36C25520R0036-005.pdf

PDF Posted

Attached to
Z1DA--FCA - Replace Fan Coil Units, Building 1 657-19-108JB
Solicitation number
36C25520R0036
Issued by

About this file

This solicitation is for a project to replace 108 obsolete fan coil units in Building 1 at the Jefferson Barracks Division of the VA Saint Louis Health Care System. The project scope includes demolition, civil, mechanical, plumbing, and electrical work to replace all fan coil units in the building, with the potential to remove up to 24 units from the project scope through bid deducts. Offerors are also to provide alternate control system bids as specified. The Department of Veterans Affairs Veterans Health Administration VISN 15 is the contracting agency.

36C25520R0036 657-19-108JB - BID DOCUMENTS - 2 of 2.pdf

View the file

Other files

File Type Posted
36C25520R0036-0004000.docx DOCX document
36C25520R0036-0003000.docx DOCX document
36C25520R0036-0002000.docx DOCX document
36C25520R0036-0001000.docx DOCX document
36C25520R0036-004.pdf PDF
36C25520R0036-003.pdf PDF
36C25520R0036-002.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

T

T T

12345791012141718192021222324

R.1

R.3

S

T

U

V

V.1

V.2

V.3

R.4

T.1

T.2

U.1

FCU-B9

300 CFM

FCU-B26

FCU-B30

FCU-B32

FCU-B23

300 CFM

FCU-B24

300 CFM

FCU-B25

300 CFM

FCU-B27

FCU-B28

FCU-B29

300 CFM

FCU-B31

10"x8"

C H

R

C H

R

C H

S

5" CHS

2" CHR

3" CHS 1" D

5" CHR 2" CHR 3" CHS 1" D

5" CHR

2" CHS 1" D

CONTINUES ON

CENTRAL PLAN

HAC

GC09

D.W.

E3

CHASE

CH-C-1

DUPLICATION

GE09A

OFFICE

GE10A

STORAGE

GE10

OI&T

GE11

STORAGE

GE12

OI&T

GE13

CORRIDOR

H002

STORAGE

GE16

CORRIDOR

H003

RECEIVING

GE17

CORRIDOR

H004

OFFICE

GE20

OFFICE

GE21

TOILET

GE22

TOILET

GE23

HAC

GE24

MECH. RM.

GE26

STEAM RM.

GE28

CORRIDOR

GE31

CORRIDOR

H005

STORAGE

GE19

PREP. RM.

GE32

DECONTAMINATION

AREA

GE29

STORAGE

GE18

STORAGE

GE18A

STORAGE

GE18B

ELEVATOR #2

E2

HAC

GE34

HAC

GE35

CORRIDOR

H001

STORAGE

GE01

STAIRWELL #1

S001

VEST.

GE02

TOILET

GE05

STORAGE

GE04

STORAGE

GE03

UTILITY RM.

GE06

STORAGE

GE07

MAIL RM.

GE09

LINEN CHUTE

GE15

1 1/4" LPR

1 1/4" LPS

1 1/4" LPS

1 1/4" LPR

1 1/4" LPR

1 1/4" LPS

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:3

A

M

01-MP-103

MECHANICAL PIPING FLOOR PLAN -

EAST - 00

27 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - EAST - 00

GENERAL NOTES

KEY NOTES

NOT USED.1

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT,

STEAM, CHS, AND CHR CONNECTION SIZES.

Plan North True North

3 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 2. IF

SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

rwwhe Image

T

T

TTT

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

T

A

A.1

A.2

A.3

B

C

C.1

D

D.1

D.2

1 2 3 4 5 6 7 9 10 11 12 13 14 15 17 18 19 20 21 22 23 2410.14.7

C.2

B.2

B.1

A.4

FCU-1-1

926 CFM

FCU-1-2

500 CFM

FCU-1-5

500 CFM

FCU-1-6

500 CFM

FCU-1-8

500 CFM

FCU-1-14

208 CFM

FCU-1-16

500 CFM

FCU-1-18

500 CFM

FCU-1-21

500 CFM

FCU-1-23A

500 CFM

FCU-1-22

208 CFM

FCU-1-20

208 CFM

FCU-1-19B

208 CFM

FCU-1-19A

208 CFM

FCU-1-17

208 CFM

FCU-1-15

208 CFM

FCU-1-13

208 CFM

FCU-1-12

FCU-1-10

208 CFM

FCU-1-9

208 CFM

FCU-1-7

FCU-1-3

208 CFMFCU-1-3A

208 CFM

FCU-1-11

FCU-1-4

208 CFM

16"x30"

2 1/2" CHR

1 1/2" CHS

1" D1" D

1 1/2" CHS2" CHR2 1/2" CHS1 1/2" CHR

CONTINUES ON

CENTRAL PLAN

1" D

WAITING RM.

1W27

STORAGE

1W23

HALLWAY

1W24

TOILET

1W25

OFFICE

1W22

ALCOVE

H117A

OFFICE

1W22A

OFFICE

1W21

OFFICE

1W20

OFFICE

1W18A

OFFICE

1W18

OFFICE

1W17

OFFICE

1W16

CORRIDOR

H118

OFFICE

1E37A

OFFICE

1W14

OXYGEN

STORAGE

1W13A

CORRIDOR

1W13

STAIRWELL NO. 4

S104

OFFICE

1W12

OFFICE

1W11B

ALCOVE

H113A

OFFICE

1W11A

OFFICE

1W10

OFFICE

1W09

CONFERENCE

RM.

1W08B

WAITING RM.

1W08A

VEST.

1W08

TOILET

1W07A

OFFICE

1W07

OFFICE

1W06

TOILET

1W05

VEST.

1W06A

CLOSET

1W06B

OFFICE

1W04

OFFICE

1W03

MECH. RM.

1W02

OFFICE

1W01

E L

E V

A T

O R

N O

E

CORRIDOR

H116

STAIRWELL NO. 3

S103

TOILET

1W31

CHECK-IN

1W30A

OFFICE

1W30

OFFICE

1W29

C O

R R

ID

O

R

W

A

TOILET

1W28

CORRIDOR

H117

CORRIDOR

H119

EXAM

C105

EXAM

C106A

FCU-1-23B

500 CFM

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:3

A

M

01-MP-111

MECHANICAL PIPING FLOOR PLAN -

WEST - 01

28 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - WEST - 01

1 Plan North

True North

GENERAL NOTES

KEY NOTES

PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.

VERIFY CONNECTION SIZE.

