This solicitation is for a project to replace 108 obsolete fan coil units in Building 1 at the Jefferson Barracks Division of the VA Saint Louis Health Care System. The project scope includes demolition, civil, mechanical, plumbing, and electrical work to replace all fan coil units in the building, with the potential to remove up to 24 units from the project scope through bid deducts. Offerors are also to provide alternate control system bids as specified. The Department of Veterans Affairs Veterans Health Administration VISN 15 is the contracting agency.
36C25520R0036 657-19-108JB - BID DOCUMENTS - 2 of 2.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25520R0036-0004000.docx | DOCX document | |
| 36C25520R0036-0003000.docx | DOCX document | |
| 36C25520R0036-0002000.docx | DOCX document | |
| 36C25520R0036-0001000.docx | DOCX document | |
| 36C25520R0036-004.pdf | ||
| 36C25520R0036-003.pdf | ||
| 36C25520R0036-002.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T
T T
12345791012141718192021222324
R.1
R.3
S
T
U
V
V.1
V.2
V.3
R.4
T.1
T.2
U.1
FCU-B9
300 CFM
FCU-B26
FCU-B30
FCU-B32
FCU-B23
300 CFM
FCU-B24
300 CFM
FCU-B25
300 CFM
FCU-B27
FCU-B28
FCU-B29
300 CFM
FCU-B31
10"x8"
C H
R
C H
R
C H
S
5" CHS
2" CHR
3" CHS 1" D
5" CHR 2" CHR 3" CHS 1" D
5" CHR
2" CHS 1" D
CONTINUES ON
CENTRAL PLAN
HAC
GC09
D.W.
E3
CHASE
CH-C-1
DUPLICATION
GE09A
OFFICE
GE10A
STORAGE
GE10
OI&T
GE11
STORAGE
GE12
OI&T
GE13
CORRIDOR
H002
STORAGE
GE16
CORRIDOR
H003
RECEIVING
GE17
CORRIDOR
H004
OFFICE
GE20
OFFICE
GE21
TOILET
GE22
TOILET
GE23
HAC
GE24
MECH. RM.
GE26
STEAM RM.
GE28
CORRIDOR
GE31
CORRIDOR
H005
STORAGE
GE19
PREP. RM.
GE32
DECONTAMINATION
AREA
GE29
STORAGE
GE18
STORAGE
GE18A
STORAGE
GE18B
ELEVATOR #2
E2
HAC
GE34
HAC
GE35
CORRIDOR
H001
STORAGE
GE01
STAIRWELL #1
S001
VEST.
GE02
TOILET
GE05
STORAGE
GE04
STORAGE
GE03
UTILITY RM.
GE06
STORAGE
GE07
MAIL RM.
GE09
LINEN CHUTE
GE15
1 1/4" LPR
1 1/4" LPS
1 1/4" LPS
1 1/4" LPR
1 1/4" LPR
1 1/4" LPS
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:3
A
M
01-MP-103
MECHANICAL PIPING FLOOR PLAN -
EAST - 00
27 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - EAST - 00
GENERAL NOTES
KEY NOTES
NOT USED.1
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT,
STEAM, CHS, AND CHR CONNECTION SIZES.
Plan North True North
3 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 2. IF
SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
rwwhe Image
T
T
TTT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
A
A.1
A.2
A.3
B
C
C.1
D
D.1
D.2
1 2 3 4 5 6 7 9 10 11 12 13 14 15 17 18 19 20 21 22 23 2410.14.7
C.2
B.2
B.1
A.4
FCU-1-1
926 CFM
FCU-1-2
500 CFM
FCU-1-5
500 CFM
FCU-1-6
500 CFM
FCU-1-8
500 CFM
FCU-1-14
208 CFM
FCU-1-16
500 CFM
FCU-1-18
500 CFM
FCU-1-21
500 CFM
FCU-1-23A
500 CFM
FCU-1-22
208 CFM
FCU-1-20
208 CFM
FCU-1-19B
208 CFM
FCU-1-19A
208 CFM
FCU-1-17
208 CFM
FCU-1-15
208 CFM
FCU-1-13
208 CFM
FCU-1-12
FCU-1-10
208 CFM
FCU-1-9
208 CFM
FCU-1-7
FCU-1-3
208 CFMFCU-1-3A
208 CFM
FCU-1-11
FCU-1-4
208 CFM
16"x30"
2 1/2" CHR
1 1/2" CHS
1" D1" D
1 1/2" CHS2" CHR2 1/2" CHS1 1/2" CHR
CONTINUES ON
CENTRAL PLAN
1" D
WAITING RM.
1W27
STORAGE
1W23
HALLWAY
1W24
TOILET
1W25
OFFICE
1W22
ALCOVE
H117A
OFFICE
1W22A
OFFICE
1W21
OFFICE
1W20
OFFICE
1W18A
OFFICE
1W18
OFFICE
1W17
OFFICE
1W16
CORRIDOR
H118
OFFICE
1E37A
OFFICE
1W14
OXYGEN
STORAGE
1W13A
CORRIDOR
1W13
STAIRWELL NO. 4
S104
OFFICE
1W12
OFFICE
1W11B
ALCOVE
H113A
OFFICE
1W11A
OFFICE
1W10
OFFICE
1W09
CONFERENCE
RM.
1W08B
WAITING RM.
1W08A
VEST.
1W08
TOILET
1W07A
OFFICE
1W07
OFFICE
1W06
TOILET
1W05
VEST.
1W06A
CLOSET
1W06B
OFFICE
1W04
OFFICE
1W03
MECH. RM.
1W02
OFFICE
1W01
E L
E V
A T
O R
N O
E
CORRIDOR
H116
STAIRWELL NO. 3
S103
TOILET
1W31
CHECK-IN
1W30A
OFFICE
1W30
OFFICE
1W29
C O
R R
ID
O
R
W
A
TOILET
1W28
CORRIDOR
H117
CORRIDOR
H119
EXAM
C105
EXAM
C106A
FCU-1-23B
500 CFM
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:3
A
M
01-MP-111
MECHANICAL PIPING FLOOR PLAN -
WEST - 01
28 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - WEST - 01
1 Plan North
True North
GENERAL NOTES
KEY NOTES
PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.
