Topeka VA Medical Center, Topeka, KS
Power System Study
Prepared by: LEO A DALY Page 1 of 1 8600 Indian Hills Drive
Omaha, NE 68114 (402)-391-8111
1. EXECUTIVE SUMMARY
LEO A DALY performed the Power Distribution System Condition Analysis at Veterans Affairs
Medical Center, Topeka, Kansas for the Department of Veterans Affairs – Office of Construction and Facilities Management, Consulting Support Service (VACO OO CFM3A). The Scope of
Condition Analysis included site visits, field surveys, collection of data, drawings, short circuit current calculations, component protection coordination, hazard risk analysis, preparation of one-line diagrams, cost estimates and recommendations.
For a campus of buildings which electrical systems are approximately 30 years of age, the field survey indicated that the power system has been maintained is in good condition. There were not any short circuit issues since all of the protective ratings exceeded the calculated fault currents: (Refer to Tab C). A majority of the feeders were less than the 5% recommended voltage drop percentage limit but there were a few feeders that exceeded this recommended limit
(Refer to Tab G). A vast majority of the coordination curves do coordinate; however there are a few could coordinate better (Refer to Tab F). A majority of the electrical system was found to be code compliant, however that are a few minor code violations that should be addressed. (Refer to Tab I). Cost estimates have been performed for all recommendations of the above analyses
(Refer to Tab K). Analysis and Recommendations can be found in Tab I.
Overall, the electrical systems for the buildings surveyed are in good to excellent condition. If the electrical system continues to be maintained with the facility staff being aware of the electrical issues and recommendations included in this report, we expect the life expectancy of the system to be 10 to 20 more years.
Building 1
Panel Flr Room Amps Emer Manufacturer Model Volts
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
BA1 0 A20E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 15.9 Yes BA‐1 0 A20E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 15.5 Yes BA‐2 0 A20E 225 ‐ Square D NQOD 120/208 X EMT 4/0 60 22 16.3 Yes BB‐1 0 B13E 225 ‐ Square D NQOD 120/208 X EMT 4/0 180 22 6.1 Yes BB‐2 0 B13E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.0 Yes BC 0 C4E 225 ‐ Square D NQOD 120/208 X EMT 1/0 190 22 4.4 Yes BC‐1 0 C4E 70 ‐ Square D NQOD 120/208 70/3 EMT 6 3 22 4.2 Yes BCT 0 A14 400 ‐ Square D NQOD 120/208 X EMT 500 30 200 24.9 Yes BD 0 A10 225 ‐ Square D NQOD 120/208 X EMT 4/0 125 22 9.8 Yes BP 0 A14 400 ‐ Square D NQOD 120/208 X EMT 500 20 65 24.9 Yes
CBDP‐1 0 A14 600 ‐ Square D NQOD 120/208 X EMT (2) 250 10 50 26.2 Yes CBDP‐2 0 A14 400 ‐ Square D NQOD 120/208 X EMT (2) 250 10 65 22.8 Yes DP1‐B 0 B22E 1600 ‐ Square D NQOD 120/208 800/3 PVC,EMT (3) 350 40 125 14.6 Yes EBAC 0 SERV 100 Y Square D NQOD 120/208 X EMT 1 200 22 3.3 Yes EBDP‐1 0 A14 400 Y Square D NQOD 120/208 X EMT 500 15 65 23.9 Yes EBDP‐2 0 A14 400 Y Square D NQOD 120/208 X EMT 500 15 65 27.3 Yes EBTR 0 A14 225 Y Square D NQOD 120/208 X EMT 4/0 5 65 22.7 Yes ECR1‐B 0 B22E 400 ‐ Square D NQOD 120/208 300/3 EMT (2)3/0 10 30 13.7 Yes EE1‐B 0 B22E 225 Y Square D NQOD 120/208 225/3 EMT (2)3/0 10 42 13.4 Yes ELEV DP 0 A14 600 Y Square D NQOD 120/208 X EMT (2)350 15 200 26.4 Yes ELS1‐B 0 B22E 100 Y Square D NQOD 120/208 40/3 EMT 2 10 22 12.7 Yes EM 0 C3E 100 Y Square D NQOD 120/208 X EMT 1/0 180 22 4.4 Yes EMB 0 B3 125 Y Square D NQOD 120/208 100/3 EMT 1/0 180 22 4.4 Yes
EMER DP 0 A14 1200 Y Square D NQOD 120/208 1200/3 EMT (4)350 400 100 7.3 Yes LS‐BB 0 B13E 100 Y Square D NQOD 120/208 X EMT 4 180 22 3.6 Yes LSDP‐1 0 A14 225 Y Square D NQOD 120/208 X EMT 250 10 65 23.9 Yes Main A 0 A14 2000 ‐ Square D NQOD 120/208 2000/3 PVC,EMT (6) 400 40 50 33.7 Yes Main B 0 A14 2000 ‐ Square D NQOD 120/208 2000/3 PVC,EMT (6) 400 40 50 30.1 Yes MCC 0 SERV 400 Y Square D NQOD 208 400/3 EMT (2)250 200 65 12.6 Yes MP1‐B 0 B22E 225 ‐ Square D NQOD 120/208 X EMT 4/0 40 22 13.8 Yes PB‐B 0 B1B 200 ‐ Square D NQOD 120/208 X EMT 1/0 140 22 5.8 Yes PP1‐B 0 B22E 100 ‐ Square D NQOD 120/208 X EMT 2 25 22 13.1 Yes
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
SC 0 SERV 225 ‐ Square D NQOD 120/208 X EMT 1/0 200 22 4.2 Yes SR 0 SERV 225 ‐ Square D NQOD 120/208 X EMT 3 200 22 1.8 Yes
TELE COMM 0 A14 100 ‐ Square D NQOD 120/208 X EMT 3 20 22 12.0 Yes 1A 1 A101E 225 ‐ Square D NQOD 120/208 X EMT 4/0 75 22 14.4 Yes 1B 1 B143E 225 ‐ Square D NQOD 120/208 X EMT 4/0 195 22 5.8 Yes 1C‐1 1 C116E 400 ‐ Square D NQOD 120/208 X EMT 500 190 22 9.6 Yes 1C‐2 1 C116E 400 ‐ Square D NQOD 120/208 X EMT 500 3 22 9.5 Yes 1D‐1 1 A115E 225 ‐ Square D NQOD 120/208 X EMT 4/0 125 22 8.9 Yes 1D‐2 1 A115E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 8.8 Yes 1K 1 A141E 225 ‐ Square D NQOD 120/208 X EMT 4/0 50 22 18.2 Yes BCA 1 C26 200 ‐ Square D NQOD 120/208 X EMT 1/0 120 22 2.8 Yes BE 1 A10 100 Y Square D NQOD 120/208 X EMT 2 125 22 4.3 Yes
CB‐1A 1 A141E 225 Y Square D NQOD 120/208 X EMT 4/0 70 22 12.9 Yes EBB‐1 1 B17 100 Y Square D NQOD 120/208 X EMT 6 115 22 2.0 Yes ECR1‐1 1 AC106E 400 Y Square D NQOD 120/208 X EMT 4/0 95 22 8.2 Yes ECR2‐1 1 AC106E 400 Y Square D NQOD 120/208 X EMT 4/0 3 22 8.1 Yes EM1 1 A101A 100 Y Square D NQOD 120/208 X EMT 1 65 22 9.6 Yes LP1‐1 1 AC110E 225 ‐ Square D NQOD 120/208 150/3 EMT 1/0 25 22 11.8 Yes LS‐1A 1 A101E 100 Y Square D NQOD 120/208 X EMT 1 75 22 7.5 Yes LS‐1B 1 B143E 100 Y Square D NQOD 120/208 X EMT 4 195 22 3.2 Yes LS‐1C 1 C116E 100 Y Square D NQOD 120/208 X EMT 1 190 22 4.2 Yes
POLICE PNL 1 B110 100 Y Square D NQOD 120/208 X EMT 2 225 22 2.4 Yes PP 1 C114D 225 ‐ Square D NQOD 120/208 X EMT 2 300 22 1.9 Yes
PP1‐1 1 AC110E 400 ‐ Square D NQOD 120/208 X EMT 4/0 25 22 12.6 Yes PP2‐1 1 AC110E 400 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 12.4 Yes
