This document contains product specifications and ordering information for electrical system upgrade components required by the Department of Veterans Affairs project number 36C25223B0020 to update electrical systems at facility 676-23-002. Key components include self-regulating heating cables for snow melting and de-icing applications on roofs and gutters, cable cover brackets, junction boxes, roof clips, adhesives, power connection kits, controllers, contactors, sensors, and other accessories. The specifications provide technical details on materials, voltages, amperages, temperature ranges, and dimensions. Ordering part numbers and catalogs are listed to procure the necessary upgrade components from approved suppliers.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--Update Electrical Systems 676-23-002, newest first.
File Type Posted
36C25223B0020 0008.docx DOCX document
36C25223B0020 0007.docx DOCX document
36C25223B0020 0006.docx DOCX document
36C25223B0020 0005.docx DOCX document
36C25223B0020 0004.docx DOCX document
36C25223B0020 0003.docx DOCX document
S04 - 676-23-02 upgrade elec- site visit roster.pdf PDF
36C25223B0020 0002.docx DOCX document
36C25223B0020 0001.docx DOCX document
S06 - 0001 Att 1 676-23-002 Update Electrical System - Appendix A- Combined Specs REVISED.pdf PDF
S06 - 0001 Att 2 676-23-002 Update Electric System - Appendix B- Tank Sketches.pdf PDF
S02 - ATT 4 VHA COVID COMPLIANCE.pdf PDF
S02 - ATT 1 Combined SOW - 676-23-002 Update Electric System.pdf PDF
S02 - ATT 2 Wage Rates 3.30.23.pdf PDF
S02 - ATT 3 VHA Directive 1192_01_D_2020-08-10 Seasonal Flu Shot.pdf PDF
36C25223B0020_2.docx DOCX document
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix C :

• Recent Design Example for Building 400 - Snow Melt Trace

(FOR REFERENCE ONLY)

• Roof Sketches showing rough building footprint dimensions

(FOR REFERENCE ONLY)

Raychem IceStop Self-Regulating Heating Cable

PROJECT: Tomah VA Medical Center

Q-FIRST, INC.

10336 S. Western Avenue Chicago, IL 60643 708.655.1462 qfirstinc@yahoo.com

Q-First, Inc.

10336 S. Western Avenue DATE: August 29, 2022

Chicago, IL 60643

708-655-1462 cell joe@qfirstinc.com

PROJECT:

ITEM # QTY UNIT MODEL

1 1200 ft. GM-2X

2 1100 ft. CCB-AL

3 14 ea. WPCK-R

4 14 ea. JB-55

5 2 ea. H914

6 15 ea. RIM Adhesive

7 40 ea. DSH

8 1 ea.

APS-4C-

208/240V

9 2 ea.

SC-40C

208/240V 1P &

3P

10 2 ea. cut charge

11 4 ea. WSTK

12 2 ea. Snow Owl

Splice / Tee Kit

Aerial Mounted Moisture & Temperature Sensor

Junction box, 5"x5"

Downspout hanger

Tomah VA Medical Center

IceStop self-regulating heating cable, 208-277 V, with polyolefin jacket

Cable Cover Bracket, aluminum

Roof & Gutter De-icing Power Connection Kit with End Seal

DESCRIPTION

TO: Digital Roofing Co.

Bill of Materials nVent cable cut charge

Roof clips (50 ea)

Roof adhesive/sealant for RIM systems, 10.3 oz. tube

SC-40C Satellite Contactor with Integral GFEP (208/240 VAC) Three

Phase

Automatic snow / ice melting system controller with GFEP, 208-240 VAC, three phase mailto:joe@qfirstinc.com

Tomah VA Medical Center

NOTES

1. Replace existing Raychem GutterMelt cable with the same product.

2. Use cable cover bracket in all gutters which will help the cable stay in place. Also it will help the cable be more efficient in spreading the heat.

3. Changing voltage from 120 VAC to 208 VAC. On a building this size 208 VAC is a much more efficient.

4. Pulling all new wires from the panels to the power connection points.

5. Adding controls (1) APS-4C controller and (2) SC-40C satellite contactors. The current system had no controls and the cable was on when we were examining it in August.

6. Adding new power connection kits at 14 different locations.

7. Installing Snow Owl aerial sensors at 2 different locations.

8. Extend cable through downspouts 5 ft. into conditioned space.

9. Megger test all connections to extend warranty.

10. Provide the registration for the 20 yr extended warranty.

Q-FIRST, INC.

10336 S. Western Avenue Chicago, IL 60643 708.655.1462 qfirstinc@yahoo.com nVent.com | 1Raychem-DS-EU0079-GM2XT-EN-1805

SELF-REGULATING HEATING CABLES

FOR ROOF & GUTTER SNOW MELTING

AND DE-ICING

GM-2X/GM-2XT

Nickel-plated copper conductors

Self-regulating conductive core

Modified polyolefin inner jacket

Tinned-copper braid

Fluoropolymer (-XT) or modified polyolefin (-X) outer jacket

Heating cable construction

PRODUCT DESCRIPTION

nVent RAYCHEM GM-2X and GM-2XT heating cables provide roof and gutter snow melting and de-icing for following applications:

• Roofs comprising standard roofing materials, including slate, shingle, bitumen, tar, wood, metal, and plastic.

