36C25519R0081 0001 Drawings- Correct Basement and Pharmacy Deficiencies-Vol 2.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25519R0081-0003000.docx | DOCX document | |
| 36C25519R0081-0002002.pdf | ||
| 36C25519R0081-0002001.pdf | ||
| 36C25519R0081-0002000.docx | DOCX document | |
| 36C25519R0081-0002003.pdf | ||
| 36C25519R0081-0001001.pdf | ||
| 36C25519R0081-0001000.docx | DOCX document | |
| 36C25519R0081-004.pdf | ||
| 36C25519R0081-001.docx | DOCX document | |
| 36C25519R0081-003.pdf | ||
| 36C25519R0081-005.pdf | ||
| 36C25519R0081-002.pdf | ||
| 36C25519R0081-000.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
E-001
ELECTRICAL NOTES AND SYMBOLS
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
D
D
D
D D
D
D D D
D D D
D D D
D
D D
D D
D
LPB-M4A-120VC
LPB-L4-277VC
PPB-M4-120VC
LPB-M4-120VC
E D D D D D D D
S1
D2D2
NOTE: REMOVE ALL EXISTING
BRANCH CIRCUIT WIRING SERVING
AREA BACK TO POINT OF
SUPPLY AS REQUIRED.
D2D3D3 D3
D3
WAP
D3D3D3
W
KLMNNaP w 6.3
6.2
Q
E 1.10
W2
W 2.8
W 3.7
W 4.6
5.8
5.4
5.7
W 5.5
E 1.11
EXISTING CORRIDOR LIGHTING
CIRCUIT SHALL BE REUSED AS
NECCESSARY FOR CONNECTION
TO PROPOSED LIGHT FIXTURES
AS INDICATED ON LIGHTING
PLAN. EXISTING CONTROLS
SHALL REMAIN FOR REUSE.
D
D
DEMOLITION PLAN NOTES:
1. DEMOLITION PLANS SHOW THE GENERAL EXTENT OF THE
ELECTRICAL DEMOLITION WORK. THE ELECTRICAL CONTRACTOR
SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT BEING
REMOVED, SEE MECHANICAL PLANS. OWNER SHALL HAVE THE OPTION
TO RETAIN REUSABLE ITEMS, SUCH AS COVERPLATES, RECEPTACLES,
LIGHTS, PANELS, ETC. NOT BEING USED IN THE FINISHED WORK.
COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION.
PROPERLY AND LEGALLY DISPOSE OF ALL EQUIPMENT AND MATERIALS
BEING REMOVED.
2. REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND
CEILINGS IN REMODELED AREAS. PLUG BOTH ENDS OF REMAINING
CONDUIT IN WALL OR FLOOR WHERE CUT.
3. ELECTRICAL OUTLETS, ETC. POSSIBLY CONCEALED BY STORAGE
SHELVING, CASEWORK, FURNITURE, ETC. ARE NOT SHOWN AND
MAY REQUIRE REMOVAL.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING
ALL OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF
EQUIPMENT AND ELECTRICAL DEVICES, ETC.
5. WHERE EQUIPMENT AND OTHER DEVICES ARE BEING REMOVED,
THE CIRCUITING SHALL BE REMOVED, IF POSSIBLE, BACK TO POINT
OF SUPPLY. WHERE REQUIRED, CIRCUITING SHALL BE EXTENDED
TO MAINTAIN CONTINUITY OF THE CIRCUIT OR OPERATION OF THE
SYSTEM.
6. ALL DEVICES SHOWN DASHED ON THE DEMOLITION PLAN(S) SHALL
BE REMOVED, UNLESS NOTED OTHERWISE.
7. PROVIDE MATCHING BLANK COVERPLATES WHERE DEVICES ARE
BEING REMOVED FROM EXISTING WALLS TO REMAIN.
8. FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR
TO BEGINNING WORK.
SCOPE OF WORK LEGEND
SHADED AREA NOT IN SCOPE OF WORK
DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO
REMAIN AND NOT VACATED.
COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.
ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY
CONTRACTOR.
PROJECT
LOCATION
ACA
ACA
ACA
ACA
H
ACA
G
D D D
PROJECT
LOCATION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
ED101
ELECTRICAL DEMOLITION PLANS -
PARTIAL BASEMENT & SECOND
FLOOR PLANS
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
N
1/8" = 1'-0"
DEMOLITION PLAN - PARTIAL BASEMENT FLOOR PLAN
KEYED NOTES:
D2 RELOCATE EXISTING ACCESS CONTROL DEVICES ASSOCIATED WITH EXISTING
CORRIDOR TO BE REMOVED. PRESERVE EXISTING DEVICES AND CABLING
DURING DEMOLITION AS REQUIRED.
D3 EXISTING DEVICE TO BE REMOVED AND REINSTALLED IN EXISITNG LOCATION.
REMOVE CABLING AND COIL ABOVE CEILING FOR FUTURE USE. PRESERVE AND
PROTECT DEVICES AND ASSOCIATED CABLING DURING CONSTRUCTION.
