TITLE SHEET

G001

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

REPLACE CONDENSATE LINES AND PUMPS,

OSCAR G. JOHNSON VA MEDICAL CENTER

IRON MOUNTAIN, MI 49801

BID DOCUMENT SET

MARCH 04, 2022

SHEET INDEXGENERAL NOTES

DIRECTOR

ASSOCIATE DIRECTOR

ASSOCIATE DIRECTOR FOR N&PCS

CHIEF OF POLICE

CHIEF OF ENGINEERING

INFECTION CONTROL NURSE

PATIENT SAFETY

A.F.G.E.

INDUSTRIAL HYGIENIST

APPROVALS

CHIEF OF STAFF

SAFETY

VERIFY ALL DIMENSIONS RELATING NEW CONSTRUCTION TO EXISTING CONSTRUCTION.1.

GENERAL TRADE SHALL PATCH HOLES IN SLABS, PARTITIONS, AND CEILINGS CAUSED BY ANY TRADE AS FOLLOWS:2.

A). AT REMOVED DUCTWORK, CONDUIT, AND PIPING

B). AT NEW DUCTWORK, CONDUIT AND PIPING IN EXISTING PARTITIONS

C). AT ADDED OR REMOVED PARTITION MOUNTED ITEMS

WHERE EXPOSED TO VIEW, PATCHED SURFACES SHALL MATCH ADJACENT FINISHES. WORK SHALL MAINTAIN EXISTING

SEPARATION RATINGS.

3.

GENERAL TRADE SHALL REMOVE ACOUSTICAL TILE AND PLASTER CEILINGS WHERE REQUIRED FOR MECHANICAL OR ELECTRICAL TRADES. REINSTALL ACOUSTICAL TILE AND PATCH PLASTER WHEN WORK ABOVE CEILING

HAS BEEN COMPLETED.

4.

CONSTRUCTION IN SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT IS CURRENTLY IN PROGRESS. ACTUAL

EXISTING CONDITIONS MAY VARY FROM CONDITIONS INDICATED ON THESE DRAWINGS.

5.

SEE SPECIFICATION SECTION 01 35 26 FOR INFECTION CONTROL. SEE SPECIFICATION SECTION 01 00 00 FOR PHASING AND WORK

TIME LIMITATIONS

6.

ALL CONTRACTORS UTILIZING ELECTRONIC DRAWING SETS ARE RESPONSIBLE TO CONFIRM DRAWINGS ARE PRINTED/INSERTED INTO OTHER SOFTWARE TO SCALE. CONSTRUCTION DRAWINGS ON FULL SIZE SHEETS ARE TO BE 24" X 36" OR 30" X 42" WHEN

PRINTED AT 1:1. A SCALE VERIFICATION IS PROVIDED BELOW.

7.

4'0" 2' 8' 12'

2'0" 1' 4' 6'

1'0" 6" 2' 3'

8"0" 4" 16" 24"

6"0" 3" 12" 18"

4"0" 2" 8" 12"

2"0" 1" 4" 6"

1/8" = 1'-0"

1/4" = 1'-0"

1/2" = 1'-0"

3/4" = 1'-0"

1" = 1'-0"

1 1/2" = 1'-0"

3" = 1'-0"

SCALE VERIFICATION

8. FURNISH AND INSTALL FIRESTOPS IN WALLS, FLOORS, AND PARTITIONS AND AROUND PENETRATIONS OF PIPE, DUCT, CABLE AND OTHER ELECTRICAL DEVICES OR IN BLANK OPENINGS AS INDICATED AT FIRE RATED LOCATION ON THE REFLECTED CEILING PLAN. FIRE STOPPING SHALL BE INSTALLED AND TESTED AS LISTED IN ASTM E814, E119, AND UNDERWRITERS LABORATORIES: FIRE RESISTANCE DIRECTORY. WHERE THERE IS NO SPECIFIC THIRD PARTY TESTED ASSEMBLY, ENGINEERING JUDGEMENTS SHALL BE BASED UPON THE REFERENCED DOCUMENTS AND MUST BE PROVIDED VIA THIRD PARTY AND SUBMITTED TO THE AHJ FOR APPROVAL PRIOR TO INSTALLATION. COSTS ASSOCIATED WITH THE ENGINEERING JUDGEMENT SHALL BE THE RESPONSIBILITY OF THE FIRESTOPPING TRADE. FIRESTOPPING OF ALL PENETRATIONS SHALL BE BY A LICENSED FIRESTOPPING TRADE. UPON COMPLETION OF THE FIRESTOPPING SYSTEM, PROVIDE A RECORD IN THE O&M MANUAL OF THE INSTALLED SYSTEMS INDICATING THE UL REFERENCE, LOCATION OF THE PENETRATION AND INSTALLED HOURLY RATING. ALL PENETRATIONS SHALL BE LABELED WITH A PERMANENT TAG INDICATED THE HOURLY RATING, SYSTEM REFERENCE NUMBER, INSTALLERS NAME, ADDRESS, PHONE NUMBER AND DATE OF INSTALLATION. TAGS SHALL BE LABELED WITH “WARNING FIRESTOPPING DO NOT

DISTURB. NOTIFY BUILDING MANAGEMENT OF ANY DAMAGE” OR SIMILAR.

A. FIRESTOPPING MATERIALS SHALL CONFORM TO FLAME (F) AND TEMPERATURE (T) RATINGS AS REQUIRED BY LOCAL BUILDING CODE AND AS TESTED BY NATIONALLY ACCEPTED TEST AGENCIES PER ASTM E814, UL 1479, OR UL 2079. THE F RATING MUST BE A MINIMUM OF ONE

(1) HOUR BUT NOT LESS THAN THE FIRE RESISTANCE RATING OF THE ASSEMBLY BEING PENETRATED. T RATING, WHEN REQUIRED BY CODE AUTHORITY, SHALL BE BASED ON THE MEASUREMENT OF THE TEMPERATURE RISE ON THE PENETRATING ITEM(S). THE FIRE TEST

PRESSURE DIFFERENTIAL OF A MINIMUM 0.01" OF WATER COLUMN IS REQUIRED.

B. T AND F RATINGS AT FLOOR PENETRATIONS SHALL BE EQUAL AND NOT LESS THAN 2 HOUR.

C. PENETRATIONS THRU WALL SHALL HAVE AN F RATING EQUAL TO THAT OF THE RATED WALL ASSEMBLY D. SYSTEM SHALL WITHSTAND THE PASSAGE OF COLD SMOKE EITHER AS AN INHERENT PROPERTY OF THE SYSTEM OR BY THE USE OF E. SEPARATE PRODUCT INCLUDED AS A PART OF THE UL SYSTEM OR DEVICE AND DESIGNED TO PERFORM THIS FUNCTION.

1.1. AT SMOKE BARRIER WALLS - 1S, 2S, AND 3S WALLS IN HOSPITAL OCCUPANCY, WALL ASSEMBLIES MUST HAVE A MAXIMUM L RATING OF 50

CFM PER 100SF OF WALL ASSEMBLY.

F. SMOKE RATED WALLS SHALL BE SEALED WITH A PRODUCT TO RESIST THE PASSAGE OF SMOKE.

G. FIRESTOPPING PRODUCTS SHALL BE ASBESTOS-FREE, FREE OF ANY PCBS, AND FREE OF ANY LEAD.

H. FOR ALL CABLING FIRE PENETRATIONS AT WALLS, PROVIDE THE EZ-PATH FIRE RATED PATHWAY SYSTEM BY SPECIFIED TECHNOLOGIES, INC. OR EQUIVALENT SYSTEM BY HILTI CORPORATION.

10. PROVIDE MANUFACTURER'S STANDARD WARRANTY ON ALL ITEMS.

9. WHERE MECHANICAL AND ELECTRICAL PENETRATIONS THROUGH FLOOR SLABS ARE REMOVED, OR CUT FOR NEW WORK, PATCH HOLES

THROUGH THE SLAB.

B. FILL HOLES 3" TO 12" IN DIAMETER WITH CLASS B CONCRETE. ANCHOR TO SLAB WITH TWO NO. 4 DOWELS.

C. FILL HOLES 12" X 12" TO 36" X 36" WITH NO. 4 DOWELS, 8" O.C. BOTH WAYS.

11. THE SEALANT SCHEDULE IN NO WAY LISTS EVERY SEALANT JOINT CONDITION REQUIRED ON THIS PROJECT AND DOES NOT RELIEVE THE CONTRACTOR RESPONSIBILITY TO CAULK ITEMS AS INDICATED IN DETAILS. REFERENCE DETAILS AND NOTES FOR REQUIRED SEALANT LOCATIONS. UNLESS NOTED OTHERWISE PROVIDE SEALANT PER THE BELOW SCHEDULE APPROVED FOR USE WITH MATERIAL INSTALLED AGAINST (USE M-MORTAR, G-GLASS, A-ALUMINUM, O-OTHER (LIST ACCEPTABLE SUBSTRATES AND PREPARATIONS)). PRIOR TO INSTALLATION OF SEALANT, CONTRACTOR SHALL PROVIDE A SEALANT SCHEDULE SHOWING PRODUCT SELECTION, MANUFACTURER'S APPROVAL FOR MATERIAL USAGE (PROVIDE PRIMER IF REQUIRED) AND WITH MANUFACTURERS FULL SELECTION OF COLORS SUBMITTED TO THE ARCHITECT FOR REVIEW FOR EACH APPLICATION:

D. ALL HOLES TO BE FILLED IN STRUCTURAL FLOOR SLABS SHALL BE FILLED OR FORMED IN SUCH A MANNER AS

TO PREVENT NEW CURED CONCRETE FROM FALLING TO FLOOR BELOW.

E. PATCH EXISTING SLABS ON GRADE WHERE FLOOR HAS BEEN CUT FOR PLUMBING, HEATING AND OTHER REMODELING WORK. REINFORCE CUTS GREATER THAN 24" IN EACH DIRECTION WITH 6 X 6 WL.4 X WL.4 WIRE MESH. REINFORCE TRENCHES LESS THAN 24" WIDE WITH TWO #3 RODS CONTINUOUS. REPAIR UNDERSLAB

VAPOR RETARDER WITH MATERIAL EQUAL TO ORIGINAL INSTALLATION.