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

2 2

3 MODIFY LAY IN CEILING TO ACCOMMODATE FAN COIL UNIT

ACCESS PANEL. NO OA DUCT CONNECTION REQUIRED FOR FCU.

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

T

RAD

RAD

8.1

E.1 F G H H.2 J.1 J.2 L M N 0 PE G.1 H.1 J K K.2 Q

10.1

N.1

FCU-1-25

700 CFM

FCU-1-26

208 CFM

FCU-1-27

208 CFM

16"x30"

1 1/2" CHS

2 1/2" CHR

1" D

C O

N T

IN

U

E S

O N

E A

S T

P

LA

N

C O

N T

IN

U

E S

O N

W E

S T

P

LA

N

CORRIDOR

H115

EXAM

C106

CHECK-IN

C108A

CORRIDOR

H114

CHECK-IN

C108

WAITING RM.

H115A

CHASE

CH-C-3

VEST.

C104

OFFICE

C104A EXAM

C102F

TOILET

C102G

STORAGE

C102H

TREAT. RM.

C102A

CONTROL

C102E

TOILET

C103

CLOSET

C104B

CHEMICAL

STORAGE

C102

WORK RM.

C102C

BREAK RM.

C102B

CORRIDOR

H111

VA POLICE

C101

ARMORY

C102I

STAIRWELL NO. 2

S102

VEST.

H109

CLEAN UTILITY

C102J

STORAGE

C129

WAITING RM.

C131

TOILET, MALE

C127

TOILET, FEMALE

C126

OFFICE

C125

OFFICE

C122A

OFFICE

C122

TOILET

C127

HAC

C121

CORRIDOR

H107

CHASE

CH-C-5

M A

IL

R

M

C C

AGENT CASHIER

C119B

CLOSET

C126A

OFFICE

C115B

OFFICE

C115A

OFFICE

C115

C O

R R

ID

O

R

H

OFFICE

C117

OFFICE

C116

OFFICE

C110

OFFICE

C112

OFFICE

C114

OFFICE

C113

OFFICE

C111

COPY RM.

C109

UTILITY

E4

VACANT

C123C

D.W.

E3

LOBBY

C124

CORRIDOR

H106

HALLWAY

C123

EXAM

C105

EXAM

C106A

RECEPTION

C118

HOLDING

C102D

CORRIDOR

H113

WAITING RM.

C128

V A

C A

N T

C

AGENT CASHIER

C119

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:3

A

M

01-MP-112

MECHANICAL PIPING FLOOR PLAN -

CENTRAL - 01

29 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - CENTRAL - 01

P la n N or th

T ru e N or th

GENERAL NOTES

KEY NOTES

PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.

VERIFY CONNECTION SIZE.

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

3 PROVIDE JOHNSON CONTROLS METASYS NETWORK

AUTOMTION ENGINE (OR APPROVED COMPATIBLE EXPANSION)

FOR EXPANSION TO THE BUILDING DDC SYSTEM.

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

DN

T

T

T

T T

12345791012141718192021222324

R.1

R.2

R.3

S

T

U

V

V.1

V.2

V.3

R.4

T.1

T.2

U.1

FCU-1-27

208 CFM

FCU-1-41

300 CFM

FCU-1-42

FCU-1-43

FCU-1-44

FCU-1-45

FCU-1-46 FCU-1-47

FCU-1-48

FCU-1-49 FCU-1-50

FCU-1-51

FCU-1-52

FCU-1-40

208 CFM

FCU-1-38

300 CFM

FCU-1-39

352 CFM

FCU-1-29

FCU-1-28

FCU-1-30

FCU-1-31 FCU-1-32

FCU-1-33

FCU-1-34

FCU-1-35

FCU-1-36

FCU-1-37

30"x10"

2" CHR

2 1/2" CHS1" D

CONTINUES ON

CENTRAL PLAN

STAIRWELL NO. 1

S101

CORRIDOR

H104

ELEVATOR NO. 2

E2

BREAK RM.

1E40A

LAB.

1E40

VACANT

C123C

D.W.

E3

LOBBY

C124

CORRIDOR

H106

HALLWAY

C123

WAITING RM.

1E01

BREAK RM.

1E02

OFFICE

1E04

M E

C H

R

M

E

OFFICE

1E07

OFFICE

1E08

OFFICE

1E09CONFERENCE

RM.

1E11

WAITING RM.

1E11A

OFFICE

1E12

OFFICE

1E14

CORRIDOR

H101

TOILET, STAFF

1E16

INJECTIONS

1E17

OFFICE

1E17A

MENTAL HEALTH

CHECK-IN

1E18

OFFICE

1E19

CORRIDOR

H102

CORRIDOR

H103A

C O

R R

ID

O

R

E

K

ELEC. CLOSET

1E15H

ELEC. CLOSET

1E15J

OFFICE

1E15A

OFFICE

1E15B

OFFICE

1E15C

CONFERENCE

RM.

1E16D

OFFICE

1E15E

OFFICE

1E15F

OFFICE

1E15G

OFFICE

1E125

STORAGE

1E22

STORAGE

1E24

HAC

1E23

OFFICE

1E25

X-RAY

1E27

CONTROL RM.

1E28

TOILET

1E26

CR

1E29

READING RM.

1E32

TOILET

1E30

CONTROL RM.

1E31

UNDER

CONSTRUCTION

1E33

UNDER

CONSTRUCTION

1E34

UNDER

CONSTRUCTION

1E35

UNDER

CONSTRUCTION

1E36

UNDER

CONSTRUCTION

1E37

WAITING RM.

1E38

CORRIDOR

H105

LAB.

1E39

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:4

A

M

01-MP-113

MECHANICAL PIPING FLOOR PLAN -

EAST - 01

30 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - EAST - 01

1 1

GENERAL NOTES

KEY NOTES

PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.

VERIFY CONNECTION SIZE.