UNNAMED (2) 1 A20 100 ‐ Square D NQOD 120/208 100/3 EMT 3 10 22 12.2 Yes 2A‐1 2 A202E 225 ‐ Square D NQOD 120/208 X EMT 4/0 90 22 12.8 Yes 2A‐2 2 A202E 225 ‐ Square D NQOD 120/208 X EMT 4/0 30 22 12.5 Yes 2B 2 B220E 225 ‐ Square D NQOD 120/208 X EMT 4/0 210 22 5.5 Yes 2C‐1 2 C211E 400 ‐ Square D NQOD 120/208 X EMT 500 205 22 9.4 Yes 2C‐2 2 C211E 400 ‐ Square D NQOD 120/208 X EMT 500 3 22 9.0 Yes 2CC‐1 2 C203 400 ‐ Square D NQOD 120/208 X EMT 500 3 22 8.1 Yes
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
2CC‐2 2 C203 400 ‐ Square D NQOD 120/208 X EMT 500 35 22 8.1 Yes 2C‐MR 2 C208M 125 ‐ Square D NQOD 120/208 X EMT 1 300 22 2.3 Yes 2D‐1 2 A212E 225 ‐ Square D NQOD 120/208 X EMT 4/0 140 22 8.3 Yes 2D‐2 2 A212E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 8.2 Yes 2DB 2 A212E 100 ‐ Square D NQOD 120/208 X EMT ? 140 22 3.9 Yes 2K‐1 2 A229E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 15.3 Yes 2K‐2 2 A229E 225 ‐ Square D NQOD 120/208 X EMT 4/0 65 22 15.7 Yes 2XR 2 B220B 225 ‐ Square D NQOD 120/208 X EMT 500 270 22 7.5 Yes 2XR‐1 2 B223A 125 ‐ Square D NQOD 120/208 100/3 EMT 2 35 22 3.9 Yes 2XRA 2 B218 100 ‐ Square D NQOD 120/208 X EMT 2 50 22 4.9 Yes
AC‐RM215 2 C203 225 ‐ Square D NQOD 120/208 X EMT 250 170 22 7.8 Yes B‐CT 2 A229B 225 ‐ Square D NQOD 120/208 X EMT 4/0 100 22 10.4 Yes C‐1 2 A234 225 Y Square D NQOD 120/208 175/3 EMT 2/0 145 42 12.6 Yes C‐2 2 A234 225 Y Square D NQOD 120/208 175/3 EMT 2/0 3 42 12.2 Yes
CB‐2A 2 A229E 225 Y Square D NQOD 120/208 X EMT 4/0 90 22 11.6 Yes Comp RM ‐ A 2 A234 225 ‐ Square D NQOD 120/208 X EMT 4/0 140 22 8.3 Yes ELAB‐1 2 C203 225 Y Square D NQOD 120/208 X EMT 4/0 180 22 6.7 Yes ELAB‐2 2 C203 100 Y Square D NQOD 120/208 X EMT 3 3 22 6.5 Yes EM2 2 A230A 225 Y Square D NQOD 120/208 X EMT 1 190 22 3.5 Yes LS‐2B 2 B226E 100 Y Square D NQOD 120/208 X EMT 4 210 22 2.8 Yes LS‐2C 2 C211E 100 Y Square D NQOD 120/208 X EMT 1 205 22 3.8 Yes TE 2 A201T 225 Y Square D NQOD 120/208 X EMT 250 80 22 1.2 Yes
UNNAMED (1) 2 B216 100 Y Square D NQOD 120/208 X EMT 3 200 22 2.8 Yes 3A 3 A301E 225 ‐ Square D NQOD 120/208 X EMT 4/0 85 22 12.8 Yes 3B1 3 B324E 225 ‐ Square D NQOD 120/208 X EMT 3/0 105 22 4.3 Yes 3B2 3 B324E 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 22 4.3 Yes 3B2A 3 B324E 100 ‐ Square D NQOD 120/208 X EMT 2 3 22 4.2 Yes 3BR 3 B326 100 ‐ Square D NQOD 120/208 X EMT 2 95 22 3.2 Yes 3C‐1 3 C306E 225 ‐ Square D NQOD 120/208 X EMT 300 185 22 7.3 Yes 3C‐2 3 C306E 225 ‐ Square D NQOD 120/208 X EMT 300 3 22 7.2 Yes 3D‐1 3 A325E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 8.7 Yes 3D‐2 3 A325E 225 ‐ Square D NQOD 120/208 X EMT 4/0 150 22 8.6 Yes
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
3K1 3 A342E 225 ‐ Square D NQOD 120/208 X EMT 1/0 85 22 7.8 Yes 3K2 3 A342E 225 ‐ Square D NQOD 120/208 X EMT 1/0 3 22 7.6 Yes CB‐3C 3 C306E 100 Y Square D NQOD 120/208 X EMT 1 185 22 3.6 Yes CB‐3D 3 A325E 100 Y Square D NQOD 120/208 X EMT 1 145 22 4.4 Yes LS‐3A 3 A301E 100 Y Square D NQOD 120/208 X EMT 1 85 22 6.8 Yes 4A 4 A401E 225 ‐ Square D NQOD 120/208 X EMT 4/0 100 22 11.5 Yes
4AC1 4 B401C 225 Y Square D NQOD 120/208 X EMT 6 230 22 2.9 Yes 4B 4 B401C 400 ‐ Square D NQOD 120/208 X EMT 500 230 22 8.4 Yes 4C‐1 4 C406E 225 ‐ Square D NQOD 120/208 X EMT 4/0 200 22 6.9 Yes 4C‐2 4 C406E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.8 Yes 4D‐1 4 A429E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 8.0 Yes 4D‐2 4 A429E 225 ‐ Square D NQOD 120/208 X EMT 4/0 160 22 7.9 Yes 4K 4 A444E 225 ‐ Square D NQOD 120/208 X EMT 1/0 100 22 7.8 Yes
CB‐4A 4 A444E 225 Y Square D NQOD 120/208 X EMT 4/0 105 22 10.2 Yes CB‐4B 4 B401C 400 ‐ Square D NQOD 120/208 X EMT 250 230 65 6.3 Yes CB‐4C 4 C406E 100 Y Square D NQOD 120/208 X EMT 1 200 22 3.3 Yes CB‐4D 4 A429E 100 Y Square D NQOD 120/208 X EMT 1 160 22 4.1 Yes DB 4 ICU 400 Y Square D NQOD 120/208 X EMT 500 180 65 9.4 Yes
EB4MR 4 B401C 225 Y Square D NQOD 120/208 X EMT 4/0 230 22 5.8 Yes LS‐4A 4 A401E 100 Y Square D NQOD 120/208 X EMT 1 105 22 6.0 Yes 5A 5 A503E 225 ‐ Square D NQOD 120/208 X EMT 4/0 115 22 10.4 Yes 5C‐1 5 C505E 225 ‐ Square D NQOD 120/208 X EMT 4/0 215 22 6.5 Yes 5C‐2 5 C505E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.4 Yes 5D‐1 5 A522E 225 Y Square D NQOD 120/208 X EMT 4/0 170 22 7.5 Yes 5D‐2 5 A522E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 7.4 Yes 5K 5 A546E 225 ‐ Square D NQOD 120/208 X EMT 1/0 115 22 6.9 Yes 5KA 5 A546E 225 ‐ Square D NQOD 120/208 X EMT 4/0 100 22 11.5 Yes CB‐5C 5 C505E 100 Y Square D NQOD 120/208 X EMT 1 215 22 3.1 Yes CB‐5D 5 A522E 100 ‐ Square D NQOD 120/208 X EMT 2 10 22 3.8 Yes LS‐5A 5 A503E 100 Y Square D NQOD 120/208 X EMT 2 120 22 5.2 Yes 6A1 6 A603E 225 ‐ Square D NQOD 120/208 X EMT 4/0 130 22 9.5 Yes 6A2 6 A603E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 9.4 Yes
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
B 6 A610C 100 ‐ Square D NQOD 120/208 X EMT 3 40 22 3.9 Yes LS‐6A 6 A603E 100 Y Square D NQOD 120/208 X EMT 2 135 22 4.6 Yes 7A 7 PENT 225 ‐ Square D NQOD 120/208 X EMT 3/0 120 22 9.1 Yes
EB7A 7 PENT 100 Y Square D NQOD 120/208 100/3 EMT 1/0 120 18 7.2 Yes P1A 7 PENT 400 ‐ Square D NQOD 120/208 X EMT 350 120 65 11.3 Yes
Bldg 54 ‐ E Bldg 54 80 Y Square D NQOD 120/208 80/3 PVC,EMT 2 415 22 2.5 Yes
Building 2
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