A. FILL HOLES 3" AND SMALLER IN DIAMETER WITH NON-SHRINK GROUT.

1. ALL PRESENT SERVICES INSTALLED AND OPERATING SHALL BE KEPT

IN OPERATION THROUGH THE NEW CONSTRUCTION UNTIL EQUAL

NEW SERVICES OR TEMPORARY LINES SATISFACTORY TO OWNER

ARE INSTALLED AND OPERATING

2. PARTITIONS SHOWN TO BE REMOVED SHALL BE COMPLETELY

REMOVED FROM STRUCTURE ABOVE TO STRUCTURAL FLOOR SLAB

3. CUT OPENINGS IN EXISTING WALLS. OPENINGS IN MASONRY AND

CONCRETE SHALL BE SAWCUT; EXECUTE WORK WITH A MINIMUM

DISTURBANCE TO EXISTING CONSTRUCTION WHICH REMAINS

4. UNLESS NOTED OTHERWISE ON THE PLANS, REMOVE EXISTING BASE

AS REQUIRED TO INSTALL NEW BASE. BASE SHALL BE REMOVED

DOWN TO ORIGINAL FINISHED WALL SURFACE; REMOVE ALL

ADHESIVE RESIDUE WHICH WILL INTERFERE WITH INSTALLATION OF

NEW BASE

5. ALL MATERIALS, RUBBISH, AND DEBRIS SHALL BE REMOVED FROM

THE BUILDING AND FROM THE PREMISES AS SOON AS IT

ACCUMULATES; REMOVAL OF RUBBISH AND DEBRIS SHALL BE

CONDUCTED IN SUCH A WAY THAT A MINIMUM OF DUST IS CAUSED

6. MAINTAIN OWNER OCCUPIED AREAS AS CLEAN AS POSSIBLE TO

AVOID INTERFERENCE WITH OWNER'S OPERATIONS

DEMOLITION NOTES

SEALANT SCHEDULE

SILICONE - 50% MOVEMENT -

CLASS 50

SILICONE - 25%

MOVEMENT/MILDEW

RESISTANT - CLASS

SINGLE

COMPONENT

URETHANE - 35%

MOVEMENT -

CLASS 35

MULTI-COMPONENT

URETHANE - 50%

MOVEMENT - CLASS

TAMPER RESISTANT

URETHANE - 12.5%

MOVEMENT CLASS

12.5 , ASTM D-412

375 TENSILE

STRENGTH

TAMPER PROOF

EPOXY - 0%

MOVEMENT CLASS 0

ASTM C-882 3530

BOND STRENGTH

LATEX - NO MOVEMENT -

CLASS 12.5

ACOUSTICAL

SEALANT -

NON-HEAD OF

WALL - 12.5%

MOVEMENT

ACOUSTICAL SEALANT

- HEAD OF WALL -

EXPANSION JOINTS -

33% MOVEMENT

BUILDING

INTERIOR -

UTILIZE

TAMPER

RESISTANT/

PROOF

PRODUCTS

ONLY IN

PSYCHIATRIC

CARE AREAS

BELOW

CEILING

LINES

JOINT BETWEEN SILLS AND

EXTERIOR FENESTRATIONS:

GRADE NS

JOINTS BETWEEN

PLUMBING FIXTURES

AND ADJOINING

MATERIALS: GRADE

NS

CONTROL JOINTS

SCHEDULED TO

BE CAULKED:

GRADE NS

EXPANSION JOINTS

NOT EXPOSED TO

UV: GRADE NS -

VERTICAL (AND

CEILING), GRADE P,

USE T - HORIZONTAL

CONTROL JOINTS/

EXPANSION

SCHEDULED TO BE

CAULKED: GRADE

NS AT VERTICAL,

GRADE P USE T AT

HORIZONTAL

JOINT BETWEEN

WALLS AND

ACOUSTICAL GRID:

GRADE NS

INTERIOR DOOR FRAMES

NOT EXPOSED TO UV, AT

INTERSECTION OF WALL

AND FRAME: GRADE NS, P

TYPICAL. USE SINGLE

COMPONENT URETHANE

SEALANT GRADE NS, T AT

FLOOR INTERSECTION

WALL

PERIMETERS

HEAD OF WALL JOINTS

JOINT BETWEEN INTEGRAL

BASE AND DOOR FRAMES:

GRADE NS

VERTICAL JOINTS AT

INSIDE CORNERS OF

CERAMIC TILE

CONDITIONS: GRADE

NS

PENETRATIONS

OF MECHANICAL

EQUIPMENT IN

SMOKE TIGHT

WALLS: GRADE

NS

JOINTS BETWEEN

DIS-SIMILAR

MATERIALS: GRADE

NS

INTERIOR DOOR

FRAMES NOT

EXPOSED TO UV, AT

INTERSECTION OF

WALL AND FRAME:

GRADE NS, P

TYPICAL.

JOINTS WHERE NO

MOVEMENT IS EXPECTED:

GRADE NS

SMOKE RESISTANT

EXPANSION JOINTS

(WHERE SILICONE

SEALANTS ARE NOT

UTILIZED)

EXPANSION JOINTS EXPOSED

TO UV: GRADE NS VERTICAL,

GRADE P USE T - HORIZONTAL

JOINT BETWEEN

TILED FLOOR AND

WALL

INTERSECTIONS:

GRADE NS, USE T

TERMINATION OF

VINYL WALL

COVERING:

GRADE NS

BETWEEN

COUNTERTOP AND

WALL SURFACES,

JOINTS BETWEEN

SILLS AND

EXTERIOR

FENESTRATIONS:

GRADE NS

JOINTS WHERE NO

MOVEMENT IS

EXPECTED: GRADE

NS

JOINTS BETWEEN DIS-SIMILAR

MATERIALS SUBJECT TO UV

EXPOSURE: GRADE NS

BETWEEN

COUNTERTOP AND

WALL SURFACES:

GRADE NS

JOINT BETWEEN

WALLS AND

ACOUSTICAL

GRID: GRADE NS

JOINTS BETWEEN

PLUMBING

FIXTURES AND

ADJOINING

MATERIALS: GRADE

NS

JOINTS BETWEEN

DIS-SIMILAR

MATERIALS NOT

SUBJECT TO UV

EXPOSURE:

GRADE NS

JOINT BETWEEN

INTEGRAL BASE

AND DOOR FRAMES:

GRADE NS

1. SUBMIT SEALANT SCHEDULE PRIOR TO INSTALLATION OF SEALANTS INDICATING WHERE SEALANT IS SCHEDULED TO BE INSTALLED FOR APPROVAL. PROVIDE ACTUAL SAMPLES FOR COLOR SELECTION FROM FULL RANGE OF COLORS FOR EACH SEALANT SCHEDULED TO BE INSTALLED. SEALANTS MUST BE FROM ONE OF THE PRODUCTS LISTED BELOW

2. SILICONE SEALANT

2.1. DOW CORNING CORPORATION: 795 SILICONE BUILDING SEALANT

2.2. MOMENTIVE PERFORMANCE MATERIALS (GE): SILPRUF NB SCS9000

2.3. PECORA CORPORATION: 890 NST SILICONE SEALANT

2.4. TREMCO: SPECTREM 1

3. URETHANE JOINT SEALANTS

3.1. BASF BUILDING SYSTEMS (SONNEBORN): SONOLASTIC NP-1

3.2. BOSTIK, INC.: CHEM-CALK 2020

3.3. SIKA CORPORATION: SIKAFLEX-1A

4. MULTI-COMPONENT NON-SAG URETHANE

4.1. DYNATROL II

4.2. TREMCO DYMERIC 240/240FC

5. ACOUSTICAL SEALANT (EXCEPT HEAD OF WALL)

5.1. PECORA AC-20 FTR

5.2. USG SHEETROCK ACOUSTICAL SEALANT

6. ACOUSTICAL SEALANT (HEAD OF WALL)

6.1. FIRE JOINT SPRAY (CFS-SP WB), MANUFACTURED BY HILTI INC., TULSA, OKLAHOMA, PHONE: 800-879-6000

6.2. RECTORSEAL SMOKE AND ACOUSTIC SEALANT, MANUFACTURED BY RECTORSEAL, HOUSTON, TEXAS, PHONE: 800-231-3345

7. TAMPER RESISTANT URETHANE (POLYURETHANE) SEALANT

7.1. PECORA DYNAFLEX

7.2. BASF MASTERSEAL CR 195

7.3. SIKAFLEX 2C NS TG

8. TAMPER PROOF EPOXY SEALANT

8.1. PECORA DYNAPOXY EP-1200

SEALANT NOTES

GENERAL

G001 TITLE SHEET

HVAC

MS101 BOILER PLANT AND SITE PLANS

MD101 SUB-BASEMENT DEMOLITION PLAN

MD102 BASEMENT DEMOLITION PLAN - WEST

MD103 BASEMENT DEMOLITION PLAN - EAST

MD104 SECOND FLOOR DEMOLITION PLAN

MD105 FOURTH FLOOR DEMOLITION PLAN

MD106 SIXTH FLOOR DEMOLITION PLAN

MP101 SUB-BASEMENT NEW WORK PLAN

MP102 BASEMENT NEW WORK PLAN - WEST

MP103 BASEMENT NEW WORK PLAN - EAST

MP104 SECOND FLOOR NEW WORK PLAN

MP105 FOURTH FLOOR NEW WORK PLAN

MP106 SIXTH FLOOR NEW WORK PLAN

M501 DETAILS

M601 SCHEDULES

ELECTRICAL

ED101 SUB-BASEMENT DEMOLITION PLAN

EP101 SUB-BASEMENT POWER PLAN

EP102 SIXTH FLOOR NEW WORK PLAN

E601 SCHEDULES

J.G.D. K.K.S.