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

Plan North True North

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

TTTT

TT

T

TT

TT

TT

T TT

T

T T

D N

U P

D N

U P

RAD

RAD

A

A.1

A.2

A.3

B

C

C.1

D

D.1

D.2

1 2 3 4 5 6 7 8 8.1 9 10 11 12 13 14 15 17 18 19 20 21 22 23 2410.14.7

C.2

B.2

B.1

A.4

FCU-2-1

FCU-2-2

FCU-2-3

208 CFM

FCU-2-4

208 CFM

FCU-2-5

208 CFM

FCU-2-6

FCU-2-7

208 CFM

FCU-2-8

FCU-2-9

500 CFM

FCU-2-10

208 CFM

FCU-2-11

208 CFM

FCU-2-12

FCU-2-13

208 CFM

FCU-2-70

FCU-2-14

208 CFM

FCU-2-15

300 CFM

FCU-2-16

300 CFM

FCU-2-17

300 CFM

FCU-2-18

300 CFM

FCU-2-19

500 CFM

FCU-2-20

500 CFM

FCU-2-21

500 CFM

FCU-2-22

500 CFM

FCU-2-23

500 CFM

FCU-2-24

500 CFM

FCU-2-33

208 CFM

18"x36"

2" CHR2 1/2" CHS1" D

2 1/2" CHR

1 1/2" CHS1" D

1 1/2" CHR2 1/2" CHS1" D

CONTINUES ON

CENTRAL PLAN

LAB.

2C19 CORRIDOR

H206

EXAM

2W13

TOILET

2W14

EXAM

2W15

EXAM

2W16

TOILET

2W17

WAITING RM.

2W18

SICK WAITING

RM.

2W19

TOILET, STAFF

2W20

CHASE

CH-W-1

OFFICE

2W21

PATIENT NOUR.

2W22

OFFICE

2W22A

OFFICE

2W22C

TOILET

2W23

OFFICE

2W24

VACANT

2W25

OFFICE

2W26

EXAM

2W27

EXAM

2W28

OFFICE

2W28A

TRIAGE

2W28B

OFFICE

2W28C

EXAM

2W29

STORAGE

2W29A

EXAM

2W29B

STORAGE

SW29C

CLINICAL

PHARMACY

2W29D

TOILET, STAFF

2W29F

VEST.

2W29E

OFFICE

2W30

EXAM

2W32

OFFICE

2W33

WAITING RM.

2W35

TOILET

2W34

HAC

2W36

CHASE

CH-W-5

STAIRWELL NO. 3

S203

ELEVATOR NO. 1

E1

CORRIDOR

H209

RECEPTION

2W01

CORRIDOR

H208

FAX RM.

2W02

TOILET

2W03

MED. PREP.

2W04

STORAGE

2W05

BREAK RM.

2W06

EXAM

2W07

TOILET

2W08

EXAM

2W09

EXAM

2W10

TOILET

2W11

EXAM

2W12

STAIRWELL NO. 4

S204

CORRIDOR

H207

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:4

A

M

01-MP-121

MECHANICAL PIPING FLOOR PLAN -

WEST - 02

31 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - WEST - 02

1 Plan North

True North

1 1

GENERAL NOTES

KEY NOTES

PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.

VERIFY CONNECTION SIZE.

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

2 2

2 2 2 2

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

T

T

T T

T T

T T T

T

ROOF BELOW

ROOF BELOW

UP

DN

UP

UP

8.1

E.1 F G H H.2 J.1 J.2 L M N 0 PE G.1 H.1 J K K.2 Q

10.1

N.1

FCU-2-25

500 CFM

FCU-2-26

FCU-2-27

208 CFM

FCU-2-28

FCU-2-29

208 CFM

FCU-2-30 FCU-2-31

FCU-2-32

208 CFM

FCU-2-34

300 CFM

FCU-2-35

300 CFM

FCU-2-37

500 CFM

FCU-2-38

500 CFM

FCU-2-39

FCU-2-40

1000 CFM

FCU-2-41

500 CFM

FCU-2-43

500 CFM

FCU-2-44

300 CFM

FCU-2-36

FCU-2-69

18"x36" 12"x30"

2 1/2" CHR2" CHS1" D

2 1/2" CHR

1 1/2" CHS

1" D

C O

N T

IN

U

E S

O N

E A

S T

P

LA

N

C O

N T

IN

U

E S

O N

W E

S T

P

LA

N ELEC RM.

2C18

TOILET, MALE

2C16

EXAM

2C15

EXAM

2C14

NURSE STATION

2C13

OPTICAL SHOP

2C12

EXAM

2C11

STORAGE

2C10A

LAB.

2C10

SERVER RM.

2C10B

UNDER

CONSTRUCTION

2C09

LAB.

2C08

LAB.

2C07

CORRIDOR

H204

OFFICE

2C04

VETERAN

HEALTH

EDUCATION

2C03

LOW VISION

THERAPY

2C02

OFFICE

2C01A

RECEPTION

2C01B

LOW VISION

CLINIC

2C01

OFFICE

2C29

STAIRWELL NO. 2

S202

HAC

2C28

TOILET, FEMALE

2C27

CORRIDOR

H205EXAM

2C25

LAB.

2C23

LAB.

2C20

STORAGE

2C21

TOILET

2C24

STORAGE

2C22

OFFICE

2C05

HAC

2C06

D.W.

E3

LAB.

2C19

CORRIDOR

H206

KITCHENETTE

2C17

FCU-2-42

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:4

A

M

01-MP-122

MECHANICAL PIPING FLOOR PLAN -

CENTRAL - 02

32 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - CENTRAL - 02

P la n N or th

T ru e N or th

GENERAL NOTES

KEY NOTES

PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.

VERIFY CONNECTION SIZE.

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

2 2

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

T

T

T

T

T T

T

T T

T T

T

T

T

T

T

T

D N

U P

12345791012141718192021222324

R.1

R.2

R.3

S

T

U

V

V.1

V.2

V.3

R.4

T.1

T.2

U.1

FCU-2-45

500 CFM

FCU-2-46

500 CFM

FCU-2-48

300 CFM

FCU-2-47

500 CFM

FCU-2-49

500 CFM FCU-2-51

300 CFM

FCU-2-52

208 CFM

FCU-2-50

300 CFM

FCU-2-53

800 CFM

FCU-2-54

208 CFM

FCU-2-55

208 CFM

FCU-2-56

208 CFM

FCU-2-57

500 CFM

FCU-2-58

500 CFM

FCU-2-59

208 CFM

FCU-2-60

500 CFM

FCU-2-61

500 CFM

FCU-2-62

500 CFM

FCU-2-63

FCU-2-64

FCU-2-44

300 CFM

2 1/2" CHR1 1/2" CHS1" D 1" D 2 1/2" CHS 2" CHR

1" D 2 1/2" CHS1 1/2" CHR

30"x14"

CONTINUES ON

CENTRAL PLAN

OFFICE

2C05

HAC

2C06

D.W.

E3

OFFICE

2E07A

TOILET

2E07C

OFFICE

2E08

OFFICE

2E09

TOILET

2E10

TELERETINAL

IMAGING

2E11

TOILET

2E12A

OFFICE

2E12

CHASE

CH-E-9

TREAT. RM.

2E13

LACTATION RM.

2E15

SOILED

LINEN

CHUTE

2E15A

EXAM

2E16

STORAGE

2E16A

KITCHENETTE

2E17

CHASE

CH-E-7

VITAL SIGN RM.

2E19

CHASE

CH-E-1

EXAM

2E20

EXAM

2E21

TOILET

2E22A

OFFICE

2E22

OFFICE

2E23

TOILET

2E24

EXAM

2E25

CORRIDOR

H203

EXAM

2E25A

TOILET

2E25B

EXAM

2E26

WAITING RM.

2E27

TOILET

2E28

EXAM

2E29

OXYGEN

STORAGE

2E30

TOILET, STAFF

2E31

ELEVATOR NO. 2

E2

C O

R R

ID

O

R

H

RECEPTION

2E18

STAIRWELL NO. 1

S201

STORAGE

2E03

STORAGE

2E02

ELEC. RM.

2E04

TOILET

2E05A

HAC

2E01

CORRIDOR

H201

OFFICE

2E06

FAX RM.

2E05B

TOILET

2E06A

TOILET

2E07B

OFFICE

2E07

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:4

A

M

01-MP-123

MECHANICAL PIPING FLOOR PLAN -

EAST - 02

33 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - EAST - 02

1 1

GENERAL NOTES

KEY NOTES

PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.

VERIFY CONNECTION SIZE.

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

2 2

Plan North True North

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

T

TTT

T

T

T

TT

T

T

T

T

T

TT

T

T

T

D N

D N

A

A.1

A.2

A.3

B

C

C.1

D

D.1

D.2

1 2 3 4 5 6 7 8 8.1 9 10 11 12 13 14 15 17 18 19 20 21 22 23 2410.14.7

C.2

B.2

B.1

A.4

FCU-3-1

300 CFM

FCU-3-2

300 CFM

FCU-3-3

700 CFM

FCU-3-4

352 CFM

FCU-3-5

208 CFM

FCU-3-6

208 CFM

FCU-3-7

700 CFM

FCU-3-8

208 CFM

FCU-3-9

352 CFM

FCU-3-10

700 CFM

FCU-3-11

700 CFM

FCU-3-12

700 CFM

FCU-3-14

208 CFM

FCU-3-13

700 CFM

FCU-3-15

700 CFM

FCU-3-16

208 CFM

FCU-3-17

208 CFM

FCU-3-18

700 CFM

FCU-3-19

700 CFM

FCU-3-20

700 CFM

18"x42"

2 1/2" CHR1 1/2" CHS1" D

2 1/2" CHR2" CHS1" D

1 1/4" CHR

2 1/2" CHS

1" D

CONTINUES ON

CENTRAL PLAN

OFFICE

H309

OFFICE

H306

STAIRWELL NO. 4

S304

FILE RM.

W310

OFFICE

W311

OFFICE

W312

TOILET, FEMALE

W313

CHASE

CH-W-1

MECH. RM.

W314

TELEPHONE RM.

W315

CHASE

CH-C-10

RECEPTION

W316

ELEVATOR NO. 1

E1

CHASE

CH-W-2

CORRIDOR

H305

LOBBY

W318

OFFICE

H307

STAIRWELL NO. 3

S303

CHASE

CH-W-5

TOILET, MALE

W301

STAFF LOUNGE

W302

MAIL RM.

W303

OFFICE

W304

OFFICE

W305

COPY RM.

W306

OFFICE

W307

OFFICE

W309

CONFERENCE

RM.

W308

OFFICE

H308

FCU-3-12A

208 CFM

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:5

A

M

01-MP-131

MECHANICAL PIPING FLOOR PLAN -

WEST - 03

34 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - WEST - 03

1 Plan North

True North

1 1

1 1

1 1

GENERAL NOTES

KEY NOTES

PROVIDE CONNECTION TO EXISTING SUPPLY DUCT.

VERIFY CONNECTION SIZE.

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

4 4 4 4 4

4 4 2 2

3 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 2. IF

SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.

4 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 3. IF

SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.

3 3

2 2 2 2 2

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

UP

8.1

E.1 F G H H.2 J.1 J.2 L M N 0 PE G.1 H.1 J K K.2 Q

10.1

N.1

FCU-3-21

FCU-3-22

FCU-3-23

FCU-3-25

FCU-3-26

FCU-3-27

FCU-3-28

FCU-3-29

FCU-3-30

FCU-3-31

FCU-3-32

20"x30"

18"x42"

1" D 3" CHS

2" CHR

1" D 2" CHS

3" CHR

1" D 1" CHS

3" CHR

C O

N T

IN

U

E S

O N

E A

S T

P

LA

N

C O

N T

IN

U

E S

O N

W E

S T

P

LA

N

MECH. RM.

3C23

LAB.

3C21

LAB.

3C18

LAB.

3C17

LAB.

3C15

LAB.

3C13

LAB.

3C12

OFFICE

3C11

LAB.

3C08

LAB.

3C27

OFFICE

C307

OFFICE

C305

OFFICE

C304

OFFICE

C306

OFFICE

C303

OFFICE

C302

LAB.

3C04

MECH. RM.

3C06

PREP. RM.

3C29

TOILET

C307A

PREP. RM.

3C28

STAIRWELL NO. 2

S302

CHASE

CH-C-5

STORAGE

C301

DARK RM.

3C06A

CORRIDOR

H304

CORRIDOR

H303

LAB.

3C09

CHASE

CH-C-4

CHASE

CH-C-3

STERILIZATION

RM.

3C14

STERILIZATION

RM.

3C16HAC

3C20

LAB.

3C07

D.W.

E3

CHASE

CH-C-1

CHASE

CH-C-10

CHASE

CH-W-2

CORRIDOR

H305

FCU-3-24

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:5

A

M

01-MP-132

MECHANICAL PIPING FLOOR PLAN -

CENTRAL - 03

35 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - CENTRAL - 03

P la n N or th

T ru e N or th

GENERAL NOTES

KEY NOTES

NOT USED.1

2 NOT USED.

3 PROVIDE JOHNSON CONTROLS METASYS NETWORK

AUTOMATION ENGINE (OR APPROVED COMPATIBLE EXPANSION)

FOR EXPANSION TO THE BUILDING DDC SYSTEM.

