Attachment IX - Arc Flash Survey Diagrams.pdf
PDF 4 MB Posted
- Attached to
- H959--Triennial Electrical Breaker Testing Federal contract opportunity
- Solicitation number
- 36C25024Q0966
About this file
This document appears to be an attachment related to a federal contract opportunity for triennial electrical breaker testing. The key details are:
The federal contract opportunity is for Triennial Electrical Breaker Testing (Solicitation 36C25024Q0966), issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. The solicitation requires electrical breaker testing services at the Richard L. Roudebush VA Medical Center in Indianapolis, Indiana. The document includes detailed electrical system diagrams and circuit breaker specifications that appear to be part of the Performance Work Statement or Statement of Objectives for this contract opportunity. No award date or pricing terms are provided in the attachment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment XIII - RFI Questions and Answers FINAL.pdf | ||
| 36C25024Q0966 0004.docx | DOCX document | |
| Attachment VIII - SOW Revised.docx | DOCX document | |
| Attachment XII - 36C25024Q0966 RFI Template.docx | DOCX document | |
| Attachment XI - RFI Questions and Answers.docx | DOCX document | |
| Attachment X - Single Line Diagrams Updated.pdf | ||
| 36C25024Q0966 0003.docx | DOCX document | |
| 36C25024Q0966 0002.docx | DOCX document | |
| 36C25024Q0966 0001.docx | DOCX document | |
| 36C25024Q0966.docx | DOCX document | |
| Attachment I - SCA WD.pdf | ||
| Attachment VI - Panel Amperage and Locations.pdf | ||
| Attachment II - Limitations on Subcontracting - Certificate of Compliance.pdf | ||
| Attachment V - Single Line Diagrams.pdf | ||
| Attachment III - VHA Directive 1192-01.pdf | ||
| Attachment VII - Master List.pdf | ||
| Attachment IV - Specs.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet Index
SHEET NO. SHEET NAME BUILDING
DRAWING
NUMBER
E-601-1 BLDG1-AMS 1 1 OF 10
E-601-2 BLDG1-AMS 1 2 OF 10
E-601-3 BLDG1-AMS 1 3 OF 10
E-601-4 BLDG1-AMS 1 4 OF 10
E-601-5 BLDG1-AMS 1 5 OF 10
E-601-6 BLDG1-AMS 1 6 OF 10
E-601-7 BLDG1-AMS 1 7 OF 10
E-601-8 BLDG1-AMS 1 8 OF 10
E-601-9 BLDG1-AMS 1 9 OF 10
E-601-10 BLDG1-AMS 1 10 OF 10
E-602-1 BLDG1-CNE 1 1 OF 12
E-602-2 BLDG1-CNE 1 2 OF 12
E-602-3 BLDG1-CNE 1 3 OF 12
E-602-4 BLDG1-CNE 1 4 OF 12
E-602-5 BLDG1-CNE 1 5 OF 12
E-602-6 BLDG1-CNE 1 6 OF 12
E-602-7 BLDG1-CNE 1 7 OF 12
E-602-8 BLDG1-CNE 1 8 OF 12
E-602-9 BLDG1-CNE 1 9 OF 12
E-602-10 BLDG1-CNE 1 10 OF 12
E-602-11 BLDG1-CNE 1 11 OF 12
E-602-12 BLDG1-CNE 1 12 OF 12
E-603-1 BLDG1-CS 1 1 OF 2
E-603-2 BLDG1-CS 1 2 OF 2
E-604-1 BLDG1-25D 1 1 OF 1
E-605-1 BLDG1-SS1D 1 1 OF 6
E-605-2 BLDG1-SS1D 1 2 OF 6
E-605-3 BLDG1-SS1D 1 3 OF 6
E-605-4 BLDG1-SS1D 1 4 OF 6
E-605-5 BLDG1-SS1D 1 5 OF 6
E-605-6 BLDG1-SS1D 1 6 OF 6
E-606-1 BLDG19 19 1 OF 1
E-607-1 BLDG21 21 1 OF 1
E-608-1 BLDG22 22 1 OF 3
E-608-2 BLDG22 22 2 OF 3
E-608-3 BLDG22 22 3 OF 3
E-609-1 MVLOOP 1 OF 3
E-609-2 MVLOOP 2 OF 3
E-609-3 MVLOOP 3 OF 3
E-610-1 PRKG GRG 20 1 OF 1
ELECTRICAL
CB-400A AATSCR2 (E)
CB-800A AATSEQ7 (E)
CB-800A AATSEQ6 (E)
NOTE NOTE
CB-400A A1SMT1
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.1 x P) 1 (400A)
LTD (1-4) 3
STPU (1.5-9 x LTPU) 9 (3600A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 10 (4000A)
250 kcmil
260.0 ft
MCB-500A A1SMLT1
GE
Frame/Model THJK
Sensor/Trip 500.0 A
Plug 500.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (5000A)
A1SMLT1
Rm D-1355
480.0 V
AFIE 0.75 Cal/cm^2
Bolted Fault 16.873 kA
Voltage Drop 4.57 %
CB-400A AATSCR2 (N)
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.1 x P) 0.5 (200A)
LTD (1-4) 2
STPU (1.5-9 x LTPU) 3.5 (700A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 15 (6000A)
500 kcmil
40.0 ft
E N
AATSCR2
Position - Normal On
AATSCR2 (N)
Rm A-B140
480.0 V
AFIE 2.51 Cal/cm^2
Bolted Fault 28.163 kA
Voltage Drop 4.57 %
500 kcmil
260.0 ft
MCB-400A A5HCRDP1
EATON/CUTLER-HAMMER
Frame/Model HKD
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (5-10 x Trip) 10 (4000A)
CB-800A AATSEQ7 (N)
GE
Frame/Model AKR-30L
Sensor/Trip 800.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.1 x P) 0.95 (380A)
LTD (1-4) 3
STPU (1.5-9 x LTPU) 5 (1900A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 15 (6000A)
500 kcmil
45.0 ft
AATSEQ7 (N)
Rm A-B140
480.0 V
AFIE 2.79 Cal/cm^2
Bolted Fault 31.563 kA
Voltage Drop 4.75 % E N
AATSEQ7
Position - Normal On
500 kcmil
300.0 ft
MCB-800A A8HEQDP1
GE
Frame/Model SKHA
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
MAX
A8HEQDP1
Rm A-8086
480.0 V
AFIE 1.06 Cal/cm^2
Bolted Fault 18.172 kA
Voltage Drop 5.93 %
CB-200A A8EMCC1
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
3/0 AWG
20.0 ft
A8EMCC1
Rm A-8086
480.0 V
AFIE 0.74 Cal/cm^2
Bolted Fault 16.581 kA
Voltage Drop 6.01 %
CB-200A SF50
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
4/0 AWG
40.0 ft
SF50
Rm
480.0 V
AFIE 0.69 Cal/cm^2
Bolted Fault 15.478 kA
Voltage Drop 6.05 %
MTR-SF50
80 hp
CB-200A SF49
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
4/0 AWG
40.0 ft
SF49
Rm
480.0 V
AFIE 0.69 Cal/cm^2
Bolted Fault 15.478 kA
Voltage Drop 6.05 %
MTR-SF49
80 hp
CB-80A RF49
GE
Frame/Model FCS
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
2 AWG
40.0 ft
RF49
Rm
480.0 V
AFIE 0.28 Cal/cm^2
Bolted Fault 13.115 kA
Voltage Drop 6.08 %
MTR-RF49
40 hp
CB-80A RF50
GE
Frame/Model FCS
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
2 AWG
40.0 ft
RF50
Rm
480.0 V
AFIE 0.28 Cal/cm^2
Bolted Fault 13.115 kA
Voltage Drop 6.08 %
MTR-RF50
40 hp
CB-60A EF2
GE
Frame/Model SELA
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
MAX
8 AWG
40.0 ft
EF2
Rm
480.0 V
AFIE 0.27 Cal/cm^2
Bolted Fault 6.515 kA
Voltage Drop 6.40 %
MTR-EF2
30 hp
CB-60A PRE-HEAT PUMP 1A
GE
Frame/Model SELA
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
MAX
8 AWG
40.0 ft
PRE-HEAT PUMP 1A
Rm
480.0 V
AFIE 0.27 Cal/cm^2
Bolted Fault 6.515 kA
Voltage Drop 6.40 %
MTR-PHP 1A
30 hp
CB-60A PRE-HEAT PUMP 1B
GE
Frame/Model SELA
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
MAX
8 AWG
40.0 ft
PRE-HEAT PUMP 1B
Rm
480.0 V
AFIE 0.27 Cal/cm^2
Bolted Fault 6.515 kA
Voltage Drop 6.40 %
MTR-PHP 1B
30 hp
CB-800A AATSEQ6 (N)
GE
Frame/Model AKR-30L
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.1 x P) 0.95 (760A)
LTD (1-4) 3
STPU (1.5-9 x LTPU) 5 (3800A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 15 (12000A)
500 kcmil
50.0 ft
AATSEQ6 (N)
Rm
480.0 V
AFIE 2.73 Cal/cm^2
Bolted Fault 30.810 kA
Voltage Drop 4.65 %E N
AATSEQ6
Position - Normal On
AATSEQ6 (L)
Rm