DWG. 01 OF 20

MULTICORELINK:21FEDE0500MS101WZ-21FEDE0500MS101WZ

MULTICORELINK:21FEDE0500MS101WZ-21FEDE0500MS101WZ

MULTICORELINK:21FED0500MD101WFSBE-MD101

MULTICORELINK:21FED0500MD101WFSBE-MD101

MULTICORELINK:21FED0500MD102WF00W-MD102

MULTICORELINK:21FED0500MD102WF00W-MD102

MULTICORELINK:21FED0500MD103WF00E-MD103

MULTICORELINK:21FED0500MD103WF00E-MD103

MULTICORELINK:21FED0500MD104WF02W-MD104

MULTICORELINK:21FED0500MD104WF02W-MD104

MULTICORELINK:21FED0500MD105WF04-MD105

MULTICORELINK:21FED0500MD105WF04-MD105

MULTICORELINK:21FED0500MD106WF06-MD106

MULTICORELINK:21FED0500MD106WF06-MD106

MULTICORELINK:21FED0500MP101WFSBE-MP101

MULTICORELINK:21FED0500MP101WFSBE-MP101

MULTICORELINK:21FED0500MP102WF00W-MP102

MULTICORELINK:21FED0500MP102WF00W-MP102

MULTICORELINK:21FED0500MP103WF00E-MP103

MULTICORELINK:21FED0500MP103WF00E-MP103

MULTICORELINK:21FED0500MP104WF02W-MP104

MULTICORELINK:21FED0500MP104WF02W-MP104

MULTICORELINK:21FED0500MP105WF04-MP105

MULTICORELINK:21FED0500MP105WF04-MP105

MULTICORELINK:21FED0500M501WD-M501

MULTICORELINK:21FED0500M501WD-M501

MULTICORELINK:21FED0500M601WS-M601

MULTICORELINK:21FED0500M601WS-M601

6"HPS-UP

3"HPS-UP

4"CPD-UP

TU

N

N

EL

T O

M

AI

N B

U

IL

D

IN

G

6" AIR

INTAKE

6" ASH LINE

6" ASH INTAKE WITH

GRID, GRID HOPPER

& DUST SHIELD

(2 PER BOILER).

INCLINED

APRON

FEEDER

PIPING

STACKED

ALONG

WALL IN

TUNNEL

REMOVE 3/4" HPC FROM STEAM

MAIN DRIP ABOVE TO LPS.

REMOVE

6" LPS IN

TUNNEL

- SEE

F2/MS101

HPC

G

AS

G

AS

G

AS

G

AS

GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS

G as

G

AS

6"HPS, 3"HPS, 6"LPS AND

4"CPD STACKED ALONG

WALL IN TUNNEL

REMOVE 6"LPS

EXPANSION

JOINT IN TUNNEL

REMOVE 6"LPS PIPE IN TUNNEL

FROM SUB-BASEMENT TO BOILER

PLANT (SUPPORTS TO REMAIN).

REMOVE 6"LPS PIPE IN TUNNEL

FROM SUB-BASEMENT TO BOILER

PLANT (SUPPORTS TO REMAIN).

ABANDONED

LPS AND LPCR

IN CONDUIT

REMOVE 6" AND 3" HPS DRIP

TRAPS TO LPS. PROVIDE NEW

TRAPS AND EXTEND 1" HPC TO

SUB-BASEMENT (T-11 AND T-10).

F3 M501

C9

MS101

C9

MS101

SEE DETAIL

THIS SHEET

8" UP

6" H.P. STEAM-DN.

3" H.P. STEAM-DN.

6" LP. STEAM-UP & DN.

4" PUMP DISCHARGE-DN.

FORCED DRAFT FAN-S.W.S.I.

10,000 C.F.M.-3" S.P.- 700 R.P.M.-8.5 B.H.P.

DRIVE-ELECTRIC MOTOR ON

BOILERS 2 & 3 AND COMBI-

NATION ELECTRIC MOTOR &

STEAM TURBINE ON BOILER

NO.1.

MOTOR: 10 H.P.-3 PHASE-208 V.

1200 R.P.M.-60 CVCLE

TURBINE: ALL PURPOSE-100 LBS

OPERATING PRESSURE-5 LBS

BACK PRESSURE.

DUAL DRIVE ON BOILER NO.1

TO SHOW COMBINATION ARRANGEMENT ONLY

BOILER (TYPICAL)

HEATING SURFACE EXCLUSIVE

OF REAR WATER WALL-2924

2"

2"

1"

HEADER BLOW OFF

(TYPICAL) SEE

DETAIL SHEET

BOILER NO.3

1"

1"

1" UP

1"

3"3"

2"

2"

1"

1"

UP TO FEED WATER

REGULATOR (TYPICAL)

MUD DRUM BLOW-

OFF (TYPICAL) SEE

DETAIL-SHEET

CINDER REINJECTION

SYSTEM-TYPICAL FOR

ALL BOILERS-SEE

SECTION "A-A".

STEAM JETS

(TYPICAL)

BOILER NO.2

3"3"

2"

2"

TO TURBINE DRIVE FOR STOKER

BOILER NO.1

4"

INSTRUMENT AND

COMBUSTION CONTROL

PANEL (SEE SPECS)

R

EM

O

VA

BL

E

AC

C

ES

S

PA

N

EL

S

O N

B

AC

K

SPREADER TYPE

STOKER. (1 PER BOILER)

ELECTRIC MOTOR-1 HP-

3 PHASE-208V.-60~

1750 RPM-(1 PER BOILER)

4"

TUBULAR DUST

COLLECTOR

(TYPICAL ALL BOILERS)

SEE SECTION "A-A"

RECIPROCATING DUPLEX

BOILER FEED PUMPS. NO.1

UNIT ARRANGED FOR TUBE

CLEANER SERVICE.

PUMPS-THREE-EACH TO DE-

LIVER 15000 LBS/HR. AT 175 LBS.

PRESSURE.

ENGINE RATED AT 100 LBS

WITH 5 LB DISCHARGE PRESSURE

FOR PIPING SEE DETAIL

THIS SHEET

FUNNEL-SEE ISOMETRIC

DETAIL OF TYPICAL PIPING

& CONNECTIONS FOR BOILER

FEED PUMPS

4" VENT

TO FLOOR DRAIN

SEE BSMT. PLAN-THIS SHEET

4" 3" 3" 3"

4"

4" 3"

4"

2" 3" 11

4"

3"

1"

2"

ASH HANDLING CONTROL

PANEL-SEE DETAIL

THIS SHEET.

2" H

.P . S

TE

AM

. U P.

2"

4"

3" 3"

NO.

1 FUNNEL

4"

NO.

FLOOR

DRAIN

FUNNEL

NO.

FLOOR

DRAIN

FUNNEL

1"1"

2"

PN

68 U.H.

1610 R.P.M.

256 C.F.M.42 U.H.

850 R.P.M.

135 C.F.M.

REMOVE 3/4" HPC

TO TUNNEL BELOW.

SEE C7/MS101

EXTEND NEW 1" HPC

PIPE TO LPS MAIN

AT X=11'-0"

REPLACE HP DRIP

TRAP NEAR FLOOR

F3 M501

T-

6" H.P. STEAM

3" H.P. STEAM

REMOVE 6"-5# STEAM

4" ROW WATER

2" SOFT WATER

4" RUMP D.S.C.

FA

TEL

SEC

PRI

A-A

A-A

ELECTRICAL

CONDUITS TIGHT

TO TUNNEL WALL

REMOVE 6" LPS

NEW 1" DRIP TRAPS

(T-11 AND T-10)

F3 M501

1" HPC THRU TUNNEL

TO SUB-BASEMENT

BOILER PLANT AND SITE PLANS

MS101J.G.D. K.K.S.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MS101

C7 BOILER PLANT FOUNDATION PLAN

1/8" = 1'-0"

MS101

F2 SITE PLAN

1" = 30'-0"

N

4'0" 2' 8' 12'

N

4'0" 2' 8' 12'

N

15'0' 30' 45'

MS101

F7 BOILER PLANT FIRST FLOOR PLAN

1/8" = 1'-0"

MS101

C9 TUNNEL SECTION

NO SCALE

DWG. 02 OF 20

AutoCAD SHX Text

DN.

AutoCAD SHX Text

UP

AutoCAD SHX Text

DAMPER

AutoCAD SHX Text

SMOKER

AutoCAD SHX Text

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

COMPACTOR PAD

AutoCAD SHX Text

HVAC, MISC EQUIP.

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text

BOILER PLANT/GARAGE

AutoCAD SHX Text

BLDG 10

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

MAIN BUILDING 1

AutoCAD SHX Text

BLDG 12

AutoCAD SHX Text

AutoCAD SHX Text

BLDG 19

AutoCAD SHX Text

SALT SHED

AutoCAD SHX Text

(4)BENCH PAD

AutoCAD SHX Text

FUEL STATION

AutoCAD SHX Text

CONTROLS

AutoCAD SHX Text

INCENERATOR STORAGE

AutoCAD SHX Text

ELECT. SWITCHGEAR

AutoCAD SHX Text

CONTROLS

AutoCAD SHX Text

FUEL STATION

AutoCAD SHX Text

TUNNEL

AutoCAD SHX Text

BLDG 11

AutoCAD SHX Text

SALT SHED

AutoCAD SHX Text

BLDG 19

AutoCAD SHX Text

STORAGE

AutoCAD SHX Text

HAZ. STORAGE

AutoCAD SHX Text

AutoCAD SHX Text

CONC WALK

AutoCAD SHX Text

MAIN BUILDING 1

AutoCAD SHX Text

BLDG 3

AutoCAD SHX Text

BLDG 10

AutoCAD SHX Text

BOILER PLANT/GARAGE

AutoCAD SHX Text

BLDG 2

AutoCAD SHX Text #20

AutoCAD SHX Text

SMOKER

AutoCAD SHX Text #17

MULTICOREVIEWLINK:M501,X005 - HPS TRAP ASSEMBLY

MULTICORELINK:21FED0500M501WD-M501

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text 1"

AutoCAD SHX Text P

AutoCAD SHX Text

AutoCAD SHX Text T

AutoCAD SHX Text T

MULTICOREVIEWLINK:M501,X005 - HPS TRAP ASSEMBLY

MULTICORELINK:21FED0500M501WD-M501

AutoCAD SHX Text

DN

AutoCAD SHX Text

UP

MULTICOREVIEWLINK:M501,X005 - HPS TRAP ASSEMBLY

MULTICORELINK:21FED0500M501WD-M501

2"LPC

8" MPS HEADER

CPD

MPS (1-1/4") PRV 110# - 60#

TO BOILER PLANT

MPS (2-1/2" AND 2") PRV 110# - 50#

LPS (2-1/2" AND 2") PRV 50# - 10#

1-1/2"LPS-UP

1"LPC-UP

PI

TC

H 2" X=

1' -1

0"