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

U P

D N

12345791012141718192021222324

R.1

R.3

S

T

U

V

V.1

V.2

V.3

R.4

T.1

T.2

U.1

FCU-3-34

FCU-3-35

FCU-3-36

FCU-3-39

FCU-3-37

FCU-3-38 FCU-3-40

FCU-3-41

FCU-3-42

FCU-3-43

FCU-3-44

FCU-3-45

FCU-3-46

208 CFM

30"x18"

1" D

1 1/2" CHS

4" CHR

1" D

2 1/2" CHS

3" CHR

3" CHS

CONTINUES ON

CENTRAL PLAN

LAB.

3C07 D.W.

E3

CHASE

CH-C-1

CLOTHING RM.

3E08

LAB.

3E09

OFFICE

3E10

MECH. RM.

3E11

STORAGE

3E12A

CHASE

CH-E-7

LAB.

3E12

COLD RM.

3E21A

CHASE

CH-E-9

CHASE

CH-E-10

TOILET, FEMALE

E311

HAC

E312

TOILET, MALE

E310

OFFICE

E309

OFFICE

E308

OFFICE

E307

OFFICE

E306

OFFICE

E305

OFFICE

E304

COMPUTER RM.

E303

STORAGE

E303A

OFFICE, OPEN

E302

OFFICE

E301

BREAK RM.

E313

CHASE

CH-E-1

CORRIDOR

H302

STAIRWELL NO. 1

S301

CORRIDOR

H301

TRAINING RM.

3E07

OFFICE

3E05

OFFICE

3E04A OFFICE

3E04

KITCHEN

3E03

STORAGE

3E02

HAC

3E01

CHASE

CH-E-5

CHASE

CH-E-4

P la n N or th

T ru e N or th

BLDG 1

KEYPLAN

WEST

WING

CENTER

WING

EAST

WING

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:5

A

M

01-MP-133

MECHANICAL PIPING FLOOR PLAN -

EAST - 03

36 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/8" = 1'-0"

MECHANICAL PIPING FLOOR PLAN - EAST - 03

GENERAL NOTES

KEY NOTES

NOT USED.1

2 PROVIDE FAN COIL UNIT. REFER TO 01-MG-601 FOR DUCT, CHS,

AND CHR CONNECTION SIZES.

Plan North True North

3 NOT USED.

4 FAN COIL UNIT IS INCLUDED IN DEDUCTIVE ALTERNATE 3. IF

SELECTED, DO NOT DEMO ASSOCIATED FAN COIL UNIT.

1. REFER TO 01-MG-001 AND 01-MG-002 FOR MECHANICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

2. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE COR

BEFORE PROCEEDING WITH WORK.

3. PROVIDE FAN COIL UNITS WITH CONNECTIONS PER 01-MG-501

AND 01-MG-502. INSTALLATION HEIGHT SHALL PERMIT

GRAVITY DRAINAGE OF CONDENSATE. PROVIDE BALL SHUT-

OFF VALVE AT CHS/CHR CONNECTIONS.

4. REFER TO ASBESTOS ABATEMENT SPECIFICATION FOR PIPING

INSULATION ABATEMENT REQUIREMENTS.

FAN COIL SEQUENCE OF OPERATION (COOLING ONLY)

1. FAN COIL UNIT SHALL OPERATE ON A SCHEDULE AS SET BY THE ECC.

2. MODULATE V-1 TO MAINTAIN SPACE SETPOINT AND FAN SHALL CYCLE W/TEMPERATURE.

3. ALARM IF SPACE TEMPERATURE MOVES OUTSIDE OF RANGES.

ROOM TEMPERATURE

SENSOR, WALL

MOUNTED 48" AFF.

TT

SHARED ARRANGEMENT IF FEASIBLE

PC

CHS

CHR

COOLING COIL

V-1

HS

SST

FAN

RA

FILTER

HEATING COIL

RA

LPR

LPS

V-1

COOLING COIL

CHS

CHR

V-2

FAN

SST

HS

T-1

ROOM TEMPERATURE SENSOR WITH

SPACE ADJUSTABLE WALL MOUNTED

48" AFF.

T

PC

FILTER

FAN COIL SEQUENCE OF OPERATION (NONPATIENT ROOMS)

FAN COIL SHALL OPERATE ON A SCHEDULE AS SET BY ECC. FAN SHALL RUN CONTINUOUSLY

IN OCCUPIED MODE. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE

GENERATED IN THE EVENT THE UNIT FAILS TO RUN BETWEEN THE RANGE OF 70°F - 75°F SPACE

TEMPERATURE BOTH V-1 & V-2 SHALL BE CLOSED. UPON RISE IN TEMPERATURE ABOVE 75°F

V-2 SHALL MODULATE OPEN TO MAINTAIN 75°F. UPON FALL IN TEMPERATURE BELOW 70°F.

HEATING VALVE V-1 SHALL MODULATE TO OPEN TO MAINTAIN 70°F.

TT

CS

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:5

A

M

01-MP-601

MECHANICAL INSTRUMENTATION

SCHEDULE AND DETAIL

37 53

REPLACE FAN COIL UNITS

BUILDING 1

DD MDR

NTS

COOLING ONLY FAN COIL UNIT CONTROLS

NTS

FOUR PIPE FAN COIL UNIT CONTROLS

I/O POINTS LIST BUILDING 1

QUANTITY GRAPHICS REQUIRED DO AO DI AI READ WRITE TREND BACnet OBJECT

FCU

FCU START/STOP 121 X X X HARDWIRED

FCU STATUS 121 X X X HARDWIRED

ROOM TEMPERATURE SENSOR 121 X X X HARDWIRED

ROOM TEMPERATURE SETPOINT 121 X X X HARDWIRED

DISCHARGE AIR TEMPERATURE 121 X X X HARDWIRED

CHILLED WATER CONTROL VALVE 121 X X X HARDWIRED

STEAM CONTROL VALVE 5 X X X HARDWIRED

KEY NOTES

CONTROLS SHALL BE COMPATIBLE WITH JOHNSON CONTROLS

ECC. ALTERNATE 4 ALLOWS FOR SUBSTITUTE BID FOR A

STANDALONE NIAGARA TRIDIUM OR APPROVED EQUAL ECC.

REPLACED FAN COIL UNITS SHALL BE LOCALLY CONTROLLED

BY THERMOSTAT: NO DDC CONTROLS PROVIDED. PROVIDE

ROOM TEMPERATURE ALARM AT EXISTING FACILITY BAS

SYSTEM FOR REPLACED FAN COIL UNITS.

