36C25520R0036-004.pdf

PDF Posted

Attached to
Z1DA--FCA - Replace Fan Coil Units, Building 1 657-19-108JB
Solicitation number
36C25520R0036
Issued by

About this file

This solicitation is for a project to replace 108 obsolete fan coil units in Building 1 at the Jefferson Barracks Division of the VA Saint Louis Health Care System. The project scope includes demolition, civil, mechanical, plumbing, and electrical work. Offerors will provide pricing for replacing all fan coil units, with the option for the VA to deduct up to 24 units from the scope of work through alternate bids. Alternate control systems will also be proposed. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15.

36C25520R0036 657-19-108JB - BID DOCUMENTS - 1 of 2.pdf

View the file

Other files

File Type Posted
36C25520R0036-0004000.docx DOCX document
36C25520R0036-0003000.docx DOCX document
36C25520R0036-0002000.docx DOCX document
36C25520R0036-0001000.docx DOCX document
36C25520R0036-003.pdf PDF
36C25520R0036-002.docx DOCX document
36C25520R0036-005.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1CC

56G

3T 183

1CC

321G

1CC

5 4

4T

60G

51T 60T

52SG

52G

53G 53T

1CC

104T

102T

101T

1CC 55G

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VEG 19.8

01-GI-001

RA SD

Plan North

True North

11-20-19

11-20-19

Derek G McDonald 546324

Digitally signed by Derek G McDonald 546324 Date: 2019.11.20 12:46:51 -06'00'

Digitally signed by Kyle M.

Florian 428641 Date: 2019.11.20 12:50:54 -06'00' th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:1

A

M

01-MG-001

MECHANICAL ABBREVIATIONS AND

GENERAL NOTES

2 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1. CONTRACTOR SHALL PROVIDE AN INFECTION CONTROL RISK ASSESSMENT BARRIER AROUND

THE PROJECT AREA CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY

THE VA.

SEE SPECIFICATION SECTION 01 00 00 PART 1.2 - F FOR WORK HOURS.

SR SUPPLY AIR REGISTER

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SV STEAM PRESSURE REDUCING VALVE

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE

TAB TESTING, ADJUSTING, AND BALANCING

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

UCT UNDERCUT

UC UNIT COOLER

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

URV UPBLAST UNIT VENTILATOR

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

W WASTE

WAG WASTE ANESTHESIA GAS

WB WET BULB

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCPU WATER COOLED HEAT PUMPS

WEF WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFCV WATER FLOW CONTROL VALVE

WFM WATER FLOWMETER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

YR YEAR

OFM OIL FLOWMETER

OR OPERATING ROOM

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT

PD PRESSURE DROP

PEF PROPELLER TYPE EXHAUST FAN

PF PRE-FILTER

PG PRESSURE GAUGE

PGW PROPYLENE GLYCOL-WATER SOLUTION

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING VALVE STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH, ABSOLUTE

PSIG POUNDS PER SQUARE INCH, GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

RDS ROOM DATA SHEETS

REA RELIEF AIR

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

RV RELIEF VALVE

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SD-1 SCHEMATIC DESIGN SUBMISSION 1

SD-2 SCHEMATIC DESIGN SUBMISSION 2

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SG SUPPLY AIR GRILLE

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND DISTRIBUTION

SPRV STEAM PRESSURE REDUCING VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

KG KILOGRAM

KG/H KILOGRAMS PER HOUR

KPA KILOPASCAL

KW KILOWATT

KWH KILOWATT HOURS

L LITER

L/H LITERS PER HOUR

L/M LITERS PER MINUTE

L/S LITERS PER SECOND

LAT LEAVING AIR TEMPERATURE

LB/H POUND PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPG LIQUID PROPANE GAS

LPR LOW PRESSURE RETURN (STEAM

CONDENSATE)

LPRC LOW PRESSURE STEAM RETURN (CLEAN)

LPS LOW PRESSURE STEAM

LPSC LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M METER

M/S METERS PER SECOND

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN (STEAM

CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING UNIT

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOW METER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

OA OUTSIDE AIR

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OD OUTER DIAMETER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOHX FUEL OIL HEAT EXCHANGER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FINNED TUBE RADIATION

FV FACE VELOCITY

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

H HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HD HOOD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM

CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVD HOISTWAY VENT DAMPER

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING WATER PUMP

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCHES OF WATER COLUMN

IN WG INCHES OF WATER, GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

CP CONDENSATE PUMP

CR CEILING REGISTER

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO COOLING

TOWER)

CWS CONDENSER WATER SUPPLY (FROM COOLING

TOWER)

D DAMPER - AUTOMATIC

D-1 OUTDOOR AIR DAMPER

D-2 RETURN AIR DAMPER

D-3 RELIEF AIR DAMPER

Db DRY BULB TEMPERATURE dB DECIBEL

DD-1 DESIGN DEVELOPMENT SUBMISSION 1

DD-2 DESIGN DEVELOPMENT SUBMISSION 2

DDC DIRECT DIGITAL CONTROLS

DEG DEGREES

DF DIFFUSER

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DP DIFFUSER PLATE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/SDPR COMBINATION FIRE SMOKE DAMPER

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

FD FLOOR DRAIN

FD FIRE DAMPER

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AAV AUTOMATIC AIR VENT

AB AIR BLENDER

ACC AIR COOLED CONDENSER

ACCH AIR COOLED CHILLER

ACCU AIR-COOLED CONDENSING UNIT

ACD AUTOMATIC CONTROL DAMPER, MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION

ACFM ACTUAL CUBIC FEET PER MINUTE

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMD AIR FLOW MEASURING DEVICE

AFW AIR FOIL WHEEL (FAN)

AHU AIR HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEN (FAN)

BR BONE REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CEILING DIFFUSER

CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION 1)

CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION 2)

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFP CHEMICAL FEED PUMP

CFT CUBIC FEET

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CHW CHILLED WATER

CI CAST IRON

CM CARBON MONOXIDE

CM CUBIC METER

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

BAS BUILDING AUTOMATION SYSTEMS

HVAC GENERAL NOTESMECHANICAL ABBREVIATIONS

MECHANICAL ASCE 7 NONSTRUCTURAL

SEISMIC RESTRAINT AND ANCHORAGE NOTES:

GENERAL NOTES

2.

COR CONTRACTING OFFICER'S REPRESENTATIVE

REFERENCE SPECIFICATION: SECTION 13 05 41

SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS

SEISMIC DESIGN DATA FOR ANALYSIS AND DESIGN

SEISMIC RISK CATEGORY = IV

COMPONENT IMPORTANCE FACTOR IP = 1.50 (ASCE 7-10 TABLE 1.5-2)

MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS:

SS=0.533G S1=0.154G

SITE CLASS D (ASSUMED)

DESIGN SPECTRAL RESPONSE ACCELERATION PARAMETERS:

SDS=0.488G SD1=0.225G

SEISMIC DESIGN CATEGORY D BASED UPON SD1 > 0.20G

CLARIFICATION OF ASCE 7 "12 INCH RULE" SUSPENDED SEISMIC BRACING CODE EXCEPTION FOR PIPING

AND HVAC DUCTWORK:

ALL PIPING SUSPENDED BY INDIVIDUAL HANGAR RODS 12" OR LESS AS MEASURED FROM THE TOP OF THE PIPE TO THE BOTTOM OF THE SUPPORT WHERE THE HANGER IS ATTACHED. IF THE 12" LIMIT IS EXCEEDED BY ANY HANGER IN THE RUN, SEISMIC BRACING IS REQUIRED FOR THE RUN. NOTE: A SINGLE SUPPORT LOCATION THAT MEETS THE REQUIREMENT OF THIS EXCEPTION DOES NOT CONSTITUTE A SEISMIC SWAY

BRACE LOCATION.