480.0 V
AFIE 2.73 Cal/cm^2
Bolted Fault 30.810 kA
Voltage Drop 4.65 %
500 kcmil
110.0 ft
MCB-400A A2HEQDP1
EATON/CUTLER-HAMMER
Frame/Model KD
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (5-10 x Trip) 10 (4000A)
A2HEQDP1
Rm A-2117
480.0 V
AFIE 0.37 Cal/cm^2
Bolted Fault 18.686 kA
Voltage Drop 4.65 %
CB-125A TRANS A2LEQ1
CUTLER-HAMMER
Frame/Model FD
Sensor/Trip 125.0 A
Plug 125.0 A
Settings
Fixed
350 kcmil
150.0 ft
1 AWG
6.0 ft
S
P
TRANS A2LEQ1
75 kVA
Impedance 5.1100 %
Primary 480 V
Secondary 208 V
TRANS A2LEQ1 SEC
Rm A-2117
208.0 V
AFIE 1.67 Cal/cm^2
Bolted Fault 3.718 kA
Voltage Drop 4.65 %
3/0 AWG
8.0 ft
MCB-200A A2LEQ1
EATON/CUTLER-HAMMER
Frame/Model EDB
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Fixed
A2LEQ1
Rm A-2117
208.0 V
AFIE 1.64 Cal/cm^2
Bolted Fault 3.650 kA
Voltage Drop 4.65 %
CB-125A TRANS A2LEQ2
CUTLER-HAMMER
Frame/Model FD
Sensor/Trip 125.0 A
Plug 125.0 A
Settings
Fixed
1 AWG
6.0 ft
S
P
TRANS A2LEQ2
75 kVA
Impedance 5.1100 %
Primary 480 V
Secondary 208 V
TRANS A2LEQ2 SEC
Rm A-2117
208.0 V
AFIE 1.67 Cal/cm^2
Bolted Fault 3.718 kA
Voltage Drop 4.65 %
3/0 AWG
120.0 ft
MCB-200A A2LEQ2
EATON/CUTLER-HAMMER
Frame/Model EDB
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Fixed
A2LEQ2
Rm A-2132
208.0 V
AFIE 1.25 Cal/cm^2
Bolted Fault 2.871 kA
Voltage Drop 4.65 %
CB-125A TRANS A2LEQ3
CUTLER-HAMMER
Frame/Model FD
Sensor/Trip 125.0 A
Plug 125.0 A
Settings
Fixed
1 AWG
90.0 ft
S
P
TRANS A2LEQ3
75 kVA
Impedance 5.1100 %
Primary 480 V
Secondary 208 V
TRANS A2LEQ3 SEC
Rm A-2056
208.0 V
AFIE 1.57 Cal/cm^2
Bolted Fault 3.514 kA
Voltage Drop 4.65 %
3/0 AWG
9.0 ft
MCB-200A A2LEQ3
EATON/CUTLER-HAMMER
Frame/Model EDB
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Fixed
A2LEQ3
Rm A-2056
208.0 V
AFIE 1.53 Cal/cm^2
Bolted Fault 3.443 kA
Voltage Drop 4.65 %
UNFUSED DS 200A
EATON/CUTLER-HAMMER
Frame/Model DH
DS TRANS A2LEQ3 PRI
Rm A-2056
480.0 V
AFIE 0.25 Cal/cm^2
Bolted Fault 10.159 kA
Voltage Drop 4.65 %1 AWG
8.0 ft
MCB-500A A3EMCC1
GE
Frame/Model THJK
Sensor/Trip 500.0 A
Plug 500.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (5000A)
A3EMCC1
Rm MECH
480.0 V
AFIE 0.96 Cal/cm^2
Bolted Fault 21.209 kA
Voltage Drop 4.89 %
CB-100A SF33
GE
Frame/Model TED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed4 AWG
40.0 ft
SF33
Rm
480.0 V
AFIE 0.4 Cal/cm^2
Bolted Fault 12.298 kA
Voltage Drop 5.16 %
MTR-SF33
50 hp
CB-40A CCP33
GE
Frame/Model TED
Sensor/Trip 40.0 A
Plug 40.0 A
Settings
Fixed10 AWG
40.0 ft
CCP33
Rm
480.0 V
AFIE 0.15 Cal/cm^2
Bolted Fault 5.184 kA
Voltage Drop 5.26 %
MTR-CCP33
20 hp
CB-50A SF35
GE
Frame/Model TED
Sensor/Trip 50.0 A
Plug 50.0 A
Settings
Fixed6 AWG
60.0 ft
SF35
Rm
480.0 V
AFIE 0.22 Cal/cm^2
Bolted Fault 7.233 kA
Voltage Drop 5.20 %
MTR-SF35
25 hp
CB-50A SF36
GE
Frame/Model TED
Sensor/Trip 50.0 A
Plug 50.0 A
Settings
Fixed6 AWG
60.0 ft
SF36
Rm
480.0 V
AFIE 0.22 Cal/cm^2
Bolted Fault 7.233 kA
Voltage Drop 5.20 %
MTR-SF36
25 hp
CB-225A TRANS A5T2
GE
Frame/Model AKR-30L
Sensor/Trip 400.0 A
Plug 225.0 A
Settings
LTPU (0.5-1.1 x P) 0.95 (213.75A)
LTD (1-4) 4
STPU (1.5-9 x LTPU) 9 (1923.75A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 15 (3375A)
500 kcmil
220.0 ft
CB-200A TRANS A5T2 PRI
GE
Frame/Model SGLA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
ECB CB-3 TRANS A5T2 PRI
Rm
480.0 V
AFIE 1.26 Cal/cm^2
Bolted Fault 14.214 kA
Voltage Drop 4.57 %
500 kcmil
6.0 ft
S
P
TRANS A5T2
150 kVA
Impedance 5.0400 %
Primary 480 V
Secondary 208 V
TRANS A5T2 SEC
Rm A-5001
208.0 V
AFIE 3.21 Cal/cm^2
Bolted Fault 6.600 kA
Voltage Drop 4.57 %
350 kcmil
12.0 ft
MCB-500A A5LNDP1
GE
Frame/Model SGHA
Sensor/Trip 500.0 A
Plug 500.0 A
Settings
MAX
A5LNDP1
Rm A-5001
208.0 V
AFIE 3.14 Cal/cm^2
Bolted Fault 6.476 kA
Voltage Drop 4.57 %
CB-225A A7LN1,A8LN1
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
220.0 ft
MCB-225A A7LN1
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
4.0 ft
A7LN1
Rm A-7122
208.0 V
AFIE 1.53 Cal/cm^2
Bolted Fault 3.432 kA
Voltage Drop 4.57 %
CB-100A A7LN2
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
6.0 ft
A7LN2
Rm A-7122
208.0 V
AFIE 1.48 Cal/cm^2
Bolted Fault 3.338 kA
Voltage Drop 4.57 %
MCB-225A A8LN1
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
20.0 ft
A8LN1
Rm A-8122
208.0 V
AFIE 1.47 Cal/cm^2
Bolted Fault 3.315 kA
Voltage Drop 4.57 %
CB-100A A8LN2
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
8.0 ft
A8LN2
Rm A-8122
208.0 V
AFIE 1.41 Cal/cm^2
Bolted Fault 3.197 kA
Voltage Drop 4.57 %
CB-225A A7LN6,A8LN6
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
40.0 ft
MCB-225A A7LN6
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
2.0 ft
A7LN6
Rm A-7139
208.0 V
AFIE 1.81 Cal/cm^2
Bolted Fault 5.605 kA
Voltage Drop 4.57 %
MCB-225A A8LN6
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
20.0 ft
A8LN6
Rm A-8129
208.0 V
AFIE 1.88 Cal/cm^2
Bolted Fault 5.289 kA
Voltage Drop 4.57 %
CB-225A A7LN4,A8LN4
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
40.0 ft
MCB-225A A7LN4
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
1.0 ft
A7LN4
Rm A-7139
208.0 V
AFIE 1.81 Cal/cm^2
Bolted Fault 5.623 kA
Voltage Drop 4.57 %
CB-100A A7LN5
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
5.0 ft
A7LN5
Rm A-7139
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 5.452 kA
Voltage Drop 4.57 %
MCB-225A A8LN4
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
20.0 ft
A8LN4
Rm A-8129
208.0 V
AFIE 1.88 Cal/cm^2
Bolted Fault 5.289 kA
Voltage Drop 4.57 %
CB-100A A8LN5
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed2 AWG
8.0 ft
A8LN5
Rm A-8129
208.0 V
AFIE 1.94 Cal/cm^2
Bolted Fault 5.039 kA
Voltage Drop 4.57 %
CB-60A A-2117
EATON/CUTLER-HAMMER
Frame/Model HFD
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
S
P
XF2-0019
45 kVA
Impedance 5.1900 %
Primary 480 V
Secondary 208 V
TRANS A-2117 SEC
Rm A-2117
208.0 V
AFIE 0.95 Cal/cm^2
Bolted Fault 2.266 kA
Voltage Drop 4.65 %
CBL-0426
6 AWG
10.0 ft
A5LEQ2
Rm A-5003
208.0 V
AFIE 0.79 Cal/cm^2
Bolted Fault 3.517 kA
Voltage Drop 4.65 %
MCB-100A A5LEQ2
EATON/CUTLER-HAMMER
Frame/Model EDB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
CBL-0429
2 AWG
10.0 ft
CB- A5LEQ2
Frame/Model
Sensor/Trip 0.0 A
Plug 0.0 A
Settings
M A
TC
H
LI
N
E S
H E
E T
E -6
-2
M A
TC
H
LI
N
E S
H E
E T
E -6
-1
MATCHLINE SHEET E-601-1
MATCHLINE SHEET E-601-7
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
N
O
T
F
R
C
O
N
S
T
R
U
C
T
I
O
N
N
R
C
O
N
S
T
R
U
C
T
I
O
N
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
Arc Flash Survey 583-19-206
Richard L. Roudebush VAMC 1481 W. 10th, St.