MPS/C TO AIR

CURTAIN

6"LPS

4"CPD

6"HPS-TO BOILER PLANT

3"HPS-TO BOILER PLANT

3/4"MPC

REMOVE 1" LPS

3/4"HPC

3/4"HPC

MPC TO

TUNNELCAP

REMOVE 3/4" LPC

DRIP AND PIPE

REMOVE 100' OF ABANDONED 1" MPC

PIPE THRU TUNNEL AT EAST

REMOVE 350' OF 6" LPS PIPE TO

BOILER BUILD THRU TUNNEL - SEE MS101

REMOVE HPS - 4" PRV, GATE VALVE AND

4x6 RELIEF VALVE

MPC MPC

REMOVE (4) PRV AIR LOADERS AND PIPE TO PRV

6"

6"

3"

1"

4"CPD

X=9'-4"

6" LPS

CPD

1" 20 PSI STEAM

SUPPLY AND

CONDENSATE

RETURN

1"

2"

V

6"

TO KITCHEN

PRV

4" LPS

HX-3

HX-4

3" TO DOM. WH HEADER

2"

3"

1 "12

X=1'-3" 8"

3"V X=7'-8"

X=9'-4"

NEW CONNECTION

1 "12

3"LPC

X=15"

TEMPORARILY LOCATE CONDENSATE

RECEIVER AND PUMP #1 HERE. SET

ON 2" PAD.

CP

D

NEW CONNECTION

EXTEND 2"

2"

2"

3 1/2"

3 12"

6"

2"

6"

2 1/2"

2"

4" 6"

2 1/2"

5" 2"

6"

3"

12" LPS HEADER

6" 10"

4"CPD

4" HPS UP

4"3"

1"

4"CPD

X=9'-4"

2" OVERFLOW TO

FLOOR DRAIN

6" LPS

8" HPS HEADER

4" X=6'-8"

4"

3" LPC UP

4" LPS UP

2" MPS UP

3"

8" MPS HEADER

4"

1" HPC-UP

4" HPC

3/4" HPC

2" HPC

2" HPC

X=6'-4"

2" HPC

2" HPC

4" HWS/R-UP

2"

CPD

V

1" 20 PSI STEAM

SUPPLY AND

CONDENSATE

RETURN

1"

2"

CPD

CP

D

CONDENSATE PUMP

V

MPS (1-1/4") PRV 110# - 60#

6"

3/4"

TO KITCHEN

PRV

6" MPS-UP

2" MPC-UP

X=9'-3"

X=8'-1"X=7'-8" X=7'-8"

X=6'-10"

MPS (2-1/2" AND 2") PRV 110# - 50#

LPS (2-1/2" AND 2") PRV 50# - 10#

4" LPS

HX-3

HX-4

3" TO DOM. WH

6"

4"

2"

3"

3"

4"

4"

3"

3/4"

X=1'-9"

2" X=9'-8"

X=8'-2"

3"LPC-UP

X=2'-6"

3" X=8'-0"

4"

2"MPS

6" LPS

HEADER

6"LPS

6"MPS

HPS 1/2" PRV 100# - 40#

2"

2"

4"2- 1/2" 2-1/2"

3/4" LPS TRAP

1"

4"

X=5'-3"

3/4"HPC

3/4"HPC

REMOVE (5) MPC

AND HPC DRIP

TRAPS TO LPS PIPE

CAP

6"

6"

REMOVE HPS - 4" PRV, GATE VALVE AND

4x6 RELIEF VALVE

CAP

6" V-UP

6"

4" V

3"

CAP

CAP

REMOVE HPS, DRIP AND

PRV TO PUMP TRAPS

REMOVE (2) COND STEAM

PUMP TRAPS, TANK AND

PIPING

SEE PLAN FOR TEMPORARY PUMP

AND RECEIVER TO ALLOW FOR NEW

EQUIPMENT INSTALLATION.

1 "12

1 "12

CAP

REMOVE A SECTION

OF VENT PIPE

REMOVE 4" LPC

AND STRAINER TO

TANK

REMOVE A SECTION OF 1 1/2"

LPC FROM DOMESTIC

HEATERS

V

X=1'-3"

CAP

REMOVE LPS - 4"PRV,

GATE VALVE AND 4x6

RELIEF VALVE

8"

8"

3"V X=7'-8"

REMOVE (4) PRV AIR LOADERS AND PIPE TO PRV

10"

TCP

REMOVE 12'-0" SECTION

REMOVE

REMOVE

3/4"

AND PIPING

OF

4"HWS/R

X=8'-6"

X=9'-4"

REPLACE PRV

REPLACE PRV

ST

EA

M

TU

NN

EL

FD

FD FD

FD

STAIR 2

UP

UP

SERVICE

ELEV

S004

S001

S002

S003

SUB-BASEMENT DEMOLITION

PLAN

MD101

DWG. 03 OF 20

2'0" 1' 4' 6'

N

KEYPLAN

NO SCALE

N J.G.D. K.K.S.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MD101

F3 SUB-BASEMENT DEMOLITION PLAN

1/4" = 1'-0"

MD101

C8 SUB-BASEMENT TEMPORARY CONDENSATE TANK AND PUMP PLAN

1/4" = 1'-0" 2'0" 1' 4' 6'

N

REMOVE PUMP AND PIPING WHEN OTHER

SYSTEM IS OPERATIONAL AND MOVE

EQUIPMENT UP TO SIXTH FLOOR.

GENERAL NOTES

1. SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT MAY

EITHER BE STARTING CONSTRUCTION SOON, UNDER CONSTRUCTION

NOW OR FINISHING UP CONSTRUCTION. SOME OF THESE PROJECTS

MAY OVERLAP EACH OTHER. COORDINATE WITH OWNER AND ANY

APPLICABLE CONTRACTORS OF PROJECTS ON SEQUENCE OR

PHASING OF OVERLAPPING PROJECTS TO ENSURE ACCURACY AND

COORDINATED DRAWINGS. NOTIFY OWNER/ARCHITECT OF ANY

DISCREPANICES WITHIN PROJECTS.

AutoCAD SHX Text

ERV

AutoCAD SHX Text

AutoCAD SHX Text

ERV

AutoCAD SHX Text

AutoCAD SHX Text

AHU

AutoCAD SHX Text

AutoCAD SHX Text

AHU

AutoCAD SHX Text

VHAIROKleinD Pencil

VHAIROKleinD Typewritten Text Replace valve

VHAIROKleinD Typewritten Text Removed and replace 6" MPS steam valve as marked

VHAIROKleinD Text Box Asbestos estimated quantity

(11) Aircell elbows

(3) steam gaskets

FLT

AHU

AHU-6

TCP

AHU-6

-1225 SUP

-270 O.A. (22%)

-955 RET

TUNNEL ACCESS

(CONFINED SPACE)

2"3/4"

2" HWS/R UP

3" HWS/R

3/4"

1" DOWN THRU

ABANDONED

CONVECTOR

3/4"

3/4"

EXISTING 1-1/4" PRV

50# TO 10# W/ BYPASS

2 1/2" MPS-DN

S-1

S-2 R-1

R-2

R-3

S-3

R-4

X=7'-0"

2" LPCR-DN

EXISTING AHU-016

FRPS

S-4

R-5

3/4" 1"

EXISTING

CONVECTOR

T

FCU-001

1"

EXISTING

CONVECTOR

4"

1"

1"

EX. STEAM COIL

EX. HUMIDIFIER

LPS

LPC

LPS

LPC

1"

EX. FTR

1-1/4"LPCR-DN

1 1/2" LPS

3/4"LPCR-DN

1"LPS

T

1-1/2"

1-1/2" 3/4"

3/4" DRIP TRAP

X=10'-0"

X=8'-5"

3/4"

X=7'-9" FRPS(TYP.)

FRPS

1" LPS-UP

1" LPCR-UP

3" LPS

HEADER

DEMO PIPE

SEE DETAIL

E1/M501

2"

TCP

V

2"

REMOVE 1-1/2x2

RELIEF VALVE AND

PIPING TO

EXTERIOR

EXISTING

AHU

EXISTING

RETURN

FAN

2" HPS DN

TO TUNNEL

EXISTING PRV

125# TO 10#

EXISTING SNOW MELT

SYSTEM CONTROL

PANEL

2"

EX. AIR SEP

EXPANSION TANK

TO EXISTING SNOW MELT SYSTEM

1 1/4"

HX-21 P-1

P-2

R-53

S-54 R-5

S-5

S-50

R-51

S-51

CONV. AT FLOOR LINE

S-53

S-52 R-52

1-1/2"LPCR-DN

EXISTING

STEAM COIL

3"LPS

EXISTING

HUMIDIFIER

EX. FTR

EX. FTR

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4"

BASEMENT DEMOLITION PLAN - WEST

MD102

DWG. 04 OF 20

KEYPLAN

NO SCALE

N

N

2'0" 1' 4' 6'

J.G.D. K.K.S.

GENERAL NOTES

1. SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT MAY

EITHER BE STARTING CONSTRUCTION SOON, UNDER CONSTRUCTION

NOW OR FINISHING UP CONSTRUCTION. SOME OF THESE PROJECTS

MAY OVERLAP EACH OTHER. COORDINATE WITH OWNER AND ANY

APPLICABLE CONTRACTORS OF PROJECTS ON SEQUENCE OR

PHASING OF OVERLAPPING PROJECTS TO ENSURE ACCURACY AND

COORDINATED DRAWINGS. NOTIFY OWNER/ARCHITECT OF ANY

DISCREPANICES WITHIN PROJECTS.

SEE GENERAL NOTE 1 FOR

THIS AREA. VA PROJECT

585-18-114 (UPGRADE

ENTRANCES).

