36C25024B0026_Upgrade Facility Lighting - Drawings.pdf
PDF 6 MB Posted
- Solicitation number
- 36C25024B0026
About this file
This document is a set of drawings and specifications for a project to Upgrade Facility Lighting at the Louis Stokes Veterans Affairs Medical Center (LSVAMC) in Cleveland, OH. The project will include upgrading the lighting in the CARES Tower on the 3rd floor, excluding undercabinet, task, stairwell, elevator, and accessible mechanical duct lighting. The project will be solicited as a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside, requiring a minimum of 15% of the construction work to be performed by the SDVOSB contractor or subcontractor. The solicitation documents, including specifications and drawings, will be available on or about February 15, 2024, with a bid opening approximately 30 days later. The project is expected to be completed within 240 calendar days from the Notice to Proceed.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT AREA
3F-204, Med Room X
3F-200, Employee/Lockers Lounge X
3F-208, Tub Room X
3F-156, Quiet Consult X
3F-155, Staff Office X
3F-145, Office X
3F-143, Office Exam X
3F-131, Office X
3F-205, Conference Classroom X
3F-142, Toilet X
3F-141, Toilet X
Bid Alternate
1 Deleted
Rooms
Bid Alternate 2
Deleted Rooms
BID ALTERNATES 1 & 2
TRACY J.
HAUSER
E-82068
STATE OF OHIO
P
RR
O
F E
SS IONA L ENG
I N E
E
REG I TERED
S
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440546.9696 F: 440.5469699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
AREA A
AREA B KEYPLAN
08/07/2023
B
IM
/2
L o u is S to k e s C le v e la n d V
A U p g ra d e F a c ili ty L ig h ti n g /5
-2
.B
.M
.R
.r v t
/3
/2
:5
:4
P
M
G000
COVER SHEET UPGRADE FACILITY LIGHTING -
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVELAND, OH 44106
541-206
B01
08/07/2023 JLN CJF
UPGRADE FACILITY LIGHTING
LOUIS STOKES CLEVELAND VA MEDICAL CENTER
10701 EAST BLVD.
CLEVELAND, OH 44106
SHEET INDEX - GENERAL
Sheet Number Sheet Name
G000 COVER SHEET
Grand total: 1
SHEET INDEX - ELECTRICAL
Sheet Number Sheet Name
E000 ELECTRICAL COVERSHEET
E100 THIRD FLOOR ELECTRICAL KEY PLAN
ED213A THIRD FLOOR PLAN - AREA A - LIGHTING DEMOLITION
ED213B THIRD FLOOR PLAN - AREA B - LIGHTING DEMOLITION
E213A THIRD FLOOR PLAN - AREA A - LIGHTING
E213B THIRD FLOOR PLAN - AREA B - LIGHTING
E300 ENLARGED PLANS
E400 LIGHTING FIXTURE SCHEDULE AND ELECTRICAL DETAILS
Grand total: 8
SHEET INDEX - ARCHITECTURAL
Sheet Number Sheet Name
AR-103-Ala Third Floor Reflected Ceiling Plan - Skilled/Rehab. Nursing - ALTERNATE 1 - Quadrant A
(FOR REFERENCE ONLY)
AR-103-Ale Third Floor Reflected Ceiling Plan - Skilled/Rehab. Nursing - ALTERNATE 1 - Quadrant E
(FOR REFERENCE ONLY)
AE-581 INTERIOR CEILING DETAILS (FOR REFERENCE ONLY)
AE-582 INTERIOR CEILING DETAILS (FOR REFERENCE ONLY)
AE-583 INTERIOR CEILING DETAILS (FOR REFERENCE ONLY)
Grand total: 5
Revisions: Date:
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
N.C. NORMALLY CLOSED
NIC NOT IN CONTRACT
N.O. NORMALLY OPEN
SV SOLENOID VALVE
ABBR: DESCRIPTION:
TYP TYPICAL
C CONDUIT
UON UNLESS OTHERWISE NOTED
GFI GROUND FAULT INTERRUPTER
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. LIFE SAFETY, CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS
SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS.
WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING
THE NORMAL BRANCH.
4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
5. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
6. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL
BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
7. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT
LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.
PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL
ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE
FURNITURE AND/OR EQUIPMENT.
8. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR. ALL
CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.
10. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.
CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING
EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE
RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF
ANY WELDERS ASSIGNED TO THE JOB.
11. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE
IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
ELECTRICAL INSTALLATION NOTES:
NORMAL BRANCH LUMINAIRE
CRITICAL BRANCH LUMINAIRE
EMERGENCY LIFE SAFETY BRANCH LUMINAIRE
UNSWITCHED FOR NIGHT LIGHT, UNLESS NOTED 'SE'
LUMINAIRE SYMBOL KEY
SYMBOL: DESCRIPTION:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING
CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
4. THE CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS,
WALLS, AND FLOORS ASSOCIATED WITH WORK.
5. THE CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,
CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS.
6. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, LIGHTING, POWER, AND SYSTEMS.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
GENERAL CONTRACTORG.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
BUILDING CODE: IBC 20** EDITION
UBC 20**
ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION
LIFE SAFETY CODE: NFPA 101 2021 EDITION
ENERGY CONSERVATION CODE: ASHRAE 90.1 2022
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
1. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.
2. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND
OPERATES FROM EMERGENCY CIRCUIT UPON LOSS OF POWER.
3. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN
EMERGENCY CIRCUIT.
4. REFER TO SHEET E-400 FOR LUMINAIRE SCHEDULE.
5. CONTROL STATION SHALL BE CAPABLE OF RAISE/LOWER WHERE DIMMING IS INDICATED AND
SWITCHING ON/OFF AS INDICATED ON SHEETS. COORDINATE QUANTITIES OF BUTTONS FOR
CONTROL STATIONS WITH LIGHTING CONTROL MANUFACTURER.
6. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR
DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE MANUFACTURER
SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA
OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING
MULTIPLE SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC
MANUFACTURER-APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT
DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG
1 = CIRCUIT NUMBER
a = SWITCH DESIGNATION
NL = SUBSCRIPT (IF APPLICABLE)
Z = ZONE DESIGNATION
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: F1 / 1 / a / NL
DEVICE
A = MOUNTING (IF APPLICABLE)
1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS
INFORMATION. EX: A / 1
LUMINAIRE KEY:
DEVICE KEY:
FEEDERS: SWITCHBOARDS, DISTRIBUTION PANELS,
PANELBOARDS, MOTOR CONTROL CENTERS, ETC.
BRANCH CIRCUITS: LIGHTING, RECEPTACLES,
CONTROLS, ETC.
MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,
AIR HANDLING UNITS, ETC.
FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.
(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)
CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)
WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,
INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)
FINISHED SPACES / CONCEALED
CONDUIT INSTALLATION SCHEDULE
THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION
OF APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF
RMC CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE.
REFER TO CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.
INSTALLATION TYPE RMC EMT
X
X
X
X
X
X
X
ELEVATED CONCRETE SLABS (ABOVE GRADE)
X
INTERIOR LOCATIONS: CONCEALED
INTERIOR LOCATIONS: EXPOSED
INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED
INSTALLATION (FINISHED SPACES)
X
X
X
SW-1P EXISTING SWITCH - SINGLE POLE
SW-3W EXISTING SWITCH - THREE WAY3
SW-1P-ADJ EXISTING SWITCH - LOCAL TIMER - USER ADJUSTABLET
SW-1P-M EXISTING SWITCH - MOMENTARY CONTACTM
SW-OC-P-O SWITCH - OCCUPANCY SENSOR
WALL SWITCH
O
OC SW-OC-D OCCUPANCY SENSOR - DUAL TECHNOLOGY
D
EXISTING
EXISTING
SW-OC-D-W OCCUPANCY SENSOR - DUAL
TECHNOLOGY - WALL MOUNTED
D
EXISTINGOC
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
JB 26 05 33 JUNCTION BOX
J
J
ECONN 26 05 33 ELECTRICAL CONNECTION
E
E
PANEL '###' EXISTING PANELBOARD
TR-#/DTR-# EXISTING TRANSFORMER
NLC SW-NLC NURSE CALL LIGHTING CONTROLLEREXISTING
LINEAR LUMINAIRES
TROFFER
WALL SCONCE LUMINAIRE
DOWNLIGHT LUMINAIRE
AIMABLE OR WALL WASH LUMINAIRE
INDUSTRIAL LUMINAIRE
POLE MOUNTED LUMINAIRE
SINGLE FACE EXIT SIGN
DOUBLE FACE EXIT SIGN
EMERGENCY UNIT
WALL BRACKET LUMINAIRE
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:
SPEC
SECTION:
DESCRIPTION:
WALL/CEILING EMERGENCY EXIT SIGN
REFER TO LUMINAIRE
SCHEDULE
SW-4W EXISTING SWITCH - FOUR WAY
S
63889
W.T. GIENGER
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TE
A
H
F OO
I O
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440.546.9696 F: 440.546.9699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
B01
UPGRADE FACILITY LIGHTING
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVLAND,OH 44106
23000104.00
B
IM
/2
L o u is
S to k e s C le v e la n d
V A
U p g ra d e F a c ili ty L ig h ti n g
/E
.0
V A
C le v e la n d
U p g ra d e
F a c ili ty L ig h ti n g l_ C
.r v t
/1
/2
:2
:1
P
M
E000
ELECTRICAL COVER SHEET 541- 206
ShaCal ChrCam 08/07/2023Revisions: Date:
B
E F G H K M N O P S
R UV
H.2 H.4 H.8 M.5 M.9 P.9
A
C
J
11.6
15.6
17.1
19.4
22.1
28.1
N.6 O.9
Office
3F131
Two-Bed Room
3F132
Clean Linen
3F133
Two-Bed Room
3F134
One-Bed Room
3F135
Large One-Bed Room
3F136
Large One-Bed Room
3F137
One-Bed Room
3F138
One-Bed Room
3F139
One-Bed Room
3F140
Toilet
3F141
Toilet
3F142Office Exam
3F143
EMS
3F144 Office
3F145
Dining Room
3F150
Storage
3F152
Soiled Tray Cart Storage
3F153
Non-Food Storage/ Food Prep.
3F154
Staff Office
3F155
Quiet Consult
3F156
One-Bed Room
3F170
One-Bed Room
3F171
One-Bed Room
3F172
One-Bed Room
3F173
One-Bed Room
3F174
One-Bed Room
3F175
One-Bed Room
3F176
One-Bed Room
3F177
One-Bed Room
3F178
Two-Bed Room
3F179
Two-Bed Room
3F180
Soiled Linen Holding
3F190 Trash Collect
3F191 EMS Storage
3F192
Service Elevator Lobby
3FC01B
Stair 25
3S25
Stair 27
3S27
Stair 26
3S26
Toilet
3F170A
Toilet
3F171A
Toilet
3F172A
Toilet
3F173A
Toilet
3F174A
Toilet
3F175A
Toilet
3F176A
Toilet
3F177A
Toilet
3F178A
Toilet
3F179A
Toilet
3F180A
Resident Clothing & Luggage Storage
3F101
Two-Bed Room
3F102
Office
3F103 Two-Bed Room
3F104
One-Bed Room
3F105
One-Bed Room
3F106
One-Bed Room
3F107
One-Bed Room
3F108
One-Bed Room
3F109
One-Bed Room
3F110
One-Bed Room
3F111
One-Bed Room
3F112
One-Bed Room
3F113
One-Bed Room
3F114 Toilet
3F114A
Toilet
3F113A
Toilet
3F112A
Toilet
3F111A
Toilet
3F110A
Toilet
3F109A
Toilet
3F108A
Toilet
3F107A
Toilet
3F106A
Toilet
3F105A
Toilet
3F104A
Toilet
3F102A
Elec Closet
3FELC1
Elect. Closet
3FELC2
Toilet
3F132A
Toilet
3F134A
Toilet
3F135A Toilet
3F136A
Toilet
3F137A
Toilet
3F138A
Toilet
3F139A
Toilet
3F140A
Corridor
3FC05
Employee Lockers/ Lounge
3F200
Soiled Utility
3F201
Clean Utility
3F202
Equipment Storage
3F203
Med. Room
3F204
Conference Classroom
3F205
Wheelchair Scale
3F207A Expendable Supplies
3F207
Tub Room
3F208
Resident Laundry
3F209
EMS
3F210
Toilet
3F200A
Corridor
3FC01
Corridor
3FC02
Corridor
3FC03
Corridor
3FC06
Corridor
3FC07
Corridor
3FC08
Family Waiting
3FC07BNourishment
3FC07A
Crash Cart Alcove
3FC05A
Nurse Station Ward Clerk
3FC04A
Med. Room Entry
3F204A
Vending
3FC02A
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Sat. Nurse Charting
3FC01A
Corridor
3FC04
Patient Lounge TV Room/ Day room
3F151
Office
3F131
Two-Bed Room
3F132
Clean Linen
3F133
Two-Bed Room
3F134
One-Bed Room
3F135
Large One-Bed Room
3F136
Large One-Bed Room
3F137
One-Bed Room
3F138
One-Bed Room
3F139
One-Bed Room
3F140
Toilet
3F141
Toilet
3F142Office Exam
3F143
EMS
3F144 Office
3F145
Dining Room
3F150
Storage
3F152
Soiled Tray Cart Storage
3F153
Non-Food Storage/ Food Prep.
3F154
Staff Office
3F155
Quiet Consult
3F156
One-Bed Room
3F170
One-Bed Room
3F171
One-Bed Room
3F172
One-Bed Room
3F173
One-Bed Room
3F174
One-Bed Room
3F175
One-Bed Room
3F176
One-Bed Room
3F177
One-Bed Room
3F178
Two-Bed Room
3F179
Two-Bed Room
3F180
Soiled Linen Holding
3F190 Trash Collect
3F191 EMS Storage
3F192
Service Elevator Lobby
3FC01B
Stair 25
3S25
Stair 27
3S27
Stair 26
3S26
Toilet
3F170A
Toilet
3F171A
Toilet
3F172A
Toilet
3F173A
Toilet
3F174A
Toilet
3F175A
Toilet
3F176A
Toilet
3F177A
Toilet
3F178A
Toilet
3F179A
Toilet
3F180A
Resident Clothing & Luggage Storage
3F101
Two-Bed Room
3F102
Office
3F103 Two-Bed Room
3F104
One-Bed Room
3F105
One-Bed Room
3F106
One-Bed Room
3F107
One-Bed Room
3F108
One-Bed Room
3F109
One-Bed Room
3F110
One-Bed Room
3F111
One-Bed Room
3F112
One-Bed Room
3F113
One-Bed Room
3F114 Toilet
3F114A
Toilet
3F113A
Toilet
3F112A
Toilet
3F111A
Toilet
3F110A
Toilet
3F109A
Toilet
3F108A
Toilet
3F107A
Toilet
3F106A
Toilet
3F105A
Toilet
3F104A
Toilet
3F102A
Elec Closet
3FELC1
Elect. Closet
3FELC2
Toilet
3F132A
Toilet
3F134A
Toilet
3F135A Toilet
3F136A
Toilet
3F137A
Toilet
3F138A
Toilet
3F139A
Toilet
3F140A
Corridor
3FC05
Employee Lockers/ Lounge
3F200
Soiled Utility
3F201
Clean Utility
3F202
Equipment Storage
3F203
Med. Room
3F204
Conference Classroom
3F205
Wheelchair Scale
3F207A Expendable Supplies
3F207
Tub Room
3F208
Resident Laundry
3F209
EMS
3F210
Toilet
3F200A
Corridor
3FC01
Corridor
3FC02
Corridor
3FC03
Corridor
3FC06
Corridor
3FC07
Corridor
3FC08
Family Waiting
3FC07BNourishment
3FC07A
Crash Cart Alcove
3FC05A
Nurse Station Ward Clerk
3FC04A
Med. Room Entry
3F204A
Vending
3FC02A
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Sat. Nurse Charting
3FC01A
Corridor
3FC04
Patient Lounge TV Room/ Day room
3F151
Corridor
3FC02
E213A
E100
AREA A
AREA B
AREA A
AREA B
N O
M.5 M.9 J
11.6
Elec Closet
3FELC1
Elec Closet
3FELC1
F3LN52
F3LNL4
F3LNL3
F3LCH2
F3LCL3
F3LCL4
TS-2
TC-10
TN-10
F3LSH1
K M
Elect. Closet
3FELC2
Elect. Closet
3FELC2
F3LCH1
F3LEL1 F4LNL2
F3LNL1
F3LCL1
F3LCL2
TN-9
F3LCH1
S
63889
W.T. GIENGER
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TE
A
H
F OO
I O
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440.546.9696 F: 440.546.9699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
B01
UPGRADE FACILITY LIGHTING
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVLAND,OH 44106
23000104.00
B
IM
/2 o u is
S to k e s C le v e la n d
V A
U p g ra d e F a c ili ty L ig h ti n g
/E
.0
V A
C le v e la n d
U p g ra d e
F a c ili ty L ig h ti n g l_ C
.r v t
/1
/2
:2
:2
P
M
E100
THIRD FLOOR ELECTRICAL KEY
PLAN
541- 206
ShaCal ChrCam 08/07/2023
N O R
HT
1/16" = 1'-0"
THIRD FLOOR PLAN - ELECTRICAL KEY PLAN
N O R
HT
1/4" = 1'-0"
THIRD FLOOR PLAN - AREA A - ELECTRICAL CLOSET 3FELC1
N O R
HT
1/4" = 1'-0"
THIRD FLOOR PLAN - AREA B - ELECTRICAL CLOSET 3FELC2
SCALE: 1/4" = 1' - 0"
4 0 4 8123
SCALE: 1/16" = 1' - 0"
16 0 16 324812
AREA A
AREA B KEYPLAN
O C
OC
O C
O C
OC
OC
OC
OC
OC
OC
OC
OC
OC
O C
OC
O C
OC
O C
O C
O C
O C
OC
O C
B E F G H K M N O P S
R U V W X Y
H.2 H.4 H.8H.9 M.5 M.9 P.9
A
C
J
11.6
15.6
17.1
One-Bed Room
3F171
One-Bed Room
3F172
One-Bed Room
3F173
One-Bed Room
3F174
One-Bed Room
3F175
One-Bed Room
3F176
One-Bed Room
3F177
One-Bed Room
3F178
Two-Bed Room
3F179
Two-Bed Room
3F180
Soiled Linen Holding
3F190 Trash Collect
3F191 EMS Storage
3F192
Service Elevator Lobby
3FC01B
Stair 25
3S25
Toilet
3F171A
Toilet
3F172A
Toilet
3F173A
Toilet
3F174A
Toilet
3F175A
Toilet
3F176A
Toilet
3F177A
Toilet
3F178A
Toilet
3F179A
Toilet
3F180A
Resident Clothing & Luggage Storage
3F101
Two-Bed Room
3F102
Office
3F103
Two-Bed Room
3F104
One-Bed Room
3F105
One-Bed Room
3F106
One-Bed Room
3F107
One-Bed Room
3F108
Toilet
3F108A
Toilet
3F107A
Toilet
3F106A
Toilet
3F105A
Toilet
3F104A
Toilet
3F102A
Elec Closet
3FELC1
Employee Lockers/ Lounge
3F200
Soiled Utility
3F201
Clean Utility
3F202
Tub Room
3F208
Resident Laundry
3F209
EMS
3F210
Toilet
3F200A
Corridor
3FC01
Corridor
3FC03
Corridor
3FC08
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Sat. Nurse Charting
3FC01A
One-Bed Room
3F171
One-Bed Room
3F172
One-Bed Room
3F173
One-Bed Room
3F174
One-Bed Room
3F175
One-Bed Room
3F176
One-Bed Room
3F177
One-Bed Room
3F178
Two-Bed Room
3F179
Two-Bed Room
3F180
Soiled Linen Holding
3F190 Trash Collect
3F191 EMS Storage
3F192
Service Elevator Lobby
3FC01B
Stair 25
3S25
Toilet
3F171A
Toilet
3F172A
Toilet
3F173A
Toilet
3F174A
Toilet
3F175A
Toilet
3F176A
Toilet
3F177A
Toilet
3F178A
Toilet
3F179A
Toilet
3F180A
Resident Clothing & Luggage Storage
3F101
Two-Bed Room
3F102
Office
3F103
Two-Bed Room
3F104
One-Bed Room
3F105
One-Bed Room
3F106
One-Bed Room
3F107
One-Bed Room
3F108
Toilet
3F108A
Toilet
3F107A
Toilet
3F106A
Toilet
3F105A
Toilet
3F104A
Toilet
3F102A
Elec Closet
3FELC1
Employee Lockers/ Lounge
3F200
Soiled Utility
3F201
Clean Utility
3F202
Tub Room
3F208
Resident Laundry
3F209
EMS
3F210
Toilet
3F200A
Corridor
3FC01
Corridor
3FC03
Corridor
3FC08
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Sat. Nurse Charting
3FC01A
T
T
T
S
63889
W.T. GIENGER
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TE
A
H
F OO
I O
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440.546.9696 F: 440.546.9699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
B01
UPGRADE FACILITY LIGHTING
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVLAND,OH 44106
23000104.00
B
IM
/2 o u is
S to k e s C le v e la n d
V A
U p g ra d e F a c ili ty L ig h ti n g
/E
.0
V A
C le v e la n d
U p g ra d e
F a c ili ty L ig h ti n g l_ C
.r v t
/1
/2
:2
:2
P
M
ED213A
THIRD FLOOR PLAN - AREA A -
LIGHTING DEMOLITION
541- 206
ShaCal ChrCam 08/07/2023
N O R
HT
1/8" = 1'-0"
THIRD FLOOR PLAN - AREA A - LIGHTING DEMOLITION
SHEET NOTES:
1. THE ELECTRICAL LIGHTING DRAWINGS
INDICATE EXISTING ELECTRICAL ITEMS TO BE
REMOVED. THE DRAWINGS ARE INTENDED TO
INDICATE THE SCOPE OF WORK REQUIRED
AND DO NOT INDICATE EVERY BOX, CONDUIT,
OR WIRE THAT MUST BE REMOVED. THE
CONTRACTOR SHALL VISIT THE SITE PRIOR TO
SUBMITTING A BID AND VERIFY EXISTING
CONDITIONS.
2. ALL LUMINAIRES SHOWN TO BE DEMOLISHED
SHALL BE DISPOSED OF IF NOT REQUIRED BY
OWNER FOR ATTIC STOCK. CONFIRM WITH
OWNER PRIOR TO DISPOSAL IF THE LAMPS,
LENS OR SUBSET OF LUMINAIRES SHOULD BE
TURNED OVER FOR ATTIC STOCK.
3. REMOVE EXISTING LUMINAIRES AND WALL
SWITCHES WHERE SHOWN. LOCATE, IDENTIFY
AND PREPARE ELECTRICAL CIRCUIT SERVING
REMOVED LUMINAIRES FOR REUSE WITH NEW
DEVICES.
4. WHERE WALL SWITCH DEVICE IS REMOVED
AND NOT REPLACED. PROVIDE WITH BLANK
SWITCH PLATE.
5. EQUIPMENT REMOVAL IN CERTAIN LOCATIONS
MAY REQUIRE THE INSTALLATION OF A
JUNCTION BOX TO RECONNECT CIRCUITS
THAT REMAIN IN OPERATION. EXTEND
CONDUIT AND WIRING AS REQUIRED TO
MAINTAIN POWER TO REMAINING EQUIPMENT.
6. BALLASTS MANUFACTURED PRIOR TO 1980
CONTAIN PCBs AND SHALL BE DISPOSED OF BY
A FEDERAL OR STATE E.P.A. APPROVED
METHOD AND IN ACCORDANCE WITH
SPECIFICATIONS.
7. HID AND FLUORESCENT LAMPS CONTAIN
MERCURY AND SHALL BE DISPOSED OF BY A
FEDERAL OR STATE E.P.A. APPROVED METHOD
AND IN ACCORDANCE WITH SPECIFICATIONS.
8. VERIFY MANUFACTURERS INSTALLATION
GUIDELINES WITH EXISTING FIELD CONDITIONS
PRIOR TO BIDDING AND ORDERING NEW LIGHT
FIXTURES AND INSTALLATION MATERIAL.
9. MATCH EXISTING PAINTED SURFACES. WHERE
REPLACED LUMINAIRE DOES NOT FULLY
COVER EXISTING JUNCTION BOX OR PAINTED
SURFACE.
10. REFER TO CEILING REFERENCE PLANS FOR
CEILING TYPES IN EXISTING AREAS, HOWEVER,
DRAWINGS ARE FOR REFERENCE ONLY AND
CONTRACTOR SHALL BE RESPONSIBLE FOR
SURVEYING AND IDENTIFYING CEILING
CONDITIONS IN FIELD PRIOR TO ORDERING
LIGHTING FIXTURES AND CEILING TILES.
KEYNOTES:
1. CONTRACTOR SHALL ASSUME THE
DEMOLITION OF EXISTING DOWNLIGHTING IN
GYPSUM BOARD CEILINGS WILL REQUIRE
CUTTING AND PATCHING OF CEILING TO
REMOVE EXISTING LIGHTING FIXTURES AND TO
INSTALL NEW LIGHTING FIXTURES.
CONTRACTOR SHALL ASSUME THE
DEMOLITION OF EXISTING DOWNLIGHTING IN
LAY-IN GRID CEILINGS WILL REQUIRE
COMPLETE REPLACEMENT OF CEILING TILE AT
ALL LOCATIONS IN LAY-IN GRID CEILINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR
ENSURING NEW LIGHTING FIXTURE TRIM
COVERS ROUGH-IN OPENING WITHOUT THE
USE OF OVERSIZED TRIM PLATES AND SHALL
RETURN CEILING BACK TO FINISHED
CONDITION. ALL UNUSED REPLACEMENT
CEILING TILES SHALL BE DELIVERED TO
OWNER FOR ATTIC STOCK. TYPICAL FOR ALL
NEW DOWNLIGHTS.
2. CONTRACTOR SHALL ASSUME THE
REPLACEMENT OF EXISTING NIGHT LIGHT
FIXTURE IN WALL WILL REQUIRE PATCHING
AND PAINTING DUE TO SMALLER DIMENSIONS
OF NEW LIGHTING FIXTURE. PROVIDE NEW
BACKBOX AS REQUIRED TO INSTALL LIGHTING
FIXTURE.
SCALE: 1/8" = 1' - 0"
8 0 8 16246
TYP.
TYP.
TYP.
TYP.
TYP.
PHASING NOTES:
1. THIS PROJECT SHALL BE PHASED IN ORDER TO
ALLOW CONTINUOUS USE OF THE PROJECT
AREA ON A DAILY BASIS. CONTRACTOR SHALL
BE RESPONSIBLE FOR DEVELOPING PROJECT
SCHEDULE AND PHASING PLAN. CONTRACTOR
SHALL INCLUDE ANY ADDITIONAL WORK
REQUIRED TO ACCOMMODATE PHASING.
SUBMIT PHASING PLAN TO OWNER FOR
APPROVAL PRIOR TO BEGINNING
CONSTRUCTION. COORDINATE EXECUTION OF
PHASING PLAN WITH OWNER THROUGHOUT
PROJECT COMPLETION. THE FOLLOWING
PHASING CONSTRAINTS SHALL BE OBSERVED:
• WORK SHALL BE PERFORMED WITHIN A
SINGLE SPACE AT ANY GIVEN TIME.
SPACES CANNOT BE LEFT IN AN
INCOMPLETE STATE OR PROVIDED WITH
TEMPORARY LIGHTING, WORK WITHIN
EACH SPACE SHALL BE COMPLETE BY THE
END OF EACH WORKING DAY. WHERE THIS
IS NOT POSSIBLE, COORDINATE SPECIFIC
PHASING NEEDS WITH OWNER.
• CONTRACTOR SHALL COMPLY WITH THE
CAMPUS’S INFECTION CONTROL POLICIES,
COORDINATE EXACT REQUIREMENTS WITH
OWNER. CONTRACTOR SHALL PROVIDE
ANY ITEMS AS NEED TO COMPLY WITH
THESE POLICIES, SUCH AS TEMPORARY
CONSTRUCTION BARRIERS OR DUST
CARTS.
AREA A
OC
OC
OC
OC
O C
O C
OC
OC
OC
O C
O C
O C
O C
O C
O C
O C
O C
O C
OC
O C
O C
O C
O C
OC
OC
OC27
B
E F G H K M N O P S
H.2 H.8A C J
19.4
22.1
28.1
N.6 O.9
Office
3F131
Two-Bed Room
3F132
Clean Linen
3F133
Two-Bed Room
3F134
One-Bed Room
3F135
Large One-Bed Room
3F136
Large One-Bed Room
3F137
One-Bed Room
3F138
One-Bed Room
3F139
One-Bed Room
3F140
Toilet
3F141
Toilet
3F142
Office Exam
3F143
EMS
3F144
Office
3F145
Dining Room
3F150
Storage
3F152
Soiled Tray Cart Storage
3F153
Non-Food Storage/ Food Prep.
3F154
Staff Office
3F155
Quiet Consult
3F156
One-Bed Room
3F170
One-Bed Room
3F171
One-Bed Room
3F172
Stair 27
3S27
Stair 26
3S26
Toilet
3F170A
Toilet
3F171A
Toilet
3F172A
One-Bed Room
3F107
One-Bed Room
3F108
One-Bed Room
3F109
One-Bed Room
3F110
One-Bed Room
3F111
One-Bed Room
3F112
One-Bed Room
3F113
One-Bed Room
3F114Toilet
3F114A
Toilet
3F113A
Toilet
3F112A
Toilet
3F111A
Toilet
3F110A
Toilet
3F109A
Toilet
3F108A
Elect. Closet
3FELC2
Toilet
3F132A
Toilet
3F134A
Toilet
3F135A
Toilet
3F136A
Toilet
3F137A
Toilet
3F138A
Toilet
3F139A
Toilet
3F140A
Corridor
3FC05
Equipment Storage
3F203
Med. Room
3F204
Conference Classroom
3F205
Wheelchair Scale
3F207A
Expendable Supplies
3F207
Tub Room
3F208
Corridor
3FC02
Corridor
3FC06
Corridor
3FC07
Family Waiting
3FC07B
Nourishment
3FC07A
Crash Cart Alcove
3FC05A
Nurse Station Ward Clerk
3FC04A
Med. Room Entry
3F204A
Vending
3FC02A
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Corridor
3FC04
Patient Lounge TV Room/ Day room
3F151
Office
3F131
Two-Bed Room
3F132
Clean Linen
3F133
Two-Bed Room
3F134
One-Bed Room
3F135
Large One-Bed Room
3F136
Large One-Bed Room
3F137
One-Bed Room
3F138
One-Bed Room
3F139
One-Bed Room
3F140
Toilet
3F141
Toilet
3F142
Office Exam
3F143
EMS
3F144
Office
3F145
Dining Room
3F150
Storage
3F152
Soiled Tray Cart Storage
3F153
Non-Food Storage/ Food Prep.
3F154
Staff Office
3F155
Quiet Consult
3F156
One-Bed Room
3F170
One-Bed Room
3F171
One-Bed Room
3F172
Stair 27
3S27
Stair 26
3S26
Toilet
3F170A
Toilet
3F171A
Toilet
3F172A
One-Bed Room
3F107
One-Bed Room
3F108
One-Bed Room
3F109
One-Bed Room
3F110
One-Bed Room
3F111
One-Bed Room
3F112
One-Bed Room
3F113
One-Bed Room
3F114Toilet
3F114A
Toilet
3F113A
Toilet
3F112A
Toilet
3F111A
Toilet
3F110A
Toilet
3F109A
Toilet
3F108A
Elect. Closet
3FELC2
Toilet
3F132A
Toilet
3F134A
Toilet
3F135A
Toilet
3F136A
Toilet
3F137A
Toilet
3F138A
Toilet
3F139A
Toilet
3F140A
Corridor
3FC05
Equipment Storage
3F203
Med. Room
3F204
Conference Classroom
3F205
Wheelchair Scale
3F207A
Expendable Supplies
3F207
Tub Room
3F208
Corridor
3FC02
Corridor
3FC06
Corridor
3FC07
Family Waiting
3FC07B
Nourishment
3FC07A
Crash Cart Alcove
3FC05A
Nurse Station Ward Clerk
3FC04A
Med. Room Entry
3F204A
Vending
3FC02A
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Corridor
3FC04
Patient Lounge TV Room/ Day room
3F151
T
S
63889
W.T. GIENGER
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TE
A
H
F OO
I O
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440.546.9696 F: 440.546.9699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
B01
UPGRADE FACILITY LIGHTING
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVLAND,OH 44106
23000104.00
B
IM
/2 o u is
S to k e s C le v e la n d
V A
U p g ra d e F a c ili ty L ig h ti n g
/E
.0
V A
C le v e la n d
U p g ra d e
F a c ili ty L ig h ti n g l_ C
.r v t
/1
/2
:2
:2
P
M
ED213B
THIRD FLOOR PLAN - AREA B -
LIGHTING DEMOLITION
541- 206
ShaCal ChrCam 08/07/2023
N O R
HT
1/8" = 1'-0"
THIRD FLOOR PLAN - AREA B - LIGHTING DEMOLITION
SHEET NOTES:
1. THE ELECTRICAL LIGHTING DRAWINGS
INDICATE EXISTING ELECTRICAL ITEMS TO BE
REMOVED. THE DRAWINGS ARE INTENDED TO
INDICATE THE SCOPE OF WORK REQUIRED
AND DO NOT INDICATE EVERY BOX, CONDUIT,
OR WIRE THAT MUST BE REMOVED. THE
CONTRACTOR SHALL VISIT THE SITE PRIOR TO
SUBMITTING A BID AND VERIFY EXISTING
CONDITIONS.
2. ALL LUMINAIRES SHOWN TO BE DEMOLISHED
SHALL BE DISPOSED OF IF NOT REQUIRED BY
OWNER FOR ATTIC STOCK. CONFIRM WITH
OWNER PRIOR TO DISPOSAL IF THE LAMPS,
LENS OR SUBSET OF LUMINAIRES SHOULD BE
TURNED OVER FOR ATTIC STOCK.
3. REMOVE EXISTING LUMINAIRES AND WALL
SWITCHES WHERE SHOWN. LOCATE, IDENTIFY
AND PREPARE ELECTRICAL CIRCUIT SERVING
REMOVED LUMINAIRES FOR REUSE WITH NEW
DEVICES.
4. WHERE WALL SWITCH DEVICE IS REMOVED
AND NOT REPLACED. PROVIDE WITH BLANK
SWITCH PLATE.
5. EQUIPMENT REMOVAL IN CERTAIN LOCATIONS
MAY REQUIRE THE INSTALLATION OF A
JUNCTION BOX TO RECONNECT CIRCUITS
THAT REMAIN IN OPERATION. EXTEND
CONDUIT AND WIRING AS REQUIRED TO
MAINTAIN POWER TO REMAINING EQUIPMENT.
6. BALLASTS MANUFACTURED PRIOR TO 1980
CONTAIN PCBs AND SHALL BE DISPOSED OF BY
A FEDERAL OR STATE E.P.A. APPROVED
METHOD AND IN ACCORDANCE WITH
SPECIFICATIONS.
7. HID AND FLUORESCENT LAMPS CONTAIN
MERCURY AND SHALL BE DISPOSED OF BY A
FEDERAL OR STATE E.P.A. APPROVED METHOD
AND IN ACCORDANCE WITH SPECIFICATIONS.
8. VERIFY MANUFACTURERS INSTALLATION
GUIDELINES WITH EXISTING FIELD CONDITIONS
PRIOR TO BIDDING AND ORDERING NEW LIGHT
FIXTURES AND INSTALLATION MATERIAL.
9. MATCH EXISTING PAINTED SURFACES. WHERE
REPLACED LUMINAIRE DOES NOT FULLY
COVER EXISTING JUNCTION BOX OR PAINTED
SURFACE.
10. REFER TO CEILING REFERENCE PLANS FOR
CEILING TYPES IN EXISTING AREAS, HOWEVER,
DRAWINGS ARE FOR REFERENCE ONLY AND
CONTRACTOR SHALL BE RESPONSIBLE FOR
SURVEYING AND IDENTIFYING CEILING
CONDITIONS IN FIELD PRIOR TO ORDERING
FIXTURES AND CEILING TILES.
KEYNOTES:
1. CONTRACTOR SHALL ASSUME THE
DEMOLITION OF EXISTING LIGHTING IN
GYPSUM BOARD CEILINGS WILL REQUIRE
CUTTING AND PATCHING OF CEILING TO
REMOVE EXISTING LIGHTING FIXTURES AND TO
INSTALL NEW LIGHTING FIXTURES.
CONTRACTOR SHALL ASSUME THE
DEMOLITION OF EXISTING LIGHTING IN LAY-IN
GRID CEILINGS WILL REQUIRE COMPLETE
REPLACEMENT OF CEILING TILE AT ALL
DOWNLIGHT LOCATIONS IN LAY-IN GRID
CEILINGS. CONTRACTOR SHALL BE
RESPONSIBLE FOR ENSURING NEW LIGHTING
FIXTURE TRIM COVERS ROUGH-IN OPENING
AND SHALL RETURN CEILING BACK TO
FINISHED CONDITION. ALL UNUSED
REPLACEMENT CEILING TILES SHALL BE
DELIVERED TO OWNER FOR ATTIC STOCK.
TYPICAL FOR ALL NEW DOWNLIGHTS
2. EXISTING CEILING IS A SPECIALTY DECORATIVE
CEILING TILE WITH A WOOD-LOOK
APPEARANCE. CONTRACTOR SHALL TAKE
SPECIAL CARE OF EXISTING TILES IN THIS
AREA. BID SHALL ACCOMODATE
REPLACEMENT OF SPECIALTY CEILING TILES
NECESSARY TO REMOVE EXISTING LIGHTING
AND INSTALL NEW, PER KEY NOTE #1.
3. EXISTING LIGHTING FIXTURES ARE WALL-
MOUNTED WITH HOUSING TO SUPPORT
CEILING TILES. NEW SPECIFIED LIGHTING
FIXTURE DIMENSIONS DO NOT MATCH
EXISTING AND WILL REQUIRE WALL FINISH
PATCHING AND PAINTING AS WELL AS CEILING
SYSTEM REMEDIATION AND NEW CEILING
TILES. REFER TO NEW WORK PLAN FOR
ADDITIONAL INFORMATION.
4. CONTRACTOR SHALL ASSUME PENDANT
FIXTURE CANOPY WILL NOT MATCH EXISTING
LIGHTING FIXTURE AND CEILING WILL REQUIRE
PATCHING AND PAINTING TO RETURN TO
EXISTING CONDITION.
5. CONTRACTOR SHALL ASSUME THE
REPLACEMENT OF EXISTING NIGHT LIGHT
FIXTURE IN WALL WILL REQUIRE PATCHING
AND PAINTING DUE TO SMALLER DIMENSIONS
OF NEW LIGHTING FIXTURE. PROVIDE NEW
BACKBOX AS REQUIRED TO INSTALL LIGHTING
FIXTURE.
SCALE: 1/8" = 1' - 0"
8 0 8 16246
TYP.
TYP.
TYP.
TYP. 1
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
PHASING NOTES:
1. THIS PROJECT SHALL BE PHASED IN ORDER TO
ALLOW CONTINUOUS USE OF THE PROJECT
AREA ON A DAILY BASIS. CONTRACTOR SHALL
BE RESPONSIBLE FOR DEVELOPING PROJECT
SCHEDULE AND PHASING PLAN. CONTRACTOR
SHALL INCLUDE ANY ADDITIONAL WORK
REQUIRED TO ACCOMMODATE PHASING.
SUBMIT PHASING PLAN TO OWNER FOR
APPROVAL PRIOR TO BEGINNING
CONSTRUCTION. COORDINATE EXECUTION OF
PHASING PLAN WITH OWNER THROUGHOUT
PROJECT COMPLETION. THE FOLLOWING
PHASING CONSTRAINTS SHALL BE OBSERVED:
• WORK SHALL BE PERFORMED WITHIN A
SINGLE SPACE AT ANY GIVEN TIME.
SPACES CANNOT BE LEFT IN AN
INCOMPLETE STATE OR PROVIDED WITH
TEMPORARY LIGHTING, WORK WITHIN
EACH SPACE SHALL BE COMPLETE BY THE
END OF EACH WORKING DAY. WHERE THIS
IS NOT POSSIBLE, COORDINATE SPECIFIC
PHASING NEEDS WITH OWNER.
• CONTRACTOR SHALL COMPLY WITH THE
CAMPUS’S INFECTION CONTROL POLICIES,
COORDINATE EXACT REQUIREMENTS WITH
OWNER. CONTRACTOR SHALL PROVIDE
ANY ITEMS AS NEED TO COMPLY WITH
THESE POLICIES, SUCH AS TEMPORARY
CONSTRUCTION BARRIERS OR DUST
CARTS.
AREA A
OC
OC
OC
OC
OC
OC
OC
One-Bed Room
3F171
One-Bed Room
3F172
One-Bed Room
3F173
One-Bed Room
3F174
One-Bed Room
3F175
One-Bed Room
3F176
One-Bed Room
3F177
One-Bed Room
3F178
Two-Bed Room
3F179
Two-Bed Room
3F180
Soiled Linen Holding
3F190
Trash Collect
3F191
EMS Storage
3F192
Service Elevator Lobby
3FC01B
Stair 25
3S25
Toilet
3F171A
Toilet
3F172A
Toilet
3F173A
Toilet
3F174A
Toilet
3F175A
Toilet
3F176A
Toilet
3F177A
Toilet
3F178A
Toilet
3F179A
Toilet
3F180A
Resident Clothing & Luggage Storage
3F101
Two-Bed Room
3F102
Office
3F103
Two-Bed Room
3F104
One-Bed Room
3F105
One-Bed Room
3F106
One-Bed Room
3F107
One-Bed Room
3F108Toilet
3F108A
Toilet
3F107A
Toilet
3F106A
Toilet
3F105A
Toilet
3F104A
Toilet
3F102A
Elec Closet
3FELC1
Employee Lockers/ Lounge
3F200
Soiled Utility
3F201
Clean Utility
3F202
Tub Room
3F208
Resident Laundry
3F209
EMS
3F210
Toilet
3F200A
Corridor
3FC01
Corridor
3FC03
Corridor
3FC08
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Sat. Nurse Charting
3FC01A
B E F G H K M N O P S
R U V W X Y
H.2 H.4 H.8H.9 M.5 M.9 P.9
A
C
J
11.6
15.6
17.1
T T
T
D2MD2M
D2MD2M
D2MD2M
D2MD2M
D3MD3M
L4L4L4L4
D2MD2M D2MD2M D2MD2M D2MD2M
R23R23
R23R23
R23R23R23R23 R23R23
R23R23 R23R23
R23R23
L1L1
L1L1
L1L1
DWW1DWW1
DWW1DWW1
DWW1DWW1
L1L1
L1L1
L1
NL
L1
DWW1DWW1
DWW1DWW1
DWW1DWW1
L1
NL
L1
L1L1
D2MD2M
D2MD2M
D2MD2M
D2MD2M
D2MD2M
L1L1
L1
NL
L1
L1
NL
L1
L1L1
D2MD2M
D2MD2M
D2MD2M
D2MD2M
D2MD2M
D2MD2M
L1
NL
L1
L1L1
L1
NL
L1
L1/NLL1
L1L1
L1L1
L1
NL
L1
L1
NL
L1
L1L1
L1L1
L1
NL
L1
L1
NL
L1
L1L1
L1L1
L1
NL
L1
L1L1
L1
NL
L1
DWW1DWW1
DWW1DWW1
DWW1DWW1
DWW1DWW1
DWW1DWW1
DWW1DWW1
DWW1DWW1
DWW1DWW1
D3MD3M
D3WD3W
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
C1C1
C1C1
C1C1 C1C1
Corridor
3FC02
D2WD2W D2WD2W
D2WD2WD2WD2W
4 5
E100
O
O
O O
O
O
O O
S
63889
W.T. GIENGER
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TE
A
H
F OO
I O
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440.546.9696 F: 440.546.9699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
B01
UPGRADE FACILITY LIGHTING
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVLAND,OH 44106
23000104.00
B
IM
/2 o u is
S to k e s C le v e la n d
V A
U p g ra d e F a c ili ty L ig h ti n g
/E
.0
V A
C le v e la n d
U p g ra d e
F a c ili ty L ig h ti n g l_ C
.r v t
/1
/2
:3
:1
P
M
E213A
THIRD FLOOR PLAN - AREA A -
LIGHTING
541- 206
ShaCal ChrCam 08/07/2023
N O R
HT
1/8" = 1'-0"
THIRD FLOOR PLAN - AREA A - LIGHTING
SHEET NOTES:
1. LIGHTING FIXTURES IN ELEVATORS, ELEVATOR
HOISTWAYS, STAIRWELLS, AND HVAC SHAFTS
SHALL BE EXISTING TO REMAIN UNLESS
OTHERWISE NOTED.
2. EXIT SIGNAGE SHALL BE EXISTING TO REMAIN
UNLESS OTHERWISE NOTED.
3. EXISTING SWITCH CONTROLS SHALL BE
EXISTING TO REMAIN AND NEW LIGHTING
FIXTURES SHALL BE RECONNECTED TO
EXISTING CIRCUITS VIA EXISTING SWITCH
CONTROLS UNLESS OTHERWISE NOTED.
DIMMING DRIVERS IN AREAS WHERE LIGHTING
FIXTURES ARE NOT DIMMED SHALL REMAIN
UNCONNECTED AND FOR FUTURE USE (ONLY
SWITCHING FUNCTION SHALL BE UTILIZED).
KEYNOTES:
1. REFER TO 2/E300 FOR TYPICAL ONE-BED
ROOM LIGHTING LAYOUT.
2. REFER TO 1/E300 FOR TYPICAL TWO-BED
ROOM LIGHTING LAYOUT.
3. CONTRACTOR SHALL IDENTIFY FUCTION OF
ALL SWITCHES AT ALL LOCATIONS WITH
MULTIPLE SWITCH CONTROLS PRIOR TO
REPLACEMENT OF EXISTING LIGHTING
FIXTURES. PROVIDE UPDATED DEVICE
COVERPLATES WITH ENGRAVED LABELING
FOR FUNCTION OF EACH SWITCH. PROVIDE A
DOCUMENT WITH PROPOSED SWITCH
LABELING AT EACH LOCATION TO VA FOR
REVIEW PRIOR TO ENGRAVING.
4. MOUNT NEW COVE LIGHT DRIVER/LOW-
VOLTAGE POWER SUPPLY IN A
MANUFACTURER APPROVED ENCLOSURE AT
AN ACCESSIBLE LOCATION ABOVE LAY-IN
FINISHED CEILING. COORDINATE WITH
EXISTING CONDITIONS AND NOTE
INSTALLATION LOCATION ON AS-BUILT
DRAWINGS.
5. PROVIDE A SAMPLE OF INTENDED SUBMITTAL
LIGHTING FIXTURE AND MOCK-UP A
FUNCTIONAL 8' SECTION OF COVE FOR VA COR
APPROVAL PRIOR TO ORDERING LIGHTING
FIXTURES. PROVIDE SEVEN-DAY NOTIFICATION
TO VA AND ENGINEER PRIOR TO MOCK-UP TO
SCHEDULE A SITE VISIT.
6. AS PART OF BID ALTERNATE 1, ELIMINATE NEW
LIGHTING SCOPE IN THIS ROOM. EXISTING
LIGHTING FIXTURES SHALL REMAIN.
7. SPECIFIED NEW LIGHTING FIXTURE TYPE L1 IS
SLIGHTLY WIDER THAN EXISTING.
CONTRACTOR SHALL MODIFY EXISTING
CEILING SUPPORT SYSTEM TO ACCOMMODATE
NEW LIGHTING FIXTURE AND TRIM EXISTING
TILES AS REQUIRED TO FIT. TYPICAL FOR ALL
CORRIDOR LINEAR LIGHTING FIXTURES. REFER
TO PHOTOS ON THIS SHEET FOR EXISTING
INSTALLATION CONDITION.
8. EXISTING LIGHTING FIXTURE IS INSTALLED IN A
GYPSUM BOARD CEILING. MODIFY OPENING AS
REQUIRED TO ACCOMMODATE NEW LIGHTING
FIXTURE TYPE L4 AND PAINT TO MATCH.
REFER TO PHOTO ON THIS SHEET FOR
EXISTING INSTALLATION CONDITION.
SCALE: 1/8" = 1' - 0"
8 0 8 16246
PHASING NOTES:
1. THIS PROJECT SHALL BE PHASED IN ORDER TO
ALLOW CONTINUOUS USE OF THE PROJECT
AREA ON A DAILY BASIS. CONTRACTOR SHALL
BE RESPONSIBLE FOR DEVELOPING PROJECT
SCHEDULE AND PHASING PLAN. CONTRACTOR
SHALL INCLUDE ANY ADDITIONAL WORK
REQUIRED TO ACCOMMODATE PHASING.
SUBMIT PHASING PLAN TO OWNER FOR
APPROVAL PRIOR TO BEGINNING
CONSTRUCTION. COORDINATE EXECUTION OF
PHASING PLAN WITH OWNER THROUGHOUT
PROJECT COMPLETION. THE FOLLOWING
PHASING CONSTRAINTS SHALL BE OBSERVED:
• WORK SHALL BE PERFORMED WITHIN A
SINGLE SPACE AT ANY GIVEN TIME.
SPACES CANNOT BE LEFT IN AN
INCOMPLETE STATE OR PROVIDED WITH
TEMPORARY LIGHTING, WORK WITHIN
EACH SPACE SHALL BE COMPLETE BY THE
END OF EACH WORKING DAY. WHERE THIS
IS NOT POSSIBLE, COORDINATE SPECIFIC
PHASING NEEDS WITH OWNER.
• CONTRACTOR SHALL COMPLY WITH THE
CAMPUS’S INFECTION CONTROL POLICIES,
COORDINATE EXACT REQUIREMENTS WITH
OWNER. CONTRACTOR SHALL PROVIDE
ANY ITEMS AS NEED TO COMPLY WITH
THESE POLICIES, SUCH AS TEMPORARY
CONSTRUCTION BARRIERS OR DUST
CARTS.
AREA A
AREA B KEYPLAN
CORRIDOR TYPE L1 - EXISTING INSTALLATION CONDITION PHOTOS
TUB ROOM TYPE L4 - EXISTING INSTALLATION CONDITION PHOTO
OC
OC
OC
OC
OC
O C
OC
O C
O C
OC
OC
OC
Office
3F131
Two-Bed Room
3F132
Clean Linen
3F133
Two-Bed Room
3F134
One-Bed Room
3F135
Large One-Bed Room
3F136
Large One-Bed Room
3F137
One-Bed Room
3F138
One-Bed Room
3F139
One-Bed Room
3F140
Toilet
3F141
Toilet
3F142
Office Exam
3F143
EMS
3F144
Office
3F145
Dining Room
3F150
Storage
3F152
Soiled Tray Cart Storage
3F153
Non-Food Storage/ Food Prep.