S1 PROVIDE P.A. SPEAKER FLUSH IN CEILING AT LOCATION AS INDICATED. PROVIDE
CABLING AS REQUIRED TO CONNECT TO EXISTING SYSTEM. VERIFY ALL
REQUIREMENTS PRIOR TO ROUGH-IN.
N
1" = 100'-0"
KEYPLAN - BASEMENT4' 8' 16'
1/8" = 1'-0"
0'
N
1/8" = 1'-0"
DEMOLITION PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'
1/8" = 1'-0"
0'
N
1" = 100'-0"
KEYPLAN SECOND FLOOR
NOTES:
1. REMOVE EXISTING LED LIGHT FIXTURES AND RETURN TO OWNER FOR
FUTURE USE.
2. EXISTING CAT6 CABLING LOCATED WITHIN SPACE SHALL BE COILED IN
PLACE ABOVE ACCESSIBLE CEILING FOR FUTURE USE. THIS INCLUDES BUT
NOT LIMITED TO ALL GREEN, PINK, AND ORANGE JACKETED CABLING.
COORDINATE WITH COR.
05/09/2019 623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
LIGHTING PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.
SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN
ALL CONDUITS.
3. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF
FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING OF
ONE HOUR.
4. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
5. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LIGHT FIXTURE LOCATIONS. VERIFY ALL DISCREPANCIES WITH
ARCHITECT PRIOR TO ROUGH-IN.
TLT.
B011B
TLT.
B011H
ON-CALL RM. 1
B011A
ON-CALL RM. 2
B011C ON-CALL RM. 3
B011D
TLT.
B011E
ON-CALL RM. 4
B011F
ON-CALL RM. 5
B011G
DOUGLASS CLASSROOM
(EXTG)
B007
ELEC. (EXTG)
B011J
HAS
B013
ON-CALL ROOMS/LOUNGE
B011
OFFICE
B006
W2
HB
W2
HB
HB
W2
LPB-M4A-120VC
LPB-L4-277VC
PPB-M4-120VC
LPB-M4-120VC
LACTATION
B009
S1
S1
S1
S1 S1
S1 S1
S1
S1 S1
S1S1
S1 S1 S1
S1
S1
S1
S1
S1
S1
S1 S1
S1
S1
S1
S1S1S1S1
S1S1S1
S1 S1 S1
S1S1S1S1
S1 S1 S1 S1
S1
S1S1S1
E
X1
S1
CHIEF
B006A
ASSOC.CHIEF
B006B
S1
S1
S1
L1
L1
VTS/TRVL SUPRVISOR
B013A
L1
L1
OFFICE
B010
OFFICE
B010A
OFFICE
B006C
S1
S1
S1 S1
S1
S1
S1 S1
S1
S1
S1
S1
S1
S1 S1 S1 S1
L1
L1
NL NL
KLMNNaP w 6.3
6.2
Q
E 1.10
W2
W 2.8
W 3.7
W 4.6
5.8
5.4
5.7
W 5.5
E 1.11
LPB-L4-277VC
L5
L4 S1S1S1S1
NL
L4 L3
LPB-L4-277VC
L5
NL
X1
X1 L6
PROJECT
LOCATION
SCOPE OF WORK LEGEND
SHADED AREA NOT IN SCOPE OF WORK
DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO
REMAIN AND NOT VACATED.
COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.
ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY
CONTRACTOR.
ACA
ACA
ACA
ACA
H
ACA
G
M1 M1 M1
M1
CSCA
F236L2
PROJECT
LOCATION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EL101
LIGHTING PLANS - PARTIAL
BASEMENT & SECOND FLOOR PLANS
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
N
1/8" = 1'-0"
LIGHTING PLAN - PARTIAL BASEMENT PLAN
KEYED NOTES:
L1 PROVIDE INTERLOCK WIRING BETWEEN LOCAL OCCUPANCY SENSORS PER
MANUFACTURERS REQUIREMENTS.
L2 CONNECT TO EXISTING 277V. 20A. LIGHTING CIRCUIT SERVING EXISTING AREA.
L3 CONNECT TO NEAREST LIFE SAFETY EMERGENCY 277V. 20A. LIGHTING CIRCUIT
SERVING EXISTING AREA.
L4 CONNECT TO EXISTING 277V. 20A. CORRIDOR LIGHTING CIRCUIT SERVING AREA.
CONNECT TO EXISTING CONTROLS AS REQUIRED.
L5 PROVIDE 277V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANEL AS INDICATED.
MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED. UPDATE PANEL
DIRECTORY.
L6 INSTALL EXIT SIGN IN EXISTING LOCATION. CONNECT TO EXISTING LIFE SAFETY
CIRCUIT AS REQUIRED.
