36C25218B0884-007.pdf
PDF 5 MB Posted
- Attached to
- Food and Nutrition Site Preparation, 537-18-145
- Solicitation number
- 36C25218B0884
About this file
36C25218B0884 Exhibit 6.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25218C0211-000.docx | DOCX document | |
| 36C25218B0884-009.pdf | ||
| 36C25218B0884-005.pdf | ||
| 36C25218B0884-001.docx | DOCX document | |
| 36C25218B0884-008.pdf | ||
| 36C25218B0884-002.docx | DOCX document | |
| 36C25218B0884-006.pdf | ||
| 36C25218B0884-004.pdf | ||
| 36C25218B0884-003.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Item # _____________________________________
Quantity ___________________________________
C.S.I. Section 11400
F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher Page 1 of 12
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER
FLIGHT-TYPE DISHWASHER701 S Ridge Avenue, Troy, OH 45374 1-888-4HOBART • www.hobartcorp.com
FT
1000 E
N E
R G
Y R
E C
O V
E R
Y W
IT
H
B
LO
W E
R D
R Y
E R
FLIG
H
T -T
Y P
E D
IS
H
W A
S H
E R
STANDARD FEATURES
■ Pumped rinse system (pressure gauge not required)
■ Water usage 58 gph
■ Digital controls with machine diagnostics
■ Low temperature alert
■ Single point vent location
■ 31" access on prewash, power wash and power rinse chambers; 20" access on dual rinse and ASR chambers
■ Start and stop switches at both ends
■ Doors open indicator
■ Drains open indicator
■ Door interlocks
■ 31⁄2 H.P. prewash, 5 H.P. power wash and power rinse pump motors, all TEFC
■ Capless Auto Clean wash arms
■ Easy to remove stainless steel scrap pans and baskets
■ 30" wide conveyor belt
■ Dual Rinse
■ Automatic Soil Removal system (ASR)
■ Auto Clean
■ Auto Delime
■ Energy Recovery
■ Front and rear panels
■ Variable speed conveyor
DIRECTION OF OPERATION
❑ Right to Left
❑ Left to Right
VOLTAGE
❑ 208/60/3
❑ 240/60/3
❑ 480/60/3
❑ Other voltages available – consult factory
MODEL
❑ FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher
OPTIONS AT EXTRA COST
❑ Electric Tank Heat
❑ Steam Tank Heat
❑ Booster Heater
| ❑ Electric |
| ❑ Steam |
❑ Blower Dryer
| ❑ Electric |
| ❑ Steam |
❑ 6" higher than standard chamber
❑ Multiple conveyor choices
❑ Circuit breakers
❑ Security package
❑ Other options available, consult factory
ACCESSORIES
❑ Flanged feet
❑ Water hammer arrestor/PRV (installed by others)
❑ Drain water tempering kit (installed by others)
❑ Vent connection kit
Specifications, Details and Dimensions on Inside and Back.
• LA Research Report M660004
• Complies with EPA Reduction of Lead in Drinking
Water Act 2014
• Meets requirements of ASSE Standard No. 1004
Hobart FT1000‐DRYYES Item #1
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 1
701 S Ridge Avenue, Troy, OH 45374 1-888-4HOBART • www.hobartcorp.com
Page 2 of 12 F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher
DESIGN: Fully automatic, flight-type dish machine consisting of a load section with Automatic Soil Removal system, power recirculating prewash, power wash, power rinse and dual rinse/final rinse section.
Included with each machine will be flexible plastic strip curtains to control overspray.
CONSTRUCTION: Stainless steel tank and chambers with No. 3 polish on appearance surfaces. Frame, legs and feet to be constructed of stainless steel.
Inspection doors to be chamber width.
PUMPS: Recirculating stainless steel pumps with stainless steel impellers. Pump housing has easy to remove coverplate for access to impeller. Wash pumps are self-draining.
MOTORS: Totally enclosed fan cooled (TEFC) design with overload protection. Pump motors to be 31⁄2 H.P. for prewash, 5 H.P. for power wash and power rinse, and conveyor motor to be 1⁄3 H.P. Available in electrical specifications of 208/60/3, 240/60/3 and 480/60/3.
CONTROLS: A stainless steel control center with electronic digital controls mounted at eye level.
Power “On/Off” and “Start/Stop” switches integrated into keypad. Digital display indicates door(s) open, low temperature alert, tanks/final rinse temperatures, Auto Clean and Auto Delime instructions and notifica-tions, and other pertinent operating data. Additional “Start/Stop” switches are located at each end of machine. Conveyor speed button included on the control center to provide for the adjustable speed conveyor.
FLIGHT-TYPE CONVEYOR: Stainless steel side links, tie rods and conveyor tracks. Injection molded, resilient Duraflex flight links.
VENT: Indirect vent connection with integral powered fan.
AUTOMATIC SOIL REMOVAL SYSTEM (ASR):
Two foot section with specialized soil removal wash arms which removes food soil from the ware before it reaches the prewash tank. System will pump food soil from the ASR tank into an external collector located under the load section, minimizing the need to pre-scrap dishes and reducing detergent consump-tion. Operator can easily remove and clean external collector without interruption of machine operation.
RECIRCULATING PREWASH SECTION: Prewash compartment is fitted with upper and lower wash arms. Large removable one piece perforated stainless steel screen sloped downward to deep stainless steel scrap basket.
TANK HEAT: Power wash, power rinse and dual rinse tank water temperatures are thermostatically controlled. Low water protection is provided. Specify either electric or steam heat.
FINAL RINSE: Easily removed final rinse arms.
ENERGY RECOVERY: Energy Recovery system operates with a cold water line, capturing energy from exhaust air, and using it to elevate the temperature of the water entering the booster heater. The result is savings – both in hot water and in energy.
CONVEYOR DRIVE UNIT: Powered by a 1⁄3 H.P.
motor. Trip mechanism provided on unload section.
Jam protection is provided by load sensing switch at drive platform. Conveyor speed adjustment of 4.0 feet per minute to 8.5 feet per minute is provided on the digital display keypad.
DRAINS: Manual, hand-operated, located at each tank. One manual and automatic master drain to be used for Auto Clean and Auto Delime.
BLOWER DRYER: Includes (2) 2 H.P. fan motors with sealed ball bearings and overload protection.
Available in electric or steam heat.
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER
FLIGHT-TYPE DISHWASHER
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 2
F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher Page 3 of 12
No other control system allows easier monitoring.
The digital controls are placed in a convenient panel that lets operators verify proper operation and temperatures at a glance. Digital display indicates the unit is on, and confirms that the doors are closed. Automatic door interlocks prevent the pump and conveyor from operating if the doors are open.