Indianapolis, IN 46202
19-303
Structural Engineer:
12/17/2020 40
E-601-1
BLDG 1 - AMS
1 BLDG 1 - AMS
SCALE: NTS
JAV ABT
CB-800A AATSEQ1 (E)
NOTE
MV LOOP
E N
AATSEQ1
Position - Normal On
S
P
TRANS AMS3
1500 kVA
Impedance 5.7499 %
Primary 13200 V
Secondary 480 V
TRANS AMS3 SEC
Rm A-B140
480.0 V
AFIE 71.46 Cal/cm^2
Bolted Fault 35.667 kA
Voltage Drop 4.57 %
750 kcmil
5.0 ft
MCB-1600A AMS3
GE
Frame/Model AKR-50
Sensor/Trip 1600.0 A
Plug 1600.0 A
Settings
LTPU (0.5-1.1 x P) 1 (1600A)
LTD (1-4) 1
STPU (1.5-9 x LTPU) 4 (6400A)
STD (Min-Max) Max (I^s T Off)
INST (1 x ST Rating) Fixed (50000A)
AMS3
Rm A-B140
480.0 V
AFIE 26.59 Cal/cm^2
Bolted Fault 35.640 kA
Voltage Drop 4.57 %
CB-400A A6HNDP1
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.1 x P) 1 (400A)
LTD (1-4) 3
STPU (1.5-9 x LTPU) 9 (3600A)
STD (Min-Max) Int (I^s T Off)
INST (1.5-15 x P) 15 (6000A)
500 kcmil
300.0 ft
MCB-400A A6HNDP1
EATON/CUTLER-HAMMER
Frame/Model HKD
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (5-10 x Trip) 10 (4000A)
A6HNDP1
Rm A-6173
480.0 V
AFIE 0.27 Cal/cm^2
Bolted Fault 11.619 kA
Voltage Drop 4.57 %
CB-100A A6HN1
EATON/CUTLER-HAMMER
Frame/Model HFD
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
100.0 ft
MCB-100A A6HN1
CUTLER-HAMMER
Frame/Model GHB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Thermal Curve
INST (Fixed) Fixed (1000A)
A6HN1
Rm A-6004
480.0 V
AFIE 0.1 Cal/cm^2
Bolted Fault 6.786 kA
Voltage Drop 4.57 %
CB-70A A7HN1,A8HN1
CUTLER-HAMMER
Frame/Model GHB
Sensor/Trip 70.0 A
Plug 70.0 A
Settings
Thermal Curve
INST (Fixed) Fixed (1000A)
2 AWG
20.0 ft
MCB-60A A7HN1
GE
Frame/Model TEY
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A7HN1
Rm A-7122
480.0 V
AFIE 0.09 Cal/cm^2
Bolted Fault 6.102 kA
Voltage Drop 4.57 %
CB-100A A6HN3
EATON/CUTLER-HAMMER
Frame/Model HFD
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
220.0 ft
MCB-100A A6HN3
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
A6HN3
Rm A-6075
480.0 V
AFIE 0.11 Cal/cm^2
Bolted Fault 4.303 kA
Voltage Drop 4.57 %
CB-60A A7HN2
GE
Frame/Model TED
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
4 AWG
20.0 ft
MCB-60A A7HN2
GE
Frame/Model TEY
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
A7HN2
Rm A-7139
480.0 V
AFIE 0.1 Cal/cm^2
Bolted Fault 3.929 kA
Voltage Drop 4.57 %
CB-100A A6HN2
EATON/CUTLER-HAMMER
Frame/Model HFD
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
130.0 ft
MCB-100A A6HN2
CUTLER-HAMMER
Frame/Model GHB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Thermal Curve
INST (Fixed) Fixed (1000A)
A6HN2
Rm A-6145
480.0 V
AFIE 0.08 Cal/cm^2
Bolted Fault 5.951 kA
Voltage Drop 4.57 %
CB-60A A8HN2
CUTLER-HAMMER
Frame/Model GHB
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Thermal Curve
INST (Fixed) Fixed (800A)
6 AWG
100.0 ft
MCB-60A A8HN2
GE
Frame/Model TEY
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
A8HN2
Rm A-8129
480.0 V
AFIE 0.04 Cal/cm^2
Bolted Fault 2.938 kA
Voltage Drop 4.57 %
CB-175A TRANS A6T1
EATON/CUTLER-HAMMER
Frame/Model HJD
Sensor/Trip 175.0 A
Plug 175.0 A
Settings
Thermal Curve (Fixed)
INST (5-10 x Trip) 10 (1750A)
4/0 AWG
6.0 ft
S
P
TRANS A6T1
112.5 kVA
Impedance 5.6000 %
Primary 480 V
Secondary 208 V
TRANS A6T1 SEC
Rm A-6173
208.0 V
AFIE 2.14 Cal/cm^2
Bolted Fault 4.620 kA
Voltage Drop 4.57 %
350 kcmil
8.0 ft
CB-400A A6LNDP1
EATON/CUTLER-HAMMER
Frame/Model DK
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (5-10 x Trip) 10 (4000A)
A6LNDP1
Rm A-6173
208.0 V
AFIE 2.1 Cal/cm^2
Bolted Fault 4.538 kA
Voltage Drop 4.57 %
CB-100A A6LN1
EATON/CUTLER-HAMMER
Frame/Model HFD
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed2 AWG
8.0 ft
MCB-100A A6LN1
EATON/CUTLER-HAMMER
Frame/Model QBHW
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
A6LN1
Rm A-6173
208.0 V
AFIE 0.03 Cal/cm^2
Bolted Fault 4.375 kA
Voltage Drop 4.57 %
CB-225A A6LN2
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed4/0 AWG
110.0 ft
MCB-225A A6LN2
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
A6LN2
Rm A-6004
208.0 V
AFIE 1.57 Cal/cm^2
Bolted Fault 3.510 kA
Voltage Drop 4.57 %
CB-225A A6LN3
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed4/0 AWG
110.0 ft
MCB-225A A6LN3
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
A6LN3
Rm A-6004
208.0 V
AFIE 1.57 Cal/cm^2
Bolted Fault 3.510 kA
Voltage Drop 4.57 %
CB-225A A6LN4
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed4/0 AWG
140.0 ft
MCB-225A A6LN4
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
A6LN4
Rm A-6145
208.0 V
AFIE 1.46 Cal/cm^2
Bolted Fault 3.298 kA
Voltage Drop 4.57 %
CB-225A A6LN5
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed4/0 AWG
140.0 ft
MCB-225A A6LN5
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
A6LN5
Rm A-6145
208.0 V
AFIE 1.46 Cal/cm^2
Bolted Fault 3.298 kA
Voltage Drop 4.57 %
CB-225A A6LN6
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed4/0 AWG
200.0 ft
MCB-225A A6LN6
GE
Frame/Model THQD
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
A6LN6
Rm A-6075
208.0 V
AFIE 1.28 Cal/cm^2
Bolted Fault 2.936 kA
Voltage Drop 4.57 %
CB-225A A6LN7
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed4/0 AWG
200.0 ft
MCB-225A A6LN7
GE
Frame/Model THQD
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
A6LN7
Rm A-6075
208.0 V
AFIE 1.28 Cal/cm^2
Bolted Fault 2.936 kA
Voltage Drop 4.57 %
CB-150A A7LN3,A8LN3
EATON/CUTLER-HAMMER
Frame/Model ED
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Fixed
4/0 AWG
20.0 ft
MCB-150A A7LN3
GE
Frame/Model SFHA
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
MAX
A7LN3
Rm A-7098B
208.0 V
AFIE 1.12 Cal/cm^2
Bolted Fault 4.274 kA
Voltage Drop 4.57 %
4/0 AWG
4.0 ft
MCB-150A A8LN3
GE
Frame/Model SFHA
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
MAX
A8LN3
Rm A-8098B
208.0 V
AFIE 1.14 Cal/cm^2
Bolted Fault 4.112 kA
Voltage Drop 4.57 %
4/0 AWG
20.0 ft
CB-800A AATSEQ1 (N)
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.1 x P) 1 (800A)
LTD (1-4) 3
STPU (1.5-9 x LTPU) 4 (3200A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 15 (12000A)
500 kcmil
20.0 ft
AATSEQ1 (E)0
Rm A-B140
480.0 V
AFIE 2.96 Cal/cm^2
Bolted Fault 33.877 kA
Voltage Drop 4.71 %
500 kcmil
10.0 ft
CB-400A A1SMT1
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.1 x P) 1 (400A)
LTD (1-4) 3
STPU (1.5-9 x LTPU) 9 (3600A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 10 (4000A)
250 kcmil
260.0 ft
MCB-500A A1SMLT1
GE
Frame/Model THJK
Sensor/Trip 500.0 A
Plug 500.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (5000A)
A1SMLT1
Rm D-1355
480.0 V
AFIE 0.75 Cal/cm^2
Bolted Fault 16.873 kA
Voltage Drop 4.57 %
STPU (1.5-9 x LTPU) 3.5 (700A)
STD (Min-Max) Min (I^s T Off)
2 AWG
4.0 ft
MCB-80A A8HN1
GE
Frame/Model TEY
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A8HN1
Rm A-8122
480.0 V
AFIE 0.08 Cal/cm^2
Bolted Fault 5.712 kA
Voltage Drop 4.57 %
2 AWG
20.0 ft
CB-100A A6LN4A
EATON/CUTLER-HAMMER
Frame/Model EDB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
CBL-0431
2 AWG
10.0 ft
A6LN4A
Rm A-6145
208.0 V
AFIE 1.21 Cal/cm^2
Bolted Fault 3.167 kA
Voltage Drop 4.57 %
M A
TC
H
LI
N
E S
H E
E T
E -6
-2
M A
TC
H
LI
N
E S
H E
E T
E -6
-1
MATCHLINE SHEET E-601-2
MATCHLINE SHEET E-601-8
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
N
R
C
O
N
S
T
R
U
C
T
I
O
N
N
R
C
O
N
S
T
R
U
C
T
I
O
N
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
Arc Flash Survey 583-19-206
Richard L. Roudebush VAMC 1481 W. 10th, St.
