This document is a set of drawings and specifications for a project to Upgrade Facility Lighting at the Louis Stokes Veterans Affairs Medical Center (LSVAMC) in Cleveland, OH. The project will include upgrading the lighting in the CARES Tower on the 3rd floor, excluding undercabinet, task, stairwell, elevator, and accessible mechanical duct lighting. The project will be solicited as a 100% Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside, requiring a minimum of 15% of the construction work to be performed by the SDVOSB contractor or subcontractor. The solicitation documents, including specifications and drawings, will be available on or about February 15, 2024, with a bid opening approximately 30 days later. The project is expected to be completed within 240 calendar days from the Notice to Proceed.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT AREA

3F-204, Med Room X

3F-200, Employee/Lockers Lounge X

3F-208, Tub Room X

3F-156, Quiet Consult X

3F-155, Staff Office X

3F-145, Office X

3F-143, Office Exam X

3F-131, Office X

3F-205, Conference Classroom X

3F-142, Toilet X

3F-141, Toilet X

Bid Alternate

1 Deleted

Rooms

Bid Alternate 2

Deleted Rooms

BID ALTERNATES 1 & 2

TRACY J.

HAUSER

E-82068

STATE OF OHIO

P

RR

O

F E

SS IONA L ENG

I N E

E

REG I TERED

S

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440546.9696 F: 440.5469699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

AREA A

AREA B KEYPLAN

08/07/2023

B

IM

/2

L o u is S to k e s C le v e la n d V

A U p g ra d e F a c ili ty L ig h ti n g /5

-2

.B

.M

.R

.r v t

/3

/2

:5

:4

P

M

G000

COVER SHEET UPGRADE FACILITY LIGHTING -

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVELAND, OH 44106

541-206

B01

08/07/2023 JLN CJF

UPGRADE FACILITY LIGHTING

LOUIS STOKES CLEVELAND VA MEDICAL CENTER

10701 EAST BLVD.

CLEVELAND, OH 44106

SHEET INDEX - GENERAL

Sheet Number Sheet Name

G000 COVER SHEET

Grand total: 1

SHEET INDEX - ELECTRICAL

Sheet Number Sheet Name

E000 ELECTRICAL COVERSHEET

E100 THIRD FLOOR ELECTRICAL KEY PLAN

ED213A THIRD FLOOR PLAN - AREA A - LIGHTING DEMOLITION

ED213B THIRD FLOOR PLAN - AREA B - LIGHTING DEMOLITION

E213A THIRD FLOOR PLAN - AREA A - LIGHTING

E213B THIRD FLOOR PLAN - AREA B - LIGHTING

E300 ENLARGED PLANS

E400 LIGHTING FIXTURE SCHEDULE AND ELECTRICAL DETAILS

Grand total: 8

SHEET INDEX - ARCHITECTURAL

Sheet Number Sheet Name

AR-103-Ala Third Floor Reflected Ceiling Plan - Skilled/Rehab. Nursing - ALTERNATE 1 - Quadrant A

(FOR REFERENCE ONLY)

AR-103-Ale Third Floor Reflected Ceiling Plan - Skilled/Rehab. Nursing - ALTERNATE 1 - Quadrant E

(FOR REFERENCE ONLY)

AE-581 INTERIOR CEILING DETAILS (FOR REFERENCE ONLY)

AE-582 INTERIOR CEILING DETAILS (FOR REFERENCE ONLY)

AE-583 INTERIOR CEILING DETAILS (FOR REFERENCE ONLY)

Grand total: 5

Revisions: Date:

ELECTRICAL ABBREVIATION KEY

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

ABBR: DESCRIPTION:

TYP TYPICAL

C CONDUIT

UON UNLESS OTHERWISE NOTED

GFI GROUND FAULT INTERRUPTER

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR

ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON

THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH

PHASE.

3. LIFE SAFETY, CRITICAL, EQUIPMENT BRANCH WIRING FOR FEEDERS AND BRANCH CIRCUITS

SHALL BE ROUTED IN SEPARATE RACEWAY, JUNCTION BOXES, PULL BOXES, AND CABINETS.

WIRING FOR EACH BRANCH SHALL BE INDEPENDENT FROM OTHER BRANCHES, INCLUDING

THE NORMAL BRANCH.

4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE

DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED

WHEN CONDUIT IS SPECIFIED EXPOSED.

5. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL

BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF

THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION

AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

6. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND

EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES

IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL

BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.

7. CONTRACTOR SHALL VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT

LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS.

PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL

ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE

FURNITURE AND/OR EQUIPMENT.

8. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,

OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL

MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT

SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER

CONTRACTOR.

9. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL

OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR. ALL

CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.

10. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.

CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING

EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE

RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF

ANY WELDERS ASSIGNED TO THE JOB.

11. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE

WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE

IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND

FINISH.

ELECTRICAL INSTALLATION NOTES:

NORMAL BRANCH LUMINAIRE

CRITICAL BRANCH LUMINAIRE

EMERGENCY LIFE SAFETY BRANCH LUMINAIRE

UNSWITCHED FOR NIGHT LIGHT, UNLESS NOTED 'SE'

LUMINAIRE SYMBOL KEY

SYMBOL: DESCRIPTION:

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING

CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND

SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE

REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.

4. THE CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS,

WALLS, AND FLOORS ASSOCIATED WITH WORK.

5. THE CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS,

CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL

CONTRACTORS.

6. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

SIMSIM

INDICATES SIMILAR DETAIL REFERENCED

IN MULTIPLE LOCATIONS

LEVEL NAME

10'-0" HEIGHT ABOVE

PROJECT 0'-0"

1 INDICATES NOTE USED TO DESCRIBE

ADDITIONAL INFORMATION ABOUT

WORK REQUIRED, SPECIFIC TO THE

SHEET AND/OR DETAIL

N

O R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

LINE TYPE AND TAG KEY:

NEW WORK BY THIS CONTRACTOR (WIDE LINE)

NEW

EXISTING TO BE REMOVED (SHORT DASHED PATTERN)

NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)

EXISTING

EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)

EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)

HALFTONING DOES NOT MODIFY SCOPE.

'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING

TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL

INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST

INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL

T101

GENERAL CONTRACTORG.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

BUILDING CODE: IBC 20** EDITION

UBC 20**

ELECTRICAL CODE: NFPA 70 (NEC) 2023 EDITION

LIFE SAFETY CODE: NFPA 101 2021 EDITION

ENERGY CONSERVATION CODE: ASHRAE 90.1 2022

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

M

A X

20" MAX.

M

A X

20"-25" MAX.

M

A X

M

IN

. 4

M

A X

M

A X

10" MAX. 10"-24" MAX.

ADA GUIDELINES - FRONT ACCESS

ADA STANDARDS FOR ACCESSIBLE DESIGN

INSTALL ABOVE COUNTER

DEVICE AT 44" ABOVE

FINISHED FLOOR.

INSTALL ABOVE COUNTER

DEVICE AT 40" ABOVE

FINISHED FLOOR.

INSTALL DEVICE AT 18"

ABOVE FINISHED FLOOR.

ADA GUIDELINES - SIDE ACCESS

INSTALL DEVICE AT 44"

ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 42"

ABOVE FINISHED FLOOR.

1. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.

2. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND

OPERATES FROM EMERGENCY CIRCUIT UPON LOSS OF POWER.

3. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN

EMERGENCY CIRCUIT.

4. REFER TO SHEET E-400 FOR LUMINAIRE SCHEDULE.

5. CONTROL STATION SHALL BE CAPABLE OF RAISE/LOWER WHERE DIMMING IS INDICATED AND

SWITCHING ON/OFF AS INDICATED ON SHEETS. COORDINATE QUANTITIES OF BUTTONS FOR

CONTROL STATIONS WITH LIGHTING CONTROL MANUFACTURER.

6. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR

DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE MANUFACTURER

SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION, ORIENTATION, AND COVERAGE AREA

OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING

MULTIPLE SENSOR DEVICES FOR APPROPRIATE COVERAGE, SUBMIT SPECIFIC

MANUFACTURER-APPROVED SENSOR LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT

DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.

ELECTRICAL GENERAL NOTES:

LUMINAIRE

F1 = FIXTURE TAG

1 = CIRCUIT NUMBER

a = SWITCH DESIGNATION

NL = SUBSCRIPT (IF APPLICABLE)

Z = ZONE DESIGNATION

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: F1 / 1 / a / NL

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

LUMINAIRE KEY:

DEVICE KEY:

FEEDERS: SWITCHBOARDS, DISTRIBUTION PANELS,

PANELBOARDS, MOTOR CONTROL CENTERS, ETC.

BRANCH CIRCUITS: LIGHTING, RECEPTACLES,

CONTROLS, ETC.

MECHANICAL EQUIPMENT FEEDERS: PUMPS, CHILLERS,

AIR HANDLING UNITS, ETC.

FLOOR MOUNTED EQUIPMENT FEEDERS: PUMPS, ETC.

(INCLUDE NO MORE THAN 6 FEET OF LFMC TO PUMP)

CONTROLS (LIGHTING, POWER, BUILDING AUTOMATION, ETC.)