THE EXCEPTION ALSO APPLIES FOR TRAPEZE SUPPORTED SYSTEMS IF THE DISTANCE AS MEASURED FROM THE POINT OF ATTACHMENT TO THE TRAPEZE TO THE POINT OF ATTACHMENT TO THE STRUCTURE IS LESS THAN 12". NOTE: IF DIRECTIONAL CHANGES OR OFFSETS TO EQUIPMENT CONNECTIONS DO NOT ALLOW FOR FLEXIBILITY OF THE TRAPEZED SYSTEM (E.G. LONG OFFSETS OR FLEXIBLE CONNECTORS) THEN THE SYSTEM MUST BE BRACED REGARDLESS OF PIPE DIAMETER OR DISTANCE TO THE STRUCTURE IF THE

COMBINED WEIGHT PER FOOT (METER) OF ALL ITEMS IS GREATER THAN 10 LBS/FT.

IN ADDITION, TO MEET THE CODE REQUIREMENTS, ALL OF THE FOLLOWING CONDITIONS MUST ALSO BE

SATISFIED:

1. LATERAL MOTION OF PIPING OR DUCTWORK WILL NOT CAUSE DAMAGING IMPACT WITH

SURROUNDING SYSTEMS (E.G. OTHER PIPE, DUCT, EQUIPMENT, SPRINKLER HEADS ETC.) OR CAUSE

LOSS OF SYSTEM VERTICAL SUPPORT.

2. PIPING MUST BE MADE OF DUCTILE MATERIAL WITH DUCTILE CONNECTIONS (E.G. WELDED STEEL

PIPE, BRAZED COPPER PIPE, ETC.)

3. VERTICAL SUPPORT CONNECTIONS CANNOT DEVELOP MOMENTS (E.G. SWIVEL JOINTS, EYE BOLTS, VIBRATION INSULATION HANGERS, ETC.)

1. ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED

IN A FURRED CHASE OR ABOVE THE CEILING.

2. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN OR

INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS.

3. ACCESS PANELS IN HARD SUSPENDED CEILINGS ARE REQUIRED FOR ALL

VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, ETC. ACCESS PANELS

SHALL BE FURNISHED AND INSTALLED UNDER THE ARCHITECTURAL

SPECIFICATIONS.

4. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT SYSTEM,

TERMINAL UNITS, FILTERS, COILS, ETC.

5. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT, SEE

EQUIPMENT DETAILS.

6. DIFFUSER, REGISTER, AND GRILLE SIZES SHOWN ON FLOOR PLANS ARE NECK

SIZES.

7. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE

MADE TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

8. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE

INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED

FLOOR.

9. ALL PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE

10. ALL CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING

BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL

SYSTEM TO INCLUDE ALL OF THE CONTROLS AND SEQUENCES SHOWN.

11. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DIFFUSERS.

12. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS FOR

ALL NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME AREAS.

DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING UNTIL

COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED.

rwwhe Image rwwhe Image e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:1

A

M

01-MG-002

MECHANICAL SYMBOLS

3 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

T

TT

M

MT

PT

TT

FT

IT

CT

SPS

SD

PDT

KR

TSL

HS

ZC

LC

LT

PDS

TSH

EPT

AT

CO2

AT

CO

AT

OC

LTCP

HVAC

ECC

TC

VSMC

PC

SC

FC

PSH

FSH

PSL

26-SF 3

26-TU-I-I

H4

H7

A

BDD

FD

VD

SUPPLY

RETURN45°

45°

N

2 1

1/24

F/S DPR

FE

AV

MV

RH

SCH

SH

TH

PS

RC

WB

CSH

SS

VR

CTPS

CTPD

FWPS

FWPD

CF

FWS

BWS

CBD

BO

TC

A

OFL

HW

SW

CW

FOR

FOS

LPG(I)

G(I)

G

HPS

HPR

MPS

MPR

LPS

LPR

PC

HWS

HWR

GHS

GHR

V

SWS

SWR

CWR

CHR

GCR

RL

RS

RHG

CWS

CHS

GCS

MW

D

GRR

GRS

X

A

PTAC

A TWU

A

FCU

FCU

A

PTACA

MB

KC

FSL

A

M

BAS

DN

DN

UP

UP

D

R

DNUP

FC

10x8

LC

M

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL UNIT NO.

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

SUPPLY FAN NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NO. 1

DRAWING NUMBER WHERE DRAWN

BUILDING NO. WHERE EQUIPMENT IS LOCATED

* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD

PRACTICE SP-58

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

MANUAL AIR VENT

QUICK-COUPLE HOSE CONNECTOR

CONNECT TO EXISTING

LIMIT OF DEMOLITION

AIR SEPERATOR

TERMINAL UNIT WITH REHEAT COIL

DOUBLE DUCT MIXING BOX.

FAN POWERED VARIABLE VOLUME

TERMINAL UNIT WITH HEATING COIL.

EXISTING DUCT TO BE REMOVED

LOUVER (LOUVER SPECIFIED IN ARCHITECTURAL

SECTION.)

FLEXIBLE DUCTWORK (INSULATED)

DUCT WITH SOUND LINING

MANUAL VOLUME DAMPER

FIRE DAMPER

BACK DRAFT DAMPER

COMBINATION FIRE/SMOKE DAMPER

POINT OF CHANGE IN DUCT CONSTRUCTION BY

STATIC PRESSURE CLASS. THE NUMBER ASSIGNS

PRESSURE CLASS (IN. OF WATER) WHICH WILL

ACCOMMODATE MAXIMUM OPERATING PRESSURE

IN THE DUCT SUBSECTION. THE SYMBOL CONTINUES

THE ASSIGNMENT UNTIL THE DUCT TERMINATES OR

ANOTHER SYMBOL APPEARS. AN "N" SUPERSCRIPT

INDICATES NEGATIVE PRESSURE.

AUTOMATIC CONTROL DAMPER MODULATING

AUTOMATIC CONTROL DAMPER TWO POSITION

MANUAL SPLITTER DAMPER

STANDARD BRANCH SUPPLY OR RETURN, NO

SPLITTER (45° TAP)

DUCT MOUNTED COIL (HOT WATER OR STEAM

COIL)

DUCT MOUNTED COIL (ELECTRIC)

CONVECTOR OR RADIATOR (RECESSED)

CONVECTOR OR RADIATOR (WALL HUNG)

FLOOR MOUNTED VERTICAL RECESSED FAN COIL UNIT.

LETTER INDICATES UNITSIZE.

FLOOR MOUNTED VERTICAL CABINET FAN

COIL UNIT. LETTER INDICATES UNIT SIZE.

THRU WALL AIR CONDITIONING UNIT.

LETTER INDICATES UNIT SIZE.

WINDOW TYPE AIR CONDITIONING UNIT.

LETTER INDICATES UNIT SIZE.

FLOOR MOUNTED HEAT PUMP. LETTER

INDICATES UNIT SIZE.