Indianapolis, IN 46202
19-303
Structural Engineer:
12/17/2020 40
E-601-2
BLDG 1 - AMS
JAV ABT
1 BLDG 1 - AMS
CB-400A AATSCR1 (E)
MV LOOP
S
P
TRANS AMS1
1000 kVA
Impedance 5.7499 %
Primary 13200 V
Secondary 480 V
TRANS AMS1 SEC
Rm A-B140
480.0 V
AFIE 71.29 Cal/cm^2
Bolted Fault 19.889 kA
Voltage Drop 1.48 %
750 kcmil
5.0 ft
MCB-1600A AMS1
GE
Frame/Model AKR-50
Sensor/Trip 1600.0 A
Plug 1600.0 A
Settings
LTPU (0.5-1.1 x P) 1 (1600A)
LTD (1-4) 1
STPU (1.5-9 x LTPU) 4 (6400A)
STD (Min-Max) Int (I^s T Off)
INST (1 x ST Rating) Fixed (50000A)
CB-400A A6HNDP2
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.1 x P) 1.1 (440A)
LTD (1-4) 1
STPU (1.5-9 x LTPU) 9 (3960A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 10 (4000A)
600 kcmil
220.0 ft
CB-500A AATSCR1 (N)
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 500.0 A
Settings
LTPU (0.5-1.1 x P) 0.9 (450A)
LTD (1-4) 3
STPU (1.5-9 x LTPU) 9 (4050A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 7 (3500A)
500 kcmil
30.0 ft
E N
AATSCR1
Position - Normal On
AATSCR1 (N)
Rm A-B140
480.0 V
AFIE 1.61 Cal/cm^2
Bolted Fault 17.902 kA
Voltage Drop 1.48 %
500 kcmil
10.0 ft
ABHCRDP1
Rm A-B140
480.0 V
AFIE 1.55 Cal/cm^2
Bolted Fault 17.323 kACB-100A ABHCR1-A4HCR3
CB-100A ABHCR3-A2HCR2 CB-200A ABT5
CB-800A TRANS ABT4
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.1 x P) 1 (800A)
LTD (1-4) 1
STPU (1.5-9 x LTPU) 3 (2400A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 15 (12000A)
500 kcmil
30.0 ft
S
P
TRANS ABT4
500 kVA
Impedance 5.8000 %
Primary 480 V
Secondary 208 V
TRANS ABT4 SEC
Rm A-B140
208.0 V
AFIE 3.22 Cal/cm^2
Bolted Fault 15.459 kA
Voltage Drop 1.48 %
500 kcmil
10.0 ft
MCB-2000A ABLNDP3
GE
Frame/Model TPS
Sensor/Trip 2000.0 A
Plug 2000.0 A
Settings
LTPU (Fixed) Fixed (2000A); Fixed
INST (LO-HI) HI (13400A)
MATCHLINE SHEET E-601-3
M A
TC
H
LI
N
E M
A
TC
H
LI
N E
MATCHLINE SHEET E-601-4
CB-ATS-1AB1(E)
NOTE
AMS1
Rm A-B140
480.0 V
AFIE 11.41 Cal/cm^2
Bolted Fault 19.876 kA
Voltage Drop 1.48 %
CB-800A ABHNDP1
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.1 x P) 1 (800A)
LTD (1-4) 1
STPU (1.5-9 x LTPU) 5 (4000A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 7 (5600A)
500 kcmil
15.0 ft
CB-ATS-1AB1
GE
Frame/Model AKR-30S
Sensor/Trip 600.0 A
Plug 600.0 A
Settings
LTPU/Current Setting 0.8; 0.5 (240A)
LTD (1-4) 1
INST (1.5-10 x S) 1.5 (900A)
600 kcmil
220.0 ft
EN
ATS-1AB1
Position - Normal On
ATS-1AB1 (N)
Rm A-B140
480.0 V
AFIE 0.95 Cal/cm^2
Bolted Fault 10.992 kA
Voltage Drop 1.48 %
CBL-0412
600 kcmil
220.0 ft
CB-PNL-ABHEQ5
GE
MATCHLINE SHEET E-601-3
MATCHLINE SHEET E-601-5
M A
TC
H
LI
N
E M
A
TC
H
LI
N E
ATS-1AB1 (E) AATSEQ4 (E)AATSCR1 (E)AATSEQ5 (E)AATSLS1 (E)AATSEQ2 (E)AATSEQ3 (E)AATSCR2 (E)AATSEQ7 (E)AATSEQ6 (E)AATSEQ1 (E)
GEN 1A
680 kW
480 V
GEN 2A
680 kW
480 V
500 kcmil
60.0 ft
GEN 1 A-WING
Rm
480.0 V
AFIE 29.24 Cal/cm^2
Bolted Fault 21.020 kA
Voltage Drop 0.00 %
GEN 2 A-WING
Rm
480.0 V
AFIE 29.53 Cal/cm^2
Bolted Fault 21.488 kA
Voltage Drop 0.00 %
500 kcmil
20.0 ft
CB-1200A GEN 1A
SIEMENS
Frame/Model RL-1600
Sensor/Trip 1200.0 A
Plug 1200.0 A
Settings
LTPU (0.5-1.0 x S) 0.95 (1140A)
LTD (3.5-30 Sec.) 17
STPU (2-12 x LTPU) 6 (6840A)
STD (0.08-0.4 Sec.) 0.22 (I^s T Off)
INST (2-15 x S) 15 (18000A)
CB-1200A GEN 2A
SIEMENS
Frame/Model RL-1600
Sensor/Trip 1200.0 A
Plug 1200.0 A
Settings
LTPU (0.5-1.0 x S) 0.95 (1140A)
LTD (3.5-30 Sec.) 17
STPU (2-12 x LTPU) 6 (6840A)
STD (0.08-0.4 Sec.) 0.22 (I^s T Off)
INST (2-15 x S) 15 (18000A)
ABHEDP1
Rm A-B138
480.0 V
AFIE 55.29 Cal/cm^2
Bolted Fault 21.730 kA
Voltage Drop 0.00 %
CB-400A AATSCR1 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.0 x S) 0.75 (300A)
LTD (3.5-30 Sec.) 30
STPU (2-12 x LTPU) 8 (2400A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (6000A)
CB-400A AATSLS1 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.0 x S) 0.75 (300A)
LTD (3.5-30 Sec.) 30
STPU (2-12 x LTPU) 8 (2400A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (6000A)
CB-800A AATSEQ1 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.0 x S) 1 (800A)
LTD (3.5-30 Sec.) 3.5
STPU (2-12 x LTPU) 2 (1600A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (12000A)
CB-400A AATSEQ5 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.0 x S) 0.75 (300A)
LTD (3.5-30 Sec.) 17
STPU (2-12 x LTPU) 5 (1500A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (6000A)
CB-600A AATSEQ2 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 600.0 A
Plug 600.0 A
Settings
LTPU (0.5-1.0 x S) 1 (600A)
LTD (3.5-30 Sec.) 6
STPU (2-12 x LTPU) 3 (1800A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (9000A)
CB-600A AATSEQ3 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 600.0 A
Plug 600.0 A
Settings
LTPU (0.5-1.0 x S) 1 (600A)
LTD (3.5-30 Sec.) 6
STPU (2-12 x LTPU) 3 (1800A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (9000A)
CB-600A AATSEQ4 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 600.0 A
Plug 600.0 A
Settings
LTPU (0.5-1.0 x S) 1 (600A)
LTD (3.5-30 Sec.) 6
STPU (2-12 x LTPU) 4 (2400A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (9000A)
CB-400A AATSCR2 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
LTPU (0.5-1.0 x S) 1 (400A)
LTD (3.5-30 Sec.) 10
STPU (2-12 x LTPU) 4 (1600A)
STD (0.08-0.4 Sec.) 0.08 (I^s T Off)
INST (2-15 x S) 15 (6000A)
CB-800A AATSEQ7 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.0 x S) 0.5 (400A)
LTD (3.5-30 Sec.) 3.5
STPU (2-12 x LTPU) 2 (800A)
STD (0.08-0.4 Sec.) 0.22 (I^s T Off)
INST (2-15 x S) 2 (1600A)
CB-800A AATSEQ6 (E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.0 x S) 0.5 (400A)
LTD (3.5-30 Sec.) 3.5
STPU (2-12 x LTPU) 2 (800A)
STD (0.08-0.4 Sec.) 0.22 (I^s T Off)
INST (2-15 x S) 2 (1600A)
CB-1600A
SQUARE D
Frame/Model NW16-LF
Sensor/Trip 1600.0 A
Plug 1600.0 A
Settings
LTPU/LTD (A 0.4-1.0 x S) 1 (1600A); 0.5
STPU (1.5-10 x LTPU) 3 (4800A)
STD (INST-0.4) 0.1 (I^s T On)
INST OR Fixed (24000A)
CBL-0415
400 kcmil
60.0 ft
GEN 3A-WING
Rm
480.0 V
AFIE 46.17 Cal/cm^2
Bolted Fault 21.637 kA
Voltage Drop 0.00 %
GEN 3A
1000 kW
480 V
CB-ATS-1AB1(E)
SIEMENS
Frame/Model RL-800
Sensor/Trip 800.0 A
Plug 800.0 A
Settings
LTPU (0.5-1.0 x S) 1 (800A)
LTD (3.5-30 Sec.) 3.5
STPU (2-12 x LTPU) 2 (1600A)
STD (0.08-0.4 Sec.) 0.4 (I^s T Off)
INST (2-15 x S) 4 (3200A)
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
N
R
C
O
N
S
T
R
U
C
T
I
O
N
N
R
C
O
N
S
T
R
U
C
T
I
O
N
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
Arc Flash Survey 583-19-206
Richard L. Roudebush VAMC 1481 W. 10th, St.
