ATTACHMENT F - Air FLow Template AnimalResearch with AC Shop markups.xlsx
XLSX spreadsheet 87 KB Posted
- Solicitation number
- 36C25223Q0334
About this file
This document contains an air flow template for the Edward Hines Jr VA Hospital Animal Research Facility outlining the systems, rooms, usage details, and air change requirements for a three-year schedule. Key details include specifications for cleaning fan systems and grilles, conducting air change testing, and replacing filters across multiple rooms and areas of the facility including animal rooms, procedure rooms, storage areas, and corridors. The related federal contract opportunity is solicitation number 36C25223Q0334 for air testing, central fan cleaning, and filter maintenance services at the Edward Hines Jr VA Hospital over a base year plus four option years. The solicitation is seeking these services from the Department of Veterans Affairs Veterans Health Administration VISN 12.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25223Q0334 0003.docx | DOCX document | |
| 36C25223Q0334 0002.docx | DOCX document | |
| ATTACHMENT C - Air Filter Information rev.xlsx | XLSX spreadsheet | |
| 36C25223Q0334 0001.docx | DOCX document | |
| ATTACHMENT A - Airflow Templates rev.pdf | ||
| ATTACHMENT B - Floor Plans.pdf | ||
| ATTACHMENT E - FACILITY MAP.pdf | ||
| ATTACHMENT C - Air Filter Information.xlsx | XLSX spreadsheet | |
| ATTACHMENT A - Airflow Templates.pdf | ||
| 36C25223Q0334_1.docx | DOCX document | |
| ATTACHMENT D - DOL WD 2015-5017 (Rev-22) dated 12.27.2022.docx | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Table 1
| Edward Hines Jr VA Hospital - Animal Research Facility (VMU)- (3 Year Schedule) | |||||||||||||||
| System: | SF-229, EF-229 & TE-1 | ||||||||||||||
| Room No. | Usage | Ceiling Ht | Sq. Ft. | Cubic Ft. | Des. SA | Act. SA | % Design | Des. EA | Act. EA | % Design | Actual Pressure | ||||
| +/--/0 | Actual | Actual | |||||||||||||
| A.C./hr | A.C./hr | ||||||||||||||
| Supply | Exhaust | ||||||||||||||
| 229-101 | Corridor | 8.1 | 297.6 | 2405 | 450 | N/A | |||||||||
| 229-103 | Receiving | 8.4 | 181.5 | 1525 | 380 | 420 | |||||||||
| 229-104 | Sterile Storage | 8.5 | 158 | 1343 | 330 | 380 | |||||||||
| 229-107 | Necropsy | 8.4 | 198.7 | 1673 | 430 | 470 | |||||||||
| 229-108 | Dirty Storage | 8.6 | 234.3 | 2015 | 390 | 440 | |||||||||
| 229-109 | Animal Room | 8.6 | 236.5 | 2034 | 390 | 440 | |||||||||
| 229-110 | Animal Room | 8.5 | 233.6 | 1986 | 390 | 440 | |||||||||
| 229-111 | Animal Room | 8.5 | 231.8 | 1971 | 390 | 440 | |||||||||
| 229-112 | Surgery | 8.1 | 233.6 | 1888 | 390 | 440 | |||||||||
| 229-113 | Animal Room | 8.1 | 353.3 | 2855 | 750 | 820 | |||||||||
| 229-114 | Corridor | 8.3 | 1400.2 | 11551 | 1930 | 1500 | |||||||||
| 229-120 | Washroom | 8.4 | 81.2 | 683 | 160 | 180 |
| Edward Hines Jr VA Hospital - Animal Research Facility (VMU)- (3 Year Schedule) | |||||||||||
| System: | SF-3 & EF-B-400 (EF-3), KEF-1, TEF-2, TEF-3 | ||||||||||
| Room No. | Usage | Ceiling Ht | Sq. Ft. | Cubic Ft. | Design SA | Actual SA | % Design | Design EA | Actual EA | % Design | Actual |
Pressure
| +/--/0 | Actual | Actual | ||||||||||||||||||||
| A.C./hr | A.C./hr | |||||||||||||||||||||
| Supply | Exhaust | |||||||||||||||||||||
| B422 | Staff Lounge/Lunch Rm | 8.3 | 217.0 | 1801 | 430 | 450 | ||||||||||||||||
| B422B | Lockers Womens | 8.3 | 248.0 | 2066 | -633 | Transfer | ||||||||||||||||
| B422C | Toilet | 8.3 | 51.0 | 425 | -- | 580 | ||||||||||||||||
| B423 | Office / Research | 8.3 | 149.6 | 1246 | 130 | N/A | ||||||||||||||||
| B425 | Office / Secretary | 8.3 | 177.1 | 1475 | 155 | N/A | ||||||||||||||||
| B425A | Office | 8.3 | 192.2 | 1595 | 200 | N/A | ||||||||||||||||
| B426 | Lockers Mens | 8.3 | 298.0 | 2473 | -540 | Transfer | ||||||||||||||||
| B426A | Toilet | 8.3 | 115.5 | 962 | -- | 540 | ||||||||||||||||
| B429 | Office | 8.3 | 342.8 | 2856 | 450 | N/A | ||||||||||||||||
| B434 | Drug Vault | 8.3 | 71.5 | 596 | 50 | N/A | ||||||||||||||||
| B4A | Corridor | 8.3 | 723.7 | 6006 | 405 | N/A | ||||||||||||||||
| Edward Hines Jr VA Hospital - Animal Research Facility (VMU)- (3 Year Schedule) | ||||||||||||||||||||||
| System: | SF-404 & EF-404 | |||||||||||||||||||||
| Room No. | Usage | Width | Ceiling Ht | Sq. Ft. | Cubic Ft. | Des. SA | Act. SA | % Design | Des. EA | Act. EA | % Design | Actual |
Pressure
| +/--/0 | Actual | Actual | ||||||||||
| A.C./hr | A.C./hr | |||||||||||
| Supply | Exhaust | |||||||||||
| B406/408 | Animal Room | 23.1 | 8.4 | 348.9 | 2931 | 1725 | 950 | |||||
| B409 | Animal Room | 17.3 | 8.3 | 244.0 | 2025 | 555 | 610 | |||||
| B410 | Animal Room | 23.7 | 8.3 | 530.9 | 4422 | 1270 | 1400 | |||||
| B411 | Animal Room | 16.9 | 8.3 | 238.6 | 1980 | 555 | 610 | |||||
| B412 | Animal Room | 21.5 | 8.4 | 487.6 | 4096 | 1160 | 1275 | |||||
| B413 | Animal Room | 16.6 | 8.3 | 234.3 | 1945 | 555 | 610 | |||||
| B414 | Necropsy | 23.3 | 8.3 | 163.3 | 1355 | 460 | 510 | |||||
| B415 | Animal Procedure Room | 16.6 | 8.3 | 235.9 | 1958 | 570 | 625 | |||||
| Corridor | Corridor | 8.3 | 810.7 | 6729 | N/A | N/A |
| B416 | Lockers Men | 13 | 10.8 | 272.0 | 2924 | N/A | N/A | ||||||
| B421 | Lockers Womens | 13.5 | 8.4 | 189.0 | 1588 | N/A | N/A | ||||||
| B403 | Storage | 17.2 | 8.4 | 223.1 | 1870 | N/A | N/A | ||||||
| B401 | Dirty Equipment | 21.2 | 8.5 | 260.8 | 2217 | N/A | N/A | ||||||
| B400A | Cage Wash | 23.8 | 8.8 | 278.8 | 2453 | N/A | N/A | ||||||
| B400C | Carcuss Disposal | 7.5 | 8.8 | 90.0 | 792 | N/A | N/A | ||||||
| Corridor | Corridor | 7.6 | 8.5 | 263.0 | 2235 | N/A | N/A | ||||||
| B400/B400A* | Cage Wash Dirty | 37 | 8.5 | 866.5 | 7366 | N/A | 2390 |
| Edward Hines Jr VA Hospital - Animal Research - Certification (3 Year Schedule) | ||||||||||||||||
| System: | SFC-400 & EF-C-400 | |||||||||||||||
| Room No. | Usage | Sq. Ft. | Cubic Ft. | Des. SA | Act. SA | % Design | Des. EA | Act. EA | % Design | Actual Pressure +/- | ||||||
| -/0 | Actual | Actual | ||||||||||||||
| A.C./hr | A.C./hr | |||||||||||||||
| Supply | Exhaust | |||||||||||||||
| South | Corridor B/C Section | N/A | 1152 | N/A | ||||||||||||
| C402/C403 | Large Animal OR 6 | N/A | 5114 | N/A | ||||||||||||
| C402A | Surgery Vestibule | N/A | 1338 | N/A | ||||||||||||
| C402B | Scrub | N/A | 1596 | N/A | ||||||||||||
| C404 | Large Animal OR 7 | N/A | 4200 | N/A | ||||||||||||
| C404A | Surgery Vestibule | N/A | 1454 | N/A | ||||||||||||
| C405 | Janitorial | N/A | 890 | N/A | ||||||||||||
| C405A | Surgery Prep | N/A | 2751 | N/A | ||||||||||||
| C406 | Large Animal OR 8 | N/A | 6228 | N/A | ||||||||||||
| C406A | Surgery Vestibule | N/A | 2751 | N/A | ||||||||||||
| C406B | Dark Room | N/A | 212 | N/A | ||||||||||||
| C406C | Scrub | N/A | 1150 | N/A | ||||||||||||
| C407 | Office | N/A | 585 | N/A | ||||||||||||
| C409 | Recovery | N/A | 1915 | N/A | ||||||||||||
| C411 | Storage | N/A | 1071 | N/A | ||||||||||||
| Corridor | Corridor North C Section | N/A | 8353 | N/A | ||||||||||||
| B438 | PI Lab | N/A | 2850 | N/A | ||||||||||||
| B439 | Procedure Room | N/A | 1320 | N/A | ||||||||||||
| B440 | Surgery | N/A | 5360 | N/A | ||||||||||||
| B444 | Small Animal Surgery | N/A | 2220 | N/A | ||||||||||||
| B444A | Scrub | N/A | 297 | N/A | ||||||||||||
| B445A | Lab Culture | N/A | 2560 | N/A | ||||||||||||
| B445 | Conference Room | N/A | 2052 | N/A | ||||||||||||
| B433 | Office | N/A | 1410 | N/A |
| Edward Hines Jr VA Hospital - Animal Research Facility (VMU)- (3 Year Schedule) | ||||||||||||||||||||||||||
| System: | SFC-400 & EF-C-400 | |||||||||||||||||||||||||
| Room No. | Usage | Ceiling Ht | Sq. Ft. | Cubic Ft. | Des. SA | Act. SA | % Design | Des. EA | Act. EA | % Design | Actual Pressure | |||||||||||||||
| +/--/0 | Actual | Actual | ||||||||||||||||||||||||
| A.C./hr | A.C./hr | |||||||||||||||||||||||||
| Supply | Exhaust | |||||||||||||||||||||||||
| B446 | XRay Lab | N/A | N/A | 3605 | N/A | N/A | ||||||||||||||||||||
| B450 | Lab | N/A | N/A | 3629 | N/A | N/A | ||||||||||||||||||||
| B451 | Clean Supply | N/A | N/A | 4715 | N/A | N/A | ||||||||||||||||||||
| B451A | Laundry | N/A | N/A | 2888 | N/A | N/A | ||||||||||||||||||||
| B452 | Procedure Lab | N/A | N/A | 1025 | N/A | N/A | ||||||||||||||||||||
| B454 | Surgery | N/A | N/A | 4287 | N/A | N/A | ||||||||||||||||||||
| B435 | Office | N/A | N/A | 1099 | N/A | N/A | ||||||||||||||||||||
| Edward Hines Jr VA Hospital - Animal Research Facility (VMU)- (3 Year Schedule) | ||||||||||||||||||||||||||
| System: | SF-411 & EF-411 aka EF-403 per House because it's installed in Room A403 | |||||||||||||||||||||||||
| Room No. | Usage | Ceiling Ht | Sq. Ft. | Cubic Ft. | Des. SA | Act. SA | % Design | Des. EA | Act. EA | % Design | Actual |
Pressure
| +/--/0 | Actual | Actual | |||||||||
| A.C./hr | A.C./hr | ||||||||||
| Supply | Exhaust | ||||||||||
| Barrier Corr. | Corridor | 8.06 | 341.9 | 2950 | N/A | N/A | |||||
| A428 | Closet | 10.8 | 19.3 | 209 | N/A | N/A | |||||
| A426A | Biohazard Sterile Supply | 8.3 | 207.9 | 1732 | 450 | 400 | |||||
| A422 | Biohazard | 8.9 | 118.6 | 1058 | 265 | 300 | |||||
| A420 | Biohazard | 8.8 | 155.7 | 1368 | 340 | 290 | |||||
| A418A* | Barrier Surgery | 8.3 | 255.5 | 2128 | 530 | 480 | |||||
| A416 | Sterile Supply | 8.8 | 155.7 | 1368 | N/A | N/A | |||||
| A414 | Barrier SHU | 8.8 | 109.3 | 956 | 225 | 210 | |||||
| Corridor C4E | Corridor | 8.3 | 87.8 | 725 | 600 | 600 | |||||
| A410 | Auto Clave | 8.1 | 25.3 | 205 | N/A | N/A | |||||
| Corridor C4B | Corridor | 8.5 | 162 | 1377 | 250 | N/A | |||||
| A408 | Janitorial | 8.5 | 57.4 | 486 | 200 | 200 | |||||
| Corridor | Corridor | 9.0 | 82.1 | 739 | N/A | 30 | |||||
| A404 | Locker Womens | 9.0 | 126.3 | 1137 | 200 | 250 | |||||
| A402 | Locker Mens | 8.5 | 126.3 | 1074 | 200 | 250 | |||||
| A424 | Biohazard | 8.9 | 1236 | N/A | N/A |
| Edward Hines Jr VA Hospital - Animal Research Facility (VMU)-3 Year Schedule | ||||||||||||||||
| System: | SF-432 & EF-440 | |||||||||||||||
| Room No. | Usage | Ceiling Ht | Sq. Ft. | Cubic Ft. | Des. SA | Act. SA | % Design | Des. EA | Act. EA | % Design | Actual Pressure | |||||
| +/--/0 | Actual | Actual | ||||||||||||||
| A.C./hr | A.C./hr | |||||||||||||||
| Supply | Exhaust | |||||||||||||||
| B400/B400A* | Cage Wash Dirty | 8.5 | 866.5 | 7365.6 | ||||||||||||
| B400COR | Corridor | 8.5 | 263.0 | 2235.2 | ||||||||||||
| A445 | Animal Room | 8.8 | 138.2 | 1219.9 | ||||||||||||
| A443 | Office | 8.8 | 65 | 573 | ||||||||||||
| A439 | Animal Room | 8.8 | 117 | 1032 | ||||||||||||
| A441 | Office | 8.8 | 137 | 1210 | ||||||||||||
| A442 | Cage Wash Clean | 8.7 | 420 | 3654 | ||||||||||||
| A438 | Clean Storage | 8.8 | 744 | 6570 | ||||||||||||
| A437 | Animal Room | 8.8 | 137 | 1210 | ||||||||||||
| A435 | Animal Room | 8.8 | 98 | 866 | ||||||||||||
| A433 | Animal Room | 8.9 | 142 | 1259 | ||||||||||||
| A431 | Animal Room | 8.9 | 175 | 1561 | ||||||||||||
| A429 | Animal Room | 8.8 | 133 | 1171 | ||||||||||||
| A434 | Vestibule | 8.5 | 111 | 941 | ||||||||||||
| A434A | Behavior Room | 8.8 | 154 | 1364 | ||||||||||||
| A434B | Behavior Room | 8.8 | 224 | 1965 | ||||||||||||
| A427 | Barrier Room | 8.8 | 115 | 1011 | ||||||||||||
| A425 | Animal Room | 8.8 | 158 | 1385 | ||||||||||||
| A423 | Animal Room | 8.9 | 163 | 1443 | ||||||||||||
| A421 | Feed Storage | 8.3 | 225 | 1872 | ||||||||||||
| S. Corridor | Corridor | 8.8 | 1124 | 9891 |
B439 - adding dampered exhaust vent, ordered 6/6/22