VERIFY CONNECTION SIZE.
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
2 2
3 MODIFY LAY IN CEILING TO ACCOMMODATE FAN COIL UNIT
ACCESS PANEL. NO OA DUCT CONNECTION REQUIRED FOR FCU.
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
T
RAD
RAD
8.1
E.1 F G H H.2 J.1 J.2 L M N 0 PE G.1 H.1 J K K.2 Q
10.1
N.1
FCU-1-25
700 CFM
FCU-1-26
208 CFM
FCU-1-27
208 CFM
16"x30"
1 1/2" CHS
2 1/2" CHR
1" D
C O
N T
IN
U
E S
O N
E A
S T
P
LA
N
C O
N T
IN
U
E S
O N
W E
S T
P
LA
N
CORRIDOR
H115
EXAM
C106
CHECK-IN
C108A
CORRIDOR
H114
CHECK-IN
C108
WAITING RM.
H115A
CHASE
CH-C-3
VEST.
C104
OFFICE
C104A EXAM
C102F
TOILET
C102G
STORAGE
C102H
TREAT. RM.
C102A
CONTROL
C102E
TOILET
C103
CLOSET
C104B
CHEMICAL
STORAGE
C102
WORK RM.
C102C
BREAK RM.
C102B
CORRIDOR
H111
VA POLICE
C101
ARMORY
C102I
STAIRWELL NO. 2
S102
VEST.
H109
CLEAN UTILITY
C102J
STORAGE
C129
WAITING RM.
C131
TOILET, MALE
C127
TOILET, FEMALE
C126
OFFICE
C125
OFFICE
C122A
OFFICE
C122
TOILET
C127
HAC
C121
CORRIDOR
H107
CHASE
CH-C-5
M A
IL
R
M
C C
AGENT CASHIER
C119B
CLOSET
C126A
OFFICE
C115B
OFFICE
C115A
OFFICE
C115
C O
R R
ID
O
R
H
OFFICE
C117
OFFICE
C116
OFFICE
C110
OFFICE
C112
OFFICE
C114
OFFICE
C113
OFFICE
C111
COPY RM.
C109
UTILITY
E4
VACANT
C123C
D.W.
E3
LOBBY
C124
CORRIDOR
H106
HALLWAY
C123
EXAM
C105
EXAM
C106A
RECEPTION
C118
HOLDING
C102D
CORRIDOR
H113
WAITING RM.
C128
V A
C A
N T
C
AGENT CASHIER
C119
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:3
A
M
01-MP-112
MECHANICAL PIPING FLOOR PLAN -
CENTRAL - 01
29 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - CENTRAL - 01
P la n N or th
T ru e N or th
GENERAL NOTES
KEY NOTES
PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.
VERIFY CONNECTION SIZE.
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
3 PROVIDE JOHNSON CONTROLS METASYS NETWORK
AUTOMTION ENGINE (OR APPROVED COMPATIBLE EXPANSION)
FOR EXPANSION TO THE BUILDING DDC SYSTEM.
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
DN
T
T
T
T T
12345791012141718192021222324
R.1
R.2
R.3
S
T
U
V
V.1
V.2
V.3
R.4
T.1
T.2
U.1
FCU-1-27
208 CFM
FCU-1-41
300 CFM
FCU-1-42
FCU-1-43
FCU-1-44
FCU-1-45
FCU-1-46 FCU-1-47
FCU-1-48
FCU-1-49 FCU-1-50
FCU-1-51
FCU-1-52
FCU-1-40
208 CFM
FCU-1-38
300 CFM
FCU-1-39
352 CFM
FCU-1-29
FCU-1-28
FCU-1-30
FCU-1-31 FCU-1-32
FCU-1-33
FCU-1-34
FCU-1-35
FCU-1-36
FCU-1-37
30"x10"
2" CHR
2 1/2" CHS1" D
CONTINUES ON
CENTRAL PLAN
STAIRWELL NO. 1
S101
CORRIDOR
H104
ELEVATOR NO. 2
E2
BREAK RM.
1E40A
LAB.
1E40
VACANT
C123C
D.W.
E3
LOBBY
C124
CORRIDOR
H106
HALLWAY
C123
WAITING RM.
1E01
BREAK RM.
1E02
OFFICE
1E04
M E
C H
R
M
E
OFFICE
1E07
OFFICE
1E08
OFFICE
1E09CONFERENCE
RM.
1E11
WAITING RM.
1E11A
OFFICE
1E12
OFFICE
1E14
CORRIDOR
H101
TOILET, STAFF
1E16
INJECTIONS
1E17
OFFICE
1E17A
MENTAL HEALTH
CHECK-IN
1E18
OFFICE
1E19
CORRIDOR
H102
CORRIDOR
H103A
C O
R R
ID
O
R
E
K
ELEC. CLOSET
1E15H
ELEC. CLOSET
1E15J
OFFICE
1E15A
OFFICE
1E15B
OFFICE
1E15C
CONFERENCE
RM.
1E16D
OFFICE
1E15E
OFFICE
1E15F
OFFICE
1E15G
OFFICE
1E125
STORAGE
1E22
STORAGE
1E24
HAC
1E23
OFFICE
1E25
X-RAY
1E27
CONTROL RM.
1E28
TOILET
1E26
CR
1E29
READING RM.
1E32
TOILET
1E30
CONTROL RM.
1E31
UNDER
CONSTRUCTION
1E33
UNDER
CONSTRUCTION
1E34
UNDER
CONSTRUCTION
1E35
UNDER
CONSTRUCTION
1E36
UNDER
CONSTRUCTION
1E37
WAITING RM.
1E38
CORRIDOR
H105
LAB.