Easy-to-read digital display indicates accurate tem-peratures of the 150°F wash, 160°F power rinse, 160°F dual rinse and 180°F final rinse — critical for proper HACCP system record-keeping.
Stainless steel pump is built for long life.
The stainless steel pump housing and impeller offer greater durability and long life. The pump motor is totally enclosed and fan cooled (TEFC) to protect it from water spray during dishroom clean-up.
Scrap baskets capture food particles and are easy to clean.
The sloped screens that carry scraps to the scrap baskets are steeper, so less soil gets into the tanks. The basket opening is larger for easy cleaning and basket handles have been designed for easy lift-out access.
The load section also features a removable scrap basket which contains soil that is pumped from the ASR section. All scrap baskets and strainers are stainless steel for strength and durability.
The FT1000 Series saves water and energy.
The unit has the lowest water and energy consumption in the industry, yet provides effective cleaning and sanitizing that meets NSF International requirements.
This is achieved through a carefully balanced ratio of water flow to pressure.
Insulated doors and thermal layered curtains also reduce heat loss. The unit’s 58 gallons per hour rinse flow rate saves both water and the energy to heat it.
Variable speed conveyor offers increased throughput.
The conveyor on the FT1000 Series is wider so it can handle more ware.
Result: more volume and versatility, quicker work. Its speed is easily adjustable for the type of ware, soiled condition, or workforce requirements. It runs at 4.0 -
8.5 feet per minute.
Energy Recovery system reclaims heat for energy.
The Energy Recovery system’s heat exchanger captures escaping heat and steam from the exhaust air in the dish machine, and uses it to preheat the incoming cold water supply to 120°F before it enters the booster heater.
In addition to energy savings, the Energy Recovery system provides a viable use for this otherwise exhausted heat.
Self-draining wash pumps help keep water clean.
Pumps are self-draining when the machine is shut down, so there is no residual water left in the pumps.
Installation is quick and easy with modular design, minimal wiring connections, and single point vent.
Modular design means the FT1000 installs quickly and reliably. The control panel is already in place, premounted to the dual rinse/final rinse section.
Wiring connections are minimal, and there is only a single vent, saving time and expense. The control box uses a “single plane” circuitry design for easy accessibility during installation and service.
The FT1000 is ready to run quickly.
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER
FLIGHT-TYPE DISHWASHER
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 3
Page 4 of 12 F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher
22" HIGH X 29-13/16"
WIDE OPENING WILL
HANDLE 18" X 26" BUN PANS
NOTE: CLEARANCE FROM WALL
24" RECOMMENDED, 6" MINIMUM
WITH DETERGENT DISPENSER
ON THE TOP
44 13/16" SEE NOTE (a)
FLOOR LINE
35"
NOTE: STRAINER PANS
REQUIRE 35" TO
BE REMOVED. EXTRA
CLEARANCE SHOULD BE
PROVIDED.
40 3/8"
NOTE: REFER TO LATEST
EDITION OF NATIONAL
ELECTRICAL CODE AND
LOCAL BUILDING CODES
FOR PROPER CLEARANCE
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
ELECTRIC L-R
P2
V1
P3
V1
E1
E2
E3
E4
P1
P1 P2
P3
E1E2E3
P3
E6E7E8E9
E4E5
E9
E8
E7
E6
E5
18 3/4"
37 1/2"
55 11/16"
63 3/8"
11 13/16"
9 15/16"
23 3/4"
60" 52"
44 9/16"
160 1/16"
DIRECTION OF OPERATION
ASR
BLOWER/
DRYER
6"
36 1/2"
62 3/4"
36 1/4"
3"
35 7/16" 35 7/16" 35 7/16" 25 9/16"
5 3/4"
23 3/4"
6" AIR
GAP
FLOOR LINE
7 3/16"3 15/16"
UNLOAD "C"
OVER FRAME "A"
43 5/16"
25 9/16"
LOAD "B" 8' 7/16"
81 7/8"
V1
EXHAUST HOOD
SUPPLIED BY
OTHERS
POWER
WASH
PRE-
WASH
POWER
RINSE
AUX
RNS
FNL
RNS
UNLOAD
END
LOAD
END
89 3/8" SEE NOTE (e)
MODEL NO. "A" "B" "C"
NOTE: OVERALL LENGTH OF MACHINE IS DIMENSION "A" + 11 13/16"
7' 6-1/2" 7' 6-1/2" 7' 6-1/2" 9' 2-1/4" 9' 2-1/4" 9' 2-1/4"
11' 1-7/8" 11' 1-7/8" 11' 1-7/8" 14' 9-3/16" 14' 9-3/16" 14' 9-3/16" 16' 8-3/4" 16' 8-3/4" 16' 8-3/4"
23' 3-1/2" 24' 3-1/4" 25' 3-3/32" 24' 11-1/4" 25' 11" 26' 10-27/32" 26' 10-7/8" 27' 10-5/8" 28' 10-15/32" 30' 6-3/16" 31' 5-15/16" 32' 5-25/32" 32' 5-3/4" 33' 5-1/2" 34' 5-11/32"
7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32"
FT1023 (7.5'-8'-7.5')
FT1024 (8.5'-8'-7.5')
FT1025 (9.5'-8'-7.5')
FT1025 (7.5'-8'-9')
FT1026 (8.5'-8'-9')
FT1027 (9.5'-8'-9')
FT1027 (7.5'-8'-11')
FT1028 (8.5'-8'-11')
FT1029 (9.5'-8'-11')
FT1030 (7.5'-8'-15')
FT1031 (8.5'-8'-15')
FT1032 (9.5'-8'-15')
FT1032 (7.5'-8'-17')
FT1033 (8.5'-8'-17')
FT1034 (9.5'-8'-17')
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 4
F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher Page 5 of 12
SERVICE CONNECTION W/O CIRCUIT BREAKERS
(5) SERVICE CONNECTIONS AS SHOWN BELOW
ELECTRIC TANK HEAT, DUAL RINSE 9 KW,
BLOWER DRYER HEAT 7 KW & BLOWERS
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 70 70 240/60/3 70 70 480/60/3 35 35
53.1 50.0 25.0
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
ELECTRIC L-R
GENERAL NOTES:
(a) THE CONTROL BOX IS ATTACHED TO THE CENTER SECTION AND IS
ROTATED 90 DEGREES FOR SHIPPING.
AFF = ABOVE FINISHED FLOOR
ALL DIMENSIONS TAKEN FROM THE FLOOR LINE MAY INCREASE 3-1/4"
WITH LEG ADJUSTMENT.
