This notice provides details for an upcoming construction project solicitation. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 will issue a solicitation on or around March 28, 2022 via Beta.SAM.gov to upgrade lobby restrooms at the Northern Indiana Health Care System located in Fort Wayne, Indiana. The project scope includes updating existing restrooms and creating two new restrooms designed to meet ABAAS accessibility standards, and will be conducted in phases to mitigate interruptions. The project magnitude is estimated between $2,000,000 to $5,000,000. The NAICS code is 238220 and the size standard is $16.5M. This will be a 100% set aside for Service-Disabled Veteran-Owned Small Businesses. The notice includes instructions on obtaining safety and environmental violation histories, and states that questions will only be addressed after solicitation release through a formal RFI process published on Beta.SAM.gov.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTRACT OFFICER REPRESENTATIVE DATE
CHIEF OF ENGINEERING DATE
INTERIOR DESIGNER DATE
DEPARTMENT HEAD DATE
CONTRACT SPECIALIST DATE LEAD USER SIGNATURE DATE
N
KEY PLAN
PROJECT LOCATION-
FIRST FLOOR
SHADE INDICATES
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
JAMES GOODEN
BLDG 1HEAPY
3850 PRIORITY WAY S. DR. STE 204
INDIANAPOLIS, IN 46240
ALICIA WARREN
317.571.8795
C U s e rs
\l s p lic h a l\ D o c u m e n ts
\1 .1
.0
A v ls p lic h a l.
rv t
/4 /2
:4
:5
P M
GI000
COVER SHEET Upgrade Lobby Restroom
2121 Lake Ave Fort Wayne, IN 46805
610A4-21-205
610A4-21-205
Upgrade Lobby Restroom
Fort Wayne Veteran's Affairs Medical Center
2121 Lake Ave Fort Wayne, IN 46805
BID DOCUMENTS
BID DOCUMENTS
FULLY SPRINKLERED
JF LS03/05/2021
SHEET INDEX
SHEET
NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
GI101 LIFE SAFETY PLAN
GC101 INFECTION CONTROL/PHASING PLAN
ARCHITECTURAL
AE001 ARCHITECTURAL SYMBOLS AND ABBREVIATIONS
AE002 WALL TYPES
AD101 FIRST FLOOR DEMOLITION PLANS
AD201 DEMOLITION IMAGES
AE101 FIRST FLOOR ARCHITECTURAL PLAN
AE601 DETAILS AND DOOR SCHEDULE
AI101 FINISH PLANS
AI201 INTERIOR FINISHES ELEVATIONS
AI202 INTERIOR FINISHES ELEVATIONS AND DETAILS
AI901 INTERIOR RENDERINGS
FIRE SUPPRESSION
F000 FIRE SUPPRESSION SYMBOLS AND ABBREVIATIONS
FX101 OVERALL FIRST FLOOR FIRE SUPPRESSION PLAN
FX401 ENLARGED FIRST FLOOR FIRE SUPPRESSION PLANS
PLUMBING
P000 PLUMBING SYMBOLS, LEGENDS, AND ABBREVIATIONS
PP100 OVERALL BASEMENT PLUMBING PLAN
PP101 OVERALL FIRST FLOOR PLUMBING PLAN
PP401 ENLARGED BASEMENT FLOOR PLUMBING PLANS
PP402 ENLARGED FIRST FLOOR PLUMBING PLANS
PP600 PLUMBING DETAILS, RISERS, AND SCHEDULES
MECHANICAL
M000 MECHANICAL SYMBOLS, LEGENDS, AND ABBREVIATIONS
MH100 OVERALL BASEMENT MECHANICAL PLAN
MH101 OVERALL FIRST FLOOR MECHANICAL PLAN
MM401 ENLARGED BASEMENT MECHANICAL PLANS
MM402 ENLARGED FIRST FLOOR MECHANICAL PLANS
MM403 ENLARGED FIRST FLOOR MECHANICAL PLANS
MM600 MECHANICAL SCHEDULES AND DETAILS
MM700 MECHANICAL CONTROL SYSTEMS
ELECTRICAL
E001 ELECTRICAL LEGEND
ED101 FIRST FLOOR DEMOLITION PLANS
EL101 FIRST FLOOR ELECTRICAL PLAN
E601 LIGHTING SCHEDULE
TECHNOLOGY
T001 TECHNOLOGY LEGEND
TD101 FIRST FLOOR REMOVALS
TA101 FIRST FLOOR TECHNOLOGY PLAN
TA102 FIRST FLOOR TECHNOLOGY PLAN - OVERALL
T501 DETAILS - TECHNOLOGY
Contact:Contact: Contact:
GUIDON DESIGN INC.
Christopher Hawk
Sr. Project Manager & MEP Team Leader
MECHANICAL &
PLUMBING ENGINEER
FORT WAYNE VA MEDICAL CENTER
Russell Becker
COR
2121 Lake Ave.
Fort Wayne, IN 46805 p: 260-426-5431 x 71387 e: russell.becker@va.gov
OWNER
GUIDON DESIGN INC.
James Gooden
Sr. Project Manager & Architectural Team Leader
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 145 e: jgooden@guidondesign.com
ARCHITECT
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 167 e: chawk@guidondesign.com
AREA MAP
VICINITY MAP
CAMPUS MAP
PROJECT LOCATION
PROJECT SITE
LOCATION
Contact:
HEAPY ENGINEERING
Joel Summers
Sr. Electrical Designer
ELECTRICAL
ENGINEER
3850 Priority Way South Suite 204 Indianapolis, IN 46240 p: 317.571.8795 e: jasummers@heapy.com
N
N
N
Revisions: Date:
DN
N
TOTAL OCCUPANCY
FEC
EXIT
OCCUPANCY LOAD FACTOR
EXITS REQUIRED
SQUARE FOOTAGE
OCCUPANCY TYPE
EGRESS EXIT SIGNAGE
FIRE EXTINGUISHER CABINET
DIAGONAL DISTANCE
EXIT SEPARATION DISTANCE
EGRESS PATH
2 HR - FIRE SEPARATION
1 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
B
1500 SF
CODE ANALYSIS LEGEND
TOTAL OCCUPANCY
FEC
EXIT
OCCUPANCY LOAD FACTOR
EXITS REQUIRED
SQUARE FOOTAGE
OCCUPANCY TYPE
EGRESS EXIT SIGNAGE
FIRE EXTINGUISHER CABINET
DIAGONAL DISTANCE
EXIT SEPARATION DISTANCE
EGRESS PATH
2 HR - FIRE SEPARATION
1 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
B
1500 SF
TOTAL OCCUPANCY
FEC
EXIT
OCCUPANCY LOAD FACTOR
EXITS REQUIRED
SQUARE FOOTAGE
OCCUPANCY TYPE
EGRESS EXIT SIGNAGE
FIRE EXTINGUISHER CABINET
DIAGONAL DISTANCE
EXIT SEPARATION DISTANCE
EGRESS PATH
2 HR - FIRE SEPARATION
1 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
B
1500 SF
E X
IT
EXIT
EXIT
TRAVEL DISTANCE= 110'-0"
T R
A V
E L
D
IS
T A
N C
E
0'
-0
EXIT SEPARATION DISTANCE = 212'-0"
EXIT
TRAVEL DISTANCE= 146'-0"
238 SF
MEN'S RESTROOM
A165
236 SF
WOMEN'S
RESTROOM
A166
73 SF
MEN'S RESTROOM
76 SF
WOMEN'S
RESTROOM
278 SF
WOMENS
RESTROOM
263 SF
MENS RESTROOM
E X
IT
E X
IT
EXIT SEPARATION DISTANCE = 212'-0"
E X
IT
N
KEY PLAN
PROJECT LOCATION-
FIRST FLOOR
SHADE INDICATES
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
JAMES GOODEN
BLDG 1HEAPY
3850 PRIORITY WAY S. DR. STE 204
INDIANAPOLIS, IN 46240
ALICIA WARREN
317.571.8795
C U s e rs
\l s p lic h a l\ D o c u m e n ts
\1 .1
.0
A v ls p lic h a l.
rv t
/3 /2
:3
:0
P M
GI101
LIFE SAFETY PLAN Upgrade Lobby Restroom
2121 Lake Ave Fort Wayne, IN 46805
610A4-21-205BID DOCUMENTS
FULLY SPRINKLERED
JF DMC03/05/2021
N
N.T.S.Scale:
FIRST FLOOR LIFE SAFETY PLAN
UP
N
PB
PB
PB
PB
TEMPORARY WALLS. SEE PLAN AND PLAN NOTES
TEMPORARY CONSTRUCTION ACCESS DOORS
REFERENCE AREA FOR ABOVE CEILING
WORK ON FLOOR BELOW.
RE: ENGINEERING DRAWINGS FOR FULL
SCOPE OF WORK
BEYOND PROJECT BOUNDARY
PROJECT BOUNDARY
IC / PHASING LEGEND
CONTINUOUS FIRESAFE SEALANT
TOP AND BOTTOM, & BOTH SIDES
3 1/2" SOUND ATTENUATION BATT.