• Gutters of standard materials, including metal, plastic, and wood.

• Drainpipes of standard materials, including metal and plastic.

The heating element of a GM-2X(T) consists of a continuous core conductive polymer extruded between two copper conductors. As current flows through the core, the heating cable regulates its heat output in accordance with ambient conditions.

The self-regulating feature eliminates hot spots and results in better temperature control to protect roof and gutter materials.

The heating cable is available with a fluoropolymer outer jacket (-XT) which provides maximum abrasion, chemical, and mechanical resistance; or a polyolefin outer jacket (-X) that is more economical for less demanding applications.

ADVANTAGES

Low installed cost

The GM-2X (T) heating cable’s parallel circuitry allows it to be cut to the exact length. Such characteristics simplify and streamline the design of a roof and gutter snow melting system.

Installation is quick and simple. Features that make the snow melting system easy to install in new build projects, or as part of ongoing during building renovation.

Our powerful portfolio of brands:

CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACERnVent.com

Ireland Tel 1800 654 241 Fax 1800 654 240 salesIe@nvent.com

United Kingdom Tel 0800 969 013 Fax 0800 968 624 salesthermaluk@nvent.com

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.

Raychem-DS-EU0079-GM2XT-EN-1805

TECHNICAL DATA

Product description and order reference GM-2XT (PCN 092961-000) GM-2X (PCN 446105-000)

Power Output (nominal) 36 W/m @ 0°C in ice water

Supply Voltage 230 Vac

Max circuit length 80 m

Minimum Installation Temperature –18°C

Maximum exposure temperature 65°C cont. power on (85°C intermittent)

Product dimensions 13,7 mm x 6,2 mm

Conductors 1,2 mm² nickel-plated copper

Braid/Outer Jacket Tinned-copper braid with fluoropolymer (-XT) or modified polyolefin (-X) outer jacket

Weight ~130 g/m

Minimum Bending Radius 16 mm

Connection Kits RAYCHEM RayClic or heat shrink connection kits must be used with GM2-X(T) heating cables.

APPROVALS

SEMCOVDE Reg. Nr. 1885

The GM-2X(T) heating cables are VDE and SEMKO Certified, and approved only when used with the appropriate agency-approved Tyco Thermal Controls connection kits and accessories.

PRODUCT REFERENCES

Voltage Max. circuit length

Circuit breaker size 6 A 10 A 13 A 16 A 20 A

GM2XT and GM-2X 230 V 25 m 40 m 50 m 60 m 80 m

The subfloor should be clean, stable and rigid, without cracks or adhesion-reducing substances.

Large cracks in the subfloor should be filled prior to laying the mat.

nVent.com | 1Raychem-DS-H59999-CCB-EN-1812

CABLE COVER BRACKET

CCB

1 5/8” (41 mm)

5/16" (8 mm)

PRODUCT OVERVIEW

nVent RAYCHEM Cable Cover Bracket (CCB) is designed to mount on the roof or gutters and embeds one or two runs of self-regulating heating cable. It is used to enhance the heat transfer from the heating cable to the snow and create larger drain paths.

CCB provides:

• Long term roof deicing solution by mechanically protecting the heating cable

• Aesthetically pleasing solution by concealing the heating cable

• High performance and reliable solution for snow melt in gutters or other roof sections

CATALOG NUMBER

CCB-CU, Cable Cover Bracket, copper

CCB-AL, Cable Cover Bracket, aluminum

MATERIALS OF CONSTRUCTION

CCB Aluminum (available in 30 colors. Please refer to RIM color guide H59379)

Copper

Custom (Corten, Zinc, Lead coated copper etc.)

ADDITIONAL MATERIALS (AS REQUIRED)

RIM Adhesive/Sealant Silicone adhesive for RIM systems

PRODUCT SPECIFICATIONS (NOMINAL)

Minimum Installation Temperature 0°F (-18°C)

Overall Dimensions Width: 1 5/8 ± 1/16 in (41 mm) Thickness: 5/16 ± 1/32 in (8 mm)

Material Thickness Aluminum: 0.040 in

Copper: 20 oz/ft2

Weight Aluminum: 170 lb/1000 ft (252 kg/km)

Copper: 310 lb/1000 ft (461 kg/km)

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.

nVent reserves the right to change specifications without notice.

Our powerful portfolio of brands:

CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACERnVent.com

Raychem-DS-H59999-CCB-EN-1812

North America Tel +1.800.545.6258 Fax +1.800.527.5703 info@nvent.com

CSA, ULI

RIGID PVC CONDUIT FITTINGS - KRALOY

ISSUE DATE:

DATE D'EMISSION: 2002 06 20

JB552 JUNCTION BOXES

SUPERCEDES:

REMPLACE: 2001 07 20

B A C

C B D

E

PRODUCT PART NOMINAL SIZE A B C

CODE NUMBER (in) (mm) (in) (mm) (in) (mm) (in) (mm)

078245 JB 552 5 129 4.680 119 5.000 127 4.485 114

PRODUCT PART NOMINAL SIZE D E

CODE NUMBER (in) (mm) (in) (mm) (in) (mm)

078245 JB 552 5 129 2.160 55 2.000 51

PRODUCT PART NOMINAL SIZE GASKET INSERT SCREW VOLUME

CODE NUMBER (in) (mm) CODE CODE CODE (cu. in) (cu. cm)

078245 JB 552 5 129 097733 072538(4) 072522 (6) 40.0 656.0

Molded with Mounting Feet

NOTES:

- Junction boxes are supplied with threaded brass inserts, screws and gasketing.

- NEMA rated 1, 2, 3, 4, 4X, 6P, 12, 13 and UL approved for use in wet locations.

CSA, ULI

RIGID PVC CONDUIT FITTINGS - KRALOY

ISSUE DATE:

DATE D'EMISSION: 2002 06 20

JB552 JUNCTION BOXES

SUPERCEDES:

REMPLACE: 2001 07 20

COVER DIMENSIONS

0.225”

0.220” 0.640”

0.250” DIA

MOLD-IN MOUNTING FEET

(6.4mm)

(5.7mm)

(16.3mm)

(5.6mm)

4.980” (127mm)

0.245”

(6 mm)

4.980”

(127mm)

RAYCHEM

WINTERGARD ROOF CLIP

nVent RAYCHEM WinterGard H913 and H914 are roof clip bracket kits that are used to secure WinterGard Wet heating cables to roofs and gutters. The clips may be attached with mechanical fasteners (screws or nails) on shake roofs or using adhesive on metal, slate or composite roofing. The H913 and H914 kits are approved for use with UL Listed and CSA Certified WinterGard Wet heating cable systems or FrostGuard pre-terminated heating cables. The H913 includes 10 roof clips and the H914 includes 50 roof clips.

FEATURES & BENEFITS

Simple to install

Maintenance free

Reliable during long life: 2 year product warranty available

SPECIFICATIONS

Anodized Aluminum

0.76 in

1.5 in

2.1 in

Material

Height

Width

Length

Catalog Number Item Name

876259-000 H913

Anodized AluminumMaterial https://raychem.nvent.com/en-us/products/thm876259-000

0.76 in

1.5 in

2.1 in

Height

Width

Length

Catalog Number Item Name

194719-000 H914

North America Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nvent.com

Europe, Middle East, Africa Tel +32.16.213.511 Fax +32.16.213.604 thermal.info@nvent.com

Asia Pacific Tel +86.21.2412.1688 Fax +86.21.5426.3167 cn.thermal.info@nvent.com

Latin America Tel +1.713.868.4800 Fax +1.713.868.2333 thermal.info@nvent.com

© 2021 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.

nVent reserves the right to change specifications without notice.

Our powerful portfolio of brands:

nVent.com CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACER https://raychem.nvent.com/en-us/products/thm194719-000

Technical Data Sheet Neutral Cure Silicone CSI Section No. 07 92 13

Product Description DuraSil is a neutral cure (RTV) silicone, adhesive sealant, designed for application on dissimilar materials such as glass, aluminum, steel, copper, masonry and many engineering plastics such as polycarbonate, vinyl (PVC), fiberglass (FRP), and acrylic. DuraSil is also well suited for difficult to bond surfaces such as Kynar 500® PVDF and Tedlar® PVF.

Applicable Performance Standards

• ASTM C920, Type S, Grade NS, Class 50, Uses NT, T2, M, G, A & O

• Federal Specification TT-S-00230-C Type II, Class A

• Corps of Engineers CRD-C-541, Type II, Class A

• Canadian Standards Board CAN 19, 13-M82

Regulatory Compliance

• Conforms to OTC Rule for Sealants

• Meets requirements of California Regs:

CARB, BAAQMD and SCAQMD

• This product does not contain cancer causing chemicals listed in California Proposition 65

• Conforms to USDA Requirements for Non-food Contact

Green Standards:

• LEED 2.2 for New Construction and Major Renovations:

Low Emitting Materials (Section 4.1) 1 Point

• NAHB Model Green Home Building Guidelines:

5 Global Impact Points

• VOC Content: less than 30 grams / liter ASTM D2369 EPA Method 24 (tested at 240°F / 115°C)

Last Revision: 07/16/20

Advantages

• Neutral Cure. Will not promote corrosion of metal

• Bonds to Kynar 500® PVDF coated metal

• Solvent free, 100% solids will not shrink

• Non-slump, applies vertically and overhead

• 10 minute skin over

• Color stability, will not suntan

• +/- 50% joint movement

• Made in the USA - ISO 9001:2015 certified

Packaging

• 10.1 oz (300 ml) 24 cartridges/carton, 45 cartons/pallet

• 2 and 5 gallon pails or 50 gallon drums available by special order

DuraSil’s low odor, non corrosive, and neutral cure chemistry will not damage unprotected metals. DuraSil is highly elastic and low modulus with mechanical properties capable of low temperature flexibility and 50% joint movement. DuraSil is recommended for metal architecture, windows and doors, curtain wall construction, and glass block.

DuraSil develops properties rapidly and is effective in many industrial applications where strength, elasticity, adhesion, and speed of set are required.

Document No. DS1211 Chem Link Construction & Maintenance Telephone: 800-826-1681 Fax: 269-679-4448 353 E. Lyons Street Schoolcraft, MI 49087 www.chemlink.com

* Color matching is available in batch quantity only

Colors White, Gray, Black & Translucent

DuraSilDuraSil®®

High Performance Adhesive/Sealant

Joint Preparation Joint surfaces should be clean, dry and free from all contamination including: dirt, oils, grease, tar, wax, rust and any other substance that may inhibit the sealant’s performance.

Joint Design Install all joint applications per ASTM and SWRI recommendations and guidelines. Joints shall be designed with a depth to width ratio of 1:2 (joint depth one-half the width). Control the depth of the sealant by using a polyethylene backer rod that is 25% larger than the joint opening at standard temperature. To prevent three-point adhesion use a backer rod or bond breaker tape to ensure proper joint movement and a long lasting weatherproof seal. Where the joint configuration will not permit a backer rod, CHEM LINK recommends that an alternative bond breaker be used.

Joint Width Inches (mm)

Joint Depth Inches (mm)

1/4 - 1/2 (6-13) 1/4 (6)

1/2 - 3/4 (13-19) 1/4 - 3/8 (6-10)

3/4 - 1 (19-25) 3/8 - 1/2 (10-13)

1 - 2 (25-50) 1/2 (13)

Typical Physical Properties

Gun Grade Zero Slump

Viscosity 550,000 cp +/- 150,000 cp

Brookfield RVF TF Spindle, 4 RPM, 73°F (23°C)

Density 8.3 lbs per gallon ASTM D1475

Tack Free Time 10 min +/- 5 min 45 +/- 5 % R.H.

Elongation at Break 600% ASTM D412

Hardness Shore A 10 +/-3 ASTM C661

Shear Strength 75 +/-5 psi ASTM D1002

Tensile Strength 135 psi ASTM D412

Low temp.

flex

Pass -15°F (-26°C) 1/4 inch mandrel ASTM D522

Shrinkage No visible shrinkage after 14 days

Service Temperature -80°F to 400°F (-62°C to 204°C)

*Test and evaluate to ensure adequate adhesion.

Compatible Substrates* Kynar 500® PVDF Coated Metal Tedlar® PVF

Galvanized Metal Glass

Aluminum EPS Foam

Copper Engineered Plastics, PVC

Stainless Steel Fiberglass FRP

Basic Uses

Window and door frames Siding

Metal Flashing Weather Sealing

Roofing Cove Joints

Curtain Walls Parapets

Expansion joints Transportation

CHEM LINK recommends an appropriate substrate primer to be used on high moving joints or dissimilar substrates which require increased adhesion properties.

Application Guidelines:

Glass Prior to application remove any residual contamination by mechanical abrasion, sand blasting or power washing. Remove all release agents and old caulk. Dry all visible and standing water prior to applying DuraSil.

Metal Prepare all metal to ensure maximum adhesion. Remove all rust, scale and residue by wire brushing to a bright metal sheen. Remove films, loose or inappropriate coatings and oils with an appropriate solvent such as alcohol.*

*CHEM LINK recommends that coated substrates be tested for adhesion prior to starting a project. Please contact Technical Services for specific application guidelines and recommendations.

Wood Wood should be clean, sound and dry prior to sealant application. Allow treated wood to weather for six months prior to application. Remove all coatings and paint (or test for compatibility) to ensure proper bonding. Do not use on fire retardant lumber.

Priming In most instances DuraSil will not require a primer.

However, certain applications or substrates may require a primer to ensure a long lasting bond and weatherproof seal. It is the applicator’s responsibility to determine the need for a primer. CHEM LINK recommends a primer be used for any application where prolonged immersion is anticipated.

Clean-Up Wet sealant can be removed using a solvent such as alcohol. Cured DuraSil can be removed by abrading or scraping the substrate.

Storage Store original, unopened containers in a cool, dry area.

Protect unopened containers from water, heat and direct sunlight. Elevated temperatures will reduce shelf life.

DuraSil will not freeze.

Shelf Life Twelve months from date of manufacture when stored at 70°F / 21°C with 50% relative humidity. High temperature and high relative humidity may significantly reduce shelf life.

Pails have a shelf life of six months.

Application Instructions Remove all dirt, oil, loose paint, frost and other contamination from all working surfaces with alcohol DO NOT USE petroleum solvents such as mineral spirits or xylene. Maintain DuraSil at room temperature before applying to ensure easy gunning and tooling. Test and evaluate to ensure adequate adhesion. Carefully gun the sealant with a smooth, continuous bead. If tooling is needed, do so within fifteen minutes of application.

Caution Avoid prolonged contact with skin. Uncured adhesive irritates eyes. In case of contact with eyes immediately flush with water. Call a physician. Please refer to the SDS for first aid information.

See www.chemlink.com for most current SDS .

KEEP OUT OF REACH OF CHILDREN.

Limitations

• In areas where prolonged chemical exposure is anticipated, contact Technical Services for recommendations.

• Allow treated wood to “cure” for six months prior to application per APA guidelines.