AIR CURTAIN

UNIT HEATER (HORIZONTAL)

UNIT HEATER (VERTICAL)

2'x2' RADIANT CEILING PANEL

2'x4' RADIANT CEILING PANEL

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

RETURN DUCT (UP & DOWN)

ROUND AND SQUARE 4-WAY CEILING DIFFUSERS

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

SQUARE 1-WAY CEILING DIFFUSERS

LINEAR SLOT DIFFUSER

SUPPLY TOP REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING

REGISTER OR GRILLE

EXHAUST OR RETURN BOTTOM

REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN REGISTER OR TOP GRILLE

(WALL TYPE)

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

CONNECT NEW DUCT TO EXISTING DUCT

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

LIMIT OF DEMOLITION

FLEXIBLE CONNECTION, EQUIPMENT, VIBRATION,

OR SEISMIC

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS: WIDTH x DEPTH)

EXISTING DUCT TO REMAIN

GATE VALVE - THREADED/FLANGED

GLOBE VALVE - THREADED/FLANGED

GATE VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

WYE STRAINER WITH VALVED DRAIN AND QUICK-COUPLE

FLEXIBLE CONNECTION

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

MODULATING CONTROL VALVE

MODULATING CONTROL BUTTERFLY VALVE

TWO POSITION CONTROL VALVE

THREE-WAY MODULATING CONTROL VALVE

THREE-WAY TWO POSITION CONTROL VALVE

PRESSURE REGULATING VALVE

PRESSURE SAFETY VALVE

AUTOMATIC BALANCING CONTROL VALVE

WATER BALANCE DEVICE

CIRCUIT SETTER VALVE

GATE VALVE WITH GLOBE-VALVED BYPASS

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

PRESSURE REDUCING VALVE (PRV)

WATER LEVEL CONTROLLER

FLOW METER

ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT

ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER - WALL

MOUNT

TEMPERATURE TRANSMITTER

TEMPERATURE TRANSMITTER, AVERAGING ELEMENT

MOISTURE (HUMIDITY) TRANSMITTER

PRESSURE TRANSMITTER

STATIC PRESSURE SENSOR

FLOW TRANSMITTER

CURRENT TRANSMITTER

CONDUCTIVITY TRANSMITTER

SMOKE DETECTOR

PRESSURE DIFFERENTIAL TRANSMITTER

PRESSURE DIFFERENTIAL SWITCH

HAND SWITCH (HAND-OFF-AUTO SWITCH)

VALVE OR DAMPER POSITION CONTROLLER

LOCAL RECORDING TIME CLOCK (RUNTIME)

TEMPERATURE SWITCH, LOW (FREEZESTAT)

TEMPERATURE SWITCH, HIGH (FREEZESTAT)

LEVEL CONTROLLER

LEVEL TRANSMITTER

PRESSURE SWITCH HIGH

PRESSURE SWITCH LOW

ELECTRONIC TO PNEUMATIC TRANSDUCER

CARBON DIOXIDE TRANSMITTER

CARBON MONOXIDE TRANSMITTER

OCCUPANCY SENSOR

LOCAL TEMPERATURE CONTROL PANEL

HVAC CONTROL PANEL

VARIABLE SPEED MOTOR CONTROLLER

INTEGRATE CONTROL POINT ON REMOTE

GRAPHICS WORKSTATION AT ENERGY

CONTROL CENTER

TEMPERATURE CONTROLLER. SEE

SEQUENCE OF OPERATION

PRESSURE CONTROLLER. SEE SEQUENCE

OF OPERATION

SPEED CONTROLLER. SEE SEQUENCE OF

OPERATION

FLOW CONTROLLER. SEE SEQUENCE OF

OPERATION

FLOW SWITCH HIGH

FLOW SWITCH LOW

TIME CLOCK CONTROLLING EQUIPMENT ON

A SCHEDULE

TEMPERATURE SENSING ELEMENT FOR

TRANSMITTING TEMPERATURE TO EMCS

(PROVIDE 12 INCHES MINIMUM

LENGTH IN DUCT WHEN SPACE PERMITS.)

SENSOR WITH AVERAGING ELEMENT

TO TRANSMIT TEMPERATURE TO EMCS

MOTOR STARTER

ELECTRIC OPERATED CONTROL

DAMPER/OR VALVE

BUILDING AUTOMATION SYSTEM

CONTROLS SYMBOLS

DRAWING SYMBOLS

DUCTWORK SYMBOLS GENERAL PIPING SYMBOLSHVAC PIPING SYMBOLS

TERMINAL UNIT SYMBOLS

AIR TERMINAL SYMBOLS

VALVE SYMBOLS

FLOOR-SUPPORTED PIPE STAND

RISER CLAMP (TYPE 42)*

WALL BRACKET (TYPE 31, 32, 33)*

CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*

SLIDING SUPPORTS (TYPE 35)*

TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT

TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)

HOT WATER

ROLLER-TYPE HANGER

VARIABLE SPRING-TYPE HANGER (TYPE 51)*

SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*

CLEVIS-TYPE HANGER

HIGH PRESSURE STEAM (60 PSIG AND ABOVE)

HIGH PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

LOW PRESSURE STEAM CONDENSATE RETURN

CONDENSATE PUMP DISCHARGE

HEATING WATER SUPPLY

HEATING WATER RETURN

GLYCOL-WATER HEATING SUPPLY

GLYCOL-WATER HEATING RETURN

SOLAR WATER SUPPLY

SOLAR WATER RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

CONDENSER WATER SUPPLY (FROM TOWER)

CONDENSER WATER RETURN (TO TOWER)

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CHILLED GLYCOL-WATER SUPPLY

CHILLED GLYCOL-WATER RETURN

MAKE-UP WATER

DRAIN LINE

VENT LINE

GLYCOL-WATER RUN AROUND SUPPLY

GLYCOL-WATER RUN AROUND RETURN

EXISTING PIPE TO BE REMOVED

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

CONDENSATE TRANSFER PUMP DISCHARGE

CONDENSATE TRANSFER PUMP SUCTION

VACUUM CONDENSATE RETURN

TUBE CLEANER WATER SUPPLY

BOILER BLOWOFF

CONTINUOUS BLOWDOWN

BOILER WATER SAMPLE

FEEDWATER SAMPLE (FROM DEAERATOR)

CHEMICAL FEED

OVERFLOW

COMPRESSED AIR

NATURAL GAS MAIN FUEL

NATURAL GAS IGNITER FUEL

LIQUEFIED PETROLEUM GAS IGNITER FUEL

FUEL OIL SUPPLY

FUEL OIL RETURN

COLD WATER (CITY WATER)

SOFTENED WATER

THERMOMETER

PRESSURE GAGE

FLOW ELEMENT

REFRIGERANT SIGHT GLASS

THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

FLOAT & THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

INVERTED BUCKET TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

DIRECTION OF PIPE PITCH (DOWN)

DIRECTION OF FLOW

ANCHOR

REDUCER OR INCREASER

ECCENTRIC REDUCER

TOP CONNECTION, 45° OR 90°

BOTTOM CONNECTION, 45° OR 90°

SIDE CONNECTION

CAPPED OUTLET

RISE OR DROP IN PIPE

UNION

PIPE UP

PIPE DOWN

CEILING MOUNTED FAN COIL UNIT

DN

UP

UP

DN

DN

DN

MECH.