Indianapolis, IN 46202
19-303
Structural Engineer:
12/17/2020 40
E-601-3
BLDG 1 - AMS
1 BLDG 1 - AMS
CB-50A AATSCR4
CB-50A AATSCR3
MCB-400A A6HNDP2
GE
Frame/Model TJJ
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
A6HNDP2
Rm A-6075
480.0 V
AFIE 0.52 Cal/cm^2
Bolted Fault 10.992 kA
Voltage Drop 1.48 %
CB-150A AATSCR4 (N)
GE
Frame/Model TED
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Fixed
4/0 AWG
50.0 ft
E N
AATSCR4
Position - Normal On
AATSCR4 (N)
Rm A-6120
480.0 V
AFIE 0.31 Cal/cm^2
Bolted Fault 9.668 kA
Voltage Drop 1.48 %
CB-125A AATSCR3 (N)
GE
Frame/Model TED
Sensor/Trip 125.0 A
Plug 125.0 A
Settings
Fixed
4/0 AWG
120.0 ft
E N
AATSCR3
Position - Normal On
AATSCR3 (N)
Rm A-6125
480.0 V
AFIE 0.26 Cal/cm^2
Bolted Fault 8.218 kA
Voltage Drop 1.48 %
1 AWG
5.0 ft
CB-125A CB1
GE
Frame/Model SEHA
Sensor/Trip 125.0 A
Plug 125.0 A
Settings
MAX
ECB-125A CB1
Rm A-6120
480.0 V
AFIE 0.31 Cal/cm^2
Bolted Fault 9.476 kA
Voltage Drop 1.48 %
1 AWG
5.0 ft
CB-125A CB
GE
Frame/Model SEHA
Sensor/Trip 125.0 A
Plug 125.0 A
Settings
MAX
ECB-125A CB
Rm A-6125
480.0 V
AFIE 0.26 Cal/cm^2
Bolted Fault 8.068 kA
Voltage Drop 1.48 %
500 kcmil
10.0 ft
ABHCRDP1
Rm A-B140
480.0 V
AFIE 1.55 Cal/cm^2
Bolted Fault 17.323 kA
Voltage Drop 1.48 %
CB-100A ABHCR1-A4HCR3
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
160.0 ft
2 AWG
4.0 ft
MCB-80A ABHCR1
GE
Frame/Model TEY
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
ABHCR1
Rm A-B153
480.0 V
AFIE 0.16 Cal/cm^2
Bolted Fault 6.238 kA
Voltage Drop 1.48 %
2 AWG
20.0 ft
2 AWG
4.0 ft
MCB-80A A1HCR1
GE
Frame/Model TEY
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A1HCR1
Rm A-1486
480.0 V
AFIE 0.15 Cal/cm^2
Bolted Fault 5.723 kA
Voltage Drop 1.48 %
2 AWG
20.0 ft
2 AWG
4.0 ft
MCB-80A A2HCR1
GE
Frame/Model TEY
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2HCR1
Rm A-2148
480.0 V
AFIE 0.14 Cal/cm^2
Bolted Fault 5.283 kA
Voltage Drop 1.48 %
2 AWG
40.0 ft
2 AWG
4.0 ft
MCB-60A A4HCR1
GE
Frame/Model TEY
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
A4HCR1
Rm A-4173
480.0 V
AFIE 0.12 Cal/cm^2
Bolted Fault 4.574 kA
Voltage Drop 1.48 %
2 AWG
160.0 ft
MCB-60A A4HCR3
GE
Frame/Model TEY
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
A4HCR3
Rm A-4064
480.0 V
AFIE 0.8 Cal/cm^2
Bolted Fault 2.988 kA
Voltage Drop 1.48 %
CB-100A ABHCR3-A2HCR2
GE
Frame/Model SFHA
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
MAX
2 AWG
40.0 ft
2 AWG
4.0 ft
MCB-80A ABHCR3
GE
Frame/Model TEY
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
ABHCR3
Rm A-B147
480.0 V
AFIE 0.35 Cal/cm^2
Bolted Fault 12.591 kA
Voltage Drop 1.48 %
2 AWG
120.0 ft
2 AWG
5.0 ft
MCB-60A A1HCR2
GE
Frame/Model TEY
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
A1HCR2
Rm A-1275
480.0 V
AFIE 0.16 Cal/cm^2
Bolted Fault 6.210 kA
Voltage Drop 1.48 %
2 AWG
180.0 ft
MCB-60A A2HCR2
GE
Frame/Model TEY
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
A2HCR2
Rm A-2057
480.0 V
AFIE 0.1 Cal/cm^2
Bolted Fault 3.450 kA
Voltage Drop 1.48 %
CB-200A ABT5
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX3/0 AWG
10.0 ft
S
P
TRANS ABT5
112.5 kVA
Impedance 4.9000 %
Primary 480 V
Secondary 208 V
TRANS ABT5 SEC
Rm A-B140
208.0 V
AFIE 2.63 Cal/cm^2
Bolted Fault 5.475 kA
Voltage Drop 1.48 %
500 kcmil
10.0 ft
MCB-400A ABLCRDP1
GE
Frame/Model TJJ
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
ABLCRDP1
Rm A-B140
208.0 V
AFIE 2.56 Cal/cm^2
Bolted Fault 5.347 kA
Voltage Drop 1.48 %
CB-225A A4LCR1-5
GE
Frame/Model TQD
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
4/0 AWG
240.0 ft
4/0 AWG
6.0 ft
MCB-150A A4LCR1
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A4LCR1
Rm A-4173
208.0 V
AFIE 1.31 Cal/cm^2
Bolted Fault 2.977 kA
Voltage Drop 1.48 %
4/0 AWG
160.0 ft
4/0 AWG
6.0 ft
MCB-150A A4LCR3
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A4LCR3
Rm A-4064
208.0 V
AFIE 0.96 Cal/cm^2
Bolted Fault 2.277 kA
Voltage Drop 1.48 %
4/0 AWG
1.0 ft
4/0 AWG
6.0 ft
MCB-150A A4LCR4
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A4LCR4
Rm A-4064
208.0 V
AFIE 0.96 Cal/cm^2
Bolted Fault 2.274 kA
Voltage Drop 1.48 %
4/0 AWG
6.0 ft
MCB-200A A4LCR5
GE
Frame/Model TFJ
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (2000A)
A4LCR5
Rm A-4064
208.0 V
AFIE 1.31 Cal/cm^2
Bolted Fault 2.977 kA
Voltage Drop 1.48 %
CB-100A A1LCR2-A4LCR2
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
140.0 ft
2 AWG
4.0 ft
MCB-80A A1LCR2
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A1LCR2
Rm A-1275
208.0 V
AFIE 1.12 Cal/cm^2
Bolted Fault 2.589 kA
Voltage Drop 1.48 %
2 AWG
120.0 ft
2 AWG
4.0 ft
MCB-80A A1LCR5
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A1LCR5
Rm A-1250
208.0 V
AFIE 0.7 Cal/cm^2
Bolted Fault 1.712 kA
Voltage Drop 1.48 %
2 AWG
20.0 ft
2 AWG
4.0 ft
MCB-100A A2LCR2
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
A2LCR2
Rm A-2057
208.0 V
AFIE 0.65 Cal/cm^2
Bolted Fault 1.619 kA
Voltage Drop 1.48 %
2 AWG
40.0 ft
MCB-80A A4LCR2