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MD102

F3 PARTIAL BASEMENT FLOOR PLAN - DEMOLITION (SOUTH)

1/4" = 1'-0"

MD102

C5 PARTIAL BASEMENT FLOOR PLAN - DEMOLITION (NORTH)

1/4" = 1'-0"

N

2'0" 1' 4' 6'

NO DEMOLITION WORK - SEE NEW

WORK PLAN. PLAN INCLUDED FOR

REFERENCE ONLY

AutoCAD SHX Text K-4330

AutoCAD SHX Text

KINGSTON

AutoCAD SHX Text

C_TOILETS

AutoCAD SHX Text

VITREOUS CHINA

AutoCAD SHX Text K-4330

AutoCAD SHX Text

KINGSTON

AutoCAD SHX Text

C_TOILETS

AutoCAD SHX Text

VITREOUS CHINA

AutoCAD SHX Text

FE

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

MULTICOREVIEWLINK:M501,X002 - STEAM PIPING IN MECH. RM. #B018C

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X002 - STEAM PIPING IN MECH. RM. #B018C

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X002 - STEAM PIPING IN MECH. RM. #B018C

MULTICORELINK:21FED0500M501WD-M501

AutoCAD SHX Text

FE

AutoCAD SHX Text T

FIRE

EQUIP

UP

STAIR 3

EX. H-1

MOD

(2)150CFM

EXISTING OA

DAMPER

1"

1 1/2"

3/4" 3/4" 1 1/2"

1 1/2"

2" 1 1/4"

1 1/2"

2"HWR/S

1-1/2"

3"

HW

R/ S

3"HWR/S

1 1/2"

1 1/2" 1"

AHU

2"HWS&R

1"

1"

3/4"

3/4"1"

1" H

W S/

R-

DN

TO

T

UN

NE

L

3/4"

EX. STEAM COIL

2" JACKETED AND

INSULATED RIGID PIPE

SNOW MELT

SYSTEM

CONTROL

PANEL

M

1-P 3

1-AS 1 1-ET 1

2" LPS

1-SWHX

2" LPC

1-P 2

3/4"

S-15R-15

R-44

S-43 R-43 S-42

R-42 R-41

R-37

S-37

S-36

R-36

S-35

R-39

R-40

S-41

S-40

R-35

S-34

S-29

S-31 R-30R-31

R-34

3/4"

1"LPS

X=9'-3"

4"

LP

S X=

8'- 7"

PI

TC

H

1"

111x64

PLENUM

108x60 X=24"

84/64 PLENUM

X=12"

14" X=5'-2"

14" @ X=7'-7"

20x12 RELIEF X=18'-4"

36x30 PLENUM

39x72

OUTSIDE

INSULATION

14"-UP TO SECOND

FLOOR ROOF

88x74 OPEN 34x68 LOUVER X=12"

20x12

36x16 EXHAUST LOUVER X=5'-1"

36/24 EXHAUST LOUVER

EXISTING RELIEF DAMPER

EXH. FAN F-3

EXHAUST DAMPER CD-4

S-30

38x68 INTAKE LOUVER

36x66 LOUVER

12" ABOVE BOTTOM

1-1/4 HPS-DN

CONTINUED ON FIRST

FLOOR TO HEATED SLAB

PUMP(S)

DP SENSOR

3/4" PRESSURE

REDUCING STATION

W/ BYPASS

ABANDONED

DUCT SERVED

ETO STERILIZERS

C

EX. FC

EX. FC

M

2"LPS

1"LPS/C-UP TO

PHARMACY

2"LPC-DN

1"MPC

1"LPC

3/4" HWS/R

3/4" HWS/R

1" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

1" HWS/R

3/4" HWS/R

UP TO CAB HTR

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R UP

TO (2) CONVECTORS

1- 1/2

"L

PS

-D N

1"

LP

C-

DN

1"LPS/C-UP

1"

4"

3"

21x25 OUTSIDE

INSULATION

X=9'-2"

1" LPS

X=7'-10"

3/4"LPC

1"LPS

3/4 "L

PC

3/4"LPC-UP

3/4" MPC-DN

TO TUNNEL

(FRPS)

UP TO

CONVECTOR

UP TO

CONVECTOR

UP TO

CONVECTOR

UP TO

CONVECTOR

UP TO

CONVECTOR

3/4"LPS/C

EX. HUMID.

3/4"

ABANDONED

CONVECTOR

ABANDONED

CONVECTOR

CAP

REMOVE A

SECTION OF

LPS AND CAP

AT DRIP LEG.

B291

B295A

B291B

231B291C

B231A

B231C

B231D

B231

B230B299C-1

B227

B228

B228C

228A

BASEMENT DEMOLITION PLAN - EAST

MD103

DWG. 05 OF 20

KEYPLAN

NO SCALE

N

N

2'0" 1' 4' 6'

J.G.D. K.K.S.

1. SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT MAY

EITHER BE STARTING CONSTRUCTION SOON, UNDER CONSTRUCTION

NOW OR FINISHING UP CONSTRUCTION. SOME OF THESE PROJECTS

MAY OVERLAP EACH OTHER. COORDINATE WITH OWNER AND ANY

APPLICABLE CONTRACTORS OF PROJECTS ON SEQUENCE OR

PHASING OF OVERLAPPING PROJECTS TO ENSURE ACCURACY AND

COORDINATED DRAWINGS. NOTIFY OWNER/ARCHITECT OF ANY

DISCREPANICES WITHIN PROJECTS.

GENERAL NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MD103

F3 BASEMENT FLOOR DEMOLITION - EAST

1/4" = 1'-0"

AutoCAD SHX Text

FE

http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com http://www.ketiv.com

FD FD FD

DWV

ELEC

CABINET

FD

DN

UP

SERVICE

ELEVATOR PASSENGER

ELEVATOR

PASSENGER

ELEVATOR

BASEMENT ROOF

FD

STAIR 2

EF-2

4" HWS/R-UP/DN

1"

3/4" HWS

2" HWS

2" HWR

3/4" HWS

2" HWS

2" HWR

3" HWS

3" HWR

3" HWR

3" HWS

3" HWR

1 1/4" HWS

1 1/4" HWR

1" HWR1" HWS

3/4" HWS

3/4" HWR3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWS

1 1/4" HWR

1" HWS

1" HWR

1 1/4" HWS

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

1 1/4" HWS

1 1/4" HWR

3/4" HWR

3" HWS

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWS

3/4" HWR 3/4" HWS

3/4" HWR

1 1/2" HWS

1 1/2" HWR

HUMIDIFIER

1-SH-5

SERVED

BY AHU-5

- 1" HWR

1" HWS

3/4" HWR

3" HWS

3" HWR

3/4" HWS3/4" HWR

1" HWR

1" HWS

3/4" HWS/R

3/4" HWR

3/4" HWS

1" HWS

1" HWS

1" HWR

3/4" HWR

3/4" HWS

4" HWR

3/4" HWS

3/4" HWR

3/4" HWR

3/4" HWS

3/4" HWR

3/4" LPC

3/4" LPS

2" LPS RISER

(S-10) UP

2" LPS RISER

(S-10) DN

2" LPS

2" LPS RISER

(R-10) UP & DN

3/4" HWR

3/4" HWS

1"

HWS1"

HWR

3/4" HWS

3/4" HWR

1" HWS

1" HWR

3/4" HWS

3/4" HWR

2" HWR

2" HWS

3/4" HWS

3/4"

HWR

3/4" HWR

3/4" HWS

3/4" HWS

1 1/2" HWS

1 1/2" HWR

3/4" HWS

3/4" HWS

1 1/2" HWS

1 1/2" HWR

3/4" HWR

3/4" HWS

1 1/2"

HWR

1 1/2" HWS

1" HWS

1" HWR

3/4" HWR3/4" HWS

3/4" HWS

3/4" HWR

3/4" HWS

1" HWS

1" HWR

3/4" HWR

3/4" HWR

3/4" HWS

3/4" HWS3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR 3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWS

3/4" HWR

3" HWS

3" HWR

3" HWS

3" HWR

1" HWS

1" HWR

3/4" HWS

3/4" HWR

M T

TT

T

T T

TM

T

T

M T

T T

T

T

T

T

T

T

3"LPC-UP/DN

4"HPS-UP/DN

EXISTING

VFD RACK

4"

1"

4" 1"

3/4"2"

2" HWS

3/4" LPC

2" HWS

2" HWR

3" HWS

3" HWR

4" HWS

4" HWR

3/4" HWR

3/4" HWS

4" HWS 4" HWR

3/4" LPC

3/4" LPS

1-1/2"LPS

1-1/4" LPC

ET-1

4" HWS

4" HWR

2" HPC-UP/DN

HWP-24/25

HX-22/23

2" HWR

AHU-4

AH-15

AH-5

RF-5

T

1"

1"

6" MPS-DN

EXISTING ROOM

EXHAUST FAN

EX. 1-1/4" AND 4" PRV

3" HWS/R-DN

1" HWS/R-DN

3/4" HWR

3/4" HWS

3" HWR3" HWS

HUMIDIFIER

6" 3"

1" LPS 3"

3/4" LPC

3"

8" X=8'-6"

8"

4"

3" LPC-UP/DN

3" LPC-DN

TRAP

3" LPS-UP

1" LPS

3/4" LPS

HUMIDIFIER

3/ 4"

L

PC

3" 6"

1-1/2"GS/R-DN

1-1/2"GS/R

3/4"

3/4"

3/4"

3/4"

3/4"

3/4" EX. FTREX. FTR

EX. FTR

EX. FTR

3"LPC-DN

1" X=0'-6"

1" X=0'-10" 3" X=0'-6"

X=6'-0"

DRAIN AND FILL

GLYCOL HEAT

SYSTEM

1" LPC-UP

X=6'-4"

REMOVE LPS - 4" PRV, GATE

VALVE AND 4x6 RELIEF

VALVE. REFER TO DETAIL

C4/M501. REMOVE

PNEUMATIC PIPE TO AIR

LOADER.

TCP TCP

2171A

21152116 2114

2299B 2112A

2129K 2129L 2113

2112 2111 2109 2107

2111A

2299H

2110C 2110A

2110B

2214 C2-1

2215 2217

2215A

SECOND FLOOR DEMOLITION PLAN

MD104

DWG. 06 OF 20

KEYPLAN

NO SCALE

N

2'0" 1' 4' 6'

N

J.G.D. K.K.S.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MD104

F3 SECOND FLOOR DEMOLITION PLAN

1/4" = 1'-0"

GENERAL NOTES

1. SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT MAY

EITHER BE STARTING CONSTRUCTION SOON, UNDER CONSTRUCTION

NOW OR FINISHING UP CONSTRUCTION. SOME OF THESE PROJECTS

MAY OVERLAP EACH OTHER. COORDINATE WITH OWNER AND ANY

APPLICABLE CONTRACTORS OF PROJECTS ON SEQUENCE OR

PHASING OF OVERLAPPING PROJECTS TO ENSURE ACCURACY AND

COORDINATED DRAWINGS. NOTIFY OWNER/ARCHITECT OF ANY

DISCREPANICES WITHIN PROJECTS.