B2 0 A14 400 ‐ Square D NQOD 120/208 X EMT 500 55 65 15.7 Yes ES 0 A15 600 Y Square D QED 120/208 X EMT (2)350 20 50 20.5 Yes LBA 0 A8E 225 ‐ Square D NQOD 120/208 X EMT 1 110 65 5.7 Yes MSB 0 A15 1600 ‐ Square D QED 120/208 1600/3 PVC,EMT (5)400 50 50 22.6 Yes P1 0 A15 400 ‐ Square D NQOD 120/208 X EMT 500 20 22 17.9 Yes SBA 0 A14 225 ‐ Square D NQOD 120/208 X EMT 1 35 65 12.9 Yes E1A 1 A136E 100 Y Square D NQOD 120/208 X EMT 2 125 65 4.2 Yes L1A‐1 1 A136E 225 ‐ Square D NQOD 120/208 X EMT 1 125 65 5.1 Yes L1A‐2 1 A136E 225 ‐ Square D NQOD 120/208 X EMT 1 3 65 5.0 Yes L1AA 1 A142A 225 ‐ Square D NQOD 120/208 X EMT 2/0 40 65 13.3 Yes L1AAA 1 A142A 100 ‐ Square D NQOD 120/208 X EMT 2/0 50 22 12.9 Yes L1B‐1 1 B112E 225 ‐ Square D NQOD 120/208 X EMT 3/0 235 65 5.6 Yes L1B‐2 1 B112E 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 65 5.6 Yes L1C‐1 1 C167E 225 ‐ Square D NQOD 120/208 X EMT 3/0 105 65 9.2 Yes L1C‐2 1 C167E 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 65 9.0 Yes E2A 2 A232E 100 Y Square D NQOD 120/208 X EMT 2 140 65 3.8 Yes E2B 2 OLD CLST 100 Y Square D NQOD 120/208 X EMT 4 120 65 3.0 Yes L2A‐1 2 A232E 225 ‐ Square D NQOD 120/208 X EMT 1 140 65 4.6 Yes L2A‐2 2 A232E 225 ‐ Square D NQOD 120/208 X EMT 1 3 65 4.5 Yes L2B‐1 2 B216E 225 ‐ Square D NQOD 120/208 X EMT 4/0 250 65 5.4 Yes L2B‐2 2 B216E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 65 5.3 Yes L2C‐1 2 C258E 225 ‐ Square D NQOD 120/208 X EMT 3/0 120 65 7.8 Yes L2C‐2 2 C258E 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 65 7.6 Yes E3A 3 A333E 100 Y Square D NQOD 120/208 X EMT 4 155 65 3.4 Yes L3A‐1 3 A333E 225 ‐ Square D NQOD 120/208 X EMT 1 155 65 3.9 Yes L3A‐2 3 A333E 225 ‐ Square D NQOD 120/208 X EMT 1 3 65 3.8 Yes L3B‐1 3 B313E 225 ‐ Square D NQOD 120/208 X EMT 3/0 265 65 5.1 Yes L3B‐2 3 B313E 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 65 5.1 Yes L3C‐1 3 C365E 225 ‐ Square D NQOD 120/208 X EMT 3/0 135 65 7.8 Yes L3C‐2 3 C365E 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 65 7.6 Yes L4A 4 PENT 225 ‐ Square D NQOD 120/208 X EMT 1 170 65 3.9 Yes
SMOKE 4 PENT 100 ‐ Square D NQOD 120/208 100/2 EMT 3 170 22 0.0 Yes
Building 3
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current
X1000 AIC Protected
A‐1 0 A21 100 ‐ Square D NQOD 120/208 X EMT 3 20 22 10.6 Yes A‐2 0 A21 100 ‐ Square D NQOD 120/208 X EMT 3 3 22 8.1 Yes B‐1 0 B10E 225 ‐ Square D NQOD 120/208 X EMT 4/0 205 22 5.5 Yes B‐2 0 B10E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 5.5 Yes B‐3 0 A17 225 ‐ Square D NQOD 120/208 X EMT 4/0 85 22 7.6 Yes C‐1 0 C29E 225 ‐ Square D NQOD 120/208 X EMT 4/0 110 22 6.9 Yes C‐2 0 C29E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.8 Yes EM 0 A1C 100 Y Square D NQOD 120/208 X EMT 1 80 22 5.6 Yes ES 0 A21 400 Y Square D QED 120/208 X EMT 500 10 200 10.1 Yes MSB 0 A21 800 ‐ Square D QED 120/208 800/3 PVC,EMT (3)300 40 42 10.9 Yes D‐1 1 A128E 225 ‐ Square D NQOD 120/208 X EMT 1 80 22 5.9 Yes D‐2 1 A128E 225 ‐ Square D NQOD 120/208 X EMT 1 3 22 5.7 Yes E‐1 1 B113E 225 ‐ Square D NQOD 120/208 X EMT 4/0 220 22 5.1 Yes E‐2 1 B113E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 5.0 Yes ED 1 A128E 100 Y Square D NQOD 120/208 X EMT 1 95 22 5.1 Yes F‐1 1 C143E 225 ‐ Square D NQOD 120/208 X EMT 4/0 125 22 6.2 Yes F‐2 1 C143E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.1 Yes EG 2 A228 100 ‐ Square D NQOD 120/208 X EMT 1 110 22 4.7 Yes G 2 A228 225 ‐ Square D NQOD 120/208 X EMT 1 95 22 5.3 Yes H‐1 2 B213E 225 ‐ Square D NQOD 120/208 X EMT 4/0 235 22 5.1 Yes H‐2 2 B213E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 5.0 Yes J‐1 2 C243E 225 ‐ Square D NQOD 120/208 X EMT 4/0 140 22 6.2 Yes J‐2 2 C243E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.1 Yes AC1 PH PH 100 ‐ Square D NQOD 120/208 X EMT 3 65 22 3.2 Yes
Building 4
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
EBA 0 A2E 100 Y Square D NQOD 120/208 X EMT 2 140 22 3.1 Yes ES 0 A2E 400 Y Square D QED 120/208 X EMT 4/0 10 200 7.4 Yes LBA 0 A2E 225 ‐ Square D NQOD 120/208 X EMT 1/0 140 22 4.3 Yes LBB 0 B9A 225 ‐ Square D NQOD 120/208 X EMT 4/0 220 22 4.2 Yes LBC 0 C19 225 ‐ Square D NQOD 120/208 X EMT 4/0 45 22 6.9 Yes LBS 0 C19 100 Y Square D NQOD 120/208 X EMT 1 45 22 5.8 Yes MSB 0 A2E 600 ‐ Square D QED 120/208 600/3 PVC,EMT (2)350 40 42 8.0 Yes SN 0 Ph Closet 100 Y Square D NQOD 120/208 X EMT 2 40 22 2.4 Yes SR 0 B10 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 22 4.1 Yes SR1 0 B10 225 ‐ Square D NQOD 120/208 X EMT 3/0 200 22 4.2 Yes E1A 1 A103E 225 Y Square D NQOD 120/208 X EMT 2 155 22 2.9 Yes L1A 1 A103E 100 ‐ Square D NQOD 120/208 X EMT 1/0 155 22 3.9 Yes L1B‐1 1 B121E 225 ‐ Square D NQOD 120/208 X EMT 4/0 235 22 3.9 Yes L1B‐2 1 B121E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 3.9 Yes L1C‐1 1 C163E 225 ‐ Square D NQOD 120/208 X EMT 4/0 115 22 6.3 Yes L1C‐2 1 C163E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.2 Yes LS1 1 A103S 100 Y Square D NQOD 120/208 X EMT 1/0 155 22 5.3 Yes E2A 2 A203E 100 Y Square D NQOD 120/208 X EMT 2 170 22 2.7 Yes L2A 2 A203E 225 ‐ Square D NQOD 120/208 X EMT 1/0 170 22 3.7 Yes L2B‐1 2 B221E 225 ‐ Square D NQOD 120/208 X EMT 4/0 250 22 3.9 Yes L2B‐2 2 B221E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 3.9 Yes L2C‐1 2 C251E 225 ‐ Square D NQOD 120/208 X EMT 4/0 130 22 6.3 Yes L2C‐2 2 C251E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.2 Yes LS2 2 A202E 100 Y Square D NQOD 120/208 X EMT 1/0 170 22 4.9 Yes
Building 5
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
EBA 0 A2E 100 Y Square D NQOD 120/208 X EMT 2 140 22 3.2 Yes ES 0 C11 400 Y Square D QED 120/208 X EMT 350 10 200 7.6 Yes LBA 0 A2E 225 ‐ Square D NQOD 120/208 X EMT 1/0 140 22 4.2 Yes LBB 0 B3E 225 ‐ Square D NQOD 120/208 X EMT 350 220 22 4.7 Yes LBC 0 C11 225 ‐ Square D NQOD 120/208 X EMT 4/0 45 22 6.9 Yes MSB 0 C11 600 ‐ Square D QED 120/208 600/3 PVC,EMT (2)350 190 42 8.0 Yes SR 0 B4 225 ‐ Square D NQOD 120/208 X EMT 2/0 200 22 3.3 Yes SR‐1 0 B4 225 ‐ Square D NQOD 120/208 225/3 EMT 250 200 22 4.6 Yes E1A 1 A102E 100 Y Square D NQOD 120/208 X EMT 2 155 22 6.6 Yes L1A 1 A102E 225 ‐ Square D NQOD 120/208 X EMT 1/0 155 22 3.9 Yes L1B‐1 1 B115E 225 ‐ Square D NQOD 120/208 X EMT 350 235 22 4.6 Yes L1B‐2 1 B115E 225 ‐ Square D NQOD 120/208 X EMT 350 235 22 4.5 Yes L1C‐1 1 C147E 225 ‐ Square D NQOD 120/208 X EMT 4/0 115 22 6.6 Yes L1C‐2 1 C147E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.5 Yes E2A 2 A202E 100 Y Square D NQOD 120/208 X EMT 2 170 22 2.7 Yes L2A 2 A202E 225 ‐ Square D NQOD 120/208 X EMT 1/0 170 22 3.7 Yes L2B‐1 2 B221E 225 ‐ Square D NQOD 120/208 X EMT 350 250 22 4.4 Yes L2B‐2 2 B221E 225 ‐ Square D NQOD 120/208 X EMT 350 3 22 4.4 Yes L2C‐1 2 C244E 225 ‐ Square D NQOD 120/208 X EMT 4/0 130 22 6.3 Yes L2C‐2 2 C244E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.2 Yes
E1 (BLDG 55) Bldg 55 100 ‐ Square D NQOD 120/208 80/3 PVC,EMT 2 350 22 1.5 Yes SMOKE Smoke shelter 100 ‐ Square D NQOD 120/208 X PVC,EMT 3 150 22 3.1 Yes