1E39
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:4
A
M
01-MP-113
MECHANICAL PIPING FLOOR PLAN -
EAST - 01
30 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - EAST - 01
1 1
GENERAL NOTES
KEY NOTES
PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.
VERIFY CONNECTION SIZE.
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
Plan North True North
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
TTTT
TT
T
TT
TT
TT
T TT
T
T T
D N
U P
D N
U P
RAD
RAD
A
A.1
A.2
A.3
B
C
C.1
D
D.1
D.2
1 2 3 4 5 6 7 8 8.1 9 10 11 12 13 14 15 17 18 19 20 21 22 23 2410.14.7
C.2
B.2
B.1
A.4
FCU-2-1
FCU-2-2
FCU-2-3
208 CFM
FCU-2-4
208 CFM
FCU-2-5
208 CFM
FCU-2-6
FCU-2-7
208 CFM
FCU-2-8
FCU-2-9
500 CFM
FCU-2-10
208 CFM
FCU-2-11
208 CFM
FCU-2-12
FCU-2-13
208 CFM
FCU-2-70
FCU-2-14
208 CFM
FCU-2-15
300 CFM
FCU-2-16
300 CFM
FCU-2-17
300 CFM
FCU-2-18
300 CFM
FCU-2-19
500 CFM
FCU-2-20
500 CFM
FCU-2-21
500 CFM
FCU-2-22
500 CFM
FCU-2-23
500 CFM
FCU-2-24
500 CFM
FCU-2-33
208 CFM
18"x36"
2" CHR2 1/2" CHS1" D
2 1/2" CHR
1 1/2" CHS1" D
1 1/2" CHR2 1/2" CHS1" D
CONTINUES ON
CENTRAL PLAN
LAB.
2C19 CORRIDOR
H206
EXAM
2W13
TOILET
2W14
EXAM
2W15
EXAM
2W16
TOILET
2W17
WAITING RM.
2W18
SICK WAITING
RM.
2W19
TOILET, STAFF
2W20
CHASE
CH-W-1
OFFICE
2W21
PATIENT NOUR.
2W22
OFFICE
2W22A
OFFICE
2W22C
TOILET
2W23
OFFICE
2W24
VACANT
2W25
OFFICE
2W26
EXAM
2W27
EXAM
2W28
OFFICE
2W28A
TRIAGE
2W28B
OFFICE
2W28C
EXAM
2W29
STORAGE
2W29A
EXAM
2W29B
STORAGE
SW29C
CLINICAL
PHARMACY
2W29D
TOILET, STAFF
2W29F
VEST.
2W29E
OFFICE
2W30
EXAM
2W32
OFFICE
2W33
WAITING RM.
2W35
TOILET
2W34
HAC
2W36
CHASE
CH-W-5
STAIRWELL NO. 3
S203
ELEVATOR NO. 1
E1
CORRIDOR
H209
RECEPTION
2W01
CORRIDOR
H208
FAX RM.
2W02
TOILET
2W03
MED. PREP.
2W04
STORAGE
2W05
BREAK RM.
2W06
EXAM
2W07
TOILET
2W08
EXAM
2W09
EXAM
2W10
TOILET
2W11
EXAM
2W12
STAIRWELL NO. 4
S204
CORRIDOR
H207
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:4
A
M
01-MP-121
MECHANICAL PIPING FLOOR PLAN -
WEST - 02
31 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - WEST - 02
1 Plan North
True North
1 1
GENERAL NOTES
KEY NOTES
PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.
VERIFY CONNECTION SIZE.
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
2 2
2 2 2 2
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
T
T
T T
T T
T T T
T
ROOF BELOW
ROOF BELOW
UP
DN
UP
UP
8.1
E.1 F G H H.2 J.1 J.2 L M N 0 PE G.1 H.1 J K K.2 Q
10.1
N.1
FCU-2-25
500 CFM
FCU-2-26
FCU-2-27
208 CFM
FCU-2-28
FCU-2-29
208 CFM
FCU-2-30 FCU-2-31
FCU-2-32
208 CFM
FCU-2-34
300 CFM
FCU-2-35
300 CFM
FCU-2-37
500 CFM
FCU-2-38
500 CFM
FCU-2-39
FCU-2-40
1000 CFM
FCU-2-41
500 CFM
FCU-2-43
500 CFM
FCU-2-44
300 CFM
FCU-2-36
FCU-2-69
18"x36" 12"x30"
2 1/2" CHR2" CHS1" D
2 1/2" CHR
1 1/2" CHS
1" D
C O
N T
IN
U
E S
O N
E A
S T
P
LA
N
C O
N T
IN
U
E S
O N
W E
S T
P
LA
N ELEC RM.
2C18
TOILET, MALE
2C16
EXAM
2C15
EXAM
2C14
NURSE STATION
2C13
OPTICAL SHOP
2C12
EXAM
2C11
STORAGE
2C10A
LAB.
2C10
SERVER RM.
2C10B
UNDER
CONSTRUCTION
2C09
LAB.
2C08
LAB.
2C07
CORRIDOR
H204
OFFICE
2C04
VETERAN
HEALTH
EDUCATION
2C03
LOW VISION
THERAPY
2C02
OFFICE
2C01A
RECEPTION
2C01B
LOW VISION
CLINIC
2C01
OFFICE
2C29
STAIRWELL NO. 2
S202
HAC
2C28
TOILET, FEMALE
2C27
CORRIDOR
H205EXAM
2C25
LAB.
2C23
LAB.
2C20
STORAGE
2C21
TOILET
2C24
STORAGE
2C22
OFFICE
2C05
HAC
2C06
D.W.
E3
LAB.
2C19
CORRIDOR
H206
KITCHENETTE
2C17
FCU-2-42
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:4
A
M
01-MP-122
MECHANICAL PIPING FLOOR PLAN -
CENTRAL - 02
32 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - CENTRAL - 02
P la n N or th
T ru e N or th
GENERAL NOTES
KEY NOTES
PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.
VERIFY CONNECTION SIZE.