• Do not use in areas subject to continuous immersion.

• Do not store in elevated temperatures.

• Remove all coatings and sealers before application.

• Please contact customer service for application guidelines with temperatures below 32°F (0°C).

• Do not use on surfaces to be painted.

• Do not use on TPO without CHEM LINK TPO primer.

• Do not use on tub and tile applications.

• Staining may occur on limestone and porous substrates, test and evaluate before application.

All properties described in this document are derived from testing conducted in laboratory conditions. Properties and performance will vary depending on environmental conditions and application technique. Test and evaluate to determine appropriate usage.

Visit www.chemlink.com for the Safety Data Sheet, Technical Data Guides and full warranty for this product.

LIMITED WARRANTY: Chem Link warrants this product’s performance, provided it is properly stored and applied within 1 year.

If this Chem Link material is proved to be defective, return remaining product and purchase receipt for refund or replacement of product exclusive of labor or cost of labor. This is the sole and exclusive remedy for defects or failure of this product. User must read and follow the direction of the current Technical Data Guide and SDS prior to product use. User determines suitability of product for intended use and assumes all risks. Manufacturer shall not be liable for damages (including consequential or incidental damages) in excess of the purchase price, except where such exclusion or limitation is prohibited by state law.

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, WRITTEN OR ORAL, STATUTORY, EXPRESS OR IMPLIED INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE; except for the above express warranty given by manufacturer, the product is sold with all faults. Chem Link SHALL NOT BE RESPONSIBLE FOR THE USE OF THIS PRODUCT IN A MANNER TO INFRINGE ON ANY PATENT OR ANY OTHER INTELLECTUAL PROPERTY RIGHTS HELD BY OTHERS. This warranty gives you specific legal rights, and you may also have other rights in the U.S. which vary from state to state. For warranty claim information, call 800-826-1681.

Downspout Hanger

ETI-DS-H58112-APS4C-EN-1812 nVent.com | 1

SNOW MELTING AND GUTTER DE-ICING CONTROLLER WITH

GROUND-FAULT PROTECTION

2.125 in (54mm)

2.125 in (54mm)

2.3125 in (59mm)

3 x 3/4 in (21mm) Conduit Entry

11.500 in (292mm)

9.125 in (232mm)

6.562 in (167mm)

1.3125 in (33mm)

PRODUCT OVERVIEW

The ETI® APS–4C snow melting and gutter de-icing controller with ground-fault protection, when used with one or more compatible sensors, automatically controls surface snow melting and roof and gutter de-icing heating cables for minimum energy costs. Applications include pavement, sidewalk, loading dock, roof, gutter, and down spout snow/ ice melting in commercial and industrial environments.

The adjustable hold-on timer continues heater operation for up to 10 hours after snow stops to ensure complete melting.

The optional RCU–4 Remote Control Unit can be located where system operation can be conveniently observed. It duplicates many of the APS–4C front panel functions.

The APS–4C provides advanced patented and patent pending ground-fault equipment protection (GFEP) as required by the national electrical codes. The GFEP automatically tests itself every time the contactors operate and once every 24 hours. The trip current can be set at 60 or 120 mA via a DIP an internal switch or retained at the 30 mA default value. As an aid to troubleshooting heating cable ground faults, the APS–4C provides an output that can indicate the ground current on a service person’s portable DVM.

The calibrated 40°F to 90°F (4°C to 32°C) high limit thermostat prevents excessive temperatures when using constant wattage and MI heating cables. It also permits safe testing at outdoor temperatures too high for continuous heater operation. The temperature sensor is included.

The APS–4C provides a complete interface for use in environments supervised by an energy management computer (EMC). This feature can also be used for general purpose remote control and annunciation.

All sensor and communications wiring is NEC Class 2. This simplifies installation while enhancing fire and shock safety.

Multiple sensors provide superior performance by better matching the controller to site performance requirements.

The APS–4C can interface up to six sensors.

The APS–4C is an exceptionally capable surface snow melting and roof and gutter de-icing controller. For complete information describing its application, installation and features, please contact your nVent representative or visit our web site at nVent.com.

APS-4C

nVent.com | 2ETI-DS-H58112-APS4C-EN-1812

GENERAL

Area of use Nonhazardous locations

Approvals

109R

Type 873 Temperature Regulating Equipment

ENCLOSURE

Protection NEMA 3R

Cover attachment Hinged polycarbonate cover, lockable

Entries One 1-1/16" entry (top) for NEC Class 2 connections Two 1-11/16" entries (bottom) for supply and load power, except 277 V single phase Two 1-1/16" entries (bottom) for supply and load power, 277 V single phase only

Material Polycarbonate

Mounting Wall mounted

CONTROL

Supply voltage APS-4C-208/240 V: 208–240 V 50/60 Hz 3-phase APS-4C-277 V: 277 V 50/60 Hz single phase APS-4C-277/480 V: 277/480 V 50/60 Hz 3-phase APS-4C-600 V: 600 V 50/60 Hz 3-phase

Contact type 3 Form A

Maximum ratings Voltage: 600 V Current: 50 A except 277 V single phase, 40 A for 277 V single phase

Heater hold-on timer 0 to 10 hours; actuated by snow stopping or toggle switch

System test Switch toggles the heater contact on and off. If temperature exceeds high limit, heater cycles to prevent damage.