AutoCAD SHX Text S8

AutoCAD SHX Text R9

AutoCAD SHX Text S9

AutoCAD SHX Text S10

AutoCAD SHX Text R20

AutoCAD SHX Text S19

AutoCAD SHX Text R19

AutoCAD SHX Text S18

AutoCAD SHX Text R18

AutoCAD SHX Text S18

AutoCAD SHX Text S17

AutoCAD SHX Text S16

AutoCAD SHX Text R17

AutoCAD SHX Text R16

AutoCAD SHX Text S17

AutoCAD SHX Text R17

AutoCAD SHX Text S16

AutoCAD SHX Text R18

AutoCAD SHX Text R11

AutoCAD SHX Text R12

AutoCAD SHX Text S12

AutoCAD SHX Text S15

AutoCAD SHX Text R16

AutoCAD SHX Text S14

AutoCAD SHX Text R15

AutoCAD SHX Text S13

AutoCAD SHX Text R12

AutoCAD SHX Text S11

AutoCAD SHX Text R11

AutoCAD SHX Text S-10

AutoCAD SHX Text R-10

AutoCAD SHX Text S-10

MULTICOREVIEWLINK:M501,X007 - BASEMENT STEAM ISOMETRIC

MULTICOREVIEWLINK:M501,X007 - BASEMENT STEAM ISOMETRIC

EXISTING RELIEF HOOD

12x x8

12x6

EXISTING

HUMDIFIER

AD

AD

AD

18X12 ACCESS DOOR MOUNTED

ON SIDE OF DUCT

1 1/2"

3/4"

3/4"

3/4"

1"

1 1/2"

1"

2"

1 1/2" 1 1/2"3/4"

3/4"

2"

3" HPS UP

2" LPC UP

1" HPC UP

1"LPS-UP/DN

1"LPC-UP/DN

1"

2" HPC

2" HPC

2" HPC DN

4" HWS/R UP/DN

1" LPS/C-UP/DN

1" LPS

TTT T

TT

T

T

T

T

T

T

T

M

T

T

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

3/4" LPS

3/4" HWS

2" HWS2" HWR3/4"

HWS

3/4" HWR

3/4" HWS

3/4" HWS

3/4" HWR

2" HWS2" HWR

2" HWR

2" HWS

3/4" HWR3/4" HWS

3/4" HWS3/4" HWR

2" HWS2" HWR

2" HWR2" HWS

3/4" HWS

3/4" HWR

2" HWR2" HWS 3/4" HWS

3/4" HWS2" HWR

2" HWS

3/4" HWR

3/4" HWS

3/4" HWS

3/4" HWR

1" HWR

3/4"

HWR

3/4"

HWS

2 1/2" HWR2 1/2" HWS

2" HWS

2" HWR2" HWR

2" HWS

3/4" HWS

3/4" HWS3/4" HWR3/4" HWR

3/4" HWS

3/4" HWS3/4" HWR

1 1/4" HWR

1 1/4" HWS 1 1/4" HWS

1 1/2" HWR

1 1/2" HWS1 1/2" HWR

3/4" HWR3/4" HWS1 1/4" HWS1 1/4" HWR

1 1/4"

HWR

3/4"

HWS

3/4" HWR3/4" HWS

1 1/2" HWS

2" HWS2" HWR

2-1/2" HWS

2-1/2" HWR

2-1/2" HWS

2-1/2" HWR

2" HWS2" HWR

3/4" HWS3/4" HWS

3/4" HWR

3/4" HWS

2" HWR

2" HWS

2 1/2" HWR

2 1/2" HWS

TTT

T T T

T

T

T

T

T

T

T

T

T

TT

T

T T

T

T

T

T

T

1 1/4"

HWS1 1/4"

HWR

3/4"

HWR

3/4"

HWS

3/4"

HWS3/4"

HWR

1"

HWS1"

HWR

1"

HWS1"

HWR

3/4"

HWS

3/4"

HWR

3/4"

HWR3/4"

HWS

1"

HWR

1"

HWS

3/4"

HWR3/4"

HWS

1"

HWS1"

HWR

3/4"

HWR3/4"

HWS

3/4"

HWS

3/4"

HWR

3/4"

HWR

3/4"

HWR3/4"

HWS

3/4"

HWS

3/4"

HWR

2" HWS

2" HWR

3/4" HWS

3/4" HWR

2" HWR2" HWS

3/4" HWS3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR3/4" HWS

3/4" HWR

2" HWS

2" HWR

2" HWS2" HWR

3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

2" HWS

2" HWR

3/4" HWS

3/4" HWR

2" HWS2" HWR

2" HWS2" HWR

1" HWS

1" HWR

3/4" HWS

3/4" HWR

2" HWS

2" HWR

2" HWS

2" HWR

3/4" HWS

3/4" HWR2" HWS2" HWR

3/4" HWS

3/4" HWR2" HWS

2" HWR

3/4" HWS

3/4" HWR

1 1/2" HWR

1 1/2" HWS

3/4" HWR3/4" HWS

1 1/2" HWS

1 1/2" HWR

3/4" HWR

3/4" HWS

3/4" HWS

1 1/2" HWR

1 1/2" HWS

3/4" HWR

3/4" HWS

3/4" HWS

3/4" HWR

1 1/4" HWS

1 1/4" HWR3/4" HWS

3/4" HWR

3/4" HWS

3/4" HWR

1" HWS

1" HWR

3/4" HWR

3/4" HWS

3/4" HWS3/4" HWR

3/4" HWS

3/4" HWR

3/4" HWR

3/4" HWS

1" HWS

1" HWR

3/4" HWS3/4" HWR

3/4" HWS

3/4"

HWS

T

T

T 43 "

T

T

T

43 "

T

S

3/4"

4" HWS/R-UP

2 1/2" HWS/R DN

3" HPS-UP

2" LPC UP

1" HPC UP

2"

EXISTING

CONVECTOR

3/4"

3/4"

T

T

T

T

T T

X=7'-10"

2-1/2" HWS/R UP

4" HWS/R-UP/DN

4" HWS/R-UP/DN

2"LPC

3"HPS

3"HPS

1"HPC

2"LPC

1"HPC

4"HPS-DN

3"LPC-DN

EX. HUMID.

3/4"

LPC

EX. CONVECTOR

3/4"HWS/R

-UP/DN

(EXPOSED)

3/4" TO UNIT

W/ VALVES

3/4"HWS/R

-UP/DN

(EXPOSED)

3/4" TO UNIT

W/ VALVES

3/4"HWS/R

-UP/DN

(EXPOSED)

3/4" TO UNIT

W/ VALVES

2"LPC

3"HPS

1"HPC

3"HPS

2"LPC

1"HPC

3"HPS

2"LPC

1"HPC

1"

1"

1 1/2"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"3/4"

3/4"

3/4"

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. RAD. HEAT PANEL

EX. RAD. HEAT PANEL

EX. RAD. HEAT PANELEX. RAD. HEAT PANEL

EX. RAD. HEAT PANEL

EX. RAD. HEAT PANEL

1"

1 1/4"

3/4"3/4" 3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOR

EX. CONVECTOREX. CONVECTOREX. CONVECTOR

EX. RAD. HEAT PANEL

EX. RAD. HEAT PANELEX. RAD. HEAT PANEL

3/4"

3/4"

3/4"

3/4"

3/4"

EX. CONVECTOR

EX. RAD. HEAT PANEL

EX. RAD. HEAT PANEL

EX. CONVECTOR

3/4"

EX. CONVECTOR

3/4"

3/4"

3/4"

3/4"

3/4"

3/4"

1"

EX. CONVECTOR

EX. CONVECTOREX. CONVECTOREX. CONVECTOR

EX. RAD. HEAT PANEL

3/4" 3/4"

3/4"

3/4"3/4"

EX. CONVECTOR EX. CONVECTOR EX. CONVECTOR EX. CONVECTOR

ROOM

PRESSURE

MONITOR

(TYP.)

3" LPS-UP/DN

(ACTIVE RISER)

1"LPC

REMOVE 3/4" HPS DRIP TRAP AND PIPINGREMOVE 3/4" HPS DRIP TRAP

AND PIPING. CAP AT MAIN.

CAP

CAP

2ND FLOOR ROOF

2ND FLOOR ROOF

FIRST FLOOR ROOF

FIRST FLOOR ROOF

FIRST FLOOR ROOF

FIRST FLOOR ROOF

BASEMENT ROOF

BASEMENT ROOF

BASEMENT ROOF

BASEMENT ROOF

MECH

SHAFT

DUMB

WAITER

DN

STAIR 5

DN

UP

STAIR 2

DN

STAIR 4

PASSENGER

ELEVATOR

PASSENGER

ELEVATOR

SERVICE

ELEVATOR

UPUP

DN

UP

STAIR 1 STAIR 3

UP

DN

LDRY

CHUT

MECH

SHAFT

MECH

SHAFT

3RD FLOOR ROOF

FIRE

EQUIP

FIRE

EQUIP

MECH

SHAFT

PASSENGER

ELEVATOR

K-4330KINGSTONC_TOILETSVITREOUS CHINA K-4330KINGSTONC_TOILETSVITREOUS CHINA

K-4330KINGSTONC_TOILETSVITREOUS CHINA

MECH

SHAFT

PIPE

SHAFT

FOURTH FLOOR DEMOLITION PLAN

MD105J.G.D. K.K.S.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MD105

F1 FOURTH FLOOR DEMOLITION PLAN

1/8" = 1'-0"

