3 Copy of Asbestos Six Month Assessment.pdf

PDF 299 KB Posted

Attached to
F101--Airborne Asbestos Mold Monitoring (550)
Solicitation number
36C25224Q0468
Issued by

About this file

This document is a government file related to an asbestos and mold assessment and monitoring contract opportunity. The key details are:

The federal contract opportunity is for Airborne Asbestos Mold Monitoring (Solicitation Number: 36C25224Q0468) issued by the Department of Veterans Affairs (VA) Veterans Health Administration, Veterans Integrated Service Network 12. The required services include asbestos and mold air testing and monitoring. The document provides detailed information on the locations, materials, and conditions of asbestos-containing materials across multiple VA buildings. This information appears to be used to support the requirements of the solicitation. No additional details on the contract's pricing, set-asides, award dates, or incumbents are provided in the document.

View the file

Other files

File Type Posted
36C25224Q0468 0003.docx DOCX document
4 Station 550 Bldg Inventory - Asbestos Surveys.pdf PDF
2 Danville VAMC - Asbestos Reinspection Report_Redacted.pdf PDF
36C25224Q0468 0002.docx DOCX document
36C25224Q0468 0001.docx DOCX document
P07 Vermilion IL WD 2015 5021 Rev 22 dated 05 10 2024.pdf PDF
36C25224Q0468.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contact Vibration Air Erosion

Floor Mastic Under Tile Black Basement and 1st

350 SF

NO Good 1

Low High Low

1st floor abated save for east foyer.

Basement significant damage 5 Floor Tile 9”x9” (Does Not Include Mastic) Green

1st

450 SF

NO

Significantly

Damaged 1

High High Low

1st floor abated save for east foyer.

Basement significant damage

Floor Mastic Under Black Tile 1st

450 SF NO Good 1

Low High Low

Abated save for east foyer

10 Piping Insulation Magnesia-Type (Heating System) basement

200 SF

NO Good 1

Low High High

Damaged, partially remediated

11 Piping Insulation Aircell -Type (Domestic Water) basement

250 SF

NO Good 1

Low High High

Damaged, partially remediated

12 Piping Fitting Insulation On Magnesia-Type (Heating System) basement

10 EA

NO Good 1

Low High High

Damaged, partially remediated

17 Piping Insulation Magnesia-Type (Heating System) firedoor basement

1 EA

Yes Damaged 4

Low High High

Repaired

Exterior window glazing basement and 1st

2000 LF

NO Good 1

Low High Low

Some damage on a few windows exterior paint white.

10000 SF

Yes Damaged 4

Low High High

Painted over

Contact Vibration Air Erosion

2 Floor Mastic Under Tile Black second floor 2600 SF

NO Good 1

Low High Low

ABATED

4 Floor Mastic Under Tile Black fifth floor 520 SF

NO Good 1

Low High Low

GOOD

Floor Tile 9"X9" (Does Not Include Mastic) Tan, Brown & Green Basement through fifth

19000 SF NO Good 1

High High High

Basement damaged,1-3 abated.

Some 9x9 remains in path lab. 9x9 remains in some stair wells, all in good condition

16 Floor Mastic Under Tile Black 1st through 5th 19000 SF

NO Good 1

Low High Low

1-3 abated

17 Floor Tile 12"X12" (Does Not Include Mastic) Light Tan 2nd

600 SF

NO

ABATED

29 Mastic On Sink Black 1st through 5th 7 EA NO Good 1 Low High Low 3 Several damaged

32 Piping Insulation Magnesia-Type (Heating System) crawlspace and attic

3000 LF

Yes Damaged 4

Low High High

Attic 90% abated, remainder damaged. crawl space unchanged, significantly damaged

33 Piping Insulation Aircell-Type (Domestic Waterline) crawlspace

350 LF

Yes Damaged 4

Low High High

Unchanged, damaged

34 Tank Insulation White 3rd floor 300 SF

Yes Damaged 4

Low High High

ABATED

36 Debris Soil Debris (MAG) crawlspace 12500 SF

Yes Damaged 4

Low High High

Unchanged; damaged

37 Thermal Taping Compound Tape attic 7000 SF

Yes Damaged 4

Low High High

90% abated, remainder damaged

38 Pipe Support Insulation On Fiberglass Insulated Lines attic

350 EA

Yes Damaged 4

Low High High

90% abated; remainder damaged

Pipe Fitting Insulation On Fiberglass Run (Chilled Waterline) crawlspace and attic