Building 6
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
N Bldg 53 100 Y Square D NQOD 120/208 X PVC,EMT 6 175 22 1.2 Yes 6E ‐ SR 100 Y Square D NQOD 120/208 X EMT 6 5 ? 5.7 Yes B6 ‐ SR 400 ‐ Square D NQOD 120/208 X EMT 350 45 ? 6.2 Yes
EMERGENCY ‐ SR 400 Y Square D NQOD 120/208 X EMT 1 10 65 6.1 Yes ES ‐ SR 100 Y Square D NQOD 120/208 X EMT 6 50 22 3.1 Yes MSB ‐ SR 400 ‐ Square D QED 120/208 400/3 PVC,EMT 500 50 50 6.9 Yes S ‐ SR 225 ‐ Square D NQOD 120/208 X EMT 1 25 22 6.2 Yes A‐1 1 A139E 225 ‐ Square D NQOD 120/208 X EMT 2/0 3 22 4.8 Yes A‐2 1 A139E 225 ‐ Square D NQOD 120/208 X EMT 2/0 98 22 4.9 Yes B‐1 1 B108E 225 ‐ Square D NQOD 120/208 X EMT 1/0 3 22 3.0 Yes B‐2 1 B108E 225 ‐ Square D NQOD 120/208 X EMT 1/0 220 22 3.0 Yes C‐1 1 C170E 225 ‐ Square D NQOD 120/208 X EMT 1 3 22 2.9 Yes C‐2 1 C170E 225 ‐ Square D NQOD 120/208 X EMT 1 190 22 2.9 Yes EA 1 A139S 225 Y Square D NQOD 120/208 X EMT ? 80 22 1.1 Yes EB 1 B119 100 Y Square D NQOD 120/208 X EMT 10 235 22 0.4 Yes EB‐1 1 B119 100 Y Square D NQOD 120/208 X EMT 10 235 22 0.4 Yes EC 1 C159 100 Y Square D NQOD 120/208 X EMT 10 205 22 0.5 Yes EC‐1 1 C159 100 Y Square D NQOD 120/208 X EMT 10 205 22 0.5 Yes LP 1 C181 100 ‐ Square D NQOD 120/208 100/3 EMT 1/0 280 22 2.5 Yes
Building 9
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
B9 0 CHILLER 300 Y Square D NQOD 120/208 X EMT 350 215 65 14.8 Yes EB9 0 CHILLER 100 ‐ Square D NQOD 120/208 X EMT 8 215 65 2.8 Yes 9E 1 A022 225 Y Square D NQOD 120/208 X EMT 1 20 100 16.0 Yes 9N 1 A022 400 Y Square D NQOD 120/208 X EMT 500 5 100 18.1 Yes A 1 A028E 400 ‐ Square D NQOD 120/208 X EMT 350 90 65 1.2 Yes CP1 1 B013 225 ‐ Square D NQOD 120/208 X EMT 3/0 120 65 6.6 Yes CP4 1 B013 225 Y Square D NQOD 120/208 X EMT 3/0 120 65 6.5 Yes CP5 1 A029 225 Y Square D NQOD 120/208 X EMT 225 115 65 6.7 Yes D‐1 1 B020E 400 ‐ Square D NQOD 120/208 X EMT 350 65 65 13.5 Yes D‐2 1 B020E 400 ‐ Square D NQOD 120/208 X EMT 350 3 65 13.2 Yes EA 1 A028E 100 Y Square D NQOD 120/208 X EMT 8 90 65 1.6 Yes EDP 1 A022 700 Y Square D QED 120/208 700/3 EMT (2)500 5 65 28.1 Yes EM1 1 B013 225 Y Square D NQOD 120/208 X EMT 1/0 120 65 6.5 Yes ES 1 A022 400 Y Square D NQOD 120/208 X EMT 350 10 100 17.0 Yes G‐1 1 C022E 400 ‐ Square D NQOD 120/208 X EMT 350 230 65 6.9 Yes G‐2 1 C022E 400 ‐ Square D NQOD 120/208 X EMT 350 3 65 6.8 Yes MR 1 A022 100 ‐ Square D NQOD 120/208 X EMT 1/0 20 100 26.1 Yes MSB 1 A022 1000 ‐ Square D QED 120/208 1000/3 PVC,EMT (3)400 60 42 20.7 Yes PDU 1 B009 200 ‐ Square D NQOD 208 200/3 EMT 4/0 70 22 12.9 Yes SN 1 A029 100 Y Square D NQOD 120/208 X EMT 2 115 65 4.2 Yes
SWBD‐A 1 A022 2000 ‐ Square D QED 120/208 2000/3 PVC,EMT (5)600 60 65 31.1 Yes B 2 A123E 400 ‐ Square D NQOD 120/208 X EMT 350 130 65 11.0 Yes CP2 2 B111 400 ‐ Square D NQOD 120/208 X EMT 1/0 95 65 8.1 Yes CP2A 2 B111 225 Y Square D NQOD 120/208 X EMT 1/0 95 65 7.9 Yes E‐1 2 B118E 400 ‐ Square D NQOD 120/208 X EMT 350 80 65 12.4 Yes E‐2 2 B118E 400 ‐ Square D NQOD 120/208 X EMT 350 3 65 12.2 Yes EE1 2 B118E 100 Y Square D NQOD 120/208 X EMT 6 80 65 2.7 Yes EH 2 C153E 100 Y Square D NQOD 120/208 X EMT 3 245 65 1.5 Yes H 2 C153E 400 ‐ Square D NQOD 120/208 X EMT 350 245 65 6.6 Yes C 3 A231E 400 ‐ Square D NQOD 120/208 X EMT 350 145 65 10.3 Yes
CP3 3 B209E 600 ‐ Square D NQOD 120/208 X EMT 250 110 65 11.5 Yes CP3A 3 B209E 400 ‐ Square D NQOD 120/208 X EMT 250 3 65 11.3 Yes
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
EF 3 B226E 100 Y Square D NQOD 120/208 X EMT 6 95 65 2.3 Yes EJ 3 C253E 100 Y Square D NQOD 120/208 X EMT 3 260 65 1.4 Yes F‐1 3 B226E 400 ‐ Square D NQOD 120/208 X EMT 350 95 65 11.6 Yes F‐2 3 B226E 400 ‐ Square D NQOD 120/208 X EMT 350 3 65 11.4 Yes J‐1 3 C253E 400 ‐ Square D NQOD 120/208 X EMT 350 260 65 6.3 Yes J‐2 3 C253E 400 ‐ Square D NQOD 120/208 X EMT 350 3 65 6.3 Yes EK 4 PENT 225 Y Square D NQOD 120/208 X EMT 3 170 65 2.1 Yes K 4 PENT 225 ‐ Square D NQOD 120/208 X EMT 250 170 65 5.5 Yes PP 4 PENT 125 ‐ Square D NQOD 120/208 X EMT 3 170 65 2.1 Yes
SMOKE Smoke shelter 100 ‐ Square D NQOD 120/208 X PVC,EMT 4 ? 65 0.0 Yes A Bldg 45 100 ‐ Square D NQOD 120/208 X PVC,EMT 2 775 65 0.7 Yes
Building 20
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
A‐1 1 116E 225 ‐ Square D NQOD 120/208 X EMT 1/0 80 22 7.9 Yes A‐2 1 116E 225 ‐ Square D NQOD 120/208 X EMT 1/0 3 22 7.7 Yes B1 1 110 100 Y Square D NQOD 120/208 X EMT 4 30 22 5.5 Yes B‐1 1 113E 225 ‐ Square D NQOD 120/208 X EMT 4/0 140 22 7.5 Yes B2 1 WAREHOUSE 100 ‐ Square D NQOD 120/208 X EMT 4 100 22 2.7 Yes B‐2 1 113E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 7.4 Yes BA 1 113E 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.7 Yes C‐1 1 103 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 6.1 Yes C‐2 1 103 225 ‐ Square D NQOD 120/208 X EMT 4/0 190 22 6.1 Yes D1 1 101 225 ‐ Square D NQOD 120/208 X EMT 3/0 305 22 3.8 Yes D‐1 1 101D 225 ‐ Square D NQOD 120/208 X EMT 3/0 305 22 6.5 Yes D‐2 1 101D 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 22 6.4 Yes EDP‐1 1 A125 600 Y Square D QED 120/208 X EMT (2) 350 30 65 15.8 Yes EDP‐2 1 110 400 Y Square D NQOD 120/208 X EMT 500 230 22 6.8 Yes EDR 1 101C 225 Y Square D NQOD 120/208 X EMT 3/0 300 22 3.8 Yes EL 1 108B 100 Y Square D NQOD 120/208 X EMT 4 275 22 1.7 Yes ES 1 125 225 Y Square D NQOD 120/208 X EMT 2 25 22 3.3 Yes F 1 A125 600 ‐ Square D NQOD 120/208 X EMT (2) 350 15 65 16.0 Yes KA 1 112 225 ‐ Square D NQOD 120/208 X EMT 3/0 220 65 3.6 Yes KB 1 112 225 ‐ Square D NQOD 120/208 X EMT 3/0 220 65 3.6 Yes MSB 1 A125 1200 ‐ Square D QED 120/208 1200/3 PVC,EMT (2)500 60 65 16.8 Yes P 1 105 225 ‐ Square D NQOD 120/208 X EMT 4/0 230 22 5.4 Yes R 1 122 400 Y Square D NQOD 120/208 400/3 EMT (2) ? 60 22 12.7 Yes S 1 A126 225 Y Square D NQOD 120/208 X EMT 1 45 22 9.4 Yes E Bldg 57 80 Y Square D NQOD 120/208 80/3 PVC,EMT 2 225 22 2.4 Yes
Building 21
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