3F154
Staff Office
3F155
Quiet Consult
3F156
One-Bed Room
3F170
One-Bed Room
3F171
One-Bed Room
3F172
Stair 27
3S27
Stair 26
3S26
Toilet
3F170A
Toilet
3F171A
Toilet
3F172A
One-Bed Room
3F107
One-Bed Room
3F108
One-Bed Room
3F109
One-Bed Room
3F110
One-Bed Room
3F111
One-Bed Room
3F112
One-Bed Room
3F113
One-Bed Room
3F114Toilet
3F114A
Toilet
3F113A
Toilet
3F112A
Toilet
3F111A
Toilet
3F110A
Toilet
3F109A
Toilet
3F108A
Elect. Closet
3FELC2
Toilet
3F132A
Toilet
3F134A
Toilet
3F135A
Toilet
3F136A
Toilet
3F137A
Toilet
3F138A
Toilet
3F139A
Toilet
3F140A
Corridor
3FC05
Equipment Storage
3F203
Med. Room
3F204
Conference Classroom
3F205
Wheelchair Scale
3F207A
Expendable Supplies
3F207
Tub Room
3F208
Corridor
3FC02
Corridor
3FC06
Corridor
3FC07
Family Waiting
3FC07B
Nourishment
3FC07A
Crash Cart Alcove
3FC05A
Nurse Station Ward Clerk
3FC04A
Med. Room Entry
3F204A
Vending
3FC02A
Telecom/ IRM
3FLVC1
Elec. Closet
3FLVC2
Corridor
3FC04
Patient Lounge TV Room/ Day room
3F151
B
E F G H K M N O P S
H.2 H.8A C J
19.4
22.1
28.1
N.6 O.9
R22R22 R22R22 R22R22
R22R22 R22R22
L6L6
L6L6
D2WD2W
D2WD2W
R22R22 R22R22
L1
NL
L1
L1L1 L1L1
L1L1
L1L1
L1L1
L1L1
L1L1
L1L1
L1L1
L1L1
L1
NL
L1
L1
NL
L1
L1L1
L1
NL
L1
P1P1
P1P1
P1/NLP1 P1P1
P1P1 P1P1
P1/NLP1
P1P1
P1/NLP1
D1MD1M D1MD1M D1MD1M D1MD1M
P1P1 P1P1
D1MD1M
D1MD1M D1MD1M
D1MD1M D1MD1M
D1MD1M
DWW1DWW1
D1MD1M
D4D4 D4D4 D4D4
D1MD1MD1MD1M
D3WD3W
D1MD1M
D1MD1M
D1MD1M
P1P1
R22R22
R22R22
R23R23 R23R23
R23R23 R23R23
D1MD1M
D1MD1M
D1MD1M
D1MD1M
D1MD1M
D1MD1M
D3MD3M D3M/NLD3M
D3MD3M
D3MD3M
D3M/NLD3M
D3MD3M
D3MD3M
D3M/NLD3M
D3MD3M D1M/NLD1M D1MD1M D1MD1M D1M/NLD1M D1MD1M D1MD1M D1M/NLD1M D1MD1M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
D3MD3M
P1/NLP1 P1P1 P1P1 P1/NLP1
L5L5 L5L5
L5L5 L5L5
D3WD3W
D3WD3W
D3WD3W
D3WD3W
D3WD3W
R21R21 R21R21
R21R21R21R21
D3WD3W
DWW1DWW1
DWW1DWW1
DWW1DWW1
DWW1DWW1
DWW1DWW1
L1
NL
L1
L1L1
L1L1
L1
NL
L1
L1
NL
L1
L1L1
L1L1
L1
NL
L1
L1
NL
L1
L1L1
D2MD2M
R22R22
R22R22
L4L4 L4L4 L4L4
D2WD2W D2WD2W
L1L1
L1
NL
L1
D1MD1M
D2MD2M
D2MD2M
D2MD2M
L1
NL
L1
L1L1
L1
NL
L1
DWW1DWW1
DWW1DWW1
DWW1DWW1
D3MD3M
D4D4
D4D4
L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3
C1C1
C1C1 C1C1
L1L1 L1
NL
L1
HA
T
D3MD3M
N
LC
N
LC
E300
E300
C1C1
E100
DWW1DWW1 DWW1DWW1 DWW1DWW1
DWW1DWW1 DWW1DWW1
DWW1DWW1DWW1DWW1
DWW1DWW1 DWW1DWW1
DWW1DWW1
DWW1DWW1DWW1DWW1
DWW2DWW2
DWW2DWW2DWW2DWW2
DWW2/NLDWW2
O
O
O O
O
O
O
O
O
S
63889
W.T. GIENGER
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TE
A
H
F OO
I O
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440.546.9696 F: 440.546.9699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
B01
UPGRADE FACILITY LIGHTING
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVLAND,OH 44106
23000104.00
B
IM
/2 o u is
S to k e s C le v e la n d
V A
U p g ra d e F a c ili ty L ig h ti n g
/E
.0
V A
C le v e la n d
U p g ra d e
F a c ili ty L ig h ti n g l_ C
.r v t
/1
/2
:2
:2
P
M
E213B
THIRD FLOOR PLAN - AREA B -
LIGHTING
541- 206
ShaCal ChrCam 08/07/2023
KEYNOTES:
1. REFER TO 2/E300 FOR TYPICAL ONE-BED
ROOM LIGHTING LAYOUT.
2. REFER TO 1/E300 FOR TYPICAL TWO-BED
ROOM LIGHTING LAYOUT.
3. CONTRACTOR SHALL IDENTIFY FUCTION OF
ALL SWITCHES AT ALL LOCATIONS WITH
MULTIPLE SWITCH CONTROLS PRIOR TO
REPLACEMENT OF EXISTING LIGHTING
FIXTURES. PROVIDE UPDATED DEVICE
COVERPLATES WITH ENGRAVED LABELING
FOR FUNCTION OF EACH SWITCH. PROVIDE A
DOCUMENT WITH PROPOSED SWITCH
LABELING AT EACH LOCATION TO VA FOR
REVIEW PRIOR TO ENGRAVING.
4. MOUNT NEW COVE LIGHT DRIVER/LOW-
VOLTAGE POWER SUPPLY IN A
MANUFACTURER APPROVED ENCLOSURE AT
AN ACCESSIBLE LOCATION ABOVE LAY-IN
FINISHED CEILING. COORDINATE WITH
EXISTING CONDITIONS AND NOTE
INSTALLATION LOCATION ON AS-BUILT
DRAWINGS.
5. PROVIDE A SAMPLE OF INTENDED SUBMITTAL
LIGHTING FIXTURE AND MOCK-UP A
FUNCTIONAL 8' SECTION OF COVE FOR VA COR
APPROVAL PRIOR TO ORDERING LIGHTING
FIXTURES. PROVIDE SEVEN-DAY NOTIFICATION
TO VA AND ENGINEER PRIOR TO MOCK-UP TO
SCHEDULE A SITE VISIT.
6. CONTRACTOR SHALL PROVIDE NEW T-GRID
PARALLEL TO THE ELEVATOR WALL FOR THE
LENGTH OF THE LIGHTING FIXTURE TO
SUPPORT THE NEW LIGHTING FIXTURE AND
THE CEILING TILES. PROVIDE NEW
PERPENDICULAR T-GRID TO BE ROUTED FROM
THE LIGHTING FIXTURE TO THE NEAREST MAIN
SUPPORT RUNNER, EVERY 2FT TO SUPPORT
CEILING TILES. PROVIDE NEW CEILING TILES
FOR THE ENTIRE LIGHTING FIXTURE LENGTH.
CONTRACTOR SHALL BE RESPONSIBLE FOR
SELECTING LIGHTING FIXTURE MOUNTING
OPTIONS AND INSTALLING IN A MANNER THAT
IS CAPABLE OF SUPPORTING EXISTING CEILING
CONSTRUCTION. TYPICAL FOR ALL LIGHTING
FIXTURES AT ELEVATOR LOBBY PERIMETER.
REFER TO PHOTOS ON THIS SHEET FOR
EXISTING INSTALLATION CONDITION.
7. SPECIFIED NEW LIGHTING FIXTURE IS
SLIGHTLY WIDER THAN EXISTING.
CONTRACTOR SHALL MODIFY EXISTING
CEILING SUPPORT SYSTEM TO ACCOMMODATE
NEW LIGHTING FIXTURE AND TRIM EXISTING
TILES AS REQUIRED TO FIT. TYPICAL FOR ALL
CORRIDOR LINEAR LIGHTING FIXTURES. REFER
TO PHOTOS ON E213A FOR EXISTING
INSTALLATION CONDITION.
8. AS PART OF BID ALTERNATE 1, ELIMINATE NEW
LIGHTING SCOPE IN THIS ROOM. EXISTING
LIGHTING FIXTURES SHALL REMAIN.
9. AS PART OF BID ALTERNATE 2, ELIMINATE NEW
LIGHTING SCOPE IN THIS ROOM. EXISITING
LIGHTING FIXTURES SHALL REMAIN.
10. EXISTING LIGHTING FIXTURE AT LOCATION HAS
BEEN PREVIOUSLY REPLACED WITH LED AND
CONTROLLED VIA A DIMMING WALL SWITCH. IT
AS ASSUMED THAT EXISTING CONTROL
DEVICE IS 0-10V DIMMING AND WILL BE
COMPATIBLE WITH NEW LIGHTING FIXTURE.
FIELD VERIFY AND REPLACE SWITCH AND
LOW-VOLTAGE CONDUCTORS AS REQUIRED
FOR CONTROL OF NEW LIGHTING FIXTURE.