GROUND-FAULT EQUIPMENT PROTECTION (GFEP)

Set point 30 mA (default); 60 mA and 120 mA selectable by DIP switch

Automatic self-test Mode A: Verifies GFEP function before contactors operate Mode B: Verifies GFEP and heaters every 24 hours

Manual test/reset Toggle switch provided for this function

Maintenance facility DC output proportional to ground current provided for troubleshooting the heater system

SNOW/ICE SENSORS

Sensor input Up to 6 sensors: CIT-1, GIT-1, SIT-6E

Circuit type NEC Class 2

Lead length Up to 500 ft (152 m) using 18 AWG 3-wire jacketed cable Up to 2,000 ft (609 m) using 12 AWG 3-wire jacketed cable

HIGH LIMIT THERMOSTAT

Adjustment range 40°F to 90°F (4°C to 32°C)

Dead band 1°F (0.6°C)

Circuit type Thermistor

Sensor interface NEC Class 2

Lead length Up to 500 ft (152 m) using 18 AWG 2-wire jacketed cable Up to 1,000 ft (504 m) using 12 AWG 2-wire jacketed cable nVent.com | 3ETI-DS-H58112-APS4C-EN-1812

ENERGY MANAGEMENT COMPUTER (EMC) INTERFACE

Inputs OVERRIDE ON (10 mA dry switch contact) OVERRIDE OFF (10 mA dry switch contact)

Outputs SUPPLY (10 mA dry switch contact) SNOW (10 mA dry switch contact) HEAT (10 mA dry switch contact) HIGH TEMP (10 mA dry switch contact) REMOTE (10 mA dry switch contact)

ENVIRONMENTAL

Operating temperature –40°F to 160°F (–40°C to 71°C) Storage temperature –50°F to 180°F (–45°C to 82°C)

ORDERING DETAILS

Catalog number Part number Description

APS-4C-208/240V P000000783 APS-4C Snow melting and de-icing controller with ground-fault protection, 208-240 Vac 50/60 Hz three phase

APS-4C-277V P000000784 APS-4C Snow melting and de-icing controller with ground-fault protection, 277 Vac 50/60 Hz single phase

APS-4C-277V/480V P000000785 APS-4C Snow melting and de-icing controller with ground-fault protection, 277/480 Vac 50/60 Hz three phase

APS-4C-600V P000000786 APS-4C Snow melting and de-icing controller with ground-fault protection, 600 Vac 50/60 Hz three phase

Snow/Ice Sensors CIT-1 512289-000 CIT-1 Snow sensor

GIT-1 126795-000 GIT-1 Gutter sensor z SIT-6E P000000112 SIT-6E Pavement snow sensor

RCU-4 P000000884 RCU-4 Remote control unit

LIMITED WARRANTY

ETI’s two year limited warranty covering defects in workmanship and materials applies.

©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.

nVent reserves the right to change specifications without notice.

Our powerful portfolio of brands:

CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACERnVent.com

ETI-DS-H58112-APS4C-EN-1812

North America Tel +1.800.545.6258 Fax +1.800.527.5703 info@nvent.com

22689 rev B 05/08 (800) 234-4239 http://www.networketi.com 1 of 3Environmental Technology, Inc.

We Manage Heat ®

D

ATA

SH

EET

Modular Snow/Ice Heater Control System

MODEL SC™–40C SATELLITE CONTACTOR

DESCRIPTION

The SC–40C Satellite Contactor answers the need for cost effective modular snow melting heater control.

One or more SC–40Cs, when used with an APS–4C Control Panel acting as the master control, allow for modular snow melting system design. There is no limit to the number of SC–40Cs that can be interfaced in a single system. This approach reduces front end design, hardware and installation costs while providing a number of useful features that would be otherwise too expensive and complex to implement.

The SC–40C provides the same advanced patented and patent pending Ground Fault Equipment Protection (GFEP) as required by the USA and Canadian National Electric codes that is found on the APS–4C. Upon sensing

CL

1.3125" (33mm)

CL

2.00" (51mm)

2.00" (51mm)

11.500" (292mm)

2.3125" (59mm)

9.125" (232mm)

6.562" (167mm)

1 x 1-1/16" (27mm) Conduit Entry

2 x 1-11/16" (43mm) Conduit Entry

TEST

RESET

GFEP

TEST

FEATURES & BENEFITS

•Modularpowercontrolofautomaticsnowmeltingsystems
•Nosystemsizelimit
•Stagedheateroperationforhighpowerquality
•Energymanagementcomputer(EMC)interface
•AccommodatesMI,constantwattageandself‑limiting

heaters a ground fault condition, an SC–40C inhibits operation of its contactor until manually reset. Circuits without a ground fault continue to operate normally thus partitioning defective heaters.

The adjustable hold‑on timer can initiate heater operation on each SC–40C for up to 10 hours to ensure complete melting and to compensate for differences between zones. The optional RCU–4 Remote Control Unit can be located where system operation can be conveniently observed. It duplicates many of the controls and indicators on the SC–40C front panel.