GC17E

PATRIOT

CAFE

GC17A

STORAGE

GC19

STORAGE

GC20

STORAGE

GC21

SERVICE

RM.

GC22

UTILITY RM.

GC01

CORRIDOR

H008

CANTEEN

GC17F

STORAGE

GC17C

ELECTRIC

CARTS

GC17

STORAGE

GC17B

STORAGE

GC02

MECH. RM.

GC13

OI&T

GC12A

STORAGE

GC12

TRANSFORMER

RM.

GC16A

STORAGE

GC13

MECH. RM.

GC10B

FILE RM.

GC03

TOILET,

MEN

GC08

COOLER

GC10A

OI&T

GC11A

OI&T

GC11B

HAC

GC09

D.W.

E3

CHASE

CH-C-1

CORRIDOR

H006

C O

R R

ID

O

R

H

ELEC.

SUPPLY

GC15A

IV RM.

GW05A

UNLOADING

AREA

GW04A

PHARMACY

SUPPLIES

GW05

PHARMACY

GW04

OFFICE

GW06

PHARMACY

GW07

DISPENSING

GW08

WAITING

RM.

GW09A

PRESCRIPTION

INTAKE

GW09

STAIRWELL

#4

S004

M E

C H

R

M

G W

PUMP RM.

GC18

CORRIDOR

H010

ELEVATOR

#1

E02

WAITING

RM.

GW02

CHECK-IN

GW10B

HAC

GW10A

OFFICE

GW10

OFFICE

GW12

OFFICE

GW12A

OFFICE

GW12B

OFFICE

GW12C

STORAGE

GW13

CORRIDOR

H009

PHARMACY

VAULT

GW14

TELEMED

GW15

FLUID

STORAGE

GW16

UNDER

CONSTRUCTION

GW17A

LOCKER

RM.,

FEMALE

GW17

TOILET,

FEMALE

GW18

STORAGE

GW19

STAIRWELL

#3

S003

STORAGE

GW19A

CORRIDOR

H011

DUPLICATION

GE09A

OFFICE

GE10A

STORAGE

GE10

OI&T

GE11

STORAGE

GE12

OI&T

GE13

LINEN

CHUTE

GE15

CORRIDOR

H002

STORAGE

GE16

CORRIDOR

H003

RECEIVING

GE17

CORRIDOR

H004

OFFICE

GE20

OFFICE

GE21

TOILET

GE22

TOILET

GE23

HAC

GE24

MECH. RM.

GE26

STEAM RM.

GE28

CORRIDOR

GE31

CORRIDOR

H005

STORAGE

GE19

PREP. RM.

GE32

DECONTAMINATION

AREA

GE29

STORAGE

GE18

STORAGE

GE18A

STORAGE

GE18B

ELEVATOR

#2

E2

HAC

GE34

HAC

GE35

CORRIDOR

H001

STORAGE

GE01

STAIRWELL

#1

S001

VEST.

GE02

TOILET

GE05

STORAGE

GE04

STORAGE

GE03

UTILITY RM.

GE06

STORAGE

GE07

MAIL RM.

GE09

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:1

A

M

01-MG-101

MECHANICAL AREA OF WORK - FLOOR

4 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/16" = 1'-0"

MECHANICAL AREA OF WORK - FLOOR 00

P la n N or th

T ru e N or th

RAD

RAD

WAITING

RM.

1W27

STORAGE

1W23

HALLWAY

1W24

TOILET

1W25

OFFICE

1W22 ALCOVE

H117A

OFFICE

1W22A

OFFICE

1W21

OFFICE

1W20

OFFICE

1W18A

OFFICE

1W18

OFFICE

1W17

OFFICE

1W16

CORRIDOR

H118

OFFICE

1E37A

OFFICE

1W14

OXYGEN

STORAGE

1W13A

CORRIDOR

1W13

STAIRWELL

NO. 4

S104

OFFICE

1W12

OFFICE

1W11B

ALCOVE

H113A

OFFICE

1W11A

OFFICE

1W10

OFFICE

1W09

CONFERENCE

RM.

1W08B

WAITING

RM.

1W08A

VEST.

1W08

TOILET

1W07A

OFFICE

1W07

OFFICE

1W06

TOILET

1W05

VEST.

1W06A

CLOSET

1W06B

OFFICE

1W04

OFFICE

1W03

MECH. RM.

1W02

OFFICE

1W01

E L

E V

A T

O R

N O

E

CORRIDOR

H116

S T

A

IR

W E

L L

N O

S

TOILET

1W31

CHECK-IN

1W30A

OFFICE

1W30

OFFICE

1W29

C O

R R

ID

O

R

W

A

TOILET

1W28

CORRIDOR

H117

CORRIDOR

H119

EXAM

C105

EXAM

C106A

CORRIDOR

H115

EXAM

C106

CHECK-IN

C108A

CORRIDOR

H114

CHECK-IN

C108

WAITING

RM.

H115A

CHASE

CH-C-3

VEST.

C104

OFFICE

C104A

EXAM

C102F TOILET

C102G

STORAGE

C102H

TREAT. RM.

C102A

CONTROL

C102E

TOILET

C103

CLOSET

C104B

CHEMICAL

STORAGE

C102

HOLDING

C102D

WORK RM.

C102C

BREAK RM.

C102B

CORRIDOR

H111

VA POLICE

C101

ARMORY

C102I

STAIRWELL

NO. 2

S102

VEST.

H109CLEAN

UTILITY

C102J

CORRIDOR

H113

WAITING

RM.

C128

STORAGE

C129

WAITING

RM.

C131

TOILET,

MALE

C127

TOILET,

FEMALE

C126

OFFICE

C125

STAIRWELL

NO. 1

S101

CORRIDOR

H104

ELEVATOR

NO. 2

E2

BREAK RM.

1E40A

LAB.

1E40

VACANT

C123C

OFFICE

C123B

D.W.

E3

LOBBY

C124

CORRIDOR

H106

HALLWAY

C123

OFFICE

C123A

OFFICE

C122A

OFFICE

C122

TOILET

C127

V A

C A

N T

C

HAC

C121

CORRIDOR

H107

CHASE

CH-C-5

M A

IL

R

M

C C

AGENT

CASHIER

C119

AGENT

CASHIER

C119B

CLOSET

C126A

OFFICE

C115B

OFFICE

C115A

OFFICE

C115

RECEPTION

C118

C O

R R

ID

O

R

H

OFFICE

C117

OFFICE

C116

OFFICE

C110

OFFICE

C112

OFFICE

C114

OFFICE

C113

OFFICE

C111

COPY RM.

C109

WAITING

RM.

1E01

BREAK RM.

1E02

OFFICE

1E04

M E

C H

R

M

E

OFFICE

1E07

OFFICE

1E08

OFFICE

1E09

CONFERENCE

RM.

1E11

WAITING

RM.

1E11A

OFFICE

1E12

OFFICE

1E12

OFFICE

1E14

CORRIDOR

H101

TOILET,

STAFF

1E16

INJECTIONS

1E17

OFFICE

1E17A

MENTAL

HEALTH

CHECK-IN

1E18

OFFICE

1E19

CORRIDOR

H102

CORRIDOR

H103A

C O

R R

ID

O

R

E

K

ELEC.

CLOSET

1E15H

ELEC.

CLOSET

1E15J

OFFICE

1E15A

OFFICE

1E15B

OFFICE

1E15C

CONFERENCE

RM.