WET AND DAMP LOCATIONS: (CONDUIT, BOXES, FITTINGS,

INSTALLED AND EQUIPPED TO PREVENT WATER ENTRY)

FINISHED SPACES / CONCEALED

CONDUIT INSTALLATION SCHEDULE

THE FOLLOWING SCHEDULE SHALL BE ADHERED TO UNLESS THEY CONSTITUTE A VIOLATION

OF APPLICABLE CODES OR ARE NOTED OTHERWISE ON THE DRAWINGS. THE INSTALLATION OF

RMC CONDUIT WILL BE PERMITTED IN PLACE OF ALL CONDUIT SPECIFIED IN THIS SCHEDULE.

REFER TO CONDUIT AND BOXES SPECIFICATION 26 05 33 FOR ADDITIONAL INFORMATION.

INSTALLATION TYPE RMC EMT

X

X

X

X

X

X

X

ELEVATED CONCRETE SLABS (ABOVE GRADE)

X

INTERIOR LOCATIONS: CONCEALED

INTERIOR LOCATIONS: EXPOSED

INTERIOR LOCATIONS: EXISTING WALLS AND EXPOSED

INSTALLATION (FINISHED SPACES)

X

X

X

SW-1P EXISTING SWITCH - SINGLE POLE

SW-3W EXISTING SWITCH - THREE WAY3

SW-1P-ADJ EXISTING SWITCH - LOCAL TIMER - USER ADJUSTABLET

SW-1P-M EXISTING SWITCH - MOMENTARY CONTACTM

SW-OC-P-O SWITCH - OCCUPANCY SENSOR

WALL SWITCH

O

OC SW-OC-D OCCUPANCY SENSOR - DUAL TECHNOLOGY

D

EXISTING

EXISTING

SW-OC-D-W OCCUPANCY SENSOR - DUAL

TECHNOLOGY - WALL MOUNTED

D

EXISTINGOC

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

JB 26 05 33 JUNCTION BOX

J

J

ECONN 26 05 33 ELECTRICAL CONNECTION

E

E

PANEL '###' EXISTING PANELBOARD

TR-#/DTR-# EXISTING TRANSFORMER

NLC SW-NLC NURSE CALL LIGHTING CONTROLLEREXISTING

LINEAR LUMINAIRES

TROFFER

WALL SCONCE LUMINAIRE

DOWNLIGHT LUMINAIRE

AIMABLE OR WALL WASH LUMINAIRE

INDUSTRIAL LUMINAIRE

POLE MOUNTED LUMINAIRE

SINGLE FACE EXIT SIGN

DOUBLE FACE EXIT SIGN

EMERGENCY UNIT

WALL BRACKET LUMINAIRE

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

WALL/CEILING EMERGENCY EXIT SIGN

REFER TO LUMINAIRE

SCHEDULE

SW-4W EXISTING SWITCH - FOUR WAY

S

63889

W.T. GIENGER

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

I O

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440.546.9696 F: 440.546.9699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

B01

UPGRADE FACILITY LIGHTING

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVLAND,OH 44106

23000104.00

B

IM

/2

L o u is

S to k e s C le v e la n d

V A

U p g ra d e F a c ili ty L ig h ti n g

/E

.0

V A

C le v e la n d

U p g ra d e

F a c ili ty L ig h ti n g l_ C

.r v t

/1

/2

:2

:1

P

M

E000

ELECTRICAL COVER SHEET 541- 206

ShaCal ChrCam 08/07/2023Revisions: Date:

B

E F G H K M N O P S

R UV

H.2 H.4 H.8 M.5 M.9 P.9

A

C

J

11.6

15.6

17.1

19.4

22.1

28.1

N.6 O.9

Office

3F131

Two-Bed Room

3F132

Clean Linen

3F133

Two-Bed Room

3F134

One-Bed Room

3F135

Large One-Bed Room

3F136

Large One-Bed Room

3F137

One-Bed Room

3F138

One-Bed Room

3F139

One-Bed Room

3F140

Toilet

3F141

Toilet

3F142Office Exam

3F143

EMS

3F144 Office

3F145

Dining Room

3F150

Storage

3F152

Soiled Tray Cart Storage

3F153

Non-Food Storage/ Food Prep.

3F154

Staff Office

3F155

Quiet Consult

3F156

One-Bed Room

3F170

One-Bed Room

3F171

One-Bed Room

3F172

One-Bed Room

3F173

One-Bed Room

3F174

One-Bed Room

3F175

One-Bed Room

3F176

One-Bed Room

3F177

One-Bed Room

3F178

Two-Bed Room

3F179

Two-Bed Room

3F180

Soiled Linen Holding

3F190 Trash Collect

3F191 EMS Storage

3F192

Service Elevator Lobby

3FC01B

Stair 25

3S25

Stair 27

3S27

Stair 26

3S26

Toilet

3F170A

Toilet

3F171A

Toilet

3F172A

Toilet

3F173A

Toilet

3F174A

Toilet

3F175A

Toilet

3F176A

Toilet

3F177A

Toilet

3F178A

Toilet

3F179A

Toilet

3F180A

Resident Clothing & Luggage Storage

3F101

Two-Bed Room

3F102

Office

3F103 Two-Bed Room

3F104

One-Bed Room

3F105

One-Bed Room

3F106

One-Bed Room

3F107

One-Bed Room

3F108

One-Bed Room

3F109

One-Bed Room

3F110

One-Bed Room

3F111

One-Bed Room

3F112

One-Bed Room

3F113

One-Bed Room

3F114 Toilet

3F114A

Toilet

3F113A

Toilet

3F112A

Toilet

3F111A

Toilet

3F110A

Toilet

3F109A

Toilet

3F108A

Toilet

3F107A

Toilet

3F106A

Toilet

3F105A

Toilet

3F104A

Toilet

3F102A

Elec Closet

3FELC1

Elect. Closet

3FELC2

Toilet

3F132A

Toilet

3F134A

Toilet

3F135A Toilet

3F136A

Toilet

3F137A

Toilet

3F138A

Toilet

3F139A

Toilet

3F140A

Corridor

3FC05

Employee Lockers/ Lounge

3F200

Soiled Utility

3F201

Clean Utility

3F202

Equipment Storage

3F203

Med. Room

3F204

Conference Classroom

3F205

Wheelchair Scale

3F207A Expendable Supplies

3F207

Tub Room

3F208

Resident Laundry

3F209

EMS

3F210

Toilet

3F200A

Corridor

3FC01

Corridor

3FC02

Corridor

3FC03

Corridor

3FC06

Corridor

3FC07

Corridor

3FC08

Family Waiting

3FC07BNourishment

3FC07A

Crash Cart Alcove

3FC05A

Nurse Station Ward Clerk

3FC04A

Med. Room Entry

3F204A

Vending

3FC02A

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Sat. Nurse Charting

3FC01A

Corridor

3FC04

Patient Lounge TV Room/ Day room

3F151

Office

3F131

Two-Bed Room

3F132

Clean Linen

3F133

Two-Bed Room

3F134

One-Bed Room

3F135

Large One-Bed Room

3F136

Large One-Bed Room

3F137

One-Bed Room

3F138

One-Bed Room

3F139

One-Bed Room

3F140

Toilet

3F141

Toilet

3F142Office Exam

3F143

EMS

3F144 Office

3F145

Dining Room

3F150

Storage

3F152

Soiled Tray Cart Storage

3F153

Non-Food Storage/ Food Prep.

3F154

Staff Office

3F155

Quiet Consult

3F156

One-Bed Room

3F170

One-Bed Room

3F171

One-Bed Room

3F172

One-Bed Room

3F173

One-Bed Room

3F174

One-Bed Room

3F175

One-Bed Room

3F176

One-Bed Room

3F177

One-Bed Room

3F178

Two-Bed Room

3F179

Two-Bed Room

3F180

Soiled Linen Holding

3F190 Trash Collect

3F191 EMS Storage

3F192

Service Elevator Lobby

3FC01B

Stair 25

3S25

Stair 27

3S27

Stair 26

3S26

Toilet

3F170A

Toilet

3F171A

Toilet

3F172A

Toilet

3F173A

Toilet

3F174A

Toilet

3F175A

Toilet

3F176A

Toilet

3F177A

Toilet

3F178A

Toilet

3F179A

Toilet

3F180A

Resident Clothing & Luggage Storage

3F101

Two-Bed Room

3F102

Office

3F103 Two-Bed Room

3F104

One-Bed Room

3F105

One-Bed Room

3F106

One-Bed Room

3F107

One-Bed Room

3F108

One-Bed Room

3F109

One-Bed Room

3F110

One-Bed Room

3F111

One-Bed Room

3F112

One-Bed Room

3F113

One-Bed Room

3F114 Toilet

3F114A

Toilet

3F113A

Toilet

3F112A

Toilet

3F111A

Toilet

3F110A

Toilet

3F109A

Toilet

3F108A

Toilet

3F107A

Toilet

3F106A

Toilet

3F105A

Toilet

3F104A

Toilet

3F102A

Elec Closet

3FELC1

Elect. Closet

3FELC2

Toilet

3F132A

Toilet

3F134A

Toilet

3F135A Toilet

3F136A

Toilet

3F137A

Toilet

3F138A

Toilet

3F139A

Toilet

3F140A

Corridor

3FC05

Employee Lockers/ Lounge

3F200

Soiled Utility

3F201

Clean Utility

3F202

Equipment Storage

3F203

Med. Room

3F204

Conference Classroom

3F205

Wheelchair Scale

3F207A Expendable Supplies

3F207

Tub Room

3F208

Resident Laundry

3F209

EMS

3F210

Toilet

3F200A

Corridor

3FC01

Corridor

3FC02

Corridor

3FC03

Corridor

3FC06

Corridor

3FC07

Corridor

3FC08

Family Waiting

3FC07BNourishment

3FC07A

Crash Cart Alcove

3FC05A

Nurse Station Ward Clerk

3FC04A

Med. Room Entry

3F204A

Vending

3FC02A

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Sat. Nurse Charting

3FC01A

Corridor

3FC04

Patient Lounge TV Room/ Day room

3F151

Corridor

3FC02

E213A

E100

AREA A

AREA B

AREA A

AREA B

N O

M.5 M.9 J

11.6

Elec Closet

3FELC1

Elec Closet

3FELC1

F3LN52

F3LNL4

F3LNL3

F3LCH2

F3LCL3

F3LCL4

TS-2

TC-10

TN-10

F3LSH1

K M

Elect. Closet

3FELC2

Elect. Closet

3FELC2

F3LCH1

F3LEL1 F4LNL2

F3LNL1

F3LCL1

F3LCL2

TN-9

F3LCH1

S

63889

W.T. GIENGER

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

I O

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440.546.9696 F: 440.546.9699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

B01

UPGRADE FACILITY LIGHTING

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVLAND,OH 44106

23000104.00

B

IM

/2 o u is

S to k e s C le v e la n d

V A

U p g ra d e F a c ili ty L ig h ti n g

/E

.0

V A

C le v e la n d

U p g ra d e

F a c ili ty L ig h ti n g l_ C

.r v t

/1

/2

:2

:2

P

M

E100

THIRD FLOOR ELECTRICAL KEY

PLAN

541- 206

ShaCal ChrCam 08/07/2023

N O R

HT

1/16" = 1'-0"

THIRD FLOOR PLAN - ELECTRICAL KEY PLAN

N O R

HT

1/4" = 1'-0"

THIRD FLOOR PLAN - AREA A - ELECTRICAL CLOSET 3FELC1

N O R

HT

1/4" = 1'-0"

THIRD FLOOR PLAN - AREA B - ELECTRICAL CLOSET 3FELC2

SCALE: 1/4" = 1' - 0"

4 0 4 8123

SCALE: 1/16" = 1' - 0"

16 0 16 324812

AREA A

AREA B KEYPLAN

O C

OC

O C

O C

OC

OC

OC

OC

OC

OC

OC

OC

OC

O C

OC

O C

OC

O C

O C

O C

O C

OC

O C

B E F G H K M N O P S

R U V W X Y

H.2 H.4 H.8H.9 M.5 M.9 P.9

A

C

J

11.6

15.6

17.1

One-Bed Room

3F171

One-Bed Room

3F172

One-Bed Room

3F173

One-Bed Room

3F174

One-Bed Room

3F175

One-Bed Room

3F176

One-Bed Room

3F177

One-Bed Room

3F178

Two-Bed Room

3F179

Two-Bed Room

3F180

Soiled Linen Holding

3F190 Trash Collect

3F191 EMS Storage

3F192

Service Elevator Lobby

3FC01B

Stair 25

3S25

Toilet

3F171A

Toilet

3F172A

Toilet

3F173A

Toilet

3F174A

Toilet

3F175A

Toilet

3F176A

Toilet

3F177A

Toilet

3F178A

Toilet

3F179A

Toilet

3F180A

Resident Clothing & Luggage Storage

3F101

Two-Bed Room

3F102

Office

3F103

Two-Bed Room

3F104

One-Bed Room

3F105

One-Bed Room

3F106

One-Bed Room

3F107

One-Bed Room

3F108

Toilet

3F108A

Toilet

3F107A

Toilet

3F106A

Toilet

3F105A

Toilet

3F104A

Toilet

3F102A

Elec Closet

3FELC1

Employee Lockers/ Lounge

3F200

Soiled Utility

3F201

Clean Utility

3F202

Tub Room

3F208

Resident Laundry

3F209

EMS

3F210

Toilet

3F200A

Corridor

3FC01

Corridor

3FC03

Corridor

3FC08

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Sat. Nurse Charting

3FC01A

One-Bed Room

3F171

One-Bed Room

3F172

One-Bed Room

3F173

One-Bed Room

3F174

One-Bed Room

3F175

One-Bed Room

3F176

One-Bed Room

3F177

One-Bed Room

3F178

Two-Bed Room

3F179

Two-Bed Room

3F180

Soiled Linen Holding

3F190 Trash Collect

3F191 EMS Storage

3F192

Service Elevator Lobby

3FC01B

Stair 25

3S25

Toilet

3F171A

Toilet

3F172A

Toilet

3F173A

Toilet

3F174A

Toilet

3F175A

Toilet

3F176A

Toilet

3F177A

Toilet

3F178A

Toilet

3F179A

Toilet

3F180A

Resident Clothing & Luggage Storage

3F101

Two-Bed Room

3F102

Office

3F103

Two-Bed Room

3F104

One-Bed Room

3F105

One-Bed Room

3F106

One-Bed Room

3F107

One-Bed Room

3F108

Toilet

3F108A

Toilet

3F107A

Toilet

3F106A

Toilet

3F105A

Toilet

3F104A

Toilet

3F102A

Elec Closet

3FELC1

Employee Lockers/ Lounge

3F200

Soiled Utility

3F201

Clean Utility

3F202

Tub Room

3F208

Resident Laundry

3F209

EMS

3F210

Toilet

3F200A

Corridor

3FC01

Corridor

3FC03

Corridor

3FC08

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Sat. Nurse Charting

3FC01A

T

T

T

S

63889

W.T. GIENGER

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

I O

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440.546.9696 F: 440.546.9699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

B01

UPGRADE FACILITY LIGHTING

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVLAND,OH 44106

23000104.00

B

IM

/2 o u is

S to k e s C le v e la n d

V A

U p g ra d e F a c ili ty L ig h ti n g

/E

.0

V A

C le v e la n d

U p g ra d e

F a c ili ty L ig h ti n g l_ C

.r v t

/1

/2

:2

:2

P

M

ED213A

THIRD FLOOR PLAN - AREA A -

LIGHTING DEMOLITION

541- 206

ShaCal ChrCam 08/07/2023

N O R

HT

1/8" = 1'-0"

THIRD FLOOR PLAN - AREA A - LIGHTING DEMOLITION

SHEET NOTES:

1. THE ELECTRICAL LIGHTING DRAWINGS

INDICATE EXISTING ELECTRICAL ITEMS TO BE

REMOVED. THE DRAWINGS ARE INTENDED TO

INDICATE THE SCOPE OF WORK REQUIRED

AND DO NOT INDICATE EVERY BOX, CONDUIT,

OR WIRE THAT MUST BE REMOVED. THE

CONTRACTOR SHALL VISIT THE SITE PRIOR TO

SUBMITTING A BID AND VERIFY EXISTING

CONDITIONS.

2. ALL LUMINAIRES SHOWN TO BE DEMOLISHED

SHALL BE DISPOSED OF IF NOT REQUIRED BY

OWNER FOR ATTIC STOCK. CONFIRM WITH

OWNER PRIOR TO DISPOSAL IF THE LAMPS,

LENS OR SUBSET OF LUMINAIRES SHOULD BE

TURNED OVER FOR ATTIC STOCK.

3. REMOVE EXISTING LUMINAIRES AND WALL

SWITCHES WHERE SHOWN. LOCATE, IDENTIFY

AND PREPARE ELECTRICAL CIRCUIT SERVING

REMOVED LUMINAIRES FOR REUSE WITH NEW

DEVICES.

4. WHERE WALL SWITCH DEVICE IS REMOVED

AND NOT REPLACED. PROVIDE WITH BLANK

SWITCH PLATE.

5. EQUIPMENT REMOVAL IN CERTAIN LOCATIONS

MAY REQUIRE THE INSTALLATION OF A

JUNCTION BOX TO RECONNECT CIRCUITS

THAT REMAIN IN OPERATION. EXTEND

CONDUIT AND WIRING AS REQUIRED TO

MAINTAIN POWER TO REMAINING EQUIPMENT.

6. BALLASTS MANUFACTURED PRIOR TO 1980

CONTAIN PCBs AND SHALL BE DISPOSED OF BY

A FEDERAL OR STATE E.P.A. APPROVED

METHOD AND IN ACCORDANCE WITH

SPECIFICATIONS.

7. HID AND FLUORESCENT LAMPS CONTAIN

MERCURY AND SHALL BE DISPOSED OF BY A

FEDERAL OR STATE E.P.A. APPROVED METHOD

AND IN ACCORDANCE WITH SPECIFICATIONS.

8. VERIFY MANUFACTURERS INSTALLATION

GUIDELINES WITH EXISTING FIELD CONDITIONS

PRIOR TO BIDDING AND ORDERING NEW LIGHT

FIXTURES AND INSTALLATION MATERIAL.

9. MATCH EXISTING PAINTED SURFACES. WHERE

REPLACED LUMINAIRE DOES NOT FULLY

COVER EXISTING JUNCTION BOX OR PAINTED

SURFACE.

10. REFER TO CEILING REFERENCE PLANS FOR

CEILING TYPES IN EXISTING AREAS, HOWEVER,

DRAWINGS ARE FOR REFERENCE ONLY AND

CONTRACTOR SHALL BE RESPONSIBLE FOR

SURVEYING AND IDENTIFYING CEILING

CONDITIONS IN FIELD PRIOR TO ORDERING

LIGHTING FIXTURES AND CEILING TILES.

KEYNOTES:

1. CONTRACTOR SHALL ASSUME THE

DEMOLITION OF EXISTING DOWNLIGHTING IN

GYPSUM BOARD CEILINGS WILL REQUIRE

CUTTING AND PATCHING OF CEILING TO

REMOVE EXISTING LIGHTING FIXTURES AND TO

INSTALL NEW LIGHTING FIXTURES.

CONTRACTOR SHALL ASSUME THE

DEMOLITION OF EXISTING DOWNLIGHTING IN

LAY-IN GRID CEILINGS WILL REQUIRE

COMPLETE REPLACEMENT OF CEILING TILE AT

ALL LOCATIONS IN LAY-IN GRID CEILINGS.

CONTRACTOR SHALL BE RESPONSIBLE FOR

ENSURING NEW LIGHTING FIXTURE TRIM

COVERS ROUGH-IN OPENING WITHOUT THE

USE OF OVERSIZED TRIM PLATES AND SHALL

RETURN CEILING BACK TO FINISHED

CONDITION. ALL UNUSED REPLACEMENT

CEILING TILES SHALL BE DELIVERED TO

OWNER FOR ATTIC STOCK. TYPICAL FOR ALL

NEW DOWNLIGHTS.

2. CONTRACTOR SHALL ASSUME THE

REPLACEMENT OF EXISTING NIGHT LIGHT

FIXTURE IN WALL WILL REQUIRE PATCHING

AND PAINTING DUE TO SMALLER DIMENSIONS

OF NEW LIGHTING FIXTURE. PROVIDE NEW

BACKBOX AS REQUIRED TO INSTALL LIGHTING

FIXTURE.

SCALE: 1/8" = 1' - 0"

8 0 8 16246

TYP.

TYP.

TYP.

TYP.

TYP.

PHASING NOTES:

1. THIS PROJECT SHALL BE PHASED IN ORDER TO

ALLOW CONTINUOUS USE OF THE PROJECT

AREA ON A DAILY BASIS. CONTRACTOR SHALL

BE RESPONSIBLE FOR DEVELOPING PROJECT

SCHEDULE AND PHASING PLAN. CONTRACTOR

SHALL INCLUDE ANY ADDITIONAL WORK

REQUIRED TO ACCOMMODATE PHASING.

SUBMIT PHASING PLAN TO OWNER FOR

APPROVAL PRIOR TO BEGINNING

CONSTRUCTION. COORDINATE EXECUTION OF

PHASING PLAN WITH OWNER THROUGHOUT

PROJECT COMPLETION. THE FOLLOWING

PHASING CONSTRAINTS SHALL BE OBSERVED:

• WORK SHALL BE PERFORMED WITHIN A

SINGLE SPACE AT ANY GIVEN TIME.

SPACES CANNOT BE LEFT IN AN

INCOMPLETE STATE OR PROVIDED WITH

TEMPORARY LIGHTING, WORK WITHIN

EACH SPACE SHALL BE COMPLETE BY THE

END OF EACH WORKING DAY. WHERE THIS

IS NOT POSSIBLE, COORDINATE SPECIFIC

PHASING NEEDS WITH OWNER.

• CONTRACTOR SHALL COMPLY WITH THE

CAMPUS’S INFECTION CONTROL POLICIES,

COORDINATE EXACT REQUIREMENTS WITH

OWNER. CONTRACTOR SHALL PROVIDE

ANY ITEMS AS NEED TO COMPLY WITH

THESE POLICIES, SUCH AS TEMPORARY

CONSTRUCTION BARRIERS OR DUST

CARTS.

AREA A

OC

OC

OC

OC

O C

O C

OC

OC

OC

O C

O C

O C

O C

O C

O C

O C

O C

O C

OC

O C

O C

O C

O C

OC

OC

OC27

B

E F G H K M N O P S

H.2 H.8A C J

19.4

22.1

28.1

N.6 O.9

Office

3F131

Two-Bed Room

3F132

Clean Linen

3F133

Two-Bed Room

3F134

One-Bed Room

3F135

Large One-Bed Room

3F136

Large One-Bed Room

3F137

One-Bed Room

3F138

One-Bed Room

3F139

One-Bed Room

3F140

Toilet

3F141

Toilet

3F142

Office Exam

3F143

EMS

3F144

Office

3F145

Dining Room

3F150

Storage

3F152

Soiled Tray Cart Storage

3F153

Non-Food Storage/ Food Prep.

3F154

Staff Office

3F155

Quiet Consult

3F156

One-Bed Room

3F170

One-Bed Room

3F171

One-Bed Room

3F172

Stair 27

3S27

Stair 26

3S26

Toilet

3F170A

Toilet

3F171A

Toilet

3F172A

One-Bed Room

3F107

One-Bed Room

3F108

One-Bed Room

3F109

One-Bed Room

3F110

One-Bed Room

3F111

One-Bed Room

3F112

One-Bed Room

3F113

One-Bed Room

3F114Toilet

3F114A

Toilet

3F113A

Toilet

3F112A

Toilet

3F111A

Toilet

3F110A

Toilet

3F109A

Toilet

3F108A

Elect. Closet

3FELC2

Toilet

3F132A

Toilet

3F134A

Toilet

3F135A

Toilet

3F136A

Toilet

3F137A

Toilet

3F138A

Toilet

3F139A

Toilet

3F140A

Corridor

3FC05

Equipment Storage

3F203

Med. Room

3F204

Conference Classroom

3F205

Wheelchair Scale

3F207A

Expendable Supplies

3F207

Tub Room

3F208

Corridor

3FC02

Corridor

3FC06

Corridor

3FC07

Family Waiting

3FC07B

Nourishment

3FC07A

Crash Cart Alcove

3FC05A

Nurse Station Ward Clerk

3FC04A

Med. Room Entry

3F204A

Vending

3FC02A

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Corridor

3FC04

Patient Lounge TV Room/ Day room

3F151

Office

3F131

Two-Bed Room

3F132

Clean Linen

3F133

Two-Bed Room

3F134

One-Bed Room

3F135

Large One-Bed Room

3F136

Large One-Bed Room

3F137

One-Bed Room

3F138

One-Bed Room

3F139

One-Bed Room

3F140

Toilet

3F141

Toilet

3F142

Office Exam

3F143

EMS

3F144

Office

3F145

Dining Room

3F150

Storage

3F152

Soiled Tray Cart Storage

3F153

Non-Food Storage/ Food Prep.

3F154

Staff Office

3F155

Quiet Consult

3F156

One-Bed Room

3F170

One-Bed Room

3F171

One-Bed Room

3F172

Stair 27

3S27

Stair 26

3S26

Toilet

3F170A

Toilet

3F171A

Toilet

3F172A

One-Bed Room

3F107

One-Bed Room

3F108

One-Bed Room

3F109

One-Bed Room

3F110

One-Bed Room

3F111

One-Bed Room

3F112

One-Bed Room

3F113

One-Bed Room

3F114Toilet

3F114A

Toilet

3F113A

Toilet

3F112A

Toilet

3F111A

Toilet

3F110A

Toilet

3F109A

Toilet

3F108A

Elect. Closet

3FELC2

Toilet

3F132A

Toilet

3F134A

Toilet

3F135A

Toilet

3F136A

Toilet

3F137A

Toilet

3F138A

Toilet

3F139A

Toilet

3F140A

Corridor

3FC05

Equipment Storage

3F203

Med. Room

3F204

Conference Classroom

3F205

Wheelchair Scale

3F207A

Expendable Supplies

3F207

Tub Room

3F208

Corridor

3FC02

Corridor

3FC06

Corridor

3FC07

Family Waiting

3FC07B

Nourishment

3FC07A

Crash Cart Alcove

3FC05A

Nurse Station Ward Clerk

3FC04A

Med. Room Entry

3F204A

Vending

3FC02A

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Corridor

3FC04

Patient Lounge TV Room/ Day room

3F151

T

S

63889

W.T. GIENGER

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

I O

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440.546.9696 F: 440.546.9699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

B01

UPGRADE FACILITY LIGHTING

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVLAND,OH 44106

23000104.00

B

IM

/2 o u is

S to k e s C le v e la n d

V A

U p g ra d e F a c ili ty L ig h ti n g

/E

.0

V A

C le v e la n d

U p g ra d e

F a c ili ty L ig h ti n g l_ C

.r v t

/1

/2

:2

:2

P

M

ED213B

THIRD FLOOR PLAN - AREA B -

LIGHTING DEMOLITION

541- 206

ShaCal ChrCam 08/07/2023

N O R

HT

1/8" = 1'-0"

THIRD FLOOR PLAN - AREA B - LIGHTING DEMOLITION

SHEET NOTES:

1. THE ELECTRICAL LIGHTING DRAWINGS

INDICATE EXISTING ELECTRICAL ITEMS TO BE

REMOVED. THE DRAWINGS ARE INTENDED TO

INDICATE THE SCOPE OF WORK REQUIRED

AND DO NOT INDICATE EVERY BOX, CONDUIT,

OR WIRE THAT MUST BE REMOVED. THE

CONTRACTOR SHALL VISIT THE SITE PRIOR TO

SUBMITTING A BID AND VERIFY EXISTING

CONDITIONS.