Each SC–40C provides a complete energy management computer (EMC) interface. This feature provides remote access for advanced applications requiring remote or zone control along with remote annunciation.

Each SC–40C maintains communications to and from the APS–4C using a 3‑wire cable. Thus, the APS–4C alarms ground faults occurring anywhere in the system. The SC–40C also inserts a short time delay between the operation of each contactor thus improving power quality by limiting the inrush current. The RCU–4 Remote Control Unit supplied permits overriding zone control in applications requiring the capability.

The SC–40C is interchangeable with the earlier SC–40. For complete information describing its application, installation and features, please contact Customer Service or check on the web at www.networketi.com.

• Advanced patented and patent pending ground fault protection

•Heaterhold‑onandtestcapabilities
•C‑UL‑US
•Simpletoinstallandoperate
•Lowsystemcosts
•Minimumenergycosts

22689 rev B 05/08(800) 234-4239http://www.networketi.com2 of 3 Environmental Technology, Inc.

Model SC–40C

SPECIFICATIONS

General

Area of use Nonhazardous locations Approvals

109R

Type 873 Temperature Regulating Equipment

Enclosure

Protection NEMA3R
Cover attachment Hingedpolycarbonatecover,lockable
Entries 1×1‑1/16"entry(top)forNECClass2connections
2×1‑11/16"entries(bottom)forsupplyandloadpower,except277VACsinglephase
2×1‑1/16"entries(bottom)forsupplyandloadpower,277VACsinglephaseonly

Material Polycarbonate Mounting Wall mounted

Communications Bus Number of cascaded units Unlimited Contactor delay 5 second Bus‑wire type 3‑wire jacketed cable Circuit type NEC Class 2 Lead length Up to 500' (152m) using 18 AWG 3‑wire jacketed cable

Up to 1,000' (304m) using 12 AWG 3‑wire jacketed cable

Control Supply ETI PN 22477: 208‑240 VAC, 35 VA, three phase 50/60 Hz

ETIPN22478:277VAC,45VA,singlephase50/60Hz
ETIPN22480:277/480VAC,45VA,threephase50/60Hz
ETIPN22481:600VAC,50VA,threephase50/60Hz
LOAD ETIPN22477:208‑240VAC,50ampmax.resistive
ETIPN22478:277VAC,40ampmax.resistive
ETIPN22480:277/480VAC,50ampmax.resistive
ETIPN22481:600VAC,50ampmax.resistive

Contact type 3 Form A Maximum Ratings Voltage: 600 VAC

Current:50amps
Heaterhold‑ontimer 0 to 10 hours; actuated by toggle switch
System test Switchtogglestheheatercontactonandoff.Iftemperatureexceedshighlimit,heater

cycles to prevent damage.

Ground Fault Equipment Protection (GFEP)

Set point 30mA(default);60mAand120mAselectablebyDIPswitch
Automaticself‑test ModeA:VerifiesGFEPfunctionbeforecontactorsoperate
ModeB:VerifiesGFEPandheatersevery24hours
Manualtest/reset Toggle switch provided for this function
Maintenancefacility DCoutputproportionaltogroundcurrentprovidedfortroubleshootingtheheater

system

Snow/Ice Sensors Not Applicable

High Limit Thermostat Adjustment range 40°F to 90°F (4°C to 32°C) Dead band 1°F (0.6°C) Sensor type Thermistor network Circuit type NEC Class 2

22689 rev B 03/08 (800) 234-4239 http://www.networketi.com 3 of 3Environmental Technology, Inc.

Model SC–40C

LIMITED WARRANTY

ETI’s two year limited warranty covering defects in workmanship and materials applies. Contact Customer Service for complete warranty information.

DISCLAIMER

Environmental Technology, Inc. makes no representations or warranties, either expressed or implied, with respect to the contents of this publication or the products that it describes, and specifically disclaims any implied warranties of merchantability or fitness for any particular purpose. Environmental Technology, Inc. reserves the right to revise this publication, and to make changes and improvements to the products described in this publication, without the obligation of Environmental Technology, Inc. to notify any person or organization of such revisions, changes or improvements.

The ETI logo, We Manage Heat, APS, CIT, GIT and SIT are registered trademarks of Environmental Technology, Inc. RCU, PTS and SC are trademarks of Environmental Technology, Inc.

Copyright © 2008 Environmental Technology, Inc. All rights reserved.