500 EA Yes Damaged 4

Low High High

Attic 90% abated, remainder damaged. Crawlspaace unchanged, significantly damaged

42 Caulking/Putties Fire Stop, On Fan Coil Unit exterior windows

400 LF

NO Good 1

Low High High

Several damaged

Material Description Approximate Quanity FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

RANKING

POTENTIAL

HAZARD

RANKING

August 2016 Inspection

Disturbance Potential

Building 22

Building 58

Homgenous Area Number August 2016 Inspection

Homgenous Area Number

HAZARD

RANKINGMaterial Description Approximate

Quanity

CURRENT

CLASSIFICATI

ON

FRIABLE

43 Floor Mastic Under Tile Black 5th floor 500 SF

NO Good 1

Low High Low

Good

45 Floor Mastic Under Tile Black 2nd floor 600 SF

NO

ABATED

Pipe Fitting Insulation On Blk Styrofoam Lines (Domestic/Chilled Lines) basement 40 EA Yes Damaged 4

Low High High

Damaged

Floor Tile 12"X12" (Does Not Include Mastic) Tan With Brown & Yellow Streaks basement 500 SF NO Good 1

High High High

Damaged

Elevator Brake Shoes attic

10 SF NO Good 1

High High High

Good

Contact Vibration Air Erosion

Floor Tile 12"X12" (Does Not Include Mastic) White With Grey Streaks 18 SF NO Good 1

High High High

Good Condition

4 Floor Mastic Under Tile Black 18 SF

NO Good 1

Low High Low

Good Condition

Floor Tile 12"X12" (Does Not Include Mastic) White With Brown Streaks 120 SF NO Good 1

High High High

Good Condition

6 Floor Mastic Under Tile Black 120 SF

NO Good 1

Low High Low

Good Condition

7 Vinyl Sheet Flooring (Does Not Include Mastic) Brown

300 SF

Yes Damaged 4

Low High High

Good Condition

16 Piping Insulation Aircell-Type (Heating System) 140 LF

NO Good 1

Low High High

Damaged in attic, partially abated

18 Floor Mastic Under Tile Black 300 SF

NO Good 1

Low High Low

Good Condition

Contact Vibration Air Erosion

3 Floor Mastic under tile Black 220 SF

NO Good 1

Low High Low

3 Damaged 6 Piping insulation Magnesia-Type (Heating System) 400 LF

Yes Damaged 4

Low High High

6 Damaged 7 PipingInsulation, Aircell-Type 100 LF

NO Damaged 4

Low High High

6 Damaged 10 Debris Pipe Debris In Soil 60 SF

Yes Removed 11 Floor Mastic under tile Black 500 SF

NO Good 1

Low High Low

3 Damaged 15 Textured paint Exterior Paint (White) 10000 SF

NO Good 1

High High High

3 Painted over

Contact Vibration Air Erosion

1 Floor Tile 12"x12" (does not include mastic) Tan 800 SF NO Good 1

High High High

Good Condition

3 Floor Tile 12"x12" (does not include mastic) Gray 90 SF NO Good 1

High High High

Good Condition

16 Piping insulation Aircell-Type (Heating System) 200 LF Yes Good 2

Low High High

Good, appears to have been partially abated

21 Window caulking Window Glazing (Gray) 1500 LF NO Good 1 Moderate High High 3 Good Condition

Contact Vibration Air Erosion

Building 98

CURRENT

CLASSIFICATI

ON

Building 72

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 Inspection

Building 69

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 Inspection

Building 64

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 InspectionHomgenous

Area Number Material Description Approximate Quanity FRIABLE

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 InspectionFRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Homgenous Area Number Material Description Approximate

Quanity

8 Floor Mastic Under Tile Black 2nd floor 1800 SF

Low High Low

Abated, although some 12x12 floor tile still exists in remote areas, all in good condition

15 Floor Tile 12"X12" (Does Not Include Mastic) Tan Elevators

130 SF

NO Good 1

High High High

ABATED

16 Floor Mastic Under Tile Black Elevators 130 SF

NO Good 1

Low High Low

ABATED

17 Floor Tile 9"X9" (Does Not Include Mastic) Tan Basement, 2nd, 3rd

6000 SF

NO Good 1

High High High

12x12 in basement, on third floor, and remote areas of 1st and 2nd floor. All in good condition

