36C25519R0081-0001002.pdf

PDF 23 MB Posted

Attached to
Correct Basement and Pharmacy Deficiencies (VA-19-00055107) 589A4-18-130
Solicitation number
36C25519R0081
Issued by

About this file

36C25519R0081 0001 Drawings- Correct Basement and Pharmacy Deficiencies-Vol 2.pdf

View the file

Other files

File Type Posted
36C25519R0081-0003000.docx DOCX document
36C25519R0081-0002002.pdf PDF
36C25519R0081-0002001.pdf PDF
36C25519R0081-0002000.docx DOCX document
36C25519R0081-0002003.pdf PDF
36C25519R0081-0001001.pdf PDF
36C25519R0081-0001000.docx DOCX document
36C25519R0081-004.pdf PDF
36C25519R0081-001.docx DOCX document
36C25519R0081-003.pdf PDF
36C25519R0081-005.pdf PDF
36C25519R0081-002.pdf PDF
36C25519R0081-000.docx DOCX document
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

E-001

ELECTRICAL NOTES AND SYMBOLS

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

D

D

D

D D

D

D D D

D D D

D D D

D

D D

D D

D

LPB-M4A-120VC

LPB-L4-277VC

PPB-M4-120VC

LPB-M4-120VC

E D D D D D D D

S1

D2D2

NOTE: REMOVE ALL EXISTING

BRANCH CIRCUIT WIRING SERVING

AREA BACK TO POINT OF

SUPPLY AS REQUIRED.

D2D3D3 D3

D3

WAP

D3D3D3

W

KLMNNaP w 6.3

6.2

Q

E 1.10

W2

W 2.8

W 3.7

W 4.6

5.8

5.4

5.7

W 5.5

E 1.11

EXISTING CORRIDOR LIGHTING

CIRCUIT SHALL BE REUSED AS

NECCESSARY FOR CONNECTION

TO PROPOSED LIGHT FIXTURES

AS INDICATED ON LIGHTING

PLAN. EXISTING CONTROLS

SHALL REMAIN FOR REUSE.

D

D

DEMOLITION PLAN NOTES:

1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE

ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR

SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING

REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION

TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,

LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.

COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.

PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS

BEING REMOVED.

2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND

CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING

CONDUIT IN WALL OR FLOOR WHERE CUT.

3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE

SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND

MAY REQUIRE REMOVAL.

4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING

ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF

EQUIPMENT AND ELECTRICAL DEVICES, ETC.

5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,

THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT

OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED

TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE

SYSTEM.

6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL

BE REMOVED, UNLESS NOTED OTHERWISE.

7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE

BEING REMOVED FROM EXISTING WALLS TO REMAIN.

8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR

TO BEGINNING WORK.

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO

REMAIN AND NOT VACATED.

COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.

ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY

CONTRACTOR.

PROJECT

LOCATION

ACA

ACA

ACA

ACA

H

ACA

G

D D D

PROJECT

LOCATION

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

ED101

ELECTRICAL DEMOLITION PLANS -

PARTIAL BASEMENT & SECOND

FLOOR PLANS

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

N

1/8" = 1'-0"

DEMOLITION PLAN - PARTIAL BASEMENT FLOOR PLAN

KEYED NOTES:

D2 RELOCATE EXISTING ACCESS CONTROL DEVICES ASSOCIATED WITH EXISTING

CORRIDOR TO BE REMOVED. PRESERVE EXISTING DEVICES AND CABLING

DURING DEMOLITION AS REQUIRED.

D3 EXISTING DEVICE TO BE REMOVED AND REINSTALLED IN EXISITNG LOCATION.

REMOVE CABLING AND COIL ABOVE CEILING FOR FUTURE USE. PRESERVE AND

PROTECT DEVICES AND ASSOCIATED CABLING DURING CONSTRUCTION.

S1 PROVIDE P.A. SPEAKER FLUSH IN CEILING AT LOCATION AS INDICATED. PROVIDE

CABLING AS REQUIRED TO CONNECT TO EXISTING SYSTEM. VERIFY ALL

REQUIREMENTS PRIOR TO ROUGH-IN.

N

1" = 100'-0"

KEYPLAN - BASEMENT4' 8' 16'

1/8" = 1'-0"

0'

N

1/8" = 1'-0"

DEMOLITION PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'

1/8" = 1'-0"

0'

N

1" = 100'-0"

KEYPLAN SECOND FLOOR

NOTES:

1. REMOVE EXISTING LED LIGHT FIXTURES AND RETURN TO OWNER FOR

FUTURE USE.

2. EXISTING CAT6 CABLING LOCATED WITHIN SPACE SHALL BE COILED IN

PLACE ABOVE ACCESSIBLE CEILING FOR FUTURE USE. THIS INCLUDES BUT

NOT LIMITED TO ALL GREEN, PINK, AND ORANGE JACKETED CABLING.

COORDINATE WITH COR.

05/09/2019 623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

LIGHTING PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF

FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF

ONE HOUR.

4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT

LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH

ARCHITECT PRIOR TO ROUGH-IN.

TLT.

B011B

TLT.

B011H

ON-CALL RM. 1

B011A

ON-CALL RM. 2

B011C ON-CALL RM. 3

B011D

TLT.

B011E

ON-CALL RM. 4

B011F

ON-CALL RM. 5

B011G

DOUGLASS CLASSROOM

(EXTG)

B007

ELEC. (EXTG)

B011J

HAS

B013

ON-CALL ROOMS/LOUNGE

B011

OFFICE

B006

W2

HB

W2

HB

HB

W2

LPB-M4A-120VC

LPB-L4-277VC

PPB-M4-120VC

LPB-M4-120VC

LACTATION

B009

S1

S1

S1

S1 S1

S1 S1

S1

S1 S1

S1S1

S1 S1 S1

S1

S1

S1

S1

S1

S1

S1 S1

S1

S1

S1

S1S1S1S1

S1S1S1

S1 S1 S1

S1S1S1S1

S1 S1 S1 S1

S1

S1S1S1

E

X1

S1

CHIEF

B006A

ASSOC.CHIEF

B006B

S1

S1

S1

L1

L1

VTS/TRVL SUPRVISOR

B013A

L1

L1

OFFICE

B010

OFFICE

B010A

OFFICE

B006C

S1

S1

S1 S1

S1

S1

S1 S1

S1

S1

S1

S1

S1

S1 S1 S1 S1

L1

L1

NL NL

KLMNNaP w 6.3

6.2

Q

E 1.10

W2

W 2.8

W 3.7

W 4.6

5.8

5.4

5.7

W 5.5

E 1.11

LPB-L4-277VC

L5

L4 S1S1S1S1

NL

L4 L3

LPB-L4-277VC

L5

NL

X1

X1 L6

PROJECT

LOCATION

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO

REMAIN AND NOT VACATED.

COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.

ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY

CONTRACTOR.

ACA

ACA

ACA

ACA

H

ACA

G

M1 M1 M1

M1

CSCA

F236L2

PROJECT

LOCATION

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EL101

LIGHTING PLANS - PARTIAL

BASEMENT & SECOND FLOOR PLANS

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

N

1/8" = 1'-0"

LIGHTING PLAN - PARTIAL BASEMENT PLAN

KEYED NOTES:

L1 PROVIDE INTERLOCK WIRING BETWEEN LOCAL OCCUPANCY SENSORS PER

MANUFACTURERS REQUIREMENTS.

L2 CONNECT TO EXISTING 277V. 20A. LIGHTING CIRCUIT SERVING EXISTING AREA.

L3 CONNECT TO NEAREST LIFE SAFETY EMERGENCY 277V. 20A. LIGHTING CIRCUIT

SERVING EXISTING AREA.

L4 CONNECT TO EXISTING 277V. 20A. CORRIDOR LIGHTING CIRCUIT SERVING AREA.

CONNECT TO EXISTING CONTROLS AS REQUIRED.

L5 PROVIDE 277V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANEL AS INDICATED.

MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED. UPDATE PANEL

DIRECTORY.

L6 INSTALL EXIT SIGN IN EXISTING LOCATION. CONNECT TO EXISTING LIFE SAFETY

CIRCUIT AS REQUIRED.

N

1" = 100'-0"

KEYPLAN - BASEMENT4' 8' 16'

1/8" = 1'-0"

0'

N

1/8" = 1'-0"

LIGHTING PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'

1/8" = 1'-0"

0'

N

1" = 100'-0"

KEYPLAN SECOND FLOOR

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EL501

LIGHTING DETAILS

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EL601

LIGHT FIXTURE SCHEDULE

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

TLT.

B011B TLT.

B011H

ON-CALL RM. 1

B011A

ON-CALL RM. 2

B011C

ON-CALL RM. 3

B011D

TLT.

B011E

ON-CALL RM. 4

B011F

ON-CALL RM. 5

B011G

ELEC. (EXTG)

B011J

HAS

B013

ON-CALL ROOMS/LOUNGE

B011

OFFICE

B006

LACTATION

B009

LPB-M4A-120VC

LPB-L4-277VC

PPB-M4-120VC

LPB-M4-120VC

CT

PRINTER

PRINTER

CT

CT

ASSOC.CHIEF

B006B

CHIEF

B006A

PP

PP

VTS/TRVL SUPRVISOR

B013A

TV

TV TV

TV

TV

CT 46"

60"

TV

U.C. REF.

CT

OFFICE

B010

OFFICE

B010A

OFFICE

B006C

MICROWAVE REF.

TV

KLMNNaP w 6.3

6.2

Q

E 1.10

W2

W 2.8

W 3.7

W 4.6

5.8

5.4

5.7

W 5.5

E 1.11

P3

P4

LPB-M4A-120VC

LPB-M4A-120VC

LPB-M4A-120VC

LPB-M4A-120VC

LPB-M4A-120VC

P4

P4

P4

P4

LPB-M4A-120VC

LPB-M4A-120VCLPB-M4A-120VC

LPB-M4A-120VC

LPB-M4A-120VC

P4

P4

P4

P4 P4

LPB-M4A-120VC

P4

LPB-M4-120VC

LPB-M4-120VC

P4

P5

LPB-M4-120VC

P4LPB-M4-120VC

P4

LPB-M4-120VC

P4

LPB-M4-120VC

P4

P4

LPB-M4-120VC

P4LPB-M4-120VC

LPB-M4-120VC

LPB-M4-120VC

LPB-M4-120VC

P4

P4

LPB-M4-120VC

P4

P4

LPB-M4-120VC

P4

LPB-M4-120VC

P4

LPB-M4-120VC

P5 LPB-M4-120VC

P5 P4

LPB-M4-120VC

P4

LPB-M4-120VC

P7

P8

P8

P7

P8 P7

P6

P1

PPB-M4-120VC

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING

OF ONE HOUR.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE

LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON

OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A

HORIZONTAL DISTANCE OF 24 INCHES.

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO

REMAIN AND NOT VACATED.

COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.

ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY

CONTRACTOR.

PROJECT

LOCATION

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EP101

POWER PLAN - PARTIAL BASEMENT

PLAN

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

N

1/8" = 1'-0"

POWER PLAN - PARTIAL BASEMENT PLAN

KEYED NOTES:

P1 PROVIDE 120V. CONNECTION TO DOOR AS REQUIRED FOR ACCESS CONTROL

SYSTEM. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.

P3 EXTEND EXISTING 12OV. CONNECTION TO DOOR AS REQUIRED FOR CONNECTION

TO RELOCATED ACCESS CONTROL DEVICES. VERIFY ALL REQUIREMENTS PRIOR

TO RELOCATION.

P4 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANEL AS INDICATED.

MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED. UPDATE PANEL

DIRECTORY.

P5 PROVIDE 120V. 20A. 1P. GFCI CIRCUIT BREAKER IN EXISTING PANEL AS

INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED.

UPDATE PANEL DIRECTORY.

P6 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN NEAREST EMERGENCY

PANELBOARD AS INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING

AS REQUIRED. UPDATE PANEL DIRECTORY.

P7 PROVIDE 120V. CONNECTION TO PLUMBING FIXTURE SENSOR. COORDINATE

EXACT LOCATION WITH PLUMBER PRIOR TO ROUGH-IN.

P8 PROVIDE FUSTAT ABOVE ACCESSIBLE CEILING FOR DISCONNECTING MEANS TO

ALL PLUMBING SENSORS IN ROOM.

N

1" = 100'-0"

KEYPLAN - BASEMENT4' 8' 16'

1/8" = 1'-0"

0'

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

PROJECT

LOCATION

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING

OF ONE HOUR.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE

LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON

OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A

HORIZONTAL DISTANCE OF 24 INCHES.

ACA

ACA

ACA

ACA

H

ACA

G

ACA

F

ACA

E.1

ACA

E

ACA

D8

ACA

D7

WALL MOUNTED MONITOR

CT 46"

RELOCATED FUME HOOD

CT

WALL MOUNTED CPU. COORDINATE EXACT

LOCATION WITH COR PRIOT TO ROUGH-IN.

P1

46"

CSCA

F236

ELECT CLOSET

E252

CT

LABEL PRINTER

PP2-D10-120VC

LP2-D10-277VC

LP2-D10-277VN

PP2-D10-120VN

PP2-D10-120VC

P6

PP2-D10-120VC

P6

P6

PP2-D10-120VN

PP2-D10-120VC

P6

PP2-D10-120VN

P6P7

P8

MEDS REF.

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO

REMAIN AND NOT VACATED.

COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.

ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY

CONTRACTOR.

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EP102

POWER PLAN - PARTIAL SECOND

FLOOR PLAN

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

N

1" = 100'-0"

KEYPLAN SECOND FLOOR

KEYED NOTES:

P1 PROVIDE 120V. CONNECTION TO DOOR AS REQUIRED FOR ACCESS CONTROL

SYSTEM. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.

P6 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN NEAREST EMERGENCY

PANELBOARD AS INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING

AS REQUIRED. UPDATE PANEL DIRECTORY.

P7 PROVIDE 120V. CONNECTION TO PLUMBING FIXTURE SENSOR. COORDINATE

EXACT LOCATION WITH PLUMBER PRIOR TO ROUGH-IN.

P8 PROVIDE FUSTAT ABOVE ACCESSIBLE CEILING FOR DISCONNECTING MEANS TO

ALL PLUMBING SENSORS IN ROOM.

N

1/8" = 1'-0"

POWER PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'

1/8" = 1'-0"

0'

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

ACA

5.6

ACA

ACA

6.3

ACA

ACA

ACA

ACA

H

ACA

G

ACA

F

ACA

E.1

ACA

E

ACA

D8

ACA

D7

(EX)EF-24

EF-CHEMO

(EX)EF-21

(EX)EF-22

(EX)12"ø

WP

P2

DEVICE ON

ROOF AT UNIT

RB-2-28

POWER PLAN NOTES:

1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH

INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF

THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.

WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,

JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.

SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.

2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN

ALL CONDUITS.

3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE

MECHANICAL EQUIPMENT CONNECTION SCHEDULE.

4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING

OF ONE HOUR.

5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE

LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON

OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A

HORIZONTAL DISTANCE OF 24 INCHES.

AREA

SHOWN

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EP106

POWER PLAN - PARTIAL ROOF PLAN

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

N

1/8" = 1'-0"

POWER PLAN - PARTIAL ROOF PLAN 4' 8' 16'

1/8" = 1'-0"

0'

KEYED NOTES:

P2 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN NEAREST EXISITING 120V NORMAL

POWER PANEL. MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED.

UPDATE PANEL DIRECTORY.

N

1" = 100'-0"

KEYPLAN - ROOF

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

BRANCH CIRCUIT/DISTRIBUTION PANEL

DISCONNECT SWITCH

CONTROL CENTER BREAKER/SWITCH

SWITCHBOARD/DISTRIBUTION PANEL/MOTOR

1/8"

1/4"

1/4"

PANEL K

PHASE B: RED

PHASE C: BLUE

PHASE A: BLACK

10,000 A.I.C.

120/208V.,3∅,4W.

1/4"

1/8"

1/8" 1/8"

1/4"

3/8"

GROUND: GREEN

NEUTRAL: WHITE

RTU #1

LPJ 200AMP

SERVES

1/8"

1/4" RTU-1

SERVES

ISO.GRD.: GRN/YEL

FED FROM DP:**1/4"

FED FROM DP:**1/4"

METAL STUD

CONDUITS

RECEPTACLE

EQUIPMENT GROUND

CONDUCTOR

GROUND SCREW ON

WIRING DEVICE

GROUND SCREW IN

OUTLET BOX

CONDUIT

4 SQUARE OUTLET BOX

DRYWALL

PLASTER RING

PLASTER RING

RECEPTACLE

OUTLET BOX SECURED

TO BOX SUPPORT

GROUND SCREW IN

OUTLET BOX

WIRE NUT (TYP.)

STUD TO STUD BOX

SUPPORT, B-LINE #BB2

SERIES OR EQUAL.

NEUTRAL

CONDUCTORS

HOT CONDUCTORS

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EP501

POWER DETAILS

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

NO SCALE

TYPICAL HEALTHCARE NAME PLATES

NO SCALE

TYPICAL RECEPTACLE MOUNTING DETAIL

NO SCALE

TYPICAL TELEVISION OUTLET DETAIL

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EP601

ELECTRICAL SCHEDULES

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

EaFGGaHJJb Ja

TLT.

B011B

TLT.

B011H

ON-CALL RM. 1

B011A

ON-CALL RM. 2

B011C

ON-CALL RM. 3

B011D

TLT.