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
2 2
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
T
T
T
T
T T
T
T T
T T
T
T
T
T
T
T
D N
U P
12345791012141718192021222324
R.1
R.2
R.3
S
T
U
V
V.1
V.2
V.3
R.4
T.1
T.2
U.1
FCU-2-45
500 CFM
FCU-2-46
500 CFM
FCU-2-48
300 CFM
FCU-2-47
500 CFM
FCU-2-49
500 CFM FCU-2-51
300 CFM
FCU-2-52
208 CFM
FCU-2-50
300 CFM
FCU-2-53
800 CFM
FCU-2-54
208 CFM
FCU-2-55
208 CFM
FCU-2-56
208 CFM
FCU-2-57
500 CFM
FCU-2-58
500 CFM
FCU-2-59
208 CFM
FCU-2-60
500 CFM
FCU-2-61
500 CFM
FCU-2-62
500 CFM
FCU-2-63
FCU-2-64
FCU-2-44
300 CFM
2 1/2" CHR1 1/2" CHS1" D 1" D 2 1/2" CHS 2" CHR
1" D 2 1/2" CHS1 1/2" CHR
30"x14"
CONTINUES ON
CENTRAL PLAN
OFFICE
2C05
HAC
2C06
D.W.
E3
OFFICE
2E07A
TOILET
2E07C
OFFICE
2E08
OFFICE
2E09
TOILET
2E10
TELERETINAL
IMAGING
2E11
TOILET
2E12A
OFFICE
2E12
CHASE
CH-E-9
TREAT. RM.
2E13
LACTATION RM.
2E15
SOILED
LINEN
CHUTE
2E15A
EXAM
2E16
STORAGE
2E16A
KITCHENETTE
2E17
CHASE
CH-E-7
VITAL SIGN RM.
2E19
CHASE
CH-E-1
EXAM
2E20
EXAM
2E21
TOILET
2E22A
OFFICE
2E22
OFFICE
2E23
TOILET
2E24
EXAM
2E25
CORRIDOR
H203
EXAM
2E25A
TOILET
2E25B
EXAM
2E26
WAITING RM.
2E27
TOILET
2E28
EXAM
2E29
OXYGEN
STORAGE
2E30
TOILET, STAFF
2E31
ELEVATOR NO. 2
E2
C O
R R
ID
O
R
H
RECEPTION
2E18
STAIRWELL NO. 1
S201
STORAGE
2E03
STORAGE
2E02
ELEC. RM.
2E04
TOILET
2E05A
HAC
2E01
CORRIDOR
H201
OFFICE
2E06
FAX RM.
2E05B
TOILET
2E06A
TOILET
2E07B
OFFICE
2E07
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:4
A
M
01-MP-123
MECHANICAL PIPING FLOOR PLAN -
EAST - 02
33 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - EAST - 02
1 1
GENERAL NOTES
KEY NOTES
PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.
VERIFY CONNECTION SIZE.
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
2 2
Plan North True North
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
T
TTT
T
T
T
TT
T
T
T
T
T
TT
T
T
T
D N
D N
A
A.1
A.2
A.3
B
C
C.1
D
D.1
D.2
1 2 3 4 5 6 7 8 8.1 9 10 11 12 13 14 15 17 18 19 20 21 22 23 2410.14.7
C.2
B.2
B.1
A.4
FCU-3-1
300 CFM
FCU-3-2
300 CFM
FCU-3-3
700 CFM
FCU-3-4
352 CFM
FCU-3-5
208 CFM
FCU-3-6
208 CFM
FCU-3-7
700 CFM
FCU-3-8
208 CFM
FCU-3-9
352 CFM
FCU-3-10
700 CFM
FCU-3-11
700 CFM
FCU-3-12
700 CFM
FCU-3-14
208 CFM
FCU-3-13
700 CFM
FCU-3-15
700 CFM
FCU-3-16
208 CFM
FCU-3-17
208 CFM
FCU-3-18
700 CFM
FCU-3-19
700 CFM
FCU-3-20
700 CFM
18"x42"
2 1/2" CHR1 1/2" CHS1" D
2 1/2" CHR2" CHS1" D
1 1/4" CHR
2 1/2" CHS
1" D
CONTINUES ON
CENTRAL PLAN
OFFICE
H309
OFFICE
H306
STAIRWELL NO. 4
S304
FILE RM.
W310
OFFICE
W311
OFFICE
W312
TOILET, FEMALE
W313
CHASE
CH-W-1
MECH. RM.
W314
TELEPHONE RM.
W315
CHASE
CH-C-10
RECEPTION
W316
ELEVATOR NO. 1
E1
CHASE
CH-W-2
CORRIDOR
H305
LOBBY
W318
OFFICE
H307
STAIRWELL NO. 3
S303
CHASE
CH-W-5
TOILET, MALE
W301
STAFF LOUNGE
W302
MAIL RM.
W303
OFFICE
W304
OFFICE
W305
COPY RM.
W306
OFFICE
W307
OFFICE
W309
CONFERENCE
RM.
W308
OFFICE
H308
FCU-3-12A
208 CFM
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:5
A
M
01-MP-131
MECHANICAL PIPING FLOOR PLAN -
WEST - 03
34 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - WEST - 03
1 Plan North
True North
1 1
1 1
1 1
GENERAL NOTES
KEY NOTES
PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.
VERIFY CONNECTION SIZE.
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
4 4 4 4 4
4 4 2 2
3 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 2. IF
SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.
4 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 3. IF
SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.
3 3
2 2 2 2 2
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
UP
8.1
E.1 F G H H.2 J.1 J.2 L M N 0 PE G.1 H.1 J K K.2 Q
10.1
N.1
FCU-3-21
FCU-3-22
FCU-3-23
FCU-3-25
FCU-3-26
FCU-3-27
FCU-3-28
FCU-3-29
FCU-3-30
FCU-3-31
FCU-3-32
20"x30"
18"x42"
1" D 3" CHS
2" CHR
1" D 2" CHS
3" CHR
1" D 1" CHS
3" CHR
C O
N T
IN
U
E S
O N
E A
S T
P
LA
N
C O
N T
IN
U
E S
O N
W E
S T
P
LA
N
MECH. RM.