VFD

G

R

A

V

W

WH

T

J

S

HVS

LVS

P T

PB

P

D

DP#__

LP

C

S

H

S

TC

F

F

RX

ES

ML

CR

FIX

J

RRB

WS

WAP

NCT

NCS

R

C

DB

CB

NCM

NWS

F

RX

ES

ML

CR

FIX

J

RRB

WS

OS

A

A

B

A

A

D

J

A

S X

S X

R M

M

N

TTB

R M

S

N

N

T T

C C

W W

B B

A

C

DB

RC

P

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE

OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN, AS REQUIRED.

B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED

EQUIPMENT GROUNDING CONDUCTOR.

C. REUSE EXISTING CIRCUITS AS MUCH AS POSSIBLE. MULTI-GANG BACKBOXES FOR

DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING

DEVICES MUST HAVE DIVIDERS BETWEEN DEVICES.

D. LIGHTING IN THE PATH OF CONSTRUCTION WILL BE REMOVED AND REINSTALLED

WHERE NECESSARY.

E. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR THE LOCATION OF

CEILING AND WALL MOUNTED DEVICES, AS REQUIRED.

F. ALL WIRING SHALL BE (3)#12 THWN/THHN COPPER 3/4C" UNLESS OTHERWISE NOTED.

G. MINIMUM SIZE CONDUIT FOR CONTROL CIRCUITS SHALL BE 1/2".

H. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS.

SEAL REMAINING ANULUS WITH FIRE CAULK.

I. FURNISH ACCESS DOORS FOR INSTALLATION BY GENERAL CONTRACTOR IN WALLS

AND CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED ELECTRICAL BOXES

AND DEVICES.

J. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN FIXTURE PIGTAILS. ARMORED CABLE

(AC) SHALL NOT BE USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED CABLE (AC)

SHALL NOT BE USED WHERE MORE THAN THREE CONDUCTORS

(PHASE/NEUTRAL/GROUND) ARE REQUIRED, WHERE EXPOSED; OR IN LENGTHS

EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.

K. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE CURRENT NATIONAL

ELECTRICAL CODE AND THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING

JURISDICTION.

L. COORDINATE ALL OUTAGES WITH VA COR PER SPECS PRIOR TO WORK BEING DONE.

M. REINSTALL IN SAME OR SIMILAR LOCATION ANY HARDWARE THAT IS TEMPORARILY

DISPLACED DURING DEMOLITION TO RESTORE FUNCTIONALITY.

N. THERMOSTATS WILL EITHER USE PATHWAYS FROM EXISTING THERMOSTATS OR WILL

HAVE CONDUIT INSTALLED IF NEEDED.

O. REPLACEMENT OF J-BOXES, CONTROLS AND CIRCUITS

A. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES,

CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP

CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE

WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND

REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

B. DISCONNECT AND REMOVE ALL WIRES AND CONDUIT BACK TO THE OVERCURRENT

DEVICE AND RELABEL AS A SPARE.

C. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS

PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

D. REMOVE ALL ACCESSIBLE ABANDONED WIRING OF ALL TYPES, OR CAP AND LABEL IN

JUNCTION BOX FOR RE-USE, IN COMPLIANCE WITH THE NATIONAL ELECTRIC

CODE.

E. REPLACE ALL EXISTING MULTI-PHASE BRANCH CIRCUIT BREAKERS WITH HANDLE TIE

BREAKERS ON ALL MULTI-PHASE CIRCUITS.

F. ALL HARDWARE NOT SHOWN FOR DEMOLITION SHALL BE SUSPENDED AND

REINSTALLED TO RETAIN EXISTING FUNCTIONALITY UNLESS OTHERWISE SPECIFIED.

G. LIGHTING IN THE PATH OF CONSTRUCTION WILL BE REMOVED AND REINSTALLED

WHERE NECESSARY.

NEW LINE TYPE.

EXISTING LINE TYPE.

DEMO LINE TYPE.

DEMO HATCH.

ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS

ELECTRICAL SYMBOLS - DIAGRAM

ELECTRICAL SYMBOLS - POWER PLAN

ELECTRICAL SYMBOLS - LIGHTING PLAN

COMMUNICATION SYMBOLS (CONTINUED): ELECTRICAL GENERAL NOTES:

ELECTRICAL GENERAL NOTES - DEMOLITION:

KEY NOTES:

NEW - EXISTING & DEMO LINE TYPES:

COMMUNICATION SYMBOLS:

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT-AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

FLUOR FLUORESCENT

FLUOR FIX FLUORESCENT FIXTURE

FOUTT TELEPHONE FLOOR OUTLET

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G OR GND ELECTRICAL GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWHM KILOWATT HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NEUT OR NEUTRAL

N

NC NORMALLY CLOSED

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PB PULL BOX OR PANEL BOARD

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

REQ REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

BRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER

OF CIRCUITS,NEUTRAL, AND SWITCH LEG

CONDUCTORS. ONE SEPARATE GREEN GROUNDING

CONDUCTOR SHALL BE PROVIDED FOR EACH

HOMERUN;NOT SHOWN

WIREWAY

RIGID CONDUIT LINE = RC

DIRECT BURIAL CABLE = DB

POWER DUCT = P

SUBSTATION

HI VOLTAGE SWITCH ON CONCRETE PAD

LOW VOLTAGE SWITCH ON CONCRETE PAD

DUAL POWER AND TELECOMMUNICATIONS MANHOLE

BUSWAY

FLOOR OUTLET, DATA COMMUNICATION

OUTLET, DATA COMMUNICATION

PUSH BUTTON

DISTRIBUTION PANEL

LIGHTING PANEL

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

RECEPTACLE, CLOCK HANGER

RECEPTACLE, DUPLEX (MOUNT 18"AFF. UNLESS NOTED

OTHERWISE)

RECEPTACLE, DUPLEX ON EMERGENCY POWER

(MOUNT 18" AFF. UNLESS NOTED OTHERWISE)

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT

INTERRUPTER (MOUNT 18" AFF. UNLESS NOTED

OTHERWISE)

RECEPTACLE, DUPLEX COUNTER HEIGHT

RECEPTACLE, QUADRAPLEX

RECEPTACLE, SINGLE

RECEPTACLE, SINGLE WITH SWITCH

RECEPTACLE, SPECIAL PURPOSE

A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.

H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

RECEPTACLE, SWITCHED DUPLEX

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN

FLEXIBLE CORD. CENTER LINE OF OUTLET: 6'-6" AFF.