5/8" TYPE X GYPSUM BOARD, BOTH SIDES
3 5/8" METAL STUD @ 16" O.C. WITH
RUNNER CHANNELS ALONG TOP
AND BOTTOM
CONSTRUCTION
SIDE
PUBLIC
SIDE
6 MIL. FIRE RETARDANT VISQUEEN
MEMBRANE. CONTINUOUSLY ADHERE
TO THE STRUCTURAL DECK ABOVE AND
TO THE FLOOR BELOW WITH TAPE.
UNDERSIDE OF STRUCTURAL DECK
UL LISTING: U465
COORDINATE WITH EXISTING CEILING
PUBLIC SIDE
1 HOUR FIRE RATED METAL DOOR ASSEMBLY
AND FRAME WITH SEALS, CARD READER,
HARDWARE AND CLOSER
TRIATEK MONITOR
HAND SANITIZER
SEAL ALL EDGES WITH TAPE
SEAL ALL EDGES WITH TAPE
REFER TO TEMPORARY BARRIER TYPE FOR
REQUIRED CONDITION TO STRUCTURE ABOVE
VA / OSHA TEMPORARY SIGNAGE
PUBLIC SIDE
SINGLE DOOR DOUBLE DOOR
CONSTRUCTION ACTIVITY - FIRE RISK: TYPE C
PATIENT RISK GROUP: MEDIUM
CLASS OF PRECAUTION MATRIX: II
1. PROVIDE TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL
CONSTRUCTION PER NFPA 241. REFER TO DETAIL 2/GI101.
2. PROVIDE TEMPORARY INFECTION CONTROL CONSTRUCTION DOOR WITH
CARD READER ACCESS. REFER TO ELEVATION 3/GI101.
3. CONTRACTOR SHALL REMOVE EXISTING ACT AS NECESSARY TO COMPLETE
ABOVE CEILING WORK - SALVAGE ACT FOR REINSTALLATION.
4. REMOVE & REPLACE GYPSUM CEILING AS NEEDED FOR ABOVE CEILING
WORK IN THESE AREAS TO PREPARE FOR NEW CONSTRUCTION ABOVE ON
FIRST FLOOR RESTROOMS. MATCH EXISTING FINISHES. REFER TO
PLUMBING PLANS FOR MORE INFORAMTION.
5. CONTRACTOR SHALL INSTALL TEMPORARY POLY DUST BARRIER DURING
WORK - REMOVE AT END OF SHIFT AND CLEAN TO PREPARE SPACE FOR
OCCUPANCY.
A. REFER TO LIST OF REQUIRED INFECTION CONTROL PRECAUTIONS OUTLINED
BY CLASS IN SPECIFICATION 01 01 10 AND ADDITIONAL INFORMATION.
B. REFER TO DRAWINGS, SPECIFICATIONS AND DOOR HARDWARE SCHEDULE
FOR ADDITIONAL INFORMATION.
C. PROJECT SHALL BE COMPLETED IN 3 SEPARATE PHASES.
D. COORDINATE FULL SCOPE OF WORK WITH ENGINEERING DRAWINGS AND
FIELD VERIFICATION. CONTRACTOR IS RESPONSIBLE FOR SCOPE OF ABOVE
CEILING WORK REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE
PROJECT BOUNDARY.
E. COORDINATE LOCATION OF TEMPORARY INFECTION CONTROL (IC) BARRIER
WALL CONSTRUCTION AND INFECTION CONTROL (IC) MEASURES WITH COR
AND PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE. TEMPORARY
IC BARRIER WALL CONSTRUCTION LOCATIONS IN DRAWINGS ARE
APPROXIMATE. CONTRACTOR SHALL PROVIDE DRAWING TO COR AND
PATIENT SAFETY/ INFECTION CONTROL REPRESENTATIVE ONCE ICRA
PROTOCOLS AND PLAN IS APPROVED.
F. SCHEDULE AND TIME OF CONSTRUCTION WORK TO BE APPROVED BY COR
BEFORE CONSTRUCTION MAY BEGIN. PROVIDE PHASING INFORMATION FOR
ABOVE CEILING WORK IN THE CONTRACTOR PROVIDED CMP SCHEDULE FOR
WORK ALSO REQUIRED ABOVE AND BELOW THE FLOOR PLATE OF THE
PROJECT BOUNDARY.
G. ABOVE CEILING WORK SHALL TAKE PLACE BETWEEN THE HOURS OF 5:00 PM
AND 5:00 AM. IN AREAS THAT REQUIRE ABOVE CEILING WORK WHERE
CEILINGS ARE TO REMAIN, CEILING TILES SHALL BE REMOVED AND STORED
IN A SAFE MANNER UNTIL CEILING TILES CAN BE REINSTALLED. DAMAGED
AND BROKEN CEILING TILES SHALL BE REPLACED BY CONTRACTOR.
H. EXIT/ACCESS FOR ADJACENT OPERATIONAL AREAS SHALL BE MAINTAINED
DURING NORMAL BUSINESS HOURS. SEE SPECIFICATION FOR HOURS OF
OPERATION.
I. WORK REQUIRING VIBRATION OR LOAD NOISE SHALL TAKE PLACE BETWEEN
THE HOURS OF 5:00 PM AND 5:00 AM. EVERY EFFORT SHALL BE MADE TO
KEEP NOISE AND VIBRATION TO A MINIMUM.
J. PROVIDE THE FOLLOWING INFECTION CONTROL MEASURES, A 24"X36"
STICKY WALK OFF MAT AND HAND SANITIZER AT EACH TEMPORARY DOOR
LOCATION. MAT SHALL BE REPLACED OR CLEANED AS NECESSARY
K. PROVIDE THE VA AND OSHA REQUIRED TEMPORARY SIGNAGE AT EACH
TEMPORARY DOOR LOCATION.
L. CONTRACTOR SHALL SUPPLY SPILL KIT. SPILL KIT TO INCLUDE SHOP VAC,
MULTI-PURPOSE SPILL CONTROL SORBENTS TO ABSORB NON AGGRESSIVE
LIQUIDS UP TO 30 GALLONS.
M. ALL NEW MATERIAL MOVED THROUGH THE FACILITY SHALL BE COVERED
WITH 4 MIL. POLY SHEET.
N. ALL DEMOLITION MATERIAL SHALL BE REMOVED FROM THE PROJECT
BOUNDARY THROUGH THE FACILITY TO DUMPSTER ALONG VA APPROVED
ROUTE IN ENCLOSED DUMPSTER CART DESIGNED FOR SUCH PURPOSE
WITH A LID.
O. ALL MATERIAL, DEBRIS AND HAZARDOUS MATERIALS SHALL BE PROPERLY
STORED IN DESIGNATED AREAS AND APPROVED CONTAINERS. FLAMMABLE
MATERIALS SHALL NOT BE STORED IN THE FACILITY.
P. PROVIDE CONTAINMENT CART FOR ABOVE CEILING ACCESS OUTSIDE
PROJECT BOUNDARY.
A. PROJECT AREAS TO BE OCCUPIED BY STAFF AND VETERANS THROUGHOUT
CONSTRUCTION.
B. REFER TO SPECIFICATION 01 00 00 FOR INFORMATION ON WORK DURATION
FOR EACH PHASE AND AREA OF WORK.
PHASING GENERAL NOTES
INFECTION CONTROL PLAN NOTES
INFECTION CONTROL GENERAL NOTES
INFECTION CONTROL PROJECT INFORMATION
C
LE
A R
6' - 0"
CLEAR
6' - 0"
C
LE
A R
6'
C
LE
A R
6'
CLEAR
6' - 0"
AE101
AE101
AE101
PHASE 3
PHASE 1
PHASE 2
WOMENS RESTROOM
MENS RESTROOM
MEN'S RESTROOM
A165
WOMEN'S RESTROOM
A166
MEN'S RESTROOM
WOMEN'S RESTROOM
N
KEY PLAN
PROJECT LOCATION-
FIRST FLOOR
SHADE INDICATES
AREA NOT IN SCOPE
AI202
9' - 3"B
8' - 6"A 8' - 6"A
7' - 8"B
C L R
MEN'S LOCKER ROOM
CORRIDOR
LOUNGE
045B
SOILED UTILITY
HAC
MECH
DISHWASHER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
JAMES GOODEN
BLDG 1HEAPY
3850 PRIORITY WAY S. DR. STE 204
INDIANAPOLIS, IN 46240
ALICIA WARREN
317.571.8795
C U s e rs
\l s p lic h a l\ D o c u m e n ts
\1 .1
.0
A v ls p lic h a l.
rv t
/3 /2
:3
:5
P M
GC101
INFECTION CONTROL/PHASING
PLAN
Upgrade Lobby Restroom
2121 Lake Ave Fort Wayne, IN 46805
610A4-21-205BID DOCUMENTS
FULLY SPRINKLERED
JF LS03/05/2021
SCALE: 1 1/2" = 1'-0"GC101
TEMPORARY 1 HR FIRE RATED SMOKE BARRIER WALL
CONSTRUCTION NFPA 241
SCALE: 1/4" = 1'-0"GC101
4 TEMPORARY WALL CONSTRUCTION ELEVATION
SCALE: 1/8" = 1'-0"GC101
1 FIRST FLOOR ENLARGED INFECTION CONTROL PLAN
N
SCALE: 1/4" = 1'-0"GC101
3 RCP_0B - Basement - MEP PHASE 3
SCALE: 1/4" = 1'-0"GC101
2 RCP_0B - Basement - MEP PHASE 1
SECTION REFERENCE
DRAWING NUMBER
SHEET LOCATION
DRAWING NUMBER
SHEET
LOCATION
DETAIL REFERENCE
OBJECT
REFERENCED
OBJECT
REFERENCED
X
XXXX
X
XXXX
SCALE: ??
VIEW TITLE
N
NORTH ARROW
LED WALL MOUNTED LIGHT FIXTURE
LED RECESSED LIGHT FIXTURE
HVAC RETURN AIR GRILLE
HVAC SUPPLY DIFFUSER
ACCESS PANEL
A 9'-0"
CEILING TAG CEILING TYPE
FINISHED CEILING HEIGHT
REFER TO CEILING LEGEND FOR MORE
INFORMATION
EXTENT OF REVISION
REVISION SET
MECH/ELEC ITEMS: REFER TO MEP SHEETS AS APPLICABLE
PROJECT BOUNDARY
BEYOND PROJECT BOUNDARY, NIC
DETAIL/DRAWING SCALE
TITLE OF DETAIL/DRAWING
DETAIL/DRAWING NUMBER
SHEET NUMBER
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACST ACOUSTIC
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ABA ARCHITECTURE'S BARRIER ACT
ADC AUTOMATIC DOOR CLOSER
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT, ADJOINING, OR ADJUSTABLE
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AHR ANCHOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
ALUM ALUMINUM
AMP AMPERE
AMT AMOUNT
ANOD ANODIZE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPD APPROVED
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASB ASBESTOS
ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTION
ASKLR AUTOMATIC SPRINKLER
ASSN ASSOCIATION
ATCH ATTACHMENT
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AVG AVERAGE
AW ACID WASTE
AWI ARCHITECTURAL WOODWORKING INSTITUTE
AWS AMERICAN WELDING SOCIETY
B PL BASE PLATE
BAT BATTEN
BD BOARD
BEV BEVEL
BKG BACKING
BLD BUILD
BLDG BUILDING
BLKG BLOCKING
BM BEAM OR BENCHMARK
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRG BEARING
BRKT BRACKET
BRZ BRONZE
BSMT BASEMENT
BTWN BETWEEN
C CELSIUS CHANNEL OR CHANNEL CELSIUS
C CONC CAST CONCRETE
C TO C CENTER TO CENTER
CAB CABINET
CB CORNER BEAD
CBB CEMENTITIOUS (BACKER) BOARD
CCW COUNTERCLOCKWISE
CEM CEMENT
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CGSFU CERAMIC GLAZED STRUCTURAL FACING UNITS
CHEM CHEMICAL
CHFR CHAMFER
CIP CAST-IN-PLACE
CIR CIRCLE
CIRC CIRCULAR
CJ CONSTRUCTION JOINT OR CONTROL JOINT
CL CENTER LINE
CLDG CLADDING
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNR CORNER
CNTR COUNTER
CO CARBON MONOXIDE, CLEANOUT
CO₂ CARBON DIOXIDE
COL COLUMN
COM COMMON
COMB COMBINATION, COMBINED
COMM COMMUNICATION
COMP COMPONENT
CONC CONCRETE
COND CONDENSER OR CONDITION
CONN CONNECT
CONSTR CONSTRUCTION
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CPM CRITICAL PATH METHOD
CPRS COMPRESSIBLE
CRS COLD ROLLED STEEL
CS CAST CONCRETE STONE
CSB CONCRETE SPLASH BLOCK
CSG CASING
CSK COUNTER SUNK
CSMT CASEMENT
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTG COATING
CTR CENTER
CTRL CONTROL
CU COPPER C
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
CURT CURTAIN
CYL CYLINDER
CYL L CYLINDER LOCK
N NORTH
NA NOT APPLICABLE
NAT NATURAL
NATL NATIONAL
NC NOISE CRITERIA
NCOMBL NONCOMBUSTIBLE
NEG NEGATIVE
NEUT NEUTRAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NR NOISE REDUCTION
NRC NOISE REDUCTION COEFFICIENT
NRP NONREMOVABLE
NS NARROW STILE
NUM NUMERAL
O/O OUT TO OUT
O OXYGEN
OA OUTSIDE AIR OR OVERALL
OC ON CENTER
OCC OCCUPY
OCT OCTAGON
OD OUTSIDE DIAMETER OR OUTSIDE DIMENSION
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
OFD OVERFLOW DRAIN
OFF OFFICE
OF/OI OWNER FURNISHED/OWNER INSTALLED
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
OPT OPTIONAL
OR OPERATING ROOM OR OUTSIDE RADIUS
ORD ORDNANCE OR OVERFLOW ROOF DRAIN
ORG ORGANIC
ORIG ORIGINAL
ORN ORNAMENTAL
OUT OUTLET
OZ OUNCE
PAR PARALLEL OR PARAPET
PART PARTIAL
PAT PATTERN
PB PUSHBUTTON
PBD PARTICLEBOARD
PC PIECE, POLYCARBONATE OR PORTLAND CEMENT
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCP PORTLAND CEMENT PLASTER
PED PEDESTAL
PEN PENETRATE
PEND PENDANT
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PHS PHILLIPS HEAD SCREW
PKG PACKAGE
PLAM PLASTIC LAMINATE
PLAS PLASTER OR PLASTIC
PLBG PLUMBING
PLYWD PLYWOOD
PMTL PAINTED METAL
PNEU PNEUMATIC
PNL PANEL
POLY POLYETHYLENE (PLASTIC)
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATE
PREFIN PREFINISH
PRELIM PRELIMINARY
PREP PREPARATION
PRESS PRESSURE
PREV PREVIOUS
PRKG PARKING
PRMLD PREMOLDED
PROJ PROJECT
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, PNEUMATIC TUBE, OR PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QRY QUARRY
QTR QUARTER
QTY QUANTITY
QUAD QUADRANT
QUAL QUALITY
R RADIUS OR RISER
RA RETURN AIR
RAD RADIATOR
RB RESILIENT BASE OR RUBBER BASE
RB HK ROBE HOOK
RBR RUBBER
RCP REFLECTED CEILING PLAN
RCVR RECEIVER
RD ROAD OR ROOF DRAIN
REC RECESSED
RECD RECEIVED
RECPT RECEPTACLE
RECT RECTANGLE
REF REFERENCE OR REFRIGERATOR
REG REGISTER
REINF REINFORCE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
RET RETURN
REV REVISION
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
RH RIGHT HAND
RHMS ROUND HEAD MACHINE SCREW
RHR RIGHT HAND REVERSE
RHWS ROUND HEAD WOOD SCREW
RLG RAILING
RM ROOM
RND ROUND
RO ROUGH OPENING
ROW RIGHT OF WAY
RPM REVOLUTIONS PER MINUTE
RS ROUGH SAWN
RT RIGHT
RV ROOF VENT
RVS REVERSE
RWL RAIN WATER LEADER
W/ WITH
W/O WITHOUT
WARR WARRANTY
WBL WOOD BLOCKING
WC WALL COVERING OR WATER CLOSET
WC WL HNG WATER CLOSET, WALL HUNG
WCHR WATER CHILLER
WCL WL MTD WATER COOLER, WALL HUNG
WD WOOD
WDW WINDOW
WF WIDE FLANGE
WFAB WALL FABRIC
WFR WOOD FRAME
WFS WOOD FURRING STRIPS
WH WATER HEATER
WHSE WAREHOUSE
WLD WELDED
WM WIRE MESH
WP WATERPROOFING
WPD WATER PRESSURE DROP
WPM WATERPROOF MEMBRANE
WR WEATHER RESISTANT
WS WEATHERSTRIP
WSCT WAINSCOT
WT WEIGHT
X BRACE CROSS BRACE
XPS EXTRUDED POLYSTYRENE BOARD (INSULATION)
YD YARD
YR YEAR
1. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING REVIT®
SOFTWARE IN A MICROSOFT WINDOWS ENVIRONMENT. A BUILDING INFORMATION
MODEL (BIM) HAS BEEN DEVELOPED FOR DESIGN COMMUNICATION. THE MODEL
DOES NOT CONTAIN COMPLETE INFORMATION FOR USE IN COST ESTIMATING,
SYSTEMS PERFORMANCE, COORDINATION, SCHEDULING, OR FACILITIES
MANAGEMENT.
2. THE CONTRACT DOCUMENT DRAWINGS HAVE BEEN PREPARED USING THE
CONSTRUCTION SPECIFICATIONS INSTITUTE'S UNIFORM DRAWING SYSTEM AND THE
NATIONAL CAD STANDARD AS GUIDES.
3. DISCREPANCIES IN THE CONTRACT DOCUMENTS SHALL BE IMMEDIATELY BROUGHT
TO THE ATTENTION OF THE ARCHITECT AND OWNER’S REPRESENTATIVE/COR.
CONTRACTOR SHALL PROVIDE THE HIGHER GRADE OF QUALITY AND/OR GREATER
QUANTITY OF WORK WHEN BIDDING IF A CLARIFICATION CAN NOT BE OBTAINED BY
THE BID DUE DATE.