L1‐1 1 110E 225 ‐ Square D NQOD 120/208 X EMT 1/0 5 22 8.3 Yes L1‐2 1 110E 225 ‐ Square D NQOD 120/208 X EMT 1/0 3 22 8.1 Yes L1A 1 106 100 ‐ Square D NQOD 120/208 X EMT 2 130 22 3.3 Yes L1B 1 109 100 ‐ Square D NQOD 120/208 X EMT 3 105 22 2.8 Yes L1C 1 109 100 ‐ Square D NQOD 120/208 X EMT 2 25 22 6.8 Yes L1D 1 112 225 ‐ Square D NQOD 120/208 X EMT 2 15 22 7.5 Yes L1E 1 112 225 ‐ Square D NQOD 120/208 X EMT 2 75 22 4.6 Yes L1F 1 115 225 ‐ Square D NQOD 120/208 X EMT 2 110 22 3.6 Yes ML 1 110E 1200 ‐ Square D QED 120/208 400/3 PVC,EMT (2)500 320 65 8.5 Yes SR ‐ SR 225 ‐ Square D NQOD 120/208 X EMT 4/0 140 22 5.1 Yes 51 A Bldg 51 60 ‐ Square D NQOD 120/208 60/3 PVC,EMT 6 170 22 1.3 Yes
Building 22
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
A 1 110M 200 ‐ Square D NQOD 120/208 X EMT 4/0 10 22 5.4 Yes B 1 110M 60 ‐ Square D NQOD 120/208 X EMT 6 15 22 4.9 Yes C 1 110M 200 ‐ Square D NQOD 120/208 X EMT 4/0 20 22 5.5 Yes CP 1 110E 100 ‐ Square D NQOD 120/208 X EMT 1 25 22 5.1 Yes DP 1 110M 400 ‐ Square D QED 120/028 400/3 PVC,EMT 500 40 22 5.5 Yes E 1 110E 100 Y Square D NQOD 120/208 100/3 EMT 3 25 22 4.8 Yes
Building 23
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
A 1 110C 225 ‐ Square D NQOD 120/208 X EMT 4 35 18 4.1 Yes B 1 109 225 ‐ Square D NQOD 120/208 X EMT 4 40 18 5.2 Yes D 1 109M 100 ‐ Square D NQOD 120/208 X EMT 3 5 22 5.6 Yes D‐1 1 109M 225 ‐ Square D NQOD 120/208 225/3 EMT 4/0 145 22 5.8 Yes
Building 24
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating x1000
Calculated Fault Current x1000 AIC Protected
BS 0 SR 100 ‐ Square D NQOD 120/208 X EMT 1 20 22 8.9 Yes EM 0 SR 225 ‐ Square D NQOD 120/208 60/3 EMT 6 10 22 9.6 Yes B24 0 SR 600 ‐ Square D UNKNOWN 120/208 X EMT (2) 350 10 200 9.9 Yes 1A‐1 1 A114E 225 ‐ Square D NQOD 120/208 X EMT 300 3 22 4.1 Yes 1A‐2 1 A114E 225 ‐ Square D NQOD 120/208 X EMT 300 320 22 4.1 Yes 1B‐1 1 B106E 225 ‐ Square D NQOD 120/208 X EMT 300 3 22 5.8 Yes 1B‐2 1 B106E 225 ‐ Square D NQOD 120/208 X EMT 300 165 22 5.9 Yes 1C 1 107A 225 ‐ Square D NQOD 120/208 X EMT 2 100 22 3.7 Yes 1D 1 A108H 100 ‐ Square D NQOD 120/208 X EMT 4 65 22 3.8 Yes 1K 1 107G 225 ‐ Square D NQOD 120/208 X EMT 300 90 22 7.4 Yes 1K1 1 107G 225 ‐ Square D NQOD 120/208 X EMT 4 90 22 3.6 Yes 1K2 1 107G 60 ‐ Square D NQOD 120/208 X EMT ? 90 22 3.5 Yes 1S‐1 1 A108 225 ‐ Square D NQOD 120/208 X EMT 1/0 5 22 4.0 Yes 1S‐2 1 A108 225 ‐ Square D NQOD 120/208 X EMT 1/0 165 22 4.1 Yes EM 1 A114E 100 ‐ Square D NQOD 120/208 X EMT ? 320 22 2.8 Yes MSB 1 SR 800 ‐ Square D QED 120/208 800/3 PVC,EMT (2)500 60 42 10.1 Yes M1 2 M1‐B 225 ‐ Square D NQOD 120/208 X EMT 3/0 230 22 4.2 Yes MAC 2 M1‐M 100 ‐ Square D UNKNOWN 120/208 100/3 EMT 1/0 30 ? 3.7 Yes MP 2 M1‐F 100 ‐ Square D NQOD 120/208 X EMT 1/0 30 ? 3.7 Yes
SMOKE Smoke shelter 100 ‐ Square D NQOD 120/208 100/2 PVC,EMT 3 185 22 0.0 Yes
Building 25
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating
Calculated Fault Current x1000 AIC Protected
A 1 105 225 ‐ Square D NQOD 120/208 X EMT 3 60 22 3.5 Yes B 1 106 225 ‐ Square D NQOD 120/208 X EMT 3/0 95 22 4.1 Yes C 1 105 100 ‐ Square D NQOD 120/208 X EMT 3 60 22 3.5 Yes D 1 106 100 ‐ Square D NQOD 120/208 X EMT 3 95 22 2.8 Yes E 1 110 225 ‐ Square D NQOD 120/208 X EMT 1/0 10 22 5.0 Yes EM 1 110 80 ‐ Square D NQOD 120/208 60/3 EMT 6 10 22 4.8 Yes MSB 1 110 400 ‐ Square D QED 120/208 400/3 PVC,EMT 500 50 42 5.1 Yes
Buildings 40,41,42,43
Panel Bldg Room Amps Emer Manufacturer Model Volts
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating
Calculated Fault Current x1000 AIC Protected
40A‐1 40 S. WALL 225 ‐ Square D NQOD 120/208 X EMT 3/0 35 22 6.9 Yes 40A‐2 40 S. WALL 225 ‐ Square D NQOD 120/208 X EMT 3/0 3 22 6.8 Yes 40‐DP 40 S. WALL 400 ‐ Square D NQOD 120/208 300/3 PVC,EMT 250 or 350 215 65 6.6 Yes
41‐Unnamed 41 110 100 ‐ Square D NQOD 120/208 100/3 EMT 3 10 22 4.9 Yes 41A‐L 41 102 225 ‐ Square D NQOD 120/208 X EMT 2/0 75 22 6.9 Yes 41A‐R 41 102 225 ‐ Square D NQOD 120/208 X EMT 2/0 3 22 6.8 Yes 41B 41 106 225 ‐ Square D NQOD 120/208 X EMT 3 75 22 4.1 Yes 41C 41 110 225 ‐ Square D NQOD 120/208 X EMT 4/0 170 22 5.4 Yes MSB 41 101 800 ‐ Square D QED 120/208 800/3 EMT (2)500 50 42 10.1 Yes 42A‐L 42 SHOP 100 ‐ Square D NQOD 120/208 X EMT 3/0 3 22 3.0 Yes 42A‐R 42 SHOP 100 ‐ Square D NQOD 120/208 100/3 PVC,EMT 3/0 360 22 3.0 Yes 43A‐L 43 101 225 ‐ Square D NQOD 120/208 X EMT 4/0 3 22 8.3 Yes 43A‐R 43 101 225 ‐ Square D NQOD 120/208 X EMT 4/0 40 22 8.4 Yes 43B‐L 43 105 100 ‐ Square D NQOD 120/208 X EMT 3/0 3 22 7.5 Yes 43B‐R 43 105 225 ‐ Square D NQOD 120/208 X EMT 3/0 60 22 7.6 Yes
ELEC SHOP 43 102 100 ‐ Square D NQOD 120/208 X EMT 2 25 22 8.4 Yes MP 43 101A 225 ‐ Square D NQOD 120/208 225/3 PVC,EMT (2) 4/0 225 22 6.5 Yes
Buildings 60,61,273
Panel Bldg Room Amps Emer Manufacturer Model # Volts
MLO
(CB)
Conduit Material
Feeder Type
Feeder Length
AIC
Rating
Calculated Fault Current x1000 AIC Protected
61A 61 107 225 ‐ Square D NQOD 120/208 X EMT 3/0 25 22 ‐ (1) ‐ (1)
P‐AC 61 SR 100 ‐ Square D NQOD 120/208 100/2 EMT 1 20 22 ‐ (1) ‐ (1)
P‐AC 60 HALLWAY D ‐ Square D NQOD 120/208 200/2 EMT 250 20 22 ‐ (1) ‐ (1)
60L 60 102 125 ‐ Square D NQOD 120/208 125/2 EMT 250 20 22 ‐ (1) ‐ (1)
S. PANEL 273 5 100 ‐ Square D NQOD 120/208 X EMT ‐ (2) 40 ‐ (2) ‐ (2) ‐ (2)
N. PANEL 273 5 100 ‐ Square D NQOD 120/208 X EMT ‐ (2) 40 ‐ (2) ‐ (2) ‐ (2)
SW ROOM 273 4 225 ‐ Square D NQOD 120/208 X PVC,EMT ‐ (2) 35 ‐ (2) ‐ (2) ‐ (2)
(1) Single‐phase load, only three‐phase data calculated in SKM
(2) Information undetermined due to age/condition of equipment
Panel Flr Room Amps Emer Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
BA1 0 A20E 225 ‐ 1 19 42 Avoid Contact Avoid Contact
BA‐1 0 A20E 225 ‐ 1 19 42 Avoid Contact Avoid Contact
BA‐2 0 A20E 225 ‐ 1 20 42 Avoid Contact Avoid Contact
BB‐1 0 B13E 225 ‐ 0 8.8 42 Avoid Contact Avoid Contact
BB‐2 0 B13E 225 ‐ 0 8.8 42 Avoid Contact Avoid Contact
BC 0 C4E 225 ‐ 0 11 42 Avoid Contact Avoid Contact
BC‐1 0 C4E 70 ‐ 0 10 42 Avoid Contact Avoid Contact
BCT 0 A14 400 ‐ 1 24 42 Avoid Contact Avoid Contact
BD 0 A10 225 ‐ 0 15 42 Avoid Contact Avoid Contact
BP 0 A14 400 ‐ 1 24 42 Avoid Contact Avoid Contact
CBDP‐1 0 A14 600 ‐ 1 24 42 Avoid Contact Avoid Contact
CBDP‐2 0 A14 400 ‐ 1 23 42 Avoid Contact Avoid Contact