(MINIMUM).

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS

OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR

AS INDICATED.

3-GANG COMPARTMENT BOX IN FLOOR FOR

TELEPHONE, DATA & RECEPTACLE.

TIME CLOCK

VENTILATOR OR FAN COIL UNIT OUTLET

CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED W/COUPLING (FLUSH

W/FINISHED FLOOR) FOR EXTENSION TO EQUIPMENT AS

DIRECTED.

SWITCH

F = FUSED SWITCH

L = LOCK

M = MANUAL MOTOR STARTING

MP = MOTOR SNAP WITH PILOT LIGHT

(THERMAL TYPE)

PB = PUSH BUTTON STATION

K = KEY OPERATED

LM = LOW VOLTAGE MASTER

MC = MOMENTARY CONTACT

P = WITH PILOT LIGHT

RC = REMOTE CONTROL

X = EXPLOSION PROOF

WP = WEATHER PROOF

OS = INTEGRAL OCCUPANCY SENSOR

LVD = LOW VOLTAGE DIMMER

LV= LOW VOLTAGE

CEILING MOUNTED OCCUPANCY SENSOR,

ARROWS INDICATE COVERAGE.

RECESSED DOWNLIGHT FIXTURE, LETTER

INDICATES TYPE.

LIGHT FIXTURE, RECESSED TROFFER, (2'x2');

LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED TROFFER, (2'x4');

LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED TROFFER, (1'x4');

LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED TROFFER,

(2'x4'); LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED TROFFER,

(1'x4'); LETTER INDICATES TYPE.

LIGHT FIXTURE, TROFFER EMERGENCY;

LETTER INDICATES TYPE.

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL

ARROWS AND FACES AS SHOWN

TRANSFORMER, PLAN

WYE CONNECTION

DUCT, CELL FLOOR HEADER

DUCT, TROLLEY

DUCT, UNDERFLOOR

JUNCTION BOX

EARTH GROUND

JUNCTION BOX

LADDER CABLE

DELTA CONNECTION

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

TRANSFORMER

WYE CONNECTION

PULL BOX

MANHOLE

PRESSURE SWITCH-CLOSE ON

INCREASE

PRESSURE SWITCH-OPEN ON

INCREASE

SWITCH, MULTIPOSITION

SWITCH, NORMALLY CLOSED FLOAT

SWITCH, NORMALLY CLOSED FOOT OPERATED

SWITCH, NORMALLY CLOSED LIMIT

SWITCH, NORMALLY CLOSED TEMPERATURE

ACTIVATED

SWITCH, NORMALLY CLOSED TIME DELAY

SWITCH, NORMALLY OPEN FLOAT

SWITCH, NORMALLY OPEN LIMIT

SWITCH, NORMALLY OPEN TEMPERATURE

ACTIVATED

SWITCH, NORMALLY OPEN TIME DELAY

SWITCH, SINGLE BREAK

NORMALLY CLOSED RELAY CONTACT

NORMALLY OPEN RELAY CONTACT

FUSE WITH RATING

MOLDED CASE CIRCUIT BREAKER

LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

MEDIUM-VOLTAGE OIL CIRCUIT BREAKER

MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER

SWITCH AND FUSE UNIT

FUSED DRAWOUT POTENTIAL TRANSFORMER

RELAY; LETTER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE

51 = AC-TIME OVERCURRENT

67 = AC-DIRECTIONAL OVERCURRENT

86 = LOCK OUT

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

FUSIBLE LINK

STARTER, COMBINATION W/DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

VARIABLE FREQUENCY DRIVE

GENERATOR, POWER

BATTERY

CAPACITOR

POTHEAD

STRESS CONE

LIGHTNING ARRESTOR

RECTIFIER, CATHODIC PROTECTION

AMMETER

VOLTMETER

WATTMETER

WATT-HOUR METER

CARD READER

ELECTRIC DOOR STRIKE

MAGNETIC DOOR POSITION SWITCH

VANDAL RESISTANT 1080P DOME IP CAMERA

FOUR SQUARE JUNCTION BOX

MAGNETIC LOCK

REMOTE DOOR RELEASE BUTTON

REQUEST TO EXIT MOTION DETECTOR

CCTV SYSTEM WORKSTATION

DURESS BUTTON

CODE BLUE BUTTON INTEGRATED NURSE CALL SYSTEM

NURSE CALL MASTER CONSOLE

ETHERNET NETWORK SWITCH

WIRELESS ACCESS POINT

DATA BOX

OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION

CABLE TELEVISION LINE = CATV

CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" CONDUIT

FIBER OPTICS LINE = FO

TELEPHONE LINE = T

INTERCOM LINE = I. MINIMUM 3/4" CONDUIT.

SOUND LINE = S

NURSE CALL LINE = NC. MINIMUM 3/4" CONDUIT.

RADIO CONDUIT RUN, MINIMUM 3/4" CONDUIT.

TELECOMMUNICATIONS MANHOLE

FLOOR RECEPTACLE, TELEPHONE

OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:

J = JACK TYPE W = WALL TYPE

OUTLET DATA ONLY

OUTLET; LETTER INDICATES AS FOLLOWS:

A = AUDIO V = VIDEO I = INTERCOM

SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE,

PROVIDE SCHEDULE ON LEGEND

SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE,

PROVIDE SCHEDULE ON LEGEND. MTD.

7'-6" AFF UNLESS OTHERWISE NOTED.

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6"

AFF UNLESS OTHERWISE NOTED.

SPEAKER PROGRAM SELECTOR SWITCH & VOLUME

CONTROL MTD. 4'-6" AFF UNLESS OTHERWISE NOTED.

OUTLET, TELEVISION

BLANK= 4 11/16" MASTER ANTENNA OUTLET BOX W/BLANK

COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.

C = CAMERA (CCTV SYSTEM), MTD 18" AFF

M = MONITOR (CTTV SYSTEM).

NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER

TOP UNLESS OTHERWISE NOTED.

NURSE CALL TERMINAL CABINET.

NURSE CALL STATION.

2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE

INDICATORS AT MASTER STATION) MTD 5'-0" AFF UNLESS

OTHERWISE NOTED.

D = DUTY STATION. MTD 5'-0" AFF UNLESS NOTED

OTHERWISE.

E = MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF

FOR TUB LOCATION, & MTD 3'-0" AFF FOR TOILET

LOCATION.

P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH

S = AUDIO VISUAL MALL STATION (STAFF) MTD 5'-0" AFF

UNLESS OTHERWISE NOTED.