Leadlength Upto500'(152m)using18AWG2‑wirejacketedcable
Upto1,000'(304m)using12AWG2‑wirejacketedcable

Energy Management Computer (EMC) Interface Inputs OVERRIDE ON (10 ma dry switch contact)

OVERRIDEOFF(10madryswitchcontact)
Outputs SUPPLY(10madryswitchcontact)

SNOW (10 ma dry switch contact)

HEAT(10madryswitchcontact)
HIGHTEMP(10madryswitchcontact)
ALARM(10madryswitchcontact)

Environmental Operating temperature –40°F to 160°F (–40°C to 71°C) Storage temperature –50°F to 180°F (–45°C to 82°C)

ORDERING INFORMATION

Order Number Description

22477 SC–40CSatelliteContactor,208‑240VAC50/60HzThreePhase
22478 SC–40CSatelliteContactor,277VAC50/60HzSinglePhase
22480 SC–40CSatelliteContactor,277/480VAC50/60HzThreePhase
22481 SC–40CSatelliteContactor,600VAC50/60HzThreePhase

Accessories 21358 RCU–4 Remote Control (Optional) 19272 High Temperature Sensor w/ 20' (6m) lead (Qty 1 included) 22690 PTS–100 Embedded Temperature Sensor (Optional)

Snow/Ice Sensors (Not Included)

10001 CIT–1AerialSnowSensor
11351 GIT–1GutterIceSensor
20756 SIT–6EPavementMountedSnow/IceSensor

Control Panels (Not Included) 22472 APS–4C Control Panel, 208‑240 VAC 50/60 Hz Three Phase

22473 APS–4C Control Panel, 277 VAC 50/60 Hz Single Phase

22475 APS–4C Control Panel, 277/480 VAC 50/60 Hz Three Phase

22476 APS–4C Control Panel, 600 VAC 50/60 Hz Three Phase nVent.com/RAYCHEM | 1RAYCHEM-DS-H60973-ETISnowOwl-EN-2012

CONNECT AND PROTECT

FEATURES & BENEFITS

• Automatic snow sensor for reduced energy consumption in surface snow melting and roof and gutter de-icing applications.

• Slim design minimizes visual impact

• Mounts on 3/4″ PVC or 1/2″ PVC with optional reducing bushing or 1/2″ NPT with included fittings

• Operates on safe low voltage power

• Wire colors match commonly available cable for easier installation

• Convenient power-on self-test to verify proper sensor operation

• Made with UV-tolerant and corrosion-resistant materials

DESCRIPTION

The Snow Owl sensor is designed to work with a controller or contactor, optimizing energy usage in heated snow/ice melting applications. Snow Owl is also an excellent solution for building automation applications.

During dry or warm weather, the system’s heaters are turned off to save energy costs. The heaters are turned on only when snow and/or ice is present, and kept on only long enough to ensure complete melting and drying.

Temperature and time parameters are preset for optimum system performance.

Typical applications include controlling snow melting systems for driveways, sidewalks, doorways, stairs, loading docks, ramps for the physically challenged and parking garages. Easy installation is another key Snow Owl feature.

Low voltage operation, up to 2,000' (609.6m) separation from the control panel, mast or roof mounting, and non-critical extension wiring are just a few of the features making this possible.

Heated Moisture Sensing Grid

1.78 [45.1 mm]

3.81 [96.7 mm]

16.0 [406.4 mm]

Windshield with Water Drain Slots

Recessed for 3/4” PVC Conduit

(1.05 ID)

Three 18 AWG Jacketed Wires

White, Black, Red

Snow Owl

Aerial general-purpose snow sensor nVent.com | 2ETI-DS-H58114-CIT1GIT1SIT6E-EN-1812 ©2020 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.

nVent reserves the right to change specifications without notice. RAYCHEM-DS-H60973-ETISnowOwl-EN-2012

Our powerful portfolio of brands:

CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACERnVent.com/RAYCHEM

North America Tel +1.800.545.6258 Fax +1.800.527.5703 thermal.info@nvent.com

SPECIFICATIONS

Input Power 24V AC 50/60Hz, 24V DC, or 24V full wave rectified AC/pulsed DC 0.2A max

Output Relay contacts: 2A max, 30V Relay contacts close when ambient temperature is at or below the set point temperature and precipitation is detected Relay contacts remain closed during pre-set delay after snow event ends Three wire connection (2 for power, 1 for relay)

Set Point Temperature 38°F

Hold-on Times Set 1 minute

Dimensions 3-3⁄4 inches tall, 1-3⁄4 inches diameter

Storage Temperature -40°C to +85°C

Can be mounted 500 feet from the controller using 22ga cable or up to 1,000 ft. using 18ga cable (Depending on load requirements)

ORDERING INFORMATION

Part Number Catalog Number Description UPC P000002358 SNOW OWL ETI Snow Owl Aerial Snow Sensor 715629420190

A

A

A A A

A

BC

bogdan babes bogdan babes Red is the new cable system A . Power connection B. Temperature sensor C. Control panel

Appendix C - Heat Cable Example.pdf
Tomah coverppg.pdf
Tomah VA R1 BOM.pdf
Tomah VA Medical Ctr notes.pdf
GM-2X datasheet.pdf
CCB datasheet.pdf
WPCK-R datasheet.pdf
JB552-K datasheet.pdf
H914 Roof Clip datasheet.pdf
Adhesive datasheet.pdf
DSH datasheet.pdf
APS-4C datasheet.pdf
SC-40C Data Sheet.pdf
WSTK datasheet.pdf
Snow Owl datasheet.pdf
Bldg Dimension for Roof
B401 Attic-Roof Layou.pdf
B402 building wall dimension
404 building walls La
B406 bldg walls Layou
B407 building walls L
408 building walls La

Blank Page

File details come from the government source that posted it. Updated .