KEYPLAN

NO SCALE

N

DWG. 07 OF 20

2-HOUR

RATED

SHAFT

2-HOUR

RATED

SHAFT

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text S-52

AutoCAD SHX Text R-52

AutoCAD SHX Text S-51

AutoCAD SHX Text S-53

AutoCAD SHX Text R-53

AutoCAD SHX Text S-54

AutoCAD SHX Text S-5

AutoCAD SHX Text R-5

AutoCAD SHX Text R-51

AutoCAD SHX Text S-50

AutoCAD SHX Text R-54

AutoCAD SHX Text S-55

AutoCAD SHX Text R-50

AutoCAD SHX Text S-49

AutoCAD SHX Text R-55

AutoCAD SHX Text R-56

AutoCAD SHX Text S-56

AutoCAD SHX Text R-57

AutoCAD SHX Text R-49

AutoCAD SHX Text S-48

AutoCAD SHX Text R-58

AutoCAD SHX Text S-57

AutoCAD SHX Text R-1

AutoCAD SHX Text S-2

AutoCAD SHX Text S-58

AutoCAD SHX Text S-1

AutoCAD SHX Text R-2

AutoCAD SHX Text R-3

AutoCAD SHX Text S-3

AutoCAD SHX Text R-4

AutoCAD SHX Text R-5

AutoCAD SHX Text S-4

AutoCAD SHX Text S-6

AutoCAD SHX Text S-5

AutoCAD SHX Text R-6

AutoCAD SHX Text S-7

AutoCAD SHX Text R-7

AutoCAD SHX Text S-10

AutoCAD SHX Text R-10

AutoCAD SHX Text S-9

AutoCAD SHX Text S-10

AutoCAD SHX Text R-9

AutoCAD SHX Text S-8

AutoCAD SHX Text R-10

AutoCAD SHX Text R-11

AutoCAD SHX Text R-12

AutoCAD SHX Text S-11

AutoCAD SHX Text S-12

AutoCAD SHX Text R-48

AutoCAD SHX Text S-47

AutoCAD SHX Text R-47

AutoCAD SHX Text S-46

AutoCAD SHX Text S-6

AutoCAD SHX Text R-8

AutoCAD SHX Text R-46

AutoCAD SHX Text R-44

AutoCAD SHX Text S-44

AutoCAD SHX Text R-44

AutoCAD SHX Text S-44

AutoCAD SHX Text S-43

AutoCAD SHX Text R-43

AutoCAD SHX Text S-42

AutoCAD SHX Text S-39

AutoCAD SHX Text R-37

AutoCAD SHX Text S-37

AutoCAD SHX Text S-36

AutoCAD SHX Text R-36

AutoCAD SHX Text S-35

AutoCAD SHX Text R-39

AutoCAD SHX Text R-40

AutoCAD SHX Text R-35

AutoCAD SHX Text S-34

AutoCAD SHX Text S-40

AutoCAD SHX Text S-41

AutoCAD SHX Text R-30

AutoCAD SHX Text S-31

AutoCAD SHX Text R-29

AutoCAD SHX Text S-29

AutoCAD SHX Text R-28

AutoCAD SHX Text R-27

AutoCAD SHX Text S-30

AutoCAD SHX Text S-28

AutoCAD SHX Text S-27

AutoCAD SHX Text R-26

AutoCAD SHX Text S-26

AutoCAD SHX Text R-25

AutoCAD SHX Text S-24

AutoCAD SHX Text S-25

AutoCAD SHX Text S-23

AutoCAD SHX Text R-24

AutoCAD SHX Text R-23

AutoCAD SHX Text R-22

AutoCAD SHX Text S-22

AutoCAD SHX Text S-18

AutoCAD SHX Text R-18

AutoCAD SHX Text R-19

AutoCAD SHX Text S-18

AutoCAD SHX Text S-19

AutoCAD SHX Text R-20

AutoCAD SHX Text R-18

AutoCAD SHX Text S-16

AutoCAD SHX Text S-17

AutoCAD SHX Text S-20

AutoCAD SHX Text R-42

AutoCAD SHX Text R-41

AutoCAD SHX Text R-34

AutoCAD SHX Text S-32

AutoCAD SHX Text R-32

AutoCAD SHX Text R-31

AutoCAD SHX Text R-16

AutoCAD SHX Text S-17

AutoCAD SHX Text S-32

AutoCAD SHX Text S-13

AutoCAD SHX Text S-14

AutoCAD SHX Text R-15

AutoCAD SHX Text S-15

AutoCAD SHX Text S-13

AutoCAD SHX Text R-13

AutoCAD SHX Text R-14

AutoCAD SHX Text

AutoCAD SHX Text S-3

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

3/4"

2" 3/4"

3/4"

3/4" 3/4"

4" HWS/R DN

TO 2ND/3RD

2"

61 EDR

25 EDR

2" 1"

2" HW

1"

3" HPS-DN

2" LPC-DN

1" HPC-DN

31 EDR8 EDR

EXISTING

PUMPS

EXISTING

ROLAIRTROL

EXISTING

HEAT

EXCHANGERS

(STACKED)

HWS-DN TO

CHILLER

HWR-DN TO

CHILLER

6" CWS/R-UP

6"3"

2-1/2" HWS/R-DN

2 1/2" HWS/R-DN

EXISTING

UNIT HEATER

EXISTING

UNIT HEATER

TO 4TH FLOOR

TO 5TH FLOOR

HX

AHU

HX

3"HPS

6"

PRV

6"LPS

STEAM PIPING IN THIS

AREA VERTICALLY

STACKED ALONG WALL

D D

1-1/4"

1-1/4"

3/4" TRAP (TYP.)

2" X=8"

RELIEF VENT TO OUTSIDE

LPS/LPCR TO

STEAM HUMID.

X= 8'

-7

X= 1'-

X= 6'-

5"

2" X=8"

2" X=4'-4"

VFD

1"

2" X=8"

A

A

REMOVE A SECTION

OF 2" LPC PIPE

REMOVE 2" DRIP TRAP

AND PIPING FOR HX.

SALVAGE TRAP.

REMOVE A SECTION OF HPS

BYPASS PIPE PER DETAIL

C7/M501.

TCP

REMOVE HPS DRIP TRAP

(CONNECTED TO STRAINER).

SALVAGE VALVES TO TRAP.

V

2" VENT TO

OUTSIDEBASEMENT ROOF

3/4"

3/4"

3/4"

53 EDR 70 EDR

3/4"

2 1/2" HW

61EDR

AHU

6" CWS/R-UP

3" HPS-DN

2" LPC-DN

1" HPC-DN

3"HPS

4" HWS/R DN

6"

5" HWS/R DN

EXISTING

PUMP

1 "14

1-1/4"

1-1/4"

PRV

VFD

61EDR

8EDR

HX

HX

EXISTING HEAT

EXCHANGERS

(STACKED)

?? EDR

90 CFM EACH

315CFM

130CFM

60CFM

6"LPS

2"LPC

RELIEF VENT

TO OUTSIDE

STEAM PIPING IN THIS AREA

VERTICALLY STACKED ALONG WALL

1-1/4"

2" X=8"

3/4" TRAP (TYP.)

2-1/2"

TRAP

(TYP.)

2-1/2" X=1'-2"

2-1/2" X=1'-10"

X=90"

X=2'-1"

X=6'-4"

3/4" X=1'-5"LPS/LPCR TO

STEAM HUMID.

REMOVE A SECTION

OF 2" LPC PIPE

A

A

REMOVE A SECTION OF HPS

BYPASS PIPE PER DETAIL

C7/M501.

1"

TCP

REMOVE HPS DRIP TRAP

(CONNECTED TO STRAINER).

SALVAGE VALVES TO TRAP.

V

2" VENT TO

OUTSIDE

2ND FLOOR ROOF

FIRST FLOOR ROOF

4TH FLOOR ROOF

FIRST FLOOR ROOFFIRST FLOOR ROOF

EXTG.

SIXTH FLOOR DEMOLITION PLAN

MD106

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MD106

F1 SIXTH FLOOR DEMOLITION PLAN - WEST

1/4" = 1'-0"

KEYPLAN

NO SCALE

N

MD106

F6 SIXTH FLOOR DEMIOLITION PLAN - EAST

1/4" = 1'-0"

A

REMOVE THE 3/4" LPC CONNECTION FROM THE DRIP TRAPS TO

THE LPC MAIN.

- REMOVE ALL DUCTS, PIPING, AND EQUIPMENT NOTED AND/OR

SHOWN DASHED.

- GENERAL TRADE SHALL PATCH WALL OPENINGS REMAINING AFTER

DEMOLITION TO MATCH ADJACENT SURFACES.

(THIS SHEET ONLY)

PLAN KEYED NOTES

GENERAL NOTES

1. SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT MAY

EITHER BE STARTING CONSTRUCTION SOON, UNDER CONSTRUCTION

NOW OR FINISHING UP CONSTRUCTION. SOME OF THESE PROJECTS

MAY OVERLAP EACH OTHER. COORDINATE WITH OWNER AND ANY

APPLICABLE CONTRACTORS OF PROJECTS ON SEQUENCE OR

PHASING OF OVERLAPPING PROJECTS TO ENSURE ACCURACY AND

COORDINATED DRAWINGS. NOTIFY OWNER/ARCHITECT OF ANY

DISCREPANICES WITHIN PROJECTS.

J.G.D. K.K.S.