N
1" = 100'-0"
KEYPLAN - BASEMENT4' 8' 16'
1/8" = 1'-0"
0'
N
1/8" = 1'-0"
LIGHTING PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'
1/8" = 1'-0"
0'
N
1" = 100'-0"
KEYPLAN SECOND FLOOR
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EL501
LIGHTING DETAILS
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EL601
LIGHT FIXTURE SCHEDULE
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
TLT.
B011B TLT.
B011H
ON-CALL RM. 1
B011A
ON-CALL RM. 2
B011C
ON-CALL RM. 3
B011D
TLT.
B011E
ON-CALL RM. 4
B011F
ON-CALL RM. 5
B011G
ELEC. (EXTG)
B011J
HAS
B013
ON-CALL ROOMS/LOUNGE
B011
OFFICE
B006
LACTATION
B009
LPB-M4A-120VC
LPB-L4-277VC
PPB-M4-120VC
LPB-M4-120VC
CT
PRINTER
PRINTER
CT
CT
ASSOC.CHIEF
B006B
CHIEF
B006A
PP
PP
VTS/TRVL SUPRVISOR
B013A
TV
TV TV
TV
TV
CT 46"
60"
TV
U.C. REF.
CT
OFFICE
B010
OFFICE
B010A
OFFICE
B006C
MICROWAVE REF.
TV
KLMNNaP w 6.3
6.2
Q
E 1.10
W2
W 2.8
W 3.7
W 4.6
5.8
5.4
5.7
W 5.5
E 1.11
P3
P4
LPB-M4A-120VC
LPB-M4A-120VC
LPB-M4A-120VC
LPB-M4A-120VC
LPB-M4A-120VC
P4
P4
P4
P4
LPB-M4A-120VC
LPB-M4A-120VCLPB-M4A-120VC
LPB-M4A-120VC
LPB-M4A-120VC
P4
P4
P4
P4 P4
LPB-M4A-120VC
P4
LPB-M4-120VC
LPB-M4-120VC
P4
P5
LPB-M4-120VC
P4LPB-M4-120VC
P4
LPB-M4-120VC
P4
LPB-M4-120VC
P4
P4
LPB-M4-120VC
P4LPB-M4-120VC
LPB-M4-120VC
LPB-M4-120VC
LPB-M4-120VC
P4
P4
LPB-M4-120VC
P4
P4
LPB-M4-120VC
P4
LPB-M4-120VC
P4
LPB-M4-120VC
P5 LPB-M4-120VC
P5 P4
LPB-M4-120VC
P4
LPB-M4-120VC
P7
P8
P8
P7
P8 P7
P6
P1
PPB-M4-120VC
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.
SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN
ALL CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE
OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING
OF ONE HOUR.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE
LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON
OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A
HORIZONTAL DISTANCE OF 24 INCHES.
SCOPE OF WORK LEGEND
SHADED AREA NOT IN SCOPE OF WORK
DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO
REMAIN AND NOT VACATED.
COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.
ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY
CONTRACTOR.
PROJECT
LOCATION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EP101
POWER PLAN - PARTIAL BASEMENT
PLAN
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
N
1/8" = 1'-0"
POWER PLAN - PARTIAL BASEMENT PLAN
KEYED NOTES:
P1 PROVIDE 120V. CONNECTION TO DOOR AS REQUIRED FOR ACCESS CONTROL
SYSTEM. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.
P3 EXTEND EXISTING 12OV. CONNECTION TO DOOR AS REQUIRED FOR CONNECTION
TO RELOCATED ACCESS CONTROL DEVICES. VERIFY ALL REQUIREMENTS PRIOR
TO RELOCATION.
P4 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANEL AS INDICATED.
MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED. UPDATE PANEL
DIRECTORY.
P5 PROVIDE 120V. 20A. 1P. GFCI CIRCUIT BREAKER IN EXISTING PANEL AS
INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED.
UPDATE PANEL DIRECTORY.
P6 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN NEAREST EMERGENCY
PANELBOARD AS INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING
AS REQUIRED. UPDATE PANEL DIRECTORY.
P7 PROVIDE 120V. CONNECTION TO PLUMBING FIXTURE SENSOR. COORDINATE
EXACT LOCATION WITH PLUMBER PRIOR TO ROUGH-IN.
P8 PROVIDE FUSTAT ABOVE ACCESSIBLE CEILING FOR DISCONNECTING MEANS TO
ALL PLUMBING SENSORS IN ROOM.
N
1" = 100'-0"
KEYPLAN - BASEMENT4' 8' 16'
1/8" = 1'-0"
0'
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
PROJECT
LOCATION
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.
SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN
ALL CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE
OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING
OF ONE HOUR.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE
LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON
OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A
HORIZONTAL DISTANCE OF 24 INCHES.
ACA
ACA
ACA
ACA
H
ACA
G
ACA
F
ACA
E.1
ACA
E
ACA
D8
ACA
D7
WALL MOUNTED MONITOR
CT 46"
RELOCATED FUME HOOD
CT
WALL MOUNTED CPU. COORDINATE EXACT
LOCATION WITH COR PRIOT TO ROUGH-IN.