3C23
LAB.
3C21
LAB.
3C18
LAB.
3C17
LAB.
3C15
LAB.
3C13
LAB.
3C12
OFFICE
3C11
LAB.
3C08
LAB.
3C27
OFFICE
C307
OFFICE
C305
OFFICE
C304
OFFICE
C306
OFFICE
C303
OFFICE
C302
LAB.
3C04
MECH. RM.
3C06
PREP. RM.
3C29
TOILET
C307A
PREP. RM.
3C28
STAIRWELL NO. 2
S302
CHASE
CH-C-5
STORAGE
C301
DARK RM.
3C06A
CORRIDOR
H304
CORRIDOR
H303
LAB.
3C09
CHASE
CH-C-4
CHASE
CH-C-3
STERILIZATION
RM.
3C14
STERILIZATION
RM.
3C16HAC
3C20
LAB.
3C07
D.W.
E3
CHASE
CH-C-1
CHASE
CH-C-10
CHASE
CH-W-2
CORRIDOR
H305
FCU-3-24
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:5
A
M
01-MP-132
MECHANICAL PIPING FLOOR PLAN -
CENTRAL - 03
35 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - CENTRAL - 03
P la n N or th
T ru e N or th
GENERAL NOTES
KEY NOTES
NOT USED.1
2 NOT USED.
3 PROVIDE JOHNSON CONTROLS METASYS NETWORK
AUTOMATION ENGINE (OR APPROVED COMPATIBLE EXPANSION)
FOR EXPANSION TO THE BUILDING DDC SYSTEM.
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
U P
D N
12345791012141718192021222324
R.1
R.3
S
T
U
V
V.1
V.2
V.3
R.4
T.1
T.2
U.1
FCU-3-34
FCU-3-35
FCU-3-36
FCU-3-39
FCU-3-37
FCU-3-38 FCU-3-40
FCU-3-41
FCU-3-42
FCU-3-43
FCU-3-44
FCU-3-45
FCU-3-46
208 CFM
30"x18"
1" D
1 1/2" CHS
4" CHR
1" D
2 1/2" CHS
3" CHR
3" CHS
CONTINUES ON
CENTRAL PLAN
LAB.
3C07 D.W.
E3
CHASE
CH-C-1
CLOTHING RM.
3E08
LAB.
3E09
OFFICE
3E10
MECH. RM.
3E11
STORAGE
3E12A
CHASE
CH-E-7
LAB.
3E12
COLD RM.
3E21A
CHASE
CH-E-9
CHASE
CH-E-10
TOILET, FEMALE
E311
HAC
E312
TOILET, MALE
E310
OFFICE
E309
OFFICE
E308
OFFICE
E307
OFFICE
E306
OFFICE
E305
OFFICE
E304
COMPUTER RM.
E303
STORAGE
E303A
OFFICE, OPEN
E302
OFFICE
E301
BREAK RM.
E313
CHASE
CH-E-1
CORRIDOR
H302
STAIRWELL NO. 1
S301
CORRIDOR
H301
TRAINING RM.
3E07
OFFICE
3E05
OFFICE
3E04A OFFICE
3E04
KITCHEN
3E03
STORAGE
3E02
HAC
3E01
CHASE
CH-E-5
CHASE
CH-E-4
P la n N or th
T ru e N or th
BLDG 1
KEYPLAN
WEST
WING
CENTER
WING
EAST
WING
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:5
A
M
01-MP-133
MECHANICAL PIPING FLOOR PLAN -
EAST - 03
36 53
REPLACE FAN COIL UNITS
BUILDING 1
DD RDT
1/8" = 1'-0"
MECHANICAL PIPING FLOOR PLAN - EAST - 03
GENERAL NOTES
KEY NOTES
NOT USED.1
2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,
AND CHR CONNECTION SIZES.
Plan North True North
3 NOT USED.
4 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 3. IF
SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.
1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL
SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.
2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR
BEFORE PROCEEDING WITH WORK.
3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501
AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT
GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-
OFF VALVE AT CHS/CHR CONNECTIONS.
4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING
INSULATION ABATEMENT REQUIREMENTS.
FAN COIL SEQUENCE OF OPERATION (COOLING ONLY)
1. FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE ECC.
2. MODULATE V-1 TO MAINTAIN SPACE SETPOINT AND FAN SHALL CYCLE W/TEMPERATURE.
3. ALARM IF SPACE TEMPERATURE MOVES OUTSIDE OF RANGES.
ROOM TEMPERATURE
SENSOR, WALL
MOUNTED 48" AFF.
TT
SHARED ARRANGEMENT IF FEASIBLE
PC
CHS
CHR
COOLING COIL
V-1
HS
SST
FAN
RA
FILTER
HEATING COIL
RA
LPR
LPS
V-1
COOLING COIL
CHS
CHR
V-2
FAN
SST
HS
T-1
ROOM TEMPERATURE SENSOR WITH
SPACE ADJUSTABLE WALL MOUNTED
48" AFF.
T
PC
FILTER
FAN COIL SEQUENCE OF OPERATION (NONPATIENT ROOMS)
FAN COIL SHALL OPERATE ON A SCHEDULE AS SET BY ECC. FAN SHALL RUN CONTINUOUSLY
IN OCCUPIED MODE. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE
GENERATED IN THE EVENT THE UNIT FAILS TO RUN BETWEEN THE RANGE OF 70°F - 75°F SPACE
TEMPERATURE BOTH V-1 & V-2 SHALL BE CLOSED. UPON RISE IN TEMPERATURE ABOVE 75°F
V-2 SHALL MODULATE OPEN TO MAINTAIN 75°F. UPON FALL IN TEMPERATURE BELOW 70°F.
HEATING VALVE V-1 SHALL MODULATE TO OPEN TO MAINTAIN 70°F.