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A4LCR2
Rm A-4097
208.0 V
AFIE 0.59 Cal/cm^2
Bolted Fault 1.473 kA
Voltage Drop 1.48 %
CB-200A ABLCR2-A2LCR4
GE
Frame/Model THQD
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Fixed
4/0 AWG
40.0 ft
4/0 AWG
4.0 ft
MCB-150A ABLCR2
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
ABLCR2
Rm A-B147
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 4.721 kA
Voltage Drop 1.48 %
4/0 AWG
20.0 ft
4/0 AWG
20.0 ft
4/0 AWG
4.0 ft
MCB-150A A2LCR3
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A2LCR3
Rm A-2117
208.0 V
AFIE 1.71 Cal/cm^2
Bolted Fault 4.249 kA
Voltage Drop 1.48 %
4/0 AWG
6.0 ft
MCB-150A A2LCR4
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A2LCR4
Rm A-2117
208.0 V
AFIE 1.7 Cal/cm^2
Bolted Fault 4.228 kA
Voltage Drop 1.48 %
A1LCR6
Rm A-1450
208.0 V
AFIE 1.81 Cal/cm^2
Bolted Fault 4.474 kA
Voltage Drop 1.48 %
MCB-150A A1LCR6
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
4/0 AWG
4.0 ft
CB-200A ABLCR1-A2LCR1
GE
Frame/Model THQD
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Fixed
4/0 AWG
160.0 ft
4/0 AWG
4.0 ft
MCB-150A ABLCR1
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
ABLCR1
Rm A-B153
208.0 V
AFIE 1.59 Cal/cm^2
Bolted Fault 3.519 kA
Voltage Drop 1.48 %
4/0 AWG
20.0 ft
2 AWG
120.0 ft
4/0 AWG
20.0 ft
MCB-150A A2LCR1
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A2LCR1
Rm A-2148
208.0 V
AFIE 1.45 Cal/cm^2
Bolted Fault 3.260 kA
Voltage Drop 1.48 %
A1LCR1
Rm A-1486
208.0 V
AFIE 1.5 Cal/cm^2
Bolted Fault 3.356 kA
Voltage Drop 1.48 %
MCB-100A A1LCR1
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
3.0 ft
A1LCR3
Rm D-1355
208.0 V
AFIE 0.88 Cal/cm^2
Bolted Fault 2.110 kA
Voltage Drop 1.48 %
MCB-80A A1LCR3
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
2 AWG
3.0 ft
A1LCR4
Rm A-1124
208.0 V
AFIE 0.6 Cal/cm^2
Bolted Fault 1.505 kA
Voltage Drop 1.48 %
MCB-100A A1LCR4
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
120.0 ft
CB-225A A4HCR2
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
160.0 ft
MCB-200A A4HCR2
GE
Frame/Model TFJ
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (2000A)
A4HCR2
Rm A-4097
480.0 V
AFIE 0.39 Cal/cm^2
Bolted Fault 10.164 kA
Voltage Drop 1.48 %
MCB-2000A ABLNDP3
GE
Frame/Model TPS
Sensor/Trip 2000.0 A
Plug 2000.0 A
Settings
LTPU (Fixed) Fixed (2000A); Fixed
INST (LO-HI) HI (13400A)
CB-225A ABLN8,9
GE
Frame/Model SFHA
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
MAX
4/0 AWG
120.0 ft
4/0 AWG
5.0 ft
MCB-225A ABLN9
GE
Frame/Model TFJ
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (2250A)
ABLN9
Rm A-B104
208.0 V
AFIE 0.19 Cal/cm^2
Bolted Fault 7.106 kA
Voltage Drop 1.48 %
4/0 AWG
10.0 ft
MCB-200A ABLN8
GE
Frame/Model TFJ
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (2000A)
ABLN8
Rm A-B103
208.0 V
AFIE 0.17 Cal/cm^2
Bolted Fault 6.948 kA
Voltage Drop 1.48 %
CB-200A ABLN11, 10
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
3/0 AWG
180.0 ft
3/0 AWG
4.0 ft
MCB-175A ABLN10
GE
Frame/Model TFJ
Sensor/Trip 175.0 A
Plug 175.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1750A)
ABLN10
Rm CORR. CB25
208.0 V
AFIE 1.62 Cal/cm^2
Bolted Fault 5.048 kA
Voltage Drop 1.48 %
3/0 AWG
6.0 ft
MCB-175A ABLN11
GE
Frame/Model TFJ
Sensor/Trip 175.0 A
Plug 175.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1750A)
ABLN11
Rm CORR. CB25
208.0 V
AFIE 1.63 Cal/cm^2
Bolted Fault 5.009 kA
Voltage Drop 1.48 %
CB-400A ABLNDP1
GE
Frame/Model TJK
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
500 kcmil
160.0 ft
MCB-400A ABLNDP1
GE
Frame/Model TJJ
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
2 AWG
20.0 ft
CB-50A ABLCR2-A
GE
Frame/Model THHQB
Sensor/Trip 50.0 A
Plug 50.0 A
Settings
Fixed
8 AWG
50.0 ft
MCB-100A ABLCR2-A
CUTLER-HAMMER
Frame/Model FB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
ABLCR2-A
Rm B-B034
208.0 V
AFIE 0.89 Cal/cm^2
Bolted Fault 2.115 kA
Voltage Drop 1.48 %
CB-60A UPS
GE
Frame/Model THHQB
Sensor/Trip 60.0 A
Plug 60.0 A
Settings
Fixed
UPSA2
20.0000
6 AWG
4.0 ft
CBL-0424
6 AWG
2.0 ft
UPSA2 SEC
Rm
208.0 V
AFIE 0 Cal/cm^2
Bolted Fault 0.001 kA
Voltage Drop 1.48 %
UPSBA2
Rm A-1450
208.0 V
AFIE 0 Cal/cm^2
Bolted Fault 0.001 kA
Voltage Drop 1.48 %
MCB-80A
GE
Frame/Model TFJ
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Thermal Curve (Fixed)
Thermal Curve (Fixed)
2 AWG
160.0 ft
12 AWG
160.0 ft
MCB-20A A5HEMCC3
GE
Frame/Model TEY
Sensor/Trip 20.0 A
Plug 20.0 A
Settings
Fixed
A5HEMCC3
Rm A-5001
480.0 V
AFIE 0.33 Cal/cm^2
Bolted Fault 0.717 kA
Voltage Drop 1.48 %
MATCHLINE SHEET E-601-3
MATCHLINE SHEET E-601-4
M A
TC
H
LI
N
E S
H E
E T
E -6
-4
M A
TC
H
LI
N
E S
H E
E T
E -6
-5
MATCHLINE SHEET E-601-4
MATCHLINE SHEET E-601-9
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
N
R
C
O
N
S
T
R
U
C
T
I
O
N
N
R
C
O
N
S
T
R
U
C
T
I
O
N
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
Arc Flash Survey 583-19-206
Richard L. Roudebush VAMC 1481 W. 10th, St.