P1
46"
CSCA
F236
ELECT CLOSET
E252
CT
LABEL PRINTER
PP2-D10-120VC
LP2-D10-277VC
LP2-D10-277VN
PP2-D10-120VN
PP2-D10-120VC
P6
PP2-D10-120VC
P6
P6
PP2-D10-120VN
PP2-D10-120VC
P6
PP2-D10-120VN
P6P7
P8
MEDS REF.
SCOPE OF WORK LEGEND
SHADED AREA NOT IN SCOPE OF WORK
DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO
REMAIN AND NOT VACATED.
COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.
ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY
CONTRACTOR.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EP102
POWER PLAN - PARTIAL SECOND
FLOOR PLAN
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
N
1" = 100'-0"
KEYPLAN SECOND FLOOR
KEYED NOTES:
P1 PROVIDE 120V. CONNECTION TO DOOR AS REQUIRED FOR ACCESS CONTROL
SYSTEM. VERIFY ALL REQUIREMENTS PRIOR TO ROUGH-IN.
P6 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN NEAREST EMERGENCY
PANELBOARD AS INDICATED. MATCH EXISTING BREAKER TYPE AND AIC RATING
AS REQUIRED. UPDATE PANEL DIRECTORY.
P7 PROVIDE 120V. CONNECTION TO PLUMBING FIXTURE SENSOR. COORDINATE
EXACT LOCATION WITH PLUMBER PRIOR TO ROUGH-IN.
P8 PROVIDE FUSTAT ABOVE ACCESSIBLE CEILING FOR DISCONNECTING MEANS TO
ALL PLUMBING SENSORS IN ROOM.
N
1/8" = 1'-0"
POWER PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'
1/8" = 1'-0"
0'
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
ACA
5.6
ACA
ACA
6.3
ACA
ACA
ACA
ACA
H
ACA
G
ACA
F
ACA
E.1
ACA
E
ACA
D8
ACA
D7
(EX)EF-24
EF-CHEMO
(EX)EF-21
(EX)EF-22
(EX)12"ø
WP
P2
DEVICE ON
ROOF AT UNIT
RB-2-28
POWER PLAN NOTES:
1. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS WITH
INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE CIRCUITS (MAXIMUM OF
THREE PHASE CONDUCTORS) MAY BE GROUPED IN A SINGLE CONDUIT.
WHERE MULTIPLE CIRCUITS ARE LOCATED IN THE SAME RACEWAY,
JUNCTION BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE ASSOCIATED WITH.
SEE SPECIFICATION SECTION "LOW VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES" FOR ADDITIONAL INFORMATION.
2. A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN
ALL CONDUITS.
3. FOR CONNECTION REQUIREMENTS TO MECHANICAL UNITS, SEE
MECHANICAL EQUIPMENT CONNECTION SCHEDULE.
4. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE
OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A T-RATING
OF ONE HOUR.
5. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
6. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL BE
LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET BOXES ON
OPPOSITE SIDES OF THE RATED WALLS SHALL BE SEPARATED BY A
HORIZONTAL DISTANCE OF 24 INCHES.
AREA
SHOWN
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EP106
POWER PLAN - PARTIAL ROOF PLAN
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
N
1/8" = 1'-0"
POWER PLAN - PARTIAL ROOF PLAN 4' 8' 16'
1/8" = 1'-0"
0'
KEYED NOTES:
P2 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN NEAREST EXISITING 120V NORMAL
POWER PANEL. MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED.
UPDATE PANEL DIRECTORY.
N
1" = 100'-0"
KEYPLAN - ROOF
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
BRANCH CIRCUIT/DISTRIBUTION PANEL
DISCONNECT SWITCH
CONTROL CENTER BREAKER/SWITCH
SWITCHBOARD/DISTRIBUTION PANEL/MOTOR
1/8"
1/4"
1/4"
PANEL K
PHASE B: RED
PHASE C: BLUE
PHASE A: BLACK
10,000 A.I.C.
120/208V.,3∅,4W.
1/4"
1/8"
1/8" 1/8"
1/4"
3/8"
GROUND: GREEN
NEUTRAL: WHITE
RTU #1
LPJ 200AMP
SERVES
1/8"
1/4" RTU-1
SERVES
ISO.GRD.: GRN/YEL
FED FROM DP:**1/4"
FED FROM DP:**1/4"
METAL STUD
CONDUITS
RECEPTACLE
EQUIPMENT GROUND
CONDUCTOR
GROUND SCREW ON
WIRING DEVICE
GROUND SCREW IN
OUTLET BOX
CONDUIT
4 SQUARE OUTLET BOX
DRYWALL
PLASTER RING
PLASTER RING
RECEPTACLE
OUTLET BOX SECURED
TO BOX SUPPORT
GROUND SCREW IN
OUTLET BOX
WIRE NUT (TYP.)
STUD TO STUD BOX
SUPPORT, B-LINE #BB2
SERIES OR EQUAL.