18 Floor Mastic Under Tile Black Basement, 2nd, 3rd 6000 SF

NO Good 1

Low High Low

See above

21 Piping Insulation Magnesia-Type (Heating System) Basement

350 LF

Yes Damaged 4

Low High High

In locked crawl space. Significantly damaged 22 Emergency Generator Muffler Insulation Grey

Generator Room

100 SF

Yes Damaged 4

Low Low Low

Repaired. Not marked as containing or not containing asbestos 30 Debris Soil Debris (MAG) Basement 10000 SF

Yes Damaged 4

Low High High

In locked crawl space. Significantly damaged 32 Firestop Caulking/Putties On Fan Coil Unit Exterior

Windows

250 LF

NO Good 1

Low High High

Visible damage to exterior window caulking on 2nd and 3rd floor. First floor in good condition.

35 Pipe Fitting Insulation On Roof Drain Penthouse 12 EA

Yes Damaged 4

Low High High

Damaged

Pipe Fitting Insulation On Fiberglass Run (Domestic & Chilled Water Line) Basement, 1st, 2nd, Penthouse 80 EA Yes Damaged 4

Low High High

Penthouse in good condition

37 Pipe Fitting Insulation On Foam Rubber Piping Insulation Basement 1st, 2nd, Penthouse

600 EA

Yes Damaged 4

Low High High

Damaged

Elevator Brake Shoes Penthouse

10 SF NO Good 1

High High High

Good Condition

Contact Vibration Air Erosion

23 Joint Compound On Gypsum Board White 2500 SF

NO Good 1

Moderate m Low

Abated as part of halls and walls project??

Pipe Fitting Insulation On Fiberglass Line (Htg, Domes/Chilled Water Line)

1500 EA Yes Damaged 4

Low High High

Still damaged throughout. Some piece meal abatement has occurred in respnse to specific issues.

26 Tank Insulation Gray 120 SF

NO

Significantly

Damaged 1

Moderate Low Low

?? There is a tank in utility room that has fresher insulation on it. Uitlity room appears to have had fairly recent abatement performed 27 Window Caulking Exterior Window Glazing 8000 LF

NO Good 1

Low Moderate High

Good. Some minor damage in peace garden 29 Piping Insulation Roof Drain Insulation (Asumed) 15 LF

Yes Damaged 4

Low High Low

3 Damaged

Contact Vibration Air Erosion

2 Floor Mastic on HA#1 1000SF

NO Good 1

Low High Low

Approximately 50% abated, 50%good 5 Floor Tile 12"X12", 1000 SF

NO Good 1

High High High

Approximately 50% abated, 50%good 7 Floor Tile 9"X9" (Does Not Include Mastic) Tan 15,450 SF

NO Good 1

High High High

Abated

8 Mastic under Floor Tile 9"X9" 15,450 SF

NO Good 1

Low High Low

Abated

Building 102

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 Inspection

Building 101

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 Inspection

12&13 Viny Sheet Flooring, Brown Mastic 1000 SF

High High High

Could not locate. Abated?

Pipe Fitting Insulation On Fiberglass Run (Htg, Domes/Chilled Water Line) 300 EA Yes Damaged 4

Low High High

Damaged

27 Window Caulking Gray 8000 LF

Yes Damaged 4

Low High High

Appears to have been repaired at some point 28 Window Caulking Gray 200 LF

NO Good 1

Low Moderate High

Good

106 Mastic on Fan Coil Unit 75 SF

NO Good 1

Low High High

Good

202 Mastic under gold sheet flooring 750 LF

NO Good 1

Low High Low

Could not locate. Abated?

Contact Vibration Air Erosion

19 Pipe Fitting Insulation On Fiberglass Run (Htg, Dome 1300 EA Yes Damaged 4 Low High high 6 Per notations on drawings, information on this insulation was provided to thew contractor by the VA and not examined in either the 2010 or 2007 assessments. Disagree that it can be classified as damaged.

Disagree that it is one homgeneous area.

Contact Vibration Air Erosion

2 Floor Mastic Under Tile Black 5800 SF

NO Good 1

Low High Low

Hallways abated, some floor tiles remain in offices.

4 Floor Mastic Under Tile Black 1500 SF

NO Good 1

Low High Low

Hallways abated, some floor tiles remain in offices.

6 Floor Mastic Under Tile Black 5000 SF

NO Good 1

Low High Low

Hallways abated, some floor tiles remain in offices.

7 Floor Tilw 12"x12", Orange/Mastic 500 SF

NO Good 1

High High High

Hallways abated, some floor tiles remain in offices.

8 Floor Tile 9"X9" (Does Not Include Mastic) Tan 13400 SF

NO Good 1

High High High

Abated

9 Floor Tile 9"X9" (Does Not Include Mastic) Black 13400 SF

NO Good 1

High High High

Abated

12 Floor Mastic Under Tile Black 2000 SF

NO Good 1

Low High Low

Abated

Pipe Fitting Insulation On Fiberglass Run (Heating & Domestic Waterline) 450 EA Yes Damaged 4

Low High High

Approximately 75% abated, 25 % damaged 17 Ceiling Tile 1'x1' (Spline System) Pinhole 3500 SF

Yes Damaged 4

Low High High

Abated

18 Mastic On Sink Black 3 EA

NO Good 1

Low High Low

Good

19 Transite-Type Panels 1200 SF

NO Good 1

Low High High

Good, but not all is transite

20 Tank Insulation Gray 50 SF

Yes Damaged 4

Moderate Low Moderate

Removed

Generator Insulation Emergency Muffler Generator Insulation 300 SF Yes Damaged 4

Low High High

Damaged

103 Vibration Dampening cloth 25 SF

NO Good 1

Low High High

Good

Building 104

Building 103

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 Inspection

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKING

Disturbance Potential POTENTIAL

HAZARD

August 2016 Inspection

Remarks Contact Vibration Air

Erosion Mar-17

2 Floor Mastic Under Tile Black second floor

2600 SF

NO Good 1

Low High Low

ABATED Abated

4 Floor Mastic Under Tile Black fifth floor

520 SF

NO Good 1

Low High Low

GOOD Good

Floor Tile 9"X9" (Does Not Include Mastic) Tan, Brown & Green Basement through fifth 19000 SF NO Good 1

High High High

Basement damaged,1-3 abated. Some 9x9 remains in path lab. 9x9 remains in some stair wells, all in good condition

No changes except West stairwell 1st floor damaged 9x9. Recommend removal

16 Floor Mastic Under Tile Black 1st through 5th

19000 SF

NO Good 1

Low High Low

1-3 abated 4-5 Good

17 Floor Tile 12"X12" (Does Not Include Mastic) Light Tan 2nd

600 SF

NO

ABATED Abated

29 Mastic On Sink Black 1st through 5th

7 EA

NO Good 1

Low High Low

Several damaged No Change

32 Piping Insulation Magnesia- Type (Heating System) crawlspace and attic

3000 LF

Yes Damaged 4

Low High High

Attic 90% abated, remainder damaged.

crawl space unchanged, damaged

No Change

33 Piping Insulation Aircell-Type (Domestic Waterline) crawlspace

350 LF

Yes Damaged 4

Low High High

Unchanged, damaged Unchanged, damaged

34 Tank Insulation White 3rd floor

300 SF

Yes Damaged 4

Low High High

ABATED Abated

36 Debris Soil Debris (MAG) crawlspace

12500 SF

Yes Damaged 4

Low High High

Unchanged; damaged Unchanged, dmaged

37 Thermal Taping Compound Tape attic

7000 SF

Yes Damaged 4

Low High High

90% abated, remainder damaged Unchanged

38 Pipe Support Insulation On Fiberglass Insulated Lines attic

350 EA

Yes Damaged 4

Low High High

90% abated; remainder damaged Unchanged

Pipe Fitting Insulation On Fiberglass Run (Chilled Waterline) crawlspace and attic 500 EA Yes Damaged 4

Low High High

Attic 90% abated, remainder damaged.