4. CONTRACTOR IS RESPONSIBLE FOR COORDINATING SCOPE OF WORK WITH
OWNER’S REPRESENTATIVE/COR AND VARIOUS FACILITY PERSONNEL INVOLVED
WITH UTILITY SHUT DOWN, INFECTION CONTROLS, OCCUPANT/EMPLOYEE SAFETY,
ACCESS CONTROL, ETC.
5. ANY INDICATION OF PROJECT LIMITS OR BOUNDARY OF DEMARCATION ARE SHOWN
FOR THE CONVENIENCE OF THE CONTRACTOR, THE FULL SCOPE OF THE PROJECT
LIMIT OF BOUNDARY REQUIRES COORDINATION WITH THE DESIGN SCOPE OF WORK
AND ACCESS TO EXISTING UTILITIES FOR TIE IN.
6. DRAWINGS ARE PREPARED FROM FIELD VERIFICATION, EXISTING FACILITY DRAWING
BASE FILES, AND USING DIMENSIONS, CONFIGURATIONS AND DETAILS OF SPECIFIC
MANUFACTURERS AS A BASIS OF DESIGN. CONTRACTOR IS RESPONSIBLE FOR
VERIFICATION OF ACTUAL DIMENSIONS, THE COORDINATION OF THE DETAILS WITH
THE PRODUCTS WHICH ARE PROVIDED PER THE SCOPE OF THE SPECIFICATIONS
AND THE SURROUNDING CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS,
ROUGH-IN DIMENSIONS, CONNECTIONS, AND OVERALL INSTALLATION
REQUIREMENTS.
7. CONTRACTOR IS RESPONSIBLE FOR THE COMPLETION OF THE ENTIRE SCOPE OF
WORK OUTLINED IN THE CONTRACT DOCUMENTS. CONTRACTOR IS RESPONSIBLE
FOR THE COORDINATION OF ALL SUB-CONTRACTORS AND THE SCOPE OF WORK
THEY PROVIDE. SUB-CONTRACTORS ARE RESPONSIBLE FOR THEIR FULL SCOPE OF
WORK WITHIN THE CONTRACT DOCUMENTS, TRADES ARE NOT SEGMENTED TO ONLY
CERTAIN SHEETS AND SPECIFICATIONS, CROSS COORDINATION IS REQUIRED.
8. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR
UNDERSTANDING INFORMATION OUTLINED IN THE SPECIFICATIONS, KEY NOTES,
GENERAL NOTES, LEGEND, CODES, ETC., PROVIDED IN THE CONTRACT DOCUMENTS.
9. CONTRACTOR AND SUB-CONTRACTORS ARE BOTH RESPONSIBLE FOR PROVIDING
AND MAINTAINING SMOKE/FIRE RATINGS OF NEW CONSTRUCTION AND EXISTING
CONSTRUCTION AS INDICATED ON DRAWINGS. THIS INCLUDES PATCHING
PENETRATIONS IN SHAFTS, WALLS, SLABS AND ROOF. ONLY U.L. APPROVED
METHODS, MATERIALS AND INSTALLATION ARE ACCEPTABLE.
10. MECHANICAL, PLUMBING, FIRE PROTECTION AND ELECTRICAL DRAWINGS SHOW
INFORMATION IN A DIAGRAMMATIC FASHION WITHOUT DIMENSIONING. THE GENERAL
CONTRACTOR IS TO COORDINATE THE LOCATIONS OF ALL MECHANICAL, PLUMBING
AND ELECTRICAL EQUIPMENT WITH RESPECT TO THE ARCHITECTURAL AND
STRUCTURAL DETAILING OF SHAFTS, CHASES, CEILING CONSTRUCTION, ETC.
11. CONTRACTOR IS RESPONSIBLE FOR VERIFYING DIMENSIONS IDENTIFIED AND NOT
IDENTIFIED IN THE CONTRACT DOCUMENTS WITH THE EXISTING AND NEW
CONSTRUCTION ELEMENTS. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION
BETWEEN THE CONTRACT DOCUMENTS, INSTALLED AND UNINSTALLED
CONSTRUCTION BEFORE THE ORDERING OF MATERIALS AND EQUIPMENT. NOTIFY
ARCHITECT AND OWNER’S REPRESENTATIVE/COR OF ANY DISCREPANCIES OR
MISSING DIMENSIONS.
12. DO NOT SCALE THE DRAWINGS. DRAWING SCALES AS INDICATED ARE FOR GENERAL
ORIENTATION AND CONTEXT ONLY.
13. THE TERM "ALIGN" MEANS TO INSTALL DIFFERENT/SIMILAR COMPONENTS OF
CONSTRUCTION TO PROVIDE A FLUSH FINISH SURFACE.
14. ALL DIMENSIONS INDICATED ARE TO FACE OF EXISTING MEMBERS, FACE OF NEW
STRUCTURAL MEMBERS, FACE OF NEW MASONRY, FACE OF NEW STUDS OR COLUMN
GRID LINES UNLESS NOTED OTHERWISE.
15. FLOOR ELEVATION 100’-0" IS EQUAL TO THE FINISH FLOOR SLAB OF THE EXISTING
SLAB FLOOR CONSTRUCTION UNLESS OTHERWISE NOTED.
16. ROUGH OPENINGS SHALL ALLOW FOR SHIM SPACE.
17. CONTRACTOR TO PROVIDE WORK WHERE DETAILS AND NOTES ARE IDENTIFIED AS
“TYPICAL” OR “SIMILAR” EACH INSTANCE THAT IS THE SAME IN NATURE TO THE
DETAIL, AREA, OR ITEM REFERENCED.
18. PROVIDED WORK SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF DELIVERY, MOUNTING,
INSTALLATION, NECESSARY BLOCKING AND ROUGH-IN.
19. INSTALLED WORK IS THE CONTRACTOR INSTALLING OWNER FURNISHED MATERIALS
AND EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF MATERIAL
DELIVERY, MOUNTING, INSTALLATION AND ROUGH IN.
20. FURNISHED WORK IS THE CONTRACTOR FURNISHING THE MATERIALS AND
EQUIPMENT TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF
DELIVERY AND ROUGH-IN.
21. ALL PROVIDED WORK SHALL BE WITH NEW MATERIALS UNLESS SPECIFICALLY
CALLED OUT AS SALVAGED OR RELOCATED WITHIN THE CONTRACT DOCUMENTS.
22. ALL PERSONS DIRECTLY OR INDIRECTLY ASSOCIATED WITH THE PROJECT SHALL BE
FAMILIAR WITH THE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND
HEALTH ACT, AND IMPLEMENT THOSE RULES AS THEY APPLY TO THIS PROJECT.
23. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND PROTECTING ALL
UTILITY LINES. LOCATIONS SHOWN ARE APPROXIMATE. REPAIR ALL DAMAGE TO
UTILITY LINES CAUSED BY CONSTRUCTION OPERATIONS AT NO COST TO THE
OWNER.
24. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING AND SHORING
REQUIRED DURING CONSTRUCTION.
25. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ADJACENT
CONSTRUCTION, FINISHES, EQUIPMENT, AND TRAVEL ROUTE TO AND FROM THE
CONSTRUCTION SITE. ANY DAMAGE OR UNACCEPTABLE WEAR BY THE
CONSTRUCTION TEAM SHALL BE REPAIRED/REPLACED BY THE CONTRACTOR AT NO
COST TO THE OWNER.
26. IN THE CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT
DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER
QUALITY OF WORK, AS DETERMINED BY THE COR, SHALL BE PROVIDED.
27. CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND COORDINATING HARDWARE,
ACCESS CONTROL AND AUTOMATIC OPERATORS ARE PROVIDED WITH COMPLETE
AND COMPATIBLE SYSTEMS REQUIRED FOR THEIR OPERATION. REFER TO DOOR
HARDWARE SCHEDULE, HARDWARE SPECIFICATIONS, AUTOMATIC OPERATOR
SPECIFICATIONS, ACCESS CONTROL SPECIFICATIONS AND ELECTRICAL DRAWINGS.
D DEPTH OR PENNY (NAIL)
D LABEL CLASS D DOOR
DAT DATUM
DB DECIBEL
DBL DOUBLE
DBL GLZ DOUBLE GLAZE
DC DIRECT CURRENT
DEG DEGREE
DEL DELETE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL DIAGRAM OR DIAGRAM DIAGONAL
DIFF DIFFERENCE OR DIFFUSER
DIM DIMENSION
DIR DIRECTION
DISP DISPENSER
DIST DISTANCE
DIV DIVIDE OR DIVISION
DL DEAD LOAD
DOC DOCUMENT
DOZ DOZEN
DN DOWN
DR DOOR, DRAIN, DRESSING ROOM, OR DRIVE
DS DOWNSPOUT
DSGN DESIGN
DWG DRAWING
E EAST
EA EACH
EFF EFFICIENCY
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELAST ELASTOMERIC
ELEC ELECTRIC
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
ENVIR ENVIRONMENT
EPA ENVIRONMENTAL PROTECTION AGENCY
EPDM ETHYLENE PROPYLENE DIENE MONOMER
EPO EMERGENCY POWER OFF
EPS EXPANDED POLYSTYRENE BOARD (INSULATION)
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ERD EXISTING ROOF DRAIN
ESC ESCAPE OR ESCUTCHEON
EST ESTIMATE
ETC AND SO FORTH OR ET CETERA
ETS EXPOSE TO STRUCTURE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION OR EXPOSED
EXT EXTERIOR, EXTERNAL, OR EXTINGUISHER
F FAHRENHEIT OR FEMALE
FA FIRE ALARM
FAB FABRIC
FAC FACTOR
FACIL FACILITY
FAS FASCIA
FCO FLOOR CLEANOUT
FCTY FACTORY
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF&E FURNITURE, FIXTURE, AND EQUIPMENT
FH FLAT HEAD OR FLAT HEAD SCREWS
FHC FIRE HOSE CABINET
FHMS FLAT HEAD MACHINE SCREW
FHP FULL HEIGHT PARTITION
FIG FIGURE
FIL FILLET
FIN FINISH
FIXT FIXTURE
FL FLOORLINE
FLASH FLASHING
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLR FLOOR
FLUOR FLUORESCENT
FM FACTORY MUTUAL
FM-G FACTORY MUTUAL GLOBAL
FO FINISHED OPENING
FOC FACE OF CONCRETE OR FACE OF CURB
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF SLAB OR FACE OF STUD
FOUNT FOUNTAIN
FOW FACE OF WALL
FP FIRE PROTECTION OR FIREPROOF
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FIRE RATING, FIRE RESISTANT, OR FRAME
FR SNK FLUSHING RIM SINK
FREQ FREQUENCY
FRMG FRAMING
FRP FIBER REINFORCED POLYESTER OR FIBERGLASS
REINFORCED PLASTIC
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET OR FOOT
FTG FOOTING
FURG FURRING
FURN FURNISH OR FURNITURE
FUT FUTURE
GA GAGE OR GYPSUM ASSOCIATION
GAL GALLON
GALV GALVANIC OR GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR
GD GUARD
GDR GUARD RAIL
GEN GENERAL OR GENERATOR
GFRG GLASS-FIBER-REINFORCED GYPSUM
GFRP GLASS-FIBER-REINFORCED PLASTIC
GI GALVANIZED IRON
GL GLASS
GR FL GROUND FLOOR
GRTG GRATING
GSB GYPSUM SHEATHING BOARD
GSM GALVANIZED SHEET METAL
GSU GLAZED STRUCTURAL UNIT
GT GROUT
GUAR GUARANTEE
GYP GYPSUM
H HIGH
H PLAM HIGH PRESSURE PLASTIC LAMINATE
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIBB
HC HOLLOW CORE
HCWD HOLLOW CORE WOOD DOOR
HDBD HARDBOARD
HDNR HARDENER
HDO HIGH DENSITY OVERLAY
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER)
HEX HEXAGON
HF HIGH FREQUENCY
HGR HANGER
HM HECTOMETER OR HOLLOW METAL
HMD HOLLOW METAL DOOR
HMDF HOLLOW METAL DOOR AND FRAME
HMF HOLLOW METAL FRAME
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HOSP HOSPITAL
HP HIGH PRESSURE OR HORSEPOWER
HS HEAT-STRENGTHENED (GLASS) OR HIGH STRENGTH
HSKPG HOUSEKEEPING
HST HOIST
HT HEIGHT
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
HVY HEAVY
HW HOT WATER
HYD HYDRANT
HYDR HYDRAULIC
IAQ INDOOR AIR QUALITY
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE DIAMETER
ID NO IDENTIFICATION NUMBER
ILLUM ILLUMINATION
INCL INCLUDED
IND INDEPENDENT OR INDUSTRIAL
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INTERCOM INTERCOMMUNICATION
INTL INTERNATIONAL
IWH INSTANTANEOUS WATER HEATER
JAN JANITOR
J-BOX JUNCTION BOX
JT JOINT
KD KILN DRIED OR KNOCKED DOWN
KO KNOCKOUT
KPL KICKPLATE
L ANGLE
LAM LAMINATE
LAM GL LAMINATED GLASS
LAV LAVATORY
LBR LUMBER
LBS POUND
LD BRG LOAD-BEARING
LDR LEADER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LH LEFT HAND
LHR LEFT HAND REVERSE OR LEFT HAND REVERSE
LATENT HEAT RATIO
LIB LIBRARY
LIN LINEAR
LIQ LIQUID
LKR LOCKER
LKR RM LOCKER ROOM
LL LEAD LINED
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LRG LARGE
LRV LOUVERED ROOF VENT
LS LUMP SUM
LT LIGHT
LT GA LIGHT GAGE
LT WT LIGHTWEIGHT
LTG LIGHTING
LTNG LIGHTNING
LVD LOUVERED
LVR LOUVER
LYR LAYER
MACH MACHINE
MAINT MAINTENANCE
MAN MANUAL
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MCB METAL CORNER BEAD
MD DECK
ME MECHANICAL ENGINEER
MEAS MEASURE
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MED MEDICAL MEDIUM OR MEDIUM MEDICAL
MEK METHYL ETHYL KETONE
MEL MELAMINE
MEMB MEMBRANE
MEMO MEMORANDUM
MF MILL FINISH
MFD MANUFACTURED
MFG MANUFACTURING
MFR MANUFACTURER
MFR REC MANUFACTURER'S RECOMMENDATION
MGT MANAGEMEN
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM MINUTE OR MINUTE MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MIT MITER
MKR MARKER
ML METAL LATH
MLDG MOLDING (MOULDING)
MLWK MILLWORK
mm MILLIMETER
MO MASONRY OPENING OR MOTOR OPERATED
MOD MODEL, MODIFY OR MODULE
MOD BIT MODIFIED BITUME
MOPR MOP RACK
MR MOISTURE RESISTANT
MS MACHINE SCREW OR MOP SINK
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
MWP MEMBRANE WATERPROOFING
X
X
XXXX
SHEET LOCATION
VIEW NUMBER
X X
X
SHEET LOCATION
VIEW NUMBER
XXXX
BUILDING SECTION REFERENCE
DRAWING NUMBER
SHEET LOCATION
BUILDING X
XXXX
X
XXXX
ELEVATION REFERENCES
NEW WALL
WALL TO BE
REMOVED
S3A.G
INDICATES STRUCTURAL MATERIAL
INDICATES NOMINAL SIZE
INDICATES STRUCTURE AND FINISH HEIGHTS
INDICATES QUALIFER
EXISTING WALL TO
REMAIN
TEMPORARY IC
BARRIER WALL
CONSTRUCTION
ROOM
ROOM TAG
NEW DOOR
EXISTING DOOR
DEMOLISHED DOOR
SA SUPPLY AIR
SALV SALVAGE
SAMP SAMPLE
SAN SANITARY
SAT SUSPENDED ACOUSTICAL TILE
SATC SUSPENDED ACOUSTICAL TILE CEILING
SB SPLASH BLOCK
SBSTR SUBSTRATE
SC SHADING COEFFICIENT OR SOLID CORE
SCHED SCHEDULE
SCHEM SCHEMATIC
SCP SCUPPER
SCRN SCREEN
SCWD SOLID CORE WOOD DOOR
SD SHOP DRAWINGS, SMOKE DETECTOR OR SOAP
DISPENSER
SDG SIDING
SECT SECTION
SEG SEGMENT
SEL SELECT
SEP SEPARATE
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT SHEET
SHT MTL FLASH SHEET METAL (FLASHING)
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SK SKETCH
SKLT SKYLIGHT
SLNT SEALANT
SM SHEET METAL
SMK SMOKE
SND SANITARY NAPKIN DISPENSER
SND INS SOUND INSULATION
S SOUTH
SNDU SANITARY NAPKIN DISPOSAL UNIT
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SPLY SUPPLY
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SS SANITARY SEWER OR SERVICE SINK
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STIF STIFFENER
STL STEEL
STL LNTL STEEL LINTEL
STL TB STEEL TUBE
STNLS STAINLESS
STOR STORAGE
STRUCT STRUCTURAL
SUB SUBSTITUTE
SURF SURFACE
SUSP SUSPEND
SV SHEET VINYL
SW SWITCH
SWDR SWING DOOR
SYM SYMBOL
SYNTH SYNTHETIC
SYS SYSTEM
TA TOILET ACCESSORY
T&G TONGUE AND GROOVE
T&M TIME AND MATERIALS
TB THROUGH BOLT OR TOWEL BAR
TCA TILE COUNCIL OF AMERICA
TD TOWEL DISPENSER
TECH TECHNICAL
TEMP TEMPERATURE OR TEMPORARY
THD THREAD
THERM THERMAL
THK THICKNESS
THRES THRESHOLD
THRU THROUGH
THRUOUT THROUGHOUT
TMPD TEMPERED
TN TRUE NORTH
TO TOP OF ___
TO FDN TOP OF FOUNDATION
TOB TOP OF BEAM
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TPH TOILET PAPER HOLDER
TR TOWEL RACK
TRANS TRANSOM
TRANS WD FIN TRANSPARENT WOOD FINISH
TRTD TREATED
TS TENSILE STRENGTH OR TUBE STEEL
TSTAT THERMOSTAT
TYP TYPICAL
U HEAT TRANSFER COEFFICIENT
UC UNDERCUT
UCD UNDERCUT DOOR
UGND UNDERGROUND
UL UNDERWRITERS LABORATORIES
ULT ULTIMATE
UNFIN UNFINISH
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UR URINAL
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VAC VACUUM
VAR VARIES
VCT VINYL COMPOSITION TILE OR VITRIFIED CLAY TILE
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VIC VICINITY
VID VIDEO
VIF VERIFY IN FIELD
VNR VENEER
VOC VOLATILE ORGANIC COMPOUND
VOL VOLUME
VOLT VOLTAGE
VR VAPOR RETARDER
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
REVISION TO PLAN CALLOUT
WALLS
DOOR TAG
KEY NOTE TAGS
WALL TAG : REFER TO WALL LEGEND FOR MORE INFORMATION
DOORS
PT-1
A
T
101 EQUIPMENT/FURNITURE TAG
FINISH INDICATION
FRAME / WINDOW
GLAZING1
1 PLAN NOTE
1 DEMOLITION NOTE
ALTERNATE/BID DEDUCT ITEM
KEY NOTE SYMBOLS
CONSTRUCTION GENERAL NOTESARCHITECTURAL SYMBOLS
REFLECTED CEILING PLAN SYMBOLS
ARCHITECTURAL ABBREVIATIONS
SPEAKERS
LED SURFACE MOUNTED LIGHT FIXTURE
OCCUPANCY SENSOROS
SPRINKLER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
JAMES GOODEN
BLDG 1HEAPY
3850 PRIORITY WAY S. DR. STE 204
INDIANAPOLIS, IN 46240
ALICIA WARREN
317.571.8795
C U s e rs
\l s p lic h a l\ D o c u m e n ts
\1 .1
.0
A v ls p lic h a l.
rv t
/3 /2
:3
:1
P M
AE001
ARCHITECTURAL SYMBOLS AND
ABBREVIATIONS
Upgrade Lobby Restroom
2121 Lake Ave Fort Wayne, IN 46805
610A4-21-205BID DOCUMENTS
FULLY SPRINKLERED
JF LS03/05/2021Revisions: Date:
A. ALL WALLS WILL BE WALL TYPE S3A.G UNLESS OTHERWISE NOTED.
B. ALL WALL TYPE INDICATORS REFER TO THIS SHEET UNLESS OTHERWISE
NOTED.
C. REFER TO DIMENSION PLANS FOR PARTITION TYPE LOCATIONS.
PARTITIONS ARE DISTINGUISHED ON PLANS BY SYMBOL DESIGNATION
GRAPHIC DESIGNATION, OR A COMBINATION OF BOTH. NOT ALL
PARTITIONS ON THIS SHEET MAY BE USED. REFER TO PARTITION TYPE
SCHEDULE ON THIS SHEET FOR PARTITIONS USED ON THIS PROJECT.
D. ALL DIMENSIONS ARE FROM FACE OF STUD TO FACE OF STUD. REFER TO
PARTITION TYPES FOR PARTITION WIDTH DIMENSIONS.
E. ALL WALL STUDS TO BE 16" O.C. UNLESS OTHERWISE NOTED.
F. REFER TO SPECIFICATIONS AND TO TABLE ON THIS SHEET FOR MINIMUM
STUD GAUGE, MAXIMUM SPACING AND ALLOWABLE LIMITING HEIGHT
DEFLECTION CRITERIA FOR GYPSUM BOARD ASSEMBLIES AND REQUIRED
FINISHES. FOR WALLS WHERE STUDS ARE ATTACHED TO STRUCTURE
ABOVE, PROVIDE CROSS BRACING AS NECESSARY MEETING THE CRITERIA
INDICATED TO ACCOMMODATE THE SPECIFIED DEFLECTION CRITERIA OF
THE WALL.
G. ALL INTERIOR NON-BEARING STUDS TO BE DESIGNED FOR A DEFLECTION
EQUAL TO BUT NOT GREATER THAN L/240, UNLESS FULL HEIGHT FINISH IS
DETERMINED TO BE FRAGILE OR BRITTLE, THEN DEFLECTION TO BE L/360.
EXAMPLES OF FRAGILE FINISHES WOULD INCLUDE BUT NOT LIMITED TO
ANY TYPE OF WALL TILE, PLASTER OR PLASTER SKIM COAT.
H. ALTHOUGH WALL STUD SIZES ARE LISTED ON PLANS AND WALL TYPES IN
AREAS WHERE STUDS ARE TO STRUCTURE ABOVE OR HIGH AREAS,
CONTRACTOR TO VERIFY SIZED INDICATED IS ADEQUATE FOR HEIGHT
LISTED. PROVIDE ADEQUATE SIZE STEEL STUD FRAMING AND NOTIFY
ARCHITECT OF ANY DISCREPANCY PRIOR TO FABRICATION OR
INSTALLATION.
I. KING STUDS AT DOOR FRAMES TO BE 18 GA. UNLESS OTHERWISE NOTED.
J. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD FOR ALL OTHER WALL
CONSTRUCTION, UNLESS OTHERWISE NOTED.
K. PROVIDE 5/8" TYPE "X" GYPSUM WALLBOARD IN BULKHEAD CONSTRUCTION.
L. REFER TO LIFE SAFETY PLANS FOR LOCATIONS AND RATINGS OF SMOKE
AND FIRE RATED PARTITIONS. REFERENCE TEST NUMBERS APPLY ONLY TO
PARTITIONS INDICATED TO BE RATED.
M. FIRE RATING TEST NUMBERS ARE FOR UNDERWRITER'S LABORATORIES
(UL) ASSEMBLIES UNLESS OTHERWISE NOTED.
N. FIRE RESISTANT RATED PARTITIONS SHALL EXTEND TO THE INSIDE FACE
OF EXTERIOR SHEATHING, INCLUDING EXTENSIONS THROUGH SOFFITS.
O. SEAL ALL OPENINGS, GAPS, PENETRATIONS, AND JOINTS IN PARTITIONS
TYPES AS FOLLOWS:
a. FIRE RATED PARTITIONS: SEAL IN ACCORDANCE WITH THE
REQUIREMENTS SPECIFIED FOR THROUGH PENETRATION
FIRESTOP SYSTEMS AND FIRE RESISTIVE JOINT SYSTEMS.
b. SMOKE TIGHT PARTITIONS: SEAL COMPLETELY WITH
ELASTOMERIC SEALANT. FOR THE LOCATION AND EXTENT OF
PARTITIONS, DESIGNATED AS "SMOKE TIGHT", REFER TO THE LIFE
SAFETY DRAWINGS.
c. ALL OTHER LOCATIONS: SEAL AS INDICATED AND REQUIRED
ELSEWHERE BY THE CONTRACT DOCUMENTS.
P. INSULATION HEAD CONDITIONS AT FLOOR / ROOF DECK:
a. FIRE RESISTANT RATED PARTITIONS SHALL USE MINERAL WOOL
INSULATION AND APPROPRIATE FIRE RATED SEALANT.
b. NON-RATED PARTITIONS REQUIRING SOUND ATTENUATION SHALL
USE SOUND ATTENUATION BATTS (SAB).
Q. PROVIDE STENCILED IDENTIFICATION FOR RATED PARTITIONS.
R. STC RATING APPLIES WHERE PARTITION TAG QUALIFIER INDICATES WITH
AN "i". PROVIDE SOUND ATTENUATION BATTS OF THICKNESS INDICATED ON
SCHEDULE WHERE INDICATED BY QUALIFIER.
S. FOR PARTITIONS WITH STC RATINGS INDICATED SOUND ATTENUATION
BATTS TO EXTEND FULL HEIGHT OF PARTITION UNLESS OTHERWISE
NOTED. FLOOR TRACK TO BE SET IN A CONTINUOUS BED OF SEALANT.
T. WHERE PARTITION TYPE INDICATES SOUND ACOUSTICAL BAT, WITH FINISH
BOARD GOING TO DECK ON ONE SIDE ONLY, PROVIDE VAPOR BARRIER TO
SECURE INSULATION IN PLACE.
U. PROVIDE 5/8" MOISTURE/MOLD RESISTANT GYPSUM BOARD IN TOILET
ROOMS AND ON WALLS BEHIND PLUMBING FIXTURES, AND IN ALL WET
LOCATIONS.
V. PROVIDE 5/8" CEMENTITIOUS BACKER BOARD BEHIND CERAMIC WALL TILE.
COORDINATE LOCATIONS WITH FINISH WALL PLANS.
W. PROVIDE CORNER AND END WALL FRAMING AS DETAILED ON 3/AE002.
WALL TYPES LEGEND AND GENERAL NOTES
X#X.#
INDICATES STRUCTURAL MATERIAL
CH = SHAFT WALL
F = FURRING
S = STEEL
M = MASONRY
W = WOOD
INDICATES NOMINAL SIZE
INDICATES STRUCTURE AND
FINISH HEIGHTS
QUALIFIER'S (X-X-X)
G GYPSUM BOARD FINISH
1SB 1 HR RATED SMOKE BARRIER
2SB 2 HR RATED SMOKE BARRIER
1F 1 HR FIRE RATED
2F 2 HR FIRE RATED
i SOUND INSULATION t THERMAL INSULATION
B BULLET RESISTANT
L LEAD LINED
M MESH (STEEL SECURITY MESH)
MR MOIST/MOLD RESISTANT GYPSUM
SP SMOKE PARTITION
TB TILE BACKER CEMENT BOARD
A = STRUCTURE TO DECK, FINISH TO DECK
B = STRUCTURE TO DECK, FINISH ONE SIDE TO DECK
C = STRUCTURE TO DECK, FINISH TO ABOVE CEILING
D = STRUCTURE TO ABOVE CEILING, FINISH TO ABOVE CEILING
P = PARTIAL HEIGHT WALL
U = STRUCTURE TO UNDERSIDE OF CELING, FINISH TO UNDERSIDE OF CEILING
*SEE WALL TYPES FOR PROJECT SPECIFIC CONSTRUCTION
CH
2 1/2" 4" 6"
F 7/8
1 1/2" 2 1/2" 3 5/8"
4" 6" 8" 12"
S
2 1/2" 3 5/8"
4" 6" 8" 12"
M
2 5/8" 3 5/8" 5 5/8" 7 5/8" 11 5/8"
W
3/4"
3 1/2"
5 1/2" 7 1/4" 11 1/4"
" 1 HR FIRE/SMOKE
10'-0" MAX 10'-0" MAX
A. LETTERED STENCILS SHALL BE APPLIED TO EACH SIDE OF RATED PARTITIONS
AT 10'-0" INTERVALS; BUT NO LESS THAN ONCE PER PARTITION LENGTH.
B. USE THE FOLLOWING LANGUAGE FOR STENCILS:
"1 HR FIRE/SMOKE" "1 HR FIRE"
"2 HR FIRE/SMOKE" "2 HR FIRE"
"LIMIT TRANSFER OF SMOKE"
PERMANENT RED PAINT
LETTERING, TYP.
CEILING LINE
STENCILING NOTES
WALL TAG LEGEND
S2A.G 2 1/2"
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
3 3/4" NA NA NA
COMMENTS
S3A.G 3 5/8" 4 7/8"
NA
NANANANA
S6A.G 6" 7 1/4" NANANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
5/8"
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
5/8" TYPE X GYP BD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
DEEP LEG SLIP TRACK AT DECK
HOLD GYPSUM BACK FROM DECK FOR
DEFLECTION
INSULATION PRESENT WITH QUALIFER (i OR t)
WALL TYPES
S3A.GTB 3 5/8" 4 7/8" NANANANA
S3A.GiTB 3 5/8" 4 7/8" NANANANA
5/8" TILE BACKER CEMENT BOARD WITH QUALIFIER (TB)
WALL TAG
STRUCTURAL
SIZE
FINISH DIM FIRE RATING UL DESIGN
MIN STC
RATING
COMMENTS
3 5/8" 4 7/8" NANANANA
F6D.TB 6" 7 1/4" NANANANA
LINE OF STRUCTURE ABOVE
LINE OF CEILING
LINE OF STRUCTURE BELOW
PLAN
STRUCTURAL SIZE
5/8"
FINISH DIMENSION
STEEL STUD BRACING @ 4'-0" O.C.
CEILING
5/8" TILE BACKER BOARD
BEAD OF CONT. SEALANT
STEEL STUDS @ 16" O.C.
INSULATION PRESENT WITH QUALIFER (i OR t)
F3D.TB
3 5/8" 4 7/8" NA34NANA
F6D.iTB 6" 7 1/4" NA37NANA
F3D.iTB
NOTE:
COORDINATE HEIGHT OF TILE BACKER
BOARD WITH HEIGHT OF TILE.
RE: ELEVATIONS
TILE, RE: ELEVATIONS
5/8" TYPE X GYP BD (ABOVE TILE BACKER BOARD)
NOTE:
• TYPICAL LIMITING HEIGHTS-INTERIOR PARTITIONS, L/240 (5 PSF), WITH 5/8"GYPSUM BOARD EACH SIDE.
• PROVIDE DIAGONAL STUD BRACING AT ALL NON FULL HEIGHT INTERIOR PARTITIONS STAGGERED AT 48" O.C. TO DECK ABOVE. PROVIDE
STUD ATTACHMENT TO DECK W/ MIN. SPAN OF 2 DECK FLUTES. BRACING TO BE THE SAME SIZE AND GAUGE AS VERTICAL STUDS.
25 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 6'-11"1-5/8"
24" L/240 6'-0"162S125-18
16" L/240 9'-6"2-1/2"
24" L/240 8'-4"250S125-18
16" L/240 12'-5"3-5/8"
24" L/240 10'-10"362S125-18
16" L/240 13'-9"4"
24" L/240 12'-0"400S125-18
22 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 8'-1"1-5/8"
24" L/240 7'-1"162S125-27
16" L/240 11'-2"2-1/2"
24" L/240 9'-9"250S125-27
16" L/240 14'-6"3-5/8"
24" L/240 12'-8"362S125-27
16" L/240 16'-1"4"
24" L/240 14'-0"400S125-27
20 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 8'-4"1-5/8"
24" L/240 7'-3"162S125-30
16" L/240 11'-7"2-1/2"
24" L/240 10'-1"250S125-30
16" L/240 15'-0"3-5/8"
24" L/240 13'-1"362S125-30
16" L/240 16'-8"4"
24" L/240 14'-7"400S125-30
16" L/240 22'-4"6"
24" L/240 19'-6"600S125-27
16" L/240 23'-1"6"
24" L/240 20'-2"600S125-30
18 GA. STUDS (NON-COMPOSITE)
STUD WIDTH STUD SPACING ALLOW. DEFLECTION HEIGHT
16" L/240 13'-0"2-1/2"
24" L/240 11'-5"250S125-43
16" L/240 17'-5"3-5/8"
24" L/240 15'-3"362S125-43
16" L/240 18'-10"4"
24" L/240 16'-5"400S125-43
16" L/240 26'-1"6"
24" L/240 22'-10"600S125-43
SSMA NON-COMPOSITE STUDS
HIGH PRIORITY PARTITION
LOWER PRIORITY PARTITION
HIGH PRIORITY CEILING /
ROOF ASSEMBLY
LOWER PRIORITY PARTITION
RATING
3 HOUR ASSEMBLY
2 HOUR ASSEMBLY
1 HOUR ASSEMBLY
SMOKE-RATED ASSEMBLY
NON-RATED ASSEMBLY
PRIORITY
NOTE: LOWER NUMBER, HIGHER PRIORITY
TOP OF METAL DECK OR CONCRETE
FIRE CAULKING AS REQUIRED BY UL# HWS0001
(BY FRAMING CONTRACTOR)
PACK FLUTES OF DECK WITH FIRE SAFING AS
REQUIRED PER UL# HWS0001
Z-CLIPS 2" WIDTH
BOTTOM OF METAL DECK
LIGHT GAUGE FRAMING DEFLECTION TRAK,
CONFORMING TO UL# HW-D-0060
5/8" TYPE X GYP. BD. EACH SIDE OF STUD
SCRIBED TO DECK UL# U465
METAL STUD
PARALLEL NOTE:
NON-RATED CONSTRUCTION SIMILAR W/O
FIRE SAFING & SCRIBING BYP. BD. TO DECK
6"
TOP OF METAL DECK OR CONCRETE
FIRE CAULKING AS REQUIRED BY UL# HWS0001
(BY FRAMING CONTRACTOR)
PACK FLUTES OF DECK WITH FIRE SAFING AS
REQUIRED PER UL# HWS0001
Z-CLIPS 2" WIDTH
BOTTOM OF METAL DECK
LIGHT GAUGE FRAMING DEFLECTION TRAK,
CONFORMING TO UL# HW-D-0060
5/8" TYPE X GYP. BD. EACH SIDE OF STUD
SCRIBED TO DECK UL# U465
METAL STUD
PERPENDICULAR NOTE:
NON-RATED CONSTRUCTION SIMILAR W/O
FIRE SAFING & SCRIBING BYP. BD. TO DECK
INSULATION STUFFED INSIDE BOX
METAL STUD FRAMING
CORNER BEAD AT ALL
OUTSIDE CORNERS (TYPICAL)
20 GA. METAL STUDS WRAPPED WITH
20 GA. TRACK ON BOTH SIDES,
CONTINUOUS FROM FLOOR TO DECK
INSULATION STUFFED INSIDE BOX
METAL STUD FRAMING
CORNER BEAD AT ALL
OUTSIDE CORNERS (TYPICAL)
20 GA. METAL STUDS WRAPPED WITH
20 GA. TRACK ON BOTH SIDES,
CONTINUOUS FROM FLOOR TO DECK
6" M
IN
V A
R
IE
S
2 1/2" METAL STUD BRACING ON BOTH
SIDES AT 48" O.C. - MIN. 3 LOCATIONS.
ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM BOARD
4 7/8"
3-5/8" METAL STUD FRAMING AT 16" O.C.
ANCHOR TO STRUCTURE ABOVE
BOTTOM OF BULKHEAD
VARIES
BOTTOM OF CEILING
VARIES
REFER TO REFLECTED CEILING PLAN
VARIES
2 1/2" METAL STUD BRACING AT 32" O.C.
ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM BOARD
3-5/8" METAL STUD FRAMING AT 16" O.C.