NEUTRAL
CONDUCTORS
HOT CONDUCTORS
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EP501
POWER DETAILS
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
NO SCALE
TYPICAL HEALTHCARE NAME PLATES
NO SCALE
TYPICAL RECEPTACLE MOUNTING DETAIL
NO SCALE
TYPICAL TELEVISION OUTLET DETAIL
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EP601
ELECTRICAL SCHEDULES
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
EaFGGaHJJb Ja
TLT.
B011B
TLT.
B011H
ON-CALL RM. 1
B011A
ON-CALL RM. 2
B011C
ON-CALL RM. 3
B011D
TLT.
B011E
ON-CALL RM. 4
B011F
ON-CALL RM. 5
B011G
DOUGLASS CLASSROOM
(EXTG)
B007
ELEC. (EXTG)
B011J
HAS
B013
ON-CALL ROOMS/LOUNGE
B011
OFFICE
B006
PRINTER
PRINTER
LACTATION
B009
PP
PP
ASSOC.CHIEF
B006B
CHIEF
B006A
S1
WAP
TV
TVTV
TV
VTS/TRVL SUPRVISOR
B013A
TV
TV
WAP
S1
S1
WAP
OFFICE
B010
OFFICE
B010A
OFFICE
B006C
S1
TV
KLMNNaP w 6.3
6.2
Q
E 1.10
W2
W 2.8
W 3.7
W 4.6
5.8
5.4
5.7
W 5.5
E 1.11
I.T. CLOSET
A056A
S9S9
S3
S3
S6S6S6
S9
WAP
S2S2S2
DMARC
A060
EXISTING P.A.
EQUIPMENT RACK
EXISTING PHONE
BACKBOARD WITH
PUNCH-DOWN BLOCKS
(3) EXISTING
DATA RACKS
S6
FSD
FSD
FSDFSD FSD FSD
LPB-M4-120VC
E
S8
P4
FSD
FSD
FSD
A056A C
A056A C
A056A C
A056A C
A056A C
A056A C
A056A CA056A C
A056A C A056A C
A056A C
A056A C
A056A C A056A C
A056A C
A056A C
A056A C
A056A C
A056A C
A056A C
A056A C
A056A A
A056A K
A056A B A056A C
A056A C A056A C
A056A C
A056A C
A056A C
A056A C
A056A C
A056A A
A056A C
A056A C
A056A C A056A C
A056A B
A056A A
A056A B
A056A A
A056A B
A056A A A056A B
A056A A
A056A C
A056A A
PROVIDE CARD READER/
CYPHER LOCK COMBINATION
DEVICE AS REQUIRED.
A056A K
A056A K
SYSTEMS PLAN NOTES:
1. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE
OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A
T-RATING OF ONE HOUR.
2. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
3. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL
BE LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET
BOXES ON OPPOSITE SIDES OF THE RATED WALLS SHALL BE
SEPARATED BY A HORIZONTAL DISTANCE OF 24 INCHES.
4. WHERE THE SAME DEVICE IS SHOWN IN THE SAME LOCATION ON
BOTH THE POWER AND SYSTEMS PLAN, ONLY ONE DEVICE IS
REQUIRED. PROVIDE BOTH POWER AND SYSTEMS WIRING AS SHOWN.
5. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED PER THE
REQUIREMENTS OF NFPA 72. DEVICES SHOWN INDICATE THE DESIGN
INTENT AND SHALL BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER
SHALL PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR
DEVICES REQUIRED BY THE AUTHORITY HAVING JURISDICTION.
6. PROVIDE J-HOOKS FOR DATA CABLING PATHWAY AS REQUIRED.
SCOPE OF WORK LEGEND
SHADED AREA NOT IN SCOPE OF WORK
DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO
REMAIN AND NOT VACATED.
COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.
ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY
CONTRACTOR.
PROJECT
LOCATION
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EY101
SYSTEMS PLAN - PARTIAL BASEMENT
PLAN
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
N
1/8" = 1'-0"
SYSTEMS PLAN - PARTIAL BASEMENT PLAN
KEYED NOTES:
P4 PROVIDE 120V. 20A. 1P. CIRCUIT BREAKER IN EXISTING PANEL AS INDICATED.
MATCH EXISTING BREAKER TYPE AND AIC RATING AS REQUIRED. UPDATE PANEL
DIRECTORY.
S1 PROVIDE P.A. SPEAKER FLUSH IN CEILING AT LOCATION AS INDICATED. PROVIDE
CABLING AS REQUIRED TO CONNECT TO EXISTING SYSTEM. VERIFY ALL
REQUIREMENTS PRIOR TO ROUGH-IN.
S2 REINSTALL EXISTING ACCESS CONTROL DEVICES AT CORRIDOR DOOR AS
REQUIRED. EXTEND, REROUTE, AND RECONNECT EXISTING CABLING AS
NECESSARY TO COMPLETE SYSTEM INSTALLATION.