TT
CS
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:0
:5
A
M
01-MP-601
MECHANICAL INSTRUMENTATION
SCHEDULE AND DETAIL
37 53
REPLACE FAN COIL UNITS
BUILDING 1
DD MDR
NTS
COOLING ONLY FAN COIL UNIT CONTROLS
NTS
FOUR PIPE FAN COIL UNIT CONTROLS
I/O POINTS LIST BUILDING 1
QUANTITY GRAPHICS REQUIRED DO AO DI AI READ WRITE TREND BACnet OBJECT
FCU
FCU START/STOP 121 X X X HARDWIRED
FCU STATUS 121 X X X HARDWIRED
ROOM TEMPERATURE SENSOR 121 X X X HARDWIRED
ROOM TEMPERATURE SETPOINT 121 X X X HARDWIRED
DISCHARGE AIR TEMPERATURE 121 X X X HARDWIRED
CHILLED WATER CONTROL VALVE 121 X X X HARDWIRED
STEAM CONTROL VALVE 5 X X X HARDWIRED
KEY NOTES
CONTROLS SHALL BE COMPATIBLE WITH JOHNSON CONTROLS
ECC. ALTERNATE 4 ALLOWS FOR SUBSTITUTE BID FOR A
STANDALONE NIAGARA TRIDIUM OR APPROVED EQUAL ECC.
REPLACED FAN COIL UNITS SHALL BE LOCALLY CONTROLLED
BY THERMOSTAT: NO DDC CONTROLS PROVIDED. PROVIDE
ROOM TEMPERATURE ALARM AT EXISTING FACILITY BAS
SYSTEM FOR REPLACED FAN COIL UNITS.
VFD
G
R
A
V
W
WH
T
J
S
HVS
LVS
P T
PB
P
D
DP#__
LP
C
S
H
S
TC
F
F
RX
ES
ML
CR
FIX
J
RRB
WS
WAP
NCT
NCS
R
C
DB
CB
NCM
NWS
F
RX
ES
ML
CR
FIX
J
RRB
WS
OS
A
A
B
A
A
D
J
A
S X
S X
R M
M
N
TTB
R M
S
N
N
T T
C C
W W
B B
A
C
DB
RC
P
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE
OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN, AS REQUIRED.
B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED
EQUIPMENT GROUNDING CONDUCTOR.
C. REUSE EXISTING CIRCUITS AS MUCH AS POSSIBLE. MULTI-GANG BACKBOXES FOR
DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING
DEVICES MUST HAVE DIVIDERS BETWEEN DEVICES.
D. LIGHTING IN THE PATH OF CONSTRUCTION WILL BE REMOVED AND REINSTALLED
WHERE NECESSARY.
E. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR THE LOCATION OF
CEILING AND WALL MOUNTED DEVICES, AS REQUIRED.
F. ALL WIRING SHALL BE (3)#12 THWN/THHN COPPER 3/4C" UNLESS OTHERWISE NOTED.
G. MINIMUM SIZE CONDUIT FOR CONTROL CIRCUITS SHALL BE 1/2".
H. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS.
SEAL REMAINING ANULUS WITH FIRE CAULK.
I. FURNISH ACCESS DOORS FOR INSTALLATION BY GENERAL CONTRACTOR IN WALLS
AND CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED ELECTRICAL BOXES
AND DEVICES.
J. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN FIXTURE PIGTAILS. ARMORED CABLE
(AC) SHALL NOT BE USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED CABLE (AC)
SHALL NOT BE USED WHERE MORE THAN THREE CONDUCTORS
(PHASE/NEUTRAL/GROUND) ARE REQUIRED, WHERE EXPOSED; OR IN LENGTHS
EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.
K. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE CURRENT NATIONAL
ELECTRICAL CODE AND THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING
JURISDICTION.
L. COORDINATE ALL OUTAGES WITH VA COR PER SPECS PRIOR TO WORK BEING DONE.
M. REINSTALL IN SAME OR SIMILAR LOCATION ANY HARDWARE THAT IS TEMPORARILY
DISPLACED DURING DEMOLITION TO RESTORE FUNCTIONALITY.
N. THERMOSTATS WILL EITHER USE PATHWAYS FROM EXISTING THERMOSTATS OR WILL
HAVE CONDUIT INSTALLED IF NEEDED.
O. REPLACEMENT OF J-BOXES, CONTROLS AND CIRCUITS
A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,
CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP
CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE
WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND
REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
B. DISCONNECT AND REMOVE ALL WIRES AND CONDUIT BACK TO THE OVERCURRENT
DEVICE AND RELABEL AS A SPARE.
C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS
PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
D. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABEL IN
JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC
CODE.
E. REPLACE ALL EXISTING MULTI-PHASE BRANCH CIRCUIT BREAKERS WITH HANDLE TIE
BREAKERS ON ALL MULTI-PHASE CIRCUITS.
F. ALL HARDWARE NOT SHOWN FOR DEMOLITION SHALL BE SUSPENDED AND
REINSTALLED TO RETAIN EXISTING FUNCTIONALITY UNLESS OTHERWISE SPECIFIED.
G. LIGHTING IN THE PATH OF CONSTRUCTION WILL BE REMOVED AND REINSTALLED
WHERE NECESSARY.
NEW LINE TYPE.
EXISTING LINE TYPE.
DEMO LINE TYPE.
DEMO HATCH.
ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS
ELECTRICAL SYMBOLS - DIAGRAM
ELECTRICAL SYMBOLS - POWER PLAN
ELECTRICAL SYMBOLS - LIGHTING PLAN
COMMUNICATION SYMBOLS (CONTINUED): ELECTRICAL GENERAL NOTES:
ELECTRICAL GENERAL NOTES - DEMOLITION:
KEY NOTES:
NEW - EXISTING & DEMO LINE TYPES:
COMMUNICATION SYMBOLS:
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT-AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT
WH WATER HEATER
WP WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G OR GND ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IESNA ILLUMINATION ENGINEERING SOCIETY
OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWHM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR NEUTRAL
N
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PA PUBLIC ADDRESS
PB PULL BOX OR PANEL BOARD
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
REQ REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
SCC SHORT CIRCUIT CAPACITY
SES SERVICE ENTRANCE SECTION
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
BRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER
OF CIRCUITS,NEUTRAL, AND SWITCH LEG
CONDUCTORS. ONE SEPARATE GREEN GROUNDING
CONDUCTOR SHALL BE PROVIDED FOR EACH
HOMERUN;NOT SHOWN
WIREWAY
RIGID CONDUIT LINE = RC
DIRECT BURIAL CABLE = DB
POWER DUCT = P
SUBSTATION
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
BUSWAY
FLOOR OUTLET, DATA COMMUNICATION
OUTLET, DATA COMMUNICATION
PUSH BUTTON
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX (MOUNT 18"AFF. UNLESS NOTED
OTHERWISE)
RECEPTACLE, DUPLEX ON EMERGENCY POWER
(MOUNT 18" AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER (MOUNT 18" AFF. UNLESS NOTED
OTHERWISE)
RECEPTACLE, DUPLEX COUNTER HEIGHT
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
RECEPTACLE, SWITCHED DUPLEX
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN
FLEXIBLE CORD. CENTER LINE OF OUTLET: 6'-6" AFF.
(MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS
OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR
AS INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR
TELEPHONE, DATA & RECEPTACLE.
TIME CLOCK
VENTILATOR OR FAN COIL UNIT OUTLET
CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED W/COUPLING (FLUSH
W/FINISHED FLOOR) FOR EXTENSION TO EQUIPMENT AS
DIRECTED.
SWITCH
F = FUSED SWITCH
L = LOCK
M = MANUAL MOTOR STARTING
MP = MOTOR SNAP WITH PILOT LIGHT
(THERMAL TYPE)
PB = PUSH BUTTON STATION
K = KEY OPERATED
LM = LOW VOLTAGE MASTER
MC = MOMENTARY CONTACT
P = WITH PILOT LIGHT
RC = REMOTE CONTROL
X = EXPLOSION PROOF
WP = WEATHER PROOF
OS = INTEGRAL OCCUPANCY SENSOR
LVD = LOW VOLTAGE DIMMER
LV= LOW VOLTAGE
CEILING MOUNTED OCCUPANCY SENSOR,
ARROWS INDICATE COVERAGE.
RECESSED DOWNLIGHT FIXTURE, LETTER
INDICATES TYPE.
LIGHT FIXTURE, RECESSED TROFFER, (2'x2');
LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED TROFFER, (2'x4');
LETTER INDICATES TYPE.
LIGHT FIXTURE, RECESSED TROFFER, (1'x4');
LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED TROFFER,
(2'x4'); LETTER INDICATES TYPE.
LIGHT FIXTURE, SURFACE MOUNTED TROFFER,
(1'x4'); LETTER INDICATES TYPE.
LIGHT FIXTURE, TROFFER EMERGENCY;
LETTER INDICATES TYPE.
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
TRANSFORMER, PLAN
WYE CONNECTION
DUCT, CELL FLOOR HEADER
DUCT, TROLLEY
DUCT, UNDERFLOOR
JUNCTION BOX
EARTH GROUND
JUNCTION BOX
LADDER CABLE
DELTA CONNECTION
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
TRANSFORMER
WYE CONNECTION
PULL BOX
MANHOLE
PRESSURE SWITCH-CLOSE ON
INCREASE
PRESSURE SWITCH-OPEN ON
INCREASE
SWITCH, MULTIPOSITION
SWITCH, NORMALLY CLOSED FLOAT
SWITCH, NORMALLY CLOSED FOOT OPERATED
SWITCH, NORMALLY CLOSED LIMIT
SWITCH, NORMALLY CLOSED TEMPERATURE
ACTIVATED
SWITCH, NORMALLY CLOSED TIME DELAY
SWITCH, NORMALLY OPEN FLOAT
SWITCH, NORMALLY OPEN LIMIT
SWITCH, NORMALLY OPEN TEMPERATURE
ACTIVATED
SWITCH, NORMALLY OPEN TIME DELAY
SWITCH, SINGLE BREAK
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
FUSE WITH RATING
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
MEDIUM-VOLTAGE OIL CIRCUIT BREAKER
MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
FUSIBLE LINK
STARTER, COMBINATION W/DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
VARIABLE FREQUENCY DRIVE
GENERATOR, POWER
BATTERY
CAPACITOR
POTHEAD
STRESS CONE
LIGHTNING ARRESTOR
RECTIFIER, CATHODIC PROTECTION
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
CARD READER
ELECTRIC DOOR STRIKE
MAGNETIC DOOR POSITION SWITCH
VANDAL RESISTANT 1080P DOME IP CAMERA
FOUR SQUARE JUNCTION BOX
MAGNETIC LOCK
REMOTE DOOR RELEASE BUTTON
REQUEST TO EXIT MOTION DETECTOR
CCTV SYSTEM WORKSTATION
DURESS BUTTON
CODE BLUE BUTTON INTEGRATED NURSE CALL SYSTEM
NURSE CALL MASTER CONSOLE
ETHERNET NETWORK SWITCH
WIRELESS ACCESS POINT
DATA BOX
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" CONDUIT
FIBER OPTICS LINE = FO
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" CONDUIT.
RADIO CONDUIT RUN, MINIMUM 3/4" CONDUIT.
TELECOMMUNICATIONS MANHOLE
FLOOR RECEPTACLE, TELEPHONE
OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE
OUTLET DATA ONLY
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND. MTD.
7'-6" AFF UNLESS OTHERWISE NOTED.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6"
AFF UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL MTD. 4'-6" AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK= 4 11/16" MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" AFF
M = MONITOR (CTTV SYSTEM).
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER
TOP UNLESS OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE
INDICATORS AT MASTER STATION) MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
D = DUTY STATION. MTD 5'-0" AFF UNLESS NOTED
OTHERWISE.
E = MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF
FOR TUB LOCATION, & MTD 3'-0" AFF FOR TOILET
LOCATION.
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
S = AUDIO VISUAL MALL STATION (STAFF) MTD 5'-0" AFF
UNLESS OTHERWISE NOTED.
U = UTILITY CALL STATION, MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF
LAMP) MTD 6" ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6"
AFF.
REMOTE DICTATING OUTLET MTD 1'-6" AFF. UNLESS
OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
PIVCLASS CARD READER
ELECTRIC DOOR STRIKE
MAGNETIC DOOR POSITION SWITCH
VANDAL RESISTANT 1080P DOME IP CAMERA
FOUR SQUARE JUNCTION BOX
MAGNETIC LOCK WITH INTEGRATED DELAY SYSTEM
REMOTE DOOR RELEASE BUTTON
REQUEST TO EXIT MOTION DETECTOR
CCTV SYSTEM WORKSTATION
NOTE:
FOR WHEELCHAIR PATIENT USE, MOUNT TELEPHONE OUTLET 36" AFF
TO BOTTOM OF OUTLET BOX.
DESK PHONES - MOUNT OUTLET 1'-6" AFF
PAY PHONES - MOUNT OUTLET 4'-0" AFF
HEIGHT OF TELECART OUTLETS SHALL BE AS INDICATED ON
BEDWALLS OR PBPU DETAILS.
SEE VA BARRIER FREE DESIGN GUIDE PG-18-13.
KEY NOTE.
1P SINGLE POLE
1PH SINGLE PHASE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE PHASE
4/C FOUR-CONDUCTOR
4W FOUR WIRE
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT / ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED
CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT OR ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE·HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA OR CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED / CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED / OWNER
INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICERS REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXST EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
CATV
CCTV
FO
T
I
S
NC
R
ES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:4
:5
A
M
01-EG-001
ELECTRICAL SYMBOLS AND
ABBREVIATIONS
38 53
REPLACE FAN COIL UNITS
BUILDING 1
RA GG
(3'-0") MAX
SEISMIC OR
EXPANSION
JOINT.
FIELD VERIFY
ACTUAL
CONDITIONS &
LOCATIONS.
FLOOR OR ROOF
STRUCTURE. FIELD VERIFY
ACTUAL CONDITIONS, TYP.
STRUCTURAL
MEMBER
(BEAM, JOIST,
ETC.),TYP.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
CONDUIT
TRAPEZE PER
DETAIL 3 THIS
SHEET,
TYP.
BEAM
CLAMP,
TYP.
CONDUIT,
TYP.
PROVIDE (5") OF SLACK AT
MIDPOINT BETWEEN TWO ENDS OF
FLEXIBLE GALVANIZED STEEL
CONDUIT. PROVIDE GREEN
INSULATED COPPER EQUIPMENT
GROUNDING CONDUCTOR WITH
FLEXIBLE CONDUIT.
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL
STEEL
EXPANSION
ANCHOR
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
SPRING
NUT
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND BOX PERIMETER
NOTE:
1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN (3").
(3'-0") MAX
FLOOR OR ROOF
STRUCTURE. FIELD VERIFY
ACTUAL CONDITIONS, TYP.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.),
TYP.
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
CONDUIT
TRAPEZE PER
DETAIL 3 THIS
SHEET, TYP.
BEAM
CLAMP,
TYP.
EXPANSION
FITTING
WITH BONDING
JUMPER
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
STEEL EXPANSION
ANCHOR
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT
FITTING
HEAD
INSULATING
BUSHING
PROVIDE EXTRA CABLE TO
MAKE COMPLETE LOOP
AROUND BOX PERIMETER
NOTES:
1. INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL 3 THIS SHEET.
2. INSTALLATION IS REQUIRED FOR CONDUIT (3") AND LARGER.
SEISMIC OR
EXPANSION
JOINT.
FIELD VERIFY
ACTUAL
CONDITIONS &
LOCATIONS.
SPRING
NUT
LENGTH AS REQUIRED
CONDUIT CLAMP
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN (36") SHALL BE
INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER SPECIFICATION SECTION
26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL.
LOCKING
SQUARE
WASHER &
LOCKNUT
(3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED
STEEL
MOUNTING
CHANNEL
(4") FOR SECURITY
AND ACCESS CONTROL
(4") FOR DATA/TELCO
(4") FOR SPARE
(2") FOR NURSE CALL
(3/8") MAX
CONDUIT,
TYP.
MINERAL WOOL
(FIRMLY
PACKED)
FIRESTOP SEALANT PER
SPECIFICATION SECTION 07 8400,
FIRESTOPPING
CONDUIT FITTING
SPRING
NUT,
TYP.
INTEGRAL GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL,
TYP.FLOOR
SLAB,
TYP.
STEEL EXPANSION
ANCHOR, TYP.
JUNCTION BOX
(SIZE AS REQUIRED)
CEILING HANGER
WIRE
DRYWALL CEILING
CROSS TEE, TYP.
CEILING MAIN
BEAM.
DRYWALL
CEILING
CROSS
TEE, TYP.
GYPSUM BOARD
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM,
TYP.
HANGER WIRE AND MOUNTING CHANNEL ATTACHED TO STRUCTURE
REFER TO SPECIFICATION SECTION 26 51 00
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
LOCKING SQUARE
WASHER & NUT
(1/4") SCREW
FIXTURE WHIP FROM JUNCTION
BOX (6') LONG MAX
GENERAL NOTE:
1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND USING THE
RECOMMENDED MOUNTING HARDWARE.
JUNCTION
BOX
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing # of
657-19-108JB
VA Health Care System Approval:
Revision: Date:
ARCHITECT/ENGINEER:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM VEG 19.8
100% CONTRACT DOCUMENTS FOR BIDDING
11/02/2019
JEFFERSON BARRACKS
1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125
/3
/2
:4
:5
A
M
01-EG-501
ELECTRICAL DETAILS
39 53
R…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .