About this file

This document includes a bid solicitation and technical specifications for a federal construction project. The Clement J. Zablocki VA Medical Center is soliciting bids to replace chiller plants and air handling units in Building 43 at their Milwaukee, WI location under Project 695-19-137. The contractor will demolish existing chillers and air handling units, install new packaged rooftop air handling units with direct expansion cooling and steam heating coils, replace additional air handling units with a single larger unit, and upgrade controls and lighting. The project cost is estimated between $1-2 million. The solicitation is scheduled for release on FedBizOpps on October 28, 2019 with bids due on December 4, 2019. The set-aside is for 100% Service Disabled Veteran Owned Small Businesses. The technical specifications outline materials, finishes, and installation requirements for louvers, vents, and other components.

36C25220B0003 0003 S06 Amend 0003 Att. 08 90 00 Lovers and Vents.pdf

View the file

Other files

File Type Posted
36C25220B0003-0006001.pdf PDF
36C25220B0003-0006000.docx DOCX document
36C25220B0003-0005006.pdf PDF
36C25220B0003-0005003.pdf PDF
36C25220B0003-0005004.pdf PDF
36C25220B0003-0005012.pdf PDF
36C25220B0003-0005009.pdf PDF
36C25220B0003-0005008.pdf PDF
36C25220B0003-0005007.pdf PDF
36C25220B0003-0005010.pdf PDF
36C25220B0003-0005002.pdf PDF
36C25220B0003-0005011.pdf PDF
36C25220B0003-0005001.pdf PDF
36C25220B0003-0005013.pdf PDF
36C25220B0003-0005005.pdf PDF
36C25220B0003-0005000.docx DOCX document
36C25220B0003-0004002.pdf PDF
36C25220B0003-0004003.pdf PDF
36C25220B0003-0004005.pdf PDF
36C25220B0003-0004001.pdf PDF
36C25220B0003-0004000.docx DOCX document
36C25220B0003-0004004.pdf PDF
36C25220B0003-0003002.pdf PDF
36C25220B0003-0003015.pdf PDF
36C25220B0003-0003009.pdf PDF
36C25220B0003-0003004.pdf PDF
36C25220B0003-0003016.pdf PDF
36C25220B0003-0003014.pdf PDF
36C25220B0003-0003006.pdf PDF
36C25220B0003-0003003.pdf PDF
36C25220B0003-0003013.pdf PDF
36C25220B0003-0003001.pdf PDF
36C25220B0003-0003007.pdf PDF
36C25220B0003-0003005.pdf PDF
36C25220B0003-0003010.pdf PDF
36C25220B0003-0003000.docx DOCX document
36C25220B0003-0003012.pdf PDF
36C25220B0003-0003011.pdf PDF
36C25220B0003-0002001.pdf PDF
36C25220B0003-0002000.docx DOCX document
36C25220B0003-0001001.pdf PDF
36C25220B0003-0001000.docx DOCX document
36C25220B0003-0001001.pdf PDF
36C25220B0003-0001000.docx DOCX document
36C25220B0003-007.pdf PDF
36C25220B0003-008.pdf PDF
36C25220B0003-012.pdf PDF
36C25220B0003-003.pdf PDF
36C25220B0003-010.pdf PDF
36C25220B0003-006.pdf PDF
Show 40 more

Latest 50 of 74 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Milwaukee VAMC 05-15

695-19-137 Replace Chiller Plant Building 43(SF1 & SF2) Bid Documents

Milwaukee, WI 53295 9-30-2019

08 90 00 - 1

SECTION 08 90 00

LOUVERS AND VENTS

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies fixed and operable wall louvers, door louvers and wall vents.

1.2 RELATED WORK – NOT USED

1.3 SUBMITTALS:

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Shop Drawings:

1. Each type, showing material, finish, size of members, method of assembly, and installation and anchorage details.

C. Manufacturer's Literature and Data:

1. Each type of louver and vent.

D. Color samples.

1.4 APPLICABLE PUBLICATIONS:

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. The Master Painters Institute (MPI):

Approved Product List – Updated Monthly

C. ASTM International (ASTM):

A240/A240M-14...........Chromium and Chromium-Nickel Stainless Steel

Plate, Sheet, and Strip for Pressure Vessels and for General Applications

A653/A653M-13...........Steel Sheet Zinc-Coated (Galvanized) or Zinc-

Iron Alloy Coated (Galvannealed) by the Hot Dip

Process

A1008/A1008M-13.........Steel, Sheet, Carbon, Cold Rolled, Structural, and High Strength Low-Alloy with Improved

Formability

B209-14.................Aluminum and Aluminum Alloy, Sheet and Plate

B209M-14................Aluminum and Aluminum Alloy, Sheet and Plate

(Metric)

B221-14.................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes

08 90 00 - 2

B221M-13................Aluminum and Aluminum Alloy Extruded Bars, Rods, Wire, Shapes, and Tubes (Metric)

D1187/D1187M-97(R2011)..Asphalt-Base Emulsions for Use as Protective

Coatings for Metal

D. National Association of Architectural Metal Manufacturers (NAAMM):

AMP 500-06..............Metal Finishes Manual

E. National Fire Protection Association (NFPA):

90A-15..................Installation of Air Conditioning and

Ventilating Systems

G. American Architectural Manufacturers Association (AAMA):

2605-13.................High Performance Organic Coatings on

Architectural Extrusions and Panels

H. Air Movement and Control Association, Inc. (AMCA):

500-L-07................Testing Louvers

PART 2 - PRODUCTS

2.1 MATERIALS:

A. Aluminum, Extruded: ASTM B221M (B221).

B. Stainless Steel: ASTM A240/A240M, Type 302B.

C. Galvanized Steel Sheet: ASTM A653/A653M; G90 min.

D. Carbon Steel and Sheet: ASTM A1008/A1008M (interior use louvers only).

E. Aluminum, Plate and Sheet: ASTM B209M (B209); alloy 3003 or 5005 with temper as required for forming.

F. Fasteners: Fasteners for securing louvers and wall vents to adjoining construction, except as otherwise specified or indicated in construction documents, to be toggle or expansion bolts of size and type as required for each specific type of installation and service condition.

1. Where type, size, or spacing of fasteners is not shown or specified, submit shop drawings showing proposed fasteners, and method of installation.

2. Fasteners for louvers, louver frames, and wire guards to be of stainless steel or aluminum with same finish as louvers.

3. Fasteners for louvers, louver frames and wire guards within mental health areas to be non-removable/tamper-proof type.

G. Inorganic Zinc Primer: MPI No. 19.

2.2 EXTERIOR WALL LOUVERS:

A. General:

08 90 00 - 3

1. Provide fixed type louvers of size and design shown.

2. Heads, sills and jamb sections are to have formed caulking slots or be designed to retain caulking. Head sections are to have exterior drip lip, and sill sections an integral water stop.

3. Furnish louvers with sill extension or separate sill as shown.

4. Frame is to be mechanically fastened or welded construction with welds dressed smooth and flush.

B. Performance Characteristics:

1. Louvers are to bear AMCA certified rating seals for air performance and water penetration ratings.

C. Aluminum Louvers:

1. General: Frames, blades, sills and mullions (sliding interlocking type); 2 mm (0.078-inch) thick extruded 6063-T5 or –T52 aluminum.

Blades to be standard type and have reinforcing bosses.

2. Louvers, fixed: Make frame sizes 13 mm (1/2-inch) smaller than openings. Single louvers frames are not to exceed 1676 mm (66 inches) wide. When openings exceed 1676 mm (66 inches), provide twin louvers separated by mullion members.

3. Louvers are to withstand the effects or gravity loads and the following wind loads and stresses within limits and under conditions indicated without permanent deformation of louver components, noise or metal fatigue caused by louver-blade rattle or flutter, or permanent damage to fasteners and anchors.

a. Wind load acting inward or outward of not less than 30 lb. per

sq. ft.

4. Louvers, operable: Louver frame opening sizes, single louver sizes and mullion requirements are to be as specified for fixed louvers.

a. Blades: Attach blades to frame with aluminum pivot pins through nylon bearings. Fasten each blade to stainless steel operation arms that are connected to minimum 3 mm (1/8-inch) thick stainless steel operating bar arranged for simultaneous operation of blades.

D. Stainless Steel Louvers: Form stainless steel louvers using 1.6 mm

(0.063-inch) thick sheet for frames, blades, sills and mullions.

1. Provide louver with fixed 45 degree standard blades with water baffle. Make overall frame size 13 mm (1/2-inch) less than opening, unless otherwise indicated in construction documents.

08 90 00 - 4

2. Single louver sections are not to exceed 66 inches in width. For openings larger than 66 inches wide, provide multiple sections not larger than 66 inches wide separated by mullions.

E. Formed Steel Louvers: Form louvers using 0.059-inch thick sheet for frames, blades, sills and mullions.

1. Provide louver with fixed 45 degree standard blades with water baffle. Make overall frame size 1/2-inch less than opening, unless otherwise indicated in construction documents.

2. Single louver sections are not to exceed 66 inches in width. For openings larger than 66 inches wide, provide multiple sections not larger than 66 inches side separated by mullions.

2.3 CLOSURE ANGLES AND CLOSURE PLATES:

A. Fabricate from 0.078-inch thick stainless steel or aluminum.

B. Provide continuous closure angles and closure plates on inside head, jambs and sill of exterior wall louvers.

C. Secure angles and plates to louver frames with screws, and to masonry or concrete with fasteners as indicated in construction documents.

2.4 WIRE GUARDS:

A. Provide wire guards on outside of all exterior louvers, except on exhaust air louvers.

B. Fabricate frames from 0.059-inch thick stainless steel designed to retain wire mesh.

C. Wire mesh to be woven from not less than 0.05-inch diameter stainless steel wire 1/2-inch square mesh.

D. Miter corners and join by concealed corner clips or locks extending not less than 2-1/4 inches into rails and stiles. Equip wire guards over 4 feet in height with a mid-rail constructed as specified for frame components.

E. Fasten frames to outside of louvers with aluminum or stainless steel devices of same finish as louvers designed to allow removal and replacement without damage to the wire guard or the louver.

2.5 BLANK-OFF PANELS:

A. Uninsulated panels attached with clips or screws as follows: Panel finish is to be same finish applied to louvers.

1. Aluminum sheet for aluminum louvers, 0.050 inch minimum thickness.

2. Galvanized-steel sheet for galvanized-steel louvers, 0.040 inch minimum.

08 90 00 - 5

3. Stainless-steel sheet for stainless-steel louvers, not less than

0.038 inch minimum.

B. Insulated laminated panels consisting of an insulating core surfaced on back and front with metal sheets and attached to back of louver with clips on screws and gasketed or sealant sealed perimeter. Panel finish is to be same finish applied to louvers.

1. Thickness: 2 inches.

2. Aluminum sheet for aluminum louver 0.032 inch minimum.

3. Galvanized-steel sheet for galvanized-steel louver 0.028 inch minimum.

4. Stainless-steel sheet for stainless-steel louvers 0.031 inch minimum.

5. Insulating Core: Rigid, glass-fiber-board insulation.

2.6 EXTERIOR DOOR LOUVERS:

A. Fabricate of 0.063-inch thick extruded aluminum. Miter frames at corners and join by concealed corner brackets. Louvers are to be weather resistant type.

B. Equip louvers on outside with wire guards, except omit wire guards for louvers in doors located completely below enclosed areaways.

2.7 INTERIOR DOOR LOUVERS:

A. Fabricate louvers for interior doors and partitions of 0.0472-inch thick steel.

B. Make louvers sight-proof type with stationary blades.

2.8 WALL VENTS:

A. Fabricate exterior wall vents from either 0.185-inch thick aluminum plate or 1/4-inch thick cast iron, perforated in diamond lattice pattern, with not over 3/4-inch openings.

B. Vents are to have aluminum screen frame with aluminum alloy insect screening mounted on back of vent by means of 3/4-inch by 3/16-inch top and bottom bars screwed to grille.

C. Vent Frames in Masonry: Fabricate of 1-3/4 inch by 1-1/4 inch by 3/16-inch steel angles bolted with 1/4-inch diameter expansion bolts at jambs.

