Questions and answers.docx

DOCX document 17 KB Posted

Attached to
J049-- Boiler Maintenance
Solicitation number
36C25621Q0433
Issued by

About this file

This document contains questions and answers regarding boiler maintenance requirements for the Southeast Louisiana Veterans Health Care System. The VA will not provide filters for RO units or spare parts for boilers and will require the contractor to perform these tasks. The contractor must also conduct steam quality checks, calibrate various temperature, flow, and pressure devices across several locations monthly, and change filters on RO units twice per year. The VA will not provide calibrated gauges or initial spare parts for hot water boilers. Responses for these requirements are due by April 12, 2020 to tiffany.conner@va.gov.

View the file

Other files

File Type Posted
Question _ answer.docx DOCX document
36C25621Q0433 0005.docx DOCX document
36C25621Q0433 0004_1.docx DOCX document
Question and answer.docx DOCX document
36C25621Q0433 0003.docx DOCX document
36C25621Q0433 0002.docx DOCX document
IMG_0508.jpg JPG image
36C25621Q0433 0001_1.docx DOCX document
36C25620P0087 P00001.pdf PDF
36C25621Q0433_1 Boiler RFQ.docx DOCX document
Wage Determination 2015-5189 Rev 17.pdf PDF
36C25621Q0433.docx DOCX document
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A. RO Unit:

Q: what specific PM requirements for RO Unit Will the VA be providing the filters for the change out twice a year on the RO Unit? A: VA will not going to provide filters for. Contractor will provide both filters changeout.

B. Steam Quality Check:

1. Is anyone currently doing this? No. This is a new requirement.

1. If so who?

C. Monthly Visits:

1. Please confirm the monthly checks are the following as per VA Directive 1810D:

Monthly and Daily checks will be conducted by the VA staff.

11a
Low-water cutoff (slow drain)
M
11b
Fire each boiler and the pilot on the alternate fuel for 1 hour
M
11c
Low-water cutoff shunt switch
M
11d
Auxiliary low-water cut-off (slow drain)
M
11e
Auxiliary low-water cut-off shunt switch
M
11f
High-water alarm
M
11g
Low-water alarm
M
11k
Flame scanner
M
13g
Operation of deaerator high and low water alarms
M
13h
Operation of deaerator steam pressure or temperature control
M
13i
Operation of condensate storage tank high and low water alarms
M
13j
Operation of all other alarm devices
M

D. Calibrated Gauges:

1. Will the VA be providing a spare set of calibrated gauges to use to swap out on each boiler so those gauges can be calibrated? No, VA will not be providing gauges.

E. Calibrate Temperature, Flow, Pressure Transmitters and Recorders:

1. Please confirm and make a complete list of all devices the VA want calibrated in the contract for the following locations:

0. Pan Am

0. IP

0. OP

0. TL

0. Research

0. CEP

0. Boilers Needs calibration

0. Da tank Needs calibration

0. PRV safety valves Needs calibration

F. Laars Hot Water Boiler:

1. Will the VA be providing initial spare parts (relief valve, ignitors, pressure & flow switches, etc)? No, VA will not be providing spare parts.