DP1‐B 0 B22E 1600 ‐ 2 (*N3) 48 42 Avoid Contact Avoid Contact
EBAC 0 SERV 100 Y 0 3.9 42 Avoid Contact Avoid Contact
EBDP‐1 0 A14 400 Y 1 23 42 Avoid Contact Avoid Contact
EBDP‐2 0 A14 400 Y 1 25 42 Avoid Contact Avoid Contact
EBTR 0 A14 225 Y 0 9.5 42 Avoid Contact Avoid Contact
ECR1‐B 0 B22E 400 ‐ 0 7.5 42 Avoid Contact Avoid Contact
EE1‐B 0 B22E 225 Y 0 7.4 42 Avoid Contact Avoid Contact
ELEV DP 0 A14 600 Y 2 (*N3) 47 42 Avoid Contact Avoid Contact
ELS1‐B 0 B22E 100 Y 0 7.3 42 Avoid Contact Avoid Contact
EM 0 C3E 100 Y 0 4.5 42 Avoid Contact Avoid Contact
EMB 0 B3 125 Y 0 5 42 Avoid Contact Avoid Contact
EMER DP 0 A14 1200 Y 3 (*N9) 104 42 Avoid Contact Avoid Contact
LS‐BB 0 B13E 100 Y 0 (*N3) 5.4 42 Avoid Contact Avoid Contact
LSDP‐1 0 A14 225 Y 1 23 42 Avoid Contact Avoid Contact
Main A 0 A14 2000 ‐ Danger!(*N3 *N9) 190 42 Avoid Contact Avoid Contact
Main B 0 A14 2000 ‐ 1 26 42 Avoid Contact Avoid Contact
MCC 0 SERV 400 Y 1 37 42 Avoid Contact Avoid Contact
MP1‐B 0 B22E 225 ‐ 0 13 42 Avoid Contact Avoid Contact
PB‐B 0 B1B 200 ‐ 0 12 42 Avoid Contact Avoid Contact
PP1‐B 0 B22E 100 ‐ 0 13 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
SC 0 SERV 225 ‐ 0 10 42 Avoid Contact Avoid Contact
SR 0 SERV 225 ‐ 2 (*N3) 39 42 Avoid Contact Avoid Contact
TELE COMM 0 A14 100 ‐ 0 7.1 42 Avoid Contact Avoid Contact
1A 1 A101E 225 ‐ 1 19 42 Avoid Contact Avoid Contact
1B 1 B143E 225 ‐ 0 8.6 42 Avoid Contact Avoid Contact
1C‐1 1 C116E 400 ‐ 1 32 42 Avoid Contact Avoid Contact
1C‐2 1 C116E 400 ‐ 1 32 42 Avoid Contact Avoid Contact
1D‐1 1 A115E 225 ‐ 0 15 42 Avoid Contact Avoid Contact
1D‐2 1 A115E 225 ‐ 0 15 42 Avoid Contact Avoid Contact
1K 1 A141E 225 ‐ 1 21 42 Avoid Contact Avoid Contact
BCA 1 C26 200 ‐ 0 8.7 42 Avoid Contact Avoid Contact
BE 1 A10 100 Y 0 5 42 Avoid Contact Avoid Contact
CB‐1A 1 A141E 225 Y 0 9.4 42 Avoid Contact Avoid Contact
EBB‐1 1 B17 100 Y 2 (*N3) 38 42 Avoid Contact Avoid Contact
ECR1‐1 1 AC106E 400 Y 0 6 42 Avoid Contact Avoid Contact
ECR2‐1 1 AC106E 400 Y 0 5.9 42 Avoid Contact Avoid Contact
EM1 1 A101A 100 Y 0 6.4 42 Avoid Contact Avoid Contact
LP1‐1 1 AC110E 225 ‐ 0 12 42 Avoid Contact Avoid Contact
LS‐1A 1 A101E 100 Y 0 5.8 42 Avoid Contact Avoid Contact
LS‐1B 1 B143E 100 Y 2 (*N3) 48 42 Avoid Contact Avoid Contact
LS‐1C 1 C116E 100 Y 0 5 42 Avoid Contact Avoid Contact
POLICE PNL 1 B110 100 Y 1 (*N3) 35 42 Avoid Contact Avoid Contact
PP 1 C114D 225 ‐ 2 (*N3) 39 42 Avoid Contact Avoid Contact
PP1‐1 1 AC110E 400 ‐ 0 7.3 42 Avoid Contact Avoid Contact
PP2‐1 1 AC110E 400 ‐ 0 7.2 42 Avoid Contact Avoid Contact
UNNAMED (2) 1 A20 100 ‐ 0 7.2 42 Avoid Contact Avoid Contact
2A‐1 2 A202E 225 ‐ 0 18 42 Avoid Contact Avoid Contact
2A‐2 2 A202E 225 ‐ 0 17 42 Avoid Contact Avoid Contact
2B 2 B220E 225 ‐ 0 8.4 42 Avoid Contact Avoid Contact
2C‐1 2 C211E 400 ‐ 1 32 42 Avoid Contact Avoid Contact
2C‐2 2 C211E 400 ‐ 1 32 42 Avoid Contact Avoid Contact
2CC‐1 2 C203 400 ‐ 1 30 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
2CC‐2 2 C203 400 ‐ 1 30 42 Avoid Contact Avoid Contact
2C‐MR 2 C208M 125 ‐ 1 (*N3) 36 42 Avoid Contact Avoid Contact
2D‐1 2 A212E 225 ‐ 0 14 42 Avoid Contact Avoid Contact
2D‐2 2 A212E 225 ‐ 0 14 42 Avoid Contact Avoid Contact
2DB 2 A212E 100 ‐ 0 10 42 Avoid Contact Avoid Contact
2K‐1 2 A229E 225 ‐ 1 19 42 Avoid Contact Avoid Contact
2K‐2 2 A229E 225 ‐ 1 19 42 Avoid Contact Avoid Contact
2XR 2 B220B 225 ‐ 3 (*N3) (*N9) 94 42 Avoid Contact Avoid Contact
2XR‐1 2 B223A 125 ‐ 0 4.3 42 Avoid Contact Avoid Contact
2XRA 2 B218 100 ‐ 0 4.7 42 Avoid Contact Avoid Contact
AC‐RM215 2 C203 225 ‐ 0 (*N3) 7 42 Avoid Contact Avoid Contact
B‐CT 2 A229B 225 ‐ 3 (*N3) (*N9) 110 42 Avoid Contact Avoid Contact
C‐1 2 A234 225 Y 0 9.3 42 Avoid Contact Avoid Contact
C‐2 2 A234 225 Y 0 9.1 42 Avoid Contact Avoid Contact
CB‐2A 2 A229E 225 Y 0 8.9 42 Avoid Contact Avoid Contact
Comp RM ‐ A 2 A234 225 ‐ 0 7.6 42 Avoid Contact Avoid Contact
ELAB‐1 2 C203 225 Y 0 6.9 42 Avoid Contact Avoid Contact
ELAB‐2 2 C203 100 Y 0 6.8 42 Avoid Contact Avoid Contact
EM2 2 A230A 225 Y 1 (*N3) 30 42 Avoid Contact Avoid Contact
LS‐2B 2 B226E 100 Y 2 (*N3) 57 42 Avoid Contact Avoid Contact
LS‐2C 2 C211E 100 Y 0 (*N3) 5.2 42 Avoid Contact Avoid Contact
TE 2 A201T 225 Y 0 7 42 Avoid Contact Avoid Contact
UNNAMED (1) 2 B216 100 Y 1 (*N3) 33 42 Avoid Contact Avoid Contact
3A 3 A301E 225 ‐ 0 17 42 Avoid Contact Avoid Contact
3B1 3 B324E 225 ‐ 0 5 42 Avoid Contact Avoid Contact
3B2 3 B324E 225 ‐ 0 5 42 Avoid Contact Avoid Contact
3B2A 3 B324E 100 ‐ 0 5 42 Avoid Contact Avoid Contact
3BR 3 B326 100 ‐ 2 (*N3) 48 42 Avoid Contact Avoid Contact
3C‐1 3 C306E 225 ‐ 1 29 42 Avoid Contact Avoid Contact
3C‐2 3 C306E 225 ‐ 1 28 42 Avoid Contact Avoid Contact
3D‐1 3 A325E 225 ‐ 1 31 42 Avoid Contact Avoid Contact
3D‐2 3 A325E 225 ‐ 1 31 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
3K1 3 A342E 225 ‐ 0 15 42 Avoid Contact Avoid Contact
3K2 3 A342E 225 ‐ 0 15 42 Avoid Contact Avoid Contact
CB‐3C 3 C306E 100 Y 0 (*N3) 5.5 42 Avoid Contact Avoid Contact
CB‐3D 3 A325E 100 Y 0 5.1 42 Avoid Contact Avoid Contact
LS‐3A 3 A301E 100 Y 0 5.6 42 Avoid Contact Avoid Contact
4A 4 A401E 225 ‐ 0 17 42 Avoid Contact Avoid Contact
4AC1 4 B401C 225 Y 1 (*N3) 32 42 Avoid Contact Avoid Contact
4B 4 B401C 400 ‐ 3 (*N9) 111 42 Avoid Contact Avoid Contact
4C‐1 4 C406E 225 ‐ 1 28 42 Avoid Contact Avoid Contact
4C‐2 4 C406E 225 ‐ 1 28 42 Avoid Contact Avoid Contact
4D‐1 4 A429E 225 ‐ 1 30 42 Avoid Contact Avoid Contact
4D‐2 4 A429E 225 ‐ 1 30 42 Avoid Contact Avoid Contact
4K 4 A444E 225 ‐ 0 14 42 Avoid Contact Avoid Contact
CB‐4A 4 A444E 225 Y 0 8.4 42 Avoid Contact Avoid Contact
CB‐4B 4 B401C 400 ‐ 0 5.3 42 Avoid Contact Avoid Contact
CB‐4C 4 C406E 100 Y 2 (*N3) 46 42 Avoid Contact Avoid Contact
CB‐4D 4 A429E 100 Y 0 5 42 Avoid Contact Avoid Contact
DB 4 ICU 400 Y 0 8.4 42 Avoid Contact Avoid Contact
EB4MR 4 B401C 225 Y 0 5.1 42 Avoid Contact Avoid Contact
LS‐4A 4 A401E 100 Y 0 5.3 42 Avoid Contact Avoid Contact
5A 5 A503E 225 ‐ 0 16 42 Avoid Contact Avoid Contact
5C‐1 5 C505E 225 ‐ 1 27 42 Avoid Contact Avoid Contact