2. ALL LUMINAIRES SHOWN TO BE DEMOLISHED

SHALL BE DISPOSED OF IF NOT REQUIRED BY

OWNER FOR ATTIC STOCK. CONFIRM WITH

OWNER PRIOR TO DISPOSAL IF THE LAMPS,

LENS OR SUBSET OF LUMINAIRES SHOULD BE

TURNED OVER FOR ATTIC STOCK.

3. REMOVE EXISTING LUMINAIRES AND WALL

SWITCHES WHERE SHOWN. LOCATE, IDENTIFY

AND PREPARE ELECTRICAL CIRCUIT SERVING

REMOVED LUMINAIRES FOR REUSE WITH NEW

DEVICES.

4. WHERE WALL SWITCH DEVICE IS REMOVED

AND NOT REPLACED. PROVIDE WITH BLANK

SWITCH PLATE.

5. EQUIPMENT REMOVAL IN CERTAIN LOCATIONS

MAY REQUIRE THE INSTALLATION OF A

JUNCTION BOX TO RECONNECT CIRCUITS

THAT REMAIN IN OPERATION. EXTEND

CONDUIT AND WIRING AS REQUIRED TO

MAINTAIN POWER TO REMAINING EQUIPMENT.

6. BALLASTS MANUFACTURED PRIOR TO 1980

CONTAIN PCBs AND SHALL BE DISPOSED OF BY

A FEDERAL OR STATE E.P.A. APPROVED

METHOD AND IN ACCORDANCE WITH

SPECIFICATIONS.

7. HID AND FLUORESCENT LAMPS CONTAIN

MERCURY AND SHALL BE DISPOSED OF BY A

FEDERAL OR STATE E.P.A. APPROVED METHOD

AND IN ACCORDANCE WITH SPECIFICATIONS.

8. VERIFY MANUFACTURERS INSTALLATION

GUIDELINES WITH EXISTING FIELD CONDITIONS

PRIOR TO BIDDING AND ORDERING NEW LIGHT

FIXTURES AND INSTALLATION MATERIAL.

9. MATCH EXISTING PAINTED SURFACES. WHERE

REPLACED LUMINAIRE DOES NOT FULLY

COVER EXISTING JUNCTION BOX OR PAINTED

SURFACE.

10. REFER TO CEILING REFERENCE PLANS FOR

CEILING TYPES IN EXISTING AREAS, HOWEVER,

DRAWINGS ARE FOR REFERENCE ONLY AND

CONTRACTOR SHALL BE RESPONSIBLE FOR

SURVEYING AND IDENTIFYING CEILING

CONDITIONS IN FIELD PRIOR TO ORDERING

FIXTURES AND CEILING TILES.

KEYNOTES:

1. CONTRACTOR SHALL ASSUME THE

DEMOLITION OF EXISTING LIGHTING IN

GYPSUM BOARD CEILINGS WILL REQUIRE

CUTTING AND PATCHING OF CEILING TO

REMOVE EXISTING LIGHTING FIXTURES AND TO

INSTALL NEW LIGHTING FIXTURES.

CONTRACTOR SHALL ASSUME THE

DEMOLITION OF EXISTING LIGHTING IN LAY-IN

GRID CEILINGS WILL REQUIRE COMPLETE

REPLACEMENT OF CEILING TILE AT ALL

DOWNLIGHT LOCATIONS IN LAY-IN GRID

CEILINGS. CONTRACTOR SHALL BE

RESPONSIBLE FOR ENSURING NEW LIGHTING

FIXTURE TRIM COVERS ROUGH-IN OPENING

AND SHALL RETURN CEILING BACK TO

FINISHED CONDITION. ALL UNUSED

REPLACEMENT CEILING TILES SHALL BE

DELIVERED TO OWNER FOR ATTIC STOCK.

TYPICAL FOR ALL NEW DOWNLIGHTS

2. EXISTING CEILING IS A SPECIALTY DECORATIVE

CEILING TILE WITH A WOOD-LOOK

APPEARANCE. CONTRACTOR SHALL TAKE

SPECIAL CARE OF EXISTING TILES IN THIS

AREA. BID SHALL ACCOMODATE

REPLACEMENT OF SPECIALTY CEILING TILES

NECESSARY TO REMOVE EXISTING LIGHTING

AND INSTALL NEW, PER KEY NOTE #1.

3. EXISTING LIGHTING FIXTURES ARE WALL-

MOUNTED WITH HOUSING TO SUPPORT

CEILING TILES. NEW SPECIFIED LIGHTING

FIXTURE DIMENSIONS DO NOT MATCH

EXISTING AND WILL REQUIRE WALL FINISH

PATCHING AND PAINTING AS WELL AS CEILING

SYSTEM REMEDIATION AND NEW CEILING

TILES. REFER TO NEW WORK PLAN FOR

ADDITIONAL INFORMATION.

4. CONTRACTOR SHALL ASSUME PENDANT

FIXTURE CANOPY WILL NOT MATCH EXISTING

LIGHTING FIXTURE AND CEILING WILL REQUIRE

PATCHING AND PAINTING TO RETURN TO

EXISTING CONDITION.

5. CONTRACTOR SHALL ASSUME THE

REPLACEMENT OF EXISTING NIGHT LIGHT

FIXTURE IN WALL WILL REQUIRE PATCHING

AND PAINTING DUE TO SMALLER DIMENSIONS

OF NEW LIGHTING FIXTURE. PROVIDE NEW

BACKBOX AS REQUIRED TO INSTALL LIGHTING

FIXTURE.

SCALE: 1/8" = 1' - 0"

8 0 8 16246

TYP.

TYP.

TYP.

TYP. 1

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

PHASING NOTES:

1. THIS PROJECT SHALL BE PHASED IN ORDER TO

ALLOW CONTINUOUS USE OF THE PROJECT

AREA ON A DAILY BASIS. CONTRACTOR SHALL

BE RESPONSIBLE FOR DEVELOPING PROJECT

SCHEDULE AND PHASING PLAN. CONTRACTOR

SHALL INCLUDE ANY ADDITIONAL WORK

REQUIRED TO ACCOMMODATE PHASING.

SUBMIT PHASING PLAN TO OWNER FOR

APPROVAL PRIOR TO BEGINNING

CONSTRUCTION. COORDINATE EXECUTION OF

PHASING PLAN WITH OWNER THROUGHOUT

PROJECT COMPLETION. THE FOLLOWING

PHASING CONSTRAINTS SHALL BE OBSERVED:

• WORK SHALL BE PERFORMED WITHIN A

SINGLE SPACE AT ANY GIVEN TIME.

SPACES CANNOT BE LEFT IN AN

INCOMPLETE STATE OR PROVIDED WITH

TEMPORARY LIGHTING, WORK WITHIN

EACH SPACE SHALL BE COMPLETE BY THE

END OF EACH WORKING DAY. WHERE THIS

IS NOT POSSIBLE, COORDINATE SPECIFIC

PHASING NEEDS WITH OWNER.

• CONTRACTOR SHALL COMPLY WITH THE

CAMPUS’S INFECTION CONTROL POLICIES,

COORDINATE EXACT REQUIREMENTS WITH

OWNER. CONTRACTOR SHALL PROVIDE

ANY ITEMS AS NEED TO COMPLY WITH

THESE POLICIES, SUCH AS TEMPORARY

CONSTRUCTION BARRIERS OR DUST

CARTS.