S3 PROVIDE CAT6 CABLING ROUTED FROM OUTLET TO DATA RACK LOCATED IN I.T.
CLOSET A056A. PROVIDE DATA TERMINATION ON ASSOCIATED PATCH PANEL AS
REQUIRED. PROVIDE ADDITIONAL PATCH PANELS AS NECESSARY. PROVIDE
PHONE TERMINATION ON PUNCH-DOWN BLOCK LOCATED ON PHONE
BACKBOARD. VERIFY ALL REQUIREMENTS WITH I.T. DEPARTMENT PRIOR TO
ROUGH-IN.
S6 REINSTALL EXISTING DEVICE IN CEILING AT EXISTING LOCATION. RECONNECT
EXISTING CABLING AS REQUIRED TO COMPLETE SYSTEM INSTALLATION
S8 PROVIDE CAT6 CABLING AS REQUIRED FROM EXISTING LENNEL ACCESS
CONTROL PANEL LOCATED IN STORAGE E005 TO DOOR AS INDICATED. VERIFY
ALL REQUIREMENTS PRIOR TO ROUGH-IN.
S9 PROVIDE OUTLET WITH (1) USB PORT AND (1) HDMI PORT FOR CONNECTION TO
WALL MOUNTED MONITOR. PROVIDE USB CABLE AND HDMI CABLE ROUTED TO
WALL MOUNTED CPU OUTLET LOCATED OUTSIDE PHARMACY. COORDINATE
EXACT LOCATION AND ALL REQUIREMENTS PRIOR TO ROUGH-IN.
N
1" = 100'-0"
KEYPLAN - BASEMENT4' 8' 16'
1/8" = 1'-0"
0'
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
ACA
ACA
ACA
ACA
H
ACA
G
ACA
F
ACA
E.1
ACA
E
ACA
D8
ACA
D7
E
WALL MOUNTED CPU
WALL MOUNTED MONITOR
RELOCATED FRAME HOOD
MEDS
REFRIGERATOR
S1 CSCA
F236
S7
S5
CT
LABEL PRINTER
ELECTRICAL
E202
TELE/ DATA
E203
EXISTING PHONE BACKBOARD
WITH PUNCH-DOWN BLOCKS
(2) EXISTING DATA RACKS
EXISTING P.A.
AMPLIFIER
EXISTING LENNEL
ACCESS CONTROL
PANEL
E203 F 46"
S10 S9
S11S11
E203 F
E203 F
SYSTEMS PLAN NOTES:
1. ALL PENETRATIONS IN THE RATED WALLS AND CEILINGS SHALL BE
SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE
OF FLAMES AND HOT GASSES. THE SEALANT SHALL HAVE A
T-RATING OF ONE HOUR.
2. ALL PIPING, CONDUIT, AND OUTLET BOXES (ELECTRIC, TELEPHONE,
COMPUTER, ETC.) IN THE RATED WALLS OR CEILING SHALL BE
CONSTRUCTED OF NON-COMBUSTIBLE MATERIAL.
3. OUTLET BOXES (ELECTRIC, TELEPHONE, COMPUTER, ETC.) SHALL
BE LIMITED TO TWO OUTLET BOXES PER STUD SPACE. OUTLET
BOXES ON OPPOSITE SIDES OF THE RATED WALLS SHALL BE
SEPARATED BY A HORIZONTAL DISTANCE OF 24 INCHES.
4. WHERE THE SAME DEVICE IS SHOWN IN THE SAME LOCATION ON
BOTH THE POWER AND SYSTEMS PLAN, ONLY ONE DEVICE IS
REQUIRED. PROVIDE BOTH POWER AND SYSTEMS WIRING AS SHOWN.
5. THE FIRE ALARM SYSTEM SHOWN HAS BEEN DESIGNED PER THE
REQUIREMENTS OF NFPA 72. DEVICES SHOWN INDICATE THE DESIGN
INTENT AND SHALL BE THE MINIMUM PROVIDED. SYSTEM SUPPLIER
SHALL PROVIDE ANY ADDITIONAL CODE REQUIRED DEVICES OR
DEVICES REQUIRED BY THE AUTHORITY HAVING JURISDICTION.
6. PROVIDE J-HOOKS FOR DATA CABLING PATHWAY AS REQUIRED.
PROJECT
LOCATION
SCOPE OF WORK LEGEND
SHADED AREA NOT IN SCOPE OF WORK
DIAGONAL HATCH AREA INDICATES WORK IN EXISTING SPACES TO
REMAIN AND NOT VACATED.
COORDINATION WITH OWNER NEEDED TO CONDUCT WORK.
ANY DAMAGES TO FINISHES OR EQUIPMENT WILL BE REPLACED BY
CONTRACTOR.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EY102
SYSTEMS PLAN - PARTIAL SECOND
FLOOR PLAN
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
N
1/8" = 1'-0"
SYSTEMS PLAN - PARTIAL SECOND FLOOR PLAN 4' 8' 16'
1/8" = 1'-0"
0'
KEYED NOTES:
S1 PROVIDE P.A. SPEAKER FLUSH IN CEILING AT LOCATION AS INDICATED. PROVIDE
CABLING AS REQUIRED TO CONNECT TO EXISTING SYSTEM. VERIFY ALL
REQUIREMENTS PRIOR TO ROUGH-IN.