5C‐2 5 C505E 225 ‐ 1 27 42 Avoid Contact Avoid Contact
5D‐1 5 A522E 225 Y 1 29 42 Avoid Contact Avoid Contact
5D‐2 5 A522E 225 ‐ 1 29 42 Avoid Contact Avoid Contact
5K 5 A546E 225 ‐ 0 13 42 Avoid Contact Avoid Contact
5KA 5 A546E 225 ‐ 0 17 42 Avoid Contact Avoid Contact
CB‐5C 5 C505E 100 Y 2 (*N3) 50 42 Avoid Contact Avoid Contact
CB‐5D 5 A522E 100 ‐ 0 (*N3) 5.3 42 Avoid Contact Avoid Contact
LS‐5A 5 A503E 100 Y 0 5.2 42 Avoid Contact Avoid Contact
6A1 6 A603E 225 ‐ 0 15 42 Avoid Contact Avoid Contact
6A2 6 A603E 225 ‐ 0 15 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
B 6 A610C 100 ‐ 3 (*N3) (*N9) 70 42 Avoid Contact Avoid Contact
LS‐6A 6 A603E 100 Y 0 5.1 42 Avoid Contact Avoid Contact
7A 7 PENT 225 ‐ 0 15 42 Avoid Contact Avoid Contact
EB7A 7 PENT 100 Y 0 5.7 42 Avoid Contact Avoid Contact
P1A 7 PENT 400 ‐ 0 6.7 42 Avoid Contact Avoid Contact
Bldg 54 ‐ E Bldg 54 80 Y 2 (*N3) (*N9) 57 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
B2 0 A14 400 ‐ 0 8 42 Avoid Contact Avoid Contact
ES 0 A15 600 Y 0 9.1 42 Avoid Contact Avoid Contact
LBA 0 A8E 225 ‐ 0 5 42 Avoid Contact Avoid Contact
MSB 0 A15 1600 ‐ 1 (*N3) 23 42 Avoid Contact Avoid Contact
P1 0 A15 400 ‐ 0 8.7 42 Avoid Contact Avoid Contact
SBA 0 A14 225 ‐ 0 7.3 42 Avoid Contact Avoid Contact
E1A 1 A136E 100 Y 0 5 42 Avoid Contact Avoid Contact
L1A‐1 1 A136E 225 ‐ 0 4.8 42 Avoid Contact Avoid Contact
L1A‐2 1 A136E 225 ‐ 0 4.7 42 Avoid Contact Avoid Contact
L1AA 1 A142A 225 ‐ 0 7.4 42 Avoid Contact Avoid Contact
L1AAA 1 A142A 100 ‐ 0 7.3 42 Avoid Contact Avoid Contact
L1B‐1 1 B112E 225 ‐ 0 5 42 Avoid Contact Avoid Contact
L1B‐2 1 B112E 225 ‐ 0 5 42 Avoid Contact Avoid Contact
L1C‐1 1 C167E 225 ‐ 0 6.3 42 Avoid Contact Avoid Contact
L1C‐2 1 C167E 225 ‐ 0 6.2 42 Avoid Contact Avoid Contact
E2A 2 A232E 100 Y 0 (*N3) 5.3 42 Avoid Contact Avoid Contact
E2B 2 OLD CLST 100 Y 0 3.7 42 Avoid Contact Avoid Contact
L2A‐1 2 A232E 225 ‐ 0 4.6 42 Avoid Contact Avoid Contact
L2A‐2 2 A232E 225 ‐ 0 4.5 42 Avoid Contact Avoid Contact
L2B‐1 2 B216E 225 ‐ 0 4.9 42 Avoid Contact Avoid Contact
L2B‐2 2 B216E 225 ‐ 0 4.9 42 Avoid Contact Avoid Contact
L2C‐1 2 C258E 225 ‐ 0 5.8 42 Avoid Contact Avoid Contact
L2C‐2 2 C258E 225 ‐ 0 5.8 42 Avoid Contact Avoid Contact
E3A 3 A333E 100 Y 2 (*N3) 43 42 Avoid Contact Avoid Contact
L3A‐1 3 A333E 225 ‐ 0 4.2 42 Avoid Contact Avoid Contact
L3A‐2 3 A333E 225 ‐ 0 4.2 42 Avoid Contact Avoid Contact
L3B‐1 3 B313E 225 ‐ 0 4.8 42 Avoid Contact Avoid Contact
L3B‐2 3 B313E 225 ‐ 0 4.8 42 Avoid Contact Avoid Contact
L3C‐1 3 C365E 225 ‐ 0 5.8 42 Avoid Contact Avoid Contact
L3C‐2 3 C365E 225 ‐ 0 5.8 42 Avoid Contact Avoid Contact
L4A 4 PENT 225 ‐ 0 4.2 42 Avoid Contact Avoid Contact
SMOKE 4 PENT 100 ‐ 0 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
A‐1 0 A21 100 ‐ 0 6.7 42 Avoid Contact Avoid Contact
A‐2 0 A21 100 ‐ 0 6.6 42 Avoid Contact Avoid Contact
B‐1 0 B10E 225 ‐ 3 (*N3) 82 42 Avoid Contact Avoid Contact
B‐2 0 B10E 225 ‐ 3 (*N3) 82 42 Avoid Contact Avoid Contact
B‐3 0 A17 225 ‐ 0 5.7 42 Avoid Contact Avoid Contact
C‐1 0 C29E 225 ‐ 0 (*N3) 7.9 42 Avoid Contact Avoid Contact
C‐2 0 C29E 225 ‐ 0 (*N3) 7.9 42 Avoid Contact Avoid Contact
EM 0 A1C 100 Y 0 5.2 42 Avoid Contact Avoid Contact
ES 0 A21 400 Y 3 (*N3) 6.6 42 Avoid Contact Avoid Contact
MSB 0 A21 800 ‐ 4 (*N3) 125 42 Avoid Contact Avoid Contact
D‐1 1 A128E 225 ‐ 3 (*N3) 84 42 Avoid Contact Avoid Contact
D‐2 1 A128E 225 ‐ 3 (*N3) 84 42 Avoid Contact Avoid Contact
E‐1 1 B113E 225 ‐ 3 (*N3) 88 42 Avoid Contact Avoid Contact
E‐2 1 B113E 225 ‐ 3 (*N3) 88 42 Avoid Contact Avoid Contact
ED 1 A128E 100 Y 0 5.1 42 Avoid Contact Avoid Contact
F‐1 1 C143E 225 ‐ 3 (*N3) 87 42 Avoid Contact Avoid Contact
F‐2 1 C143E 225 ‐ 3 (*N3) 86 42 Avoid Contact Avoid Contact
EG 2 A228 100 ‐ 0 5.1 42 Avoid Contact Avoid Contact
G 2 A228 225 ‐ 3 (*N3) 81 42 Avoid Contact Avoid Contact
H‐1 2 B213E 225 ‐ 3 (*N3) 88 42 Avoid Contact Avoid Contact
H‐2 2 B213E 225 ‐ 3 (*N3) 88 42 Avoid Contact Avoid Contact
J‐1 2 C243E 225 ‐ 3 (*N3) 87 42 Avoid Contact Avoid Contact
J‐2 2 C243E 225 ‐ 3 (*N3) 86 42 Avoid Contact Avoid Contact
AC1 PH PH 100 ‐ 0 5.1 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
EBA 0 A2E 100 Y 2 (*N3) 52 42 Avoid Contact Avoid Contact
ES 0 A2E 400 Y 0 (*N3) 7.7 42 Avoid Contact Avoid Contact
LBA 0 A2E 225 ‐ 3 (*N9) 80 42 Avoid Contact Avoid Contact
LBB 0 B9A 225 ‐ 3 (*N9) 81 42 Avoid Contact Avoid Contact
LBC 0 C19 225 ‐ 0 (*N3) 7.8 42 Avoid Contact Avoid Contact
LBS 0 C19 100 Y 3 (*N3) (*N9) 82 42 Avoid Contact Avoid Contact
MSB 0 A2E 600 ‐ 3 (*N9) 109 42 Avoid Contact Avoid Contact
SN 0 Ph Closet 100 Y 0 4.9 42 Avoid Contact Avoid Contact
SR 0 B10 225 ‐ 0 4.4 42 Avoid Contact Avoid Contact
SR1 0 B10 225 ‐ 0 4.4 42 Avoid Contact Avoid Contact
E1A 1 A103E 225 Y 3 (*N3) 58 42 Avoid Contact Avoid Contact
L1A 1 A103E 100 ‐ 3 (*N9) 78 42 Avoid Contact Avoid Contact
L1B‐1 1 B121E 225 ‐ 3 (*N9) 78 42 Avoid Contact Avoid Contact
L1B‐2 1 B121E 225 ‐ 3 (*N9) 78 42 Avoid Contact Avoid Contact
L1C‐1 1 C163E 225 ‐ 3 (*N3) (*N9) 87 42 Avoid Contact Avoid Contact
L1C‐2 1 C163E 225 ‐ 3 (*N3) (*N9) 87 42 Avoid Contact Avoid Contact
LS1 1 A103S 100 Y 3 (*N9) 79 42 Avoid Contact Avoid Contact
E2A 2 A203E 100 Y 3 (*N3) (*N9) 58 42 Avoid Contact Avoid Contact
L2A 2 A203E 225 ‐ 3 (*N9) 76 42 Avoid Contact Avoid Contact
L2B‐1 2 B221E 225 ‐ 3 (*N9) 78 42 Avoid Contact Avoid Contact
L2B‐2 2 B221E 225 ‐ 3 (*N9) 78 42 Avoid Contact Avoid Contact
L2C‐1 2 C251E 225 ‐ 3 (*N3) (*N9) 87 42 Avoid Contact Avoid Contact
L2C‐2 2 C251E 225 ‐ 3 (*N3) (*N9) 87 42 Avoid Contact Avoid Contact
LS2 2 A202E 100 Y 3 (*N9) 84 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
EBA 0 A2E 100 Y 2 (*N3) 50 42 Avoid Contact Avoid Contact
ES 0 C11 400 Y 0 5.7 42 Avoid Contact Avoid Contact
LBA 0 A2E 225 ‐ 3 (*N9) 80 42 Avoid Contact Avoid Contact
LBB 0 B3E 225 ‐ 3 (*N9) 85 42 Avoid Contact Avoid Contact
LBC 0 C11 225 ‐ 0 (*N3) 7.8 42 Avoid Contact Avoid Contact
MSB 0 C11 600 ‐ 3 (*N9) 109 42 Avoid Contact Avoid Contact
SR 0 B4 225 ‐ 3 (*N9) 72 42 Avoid Contact Avoid Contact
SR‐1 0 B4 225 ‐ 0 4.6 42 Avoid Contact Avoid Contact