AREA A

OC

OC

OC

OC

OC

OC

OC

One-Bed Room

3F171

One-Bed Room

3F172

One-Bed Room

3F173

One-Bed Room

3F174

One-Bed Room

3F175

One-Bed Room

3F176

One-Bed Room

3F177

One-Bed Room

3F178

Two-Bed Room

3F179

Two-Bed Room

3F180

Soiled Linen Holding

3F190

Trash Collect

3F191

EMS Storage

3F192

Service Elevator Lobby

3FC01B

Stair 25

3S25

Toilet

3F171A

Toilet

3F172A

Toilet

3F173A

Toilet

3F174A

Toilet

3F175A

Toilet

3F176A

Toilet

3F177A

Toilet

3F178A

Toilet

3F179A

Toilet

3F180A

Resident Clothing & Luggage Storage

3F101

Two-Bed Room

3F102

Office

3F103

Two-Bed Room

3F104

One-Bed Room

3F105

One-Bed Room

3F106

One-Bed Room

3F107

One-Bed Room

3F108Toilet

3F108A

Toilet

3F107A

Toilet

3F106A

Toilet

3F105A

Toilet

3F104A

Toilet

3F102A

Elec Closet

3FELC1

Employee Lockers/ Lounge

3F200

Soiled Utility

3F201

Clean Utility

3F202

Tub Room

3F208

Resident Laundry

3F209

EMS

3F210

Toilet

3F200A

Corridor

3FC01

Corridor

3FC03

Corridor

3FC08

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Sat. Nurse Charting

3FC01A

B E F G H K M N O P S

R U V W X Y

H.2 H.4 H.8H.9 M.5 M.9 P.9

A

C

J

11.6

15.6

17.1

T T

T

D2MD2M

D2MD2M

D2MD2M

D2MD2M

D3MD3M

L4L4L4L4

D2MD2M D2MD2M D2MD2M D2MD2M

R23R23

R23R23

R23R23R23R23 R23R23

R23R23 R23R23

R23R23

L1L1

L1L1

L1L1

DWW1DWW1

DWW1DWW1

DWW1DWW1

L1L1

L1L1

L1

NL

L1

DWW1DWW1

DWW1DWW1

DWW1DWW1

L1

NL

L1

L1L1

D2MD2M

D2MD2M

D2MD2M

D2MD2M

D2MD2M

L1L1

L1

NL

L1

L1

NL

L1

L1L1

D2MD2M

D2MD2M

D2MD2M

D2MD2M

D2MD2M

D2MD2M

L1

NL

L1

L1L1

L1

NL

L1

L1/NLL1

L1L1

L1L1

L1

NL

L1

L1

NL

L1

L1L1

L1L1

L1

NL

L1

L1

NL

L1

L1L1

L1L1

L1

NL

L1

L1L1

L1

NL

L1

DWW1DWW1

DWW1DWW1

DWW1DWW1

DWW1DWW1

DWW1DWW1

DWW1DWW1

DWW1DWW1

DWW1DWW1

D3MD3M

D3WD3W

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

C1C1

C1C1

C1C1 C1C1

Corridor

3FC02

D2WD2W D2WD2W

D2WD2WD2WD2W

4 5

E100

O

O

O O

O

O

O O

S

63889

W.T. GIENGER

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

I O

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440.546.9696 F: 440.546.9699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

B01

UPGRADE FACILITY LIGHTING

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVLAND,OH 44106

23000104.00

B

IM

/2 o u is

S to k e s C le v e la n d

V A

U p g ra d e F a c ili ty L ig h ti n g

/E

.0

V A

C le v e la n d

U p g ra d e

F a c ili ty L ig h ti n g l_ C

.r v t

/1

/2

:3

:1

P

M

E213A

THIRD FLOOR PLAN - AREA A -

LIGHTING

541- 206

ShaCal ChrCam 08/07/2023

N O R

HT

1/8" = 1'-0"

THIRD FLOOR PLAN - AREA A - LIGHTING

SHEET NOTES:

1. LIGHTING FIXTURES IN ELEVATORS, ELEVATOR

HOISTWAYS, STAIRWELLS, AND HVAC SHAFTS

SHALL BE EXISTING TO REMAIN UNLESS

OTHERWISE NOTED.

2. EXIT SIGNAGE SHALL BE EXISTING TO REMAIN

UNLESS OTHERWISE NOTED.

3. EXISTING SWITCH CONTROLS SHALL BE

EXISTING TO REMAIN AND NEW LIGHTING

FIXTURES SHALL BE RECONNECTED TO

EXISTING CIRCUITS VIA EXISTING SWITCH

CONTROLS UNLESS OTHERWISE NOTED.

DIMMING DRIVERS IN AREAS WHERE LIGHTING

FIXTURES ARE NOT DIMMED SHALL REMAIN

UNCONNECTED AND FOR FUTURE USE (ONLY

SWITCHING FUNCTION SHALL BE UTILIZED).

KEYNOTES:

1. REFER TO 2/E300 FOR TYPICAL ONE-BED

ROOM LIGHTING LAYOUT.

2. REFER TO 1/E300 FOR TYPICAL TWO-BED

ROOM LIGHTING LAYOUT.

3. CONTRACTOR SHALL IDENTIFY FUCTION OF

ALL SWITCHES AT ALL LOCATIONS WITH

MULTIPLE SWITCH CONTROLS PRIOR TO

REPLACEMENT OF EXISTING LIGHTING

FIXTURES. PROVIDE UPDATED DEVICE

COVERPLATES WITH ENGRAVED LABELING

FOR FUNCTION OF EACH SWITCH. PROVIDE A

DOCUMENT WITH PROPOSED SWITCH

LABELING AT EACH LOCATION TO VA FOR

REVIEW PRIOR TO ENGRAVING.

4. MOUNT NEW COVE LIGHT DRIVER/LOW-

VOLTAGE POWER SUPPLY IN A

MANUFACTURER APPROVED ENCLOSURE AT

AN ACCESSIBLE LOCATION ABOVE LAY-IN

FINISHED CEILING. COORDINATE WITH

EXISTING CONDITIONS AND NOTE

INSTALLATION LOCATION ON AS-BUILT

DRAWINGS.

5. PROVIDE A SAMPLE OF INTENDED SUBMITTAL

LIGHTING FIXTURE AND MOCK-UP A

FUNCTIONAL 8' SECTION OF COVE FOR VA COR

APPROVAL PRIOR TO ORDERING LIGHTING

FIXTURES. PROVIDE SEVEN-DAY NOTIFICATION

TO VA AND ENGINEER PRIOR TO MOCK-UP TO

SCHEDULE A SITE VISIT.

6. AS PART OF BID ALTERNATE 1, ELIMINATE NEW

LIGHTING SCOPE IN THIS ROOM. EXISTING

LIGHTING FIXTURES SHALL REMAIN.

7. SPECIFIED NEW LIGHTING FIXTURE TYPE L1 IS

SLIGHTLY WIDER THAN EXISTING.

CONTRACTOR SHALL MODIFY EXISTING

CEILING SUPPORT SYSTEM TO ACCOMMODATE

NEW LIGHTING FIXTURE AND TRIM EXISTING

TILES AS REQUIRED TO FIT. TYPICAL FOR ALL

CORRIDOR LINEAR LIGHTING FIXTURES. REFER

TO PHOTOS ON THIS SHEET FOR EXISTING

INSTALLATION CONDITION.

8. EXISTING LIGHTING FIXTURE IS INSTALLED IN A

GYPSUM BOARD CEILING. MODIFY OPENING AS

REQUIRED TO ACCOMMODATE NEW LIGHTING

FIXTURE TYPE L4 AND PAINT TO MATCH.

REFER TO PHOTO ON THIS SHEET FOR

EXISTING INSTALLATION CONDITION.

SCALE: 1/8" = 1' - 0"

8 0 8 16246

PHASING NOTES:

1. THIS PROJECT SHALL BE PHASED IN ORDER TO

ALLOW CONTINUOUS USE OF THE PROJECT

AREA ON A DAILY BASIS. CONTRACTOR SHALL

BE RESPONSIBLE FOR DEVELOPING PROJECT

SCHEDULE AND PHASING PLAN. CONTRACTOR

SHALL INCLUDE ANY ADDITIONAL WORK

REQUIRED TO ACCOMMODATE PHASING.

SUBMIT PHASING PLAN TO OWNER FOR

APPROVAL PRIOR TO BEGINNING

CONSTRUCTION. COORDINATE EXECUTION OF

PHASING PLAN WITH OWNER THROUGHOUT

PROJECT COMPLETION. THE FOLLOWING

PHASING CONSTRAINTS SHALL BE OBSERVED:

• WORK SHALL BE PERFORMED WITHIN A

SINGLE SPACE AT ANY GIVEN TIME.

SPACES CANNOT BE LEFT IN AN

INCOMPLETE STATE OR PROVIDED WITH

TEMPORARY LIGHTING, WORK WITHIN

EACH SPACE SHALL BE COMPLETE BY THE

END OF EACH WORKING DAY. WHERE THIS

IS NOT POSSIBLE, COORDINATE SPECIFIC

PHASING NEEDS WITH OWNER.

• CONTRACTOR SHALL COMPLY WITH THE

CAMPUS’S INFECTION CONTROL POLICIES,

COORDINATE EXACT REQUIREMENTS WITH

OWNER. CONTRACTOR SHALL PROVIDE

ANY ITEMS AS NEED TO COMPLY WITH

THESE POLICIES, SUCH AS TEMPORARY

CONSTRUCTION BARRIERS OR DUST

CARTS.

AREA A

AREA B KEYPLAN

CORRIDOR TYPE L1 - EXISTING INSTALLATION CONDITION PHOTOS

TUB ROOM TYPE L4 - EXISTING INSTALLATION CONDITION PHOTO

OC

OC

OC

OC

OC

O C

OC

O C

O C

OC

OC

OC

Office

3F131

Two-Bed Room

3F132

Clean Linen

3F133

Two-Bed Room

3F134

One-Bed Room

3F135

Large One-Bed Room

3F136

Large One-Bed Room

3F137

One-Bed Room

3F138

One-Bed Room

3F139

One-Bed Room

3F140

Toilet

3F141

Toilet

3F142

Office Exam

3F143

EMS

3F144

Office

3F145

Dining Room

3F150

Storage

3F152

Soiled Tray Cart Storage

3F153

Non-Food Storage/ Food Prep.

