36C25220B0003-0005000.docx
DOCX document Posted
- Solicitation number
- 36C25220B0003
About this file
This document provides details for a federal contract solicitation to replace chiller plants and air handling units at the Clement J. Zablocki VA Medical Center in Milwaukee, Wisconsin. The solicitation will require contractors to furnish all labor, materials, equipment and other items to demolish existing chillers and air handling units serving Building 43, and replace them with new rooftop air handling units, condensing units, and associated mechanical and control systems upgrades. The project cost is estimated between $1,000,000 to $2,000,000, with a 240-day period of performance. The solicitation is scheduled for posting on October 28, 2019 to FedBizOpps, with bid opening on December 4, 2019. A pre-bid conference will be held. The NAICS code is 238220 and the procurement is set aside 100% for Service-Disabled Veteran-Owned Small Businesses. The solicitation will be issued by the Department of Veterans Affairs Veterans Health Administration VISN 12.
36C25220B0003 0005 36C25220B0003 0005.docx
View the file
Other files
Show 40 more
Latest 50 of 74 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE
7.
ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF
PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE
OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO:
Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERE
D CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR
OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendmen t, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED
STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF
CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF
SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 12-05-2019 695-20-1-6908-0002 695-19-137 36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476 36C252 Department of Veterans Affairs Great Lakes Acquisition Center (GLAC) 115 S 84th Street, Suite 101 Milwaukee WI 53214-1476 To all Offerors/Bidders
36C25220B0003 10-28-2019
X X X
See continuation page for RFI responses and changes to specifications and drawings.
Continue to monitor beta.sam.gov for any and all changes to this solicitation.
Jerrod Schleis Contracting Officer
VA-VHA-SAOC-2018-406BE34
Amendment of Solicitation Amendment 0003 Solicitation 36C25220B0003 Replace Chiller Plant Building 43 Mental Health (SF1 & SF2) Project Number 695-19-137 Clement J. Zablocki VAMC, Milwaukee, WI
This Addendum consists of 1 amended specification section (24 pages), 7 amended drawings sheets, 5 basis of design cut sheets, a one-line diagram, and responses to requests for information # 69-76.
The following changes are hereby provided by amendment:
SPECIFICATIONS:
1. Specification 28 31 00 Fire Detection and Alarm
a. REMOVE Paragraph 2 from Section 1.1.C
b. REMOVE Paragraph e from Section 1.4.C
c. REMOVE Section 2.6 and MODIFY to read “2.6 VOICE COMMUNICATION SYSTEM (VCS) – NOT USED
d. MODIFY Section 2.13 Paragraph B to read “Provide to the VA, all hardware, software, programming tools, license and documentation necessary to permanently modify the fire alarm system on site. The minimum level of modification includes addition and deletion of devices, circuits, zones and changes to system description, and system operation”
e. REMOVE Part 2(B) and MODIFY to read “PART 2 (B) – PRODUCTS – NOT USED”
f. REMOVE Part 2(C) and MODIFY to read “PART 2 (B) – PRODUCTS – NOT USED”
g. MODIFY Paragraph 4.2 to read “DIGITIZED VOICE MESSAGES – NOT USED
DRAWINGS:
1. Sheet ED-100: ADD new duct detector on return ductwork and ADD note to read “INSTALL DUCT DETECTOR AND WIRING TO NEW SF-1 CONTROL PANEL.”
2. Sheet FPD-100: ADD new duct detector on return ductwork.
3. Sheet M-104: ADD new duct detector on return ductwork.
4. Sheet E-101: ADD new duct detector on return ductwork.
5. Sheet FPD-101: ADD new duct detector on return ductwork.
6. Sheet M-300: ADD new duct detector on return ductwork.
7. Sheet M-301: ADD new duct detector on return ductwork.
BASIS OF DESIGN UNIT CUT SHEETS (attached):
The cut sheets of the basis of design units referenced in questions from prospective bidders in this Amendment. NOTE: Cut sheets are provided as information only. Contractors are not required to provide the exact model or manufacturer listed as the basis of design. Bidders shall coordinate with all trades the work and materials provided will result in a complete and functional end product.
1. 43-ACCU2 BoD
2. 43-SF1 BoD
3. 43-SF2 BoD
4. Steam Coil BoD
5. Steam Humidifier BoD
BUILDING 43 ONE-LINE DIAGRAM (attached):
The 3rd party produced electrical one-line diagram of Building 43.
REQUEST FOR INFORMATION RESPONSES:
The requests for information from prospective bidders collected through date of this Amendment have been answered in the attachment. Answers resulting in changes to contract specifications, drawings, and Scope of Work are reflected above.
