Attachment 02 Dual Duct Air Terminal Unit Schedule Floor 01 ED.pdf

PDF 1 MB Posted

Attached to
657-26-602 Create Observation Unit JC
Solicitation number
36C25526R0162
Issued by

About this file

This document is a Dual Duct Air Terminal Unit Schedule providing specifications and performance data for multiple HVAC terminal units. The schedule lists 17 distinct dual duct units (models 1/VAV-1 through 1/VAV-17) with their associated mechanical and performance parameters.

Each unit is specified with cold and hot duct inlet sizes ranging from 5 to 12 inches, maximum air pressure drop (APD) of 0.5 inches of water column, and detailed airflow specifications. Cold duct airflow capacity ranges from 150 to 670 cubic feet per minute (CFM), while hot duct airflow varies from 115 to 335 CFM. The schedule includes maximum allowable airflow parameters for both cold and hot duct inlet conditions, outlet duct sizing (ranging from 13x5 to 24x12 inches), and design inlet static pressure of 0.75 inches of water column. Maximum HC-level outlet duct size is consistently 190 units, and all units maintain a maximum CFM specification of 400-500 to 500-600 depending on the model. The document appears to be a technical specification template used for equipment procurement, containing no procurement timeline, pricing information, set-asides, or federal contract details.

View the file