F108--36C25525Q0143_1 | Legionella Water Testing Services | Wichita VAMC
Solicitation number
36C25525Q0143
Issued by

About this file

This document is a Legionella water testing report for the Robert J. Dole VA Medical Center in Wichita, Kansas, dated December 10, 2024. The report details water sample testing results from various sinks and an ice machine across two floors of Building 1, conducted in compliance with VHA Directive 1061 for preventing healthcare-associated Legionella disease. Of the 20 water samples collected, four tested positive for Legionella pneumophila serogroup 1 at concentrations ranging from 0.4 to 1.6 CFU/mL, specifically in cold water sink samples from rooms 266-1, 264-1, and 327-1.

The testing was performed by HGS Analytical Laboratory, following ISO 11731-2017 and CDC environmental sampling procedures, with a minimum detection limit of 0.4 CFU/mL. The report includes a detailed flow chart for interpreting routine quarterly environmental water testing, which provides guidance on required actions based on Legionella detection. The laboratory is ELAP certified and complies with New York State Department of Health and Florida Administrative Code standards for drinking and non-potable water microbiology testing.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Robert J Dole VA Medical Center, December 10, 2024 -

HGS Analytical 1709 Hillyer Robinson Industrial Parkway (E) Oxford, Alabama 36203 T: (256) 212-0134 | F: (256) 236-2979 lab@hgsengineeringinc.com | hgslab.com

ELAP Lab ID: 12125 | NELAC Lab ID: E871141 | EPA Lab ID: AL01167

David A. Miller Robert J Dole VA Medical Center 5500 E Kellogg Wichita, KS 67218 (316)-685-2221 Ext 53729 David.Miller7@va.gov

December 26, 2024

Subject: Robert J Dole VA Medical Center, Q1 FY2025 Legionella Results

Dear Mr. Miller, In accordance with the VHA Directive 1061: Prevention of Healthcare-Associated Legionella Disease and Scald Injury from Potable Water Distribution Systems, samples submitted from your facility were tested for the presence of various Legionella species, including Legionella pneumophila. The following water quality parameters were also measured at the time of collection: pH, temperature, and residual biocide.

Sample analysis was performed by the HGS Analytical Laboratory at a minimum detection limit of 0.4 CFU/mL.

HGS Analytical 1709 Hillyer Robinson Industrial Parkway (E) Oxford, Alabama 36203 T: (256) 212-0134 | F: (256) 236-2979 lab@hgsengineeringinc.com | hgslab.com

ELAP Lab ID: 12125 | NELAC Lab ID: E871141 | EPA Lab ID: AL01167

Summary Flow Chart for Interpretation of Routine Quarterly Environmental Water Testing

HGS Analytical 1709 Hillyer Robinson Industrial Parkway (E) Oxford, Alabama 36203 T: (256) 212-0134 | F: (256) 236-2979 lab@hgsengineeringinc.com | hgslab.com

ELAP Lab ID: 12125 | NELAC Lab ID: E871141 | EPA Lab ID: AL01167

David A. Miller Robert J Dole VA Medical Center 5500 E Kellogg Wichita, KS 67218 (316)-685-2221 Ext 53729 David.Miller7@va.gov

Collection Date: 12/10/2024 Date of Arrival: 12/12/2024

Date of Receipt: 12/12/2024 Date of Processing: 12/12/2024 Date of Reporting: 12/26/2024

Detailed Report of Legionella Detection, Enumeration, and Serotyping

Bottle ID Building Floor Room Sample Source

Sample Type Results

1 1 2 274-1 Sink Hot No Legionella Detected

2 1 2 273-1 Sink Hot No Legionella Detected

3 1 2 278-1 Sink Hot No Legionella Detected

4 1 2 266-1

Sink Cold Legionella pneumophila, serogroup 1 (0.8 CFU/mL)

5 1 2 264-1

Sink Cold Legionella pneumophila, serogroup 1 (1.6 CFU/mL)

6 1 2 229-1 Ice Machine Cold No Legionella Detected

7 1 2 204-1 Sink Hot No Legionella Detected

8 1 2 218-1 Sink Cold No Legionella Detected

9 1 2 240-1 Sink Hot No Legionella Detected

10 1 2 238-1 Sink Cold No Legionella Detected

11 1 3 309-1 Sink Hot No Legionella Detected

12 1 3 319-1 Sink Hot No Legionella Detected

13 1 3 324-1 Sink Hot No Legionella Detected

14 1 3 327-1

Sink Cold Legionella pneumophila, serogroup 1 (0.4 CFU/mL)

15 1 3 356-1 Sink Cold No Legionella Detected

16 1 3 357A-1 Sink Hot No Legionella Detected

17 1 3 368-1 Sink Cold No Legionella Detected

18 1 3 369A-1 Sink Hot No Legionella Detected

19 1 3 360-1 Sink Cold No Legionella Detected

20 1 3 366-1 Sink Hot No Legionella Detected

Testing Methodology

Samples are processed following procedures included within ISO 11731-2017: Detection and Enumeration of Legionella and the CDC: Procedures for the Recovery of Legionella from the Environment.

This report shall not be reproduced except in full and with the permission of the analyzing laboratory. Data contained within this report relates only to the samples described above. The HGS Analytical Laboratory is ELAP certified in compliance with the New York State Department of Health (NYSDOH) and with the Florida Administrative Code 64E-1 for the examination of environmental samples in the following categories: drinking water, microbiology; non-potable water, microbiology.