3F154

Staff Office

3F155

Quiet Consult

3F156

One-Bed Room

3F170

One-Bed Room

3F171

One-Bed Room

3F172

Stair 27

3S27

Stair 26

3S26

Toilet

3F170A

Toilet

3F171A

Toilet

3F172A

One-Bed Room

3F107

One-Bed Room

3F108

One-Bed Room

3F109

One-Bed Room

3F110

One-Bed Room

3F111

One-Bed Room

3F112

One-Bed Room

3F113

One-Bed Room

3F114Toilet

3F114A

Toilet

3F113A

Toilet

3F112A

Toilet

3F111A

Toilet

3F110A

Toilet

3F109A

Toilet

3F108A

Elect. Closet

3FELC2

Toilet

3F132A

Toilet

3F134A

Toilet

3F135A

Toilet

3F136A

Toilet

3F137A

Toilet

3F138A

Toilet

3F139A

Toilet

3F140A

Corridor

3FC05

Equipment Storage

3F203

Med. Room

3F204

Conference Classroom

3F205

Wheelchair Scale

3F207A

Expendable Supplies

3F207

Tub Room

3F208

Corridor

3FC02

Corridor

3FC06

Corridor

3FC07

Family Waiting

3FC07B

Nourishment

3FC07A

Crash Cart Alcove

3FC05A

Nurse Station Ward Clerk

3FC04A

Med. Room Entry

3F204A

Vending

3FC02A

Telecom/ IRM

3FLVC1

Elec. Closet

3FLVC2

Corridor

3FC04

Patient Lounge TV Room/ Day room

3F151

B

E F G H K M N O P S

H.2 H.8A C J

19.4

22.1

28.1

N.6 O.9

R22R22 R22R22 R22R22

R22R22 R22R22

L6L6

L6L6

D2WD2W

D2WD2W

R22R22 R22R22

L1

NL

L1

L1L1 L1L1

L1L1

L1L1

L1L1

L1L1

L1L1

L1L1

L1L1

L1L1

L1

NL

L1

L1

NL

L1

L1L1

L1

NL

L1

P1P1

P1P1

P1/NLP1 P1P1

P1P1 P1P1

P1/NLP1

P1P1

P1/NLP1

D1MD1M D1MD1M D1MD1M D1MD1M

P1P1 P1P1

D1MD1M

D1MD1M D1MD1M

D1MD1M D1MD1M

D1MD1M

DWW1DWW1

D1MD1M

D4D4 D4D4 D4D4

D1MD1MD1MD1M

D3WD3W

D1MD1M

D1MD1M

D1MD1M

P1P1

R22R22

R22R22

R23R23 R23R23

R23R23 R23R23

D1MD1M

D1MD1M

D1MD1M

D1MD1M

D1MD1M

D1MD1M

D3MD3M D3M/NLD3M

D3MD3M

D3MD3M

D3M/NLD3M

D3MD3M

D3MD3M

D3M/NLD3M

D3MD3M D1M/NLD1M D1MD1M D1MD1M D1M/NLD1M D1MD1M D1MD1M D1M/NLD1M D1MD1M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

D3MD3M

P1/NLP1 P1P1 P1P1 P1/NLP1

L5L5 L5L5

L5L5 L5L5

D3WD3W

D3WD3W

D3WD3W

D3WD3W

D3WD3W

R21R21 R21R21

R21R21R21R21

D3WD3W

DWW1DWW1

DWW1DWW1

DWW1DWW1

DWW1DWW1

DWW1DWW1

L1

NL

L1

L1L1

L1L1

L1

NL

L1

L1

NL

L1

L1L1

L1L1

L1

NL

L1

L1

NL

L1

L1L1

D2MD2M

R22R22

R22R22

L4L4 L4L4 L4L4

D2WD2W D2WD2W

L1L1

L1

NL

L1

D1MD1M

D2MD2M

D2MD2M

D2MD2M

L1

NL

L1

L1L1

L1

NL

L1

DWW1DWW1

DWW1DWW1

DWW1DWW1

D3MD3M

D4D4

D4D4

L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3 L3L3

C1C1

C1C1 C1C1

L1L1 L1

NL

L1

HA

T

D3MD3M

N

LC

N

LC

E300

E300

C1C1

E100

DWW1DWW1 DWW1DWW1 DWW1DWW1

DWW1DWW1 DWW1DWW1

DWW1DWW1DWW1DWW1

DWW1DWW1 DWW1DWW1

DWW1DWW1

DWW1DWW1DWW1DWW1

DWW2DWW2

DWW2DWW2DWW2DWW2

DWW2/NLDWW2

O

O

O O

O

O

O

O

O

S

63889

W.T. GIENGER

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

I O

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440.546.9696 F: 440.546.9699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

B01

UPGRADE FACILITY LIGHTING

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVLAND,OH 44106

23000104.00

B

IM

/2 o u is

S to k e s C le v e la n d

V A

U p g ra d e F a c ili ty L ig h ti n g

/E

.0

V A

C le v e la n d

U p g ra d e

F a c ili ty L ig h ti n g l_ C

.r v t

/1

/2

:2

:2

P

M

E213B

THIRD FLOOR PLAN - AREA B -

LIGHTING

541- 206

ShaCal ChrCam 08/07/2023

KEYNOTES:

1. REFER TO 2/E300 FOR TYPICAL ONE-BED

ROOM LIGHTING LAYOUT.

2. REFER TO 1/E300 FOR TYPICAL TWO-BED

ROOM LIGHTING LAYOUT.

3. CONTRACTOR SHALL IDENTIFY FUCTION OF

ALL SWITCHES AT ALL LOCATIONS WITH

MULTIPLE SWITCH CONTROLS PRIOR TO

REPLACEMENT OF EXISTING LIGHTING

FIXTURES. PROVIDE UPDATED DEVICE

COVERPLATES WITH ENGRAVED LABELING

FOR FUNCTION OF EACH SWITCH. PROVIDE A

DOCUMENT WITH PROPOSED SWITCH

LABELING AT EACH LOCATION TO VA FOR

REVIEW PRIOR TO ENGRAVING.

4. MOUNT NEW COVE LIGHT DRIVER/LOW-

VOLTAGE POWER SUPPLY IN A

MANUFACTURER APPROVED ENCLOSURE AT

AN ACCESSIBLE LOCATION ABOVE LAY-IN

FINISHED CEILING. COORDINATE WITH

EXISTING CONDITIONS AND NOTE

INSTALLATION LOCATION ON AS-BUILT

DRAWINGS.

5. PROVIDE A SAMPLE OF INTENDED SUBMITTAL

LIGHTING FIXTURE AND MOCK-UP A

FUNCTIONAL 8' SECTION OF COVE FOR VA COR

APPROVAL PRIOR TO ORDERING LIGHTING

FIXTURES. PROVIDE SEVEN-DAY NOTIFICATION

TO VA AND ENGINEER PRIOR TO MOCK-UP TO

SCHEDULE A SITE VISIT.

6. CONTRACTOR SHALL PROVIDE NEW T-GRID

PARALLEL TO THE ELEVATOR WALL FOR THE

LENGTH OF THE LIGHTING FIXTURE TO

SUPPORT THE NEW LIGHTING FIXTURE AND

THE CEILING TILES. PROVIDE NEW

PERPENDICULAR T-GRID TO BE ROUTED FROM

THE LIGHTING FIXTURE TO THE NEAREST MAIN

SUPPORT RUNNER, EVERY 2FT TO SUPPORT

CEILING TILES. PROVIDE NEW CEILING TILES

FOR THE ENTIRE LIGHTING FIXTURE LENGTH.

CONTRACTOR SHALL BE RESPONSIBLE FOR

SELECTING LIGHTING FIXTURE MOUNTING

OPTIONS AND INSTALLING IN A MANNER THAT

IS CAPABLE OF SUPPORTING EXISTING CEILING

CONSTRUCTION. TYPICAL FOR ALL LIGHTING

FIXTURES AT ELEVATOR LOBBY PERIMETER.

REFER TO PHOTOS ON THIS SHEET FOR

EXISTING INSTALLATION CONDITION.

7. SPECIFIED NEW LIGHTING FIXTURE IS

SLIGHTLY WIDER THAN EXISTING.

CONTRACTOR SHALL MODIFY EXISTING

CEILING SUPPORT SYSTEM TO ACCOMMODATE

NEW LIGHTING FIXTURE AND TRIM EXISTING

TILES AS REQUIRED TO FIT. TYPICAL FOR ALL

CORRIDOR LINEAR LIGHTING FIXTURES. REFER

TO PHOTOS ON E213A FOR EXISTING

INSTALLATION CONDITION.

8. AS PART OF BID ALTERNATE 1, ELIMINATE NEW

LIGHTING SCOPE IN THIS ROOM. EXISTING

LIGHTING FIXTURES SHALL REMAIN.

9. AS PART OF BID ALTERNATE 2, ELIMINATE NEW

LIGHTING SCOPE IN THIS ROOM. EXISITING

LIGHTING FIXTURES SHALL REMAIN.

10. EXISTING LIGHTING FIXTURE AT LOCATION HAS

BEEN PREVIOUSLY REPLACED WITH LED AND

CONTROLLED VIA A DIMMING WALL SWITCH. IT

AS ASSUMED THAT EXISTING CONTROL

DEVICE IS 0-10V DIMMING AND WILL BE

COMPATIBLE WITH NEW LIGHTING FIXTURE.