Indianapolis, IN 46202
19-303
Structural Engineer:
12/17/2020 40
E-601-4
BLDG 1 - AMS
1 BLDG 1 - AMS
CB-150A AATSLS1 (N)CB-400A AATSLS1 (E)
ABLNDP3
Rm A-B140
208.0 V
AFIE 7.24 Cal/cm^2
Bolted Fault 15.257 kA
Voltage Drop 1.48 %
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1750A)
INST (4.5-10 x Trip) HI (1750A)
CB-400A ABLNDP1
GE
Frame/Model TJK
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
500 kcmil
160.0 ft
MCB-400A ABLNDP1
GE
Frame/Model TJJ
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
MCB-150A ABLN5
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
ABLN5
Rm A-B147
208.0 V
AFIE 0.19 Cal/cm^2
Bolted Fault 8.282 kA
Voltage Drop 1.48 %
3/0 AWG
2.0 ft
MCB-100A ABLN6
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
ABLN6
Rm A-B147
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 7.779 kA
Voltage Drop 1.48 %
1 AWG
8.0 ft
CB-400A ABLNDP2
GE
Frame/Model TJK
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
500 kcmil
100.0 ft
MCB-350A ABLNDP2
GE
Frame/Model TJJ
Sensor/Trip 350.0 A
Plug 350.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (3500A)
ABLNDP2
Rm A-B090
208.0 V
AFIE 4.1 Cal/cm^2
Bolted Fault 9.121 kA
Voltage Drop 1.48 %
CB-100A ABLN15
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
20.0 ft
MCB-80A ABLN15
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
ABLN15
Rm A-B090
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 7.497 kA
Voltage Drop 1.48 %
CB-100A ABLN2
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
20.0 ft
MCB-80A ABLN2
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
ABLN2
Rm A-B090
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 7.497 kA
Voltage Drop 1.48 %
CB-100A A1LN5,6
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
120.0 ft
MCB-80A A1LN5
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A1LN5
Rm A-1250
208.0 V
AFIE 1.54 Cal/cm^2
Bolted Fault 3.426 kA
Voltage Drop 1.48 %
CB-100A A1LN2,12
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
20.0 ft
MCB-90A A1LN12
GE
Frame/Model THHQB
Sensor/Trip 90.0 A
Plug 90.0 A
Settings
Fixed
A1LN12
Rm A-1275
208.0 V
AFIE 0.12 Cal/cm^2
Bolted Fault 7.140 kA
Voltage Drop 1.48 %
2 AWG
5.0 ft
MCB-90A A1LN2
GE
Frame/Model THHQB
Sensor/Trip 90.0 A
Plug 90.0 A
Settings
Fixed
A1LN2
Rm A-1275
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 7.352 kA
Voltage Drop 1.48 %
2 AWG
2.0 ft
MCB-80A A1LN6
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A1LN6
Rm A-1250
208.0 V
AFIE 1.51 Cal/cm^2
Bolted Fault 3.368 kA
Voltage Drop 1.48 %
2 AWG
5.0 ft2 AWG
2.0 ft
CB-225A ABLN3,3A
Frame/Model
Sensor/Trip 0.0 A
Plug 0.0 A
Settings
1/0 AWG
80.0 ft
MCB-150A ABLN3
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
ABLN3
Rm A-B104
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 5.274 kA
Voltage Drop 1.48 %
1/0 AWG
4.0 ft
ABLN3A
Rm A-B104
208.0 V
AFIE 2.52 Cal/cm^2
Bolted Fault 5.274 kA
Voltage Drop 1.48 %
1/0 AWG
4.0 ft
CB-400A A2LNDP1
GE
Frame/Model TJK
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
500 kcmil
200.0 ft
MCB-400A A2LNDP1
GE
Frame/Model TJJ
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
A2LNDP1
Rm A-2148
208.0 V
AFIE 3.19 Cal/cm^2
Bolted Fault 6.464 kA
Voltage Drop 1.48 %
CB-100A A2LN4
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
120.0 ft
MCB-80A A2LN4
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2LN4
Rm A-2003A
208.0 V
AFIE 1.33 Cal/cm^2
Bolted Fault 3.022 kA
Voltage Drop 1.48 %
CB-100A NEW PNL LIBRARY ED4
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
CB-100A A2LN5,9
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed2 AWG
120.0 ft
MCB-80A A2LN5
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2LN5
Rm A-2087
208.0 V
AFIE 1.32 Cal/cm^2
Bolted Fault 2.992 kA
Voltage Drop 1.48 %
MCB-80A A2LN9
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2LN9
Rm A-2097
208.0 V
AFIE 1.3 Cal/cm^2
Bolted Fault 2.963 kA
Voltage Drop 1.48 %
2 AWG
4.0 ft2 AWG
2.0 ft
CB-225A A4LN4-6
GE
Frame/Model THQD
Sensor/Trip 225.0 A
Plug 225.0 A
Settings
Fixed
4/0 AWG
180.0 ft
MCB-150A A4LN4
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A4LN4
Rm A-4064
208.0 V
AFIE 1.68 Cal/cm^2
Bolted Fault 3.701 kA
Voltage Drop 1.48 %
MCB-150A A4LN6
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A4LN6
Rm A-4064
208.0 V
AFIE 1.67 Cal/cm^2
Bolted Fault 3.684 kA
Voltage Drop 1.48 %
4/0 AWG
6.0 ft
4/0 AWG
2.0 ft
4/0 AWG
2.0 ft
MCB-150A A4LN5
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A4LN5
Rm A-4064
208.0 V
AFIE 1.66 Cal/cm^2
Bolted Fault 3.666 kA
Voltage Drop 1.48 %
4/0 AWG
6.0 ft
CB-100A A3LN1-A5LN2
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
20.0 ft
MCB-80A A5LN1
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A5LN1
Rm A-5007
208.0 V
AFIE 1.68 Cal/cm^2
Bolted Fault 4.182 kA
Voltage Drop 1.48 %
MCB-80A A3LN1
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A3LN1
Rm A-3006
208.0 V
AFIE 0.1 Cal/cm^2
Bolted Fault 5.422 kA
Voltage Drop 1.48 %
2 AWG
4.0 ft
2 AWG
2.0 ft
2 AWG
20.0 ft
MCB-80A A4LN1
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A4LN1
Rm A-4173
208.0 V
AFIE 0.1 Cal/cm^2
Bolted Fault 4.708 kA
Voltage Drop 1.48 %
2 AWG
4.0 ft
2 AWG
20.0 ft
MCB-80A A5LN2
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A5LN2
Rm A-5007
208.0 V
AFIE 1.65 Cal/cm^2
Bolted Fault 4.129 kA
Voltage Drop 1.48 %
2 AWG
4.0 ft
CB-100A A2LN1,8
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
20.0 ft
MCB-90A A2LN8
GE
Frame/Model THHQB
Sensor/Trip 90.0 A
Plug 90.0 A
Settings
Fixed
A2LN8
Rm A-2148
208.0 V
AFIE 0.11 Cal/cm^2
Bolted Fault 5.344 kA
Voltage Drop 1.48 %
MCB-80A A2LN1
GE
Frame/Model THHQB
Sensor/Trip 90.0 A
Plug 90.0 A
Settings
Fixed
A2LN1
Rm A-2148
208.0 V
AFIE 0.11 Cal/cm^2
Bolted Fault 5.422 kA
Voltage Drop 1.48 %
2 AWG
4.0 ft
2 AWG
6.0 ft
CB-400A A2LNDP2
GE
Frame/Model TJK
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
500 kcmil
140.0 ft
MCB-400A A2LNDP2
GE
Frame/Model TJJ
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
A2LNDP2
Rm A-2057
208.0 V
AFIE 3.97 Cal/cm^2
Bolted Fault 7.837 kA
Voltage Drop 1.48 %
CB-100A A2LN6,7
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed2 AWG
120.0 ft
MCB-80A A2LN6
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2LN6
Rm A-2117
208.0 V
AFIE 1.44 Cal/cm^2
Bolted Fault 3.239 kA
Voltage Drop 1.48 %
MCB-80A A2LN7
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2LN7
Rm A-2117
208.0 V
AFIE 1.42 Cal/cm^2
Bolted Fault 3.205 kA
Voltage Drop 1.48 %
2 AWG
4.0 ft2 AWG
2.0 ft
CB-100A A2LN10,11
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
20.0 ft
MCB-80A A2LN10
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2LN10
Rm A-2057
208.0 V
AFIE 0.11 Cal/cm^2
Bolted Fault 6.480 kA
Voltage Drop 1.48 %
MCB-80A A2LN11
GE
Frame/Model THHQB
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
A2LN11
Rm A-2057
208.0 V
AFIE 0.1 Cal/cm^2
Bolted Fault 6.156 kA
Voltage Drop 1.48 %
2 AWG
8.0 ft
2 AWG
2.0 ft
CB-100A A2LN2,3
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
12.0 ft
MCB-90A A2LN2
GE
Frame/Model THHQB
Sensor/Trip 90.0 A
Plug 90.0 A
Settings
Fixed
A2LN2
Rm A-2057
208.0 V
AFIE 0.12 Cal/cm^2
Bolted Fault 6.945 kA
Voltage Drop 1.48 %
MCB-100A A2LN3
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
A2LN3
Rm A-2057
208.0 V
AFIE 0.12 Cal/cm^2
Bolted Fault 5.953 kA
Voltage Drop 1.48 %
2 AWG
20.0 ft
2 AWG
2.0 ft
MCB-100A A4LN2