FOR CONVENIENCE WHEN CLEANING, CUSTOMER SHOULD INSTALL
WATER TAP NEAR MACHINE WITH 30 FT. OF HEAVY DUTY HOSE WITH
SQUEEZE VALVE.
THIS DRAWING IS SUPPLIED AS A REFERENCE FOR CONNECTION
INFORMATION ONLY. IT WILL NOT BE UTILIZED FOR MANUFACTURING
OF UNIT.
ELECTRICAL WARNING:
SERVICE WIRE TEMPERATURE RATING: 90C.
PLUMBING NOTES:
RECOMMENDED WATER HARDNESS TO BE 3 GRAINS OR LESS PER
GALLON FOR BEST RESULTS.
(b) RECOMMENDED BUILDING FLOWING HOT WATER PRESSURE TO THE
DISHWASHER IS 40-45 PSI.
(c) RECOMMENDED BUILDING FLOWING COLD WATER PRESSURE TO
THE DISHWASHER IS 30-35 PSI. IF COLD WATER IS LESS THAN 55°F
CONTACT SALES ENGINEERING.
(d) WATER HAMMER ARRESTOR (MEETING ASSE-1010 STANDARD OR
EQUIVALENT) TO BE SUPPLIED (BY OTHERS) IN HOT AND COLD
WATER SUPPLY LINES AT SERVICE CONNECTION.
VENTILATION NOTES:
(e) THE VENT STACK AND ITS ENCLOSURE CAN BE TEMPORARILY REMOVED
FROM THE ENERGY RECOVERY UNIT TO YIELD 81-7/8" CLEARANCE
FOR DOORWAYS.
ELECTRICAL CONNECTIONS
COMMON ON ALL MODELS:
E1 ELECTRIC CONNECTION, DETERGENT AND RINSE FEEDERS
(MACHINE SERVICE VOLTAGE), 1/2" CONDUIT.
79-1/8" AFF
E2 ELECTRIC CONNECTION, VENT FAN CONTROL.
(SWITCH CONTACTS) 1/2" CONDUIT. 79-1/8" AFF
ELECTRICAL CONNECTIONS
W/O CIRCUIT BREAKERS:
E3 ELECTRIC CONNECTION, MOTORS & CONTROLS,
1" CONDUIT. 79-1/8" AFF
E4 ELECTRIC TANK HEAT CONNECTION, POWER RINSE TANK, 20KW.
1" CONDUIT. 79-1/8" AFF
E5 ELECTRIC TANK HEAT CONNECTION, WASH TANK, 22KW.
1" CONDUIT. 79-1/8" AFF
E6 ELECTRIC TANK HEAT CONNECTION, DUAL RINSE TANK, 9KW.
BLOWER DRYER HEAT, 7KW & BLOWERS.
1" CONDUIT. 79-1/8" AFF
E7 ELECTRIC CONNECTION, BOOSTER, 18KW.
1" CONDUIT. 79-1/8" AFF
ELECTRICAL CONNECTIONS
WITH CIRCUIT BREAKERS:
E8 ELECTRIC CONNECTION, MOTORS, CONTROLS, POWER RINSE HEAT,
BOOSTER HEAT (WHEN CIRCUIT BREAKER OPTION IS SPECIFIED).
(TB1) 2" CONDUIT, 79-1/8" AFF
E9 ELECTRIC CONNECTION, WASH HEAT, DUAL RINSE HEAT,
BLOWER DRYER HEAT & BLOWERS (TB2).
2" CONDUIT, 79-1/8" AFF
PLUMBING CONNECTIONS:
P1 COMMON HOT WATER CONNECTION (AUTOMATIC FILL) 110°F WATER
MINIMUM, 1" FPT, 5-1/2" AFF see notes (b) AND (d).
P2 COMMON COLD WATER CONNECTION, 55°F WATER MINIMUM,
1" FPT, 5-1/2" AFF see notes (c) and (d).
P3 COMMON DRAIN CONNECTION.
TWO CONNECTION LOCATIONS; MAY BE DRAINED TO EITHER END
OF UNIT, PLUG OPPOSITE END.
2" FPT. 7" AFF
VENTILATION REQUIREMENTS:
V1 MINIMUM OF 24" SQUARE VENT HOOD WITH 6 INCH AIR GAP
CAPABLE OF PROVIDING 750 CFM EXHAUST AT STANDARD AIR
CONDITIONS (VENT HOOD SUPPLIED AND INSTALLED BY OTHERS).
BACK DRAFT PREVENTER REQUIRED (SUPPLIED AND INSTALLED
BY OTHERS).
95-3/8" AFF
MODEL:
FT1000
ENERGY RECOVERY
W/BLOWER DRYER
ELECTRIC
L-R OPERATION
00-949507
REV A2
SERVICE CONNECTION WITH CIRCUIT BREAKERS
(2) SERVICE CONNECTIONS AS SHOWN BELOW
MOTORS,CONTROLS,POWER RINSE & BOOSTER HEAT (TB1)
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 200 200 240/60/3 200 200 480/60/3 125 125
161.3 156.0 86.5
WASH, DUAL RINSE HEAT, B/D HEAT & BLOWERS (TB2)
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICE
208/60/3 119.1 150 150 240/60/3 113.0 150 150 480/60/3 56.5 70 70
ELECTRIC TANK HEAT, POWER RINSE
(1) 20 KW CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
208/60/3 60.0 80 80 240/60/3 57.3 80 80 480/60/3 28.6 40 40
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
ELECTRIC TANK HEAT, WASH
(1) 22 KW CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 66.0 80 80 240/60/3 63.0 80 80 480/60/3 31.5 45 45
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 54.0 70 70 240/60/3 51.5 70 70 480/60/3 25.8 35 35
ELECTRIC BOOSTER
(1) 18 KW CONNECTION AS SHOWN BELOW
Electrical and grounding connections must comply with the applicable portions of the National Electrical Code and/or other local electrical codes.
Plumbing connections must comply with applicable sanitary, safety and plumbing codes. Drain and fill line configurations vary, some methods are shown on this drawing.
Pressure gauge not required on pumped rinse machines.
MOTORS AND CONTROLS
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICE
208-240/60/3 47.2 60 60 480/60/3 32.1 40 40
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 5
Page 6 of 12 F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
ELECTRIC R-L
MODEL NO. "A" "B" "C"
NOTE: OVERALL LENGTH OF MACHINE IS DIMENSION "A" + 11 13/16"
7' 6-1/2" 7' 6-1/2" 7' 6-1/2" 9' 2-1/4" 9' 2-1/4" 9' 2-1/4"
11' 1-7/8" 11' 1-7/8" 11' 1-7/8" 14' 9-3/16" 14' 9-3/16" 14' 9-3/16" 16' 8-3/4" 16' 8-3/4" 16' 8-3/4"
23' 3-1/2" 24' 3-1/4" 25' 3-3/32" 24' 11-1/4" 25' 11" 26' 10-27/32" 26' 10-7/8" 27' 10-5/8" 28' 10-15/32" 30' 6-3/16" 31' 5-15/16" 32' 5-25/32" 32' 5-3/4" 33' 5-1/2" 34' 5-11/32"
7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32"
FT1023 (7.5'-8'-7.5')
FT1024 (8.5'-8'-7.5')
FT1025 (9.5'-8'-7.5')
FT1025 (7.5'-8'-9')
FT1026 (8.5'-8'-9')
FT1027 (9.5'-8'-9')
FT1027 (7.5'-8'-11')
FT1028 (8.5'-8'-11')
FT1029 (9.5'-8'-11')
FT1030 (7.5'-8'-15')
FT1031 (8.5'-8'-15')
FT1032 (9.5'-8'-15')
FT1032 (7.5'-8'-17')
FT1033 (8.5'-8'-17')
FT1034 (9.5'-8'-17')
DIRECTION OF OPERATION
ASR
BLOWER/
DRYER
6"
36 1/2"36 1/4"
3"
35 7/16"35 7/16"35 7/16"25 9/16"
5 3/4"
23 3/4"
6" AIR
GAP
FLOOR LINE
43 5/16"
25 9/16"
7 7/8" OVER FRAME "A" 3 15/16"
UNLOAD "C" 8' 7/16" LOAD "B"
62 3/4"
81 7/8"
V1
EXHAUST HOOD
SUPPLIED BY
OTHERS
89 3/8" SEE NOTE (e)
UNLOAD
END
LOAD
END
POWER
WASH
PRE-
WASH
POWER
RINSE
FNL
RNS
AUX
RNS
P2
V1
P3
V1
E1
E2
E3
P1
P1 P2
P3
E1 E2 E3
P3
E6 E7 E8 E9
E4 E5
E9
E8
E7
E6
E5
E4
18 3/4"
37 1/2"
55 11/16"
63 3/8"
11 13/16"
9 15/16"
23 3/4"
60" 52" 44 9/16"
160 1/16"
22" HIGH X 29-13/16"
WIDE OPENING WILL
HANDLE 18" X 26" BUN PANS
NOTE: CLEARANCE FROM WALL
24" RECOMMENDED, 6" MINIMUM
WITH DETERGENT DISPENSER
ON THE TOP
FLOOR LINE 44 13/16"
SEE NOTE (a)
35"
40 3/8"
NOTE: REFER TO LATEST
EDITION OF NATIONAL
ELECTRICAL CODE AND
LOCAL BUILDING CODES
FOR PROPER CLEARANCE
NOTE: STRAINER PANS
REQUIRE 35" TO
BE REMOVED. EXTRA
CLEARANCE SHOULD BE
PROVIDED.
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 6
F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher Page 7 of 12
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
ELECTRIC R-L
SERVICE CONNECTION W/O CIRCUIT BREAKERS
(5) SERVICE CONNECTIONS AS SHOWN BELOW
ELECTRIC TANK HEAT, DUAL RINSE 9 KW,
BLOWER DRYER HEAT 7 KW & BLOWERS
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 70 70 240/60/3 70 70 480/60/3 35 35
53.1 50.0 25.0
GENERAL NOTES:
(a) THE CONTROL BOX IS ATTACHED TO THE CENTER SECTION AND IS
ROTATED 90 DEGREES FOR SHIPPING.
AFF = ABOVE FINISHED FLOOR
ALL DIMENSIONS TAKEN FROM THE FLOOR LINE MAY INCREASE 3-1/4"
WITH LEG ADJUSTMENT.
FOR CONVENIENCE WHEN CLEANING, CUSTOMER SHOULD INSTALL
WATER TAP NEAR MACHINE WITH 30 FT. OF HEAVY DUTY HOSE WITH
SQUEEZE VALVE.
THIS DRAWING IS SUPPLIED AS A REFERENCE FOR CONNECTION
INFORMATION ONLY. IT WILL NOT BE UTILIZED FOR MANUFACTURING
OF UNIT.
ELECTRICAL WARNING:
SERVICE WIRE TEMPERATURE RATING: 90C.
PLUMBING NOTES:
RECOMMENDED WATER HARDNESS TO BE 3 GRAINS OR LESS PER
GALLON FOR BEST RESULTS.
(b) RECOMMENDED BUILDING FLOWING HOT WATER PRESSURE TO THE
DISHWASHER IS 40-45 PSI.
(c) RECOMMENDED BUILDING FLOWING COLD WATER PRESSURE TO
THE DISHWASHER IS 30-35 PSI. IF COLD WATER IS LESS THAN 55°F
CONTACT SALES ENGINEERING.
(d) WATER HAMMER ARRESTOR (MEETING ASSE-1010 STANDARD OR
EQUIVALENT) TO BE SUPPLIED (BY OTHERS) IN HOT AND COLD
WATER SUPPLY LINES AT SERVICE CONNECTION.
VENTILATION NOTES:
(e) THE VENT STACK AND ITS ENCLOSURE CAN BE TEMPORARILY REMOVED
FROM THE ENERGY RECOVERY UNIT TO YIELD 81-7/8" CLEARANCE
FOR DOORWAYS.
ELECTRICAL CONNECTIONS
COMMON ON ALL MODELS:
E1 ELECTRIC CONNECTION, DETERGENT AND RINSE FEEDERS
(MACHINE SERVICE VOLTAGE), 1/2" CONDUIT.
79-1/8" AFF
E2 ELECTRIC CONNECTION, VENT FAN CONTROL.
(SWITCH CONTACTS) 1/2" CONDUIT. 79-1/8" AFF
ELECTRICAL CONNECTIONS
W/O CIRCUIT BREAKERS:
E3 ELECTRIC CONNECTION, MOTORS & CONTROLS,
1" CONDUIT. 79-1/8" AFF
E4 ELECTRIC TANK HEAT CONNECTION, POWER RINSE TANK, 20KW.
1" CONDUIT. 79-1/8" AFF
E5 ELECTRIC TANK HEAT CONNECTION, WASH TANK, 22KW.
1" CONDUIT. 79-1/8" AFF
E6 ELECTRIC TANK HEAT CONNECTION, DUAL RINSE TANK, 9KW.
BLOWER DRYER HEAT, 7KW & BLOWERS.
1" CONDUIT. 79-1/8" AFF
E7 ELECTRIC CONNECTION, BOOSTER, 18KW.
1" CONDUIT. 79-1/8" AFF
ELECTRICAL CONNECTIONS
WITH CIRCUIT BREAKERS:
E8 ELECTRIC CONNECTION, MOTORS, CONTROLS, POWER RINSE HEAT,
BOOSTER HEAT (WHEN CIRCUIT BREAKER OPTION IS SPECIFIED).
(TB1) 2" CONDUIT, 79-1/8" AFF
E9 ELECTRIC CONNECTION, WASH HEAT, DUAL RINSE HEAT,
BLOWER DRYER HEAT & BLOWERS (TB2).
2" CONDUIT, 79-1/8" AFF
PLUMBING CONNECTIONS:
P1 COMMON HOT WATER CONNECTION (AUTOMATIC FILL) 110°F WATER
MINIMUM, 1" FPT, 5-1/2" AFF see notes (b) AND (d).
P2 COMMON COLD WATER CONNECTION, 55°F WATER MINIMUM,
1" FPT, 5-1/2" AFF see notes (c) and (d).
P3 COMMON DRAIN CONNECTION.
TWO CONNECTION LOCATIONS; MAY BE DRAINED TO EITHER END
OF UNIT, PLUG OPPOSITE END.
2" FPT. 7" AFF
VENTILATION REQUIREMENTS:
V1 MINIMUM OF 24" SQUARE VENT HOOD WITH 6 INCH AIR GAP
CAPABLE OF PROVIDING 750 CFM EXHAUST AT STANDARD AIR
CONDITIONS (VENT HOOD SUPPLIED AND INSTALLED BY OTHERS).
BACK DRAFT PREVENTER REQUIRED (SUPPLIED AND INSTALLED
BY OTHERS).
95-3/8" AFF
MODEL:
FT1000
ENERGY RECOVERY
W/BLOWER DRYER
ELECTRIC
R-L OPERATION
00-949506
REV A2
SERVICE CONNECTION WITH CIRCUIT BREAKERS
(2) SERVICE CONNECTIONS AS SHOWN BELOW
MOTORS,CONTROLS,POWER RINSE & BOOSTER HEAT (TB1)
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 200 200 240/60/3 200 200 480/60/3 125 125
161.3 156.0 86.5
WASH, DUAL RINSE HEAT, B/D HEAT & BLOWERS (TB2)
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICE
208/60/3 119.1 150 150 240/60/3 113.0 150 150 480/60/3 56.5 70 70
ELECTRIC TANK HEAT, POWER RINSE
(1) 20 KW CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
208/60/3 60.0 80 80 240/60/3 57.3 80 80 480/60/3 28.6 40 40
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
ELECTRIC TANK HEAT, WASH
(1) 22 KW CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 66.0 80 80 240/60/3 63.0 80 80 480/60/3 31.5 45 45
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICES
208/60/3 54.0 70 70 240/60/3 51.5 70 70 480/60/3 25.8 35 35
ELECTRIC BOOSTER
(1) 18 KW CONNECTION AS SHOWN BELOW
Electrical and grounding connections must comply with the applicable portions of the National Electrical Code and/or other local electrical codes.
Plumbing connections must comply with applicable sanitary, safety and plumbing codes. Drain and fill line configurations vary, some methods are shown on this drawing.
Pressure gauge not required on pumped rinse machines.
MOTORS AND CONTROLS
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICE
208-240/60/3 47.2 60 60 480/60/3 32.1 40 40
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 7
Page 8 of 12 F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
STEAM L-R
18 3/4"
37 1/2" 55 11/16"
63 3/8"
11 13/16"
2 15/16"
33 3/8"
68 13/16"
15 11/16"
9 15/16"
38 1/4"
28 15/16"
28 7/16"
21 3/4"
55 3/16"
51 15/16"
5 15/16" 6 3/4" 11 9/16"
14 11/16"
23 1/8"
44 9/16"
33"
23 3/4"
23"
160 1/16"
P4
P1
V1
P8
P3
V1
E1
E2
E3
P7
P7
P7
P7 P6
P5
P9
P2
P1
P2
P3
E1E2E3
P4
P3
P5
P6
P8
P9
Electrical and grounding connections must comply with the applicable portions of the National Electrical Code and/or other local electrical codes.
Plumbing connections must comply with applicable sanitary, safety and plumbing codes. Drain and fill line configurations vary, some methods are shown on this drawing.
Pressure gauge not required on pumped rinse machines.
DIRECTION OF OPERATION
ASR
BLOWER/
DRYER
6"
36 1/2"
62 3/4"
36 1/4"
3"
35 7/16" 35 7/16" 35 7/16" 25 9/16"
5 3/4"
23 3/4"
6" AIR
GAP
FLOOR LINE
43 5/16"
25 9/16"
3 15/16" OVER FRAME "A" 7 7/8"
UNLOAD "C"
81 7/8"
LOAD "B" 8' 7/16"
V1
EXHAUST HOOD
SUPPLIED BY
OTHERS
LOAD
END
UNLOAD
ENDAUX
RNS
FNL
RNS
POWER
WASH
PRE-
WASH
POWER
RINSE
89 3/8" SEE NOTE (f)
MODEL:
FT1000 ENERGY RECOVERY
W/BLOWER DRYER
STEAM
L-R OPERATION
00-949507
REV A2
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 8
F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher Page 9 of 12
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
STEAM L-R
22" HIGH X 29-13/16"
WIDE OPENING WILL
HANDLE 18" X 26" BUN PANS
NOTE: CLEARANCE FROM WALL
24" RECOMMENDED, 6" MINIMUM
WITH DETERGENT DISPENSER
ON THE TOP
44 13/16" SEE NOTE (a)
FLOOR LINE
35"
NOTE: STRAINER PANS
REQUIRE 35" TO
BE REMOVED. EXTRA
CLEARANCE SHOULD BE
PROVIDED.
