S05 Amendment 0001 Attachment 04-MixValve.pdf
PDF 627 KB Posted
- Solicitation number
- 36C25523R0084
About this file
This document contains technical specifications for a digital mixing center and recirculation control system, along with details of a related federal contract opportunity to construct a primary care and women's health building.
The digital mixing center is model DMC40BS and features BrainScan hot water monitoring control for accurate temperature control without a throttling valve or temperature activated pump. Operational specifications include +/-2 degree water temperature control during demand and idle periods, a 2 degree minimum temperature differential, automatic shutoff under certain failure conditions, and a programmable setpoint range of 81 to 158 degrees Fahrenheit. Technical specifications note polymer electronics and stainless steel construction, ASSE 1017 and other certifications, and connectivity options including BrainScan, Modbus, and LCD display interfaces. Dimensions and pressure drop data are provided for recirculation system sizing.
The related federal contract opportunity is solicitation number 36C25523R0084 from the Department of Veterans Affairs for construction of a primary care and women's health building at project number 657-503. No further details on required products, response dates, or other contract terms are provided.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
All dimensions and weights are approximate. Use certified print for exact dimensions. Design and materials are subject to change without notice.All dimensions and weights are approximate. Use certified print for exact dimensions. Design and materials are subject to change without notice.
Armstrong Hot Water Group, 221 Armstrong Blvd., Three Rivers, MI 49093 – USA Phone: 269-279-3602, Fax: 269-279-3130 armstronginternational.com
Armstrong Hot Water Group, 221 Armstrong Blvd., Three Rivers, MI 49093 – USA Phone: 269-279-3602, Fax: 269-279-3130 armstronginternational.com
Water Temperature Control - Recirculation Systems Digital The Brain® Model DMC40BS DMC40BS is a fully Digital Mixing Center (DMC), with BrainScan® - hot water monitoring control module, designed specifically to be the primary water temperature controller in a continuously pumped circulating hot water system.
Digital technology provides enhanced water temperature control accuracy which resists zero system demand “Temperature Creep” without the use of a manual throttling valve or a temperature activated pump shut-off device (aquastat).
Operational Specifications (DRV40)
• +/-2°F water temperature control at points of use 25’ downstream during demand
• +/-2°F water temperature control at the DRV during zero system demand “idling” periods
• 2°F minimum valve inlet to outlet temperature requirement
(system recirculation temperature loss)
• Automatic shutoff of hot water flow upon cold water inlet supply failure
• Automatic shutoff of hot water flow in the event of a power failure
• Programmable set point range of 81-158°F (27-70°C)
• Programmable thermal disinfection mode
• Programmable 1st level hi/lo temp alarm display
• Programmable temperature error level for safety shutdown
Technical Specifications (DRV40)
• 100-240 V AC
• Polymer Electronics Enclosure
• Stainless Steel Valve Construction
• Complete Assembly Lead Free Compliant
• Maximum inlet HW supply temperature 185°F (85°C)
• Minimum Circulation Flow – 5 GPM/19 LPM
• Minimum System Draw Off - 0
• ASSE 1017, CSA B125 and CE Certified
• Operational water pressure of 10-150 psig
• Display in °C or °F
• Shipping weight 334 lbs (151.5 kg)
Connectivity (DRV40) SPCO Relay Outputs – Relay which is energized during operation.
LCD Display – Provides information on set point, delivered temperature, error codes and alert conditions.
RS485 Serial Port – Connects the DRV to either BrainScan or Modbus.
BrainScan® – BAS interface for Modbus, Bacnet™ or LonWorks™ plus operates as a web server.
Modbus – DRV can be configured to communicate directly with Building Automation Systems (BAS) using Modbus protocols.
For a submittal drawing, refer to D40806.
Recirculation Systems - Digital (gpm)
Model Pressure Drop (psi)
Minimum System Draw-Off Maximum Flow @7.5 ft/sec. CV5 10 15 20
DMC40BS 48 70 85 98 0 41 22
39.0
45.0
59.0
DRV40
SERVICE BY-PASS
(NORMALLY
CLOSED)
PRESSURE GAUGE
THERMOMETER
BALL VALVE
STRAINER
SPRING
CHECK VALVE
CHECK VALVE
BRAINSCAN
2.5
4.5
13.2
14.4
7.8
4.8
RETURN
TO HEATER
1 SWEAT
HOT WATER
INLET
1-1/2 SWEAT
MIXED WATER
OUTLET
1-1/2 SWEAT
COLD WATER
INLET
1-1/2 SWEAT
RECIRC
RETURN
1 SWEAT
11.9
45.1
NOTE:
ALL VALVES AND FITTINGS IN THIS ASSEMBLY CONTAIN LESS THAN 0.25% LEAD BY WEIGHTED AVERAGE
D40806
SHEET 1 OF 2
DMC40BS
04/11/2012Jon Singer
REV DWG.
NAME DATE
DRAWN MATERIAL
TOLERANCES UNLESS
OTHERWISE SPECIFIED
A
ARMSTRONG INTERNATIONAL
FRACTIONAL 1/64
ANGULAR: 2
IN. MM
DECIMAL .XXXX .0005 -----
.XXX .005 .010
.XX .015 .10
.X ---------- .3
Copyright C 2010 ARMSTRONG INTERNATIONAL, INC.
CN32171RELEASED
DO NOT SCALE DRAWING
DIMENSIONING
ENGLISH [mm]
File details come from the government source that posted it. Updated .