11. EXISTING LIGHTING FIXTURE IS INSTALLED IN A
HARD LID CEILING. MODIFY OPENING AS
REQUIRED TO ACCOMMODATE NEW LIGHTING
FIXTURE TYPE AND PAINT TO MATCH. REFER
TO PHOTO ON SHEET E213A FOR EXISTING
INSTALLATION CONDITION.
N O R
HT
1/8" = 1'-0"
THIRD FLOOR PLAN - AREA B - LIGHTING
SHEET NOTES:
1. LIGHTING FIXTURES IN ELEVATORS, ELEVATOR
HOISTWAYS, STAIRWELLS, AND HVAC SHAFTS
SHALL BE EXISTING TO REMAIN UNLESS
OTHERWISE NOTED.
2. EXIT SIGNAGE SHALL BE EXISTING TO REMAIN
UNLESS OTHERWISE NOTED.
3. EXISTING SWITCH CONTROLS SHALL BE
EXISTING TO REMAIN AND NEW LIGHTING
FIXTURES SHALL BE RECONNECTED TO
EXISTING CIRCUITS VIA EXISTING SWITCH
CONTROLS UNLESS OTHERWISE NOTED.
DIMMING DRIVERS IN AREAS WHERE LIGHTING
FIXTURES ARE NOT DIMMED SHALL REMAIN
UNCONNECTED AND FOR FUTURE USE (ONLY
SWITCHING FUNCTION SHALL BE UTILIZED).
SCALE: 1/8" = 1' - 0"
8 0 8 16246
PHASING NOTES:
1. THIS PROJECT SHALL BE PHASED IN ORDER TO
ALLOW CONTINUOUS USE OF THE PROJECT
AREA ON A DAILY BASIS. CONTRACTOR SHALL
BE RESPONSIBLE FOR DEVELOPING PROJECT
SCHEDULE AND PHASING PLAN. CONTRACTOR
SHALL INCLUDE ANY ADDITIONAL WORK
REQUIRED TO ACCOMMODATE PHASING.
SUBMIT PHASING PLAN TO OWNER FOR
APPROVAL PRIOR TO BEGINNING
CONSTRUCTION. COORDINATE EXECUTION OF
PHASING PLAN WITH OWNER THROUGHOUT
PROJECT COMPLETION. THE FOLLOWING
PHASING CONSTRAINTS SHALL BE OBSERVED:
• WORK SHALL BE PERFORMED WITHIN A
SINGLE SPACE AT ANY GIVEN TIME.
SPACES CANNOT BE LEFT IN AN
INCOMPLETE STATE OR PROVIDED WITH
TEMPORARY LIGHTING, WORK WITHIN
EACH SPACE SHALL BE COMPLETE BY THE
END OF EACH WORKING DAY. WHERE THIS
IS NOT POSSIBLE, COORDINATE SPECIFIC
PHASING NEEDS WITH OWNER.
• CONTRACTOR SHALL COMPLY WITH THE
CAMPUS’S INFECTION CONTROL POLICIES,
COORDINATE EXACT REQUIREMENTS WITH
OWNER. CONTRACTOR SHALL PROVIDE
ANY ITEMS AS NEED TO COMPLY WITH
THESE POLICIES, SUCH AS TEMPORARY
CONSTRUCTION BARRIERS OR DUST
CARTS.
AREA A
AREA B KEYPLAN
ELEVATOR LOBBY TYPE L3 - EXISTING INSTALLATION CONDITION PHOTOS
O C
OC
O C
O C
H
H.2 H.4C
One-Bed Room
3F176
Toilet
3F176A
Toilet
3F177A
One-Bed Room
3F176
Toilet
3F176A
Toilet
3F177A
D1WD1W
D1WD1W
D5D5
D1WD1W
NL1NL1
D1WD1W
L2L2
L6L6
D2WD2W
D2WD2W
D2MD2M
N L C
K M
H.4 H.8 M.5 M.9C
Two-Bed Room
3F179
Two-Bed Room
3F180
Toilet
3F178A
Toilet
3F179A
Sat. Nurse Charting
3FC01A
Two-Bed Room
3F179
Two-Bed Room
3F180
Toilet
3F178A
Toilet
3F179A
Sat. Nurse Charting
3FC01A
D1WD1W
D1WD1W
D5D5
D1WD1W
D1WD1W
D1WD1W
D5D5
D3WD3W
L2L2
D1WD1W
NL1NL1
L2L2
D2WD2W
D2WD2W
L6L6
NL1NL1
NLC
N L C
G H
H.2
Large One-Bed Room
3F136
Toilet
3F136A
Large One-Bed Room
3F136
Toilet
3F136A
D1WD1W
D5D5
D1WD1W
NL1NL1
D1WD1W
D1WD1W
D3WD3W
L6L6
D2WD2W
D2WD2W
L2L2
N
LC1
K M N O
H.8
N.6
One-Bed Room
3F135
Toilet
3F135A
One-Bed Room
3F135
Toilet
3F135A
D3WD3W
D1WD1W
D1WD1W
NL1NL1
D5D5
D1WD1W
D1WD1W
D2WD2W
D2WD2W
L6L6
L2L2
N
LC
S
63889
W.T. GIENGER
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TE
A
H
F OO
I O
672 E ROYALTON ROAD
BROADVIEW HEIGHTS, OH 44147
P: 440.546.9696 F: 440.546.9699
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #23000104.00
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL CD DESIGN
SUBMITTAL
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SES Project : 22320
B01
UPGRADE FACILITY LIGHTING
CLEVELAND VAMC
VA MEDICAL CENTER, CLEVLAND,OH 44106
23000104.00
B
IM
/2 o u is
S to k e s C le v e la n d
V A
U p g ra d e F a c ili ty L ig h ti n g
/E
.0
V A
C le v e la n d
U p g ra d e
F a c ili ty L ig h ti n g l_ C
.r v t
/1
/2
:2
:2
P
M
E300
ENLARGED PLANS 541- 206
ShaCal ChrCam 08/07/2023
KEYNOTES:
1. ROOM AMBIENT DOWNLIGHTS (TYPE D1W) AND
LINEAR LIGHT AT HEADWALL (TYPE L2) ARE
CONTROLLED BY (2) BUTTONS ON THE
PATIENT NURSE CALL HAND SET THROUGH
EXISTING RELAYS MOUNTED ABOVE
ACCESSIBLE CEILING. REPLACEMENT
LIGHTING SHALL BE CONNECTED THROUGH
THESE EXISTING RELAYS TO MAINTAIN
EXISTING OPERATION. DOWNLIGHT OVER BED
(TYPE D5) AND AT DOOR (D3W) ARE
CONTROLLED BY SEPARATE SWITCHES AT THE
HEADWALL AND DOOR, RESPECTIVELY.
2. REPLACE EXISTING NIGHT LIGHT AT EXISTING
LOCATION AS INDICATED. CONTRACTOR SHALL
REPLACE/MODIFY EXISTING OPENING AND BOX
IS WALL AS REQUIRED FOR NEW LIGHTING
FIXTURE. PATCH AND PAINT WALL TO MATCH
EXISTING.
N O R
HT
1/4" = 1'-0"
THIRD FLOOR PLAN - LIGHTING - TYPICAL ONE BED ROOM
N O R
HT
1/4" = 1'-0"
THIRD FLOOR PLAN - LIGHTING - TYPICAL TWO BED ROOM
N O R
HT
1/4" = 1'-0"
THIRD FLOOR PLAN - AREA B - LIGHTING - LARGE ONE-BED ROOM 3F136
N O R
HT
1/4" = 1'-0"
THIRD FLOOR PLAN - AREA B - LIGHTING - LARGE ONE-BED ROOM 3F135
SHEET NOTES:
1. EXISTING SWITCH CONTROLS SHALL BE
EXISTING TO REMAIN AND NEW LIGHTING
FIXTURES SHALL BE RECONNECTED TO
EXISTING CIRCUITS VIA EXISTING SWITCH
CONTROLS UNLESS OTHERWISE NOTED.
DIMMING DRIVERS IN AREAS WHERE LIGHTING
FIXTURES ARE NOT DIMMED SHALL REMAIN
UNCONNECTED AND FOR FUTURE USE (ONLY
SWITCHING FUNCTION SHALL BE UTILIZED).
SCALE: 1/4" = 1' - 0"
4 0 4 8123
SCALE: 1/8" = 1' - 0"
8 0 8 16246
STEEL OUTLET BOX, SIZE PER N.E.C. AND
SUPPORT RIGIDLY FROM STRUCTURE
CHAIN HANGER TO STRUCTURE
6'-0" MAXIMUM LENGTH, 3/8" FLEX
CONDUIT WITH 3#18 CONDUCTORS
PENDANT MOUNTED LUMINAIRE
NOTES:
1. SELECT CHAIN LENGTH TO PROVIDE MOUNTING HEIGHT AS REQUIRED ON
DRAWINGS.
2. PROVIDE TWO CHAIN HANGERS FOR EACH LUMINAIRE.
This is the start of the file's text. The full file is on GovTribe.