1E16D

OFFICE

1E15E

OFFICE

1E15F

OFFICE

1E15G

OFFICE

1E125

STORAGE

1E22

STORAGE

1E24

HAC

1E23

OFFICE

1E25

X-RAY

1E27

CONTROL

RM.

1E28

TOILET

1E26

CR

1E29

READING

RM.

1E32

TOILET

1E30

CONTROL

RM.

1E31

UNDER

CONSTRUCTION

1E33

UNDER

CONSTRUCTION

1E34

UNDER

CONSTRUCTION

1E35

UNDER

CONSTRUCTION

1E36

UNDER

CONSTRUCTION

1E37

WAITING

RM.

1E38

CORRIDOR

H105

LAB.

1E39

UTILITY

E4

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:1

A

M

01-MG-111

MECHANICAL AREA OF WORK - FLOOR

5 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/16" = 1'-0"

MECHANICAL AREA OF WORK - FLOOR 01

P la n N or th

T ru e N or th

ROOF BELOW

DNUP

DN

UP

DN UP

DN UP

RAD RAD

TOILET,

STAFF

2W29F

OFFICE

2W28C

TRIAGE

2W28B

OFFICE

2W28A

EXAM

2W28

EXAM

2W27

VACANT

2W25

OFFICE

2W24

TOILET

2W23

OFFICE

2W22C

OFFICE

2W22A

PATIENT

NOUR.

2W22

OFFICE

2W21

TOILET,

STAFF

2W20

SICK

WAITING

RM.

2W19

STAIRWELL

NO. 4

S204

WAITING

RM.

2W18

WAITING

RM.

2W18

WAITING

RM.

2W18

EXAM

2W16

EXAM

2W16

EXAM

2W15

EXAM

2W13

EXAM

2W12

CORRIDOR

H209

EXAM

2W10

EXAM

2W09

TOILET

2W08

EXAM

2W07

EXAM

2W07

EXAM

2W07

EXAM

2W07

STORAGE

2W05

RECEPTION

2W01

ELEVATOR

NO. 1

E1

CORRIDOR

H209

STAIRWELL

NO. 3

S203

TOILET

2W34

WAITING

RM.

2W35

EXAM

2W32

OFFICE

2W30

CORRIDOR

H207

CORRIDOR

H209

LAB.

2C19

CORRIDOR

H205

ELEC RM.

2C18

TOILET,

MALE

2C16

TOILET,

MALE

2C16

KITCHENETTE

2C17

LAB.

2C19

LAB.

2C20

TOILET

2C24

EXAM

2C25

LAB.

2C23

STORAGE

2C22

EXAM

2C15

EXAM

2C11

NURSE

STATION

2C13

CORRIDOR

H205

HAC

2C28

STAIRWELL

NO. 2

S202STAIRWELL

NO. 2

S202

OFFICE

2C29

LOW VISION

CLINIC

2C01

VETERAN

HEALTH

EDUCATION

2C03

OFFICE

2C04

STAIRWELL

NO. 1

S201

ELEVATOR

NO. 2

E2

RECEPTION

2E18

TOILET,

STAFF

2E31

OFFICE

2C05

D.W.

E3

HAC

2C06

CORRIDOR

H210

LAB.

2C07

LAB.

2C08

LAB.

2C08

CORRIDOR

H204

UNDER

CONSTRUCTION

2C09

OFFICE

2C04

SERVER RM.

2C10B

STORAGE

2E02

ELEC. RM.

2E04

TOILET

2E05A

OFFICE

2E05

OFFICE

2E06

TOILET

2E06A

OFFICE

2E07

OFFICE

2E07A

TOILET

2E07C

OFFICE

2E08

CORRIDOR

H201

OFFICE

2E09

TOILET

2E10

TELERETINAL

IMAGING

2E11

OFFICE

2E12

LACTATION

RM.

2E15

EXAM

2E16

CHASE

CH-E-7

EXAM

2E20

EXAM

2E21

EXAM

2E20

OFFICE

2E22

OFFICE

2E23

EXAM

2E25

TOILET

2E24

EXAM

2E25A

EXAM

2E26

WAITING

RM.

2E27

CORRIDOR

H203

EXAM

2E29

AREA OF WORK

EXAM

2W29B

STORAGE

SW29C

TREAT. RM.

2E13

FAX RM.

2E05B

VITAL SIGN

RM.

2E19

LAB.

2C10

EXAM

2C14

OFFICE

2W28A

OFFICE

2W26

OFFICE

2W33

HAC

2W36

AREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:1

A

M

01-MG-121

MECHANICAL AREA OF WORK - FLOOR

6 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/16" = 1'-0"

MECHANICAL AREA OF WORK - FLOOR 02

P la n N or th

T ru e N or th

RAD

RAD

UP

DNDN

DN

UP

DN

LAB.

3C26

MECH. RM.

3C23

LAB.

3C21

LAB.

3C18

LAB.

3C17

LAB.

3C15

LAB.

3C13

LAB.

3C12

OFFICE

3C11

LAB.

3C08

LAB.

3C07

LAB.

3C27

OFFICE

C307

OFFICE

C305

OFFICE

C304

OFFICE

C306

OFFICE

C303

OFFICE

C302

LAB.

3C04

MECH. RM.

3C06

PREP. RM.

3C29

TOILET

C307A

PREP. RM.

3C28

STAIRWELL

NO. 2

S302

CHASE

CH-C-5

STORAGE

C301

DARK RM.

3C06A

CORRIDOR

H304

CORRIDOR

H303

D.W.

E3

CHASE

CH-C-1

LAB.

3C09

CHASE

CH-C-4

CHASE

CH-C-3

STERILIZATION

RM.

3C14

STERILIZATION

RM.

3C16

HAC

3C20

CHASE

CH-C-8

CLOTHING

RM.

3E08

LAB.

3E09

OFFICE

3E10

MECH. RM.

3E11

STORAGE

3E12A

CHASE

CH-E-7

LAB.

3E12

COLD RM.

3E21A

CHASE

CH-E-9

CHASE

CH-E-10

TOILET,

FEMALE

E311

HAC

E312

TOILET,

MALE

E310

OFFICE

E309

OFFICE

E308

OFFICE

E307

OFFICE

E306

OFFICE

E305

OFFICE

E304

COMPUTER

RM.

E303

STORAGE

E303A

OFFICE,

OPEN

E302

OFFICE

E301

BREAK RM.

E313

CHASE

CH-E-1

CORRIDOR

H302

STAIRWELL

NO. 1

S301

CORRIDOR

H301

TRAINING

RM.

3E07

OFFICE

3E05

OFFICE

3E04A

OFFICE

3E04

KITCHEN

3E03

STORAGE

3E02

HAC

3E01

CHASE

CH-E-5

CHASE

CH-E-4

OFFICE

H309

OFFICE

H306

STAIRWELL

NO. 4

S304

FILE RM.

W310

OFFICE

W311

OFFICE

W312

TOILET,

FEMALE

W313

CHASE

CH-W-1

MECH. RM.

W314

TELEPHONE

RM.

W315

CHASE

CH-C-10

RECEPTION

W316

ELEVATOR

NO. 1

E1

CHASE

CH-W-2

C O

R R

ID

O

R

H

LOBBY

W318

OFFICE

H307

STAIRWELL

NO. 3

S303

CHASE

CH-W-5

TOILET,

MALE

W301

STAFF

LOUNGE

W302

MAIL RM.