B011E

ON-CALL RM. 4

B011F

ON-CALL RM. 5

B011G

DOUGLASS CLASSROOM

(EXTG)

B007

ELEC. (EXTG)

B011J

HAS

B013

ON-CALL ROOMS/LOUNGE

B011

OFFICE

B006

PRINTER

PRINTER

LACTATION

B009

PP

PP

ASSOC.CHIEF

B006B

CHIEF

B006A

S1

WAP

TV

TVTV

TV

VTS/TRVL SUPRVISOR

B013A

TV

TV

WAP

S1

S1

WAP

OFFICE

B010

OFFICE

B010A

OFFICE

B006C

S1

TV

KLMNNaP w 6.3

6.2

Q

E 1.10

W2

W 2.8

W 3.7

W 4.6

5.8

5.4

5.7

W 5.5

E 1.11

I.T. CLOSET

A056A

S9S9

S3

S3

S6S6S6

S9

WAP

S2S2S2

DMARC

A060

EXISTING P.A.

EQUIPMENT RACK

EXISTING PHONE

BACKBOARD WITH

PUNCH-DOWN BLOCKS

(3) EXISTING

DATA RACKS

S6

FSD

FSD

FSDFSD FSD FSD

LPB-M4-120VC

E

S8

P4

FSD

FSD

FSD

A056A C

A056A C

A056A C

A056A C

A056A C

A056A C

A056A CA056A C

A056A C A056A C

A056A C

A056A C

A056A C A056A C

A056A C

A056A C

A056A C

A056A C

A056A C

A056A C

A056A C

A056A A

A056A K

A056A B A056A C

A056A C A056A C

A056A C

A056A C

A056A C

A056A C

A056A C

A056A A

A056A C

A056A C

A056A C A056A C

A056A B

A056A A

A056A B

A056A A

A056A B

A056A A A056A B

A056A A

A056A C

A056A A

PROVIDE CARD READER/

CYPHER LOCK COMBINATION

DEVICE AS REQUIRED.

A056A K

A056A K

SYSTEMS PLAN NOTES:

1. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A

T-RATING OF ONE HOUR.

2. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

3. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL

BE LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET

BOXES ON OPPOSITE SIDES OF THE RATED WALLS SHALL BE

SEPARATED BY A HORIZONTAL DISTANCE OF 24 INCHES.

4. WHERE THE SAME DEVICE IS SHOWN IN THE SAME LOCATION ON

BOTH THE POWER AND SYSTEMS PLAN, ONLY ONE DEVICE IS

REQUIRED. PROVIDE BOTH POWER AND SYSTEMS WIRING AS SHOWN.

5. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED PER THE

REQUIREMENTS OF NFPA 72. DEVICES SHOWN INDICATE THE DESIGN

INTENT AND SHALL BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER

SHALL PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR

DEVICES REQUIRED BY THE AUTHORITY HAVING JURISDICTION.

6. PROVIDE J-HOOKS FOR DATA CABLING PATHWAY AS REQUIRED.

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO

REMAIN AND NOT VACATED.

COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.

ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY

CONTRACTOR.

PROJECT

LOCATION

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EY101

SYSTEMS PLAN - PARTIAL BASEMENT

PLAN

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

N

1/8" = 1'-0"

SYSTEMS PLAN - PARTIAL BASEMENT PLAN

KEYED NOTES:

P4 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANEL AS INDICATED.

MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED. UPDATE PANEL

DIRECTORY.

S1 PROVIDE P.A. SPEAKER FLUSH IN CEILING AT LOCATION AS INDICATED. PROVIDE

CABLING AS REQUIRED TO CONNECT TO EXISTING SYSTEM. VERIFY ALL

REQUIREMENTS PRIOR TO ROUGH-IN.

S2 REINSTALL EXISTING ACCESS CONTROL DEVICES AT CORRIDOR DOOR AS

REQUIRED. EXTEND, REROUTE, AND RECONNECT EXISTING CABLING AS

NECESSARY TO COMPLETE SYSTEM INSTALLATION.

S3 PROVIDE CAT6 CABLING ROUTED FROM OUTLET TO DATA RACK LOCATED IN I.T.

CLOSET A056A. PROVIDE DATA TERMINATION ON ASSOCIATED PATCH PANEL AS

REQUIRED. PROVIDE ADDITIONAL PATCH PANELS AS NECESSARY. PROVIDE

PHONE TERMINATION ON PUNCH-DOWN BLOCK LOCATED ON PHONE

BACKBOARD. VERIFY ALL REQUIREMENTS WITH I.T. DEPARTMENT PRIOR TO

ROUGH-IN.

S6 REINSTALL EXISTING DEVICE IN CEILING AT EXISTING LOCATION. RECONNECT

EXISTING CABLING AS REQUIRED TO COMPLETE SYSTEM INSTALLATION

S8 PROVIDE CAT6 CABLING AS REQUIRED FROM EXISTING LENNEL ACCESS

CONTROL PANEL LOCATED IN STORAGE E005 TO DOOR AS INDICATED. VERIFY

ALL REQUIREMENTS PRIOR TO ROUGH-IN.

S9 PROVIDE OUTLET WITH (1) USB PORT AND (1) HDMI PORT FOR CONNECTION TO

WALL MOUNTED MONITOR. PROVIDE USB CABLE AND HDMI CABLE ROUTED TO

WALL MOUNTED CPU OUTLET LOCATED OUTSIDE PHARMACY. COORDINATE

EXACT LOCATION AND ALL REQUIREMENTS PRIOR TO ROUGH-IN.

N

1" = 100'-0"

KEYPLAN - BASEMENT4' 8' 16'

1/8" = 1'-0"

0'

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

ACA

ACA

ACA

ACA

H

ACA

G

ACA

F

ACA

E.1

ACA

E

ACA

D8

ACA

D7

E

WALL MOUNTED CPU

WALL MOUNTED MONITOR

RELOCATED FRAME HOOD

MEDS

REFRIGERATOR

S1 CSCA

F236

S7

S5

CT

LABEL PRINTER

ELECTRICAL

E202

TELE/ DATA

E203

EXISTING PHONE BACKBOARD

WITH PUNCH-DOWN BLOCKS

(2) EXISTING DATA RACKS

EXISTING P.A.

AMPLIFIER

EXISTING LENNEL

ACCESS CONTROL

PANEL

E203 F 46"

S10 S9

S11S11

E203 F

E203 F

SYSTEMS PLAN NOTES:

1. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE

SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE

OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A

T-RATING OF ONE HOUR.

2. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,

COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE

CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.

3. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL

BE LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET

BOXES ON OPPOSITE SIDES OF THE RATED WALLS SHALL BE

SEPARATED BY A HORIZONTAL DISTANCE OF 24 INCHES.

4. WHERE THE SAME DEVICE IS SHOWN IN THE SAME LOCATION ON

BOTH THE POWER AND SYSTEMS PLAN, ONLY ONE DEVICE IS

REQUIRED. PROVIDE BOTH POWER AND SYSTEMS WIRING AS SHOWN.

5. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED PER THE

REQUIREMENTS OF NFPA 72. DEVICES SHOWN INDICATE THE DESIGN

INTENT AND SHALL BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER

SHALL PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR

DEVICES REQUIRED BY THE AUTHORITY HAVING JURISDICTION.

6. PROVIDE J-HOOKS FOR DATA CABLING PATHWAY AS REQUIRED.

PROJECT

LOCATION

SCOPE OF WORK LEGEND

SHADED AREA NOT IN SCOPE OF WORK

DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO

REMAIN AND NOT VACATED.

COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.

ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY

CONTRACTOR.

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EY102

SYSTEMS PLAN - PARTIAL SECOND

FLOOR PLAN

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

N

1/8" = 1'-0"

SYSTEMS PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'

1/8" = 1'-0"

0'

KEYED NOTES:

S1 PROVIDE P.A. SPEAKER FLUSH IN CEILING AT LOCATION AS INDICATED. PROVIDE

CABLING AS REQUIRED TO CONNECT TO EXISTING SYSTEM. VERIFY ALL

REQUIREMENTS PRIOR TO ROUGH-IN.

S5 PROVIDE OUTLET WITH (2) USB PORTS AND (1) HDMI PORT FACEPLATE AT 18” AFF

ADJACENT TO DATA OUTLET SERVING WALL MOUNTED CPU. PROVIDE (1) USB

CABLE AND (1) HDMI CABLE ROUTED FROM OUTLET TO WALL MOUNTED MONITOR

LOCATED IN PHARMACY AS REQUIRED VIA 1-1/4” CONDUIT. PROVIDE (1) USB

CABLE FROM OUTLET TO LABEL PRINTER LOCATED IN PHARMACY AS REQUIRED

VIA 1-1/4” CONDUIT.

S7 PROVIDE CAT6 CABLING ROUTED TO EXISTING LENNEL ACCESS CONTROL PANEL

LOCATED IN ELECTRICAL CLOSET AS INDICATED. VERIFY ALL REQUIREMENTS

WITH EXISTING ACCESS CONTROL SYSTEM AS NECESSARY.

S9 PROVIDE OUTLET WITH (1) USB PORT AND (1) HDMI PORT FOR CONNECTION TO

WALL MOUNTED MONITOR. PROVIDE USB CABLE AND HDMI CABLE ROUTED TO

WALL MOUNTED CPU OUTLET LOCATED OUTSIDE PHARMACY. COORDINATE

EXACT LOCATION AND ALL REQUIREMENTS PRIOR TO ROUGH-IN.

S10 PROVIDE OUTLET WITH (2) CAT6 CABLES AND (1) USB CABLE FOR CONNECTION

TO LABEL PRINTER. PROVIDE CAT6 CABLING ROUTED TO DATA RACK AS

INDICATED AND USB CABLE ROUTED TO WALL MOUNTED CPU LOCATED OUTSIDE

PHARMACY. COORDINATE EXACT LOCATION AND ALL REQUIREMENTS PRIOR TO

ROUGH-IN.

S11 PROVIDE 1-1/4” CONDUIT BETWEEN OUTLETS AS REQUIRED FOR LOW-VOLTAGE

CABLING PATHWAY. PROVIDE PULL-ROPE IN CONDUIT.

N

1" = 100'-0"

KEYPLAN SECOND FLOOR

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

4'-0" 4'-0"

CEILING

PROVIDE MOUNTING AND FINISHING PLATES

AND ACCCESSORIES REQUIRED FOR A FULLY

SEALED AND FIRE RATED SYSTEM.

CORRIDOR SIDE ROOM SIDE

ROUTE CABLES IN CABLE

TRAY AS SHOWN ON PLANS

FIRE RATED THRU-WALL PATHWAY EQUAL TO LEGRAND

EZ-PATH SERIES 44. PROVIDE MODULE SIZE AS REQUIRED

FOR NUMBER OF CABLES. INSTALL PER MANUFACTURER

RECCOMENDATION.

TYPICAL J-HOOK

SUPPORTS TO BE

USED WITH-IN

6"

SEE J-HOOK

DETAIL

INDIVIDUAL ROOMS.

BOND CABLE TRAY TO EACH CONDUIT SLEEVE

VIA #6 BARE COPPER AWG GROUND WIRE.

4'-0" 4'-0"

CEILING

12" MINIMUM CONDUIT NIPPLE.

SEE GENERAL NOTE #12.

BUSHINGS

SEAL & FIREPROOF

FIREPROOF AFTER

CABLE INSTALLATION

SEAL & FIREPROOF

SUPPORTS

TYPICAL

J-HOOK

6"(MIN.)

48" AFF

DEVICE SHALL NOT BE MORE THAN

46" AFF TO CENTERLINE, TOP OF

SPECIFICATIONS.

WITH HARDWARE

OPEN. COORDINATE

OR CLOSURE/HOLD

MAGNETIC HOLD OPEN

(TYP.)

DETECTOR

SMOKE

FIRE ALARM DEVICE MOUNTING CRITERIA

SPECIFIED OTHERWISE ON THE DRAWINGS.

UNLESS MOUNTING HEIGHTS HAVE BEEN

THESE GUIDELINES SHALL BE USED

AUDIO/VISUAL

GENERAL NOTE

PULL STATION

REFER TO THE VISUAL UNIT.

AUDIO/VISUAL UNIT

AUDIO UNIT

VISUAL UNIT

ACCEPTABLE HERE

TOP OF DETECTOR

IN THIS AREA

DO NOT PLACE DETECTOR

AND AIR DIFFUSER/REGISTER/GRILL

MAINTAIN 36" BETWEEN SMOKE DETECTOR

STATION

PULL

12" 4"

90"

80"

46"

80" TO BOTTOM

AUDIO ONLY

6"(MIN.)

6"(MIN.)

90" TO TOP

AUDIO ONLYVISUAL ONLY

80" TO BOTTOM

FINISH FLOOR

CEILING

MAX. OF 5'-0", MIN. OF "d"

BUT NOT LESS THAN 12"

DETECTORS ON ONE SIDE

OR BOTH SIDES OF DOOR

AS REQUIRED BY NFPA 72.

DOOR HEADER "d"

HEIGHT OF

AIR DIFFUSER

TOP OF DEVICE 90 INCHES ABOVE

HIGHEST FLOOR LEVEL OR 6 INCHES

BELOW CEILING WHICH EVER IS LOWER.

BOTTOM OF DEVICE 80 INCHES ABOVE

HIGHEST FLOOR LEVEL OR 6 INCHES

BELOW CEILING WHICH EVER IS LOWER.

4"

ACP

SUPPLY

IFP

CEILING.

CR

120V.

4 5 6

INSTALL LABEL TO

INDICATE PANEL NAME

AND CIRCUIT.

BMS

SYSTEM MANUFACTURER.

QUANTITY AND TYPE OF CABLE PER

ACCESS CONTROL INTERFACE PANEL.

WITH HARDWARE.

SUPPLY FURNISHED

24VDC. POWER

POWER

CONNECT DOOR TO EXISTING LENNEL

ACCESS CONTROL SYSTEM. PROVIDE

EXPANSION CARDS AS REQUIRED FOR

QUANTITY OF DOORS TO BE CONNECTED

TO EXISTING SYSTEM.

AND LOCATIONS PER PLANS.

CARD READERS. QUANTITIES

DOOR JAMB.

RUN CABLE IN

VERIFY DOOR TYPE WITH ARCHITECTURAL DOOR HARDWARE SCHEDULE.

ELECTRIC STRIKE

ERICO #CAT21 OR EQUAL

INDIVIDUAL CABLE J-HOOK

OR FIXTURE SUPPORT WIRES IS NOT ACCEPTABLE.

INDEPENDENT SUPPORT ROD. USING CEILING GRID

RJ-45 CONNECTOR

FOR CAT 6 VOICE

WIRING

7 853 4 61 2

21 643 5 87 7 853 4 61 2

8 POS. / 8 COND. EIA/TIA-570 - T568B

WIRING STANDARD RJ-45

CONNECTOR FOR CAT-6 LAN WIRING

(TYPICAL)

EACH VOICE AND DATA PORT SHALL BE PROVIDED

WITH A PORT LABEL LOCATED ABOVE THE PORT.

REFER TO SPECIFICATIONS SECTION 271500 FOR

WALL OUTLET LABEL REQUIREMENTS. (TYPICAL ALL

PORTS)

VOICE #1

DATA #1

FUTURE

DATA #2

BLANK INSERT

PLATE

1" EMT

CEILING

BUSHING

NON-METALLIC

WALL

FLOOR

4 11/16"SQ. x 2 1/8"DEEP

OUTLET BOX WITH SIMPLEX

MUD RING

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

117 PIERCE ST, SUITE 110

SIOUX CITY, IOWA 51101

712.252.4014

142 N. MOSLEY ST.

WICHITA, KANSAS 67202

316.262.2500

SEAL:

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044

785.842.6464

PEC #190012-000

EY501

SYSTEMS DETAILS

CORRECT BASEMENT AND

PHARMACY DEFICIENCIES

Columbia, MO

05/13/2019

589A4-18-130

100% CONSTRUCTION DOCUMENTS

DDC MJU

NO SCALE

TYPICAL THRU-WALL CONDUIT SLEEVE

NO SCALE

THRU-WALL CONDUIT DETAIL

NO SCALE

F.A. DEVICE MOUNTING DETAIL

NO SCALE

ACCESS CONTROL DETAIL

NO SCALE

J-HOOK MOUNTING DETAIL

HORIZONTAL CABLE SCHEDULE

CONFIGURATION

PHONE DATA TELEMETRY

REMARKS REF. NOTECABLE

QUANTITY CABLE TYPE

JACKET

COLOR JACK COLOR

CABLE

QUANTITY CABLE TYPE

JACKET

COLOR JACK COLOR

CABLE

QUANTITY CABLE TYPE

JACKET

COLOR JACK COLOR

A 0 1 CAT-6 BLUE BLUE SPECIAL OUTLET 'TV'

B 1 CAT-6 GREY GREY 0

C 1 CAT-6 GREY GREY 1 CAT-6 BLUE BLUE

F 0 2 CAT-6 BLUE BLUE

K 0 1 CAT-6 PINK PINK

NO SCALE

TYPICAL DATACOM OUTLET DETAIL (QUAD)

NO SCALE

TYPICAL DATACOM OUTLET DETAIL

SPECIAL OUTLET 'WAP'

05/09/2019

623 MASSACHUSETTS STREET

SUITE #200

LAWRENCE, KANSAS 66044