DWG. 08 OF 20

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

MULTICORELINK:21FED0500M501WD-M501

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

AutoCAD SHX Text T

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

MULTICORELINK:21FED0500M501WD-M501

MULTICOREVIEWLINK:M501,X008 - SIXTH FLOOR STEAM ISOMETRIC

2"LPC

2"

2"

3 1/2"

3 12"

6"

2"

6"

2 1/2"

2"

4" 6"

2 1/2"

5" 2"

6"

3" 6" 10"

4"CPD

1"

4"CPD

X=9'-4"

6" LPS

8" HPS HEADER

4" X=6'-8"

4"

2" MPS UP

3"

8" MPS HEADER

4"

4" HPC

3/4" HPC

2" HPC

2" HPC

X=6'-4"

2" HPC

2" HPC

2"

CPD

1" 20 PSI STEAM

SUPPLY AND

CONDENSATE

RETURN

1"

2"

CPDCPD

CP

D

V

MPS (1-1/4") PRV 110# - 60#

6"

3/4"

TO BOILER PLANT

TO KITCHEN

PRV

6" MPS-UP

2" MPC-UP

X=9'-3"

X=8'-1"X=7'-8" X=7'-8"

X=6'-10"

MPS (2-1/2" AND 2") PRV 110# - 50#

LPS (2-1/2" AND 2") PRV 50# - 10#

4" LPS

HX-3

HX-4

3" TO DOM. WH

6"

4"

2"

3"

3"

4"

4"

3"

2"

2"

3/4"

X=1'-9"

2" X=9'-8"

X=8'-2"

3"LPC-UP

1-1/2"LPS-UP

1"LPC-UP

PITCH

PI

TC

H X=

3' -7

2" X=

2' -0

2" X=

1' -1

0"

4"

MPS/C TO AIR

CURTAIN

2"MPS

6" LPS

HEADER

4"CPD

6"HPS-TO BOILER PLANT

3"HPS-TO BOILER PLANT

6"MPS

1-1/2"LPC-UP

2"

2"

2- 1/2" 2-1/2"

4"

3/4"MPC

3/4"HPC

6"

6" V-UP

4" V

3"

1 "12

V

X=1'-3"

NEW 2" GATE VALVE IN

EXISTING HPS PIPING

NEW 2" GLOBE VALVE

AND BYPASS PIPE

1"

NEW 2" GLOBE VALVE

AND BYPASS PIPE

2-1/2" CONN. TO

VENT. X=7'-8"

3"

4" X=15"

1-1/2"LPC X=1'-3"

3"

2"

1-1/2"

3"

3"V X=7'-8"

10"

TCP

3/4"

NEW COND TANK/PUMP

PACKAGE SET IN PIT.3

REMOVE AND REPLACE

RAILING AS REQUIRED FOR

TANK RIGGING.

7 3A

7 2A

1"

1" HPC THRU TUNNEL TO

NEW DRIPS - SEE MS101

(220'-0")

T-6 T-7

T-8

T-9T-5

NEW CONDENSATE

TANK/PUMP SET ON

CONCRETE PAD

E3 M501

1" LPS DRIP TRAP TO

HEADER. NEW 3" DIRT LEG

PI

TC

H

1"D X=10"

1-1/4"V

1-1/4"V

1"D X=12"

FD

FD FD

FD

STAIR 2

UP

UP

ELEV

S004

S001

S002

SUB-BASEMENT NEW WORK PLAN

MP101

DWG. 09 OF 20

4'0" 2' 8' 12'

N

KEYPLAN

NO SCALE

N J.G.D. K.K.S.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MP101

F3 SUB-BASEMENT NEW WORK PLAN

1/4" = 1'-0"

(THIS SHEET ONLY)

PLAN KEYED NOTES

NEW CONNECTION TO (4) HPC 3/4" DRIP PIPES. EXTEND TO LPS

HEADER WITH CHECK VALVE IN EACH. SEE DETAIL M3/H501.

NEW CONNECTION TO EXISTING PIPING.

NEW LPS PRV-3B. EXTEND 4x2 REDUCER TO PRV. 2x4 INCREASER TO NEW GATE VALVE AND 4x10 INCREASER AT CONNECTION.

NEW MPS PRV-2B. EXTEND 4x2 REDUCER TO PRV. 2x4 INCREASER TO NEW GATE VALVE AND 4x10 INCREASER AT CONNECTION.

PROVIDE 1" DRAIN VALVE AND PIPE TO FLOOR DRAIN.

ROTATE EXISTING STRAINER 90° TO BE PARALLEL TO FLOOR. REPIPE

DRAIN TO ELBOW DOWN.

REPLACE STEAM PRV WITH NEW - SEE SCHEDULE. RECONNECT

STEAM PILOT.

CONNECT NEW DDC POINTS TO TCP.

REINSULATE 12" STEAM HEADER. PROVIDE PVC BAGGING.

INSTALL OWNER FURNISHED 6" HPS VALVE TO REPLACE EXISTING.

GENERAL NOTES

1. SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT MAY

EITHER BE STARTING CONSTRUCTION SOON, UNDER CONSTRUCTION

NOW OR FINISHING UP CONSTRUCTION. SOME OF THESE PROJECTS

MAY OVERLAP EACH OTHER. COORDINATE WITH OWNER AND ANY

APPLICABLE CONTRACTORS OF PROJECTS ON SEQUENCE OR

PHASING OF OVERLAPPING PROJECTS TO ENSURE ACCURACY AND

COORDINATED DRAWINGS. NOTIFY OWNER/ARCHITECT OF ANY

DISCREPANICES WITHIN PROJECTS.

AutoCAD SHX Text

ERV

AutoCAD SHX Text

AutoCAD SHX Text

AHU

AutoCAD SHX Text

MULTICOREVIEWLINK:M501,X003 - Det0002 STEAM MAIN DRIP

MULTICORELINK:21FED0500M501WD-M501

VHAIROKleinD Pencil

VHAIROKleinD Typewritten Text Replace valve

VHAIROKleinD Typewritten Text Replace 6" MPS valve as marked

VHAIROKleinD Text Box Cast iron is not acceptable per VA design alert 151.

Any bolt that is removed on steam and condensate flanges will be replaced with Grade A193 bolt, A194 Nut, and F436 Washer or equivalent grade.

FLT

AHU

AHU-6

TCP

AHU-6

-1225 SUP

-270 O.A. (22%)

-955 RET

TUNNEL ACCESS

(CONFINED SPACE)

2"3/4"

2" HWS/R UP

3" HWS/R

3/4"

1" DOWN THRU

ABANDONED

CONVECTOR

3/4"

3/4"

EXISTING 1-1/4" PRV

50# TO 10# W/ BYPASS

2 1/2" MPS-DN

S-1

S-2 R-1

R-2

R-3

S-3

R-4

X=7'-0"

2" LPCR-DN

EXISTING AHU-016

FRPS

S-4

R-5

3/4" 1"

EXISTING

CONVECTOR

T

FCU-001

1"

EXISTING

CONVECTOR

4"

1"

1"

EX. STEAM COIL

EX. HUMIDIFIER

LPS

LPC

LPS

LPC

1"

EX. FTR

1-1/4"LPCR-DN

1 1/2" LPS

3/4"LPCR-DN

1"LPS

T

1-1/2"

1-1/2" 3/4"

3/4" DRIP TRAP

X=10'-0"

X=8'-5"

3/4"

X=7'-9" FRPS(TYP.)

FRPS

1" LPS-UP

1" LPCR-UP

3" LPS

HEADER

2"

TCP

3" VENT TO

OUTSIDE

V

47A

D9

M501

EXISTING

AHU

EXISTING

RETURN

FAN

2" HPS DN

TO TUNNEL

EXISTING PRV

125# TO 10#

EXISTING SNOW MELT

SYSTEM CONTROL

PANEL

2"

EX. AIR SEP

EXPANSION TANK

TO EXISTING SNOW MELT SYSTEM

1 1/4"

HX-21 P-1

P-2

R-53

S-54 R-5

S-5

S-50

R-51

S-51

CONV. AT FLOOR LINE

S-53

S-52 R-52

1-1/2"LPCR-DN

EXISTING

STEAM COIL

3"LPS

EXISTING

HUMIDIFIER

EX. FTR

EX. FTR

3/4" HWS/R

3/4" HWS/R

3/4" HWS/R

3/4"

BASEMENT NEW WORK PLAN - WEST

MP102

KEYPLAN

NO SCALE

N

N

4'0" 2' 8' 12'

(THIS SHEET ONLY)

PLAN KEYED NOTES

NEW PRV-7B, VALVES AND PIPING. SEE DETAIL C2/M501.

NEW CONNECTION TO EXISTING PIPING.

CONNECT NEW DDC POINTS TO EXISTING TCP.

REPLACE STEAM PRV WITH NEW - SEE SCHEDULE. RECONNECT

STEAM PILOT.

NEW 2x3 RELIEF VALVE CONNECTION TO STEAM HEADER.

REPLACE STEAM PRV-9 WITH NEW. SEE SCHEDULE. RECONNECT

STEAM PILOT. REMOVE AIR HEADER AND PIPE TO PRV.

GENERAL NOTES

1. SOME AREAS SURROUNDING THE LIMITS OF THIS CONTRACT MAY

EITHER BE STARTING CONSTRUCTION SOON, UNDER CONSTRUCTION

NOW OR FINISHING UP CONSTRUCTION. SOME OF THESE PROJECTS

MAY OVERLAP EACH OTHER. COORDINATE WITH OWNER AND ANY

APPLICABLE CONTRACTORS OF PROJECTS ON SEQUENCE OR

PHASING OF OVERLAPPING PROJECTS TO ENSURE ACCURACY AND

COORDINATED DRAWINGS. NOTIFY OWNER/ARCHITECT OF ANY

DISCREPANICES WITHIN PROJECTS.

SEE GENERAL NOTE 1 FOR

THIS AREA. VA PROJECT

585-18-114 (UPGRADE

ENTRANCES).

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

PhaseARCHITECT/ENGINEER OF RECORD STAMP 585-21-113

MARCH 04, 2022

Revisions: Date:

REPLACE CONDENSATE LINES AND PUMPS

OSCAR G. JOHNSON VAMC

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com FULLY SPRINKLERED

BID DOCUMENT SET

Comm. Number: 21FED05.00

50% OWNER REVIEW 01/27/2022

VA FORM 08 - 6231

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

95% OWNER REVIEW 02/14/2022

BID DOCUMENT SET 03/04/2022

MP102

F3 BASEMENT NEW WORK PLAN - WEST

1/4" = 1'-0"

J.G.D. K.K.S.

DWG. 10 OF 20

MP102

C5 PARTIAL BASEMENT FLOOR PLAN - NEW WORK (NORTH)

1/4" = 1'-0" 4'0" 2' 8' 12'

N

AutoCAD SHX Text K-4330

AutoCAD SHX Text

KINGSTON

AutoCAD SHX Text

C_TOILETS

AutoCAD SHX Text

VITREOUS CHINA

AutoCAD SHX Text K-4330

AutoCAD SHX Text

KINGSTON

AutoCAD SHX Text

C_TOILETS

AutoCAD SHX Text

VITREOUS CHINA

AutoCAD SHX Text

FE

AutoCAD SHX Text T

AutoCAD SHX Text T