40 3/8"
NOTE: REFER TO LATEST
EDITION OF NATIONAL
ELECTRICAL CODE AND
LOCAL BUILDING CODES
FOR PROPER CLEARANCE
MODEL NO. "A" "B" "C"
NOTE: OVERALL LENGTH OF MACHINE IS DIMENSION "A" + 11 13/16"
7' 6-1/2" 7' 6-1/2" 7' 6-1/2" 9' 2-1/4" 9' 2-1/4" 9' 2-1/4"
11' 1-7/8" 11' 1-7/8" 11' 1-7/8" 14' 9-3/16" 14' 9-3/16" 14' 9-3/16" 16' 8-3/4" 16' 8-3/4" 16' 8-3/4"
23' 3-1/2" 24' 3-1/4" 25' 3-3/32" 24' 11-1/4" 25' 11" 26' 10-27/32" 26' 10-7/8" 27' 10-5/8" 28' 10-15/32" 30' 6-3/16" 31' 5-15/16" 32' 5-25/32" 32' 5-3/4" 33' 5-1/2" 34' 5-11/32"
7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32"
FT1023 (7.5'-8'-7.5')
FT1024 (8.5'-8'-7.5')
FT1025 (9.5'-8'-7.5')
FT1025 (7.5'-8'-9')
FT1026 (8.5'-8'-9')
FT1027 (9.5'-8'-9')
FT1027 (7.5'-8'-11')
FT1028 (8.5'-8'-11')
FT1029 (9.5'-8'-11')
FT1030 (7.5'-8'-15')
FT1031 (8.5'-8'-15')
FT1032 (9.5'-8'-15')
FT1032 (7.5'-8'-17')
FT1033 (8.5'-8'-17')
FT1034 (9.5'-8'-17')
GENERAL NOTES:
(a) THE CONTROL BOX IS ATTACHED TO THE CENTER SECTION AND IS
ROTATED 90 DEGREES FOR SHIPPING.
AFF = ABOVE FINISHED FLOOR
ALL DIMENSIONS TAKEN FROM THE FLOOR LINE MAY INCREASE 3-1/4"
WITH LEG ADJUSTMENT.
FOR CONVENIENCE WHEN CLEANING, CUSTOMER SHOULD INSTALL
WATER TAP NEAR MACHINE WITH 30 FT. OF HEAVY DUTY HOSE WITH
SQUEEZE VALVE.
THIS DRAWING IS SUPPLIED AS A REFERENCE FOR CONNECTION
INFORMATION ONLY. IT WILL NOT BE UTILIZED FOR MANUFACTURING
OF UNIT.
ELECTRICAL WARNING:
SERVICE WIRE TEMPERATURE RATING: 90C.
VENTILATION NOTES:
(f) THE VENT STACK AND ITS ENCLOSURE CAN BE TEMPORARILY REMOVED
FROM THE ENERGY RECOVERY UNIT TO YIELD 81-7/8" CLEARANCE FOR
DOORWAYS.
PLUMBING NOTES:
RECOMMENDED WATER HARDNESS TO BE 3 GRAINS OR LESS PER
GALLON FOR BEST RESULTS.
(b) RECOMMENDED BUILDING FLOWING HOT WATER PRESSURE TO THE
DISHWASHER IS 40-45 PSI.
(c) RECOMMENDED BUILDING FLOWING COLD WATER PRESSURE TO THE
DISHWASHER IS 30-35 PSI. IF COLD WATER IS LESS THAN 55°F
CONTACT SALES ENGINEERING.
(d) WATER HAMMER ARRESTOR (MEETING ASSE-1010 STANDARD OR
EQUIVALENT) TO BE SUPPLIED (BY OTHERS) IN HOT AND COLD
WATER SUPPLY LINES AT SERVICE CONNECTION.
(e) IF STEAM PRESSURE IS UNDER 10 PSI FLOWING PRESSURE
AT THE DISHWASHER, CONTACT SALES ENGINEERING.
ELECTRICAL CONNECTIONS
COMMON ON ALL MODELS:
E1 ELECTRIC CONNECTION, DETERGENT AND RINSE FEEDERS
(MACHINE SERVICE VOLTAGE), 1/2" CONDUIT.
79-1/8" AFF
E2 ELECTRIC CONNECTION, VENT FAN CONTROL.
(SWITCH CONTACTS) 1/2" CONDUIT. 79-1/8" AFF
ELECTRICAL CONNECTIONS
WITH & W/O CIRCUIT BREAKERS:
E3 ELECTRIC CONNECTION, MOTORS & CONTROLS,
1" CONDUIT. 79-1/8" AFF
PLUMBING CONNECTIONS:
P1 COMMON HOT WATER CONNECTION (AUTOMATIC FILL) 110°F WATER
MINIMUM, 1" FPT, 5-1/2" AFF see notes (b) AND (d).
P2 COMMON COLD WATER CONNECTION, 55°F WATER MINIMUM,
1" FPT, 5-1/2" AFF see notes (c) and (d).
P3 COMMON DRAIN CONNECTION.
TWO CONNECTION LOCATIONS; MAY BE DRAINED TO EITHER END
OF UNIT, PLUG OPPOSITE END.
2" FPT. 7" AFF
P4 COMMON STEAM CONNECTION (TANK HEAT, STEAM BOOSTER &
BLOWER DRYER). 1-1/2" FPT, 4-3/8" AFF (10-45 PSI FLOWING PRESSURE)
see note (e).
P5 STEAM RELIEF VALVE, (WHEN STEAM BOOSTER OPTION IS SPECIFIED)
1" FPT, MUST BE PIPED TO OPEN DRAIN RECEIVER IN THE FLOOR.
16-15/16" AFF
P6 HOT WATER RELIEF VALVE, (WHEN STEAM BOOSTER OPTION IS SPECIFIED)
3/4" FPT, MUST BE PIPED TO OPEN DRAIN RECEIVER IN THE FLOOR.
15-9/16" AFF
P7 CONDENSATE RETURN, GRAVITY CONNECTION (TANK HEAT),
BUCKET TYPE TRAPS FURNISHED, 3 CONNECTIONS.
3/4" FPT, 11" AFF
P8 CONDENSATE RETURN, GRAVITY CONNECTION (WHEN STEAM BOOSTER
OPTION IS SPECIFIED), BUCKET TYPE TRAP FURNISHED.
3/4" FPT, 4-3/4" AFF
P9 CONDENSATE RETURN, GRAVITY CONNECTION (STEAM BLOWER DRYER),
BUCKET TYPE TRAP FURNISHED.
3/4" FPT, 13" AFF
VENTILATION REQUIREMENTS:
V1 MINIMUM OF 24" SQUARE VENT HOOD WITH 6 INCH AIR GAP
CAPABLE OF PROVIDING 750 CFM EXHAUST AT STANDARD AIR
CONDITIONS (VENT HOOD SUPPLIED AND INSTALLED BY OTHERS).
BACK DRAFT PREVENTER REQUIRED (SUPPLIED AND INSTALLED
BY OTHERS).