S5 PROVIDE OUTLET WITH (2) USB PORTS AND (1) HDMI PORT FACEPLATE AT 18” AFF
ADJACENT TO DATA OUTLET SERVING WALL MOUNTED CPU. PROVIDE (1) USB
CABLE AND (1) HDMI CABLE ROUTED FROM OUTLET TO WALL MOUNTED MONITOR
LOCATED IN PHARMACY AS REQUIRED VIA 1-1/4” CONDUIT. PROVIDE (1) USB
CABLE FROM OUTLET TO LABEL PRINTER LOCATED IN PHARMACY AS REQUIRED
VIA 1-1/4” CONDUIT.
S7 PROVIDE CAT6 CABLING ROUTED TO EXISTING LENNEL ACCESS CONTROL PANEL
LOCATED IN ELECTRICAL CLOSET AS INDICATED. VERIFY ALL REQUIREMENTS
WITH EXISTING ACCESS CONTROL SYSTEM AS NECESSARY.
S9 PROVIDE OUTLET WITH (1) USB PORT AND (1) HDMI PORT FOR CONNECTION TO
WALL MOUNTED MONITOR. PROVIDE USB CABLE AND HDMI CABLE ROUTED TO
WALL MOUNTED CPU OUTLET LOCATED OUTSIDE PHARMACY. COORDINATE
EXACT LOCATION AND ALL REQUIREMENTS PRIOR TO ROUGH-IN.
S10 PROVIDE OUTLET WITH (2) CAT6 CABLES AND (1) USB CABLE FOR CONNECTION
TO LABEL PRINTER. PROVIDE CAT6 CABLING ROUTED TO DATA RACK AS
INDICATED AND USB CABLE ROUTED TO WALL MOUNTED CPU LOCATED OUTSIDE
PHARMACY. COORDINATE EXACT LOCATION AND ALL REQUIREMENTS PRIOR TO
ROUGH-IN.
S11 PROVIDE 1-1/4” CONDUIT BETWEEN OUTLETS AS REQUIRED FOR LOW-VOLTAGE
CABLING PATHWAY. PROVIDE PULL-ROPE IN CONDUIT.
N
1" = 100'-0"
KEYPLAN SECOND FLOOR
05/09/2019
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
4'-0" 4'-0"
CEILING
PROVIDE MOUNTING AND FINISHING PLATES
AND ACCCESSORIES REQUIRED FOR A FULLY
SEALED AND FIRE RATED SYSTEM.
CORRIDOR SIDE ROOM SIDE
ROUTE CABLES IN CABLE
TRAY AS SHOWN ON PLANS
FIRE RATED THRU-WALL PATHWAY EQUAL TO LEGRAND
EZ-PATH SERIES 44. PROVIDE MODULE SIZE AS REQUIRED
FOR NUMBER OF CABLES. INSTALL PER MANUFACTURER
RECCOMENDATION.
TYPICAL J-HOOK
SUPPORTS TO BE
USED WITH-IN
6"
SEE J-HOOK
DETAIL
INDIVIDUAL ROOMS.
BOND CABLE TRAY TO EACH CONDUIT SLEEVE
VIA #6 BARE COPPER AWG GROUND WIRE.
4'-0" 4'-0"
CEILING
12" MINIMUM CONDUIT NIPPLE.
SEE GENERAL NOTE #12.
BUSHINGS
SEAL & FIREPROOF
FIREPROOF AFTER
CABLE INSTALLATION
SEAL & FIREPROOF
SUPPORTS
TYPICAL
J-HOOK
6"(MIN.)
48" AFF
DEVICE SHALL NOT BE MORE THAN
46" AFF TO CENTERLINE, TOP OF
SPECIFICATIONS.
WITH HARDWARE
OPEN. COORDINATE
OR CLOSURE/HOLD
MAGNETIC HOLD OPEN
(TYP.)
DETECTOR
SMOKE
FIRE ALARM DEVICE MOUNTING CRITERIA
SPECIFIED OTHERWISE ON THE DRAWINGS.
UNLESS MOUNTING HEIGHTS HAVE BEEN
THESE GUIDELINES SHALL BE USED
AUDIO/VISUAL
GENERAL NOTE
PULL STATION
REFER TO THE VISUAL UNIT.
AUDIO/VISUAL UNIT
AUDIO UNIT
VISUAL UNIT
ACCEPTABLE HERE
TOP OF DETECTOR
IN THIS AREA
DO NOT PLACE DETECTOR
AND AIR DIFFUSER/REGISTER/GRILL
MAINTAIN 36" BETWEEN SMOKE DETECTOR
STATION
PULL
12" 4"
90"
80"
46"
80" TO BOTTOM
AUDIO ONLY
6"(MIN.)