W303

OFFICE

W304

OFFICE

W305

COPY RM.

W306

OFFICE

W307

OFFICE

W309 CONFERENCE

RM.

W308

OFFICE

H308

AREA OF WORKAREA OF WORK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:2

A

M

01-MG-131

MECHANICAL AREA OF WORK - FLOOR

7 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1/16" = 1'-0"

MECHANICAL AREA OF WORK - FLOOR 03

P la n N or th

T ru e N or th

SMACNA FIGURE 4-6

45° LEED IN

RIGID DUCT TO AIR

TERMINAL

UNIT.

MAIN SUPPLY

PLAN VIEW

FLOW

F

LO

W

NOTES:

1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.

2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR

PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.

NOTES:

1. VENT ALL HIGH POINTS.

2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.

TYPICAL MANUAL OR AUTOMATIC AIR VENT

ELEVATION

ELEVATION

WELDED

PIPING

ELEVATION

THREADED

PIPING

TYP. WATER PIPING

REDUCER IF NEEDED.

3/4" BALL VALVE

ADAPTER TO 3/4" HOSE

THREAD-PROVIDED HOSE

CAP NUT

TYPICAL CHILLED AND HOT WATER PIPING DRAIN VALVE CONNECTIONS.

AIR VENT

MV

OR

AV

1/2" BALL VALVE

CIRCULATING WATER PIPING

1/4" COPPER TUBING

1/2" X 4" NIPPLE

NOTES:

1. RIGID STRAIGHT FAN COIL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3 TIMES THE DIAMETER OF INLET

2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX, BUT ALLOWED TO ACCOMMODATE

MINOR OFFSETS. MAXIMUM LENGTH 3'-0".

3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE BOX INLET, PROVIDED THE EQUIVALENT

LENGTH OF THE BRANCH DUCT, AS SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER LENGTHS, INCREASE THE DUCT

SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC PRESSURE DROP AT OR BELOW 0.2"/100'.

4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM FAN COIL UNIT SUPPLY AIR DUCT TO DIFFUSER, SHALL NOT

EXCEED 5'-0". USE RIGID ELBOWS FOR CHANGE OF DIRECTION GREATER THAN 45°.

5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE INSULATION W/VAPOR BARRIER FOR

CONNECTING DUCT SECTIONS.

SEE NOTE 1

SEE NOTE 2

SEE NOTE 3

FLEXIBLE AIR DUCT

CONNECTOR. SEE DETAIL.

DIFFUSER (TYP.)

S E

E N

O T

E

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT

(TYP.)

SEE NOTE 5

FCU

30°

15°

15°

NOTES:

1. UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

M

AX.

M A

X

E Q

U

IP

M E

N T

AIR

FLOW

AIR

FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEW

TYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

M

AX.

M A

X

M A

X

M A

X

6" PLENUM

FINISHED CEILING

4-WAY DEFLECTION

SUPPLY AIR GRILLE

HANGER ROD

SUPPORTS SECURE TO

STRUCTURE ABOVE

WITH SPRING

ISOLATORS (TYP)DUCT SIZE TO SUIT

SUPPLY AIR GRILLE

304 SS DRAIN PAN

& PIPE CONNECTION

FOR SOFFIT SEE

ARCH. DRAWINGS

RETURN

AIR GRILLE

ACCESS DOOR SIZED TO

ALLOW ACCESS TO

ELECTRICAL AND COIL

CONNECTIONS AND ALLOW

FOR MOTOR/FAN ASSEMBLY

REMOVAL. ACCESS DOOR

NOT REQUIRED WHEN OVER

ACOUSTIC TILE CEILING.

COIL

FAN

FILTER

TERMINATE OVERFLOW

DRAIN ABOVE LAVATORY,

SINK, OR FLOOR DRAIN

INSULATE FULL LENGTH

OF THE CONDENSATE

DRAIN PIPING

ACCESS DOOR

NOTES:

1. SIX INCH PLENUM AS SHOWN SHALL BE SUPPLIED BY MANUFACTURER OF FAN COIL UNIT.

2. SEE DETAIL FOR SUPPLY & RETURN PIPING CONNECTIONS. PROVIDE ACCESS FOR FILTER REMOVAL.

3. SEE FAN COIL UNIT SCHEDULE FOR PIPE SIZES.

4. SUPPLY & RETURN GRILLES SHALL BE SIZED TO SUIT CONNECTIONS ON FAN COIL UNIT. DUCTWORK

SHALL SUIT GRILLES AND FAN COIL UNIT FURNISHED. TYP. FOR UNIT ABOVE DROP CEILING.

5. PROVIDE AUXILIARY DRIP PAN PER SPECIFICATION SECTION 23 82 00.

6. PROVIDE INTERNAL INSULATION PER SPECIFICATION SECTION 23 82 00.

OA DUCT

WHERE SHOWN

ON PLANS

12"

CEILING

CONICAL OUTLET

BRANCH DUCT

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

NOTES:

THE USE OF FLEXIBLE AIR DUCT CONNECTORS ARE NOT PERMITTED

FOR THE DEDICATED AHU SERVING THE SURGICAL

SUITE.

TYPICAL DIFFUSER

OR REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

SUPPORT SADDLE

FROM STRUCTURE

FLEXIBLE DUCT SIZE

SAME AS DIFFUSER

INLET: 5'-0" MAX LENGTH.

USE RIGID ELBOWS FOR

CHANGE OF DIRECTION

GREATER THAN 45°

SHEET METAL

SADDLE

VOLUME DAMPER

W/ LOCKING QUAD

1/2" 1/2" 1 1/2"

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED

CONNECTION ON

FAN SIDE

WASHER 1-1/2" MIN. TO 3" MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" DRAW BAND

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

5/16" FLANGE

DUCT

SHEET METAL

SCREWS

ON 12" CENTERS

RIVET ON 4"

CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" BAND IRON

BOLT ON 4" CENTERS

1" FLANGE & HEMALTERNATE

POSITION

OF BOLT

1 1/2"

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1 1/2" MIN. TO 3" MAX. INSTALLED. 6"

NOMINAL WITH MATERIAL TAUTFLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

CHILLED WATER

RETURN

MANUAL AIR VENT

UNION CONNECTIONS

(TYP.)

DRAIN WITH HOSE

CONNECTION

MV

2 POSITION

MODULATING

CONTROL VALVE

CHILLED WATER

SUPPLY

GASKET ALL AROUND WHEN MOUNTED

AGAINST CEILING AND/OR WALL

HANGER ROD SUPPORTS

SECURE TO STRUCTURE

ABOVE (TYP)

DROP

CEILING

PROVIDE CONNECTION TO

EXISTING SUPPLY DUCT

DRAIN PAN & PIPE

CONNECTION

RETURN AIR

GRILLE & FILTER

ACCESS DOOR &

GRILLS

FINISHED CEILING

COIL

FAN

NOTES:

1. PROVIDE AUXILIARY DRIP PAN PER SPECIFCATION SECTION 23 82 00.

2. PROVIDE INTERNAL INSULATION PER SPECIFICATION SECTION 23 82 00.

3. SIX INCH PLENUM AS SHOWN SHALL BE SUPPLIED BY MANUFACTURER OF FAN COIL UNIT.

4. SEE DETAIL FOR SUPPLY & RETURN PIPING CONNECTIONS. PROVIDE ACCESS FOR FILTER REMOVAL.

5. SEE FAN COIL UNIT SCHEDULE FOR PIPE SIZES.

6. DUCTWORK SHALL BE SIZED TO SUIT GRILLES AND FAN COIL UNIT FURNISHED. TYP. FOR UNIT ABOVE

DROP CEILING.