Crawlspaace unchanged, damaged

Unchanged

42 Caulking/Putties Fire Stop, On Fan Coil Unit exterior windows

400 LF

NO Good 1

Low High High

Several damaged Several damaged

43 Floor Mastic Under Tile Black 5th floor

500 SF

NO Good 1

Low High Low

Good Good

45 Floor Mastic Under Tile Black 2nd floor

600 SF

NO

ABATED Abated

Pipe Fitting Insulation On Blk Styrofoam Lines (Domestic/Chilled Lines) basement 40 EA Yes Damaged 4

Low High High

Damaged Damaged

Floor Tile 12"X12" (Does Not Include Mastic) Tan With Brown & Yellow Streaks basement 500 SF NO Good 1

High High High

Damaged Damaged

102 Elevator Brake Shoes attic 10 SF NO Good 1 High High High 3 Good Good

Disturbance Potential POTENTIAL

HAZARD

RANKING

REMARKS August 2017

Homgenous Area Number Material Description

Approxim ate

Quanity

FRIABLE

CURRENT

CLASSIFICATI

ON

HAZARD

RANKIN

G

Erosion

Floor Mastic Under Tile Black 2nd floor 1800 SF NO Good 1 Low High Low 3

Abated, although some 12x12 floor tile still exists in remote areas, all in good condition

Floor Tile 12"X12" (Does Not Include Mastic) Tan Elevators 130 SF NO Good 1 High High High 3

ABATED

Floor Mastic Under Tile Black Elevators 130 SF NO Good 1 Low High Low 3

ABATED

Floor Tile 9"X9" (Does Not Include Mastic) Tan Basement, 2nd, 3rd 6000 SF NO Good 1 High High High 3

12x12 in basement, on third floor, and remote areas of 1st and 2nd floor

Floor Mastic Under Tile Black Basement, 2nd, 3rd 6000 SF NO Good 1 Low High Low 3

See above

Piping Insulation Magnesia-Type (Heating System) Basement 350 LF Yes Damaged 4 Low High High 6

In locked crawl space. Extensively damaged

Emergency Generator Muffler Insulation Grey Generator Room 100 SF Yes Damaged 5 Low High Low 5

Repaired. Not marked as containing or not containing asbestos

Debris Soil Debris (MAG) Basement 10000 SF Yes Damaged 4 Low High High 6

In locked crawl space. Extensively damaged

Firestop Caulking/Putties On Fan Coil Unit Exterior Windows 250 LF NO Good 1 Low High High 3

Visible damage to exterior window caulking on 2nd and 3rd floor. First floor in good condition.

Pipe Fitting Insulation On Roof Drain Penthouse 12 EA Yes Damaged 4 Low High High 6

Damaged

Pipe Fitting Insulation On Fiberglass Run (Domestic & Chilled Water Line) Basement, 1st, 2nd, Penthouse 80 EA Yes Damaged 4 Low High High 6

Penthouse in good condition

Pipe Fitting Insulation On Foam Rubber Piping Insulation Basement 1st, 2nd, Penthouse 600 EA Yes Damaged 4 Low High High 6

Damaged

102 Elevator Brake Shoes Penthouse 10 SF NO Good 1 High High High 3

Good Condition

Disturbance Potential POTENTI

AL

HAZARD

REMARKS

Building 98

Homgeno us Area Number

Material Description Approxim ate Quanity

FRIABLE CURRENT

CLASSIFICATION

HAZARD

Aug-16 Mar-17

Erosion

2 Floor Mastic Under Tile Black Basement and 1st

350 SF NO Good 1 Low High Low 6 1st floor abated save for east foyer.

Basement significant damage

Significantly Damaged

Significantly Damaged

5 Floor Tile 9”x9” (Does Not Include Mastic) Green 1st

450 SF NO Significantly Damaged 1 High High Low 7 1st floor abated save for east foyer.

Basement significant damage Good Good

Floor Mastic Under Black Tile

1st 450 SF NO Good 1 Low High Low 3 Abated save for east foyer Good Good

10 Piping Insulation Magnesia-Type

(Heating System) basement

200 SF NO Good 1 Low High High 3 Damaged, partially remediated Good Good

11 Piping Insulation Aircell -Type

(Domestic Water) basement

250 SF NO Good 1 Low High High 3 Damaged, partially remediated Good Damaged

12 Piping Fitting Insulation On

Magnesia-Type (Heating System) basement

10 EA NO Good 1 Low High High 3 Damaged, partially remediated Good Damaged

17 Piping Insulation Magnesia-Type

(Heating System) firedoor basement

1 EA Yes Good 4 Low High High 3 Repaired Good Good

18 Exterior window glazing basement and 1st 2000 LF NO Good 1 Low High Low 3 Some damage on a few windows Good Good

19 exteerior pain white. 10000 SF Yes Good 4 Low High High 3 Painted over Good Good