U = UTILITY CALL STATION, MTD 5'-0" AFF UNLESS

OTHERWISE NOTED.

NURSE CALL STATION.

2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF

LAMP) MTD 6" ABOVE DOOR.

D = CORRIDOR DOME LIGHT.

I = AUXILIARY INTERSECTIONAL DOME LIGHT.

TELEPHONE TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6"

AFF.

REMOTE DICTATING OUTLET MTD 1'-6" AFF. UNLESS

OTHERWISE NOTED.

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL

OPERATION OF INSTRUMENT & TYPE REQUIRED).

INTERCOM STAFF STATION.

PIVCLASS CARD READER

ELECTRIC DOOR STRIKE

MAGNETIC DOOR POSITION SWITCH

VANDAL RESISTANT 1080P DOME IP CAMERA

FOUR SQUARE JUNCTION BOX

MAGNETIC LOCK WITH INTEGRATED DELAY SYSTEM

REMOTE DOOR RELEASE BUTTON

REQUEST TO EXIT MOTION DETECTOR

CCTV SYSTEM WORKSTATION

NOTE:

FOR WHEELCHAIR PATIENT USE, MOUNT TELEPHONE OUTLET 36" AFF

TO BOTTOM OF OUTLET BOX.

DESK PHONES - MOUNT OUTLET 1'-6" AFF

PAY PHONES - MOUNT OUTLET 4'-0" AFF

HEIGHT OF TELECART OUTLETS SHALL BE AS INDICATED ON

BEDWALLS OR PBPU DETAILS.

SEE VA BARRIER FREE DESIGN GUIDE PG-18-13.

KEY NOTE.

1P SINGLE POLE

1PH SINGLE PHASE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE PHASE

4/C FOUR-CONDUCTOR

4W FOUR WIRE

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT / ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT OR ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE·HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA OR CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED / CONTRACTOR

INSTALLED

CF/OI CONTRACTOR FURNISHED / OWNER

INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICERS REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

CUR CURRENT

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMERGENCY MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLT FLOODLIGHT

CATV

CCTV

FO

T

I

S

NC

R

ES

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:4

:5

A

M

01-EG-001

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

38 53

REPLACE FAN COIL UNITS

BUILDING 1

RA GG

(3'-0") MAX

SEISMIC OR

EXPANSION

JOINT.

FIELD VERIFY

ACTUAL

CONDITIONS &

LOCATIONS.

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

STRUCTURAL

MEMBER

(BEAM, JOIST,

ETC.),TYP.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

CONDUIT

TRAPEZE PER

DETAIL 3 THIS

SHEET,

TYP.

BEAM

CLAMP,

TYP.

CONDUIT,

TYP.

PROVIDE (5") OF SLACK AT

MIDPOINT BETWEEN TWO ENDS OF

FLEXIBLE GALVANIZED STEEL

CONDUIT. PROVIDE GREEN

INSULATED COPPER EQUIPMENT

GROUNDING CONDUCTOR WITH

FLEXIBLE CONDUIT.

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL

STEEL

EXPANSION

ANCHOR

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT FITTING

SPRING

NUT

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND BOX PERIMETER

NOTE:

1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN (3").

(3'-0") MAX

FLOOR OR ROOF

STRUCTURE. FIELD VERIFY

ACTUAL CONDITIONS, TYP.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.),

TYP.

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

CONDUIT

TRAPEZE PER

DETAIL 3 THIS

SHEET, TYP.

BEAM

CLAMP,

TYP.

EXPANSION

FITTING

WITH BONDING

JUMPER

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL

STEEL EXPANSION

ANCHOR

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT

FITTING

HEAD

INSULATING

BUSHING

PROVIDE EXTRA CABLE TO

MAKE COMPLETE LOOP

AROUND BOX PERIMETER

NOTES:

1. INSTALLATION IS ACCEPTABLE ALTERNATE TO DETAIL 3 THIS SHEET.

2. INSTALLATION IS REQUIRED FOR CONDUIT (3") AND LARGER.

SEISMIC OR

EXPANSION

JOINT.

FIELD VERIFY

ACTUAL

CONDITIONS &

LOCATIONS.

SPRING

NUT

LENGTH AS REQUIRED

CONDUIT CLAMP

SIZE AS REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

REFER TO PLANS FOR

QUANTITY & SIZE OF

CONDUITS

NOTES:

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN (36") SHALL BE

INSTALLED WITH A CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER SPECIFICATION SECTION

26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.

3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS REFER TO SPECIFICATION SECTION 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL.

LOCKING

SQUARE

WASHER &

LOCKNUT

(3/8") MIN

GALVANIZED THREADED

ROD, TYP.

WASHER &

LOCKNUT

INTEGRAL

GALVANIZED

LIPPED

STEEL

MOUNTING

CHANNEL

(4") FOR SECURITY

AND ACCESS CONTROL

(4") FOR DATA/TELCO

(4") FOR SPARE

(2") FOR NURSE CALL

(3/8") MAX

CONDUIT,

TYP.

MINERAL WOOL

(FIRMLY

PACKED)

FIRESTOP SEALANT PER

SPECIFICATION SECTION 07 8400,

FIRESTOPPING

CONDUIT FITTING

SPRING

NUT,

TYP.

INTEGRAL GALVANIZED

LIPPED STEEL

MOUNTING CHANNEL,

TYP.FLOOR

SLAB,

TYP.

STEEL EXPANSION

ANCHOR, TYP.

JUNCTION BOX

(SIZE AS REQUIRED)

CEILING HANGER

WIRE

DRYWALL CEILING

CROSS TEE, TYP.

CEILING MAIN

BEAM.

DRYWALL

CEILING

CROSS

TEE, TYP.

GYPSUM BOARD

WIRE TIE THROUGH

MOUNTING CHANNEL

& CROSS BEAM,

TYP.

HANGER WIRE AND MOUNTING CHANNEL ATTACHED TO STRUCTURE

REFER TO SPECIFICATION SECTION 26 51 00

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

LOCKING SQUARE

WASHER & NUT

(1/4") SCREW

FIXTURE WHIP FROM JUNCTION

BOX (6') LONG MAX

GENERAL NOTE:

1. INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING INSTRUCTIONS AND USING THE

RECOMMENDED MOUNTING HARDWARE.

JUNCTION

BOX

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:4

:5

A

M

01-EG-501

ELECTRICAL DETAILS

39 53

R…