6"(MIN.)
90" TO TOP
AUDIO ONLYVISUAL ONLY
80" TO BOTTOM
FINISH FLOOR
CEILING
MAX. OF 5'-0", MIN. OF "d"
BUT NOT LESS THAN 12"
DETECTORS ON ONE SIDE
OR BOTH SIDES OF DOOR
AS REQUIRED BY NFPA 72.
DOOR HEADER "d"
HEIGHT OF
AIR DIFFUSER
TOP OF DEVICE 90 INCHES ABOVE
HIGHEST FLOOR LEVEL OR 6 INCHES
BELOW CEILING WHICH EVER IS LOWER.
BOTTOM OF DEVICE 80 INCHES ABOVE
HIGHEST FLOOR LEVEL OR 6 INCHES
BELOW CEILING WHICH EVER IS LOWER.
4"
ACP
SUPPLY
IFP
CEILING.
CR
120V.
4 5 6
INSTALL LABEL TO
INDICATE PANEL NAME
AND CIRCUIT.
BMS
SYSTEM MANUFACTURER.
QUANTITY AND TYPE OF CABLE PER
ACCESS CONTROL INTERFACE PANEL.
WITH HARDWARE.
SUPPLY FURNISHED
24VDC. POWER
POWER
CONNECT DOOR TO EXISTING LENNEL
ACCESS CONTROL SYSTEM. PROVIDE
EXPANSION CARDS AS REQUIRED FOR
QUANTITY OF DOORS TO BE CONNECTED
TO EXISTING SYSTEM.
AND LOCATIONS PER PLANS.
CARD READERS. QUANTITIES
DOOR JAMB.
RUN CABLE IN
VERIFY DOOR TYPE WITH ARCHITECTURAL DOOR HARDWARE SCHEDULE.
ELECTRIC STRIKE
ERICO #CAT21 OR EQUAL
INDIVIDUAL CABLE J-HOOK
OR FIXTURE SUPPORT WIRES IS NOT ACCEPTABLE.
INDEPENDENT SUPPORT ROD. USING CEILING GRID
RJ-45 CONNECTOR
FOR CAT 6 VOICE
WIRING
7 853 4 61 2
21 643 5 87 7 853 4 61 2
8 POS. / 8 COND. EIA/TIA-570 - T568B
WIRING STANDARD RJ-45
CONNECTOR FOR CAT-6 LAN WIRING
(TYPICAL)
EACH VOICE AND DATA PORT SHALL BE PROVIDED
WITH A PORT LABEL LOCATED ABOVE THE PORT.
REFER TO SPECIFICATIONS SECTION 271500 FOR
WALL OUTLET LABEL REQUIREMENTS. (TYPICAL ALL
PORTS)
VOICE #1
DATA #1
FUTURE
DATA #2
BLANK INSERT
PLATE
1" EMT
CEILING
BUSHING
NON-METALLIC
WALL
FLOOR
4 11/16"SQ. x 2 1/8"DEEP
OUTLET BOX WITH SIMPLEX
MUD RING
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
117 PIERCE ST, SUITE 110
SIOUX CITY, IOWA 51101
712.252.4014
142 N. MOSLEY ST.
WICHITA, KANSAS 67202
316.262.2500
SEAL:
623 MASSACHUSETTS STREET
SUITE #200
LAWRENCE, KANSAS 66044
785.842.6464
PEC #190012-000
EY501
SYSTEMS DETAILS
CORRECT BASEMENT AND
PHARMACY DEFICIENCIES
Columbia, MO
05/13/2019
589A4-18-130
100% CONSTRUCTION DOCUMENTS
DDC MJU
NO SCALE
TYPICAL THRU-WALL CONDUIT SLEEVE
NO SCALE
THRU-WALL CONDUIT DETAIL
NO SCALE
F.A. DEVICE MOUNTING DETAIL
NO SCALE
ACCESS CONTROL DETAIL
NO SCALE
J-HOOK MOUNTING DETAIL
HORIZONTAL CABLE SCHEDULE
CONFIGURATION
PHONE DATA TELEMETRY
REMARKS REF. NOTECABLE
QUANTITY CABLE TYPE
JACKET
COLOR JACK COLOR
CABLE
QUANTITY CABLE TYPE
JACKET
COLOR JACK COLOR
CABLE
QUANTITY CABLE TYPE
JACKET
COLOR JACK COLOR
A 0 1 CAT-6 BLUE BLUE SPECIAL OUTLET 'TV'
B 1 CAT-6 GREY GREY 0
C 1 CAT-6 GREY GREY 1 CAT-6 BLUE BLUE
F 0 2 CAT-6 BLUE BLUE
K 0 1 CAT-6 PINK PINK
NO SCALE
TYPICAL DATACOM OUTLET DETAIL (QUAD)
NO SCALE
TYPICAL DATACOM OUTLET DETAIL
SPECIAL OUTLET 'WAP'
05/09/2019