2.9 AIR INTAKE VENTS:

A. Fabricate exterior louvered wall ventilators for fresh air intake for air conditioning units from extruded aluminum, ASTM B221M (B221). Form

08 90 00 - 6 with integral horizontal louvers and frame, with drip extending beyond face of wall and integral water stops.

B. Provide aluminum closures where shown for inside face of dummy vents.

C. Provide 0.032-inch thick aluminum sleeves in cavity walls.

2.10 BRICK VENTS:

A. Vents are to be of size shown formed of approximately 3 mm (0.125 inch) thick cast aluminum, or 3 mm (0.118 inch) extruded aluminum.

B. Provide vents complete with aluminum screen frame with corrosion resistant insect screening mounted on back of vent.

C. Provide vents with required anchors.

2.11 FINISH:

A. In accordance with NAAMM Metal Finishes Manual: AMP 500-505

B. Aluminum Louvers, Air Intake Vents, Blank Off Panels:

1. Anodized finish

a. AA-M10C22A42, Chemically etched medium matte, with integrally colored anodic coating, Class I Architectural, 0.17 mm (0.7 mils) thick.

2. Organic Finish: AAMA 2605 (Fluorocarbon coating) with total dry film thickness of not less than 1.2 mil

C. Aluminum Wall Vents and Brick Vents: Sand blasted satin finish.

D. Stainless Steel: Mechanical finish No. 4 in accordance with NAAMM Metal

Finishes Manual.

E. Galvanized Sheet Steel: Two-coat baked-enamel or powder-coat finish consisting of prime coat and thermosetting topcoat, with a minimum dry film thickness of 2 mils.

1. Paint interior surfaces of lightproof louvers with two (2) additional finish shop coats of baked-on flat black enamel.

2. Finish painting of exposed surfaces of shop primed louvers is specified in Section 09 91 00, PAINTING.

F. Steel: Surfaces of steel work, for which no other finish is specified, are to be cleaned free from scale, rust, oil and grease, and then given a light colored prime paint after fabrication, except ferrous metals concealed in finished work. Paint all contact surfaces of assembled work (except welded contact surfaces) with an additional shop coat of similar paint.

08 90 00 - 7

2.12 PROTECTION:

A. Provide protection for aluminum against galvanic action wherever dissimilar materials are in contact, by painting the contact surfaces of the dissimilar material with a heavy coat of bituminous coating

(complete coverage), or by separating the contact surfaces with a performed synthetic rubber tape having pressure sensitive adhesive coating on one side.

B. Isolate the aluminum from plaster, concrete and masonry by coating aluminum with zinc-chromate primer.

C. Protect finished surfaces from damage during fabrication, erection, and after completion of the work. Strippable plastic coating on finish is not approved.

PART 3 - EXECUTION

3.1 INSTALLATION:

A. Set work accurately, in alignment and where indicated in construction documents. Install plumb, level, free of rack and twist, and set parallel or perpendicular as required to line and plane of surface.

B. Furnish setting drawings and instructions for installation of anchors and for the positioning of items having anchors to be built into masonry construction. Provide temporary bracing for such items until masonry is set.

C. Provide anchoring devices and fasteners as shown and as necessary for securing louvers to building construction as specified. Power actuated drive pins may be used, except for removal items and where members would be deformed or substrate damaged by their use.

D. Set wall louvers in masonry walls during progress of the work. If wall louvers are not delivered to job in time for installation in prepared openings, make provision for later installation. Set in cast-in-place concrete in prepared openings.

3.2 CLEANING AND ADJUSTING:

A. After installation, all exposed prefinished and plated items and all items fabricated from stainless steel and aluminum are to be cleaned as recommended by the manufacturer and protected from damage until completion of the project.

B. All movable parts, including hardware, are to be cleaned and adjusted to operate as designed without binding or deformation of the members, so as to be centered in the opening of frame, and where applicable, to

08 90 00 - 8 have all contact surfaces fit tight and even without forcing or warping the components.

C. Restore louvers and vents damaged during installation and construction so no evidence remains of corrective work. If results of restoration are unsuccessful, as determined by Contracting Officer

Representative (COR) damaged units and replace with new units.

- - - E N D - - -

File details come from the government source that posted it. Updated .