Q69. If an electrical one line is unavailable and JCI has not provided any information on the electrical requirements of the equipment, how can a contractor provide a price for the electrical feeders to be installed?
A69. The JCI unit identified in the drawings is the basis of design unit only. Contractors are not required to install this particular unit. The bidding contractor, electrical contractor, mechanical contractor, etc. should coordinate the work and materials provided by each trade with result in a complete and functional end product. The VA has provided a one-line diagram of Building 43.
Q70. JCI still has not provided any information on the mechanical units of the project, can the VA provide this information to assist in the completion of this bid?
A70. Mechanical unit requirements will vary based on the selected unit. The JCI unit identified in the drawings is the basis of design unit only. Contractors are not required to install this particular unit. The bidding contractor, electrical contractor, mechanical contractor, etc. should coordinate the work and materials provided by each trade with result in a complete and functional end product. The basis of design cut sheets are provided for information only.
Q71. M-400 does not contain enough information for an electrical contractor to reference the latest version of the NEC to provide pricing for the electrical feeders. Can the required electrical information for the mechanical equipment be provided? Information needed; FLA, HP and Voltage in order to design/build the electrical feeders for the VA.
a. 43-SF1, please provide FLA and HP of complete unit.
b. 43-SF2, please provide FLA and HP of complete unit.
c. Does 43-SHC1 have any power requirements?
d. Does 43-ACCU2 have any power requirements?
e. Does 43-SH1 have any power requirements?
A71.
a. 43-SF1 requirements may vary depending on the unit selected (see responses 69 & 70 above). See Amendment 05 Attachments for basis of design 43-SF1 requirements.
b. 43-SF2 requirements may vary depending on the unit selected (see responses 69 & 70 above). See Amendment 05 Attachments for basis of design 43-SF2 requirements.
c. 43-SHC1 requirements may vary depending on the unit selected (see responses 69 & 70 above). See Amendment 05 Attachments for basis of design 43-SHC1 requirements.
d. 43-ACCU2requirements may vary depending on the unit selected (see responses 69 & 70 above). See Amendment 05 Attachments for basis of design 43-ACCU2 requirements.
e. 43-SH1 requirements may vary depending on the unit selected (see responses 69 & 70 above). See Amendment 05 Attachments for basis of design 43-SH1 requirements.
Q72. There is a statement in the scope of work that requires fire alarm per NFPA. Based on the work that is on the drawings, NFPA would require duct detectors on all the HVAC units. The SF1 & SF2 control drawings M-300 and M-301 show detectors on the supply fans. Because the size of these units, NFPA also requires duct detection on the returns of these units.
A72. Duct detectors added to the return ducts of both units. See Drawing Revisions.
Q73. Are the duct detectors provided by the HVAC unit manufacturer? They are not shown on electrical drawings.
A73. Duct detectors are not provided by the HVAC unit manufacturer. New duct detectors are shown on electrical Sheets ED-100 and E-101, as well as Sheets FPD-100, M-104, FPD-101, M-300, and M-301.
Q74. If they are provided by HVAC unit manufacturer, is the fire alarm contractor required to monitor them?
A74. Duct detectors are not provided by the unit manufacturer. Duct detectors are required to be tied into the existing fire alarm system.
Q75. Will the electrical contractor know they have to install fire alarm if not shown on drawings?
A75. General Note 2 on Sheet FPD-100 and FPD-101 states the all new control devices to be tied into existing fire alarm system located in the area. Contractor is responsible for following project Specifications and NFPA 13 requirements. Coordination between trades shall be conducted to ensure the bid provides a complete and functional end product.
Q76. Section 28 31 00 Fire Detection and Alarm calls for a digitized voice system for building 43. The fire alarm system was upgraded in 2017 and is not a voice system.
A76. Digitized voice system is not required in Building 43. See Specification Revisions. Tie-in to existing system shall be compatible with existing equipment.
See attached document: S06 Amend 0005 Att. 28 31 00.
See attached document: S06 Amend 0005 Att. ED-100.
See attached document: S06 Amend 0005 Att. FPD-100.
See attached document: S06 Amend 0005 Att. M-104.
See attached document: S06 Amend 0005 Att. E-101.
See attached document: S06 Amend 0005 Att. FPD-101.
See attached document: S06 Amend 0005 Att. M-300.
See attached document: S06 Amend 0005 Att. M-301.
See attached document: S06 Amend 0005 Att. 43-ACCU2 BoD.
See attached document: S06 Amend 0005 Att. 43-SF1 BoD.
See attached document: S06 Amend 0005 Att. 43-SF2 BoD.
See attached document: S06 Amend 0005 Att. Steam Coil BoD.
See attached document: S06 Amend 0005 Att. Steam Humidifier BoD.