E1A 1 A102E 100 Y 2 (*N3) 55 42 Avoid Contact Avoid Contact
L1A 1 A102E 225 ‐ 3 (*N9) 78 42 Avoid Contact Avoid Contact
L1B‐1 1 B115E 225 ‐ 3 (*N9) 84 42 Avoid Contact Avoid Contact
L1B‐2 1 B115E 225 ‐ 3 (*N9) 83 42 Avoid Contact Avoid Contact
L1C‐1 1 C147E 225 ‐ 0 (*N3) 8.1 42 Avoid Contact Avoid Contact
L1C‐2 1 C147E 225 ‐ 3 (*N3) (*N9) 89 42 Avoid Contact Avoid Contact
E2A 2 A202E 100 Y 3 (*N3) 59 42 Avoid Contact Avoid Contact
L2A 2 A202E 225 ‐ 3 (*N9) 76 42 Avoid Contact Avoid Contact
L2B‐1 2 B221E 225 ‐ 3 (*N9) 83 42 Avoid Contact Avoid Contact
L2B‐2 2 B221E 225 ‐ 3 (*N9) 82 42 Avoid Contact Avoid Contact
L2C‐1 2 C244E 225 ‐ 3 (*N3) (*N9) 81 42 Avoid Contact Avoid Contact
L2C‐2 2 C244E 225 ‐ 3 (*N3) (*N9) 81 42 Avoid Contact Avoid Contact
E1 (BLDG 55) Bldg 55 100 ‐ 2 (*N9) 50 42 Avoid Contact Avoid Contact
SMOKE Smoke shelter 100 ‐ 2 (*N3) 50 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
N Bldg 53 100 Y 2 (*N9) 45 42 Avoid Contact Avoid Contact
6E ‐ SR 100 Y 0 5 42 Avoid Contact Avoid Contact
B6 ‐ SR 400 ‐ 0 5.3 42 Avoid Contact Avoid Contact
EMERGENCY ‐ SR 400 Y 0 6.6 42 Avoid Contact Avoid Contact
ES ‐ SR 100 Y 0 3.8 42 Avoid Contact Avoid Contact
MSB ‐ SR 400 ‐ 3 (*N9) 101 42 Avoid Contact Avoid Contact
S ‐ SR 225 ‐ 0 (*N3) 7.9 42 Avoid Contact Avoid Contact
A‐1 1 A139E 225 ‐ 3 (*N9) 86 42 Avoid Contact Avoid Contact
A‐2 1 A139E 225 ‐ 3 (*N9) 86 42 Avoid Contact Avoid Contact
B‐1 1 B108E 225 ‐ 3 (*N9) 68 42 Avoid Contact Avoid Contact
B‐2 1 B108E 225 ‐ 3 (*N9) 69 42 Avoid Contact Avoid Contact
C‐1 1 C170E 225 ‐ 3 (*N9) 67 42 Avoid Contact Avoid Contact
C‐2 1 C170E 225 ‐ 3 (*N9) 68 42 Avoid Contact Avoid Contact
EA 1 A139S 225 Y 0 2.7 42 Avoid Contact Avoid Contact
EB 1 B119 100 Y 0 (*N1) 6.2 42 Avoid Contact Avoid Contact
EB‐1 1 B119 100 Y 0 (*N1) 6.2 42 Avoid Contact Avoid Contact
EC 1 C159 100 Y 0 (*N1) 5.9 42 Avoid Contact Avoid Contact
EC‐1 1 C159 100 Y 0 (*N1) 5.9 42 Avoid Contact Avoid Contact
LP 1 C181 100 ‐ 0 3.4 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
B9 0 CHILLER 300 Y 0 7.8 42 Avoid Contact Avoid Contact
EB9 0 CHILLER 100 ‐ 0 3.6 42 Avoid Contact Avoid Contact
9E 1 A022 225 Y 0 8.3 42 Avoid Contact Avoid Contact
9N 1 A022 400 Y 0 8.6 42 Avoid Contact Avoid Contact
A 1 A028E 400 ‐ 0 7 42 Avoid Contact Avoid Contact
CP1 1 B013 225 ‐ 0 5.4 42 Avoid Contact Avoid Contact
CP4 1 B013 225 Y 0 5.3 42 Avoid Contact Avoid Contact
CP5 1 A029 225 Y 0 5.4 42 Avoid Contact Avoid Contact
D‐1 1 B020E 400 ‐ 0 7.5 42 Avoid Contact Avoid Contact
D‐2 1 B020E 400 ‐ 0 7.4 42 Avoid Contact Avoid Contact
EA 1 A028E 100 Y 0 (*N3) 18 42 Avoid Contact Avoid Contact
EDP 1 A022 700 Y 0 13 42 Avoid Contact Avoid Contact
EM1 1 B013 225 Y 0 5.3 42 Avoid Contact Avoid Contact
ES 1 A022 400 Y 0 7.5 42 Avoid Contact Avoid Contact
G‐1 1 C022E 400 ‐ 0 5.5 42 Avoid Contact Avoid Contact
G‐2 1 C022E 400 ‐ 0 5.5 42 Avoid Contact Avoid Contact
MR 1 A022 100 ‐ 0 10 42 Avoid Contact Avoid Contact
MSB 1 A022 1000 ‐ 4 (*N3) (*N9) 151 42 Avoid Contact Avoid Contact
PDU 1 B009 200 ‐ 0 7.3 42 Avoid Contact Avoid Contact
SN 1 A029 100 Y 0 4.3 42 Avoid Contact Avoid Contact
SWBD‐A 1 A022 2000 ‐ Dangerous! (*N3) 155 42 Avoid Contact Avoid Contact
B 2 A123E 400 ‐ 0 6.8 42 Avoid Contact Avoid Contact
CP2 2 B111 400 ‐ 0 5.9 42 Avoid Contact Avoid Contact
CP2A 2 B111 225 Y 0 5.8 42 Avoid Contact Avoid Contact
E‐1 2 B118E 400 ‐ 0 7.2 42 Avoid Contact Avoid Contact
E‐2 2 B118E 400 ‐ 0 7.1 42 Avoid Contact Avoid Contact
EE1 2 B118E 100 Y 0 3.5 42 Avoid Contact Avoid Contact
EH 2 C153E 100 Y 1 (*N3) 20 42 Avoid Contact Avoid Contact
H 2 C153E 400 ‐ 0 5.4 42 Avoid Contact Avoid Contact
C 3 A231E 400 ‐ 0 6.6 42 Avoid Contact Avoid Contact
CP3 3 B209E 600 ‐ 0 7 42 Avoid Contact Avoid Contact
CP3A 3 B209E 400 ‐ 0 6.9 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
EF 3 B226E 100 Y 0 3.3 42 Avoid Contact Avoid Contact
EJ 3 C253E 100 Y 1 (*N3) 21 42 Avoid Contact Avoid Contact
F‐1 3 B226E 400 ‐ 0 7 42 Avoid Contact Avoid Contact
F‐2 3 B226E 400 ‐ 0 6.9 42 Avoid Contact Avoid Contact
J‐1 3 C253E 400 ‐ 0 5.4 42 Avoid Contact Avoid Contact
J‐2 3 C253E 400 ‐ 0 5.3 42 Avoid Contact Avoid Contact
EK 4 PENT 225 Y 3 (*N9) 58 42 Avoid Contact Avoid Contact
K 4 PENT 225 ‐ 0 4.9 42 Avoid Contact Avoid Contact
PP 4 PENT 125 ‐ 3 (*N9) 59 42 Avoid Contact Avoid Contact
A Bldg 45 100 ‐ 0 (*N1) (*N9) 14 42 Avoid Contact Avoid Contact
Hazard Risk Category2
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
A‐1 1 116E 225 ‐ 0 (*N3) 7.5 42 Avoid Contact Avoid Contact
A‐2 1 116E 225 ‐ 0 (*N3) 7.6 42 Avoid Contact Avoid Contact
B1 1 110 100 Y 0 4.9 42 Avoid Contact Avoid Contact
B‐1 1 113E 225 ‐ 0 (*N3) 7.3 42 Avoid Contact Avoid Contact
B2 1 WAREHOUSE 100 ‐ 3 (*N9) 66 42 Avoid Contact Avoid Contact
B‐2 1 113E 225 ‐ 0 (*N3) 7.3 42 Avoid Contact Avoid Contact
BA 1 113E 225 ‐ 0 (*N3) 7.3 42 Avoid Contact Avoid Contact
C‐1 1 103 225 ‐ 3 (*N3) (*N9) 86 42 Avoid Contact Avoid Contact
C‐2 1 103 225 ‐ 3 (*N3) (*N9) 86 42 Avoid Contact Avoid Contact
D1 1 101 225 ‐ 0 4.2 42 Avoid Contact Avoid Contact
D‐1 1 101D 225 ‐ 0 5.3 42 Avoid Contact Avoid Contact
D‐2 1 101D 225 ‐ 0 5.3 42 Avoid Contact Avoid Contact
EDP‐1 1 A125 600 Y 0 (*N3) 11 42 Avoid Contact Avoid Contact
EDP‐2 1 110 400 Y 0 (*N3) 8.5 42 Avoid Contact Avoid Contact
EDR 1 101C 225 Y 3 (*N9) 77 42 Avoid Contact Avoid Contact
EL 1 108B 100 Y 2 (*N9) 52 42 Avoid Contact Avoid Contact
ES 1 125 225 Y 3 (*N9) 72 42 Avoid Contact Avoid Contact
F 1 A125 600 ‐ 0 (*N3) 11 42 Avoid Contact Avoid Contact
KA 1 112 225 ‐ 0 5.5 42 Avoid Contact Avoid Contact
KB 1 112 225 ‐ 0 5.5 42 Avoid Contact Avoid Contact
MSB 1 A125 1200 ‐ 4 (*N9) 137 42 Avoid Contact Avoid Contact
P 1 105 225 ‐ 0 4.9 42 Avoid Contact Avoid Contact
R 1 122 400 Y 0 7.3 42 Avoid Contact Avoid Contact
S 1 A126 225 Y 0 6.3 42 Avoid Contact Avoid Contact
E Bldg 57 80 Y 0 (*N3) 3.9 42 Avoid Contact Avoid Contact
Hazard Risk Category
Arc Flash Boundary
(in.)
Limited Approach
Boundary (in.)
Restricted Approach Boundary
Prohibited Approach Boundary
L1‐1 1 110E 225 ‐ 0 (*N3) 7.3 42 Avoid…