GE
Frame/Model THHQB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
A4LN2
Rm A-4097
208.0 V
AFIE 0.12 Cal/cm^2
Bolted Fault 6.053 kA
Voltage Drop 1.48 %
2 AWG
30.0 ft
CB-80A A4LN2
GE
Frame/Model THED
Sensor/Trip 80.0 A
Plug 80.0 A
Settings
Fixed
CB-200A ABLN12
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
3/0 AWG
170.0 ft
MCB-150A ABLN12
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
ABLN12
Rm A-B106
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 5.339 kA
Voltage Drop 1.48 %
CB-200A ABLN13
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
3/0 AWG
170.0 ft
MCB-175A ABLN13
GE
Frame/Model TFK
Sensor/Trip 175.0 A
Plug 175.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1750A)
ABLN13
Rm A-B106
208.0 V
AFIE 0.15 Cal/cm^2
Bolted Fault 5.339 kA
Voltage Drop 1.48 %
CB-175A ABLN5,6
GE
Frame/Model SFHA
Sensor/Trip 175.0 A
Plug 175.0 A
Settings
MAX
3/0 AWG
80.0 ft
CB-175A ABLN14
GE
Frame/Model SFHA
Sensor/Trip 175.0 A
Plug 175.0 A
Settings
MAX
3/0 AWG
170.0 ft
MCB-150A ABLN14
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
ABLN14
Rm A-B107
208.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 5.339 kA
Voltage Drop 1.48 %
CB-150A A1LN7, A1LN8
GE
Frame/Model SFHA
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
MAX
1/0 AWG
50.0 ft
MCB-150A A1LN8
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A1LN8
Rm A-1411
208.0 V
AFIE 1.18 Cal/cm^2
Bolted Fault 3.984 kA
Voltage Drop 1.48 %
1/0 AWG
130.0 ft
1/0 AWG
2.0 ft
MCB-150A A1LN7
GE
Frame/Model TFJ
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
Thermal Curve (Fixed)
INST (4.5-10 x Trip) HI (1500A)
A1LN7
Rm
208.0 V
AFIE 0.2 Cal/cm^2
Bolted Fault 8.822 kA
Voltage Drop 1.48 %
AATSLS1 (N)
Rm A-B140
480.0 V
AFIE 0.53 Cal/cm^2
Bolted Fault 12.042 kA
Voltage Drop 1.48 %
E N
AATSLS1
Position - Normal On
1/0 AWG
10.0 ft
MCB-150A ABHLS3
GE
Frame/Model SFHA
Sensor/Trip 150.0 A
Plug 150.0 A
Settings
MAX
6 AWG
100.0 ft
6 AWG
20.0 ft
CB-100A ABHLS1-A4HLS3
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
160.0 ft
2 AWG
4.0 ft
MCB-80A ABHLS1
2 AWG
20.0 ft
CBL-0412
600 kcmil
220.0 ft
PNL-ABHEQ5
Rm A-B148
480.0 V
AFIE 0.41 Cal/cm^2
Bolted Fault 7.551 kA
Voltage Drop 1.48 %
CB-PNL-ABHEQ5
GE
Frame/Model SGHA
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
MAX
CB-TX-ABLEQ5
GE
Frame/Model SFHA
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
MAX
CBL-0418
3/0 AWG
5.0 ft
S
P
TX-ABLEQ5
112.5 kVA
Impedance 5.1000 %
Primary 480 V
Secondary 208 V
TX-ABLEQ5-SEC
Rm A-B148
208.0 V
AFIE 2.12 Cal/cm^2
Bolted Fault 4.533 kA
Voltage Drop 1.48 %
CBL-0419
500 kcmil
10.0 ft
CB-PNL-ABLEQ5
GE
Frame/Model SGHA
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
MAX
PNL-ABLEQ5
Rm A-B148
208.0 V
AFIE 2.08 Cal/cm^2
Bolted Fault 4.462 kA
Voltage Drop 1.48 %
CBL-0421
1/0 AWG
2.0 ft
1/0 AWG
50.0 ft
CBL-0425
2 AWG
5.0 ft
CB-A2LN12
EATON/CUTLER-HAMMER
Frame/Model BAB
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
PNL-A2LN12
Rm A-2003A
208.0 V
AFIE 0.05 Cal/cm^2
Bolted Fault 6.252 kA
Voltage Drop 1.48 % MATCHLINE SHEET E-601-5
MATCHLINE SHEET E-601-10
M A
TC
H
LI
N
E S
H E
E T
E -6
-5
M A
TC
H
LI
N
E S
H E
E T
E -6
-4
MATCHLINE SHEET E-601-5
MATCHLINE SHEET E-601-3
MATCHLINE SHEET E-601-5
MATCHLINE SHEET E-601-10
VA PROJECT NUMBER
Building Number
Drawing Number
Project Title
Date Checked Drawn
Drawing Title
Approved:
VA FORM 08-6231
A
B C
D E
21 4 5 6 7
321 4 5 6 7
A B
C D
E
Dwg. of
LocationLocation
Office of Construction and Facilities Management
PROJECT MANAGER: ACG Project Number
N
R
C
O
N
S
T
R
U
C
T
I
O
N
N
R
C
O
N
S
T
R
U
C
T
I
O
N
CONSULTANTS:
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 NC License #: C-1848
U.S. Department of Veterans Affairs
© COPYRIGHT Apogee Consulting Group, P.A.Revisions: Date#
Arc Flash Survey 583-19-206
Richard L. Roudebush VAMC 1481 W. 10th, St.
Indianapolis, IN 46202
19-303
Structural Engineer:
12/17/2020 40
E-601-5
BLDG 1 - AMS
1 BLDG 1 - AMS
SCALE: NTS
JAV ABT
bbrowning Text Box bbrowning Text Box bbrowning Text Box
CB-600A AATSEQ4 (E)
CB-400A AATSEQ5 (E)
CB-600A AATSEQ2 (E)
CB-600A AATSEQ3 (E)
MV LOOP
F5NMCC1? COULDNT OPEN
S
P
TRANS AMS2
1000 kVA
Impedance 5.7499 %
Primary 13200 V
Secondary 480 V
TRANS AMS2 SEC
Rm A-B140
480.0 V
AFIE 71.81 Cal/cm^2
Bolted Fault 23.310 kA
Voltage Drop 3.71 %
750 kcmil
5.0 ft
MCB-1600A AMS2
GE
Frame/Model AKR-50
Sensor/Trip 1600.0 A
Plug 1600.0 A
Settings
LTPU (0.5-1.1 x P) 1 (1600A)
LTD (1-4) 2
STPU (1.5-9 x LTPU) 5 (8000A)
STD (Min-Max) Int (I^s T Off)
INST (1 x ST Rating) Fixed (50000A)
AMS2
Rm A-B140
480.0 V
AFIE 11.93 Cal/cm^2
Bolted Fault 23.297 kA
Voltage Drop 3.71 %
CB-600A AATSEQ5 (N)
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 600.0 A
Settings
LTPU (0.5-1.1 x P) 0.5 (300A)
LTD (1-4) 4
STPU (1.5-9 x LTPU) 1.5 (450A)
STD (Min-Max) Min (I^s T On)
INST (1.5-15 x P) 10 (6000A)
500 kcmil
35.0 ft
AATSEQ5 (N)
Rm
480.0 V
AFIE 1.84 Cal/cm^2
Bolted Fault 20.409 kA
Voltage Drop 3.79 %
E N
AATSEQ5
Position - Normal On
500 kcmil
200.0 ft
MCB-300A A6HEMCC1
EATON/CUTLER-HAMMER
Frame/Model HKD
Sensor/Trip 300.0 A
Plug 300.0 A
Settings
Thermal Curve (Fixed)
INST (5-10 x Trip) 10 (3000A)
A6HEMCC1
Rm A-6144
480.0 V
AFIE 0.25 Cal/cm^2
Bolted Fault 11.913 kA
Voltage Drop 4.26 %
CB-100A SF42
EATON/CUTLER-HAMMER
Frame/Model HMCP
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
INST (300-1000A) G (900A)
4 AWG
60.0 ft
MTR-SF42
50 hp
SF42
Rm
480.0 V
AFIE 0.19 Cal/cm^2
Bolted Fault 7.542 kA
Voltage Drop 4.67 %
500 kcmil
30.0 ft
A6EMCC1
Rm A-6144
480.0 V
AFIE 0.24 Cal/cm^2
Bolted Fault 11.180 kA
Voltage Drop 4.30 %
CB-70A SF46
GE
Frame/Model SELA
Sensor/Trip 70.0 A
Plug 70.0 A
Settings
MAX
2 AWG
60.0 ft
MTR-SF46
30 hp
SF46
Rm
480.0 V
AFIE 0.21 Cal/cm^2
Bolted Fault 8.238 kA
Voltage Drop 4.46 %
CB-50A RF46
GE
Frame/Model SELA
Sensor/Trip 50.0 A
Plug 50.0 A
Settings
MAX
6 AWG
60.0 ft
MTR-RF46
20 hp
RF46
Rm
480.0 V
AFIE 0.21 Cal/cm^2
Bolted Fault 5.841 kA
Voltage Drop 4.55 %
CB-600A AATSEQ2 (N)
GE
Frame/Model AKR-30H
Sensor/Trip 800.0 A
Plug 600.0 A
Settings
LTPU (0.5-1.1 x P) 1 (600A)
LTD (1-4) 4
STPU (1.5-9 x LTPU) 9 (5400A)
STD (Min-Max) Min (I^s T Off)
INST (1.5-15 x P) 15 (9000A)
350 kcmil
45.0 ft
AATSEQ2 (N)
Rm
480.0 V
AFIE 1.92 Cal/cm^2
Bolted Fault 21.291 kA
Voltage Drop 3.81 %E N
AATSEQ2
Position - Normal On
350 kcmil
280.0 ft
MCB-300A A3HEQDP1
GE
Frame/Model TJJ
Sensor/Trip 400.0 A
Plug 400.0 A
Settings
Thermal Curve (Fixed)
INST (3-10 x Trip) HI (4000A)
A1HEQDP1
Rm A-1486
480.0 V
AFIE 4.24 Cal/cm^2
Bolted Fault 13.783 kA
Voltage Drop 4.45 %
500 kcmil
50.0 ft
CB-100A TRANS A5T1
GE
Frame/Model THED
Sensor/Trip 100.0 A
Plug 100.0 A
Settings
Fixed
2 AWG
260.0 ft
DS A5T1 PRI
EATON/CUTLER-HAMMER
Frame/Model DH
DS TRANS A5T1 PRI
Rm A-5001
480.0 V
AFIE 0.13 Cal/cm^2
Bolted Fault 4.043 kA
Voltage Drop 4.45 %
2 AWG
7.0 ft
S
P
TRANS A5T1
75 kVA
Impedance 5.1000 %
Primary 480 V
Secondary 208 V
TRANS A5T1 SEC
Rm A-5001
208.0 V
AFIE 1.3 Cal/cm^2
Bolted Fault 3.004 kA
Voltage Drop 4.45 %
4/0 AWG
5.0 ft
DS A5T1 SEC
EATON/CUTLER-HAMMER
Frame/Model DH
F-200A A5T1 SEC
GOULD SHAWMUT
Frame/Model TRS
Sensor/Trip 200.0 A
DS TRANS A5T1 SEC
Rm A-5001
208.0 V
AFIE 1.29 Cal/cm^2
Bolted Fault 2.976 kA
Voltage Drop 4.45 %
4/0 AWG
20.0 ft
4/0 AWG
6.0 ft
MCB-200A A4LIP2
GE
Frame/Model TFJ
Sensor/Trip 200.0 A
Plug 200.0 A
Settings
Thermal Curve (Fixed)
INST…