This document is a Heterotrophic Plate Count (HPC) laboratory test results report from HGS Analytical for the Robert J Dole VA Medical Center, dated December 23, 2024. The report details water sample testing performed on December 10, 2024, with samples collected from multiple rooms across Buildings 1 and 19, specifically from floors, rooms, and water lines such as 102-1, 106N-1, 106S-1, 117-19, 118-19, 119-19, and 120-19.

The test results predominantly show bacterial counts below 10 CFU/mL, which meets the Infection Control Standards for VA Clinics' lowest threshold requiring no additional action. However, one notable exception is sample 7C from Room 120-19 in Building 19, which registered 30,000 CFU/mL - significantly exceeding the 500 CFU/mL threshold that requires taking the line out of service, shocking all lines, and retesting to determine treatment efficacy. The testing was conducted using Standard Methods 9215C (spread plate method) and followed SOP-034 for characterizing water samples by heterotrophic plate count. The laboratory is ELAP certified and compliant with New York State Department of Health and Florida Administrative Code standards for drinking and non-potable water microbiology testing.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Robert J Dole VA Medical Center, December 10, 2024 - 1 of 4

HGS Analytical 1709 Hillyer Robinson Industrial Parkway (E)

Oxford, Alabama 36203 T: (256) 212-0134 | F: (256) 236-2979 lab@hgsengineeringinc.com | hgslab.com

ELAP Lab ID: 12125 | NELAC Lab ID: E871141 | EPA Lab ID: AL01167

David A. Miller Robert J Dole VA Medical Center 5500 E Kellogg Wichita, KS 67218 (316)-685-2221 Ext 53729 David.Miller7@va.gov

December 23, 2024

Subject: Robert J Dole VA Medical Center, Q1 FY2025 Heterotrophic Plate Count Results

Dear Mr. Miller, The HGS Analytical Laboratory performed heterotrophic plate count analysis on samples taken from the Robert J Dole VA Medical Center on December 10, 2024, and delivered to the laboratory on December 12, 2024.

The Infection Control Standards for VA Clinics indicate these actions at the following bacterial thresholds:

1. Detection greater than 500 CFU/mL: Take the line out of service, shock all the lines, and retest to determine treatment efficacy.

2. Detection greater than 200 CFU/mL but less than 500 CFU/mL: Lines may remain in service, but it is recommended that they be shocked again.

3. Detection less than 200 CFU/mL: No additional action -- Continue current disinfection protocols.

Robert J Dole VA Medical Center, December 10, 2024 - 2 of 4

HGS Analytical 1709 Hillyer Robinson Industrial Parkway (E)

Oxford, Alabama 36203 T: (256) 212-0134 | F: (256) 236-2979 lab@hgsengineeringinc.com | hgslab.com

ELAP Lab ID: 12125 | NELAC Lab ID: E871141 | EPA Lab ID: AL01167

David A. Miller Robert J Dole VA Medical Center 5500 E Kellogg Wichita, KS 67218 (316)-685-2221 Ext 53729 David.Miller7@va.gov

Collection Date: 12/10/2024 Date of Arrival: 12/12/2024

Date of Receipt: 12/12/2024 Date of Processing: 12/12/2024 Date of Reporting: 12/23/2024

Detailed Report of Heterotrophic Plate Counts

Bottle ID Building Floor Room Water Line Results

1A 1 1 102-1 <10 CFU/mL

1B 1 1 102-1 <10 CFU/mL

1C 1 1 102-1 <10 CFU/mL

1D 1 1 102-1 <10 CFU/mL

1E 1 1 102-1 Cavitron <10 CFU/mL

2A 1 1 106N-1 <10 CFU/mL

2B 1 1 106N-1 <10 CFU/mL

2C 1 1 106N-1 <10 CFU/mL

2D 1 1 106N-1 <10 CFU/mL

2E 1 1 106N-1 Cavitron <10 CFU/mL

3A 1 1 106S-1 <10 CFU/mL

3B 1 1 106S-1 <10 CFU/mL

3C 1 1 106S-1 <10 CFU/mL

3D 1 1 106S-1 <10 CFU/mL

3E 1 1 106S-1 Cavitron <10 CFU/mL

4A 19 1 117-19 <10 CFU/mL

4B 19 1 117-19 <10 CFU/mL

Robert J Dole VA Medical Center, December 10, 2024 - 3 of 4

Bottle ID Building Floor Room Water Line Results

4C 19 1 117-19 <10 CFU/mL

4D 19 1 117-19 <10 CFU/mL

5A 19 1 118-19 <10 CFU/mL

5B 19 1 118-19 <10 CFU/mL

5C 19 1 118-19 <10 CFU/mL

5D 19 1 118-19 <10 CFU/mL

5E 19 1 118-19 Cavitron <10 CFU/mL

6A 19 1 119-19 <10 CFU/mL

6B 19 1 119-19 <10 CFU/mL

6C 19 1 119-19 <10 CFU/mL

6D 19 1 119-19 <10 CFU/mL

7A 19 1 120-19 <10 CFU/mL

7B 19 1 120-19 <10 CFU/mL

7C 19 1 120-19 30,000 CFU/mL

7D 19 1 120-19 <10 CFU/mL

Robert J Dole VA Medical Center, December 10, 2024 - 4 of 4

Testing Methodology

The samples referenced within this report have been processed in accordance with procedures outlined in Standard Methods 9215C (spread plate method) and SOP-034 (Characterization of Water Samples by Heterotrophic Plate Count).

--This report shall not be reproduced except in full and with the permission of the analyzing laboratory. Data contained within this report relates only to the samples described above. The HGS Analytical Laboratory is ELAP certified in compliance with the New York State Department of Health (NYSDOH) and with the Florida Administrative Code 64E-1 for the examination of environmental samples in the following categories: drinking water, microbiology; non-potable water, microbiology.