Disturbance Potential POTENTI

AL

HAZARD

REMARKS

Building 22

Homgenous Area Number

Material Description

Approximate Quanity FRIABLE

CURRENT

CLASSIFICA

TION

HAZARD

Aug-16 Feb-17

3 Floor Tile 12"X12" (Does Not Include

Mastic) White With Grey Streaks

18 SF NO Good 1 High High High 3 Good Condition Good Condition

4 Floor Mastic Under Tile Black

18 SF NO Good 1 Low High Low 3 Good Condition Good Condition

5 Floor Tile 12"X12" (Does Not Include

Mastic) White With Brown Streaks

120 SF NO Good 1 High High High 3 Good Condition Good Condition

6 Floor Mastic Under Tile Black

120 SF NO Good 1 Low High Low 3 Good Condition Good Condition

7 Vinyl Sheet Flooring (Does Not

Include Mastic) Brown

300 SF Yes Damaged 4 Low High High 6 Good Condition Good Condition

16 Piping Insulation Aircell-Type

(Heating System)

140 LF NO Good 1 Low High High 3 Damaged in attic, partially abated Damaged in attic,may need further abatement.

18 Floor Mastic Under Tile Black

300 SF NO Good 1 Low High Low 3 Good Condition Good Condition

Contact Vibration Air Erosion

1 Floor Tile 12"x12" (does not include mastic) Tan

800 SF NO Good 1 High High High 3 Good Condition Good Condition

3 Floor Tile 12"x12" (does not include mastic) Gray

90 SF NO Good 1 High High High 3 Good Condition Good Condition

16 Piping insulation Aircell-Type

(Heating System)

200 LF Yes Good 2 Low High High 3 Good, appears to have been partially abated

Good, appears to have been partially abated

21 Window caulking Window Glazing

(Gray)

1500 LF NO Good 1 Moderate High High 3 Good Condition Good Condition

REMARKS

Building 72

Disturbance Potential POTENTIAL

HAZARD

RANKING

REMARKS

Building 64

Homgenous Area Number

Material Description

Approximate Quanity

FRIABLE CURRENT

CLASSIFICA

TION

HAZARD

RANKIN

G

Homgenous Area Number

Material Description

Approximate Quanity FRIABLE

CURRENT

CLASSIFICA

TION

HAZARD

RANKIN

G

Disturbance Potential POTENTIAL

HAZARD

23 Joint Compound On Gypsum Board White Throughout

2500 SF

NO Good 1

Moderate m Low

Abated as part of halls and walls project??

Pipe Fitting Insulation On Fiberglass Line (Htg, Domes/Chilled Water Line) Throughout, see diagrams

1500 EA Yes Damaged 4

Low High High

Still damaged throughout. Some piece meal abatement has occurred in response to specific issues.

26 Tank Insulation Gray

120 SF

NO

Significantly Damaged 1

Moderate Low Low

?? There is a tank in utility room that has fresher insulation on it. Uitlity room appears to have had fairly recent abatement performed 27 Window Caulking

Exterior Window Glazing

8000 LF

NO Good 1

Low Moderate High

Good. Some minor damage in peace garden 29 Piping Insulation

Roof Drain Insulation (Assumed)

15 LF

Yes Damaged 4

Low High Low

3 Damaged

Disturbance Potential POTENTI

AL

HAZARD

August 2016 Inspection

Building 101

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICAT

ION

HAZARD

19 Pipe Fitting Insulation O 1300 EA Yes Damaged 4 Low High high 6 Per notations on drawings, information on this insulation was provided to thew contractor by the VA and not examind in either the 2010 or 2007 assessments. Disagree that it can be classified as damaged. Disagree that it is one homgeneous area.

Disturbance Potential POTENTI

AL

HAZARD

August 2016 Inspection

Building 103

Homgenous Area Number Material Description Approximate

Quanity FRIABLE

CURRENT

CLASSIFICAT

ION

HAZARD

Erosion Mar-17

3 Floor Mastic under tile Black

220 SF

NO Good 1

Low High Low 3 Damaged Damaged

6 Piping insulation Magnesia-Type (Heating System)

400 LF

Yes Damaged 4

Low High High

6 Damaged Damaged 7 PipingInsulation, Aircell-Type

100 LF

NO Damaged 4 Low High High

6 Damaged Damaged 10 Debris Pipe

Debris In Soil

60 SF

Yes Removed Removed 11 Floor Mastic under tile Black

500 SF

NO Good 1 Low High Low

3 Damaged Damaged 15 Textured paint

Exterior Paint (White)