FIELD VERIFY AND REPLACE SWITCH AND

LOW-VOLTAGE CONDUCTORS AS REQUIRED

FOR CONTROL OF NEW LIGHTING FIXTURE.

11. EXISTING LIGHTING FIXTURE IS INSTALLED IN A

HARD LID CEILING. MODIFY OPENING AS

REQUIRED TO ACCOMMODATE NEW LIGHTING

FIXTURE TYPE AND PAINT TO MATCH. REFER

TO PHOTO ON SHEET E213A FOR EXISTING

INSTALLATION CONDITION.

N O R

HT

1/8" = 1'-0"

THIRD FLOOR PLAN - AREA B - LIGHTING

SHEET NOTES:

1. LIGHTING FIXTURES IN ELEVATORS, ELEVATOR

HOISTWAYS, STAIRWELLS, AND HVAC SHAFTS

SHALL BE EXISTING TO REMAIN UNLESS

OTHERWISE NOTED.

2. EXIT SIGNAGE SHALL BE EXISTING TO REMAIN

UNLESS OTHERWISE NOTED.

3. EXISTING SWITCH CONTROLS SHALL BE

EXISTING TO REMAIN AND NEW LIGHTING

FIXTURES SHALL BE RECONNECTED TO

EXISTING CIRCUITS VIA EXISTING SWITCH

CONTROLS UNLESS OTHERWISE NOTED.

DIMMING DRIVERS IN AREAS WHERE LIGHTING

FIXTURES ARE NOT DIMMED SHALL REMAIN

UNCONNECTED AND FOR FUTURE USE (ONLY

SWITCHING FUNCTION SHALL BE UTILIZED).

SCALE: 1/8" = 1' - 0"

8 0 8 16246

PHASING NOTES:

1. THIS PROJECT SHALL BE PHASED IN ORDER TO

ALLOW CONTINUOUS USE OF THE PROJECT

AREA ON A DAILY BASIS. CONTRACTOR SHALL

BE RESPONSIBLE FOR DEVELOPING PROJECT

SCHEDULE AND PHASING PLAN. CONTRACTOR

SHALL INCLUDE ANY ADDITIONAL WORK

REQUIRED TO ACCOMMODATE PHASING.

SUBMIT PHASING PLAN TO OWNER FOR

APPROVAL PRIOR TO BEGINNING

CONSTRUCTION. COORDINATE EXECUTION OF

PHASING PLAN WITH OWNER THROUGHOUT

PROJECT COMPLETION. THE FOLLOWING

PHASING CONSTRAINTS SHALL BE OBSERVED:

• WORK SHALL BE PERFORMED WITHIN A

SINGLE SPACE AT ANY GIVEN TIME.

SPACES CANNOT BE LEFT IN AN

INCOMPLETE STATE OR PROVIDED WITH

TEMPORARY LIGHTING, WORK WITHIN

EACH SPACE SHALL BE COMPLETE BY THE

END OF EACH WORKING DAY. WHERE THIS

IS NOT POSSIBLE, COORDINATE SPECIFIC

PHASING NEEDS WITH OWNER.

• CONTRACTOR SHALL COMPLY WITH THE

CAMPUS’S INFECTION CONTROL POLICIES,

COORDINATE EXACT REQUIREMENTS WITH

OWNER. CONTRACTOR SHALL PROVIDE

ANY ITEMS AS NEED TO COMPLY WITH

THESE POLICIES, SUCH AS TEMPORARY

CONSTRUCTION BARRIERS OR DUST

CARTS.

AREA A

AREA B KEYPLAN

ELEVATOR LOBBY TYPE L3 - EXISTING INSTALLATION CONDITION PHOTOS

O C

OC

O C

O C

H

H.2 H.4C

One-Bed Room

3F176

Toilet

3F176A

Toilet

3F177A

One-Bed Room

3F176

Toilet

3F176A

Toilet

3F177A

D1WD1W

D1WD1W

D5D5

D1WD1W

NL1NL1

D1WD1W

L2L2

L6L6

D2WD2W

D2WD2W

D2MD2M

N L C

K M

H.4 H.8 M.5 M.9C

Two-Bed Room

3F179

Two-Bed Room

3F180

Toilet

3F178A

Toilet

3F179A

Sat. Nurse Charting

3FC01A

Two-Bed Room

3F179

Two-Bed Room

3F180

Toilet

3F178A

Toilet

3F179A

Sat. Nurse Charting

3FC01A

D1WD1W

D1WD1W

D5D5

D1WD1W

D1WD1W

D1WD1W

D5D5

D3WD3W

L2L2

D1WD1W

NL1NL1

L2L2

D2WD2W

D2WD2W

L6L6

NL1NL1

NLC

N L C

G H

H.2

Large One-Bed Room

3F136

Toilet

3F136A

Large One-Bed Room

3F136

Toilet

3F136A

D1WD1W

D5D5

D1WD1W

NL1NL1

D1WD1W

D1WD1W

D3WD3W

L6L6

D2WD2W

D2WD2W

L2L2

N

LC1

K M N O

H.8

N.6

One-Bed Room

3F135

Toilet

3F135A

One-Bed Room

3F135

Toilet

3F135A

D3WD3W

D1WD1W

D1WD1W

NL1NL1

D5D5

D1WD1W

D1WD1W

D2WD2W

D2WD2W

L6L6

L2L2

N

LC

S

63889

W.T. GIENGER

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

I O

672 E ROYALTON ROAD

BROADVIEW HEIGHTS, OH 44147

P: 440.546.9696 F: 440.546.9699

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #23000104.00

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL CD DESIGN

SUBMITTAL

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com

SES Project : 22320

B01

UPGRADE FACILITY LIGHTING

CLEVELAND VAMC

VA MEDICAL CENTER, CLEVLAND,OH 44106

23000104.00

B

IM

/2 o u is

S to k e s C le v e la n d

V A

U p g ra d e F a c ili ty L ig h ti n g

/E

.0

V A

C le v e la n d

U p g ra d e

F a c ili ty L ig h ti n g l_ C

.r v t

/1

/2

:2

:2

P

M

E300

ENLARGED PLANS 541- 206

ShaCal ChrCam 08/07/2023

KEYNOTES:

1. ROOM AMBIENT DOWNLIGHTS (TYPE D1W) AND

LINEAR LIGHT AT HEADWALL (TYPE L2) ARE

CONTROLLED BY (2) BUTTONS ON THE

PATIENT NURSE CALL HAND SET THROUGH

EXISTING RELAYS MOUNTED ABOVE

ACCESSIBLE CEILING. REPLACEMENT

LIGHTING SHALL BE CONNECTED THROUGH

THESE EXISTING RELAYS TO MAINTAIN

EXISTING OPERATION. DOWNLIGHT OVER BED

(TYPE D5) AND AT DOOR (D3W) ARE

CONTROLLED BY SEPARATE SWITCHES AT THE

HEADWALL AND DOOR, RESPECTIVELY.

2. REPLACE EXISTING NIGHT LIGHT AT EXISTING

LOCATION AS INDICATED. CONTRACTOR SHALL

REPLACE/MODIFY EXISTING OPENING AND BOX

IS WALL AS REQUIRED FOR NEW LIGHTING

FIXTURE. PATCH AND PAINT WALL TO MATCH

EXISTING.

N O R

HT

1/4" = 1'-0"

THIRD FLOOR PLAN - LIGHTING - TYPICAL ONE BED ROOM

N O R

HT

1/4" = 1'-0"

THIRD FLOOR PLAN - LIGHTING - TYPICAL TWO BED ROOM

N O R

HT

1/4" = 1'-0"

THIRD FLOOR PLAN - AREA B - LIGHTING - LARGE ONE-BED ROOM 3F136

N O R

HT

1/4" = 1'-0"

THIRD FLOOR PLAN - AREA B - LIGHTING - LARGE ONE-BED ROOM 3F135

SHEET NOTES:

1. EXISTING SWITCH CONTROLS SHALL BE

EXISTING TO REMAIN AND NEW LIGHTING

FIXTURES SHALL BE RECONNECTED TO

EXISTING CIRCUITS VIA EXISTING SWITCH

CONTROLS UNLESS OTHERWISE NOTED.

DIMMING DRIVERS IN AREAS WHERE LIGHTING

FIXTURES ARE NOT DIMMED SHALL REMAIN

UNCONNECTED AND FOR FUTURE USE (ONLY

SWITCHING FUNCTION SHALL BE UTILIZED).

SCALE: 1/4" = 1' - 0"

4 0 4 8123

SCALE: 1/8" = 1' - 0"

8 0 8 16246

STEEL OUTLET BOX, SIZE PER N.E.C. AND

SUPPORT RIGIDLY FROM STRUCTURE

CHAIN HANGER TO STRUCTURE

6'-0" MAXIMUM LENGTH, 3/8" FLEX

CONDUIT WITH 3#18 CONDUCTORS

PENDANT MOUNTED LUMINAIRE

NOTES:

1. SELECT CHAIN LENGTH TO PROVIDE MOUNTING HEIGHT AS REQUIRED ON

DRAWINGS.

2. PROVIDE TWO CHAIN HANGERS FOR EACH LUMINAIRE.