OA DUCT

WHERE SHOWN

ON PLANS

GASKET ALL AROUND WHEN MOUNTED

AGAINST CEILING AND/OR WALL

HANGER ROD SUPPORTS

SECURE TO STRUCTURE

ABOVE (TYP)

FINISHED

CEILING

4-WAY DEFLECTION

SUPPLY AIR GRILLE

DRAIN PAN & PIPE

CONNECTION RETURN AIR

GRILLE & FILTER

ACCESS DOOR &

GRILLS

FINISHED CEILING

COIL

FAN

NOTES:

1. PROVIDE AUXILIARY DRIP PAN PER SPECIFCATION SECTION 23 82 00.

2. PROVIDE INTERNAL INSULATION PER SPECIFICATION SECTION 23 82 00.

3. SIX INCH PLENUM AS SHOWN SHALL BE SUPPLIED BY MANUFACTURER OF FAN COIL UNIT.

4. SEE DETAIL FOR SUPPLY & RETURN PIPING CONNECTIONS. PROVIDE ACCESS FOR FILTER REMOVAL.

5. SEE FAN COIL UNIT SCHEDULE FOR PIPE SIZES.

OA DUCT

WHERE SHOWN

ON PLANS

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:2

A

M

01-MG-501

MECHANICAL DETAILS

8 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

NTS

ALTERNATE SUPPLY DUCT TAKEOFF - AIR TERMINAL UNITS

NTS

DRAIN VALVE AND AIR VENT CONNECTIONS (HYDRONIC SYSTEMS)

NTS

DUCT CONNECTION - FAN COIL UNITS

NTS

DUCTWORK TRANSITIONS (WITH EQUIPMENT MOUNTED IN DUCT)

NTS

FAN COIL UNIT - HORIZONTAL HIDDEN

NTS

FLEXIBLE AIR DUCT CONNECTOR

NTS

FLEXIBLE DUCT CONNECTIONS

NTS

FAN COIL PIPING CONNECTION

NTS

FAN COIL UNIT - RECESSED

NTS

FAN COIL UNIT - EXPOSED

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" MIN.)

BAND

1-5/8" 12 GAUGE

CHANNEL OR 2"x2"x1/4" ANGLE

1/2" DIA.

HANGER RODS WITH

36" MAX. SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF MIN.

DENSITY) UNDER INSULATION

SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NOTES:

SEE SPECIFICATIONS FOR DETAILED

HANGER REQUIREMENTS

1" M

A X

SIDE VIEW TRAPEZE HANGER FOR UP TO 1000 LB.

UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1 -

SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER TYPE 43 -

SEE SPECIFICATIONS

8 97

THRU 3/4 1 1/41 1 1/2 2 1/22 3 54 6 108 12 1614 18 2420

30 322825 27

2319 221714 16

-16 -1412 13 -

1210 119

5 FTFT.

FT.

IN.

TUBING

PIPE

NOM. SIZE

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

MAXIMUM PIPE/TUBING SUPPORT SPACING

STEEL EXPANSION SHIELD FOR

EXISTING CONSTRUCTION AND

INSERTS FOR NEW CONSTRICTION THIS

TYPE SHALL BE USED ONLY IN SLABS

OR BEAMS OF 4" MIN DEPTH

3/8" MIN DIA EXPANSION BOLTS FOR

EXISTING CONSTRUCTION AND

INSERTS FOR NEW CONSTRUCTION

CONCRETE

FLOOR SLAB

CLIP

ANGLE

NUTS & WASHERS

3/8" MIN DIA

HANGER RODS

FOR PIPES UNDER 2" IN SIZE USE 1

1/2"x1 1/2"x1/4" ANGLE. ALL PIPES

2" & LARGER USE 3"x3"x1/4" ANGLE

TURNBUCKLE

3/8" MIN DIA

HANGER RODS

3/8" MIN DIA INSERTS NEW

CONSTRUCTION ONLY.

NOTES:

NOT REQUIRED FOR AIR TERMINAL UNITS.

EQUIPMENT WEIGHT

250 LBS. OR LESS

SEISMIC BRACING FOR LIGHT

SUSPENDED EQUIPMENT

FLOOR MOUNT EQUIPMENT

RESTRAINED BY RESILIENT PADS

(TYPE DS)

FLOOR

EQUIPMENT

BASE ANCHOR BOLT

NEOPRENE

WASHER & SLEEVE

BONDED STEEL

PLATE

RESILIENT

PAD

HANGER

ROD

(TYP)

CROSS BRACING

RODS ALL FOUR

SIDES

LOCK

NUTS

(TYP)

CLAMP

RIGID DUCT TO AIR

TERMINAL

UNIT.

ROUND SHEET

METAL

DUCT.

MAIN SUPPLY

"D"

45°M A

X

PLAN VIEW

STEAM PIPING CONNECTIONS TO VERTICAL TYPE FAN COIL UNIT

STEAM

CONDENSATE

RETURN

INVERTED

BUCKET TRAP

STEAM SUPPLY

FAN COIL

UNIT

STEAM PIPING CONNECTIONS TO HORIZONTAL TYPE FAN COIL UNIT

FCU STEAM COIL

STEAM CONDENSATE RETURN

INVERTED

BUCKET TRAP

STEAM SUPPLY

SCALE POCKET

SCALE POCKET

STEAM CONTROL

VALVE, 2 POSITION

STEAM CONTROL VALVE

NOTES:

1. UNIT MOUNTED THERMOSTAT SHALL MAINTAIN SPACE TEMPERATURE

BY CYCLING THE FAN. THE CONTROL VALVE SHALL BE INTERLOCK

WITH THE FAN.

M

IN

M

IN

M

IN

M

IN

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:2

A

M

01-MG-502

MECHANICAL DETAILS

9 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

NTS

PIPE HANGERS

NTS

SECURING HANGER RODS IN CONCRETE

NTS

SEISMIC BRACING FOR EQUIPMENT

NTS

SUPPLY DUCT TAKEOFF - AIR TERMINAL UNIT

NTS

FAN COIL UNIT (STEAM) - PIPING CONNECTIONS

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:2

A

M

01-MG-503

MECHANICAL DETAILS

10 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

NTS

FIGURE 6.4.1.5-6 CABLE AND RIGID BRACE ATTACHMENTS TO STRUCTURE

NTS

FIGURE 6.4.1.5-7 HANGER ATTACHMENT DETAILS

NTS

FIGURE 6.4.1.6-2 SUSPENDED EQUIPMENT

NTS

FIGURE 6.4.3.1-11 RIGID BRACING - SINGLE PIPE TRANSVERSE

NTS

FIGURE 6.4.3.1-12 CABLE BRACING - SINGLE PIPE TRANSVERSE

GENERAL NOTES

1. REFER TO 01-MG-001 FOR SEISMIC RESTRAINT NOTES AND

FACILITY-SPECIFIC SEISMIC DESIGN BASIS PARAMETERS.

2. FIGURES ARE FROM FEMA E-74 REDUCING THE RISKS OF

NONSTRUCTURAL EARTHQUAKE DAMAGE - A PRACTICAL

GUIDE, DECEMBER 2012.