10000 SF

NO Good 1

High High High

3 Painted over Painted over

Disturbance Potential POTENTIA

L HAZARD

RANKING

August 2016 Inspection

Building 69

Homgenous Area Number

Material Description

Approximate Quanity FRIABLE CURRENT

CLASSIFICATION

HAZARD

2 Floor Mastic on

HA#1

1000SF NO Good 1 Low High Low 3 Approximately 50% abated, 50%good Approximately 50% abated, 50%good

5 Floor Tile 12"X12", 1000 SF NO Good 1 High High High 3 Approximately 50% abated, 50%good Approximately 50% abated, 50%good

7 Floor Tile 9"X9" (Does Not Include Mastic) Tan

15,450 SF NO Good 1 High High High 3 Abated Abated

8 Mastic under Floor Tile 9"X9"

15,450 SF NO Good 1 Low High Low 3 Abated Abated

12&13 Viny Sheet Flooring, Brown Mastic

1000 SF NO Good 1 High High High 3 Could not locate. Abated? Could not locate.

Abated?

Pipe Fitting Insulation On Fiberglass Run (Htg, Domes/Chilled Water Line)

300 EA Yes Damaged 4 Low High High 6 Damaged

27 Window Caulking Gray

8000 LF Yes Damaged 4 Low High High 6 Appears to have been repaired at some point

28 Window Caulking Gray

200 LF NO Good 1 Low Moderate High 3 Good

106 Mastic on Fan Coil Unit

75 SF NO Good 1 Low High High 3 Good

202 Mastic under gold sheet flooring

750 LF NO Good 1 Low High Low 3 Could not locate. Abated? Could not locate.

Abated?

Disturbance Potential POTENTIA

L HAZARD

RANKING

August 2016 Inspection

Building 102

Homgenous Area Number

Material Description

Approximate Quanity FRIABLE

CURRENT

CLASSIFICATIO

N

HAZARD

2 Floor Mastic Under Tile Black

5800 SF NO Good 1 Low High Low 3 Hallways abated, some floor tiles remain in offices.

Hallways abated, some floor tiles remain in offices.

4 Floor Mastic Under Tile Black

1500 SF NO Good 1 Low High Low 3 Hallways abated, some floor tiles remain in offices.

Hallways abated, some floor tiles remain in offices.

6 Floor Mastic Under Tile Black

5000 SF NO Good 1 Low High Low 3 Hallways abated, some floor tiles remain in offices.

Hallways abated, some floor tiles remain in offices.

7 Floor Tilw 12"x12", Orange/Mastic

500 SF NO Good 1 High High High 3 Hallways abated, some floor tiles remain in offices.

Hallways abated, some floor tiles remain in offices.

8 Floor Tile 9"X9" (Does Not Include Mastic) Tan

13400 SF NO Good 1 High High High 3 Abated Abated

9 Floor Tile 9"X9" (Does Not Include Mastic) Black

13400 SF NO Good 1 High High High 3 Abated Abated

12 Floor Mastic Under Tile Black

2000 SF NO Good 1 Low High Low 3 Abated Abated

14 Pipe Fitting Insulation On Fiberglass Run (Heating & Domestic Waterline)

450 EA Yes Damaged 4 Low High High 6 Approximately 75% abated, 25 % damaged

Approximately 75% abated, 25 % damaged

17 Ceiling Tile 1'x1' (Spline System) Pinhole

3500 SF Yes Damaged 4 Low High High 6 Abated Abated

18 Mastic On Sink Black

3 EA NO Good 1 Low High Low 3 Good Good

19 Transite-Type Panels

1200 SF NO Good 1 Low High High 3 Good, but not all is transite Good, but not all is transite

20 Tank Insulation Gray

50 SF Yes Damaged 4 Moderate Low Moderate 5 Removed Removed

21 Generator Insulation Emergency Muffler Generator Insulation

300 SF Yes Damaged 4 Low High High 6 Damaged Damaged

103 Vibration Dampening cloth

25 SF NO Good 1 Low High High 3 Good Good

Disturbance Potential POTENTIAL

HAZARD

RANKING

August 2016 Inspection

Building 104

Homgenous Area Number

Material Description

Approximate Quanity FRIABLE CURRENT

CLASSIFICATION

HAZARD

All Buildings
58
98
22
64-72
101
103
69
102
104