95-3/8" AFF
MOTORS AND CONTROLS
SERVICE CONNECTION WITH & W/O CIRCUIT BREAKERS
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICE
208-240/60/3 54.5 70 70 480/60/3 36.4 45 45
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 9
Page 10 of 12 F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
STEAM R-L
18 3/4"
37 1/2"
55 11/16"
63 3/8"
11 13/16"
22 5/8" 53 3/8"
88 3/4"
15 11/16"
9 15/16"
38 1/4"
28 15/16"
28 7/16"
23 3/4"
60"
52"
5 7/8"
32 15/16"
6 3/4"
11 5/8"
14 5/8"
23 1/8"
44 9/16"
23 1/16"
160 1/16"
P4
P2
V1
P8
P3
V1
E1
E2
E3
P7
P7
P7
P7P6
P8
P9
P1
P1 P2
P3
E1 E2 E3
P4
P3
P5 P6
P5
P9
DIRECTION OF OPERATION
ASR
BLOWER/
DRYER
6"
36 1/2"36 1/4"
3"
35 7/16"35 7/16"35 7/16"25 9/16"
5 3/4"
23 3/4"
6" AIR
GAP
FLOOR LINE
7 3/16" 3 15/16"
UNLOAD "C"
OVER FRAME "A"
43 5/16"
25 9/16"
81 7/8"
8' 7/16" LOAD "B"
62 3/4"
V1
EXHAUST HOOD
SUPPLIED BY
OTHERS
89 3/8" SEE NOTE (f)
UNLOAD
END
LOAD
END
POWER
WASH
PRE-
WASH
POWER
RINSE
AUX
RNS
FNL
RNS
MODEL:
FT1000 ENERGY RECOVERY
W/BLOWER DRYER
STEAM
R-L OPERATION
00-949506
REV A2
Electrical and grounding connections must comply with the applicable portions of the National Electrical Code and/or other local electrical codes.
Plumbing connections must comply with applicable sanitary, safety and plumbing codes. Drain and fill line configurations vary, some methods are shown on this drawing.
Pressure gauge not required on pumped rinse machines.
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 10
F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher Page 11 of 12
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER,
STEAM R-L
MODEL NO. "A" "B" "C"
NOTE: OVERALL LENGTH OF MACHINE IS DIMENSION "A" + 11 13/16"
7' 6-1/2" 7' 6-1/2" 7' 6-1/2" 9' 2-1/4" 9' 2-1/4" 9' 2-1/4"
11' 1-7/8" 11' 1-7/8" 11' 1-7/8" 14' 9-3/16" 14' 9-3/16" 14' 9-3/16" 16' 8-3/4" 16' 8-3/4" 16' 8-3/4"
23' 3-1/2" 24' 3-1/4" 25' 3-3/32" 24' 11-1/4" 25' 11" 26' 10-27/32" 26' 10-7/8" 27' 10-5/8" 28' 10-15/32" 30' 6-3/16" 31' 5-15/16" 32' 5-25/32" 32' 5-3/4" 33' 5-1/2" 34' 5-11/32"
7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32" 7' 8-1/2" 8' 8-1/4" 9' 8-3/32"
FT1023 (7.5'-8'-7.5')
FT1024 (8.5'-8'-7.5')
FT1025 (9.5'-8'-7.5')
FT1025 (7.5'-8'-9')
FT1026 (8.5'-8'-9')
FT1027 (9.5'-8'-9')
FT1027 (7.5'-8'-11')
FT1028 (8.5'-8'-11')
FT1029 (9.5'-8'-11')
FT1030 (7.5'-8'-15')
FT1031 (8.5'-8'-15')
FT1032 (9.5'-8'-15')
FT1032 (7.5'-8'-17')
FT1033 (8.5'-8'-17')
FT1034 (9.5'-8'-17')
22" HIGH X 29-13/16"
WIDE OPENING WILL
HANDLE 18" X 26" BUN PANS
NOTE: CLEARANCE FROM WALL
24" RECOMMENDED, 6" MINIMUM
WITH DETERGENT DISPENSER
ON THE TOP
FLOOR LINE 44 13/16"
SEE NOTE (a)
35"
40 3/8"
NOTE: REFER TO LATEST
EDITION OF NATIONAL
ELECTRICAL CODE AND
LOCAL BUILDING CODES
FOR PROPER CLEARANCE
NOTE: STRAINER PANS
REQUIRE 35" TO
BE REMOVED. EXTRA
CLEARANCE SHOULD BE
PROVIDED.
VENTILATION REQUIREMENTS:
V1 MINIMUM OF 24" SQUARE VENT HOOD WITH 6 INCH AIR GAP
CAPABLE OF PROVIDING 750 CFM EXHAUST AT STANDARD AIR
CONDITIONS (VENT HOOD SUPPLIED AND INSTALLED BY OTHERS).
BACK DRAFT PREVENTER REQUIRED (SUPPLIED AND INSTALLED
BY OTHERS).
95-3/8" AFF
GENERAL NOTES:
(a) THE CONTROL BOX IS ATTACHED TO THE CENTER SECTION AND IS
ROTATED 90 DEGREES FOR SHIPPING.
AFF = ABOVE FINISHED FLOOR
ALL DIMENSIONS TAKEN FROM THE FLOOR LINE MAY INCREASE 3-1/4"
WITH LEG ADJUSTMENT.
FOR CONVENIENCE WHEN CLEANING, CUSTOMER SHOULD INSTALL
WATER TAP NEAR MACHINE WITH 30 FT. OF HEAVY DUTY HOSE WITH
SQUEEZE VALVE.
THIS DRAWING IS SUPPLIED AS A REFERENCE FOR CONNECTION
INFORMATION ONLY. IT WILL NOT BE UTILIZED FOR MANUFACTURING
OF UNIT.
ELECTRICAL WARNING:
SERVICE WIRE TEMPERATURE RATING: 90C.
PLUMBING NOTES:
RECOMMENDED WATER HARDNESS TO BE 3 GRAINS OR LESS PER
GALLON FOR BEST RESULTS.
(b) RECOMMENDED BUILDING FLOWING HOT WATER PRESSURE TO THE
DISHWASHER IS 40-45 PSI.
(c) RECOMMENDED BUILDING FLOWING COLD WATER PRESSURE TO THE
DISHWASHER IS 30-35 PSI. IF COLD WATER IS LESS THAN 55°F
CONTACT SALES ENGINEERING.
(d) WATER HAMMER ARRESTOR (MEETING ASSE-1010 STANDARD OR
EQUIVALENT) TO BE SUPPLIED (BY OTHERS) IN HOT AND COLD
WATER SUPPLY LINES AT SERVICE CONNECTION.
(e) IF STEAM PRESSURE IS UNDER 10 PSI FLOWING PRESSURE
AT THE DISHWASHER, CONTACT SALES ENGINEERING.