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:2

A

M

01-MG-504

MECHANICAL DETAILS

11 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

NTS

FIGURE 6.4.3.1-13 RIGID BRACING - SINGLE PIPE ALTERNATE TRANSVERSE

NTS

FIGURE 6.4.3.1-14 RIGID BRACING - SINGLE PIPE LONGITUDINAL

NTS

FIGURE 6.4.3.1-15 RIGID BRACING - TRAPEZE SUPPORTED PIPING

NTS

FIGURE 6.4.3.1-16 CABLE BRACING - TRAPEZE SUPPORTED PIPING

4 NTS

FIGURE 6.4.6.1-8 SUSPENDED DUCTWORK

1. REFER TO 01-MG-001 FOR SEISMIC RESTRAINT NOTES AND

FACILITY-SPECIFIC SEISMIC DESIGN BASIS PARAMETERS.

2. FIGURES ARE FROM FEMA E-74 REDUCING THE RISKS OF

NONSTRUCTURAL EARTHQUAKE DAMAGE - A PRACTICAL

GUIDE, DECEMBER 2012.

GENERAL NOTES

e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing # of

657-19-108JB

VA Health Care System Approval:

Revision: Date:

ARCHITECT/ENGINEER:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM VEG 19.8

100% CONTRACT DOCUMENTS FOR BIDDING

11/02/2019

JEFFERSON BARRACKS

1 JEFFERSON BARRACKS DRIVE - ST. LOUIS, MO 63125

/3

/2

:0

:2

A

M

01-MG-601

MECHANICAL SCHEDULES

12 53

REPLACE FAN COIL UNITS

BUILDING 1

DD RDT

1. EE NUMBERS ARE IDENTIFICATION NUMBERS SPECIFIC TO VA

EQUIPMENT. GC SHALL PROVIDE UPDATED EE LIST OF ALL

EQUIPMENT REMOVED TO VA COR.

GENERAL NOTES

NOTES

1. SINGLE PHASE, 115V, ECM MOTOR SHALL BE PROVIDED.

2. 2-WAY MODULATING VALVE SHALL BE PROVIDED PER UTILITY SERVICE.

3. SEE MI SHEETS FOR CONTOLS.

4. ENSURE UNIT IS MOUNTED HIGH ENOUGH TO ALLOW FOR GRAVITY DRAINAGE.

5. EE # IS LISTED ON THE EXSITNG UNITS. HOWEVER, NOT ALL WERE IDENTIFIED DURING THE SURVEY. CONTRACTOR SHALL PROVIDE A LIST OF EE NUMBERS TO ALL EQUIPMENT REMOVED TO VA COR SO THAT THE MAINENANCE LOG CAN BE UPDATED.

6. SELECTIONS BASED ON AN ALTITUDE OF 510 FT.

7. INCLUDE 3/4" DRAIN AND 8"x6" DUCTED OA INLET TO FCU PLENUM.

COOLING ONLY TWO PIPE FAN COIL UNIT SCHEDULE

MARK

EE

NUMBER

LOCATION TYPE

HIDDEN/

RECESSED/

EXPOSED

BASIS OF

DESIGN (OR

APPROVED

EQUAL)

UNIT

SIZE

FAN AIR

FLOW

OUTSIDE

AIR

FLOW

EXTERNAL

APD (IN WG)

COOLING REQUIREMENTS CIRCULATING WATER

FILTER

MERV

RATING

FAN

MOTOR

POWER

(HP)

REMARKSMIN SENS

CAPACITY

(MBTUH)

MIN TOTAL

CAPACITY

(MBTUH)

WATER

FLOW RATE

(GPM)

EWT

(°F)

WPD

(FT)

RUNOUT

SIZE (IN)

FCU-3-12 H306 HORIZONTAL HIDDEN DAIKIN 10 700 CFM 125 CFM 0.8 13.6 16.5 3.3 45 3 0.75 8 0.25 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-12A W316 HORIZONTAL HIDDEN DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-13 H306 HORIZONTAL HIDDEN DAIKIN 10 700 CFM 125 CFM 0.8 13.6 16.5 3.3 45 3 0.75 8 0.25 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-14 W312 HORIZONTAL HIDDEN DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-15 H306 HORIZONTAL HIDDEN DAIKIN 10 700 CFM 125 CFM 0.8 13.6 16.5 3.3 45 3 0.75 8 0.25 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-16 W311 HORIZONTAL HIDDEN DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-17 W310 HORIZONTAL HIDDEN DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-18 H309 HORIZONTAL HIDDEN DAIKIN 10 700 CFM 125 CFM 0.8 13.6 16.5 3.3 45 3 0.75 8 0.25 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-19 H309 HORIZONTAL HIDDEN DAIKIN 10 700 CFM 125 CFM 0.8 13.6 16.5 3.3 45 3 0.75 8 0.25 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-20 H309 HORIZONTAL HIDDEN DAIKIN 10 700 CFM 125 CFM 0.8 13.6 16.5 3.3 45 3 0.75 8 0.25 1, 2, 3, 4, 5, 6, 7, 8

FCU-3-46 3E21A HORIZONTAL EXPOSED DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B1 12128 GW13 HORIZONTAL RECESSED DAIKIN 4 400 CFM 100 CFM 0.8 7.6 8 1.6 45 1.5 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B2 GW13 HORIZONTAL RECESSED DAIKIN 4 400 CFM 100 CFM 0.8 7.6 8 1.6 45 1.5 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B3 14125 GW16 HORIZONTAL HIDDEN DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B4 14129 GW12 HORIZONTAL RECESSED DAIKIN 4 300 CFM 55 CFM 0.8 6.5 7.3 1.7 45 1.7 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B4A 14131 GW12A HORIZONTAL RECESSED DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.9 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B5 14133 GW10 HORIZONTAL RECESSED DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.9 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B5A GW17 HORIZONTAL EXPOSED DAIKIN 2 236 CFM 70 CFM 0.8 5.1 5.5 1.9 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B5B GW17A HORIZONTAL EXPOSED DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B5C GW15 HORIZONTAL HIDDEN DAIKIN 4 300 CFM 55 CFM 0.8 6.5 7.3 1.7 45 1.7 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B6 14445 GW09 HORIZONTAL RECESSED DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.9 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B8 GW08 HORIZONTAL EXPOSED DAIKIN 2 208 CFM 55 CFM 0.8 4.5 5.1 1.5 45 1.1 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B15 GC17A HORIZONTAL HIDDEN DAIKIN 10 1065 CFM 120 CFM 0.8 23 30 7 45 11.4 1 8 0.25 1, 2, 3, 4, 5, 6, 7, 8

FCU-B33 14127 GW14 HORIZONTAL RECESSED DAIKIN 4 400 CFM 100 CFM 0.8 7.6 8 1.7 45 1.5 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

FCU-B34 GC22 HORIZONTAL EXPOSED DAIKIN 6 500 CFM 65 CFM 0.8 9.9 10.6 2.1 45 1.4 0.75 8 0.125 1, 2, 3, 4, 5, 6, 7, 8

Grand total: 116

COOLING ONLY TWO PIPE FAN COIL UNIT SCHEDULE

MARK

EE

NUMBER

LOCATION TYPE

HIDDEN/

RECESSED/

EXPOSED

BASIS OF

DESIGN (OR

AP…

This is the start of the file's text. The full file is on GovTribe.