near Ceiling Lower I Beam White Metal 13.6 Positive No 6 Building 10 Near Ceiling Angle Brace White Metal 16.6 Positive No 7 Building 10 Near Ceiling Angle Brace White Metal 11.9 Positive No 8 Building 10 Near Ceiling Tension Rods White Metal 10.9 Positive No 9 Building 10 Near Ceiling Tension Rods White Metal 7.3 Positive No 10 Building 10 Near Ceiling Upright I Beam White Metal 9.0 Positive No 11 Building 10 Near Ceiling Upright I Beam White Metal 11.8 Positive No 12 Building 10 Near Ceiling Upper I Beam White Metal 12.2 Positive No 13 Building 10 Near Ceiling Upper I Beam White Metal 12.5 Positive No 14 Building 10 Near Ceiling Upper I Beam White Metal 12.4 Positive No 15 Building 10 Near Ceiling Ceiling Deck White Concrete 5.1 Positive No 16 Building 10 Near Ceiling Ceiling Deck White Concrete 5.2 Positive No 17 Building 10 Main Floor South Wall White Brick 7.2 Positive No 18 Building 10 Main Floor South Wall White Brick 8.7 Positive No 19 Building 10 Main Floor East Wall Column White Brick 10.5 Positive No 20 Building 10 Main Floor East Wall Column White Brick 4.9 Positive No 21 Building 10 Main Floor West Wall Column White Brick 13.2 Positive No 22 Building 10 Main Floor West Wall Column White Brick 17.1 Positive No 23 Building 10 Main Floor West Wall White Brick 15.4 Positive No 24 Building 10 Main Floor West Wall White Brick 15.8 Positive No
XRF: Niton XLP 300A SERIAL # 25752
AREA/FLOOR: I = INTERIOR E = EXTERIOR B = BASEMENT 1 = FIRST FLOOR
RESULT: P = POSITIVE N = NEGATIVE
SUBSTRATE: W = WOOD M = METAL C = CONCRETE B = BRICK D = DRYWALL P = PLASTER I - INCONCLUSIVE
XRF Data Sheet 10-0117-066
December 10, 2010
CLIENT PROPERTY INSPECTOR
Environmental Protection Associates Veterans Healthcare System of the Ozarks Name: Mike Cole
#9 Remington Cove Boiler Plant Signature:
Little Rock, Arkansas 72204 Fayetteville, Arkansas Inspection Date:
TEST
NO. AREA OR FLOOR ROOM EQUIV. OR
NAME COMPONENT COLOR SUBSTRATE
XRF READING
(MG/CM2)
RESULT
(POS., NEG.,
INC.)
QUANTITY CORRECTION
(YES/NO)
25 Building 10 Main Floor West Wall White Brick 14.3 Positive No 26 Building 10 Near Ceiling North Wall Column White Brick 9.8 Positive No 27 Building 10 Near Ceiling North Wall Column White Brick 11.2 Positive No 28 Building 10 Near Ceiling North Wall Lower I Beam White Brick 12.3 Positive No 29 Building 10 Near Ceiling North Wall Lower I Beam White Brick 10.2 Positive No 30 NIST SRM 2573 Red 1.0 No 31 NIST SRM 2573 Red 1.2 No 32 NIST SRM 2573 Red 1.0 No
XRF: Niton XLP 300A SERIAL # 25752 SUBSTRATE: W = WOOD M = METAL C = CONCRETE B = BRICK D = DRYWALL P = PLASTER I - INCONCLUSIVE
AREA/FLOOR: I = INTERIOR E = EXTERIOR B = BASEMENT 1 = FIRST FLOOR
XRF Data Sheet 10-0117-066