VENTILATION NOTES:
(f) THE VENT STACK AND ITS ENCLOSURE CAN BE TEMPORARILY REMOVED
FROM THE ENERGY RECOVERY UNIT TO YIELD 81-7/8" CLEARANCE FOR
DOORWAYS.
ELECTRICAL CONNECTIONS
COMMON ON ALL MODELS:
E1 ELECTRIC CONNECTION, DETERGENT AND RINSE FEEDERS
(MACHINE SERVICE VOLTAGE), 1/2" CONDUIT.
79-1/8" AFF
E2 ELECTRIC CONNECTION, VENT FAN CONTROL.
(SWITCH CONTACTS) 1/2" CONDUIT. 79-1/8" AFF
ELECTRICAL CONNECTIONS
WITH & W/O CIRCUIT BREAKERS:
E3 ELECTRIC CONNECTION, MOTORS & CONTROLS,
1" CONDUIT. 79-1/8" AFF
PLUMBING CONNECTIONS:
P1 COMMON HOT WATER CONNECTION (AUTOMATIC FILL) 110°F WATER
MINIMUM, 1" FPT, 5-1/2" AFF see notes (b) AND (d).
P2 COMMON COLD WATER CONNECTION, 55°F WATER MINIMUM,
1" FPT, 5-1/2" AFF see notes (c) and (d).
P3 COMMON DRAIN CONNECTION.
TWO CONNECTION LOCATIONS; MAY BE DRAINED TO EITHER END
OF UNIT, PLUG OPPOSITE END.
2" FPT. 7" AFF
P4 COMMON STEAM CONNECTION (TANK HEAT, STEAM BOOSTER &
BLOWER DRYER). 1-1/2" FPT, 4-3/8" AFF (10-45 PSI FLOWING PRESSURE)
see note (e).
P5 STEAM RELIEF VALVE, (WHEN STEAM BOOSTER OPTION IS SPECIFIED)
1" FPT, MUST BE PIPED TO OPEN DRAIN RECEIVER IN THE FLOOR.
16-15/16" AFF
P6 HOT WATER RELIEF VALVE, (WHEN STEAM BOOSTER OPTION IS SPECIFIED)
3/4" FPT, MUST BE PIPED TO OPEN DRAIN RECEIVER IN THE FLOOR.
15-9/16" AFF
P7 CONDENSATE RETURN, GRAVITY CONNECTION (TANK HEAT),
BUCKET TYPE TRAPS FURNISHED, 3 CONNECTIONS.
3/4" FPT, 11" AFF
P8 CONDENSATE RETURN, GRAVITY CONNECTION (WHEN STEAM BOOSTER
OPTION IS SPECIFIED), BUCKET TYPE TRAP FURNISHED.
3/4" FPT, 4-3/4" AFF
P9 CONDENSATE RETURN, GRAVITY CONNECTION (STEAM BLOWER DRYER),
BUCKET TYPE TRAP FURNISHED.
3/4" FPT, 13" AFF
MOTORS AND CONTROLS
SERVICE CONNECTION WITH & W/O CIRCUIT BREAKERS
(1) SERVICE CONNECTION AS SHOWN BELOW
ELEC.
SPECS.
RATED
AMPS
MINIMUM
SUPPLY
CONDUCTOR
AMPACITY
MAXIMUM
PROTECTIVE
DEVICE
208-240/60/3 54.5 70 70 480/60/3 36.4 45 45
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 11
Page 12 of 12 F40392 – FT1000 Energy Recovery with Blower Dryer Flight-Type Dishwasher
As continued product improvement is a policy of Hobart, specifications are subject to change without notice.
FT1000 ENERGY RECOVERY
WITH BLOWER DRYER
FLIGHT-TYPE DISHWASHER
FT1000 Energy Recovery with Blower Dryer Series (7.5, 9 Load / 8 Center / 7.5, 9, 11 Unload)
Machine Ratings (Mechanical) Conveyor Speed — Feet per minute 4.0 - 8.5
Dishes per Hour 14,316
Motor — Horsepower ASR Soil - 1⁄4; ASR Wash - 1⁄3; Pre-Wash - 31⁄2; Wash - 5; Rinse - 5;
Dual Rinse - 1⁄6; Final Rinse - 1⁄2; Conveyor - 1⁄3; Blower Dryer (2) 2
Tank Capacity — Gallons ASR - 7.2; Pre-Wash - 40; Wash - 40; Rinse - 40; Dual Rinse - 7.2
Rate of Final Rinse — Gallons per minute (Pumped rinse) .97
Final Rinse Consumption — Gallons per hour (Pumped rinse) 58
Exhaust Requirements — Cubic feet per minute 750 (at standard air conditions)
Latent/Sensible Heat — BTU per hour Electric - Latent: 87,400 / Sensible: 37,400 Steam - Latent: 103,900 / Sensible: 44,500
Electric Heat Requirements —
Tank Heat - Kilowatt (Regulated)
Optional Electric Booster - Kilowatt
Optional Blower Dryer - Kilowatt
Disconnect switches are recommended for each power circuit connected to dishwasher. These disconnect switches are NOT furnished by Hobart and should be installed by the electrical contractor at the time of installation.
Circuit breakers optional at extra cost.
Total tank heat - 51KW (Wash, Rinse, Dual Rinse)
18KW - 110°F incoming water raised to 185°F (75°F rise) (180°F minimum)
7.0 KW
Steam Heat Requirements —
Steam Consumption
Tank Heat - Pounds per hour - maximum (Regulated) - based on 10 to 45 PSI steam at the machine
Optional Steam Booster - Pounds per hour - maximum
- based on 20 PSI steam, 110°F incoming water raised to 185°F (75°F rise) (180°F minimum)
Optional Steam Blower Dryer - Pounds per hour -maximum - based on 20 PSI steam
213 lbs./150°F Wash minimum - 160°F Rinse minimum - 160°F Dual Rinse minimum
42 lbs./180°F Final Rinse minimum
30 lbs.
Peak Rate of Drain Flow — Gallons per minute Initial rate with full tanks 38
Shipping Weight Crated Varies by individual model - consult your Hobart representative
FT (flight type) Models—many additional variations of these model specifications are available. Engineering data furnished on request. Numbers in parentheses, after model number from left to right, represent length in feet of the following respectively; Loading section, Washing and Power Rinsing sections, Unloading section.
F40392 (REV. 09/14) LITHO IN U.S.A. (H-01)
Aldevra Lead 9158 ‐ 36C252‐18‐Q‐0554 ‐ VAMC Gill Marke ng Co., a division of Gill Group, Inc. Page: 12