ANCHOR TO STRUCTURE ABOVE
TYPICAL WALL CONSTRUCTION,
RE: FLOOR PLAN AND WALL TYPES
FOR ADDITIONAL INFORMATION
BOTTOM OF BULKHEAD
VARIES
BOTTOM OF CEILING
VARIES
6" M
IN
V A
R
IE
S
2 1/2" METAL STUD BRACING AT 32" O.C.
ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM BOARD
3-5/8" METAL STUD FRAMING AT 16" O.C.
ANCHOR TO STRUCTURE ABOVE
V A
R
IE
S 6"
M
IN
REFER TO REFLECTED CEILING PLAN
VARIES
BOTTOM OF BULKHEAD
VARIES
BOTTOM OF CEILING
VARIES
5/8" TYPE "X" GYPSUM BOARD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
JAMES GOODEN
BLDG 1HEAPY
3850 PRIORITY WAY S. DR. STE 204
INDIANAPOLIS, IN 46240
ALICIA WARREN
317.571.8795
C U s e rs
\l s p lic h a l\ D o c u m e n ts
\1 .1
.0
A v ls p lic h a l.
rv t
/3 /2
:3
:1
P M
AE002
WALL TYPES Upgrade Lobby Restroom
2121 Lake Ave Fort Wayne, IN 46805
610A4-21-205BID DOCUMENTS
FULLY SPRINKLERED
JF DMC03/05/2021
SCALE: 1 1/2" = 1'-0"AE002
1 RATED WALL PRIORITY
SCALE: 1 1/2" = 1'-0"AE002
2 DEFLECTION TRACK
WALL TYPE SCHEDULE
WALL TYPES USED IN THIS PROJECT
F3D.iTB
F3D.TB
S3.A1
S3A.G
S3A.GiTB
S3A.GTB
S6A.GiTB
SCALE: 3" = 1'-0"AE002
3 TYPICAL CORNER FRAMING DETAIL
SCALE: 1 1/2" = 1'-0"AE002
4 TYPICAL BULKHEAD DETAIL - SINGLE STUD
SCALE: 1 1/2" = 1'-0"AE002
5 TYPICAL BULKHEAD DETAIL
SCALE: 1 1/2" = 1'-0"AE002
6 TYPICAL BULKHEAD DETAIL
OS OS
N
F
AP
F
F
N
N
S F
8 8
4' - 10 1/4"
3' - 7" 1' - 7 3/4"
10 10
11 11
(1) (2)
(3) 4
6'
/4
MEN'S RESTROOM
WOMEN'S RESTROOM
8' - 2 1/2"
10' - 4 1/2"
1/
2"
3'
10112 (4)
(5)
1'
/2
3'
MEN'S RESTROOM
A165
WOMEN'S RESTROOM
A166
4 4
2 2
4 4
(6)
(7)
4' - 0"
/8
4' - 2 5/8"5' - 9 1/8"
6'
/8
3' - 5"
3' - 10"
15 15
3' - 0"
3' - 0"
8' - 0"C 8' - 0"C
8' - 0"B
8' - 0"B
8' - 0"C
8 8
/2
9' - 10 1/2" 10' - 0 1/2"
13' - 7 3/8"
8'
/8
9'
/8
7' - 6"
6' - 10 1/4"
8' - 1"B
8' - 2"B
MEN'S RESTROOM
WOMEN'S RESTROOM
8' - 7 1/2"
8'
/8 " 12
/8
6'
/8
10' - 9 1/2"
8' - 0"A 8' - 0"A
MEN'S
RESTROOM
A165
WOMEN'S
RESTROOM
A166
A. COORDINATE DEMOLITION WITH NEW CONSTRUCTION. ALL DEMOLITION AND
REPAIR NECESSARY TO COMPLETE NEW AND REMODEL CONSTRUCTION
SHALL BE PROVIDED. CONTRACTOR SHALL REMOVE EXISTING
IMPROVEMENTS WHETHER OR NOT SPECIFICALLY INDICATED ON THE
DRAWINGS TO FACILITATE THE COMPLETION OF ALL REQUIRED WORK.
CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL QUANTITIES AND
ITEMS REQUIRED TO BE REMOVED.
B. REFER TO ARCHITECTURAL SYMBOLS ON SHEET AE001 FOR DEMOLITION
SYSTEMS AND DRAWING NOMENCLATURE.
C. EXISTING STRUCTURE WITHIN THE PROJECT BOUNDARY SHALL REMAIN
UNLESS OTHERWISE NOTED.
D. SURFACES TO BE CUT AND CONDITIONS UNDER WHICH CUTTING IS TO BE
PREFORMED SHALL BE REVIEWED BY CONTRACTOR PRIOR TO CUTTING TO
VERIFY NO UNSAFE OR UNSATISFACTORY CONDITIONS EXIST. SUCH
CONDITIONS SHALL BE RECTIFIED BEFORE WORK MAY PROCEED.
E. EXTENTS OF DEMOLITION SHALL BE COORDINATED WITH THE
ARCHITECTURAL FLOOR PLANS AE101 AND ENGINEERING DRAWINGS FOR
ADDITIONAL INFORMATION.
F. DIMENSIONS SHOWN FOR EXISTING CONSTRUCTION TO BE DEMOLISHED
ARE APPROXIMATE AND ARE INTENDED TO GIVE A GENERAL SCOPE OF
WORK TO BE REMOVED OR TEMPORARILY REMOVED TO ACCOMMODATE
NEW CONSTRUCTION. COORDINATE DEMOLITION WORK WITH DESIGN
INTENT OF NEW CONSTRUCTION TO PROVIDE ADEQUATE AREA FOR THIS
WORK.
G. CONTRACTORS SHALL REMOVE INDICATED DEMOLITION OF CONSTRUCTION
ASSEMBLIES IN THEIR ENTIRETY, UNLESS OTHERWISE NOTED, TO
ACCOMMODATE NEW CONSTRUCTION.
H. MAKE ALL DEMOLITION CLEAN AND COMPLETE IN A MANNER TO RECEIVE
NEW FINISHES. DEMOLITION SHOULD BE PERFORMED IN A MANNER SUCH
THAT THE CONTRACTOR CAN SEAMLESSLY PATCH NEW WORK TO BE
SMOOTH AND UNDETECTABLE.
I. ABOVE CEILING WORK WHERE CEILINGS ARE TO REMAIN, CEILING TILES
SHALL BE REMOVED AND STORED IN A SAFE MANNER UNTIL CEILING TILES
CAN BE REINSTALLED. DAMAGED AND BROKEN CEILING TILES SHALL BE
REPLACED BY CONTRACTOR. GYPSUM BOARD CEILINGS SHALL BE PATCHED
AND PAINTED TO SEAMLESSLY MATCH EXISTING CEILING COLOR
FOLLOWING ABOVE CEILING DEMOLITION ACTIVITY. THIS SHALL INCLUDE
REPAIR TO THE CEILING GRID, SUSPENSION SYSTEM AND ALL ASSOCIATED
ASSEMBLIES AS WELL AS THE REPLACEMENT OF DAMAGED CEILING
PANELS, WITHIN AND BEYOND PROJECT LIMITS.
J. COORDINATE FULL SCOPE OF DEMOLITION WORK WITH ENGINEERING AND
VENDOR DRAWINGS.
K. WHERE EXISTING FLOOR FINISH IS REMOVED, FLOORING AND ADHESIVE
SHALL BE REMOVED TO PROVIDE A CLEAN FLOOR SLAB. FLOOR SLAB SHALL
BE FILLED/ LEVELED TO PROVIDE A LEVEL FINISH PER NEW FLOORING
MANUFACTURES RECOMMENDATIONS. REFER TO SPECIFICATION 09 05 16.
L. WALLS SHALL BE REMOVED THROUGHOUT PROJECT BOUNDARY UNLESS
OTHERWISE INDICATED.
M. FLOORING AND WALL BASE SHALL BE REMOVED THROUGHOUT PROJECT
BOUNDARY UNLESS OTHERWISE INDICATED.
N. REMOVE AND SALVAGE WALL MOUNTED ACCESSORIES AND MOUNTING
HARDWARE THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE
NOTED. CONTRACTOR TO REINSTALL. REFER TO SHEET AI201.
O. REMOVE ALL PLUMBING FIXTURES AND ASSOCIATED ACCESSORIES
THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE NOTED. REFER TO
PLUMBING PLAN FOR ADDITIONAL INFORMATION.
P. REMOVE DOOR LEAVES, FRAMES AND HARDWARE THROUGHOUT PROJECT
BOUNDARY UNLESS OTHERWISE NOTED.
Q. REMOVE EXISTING WALL PROTECTION, CORNER GUARDS, HANDRAILS AND/
OR GUARDRAILS THROUGHOUT PROJECT BOUNDARY UNLESS OTHERWISE
NOTED.
1. REMOVE CERAMIC TILE FLOORING, ASSUME THICK SET MORTAR BED.
2. REMOVE EXISTING CHASE WALL TO ACCOMMODATE NEW WORK -
COORDINATE WITH RENOVATION PLANS.
3. REMOVE EXISTING TOILET PARTITIONS AND DISPOSE.
4. REMOVE EXISTING PLUMBING FIXTURE - COORDINATE WITH MEP
DRAWINGS.
5. REMOVE DOOR, FRAME, AND HARDWARE IN ITS ENTIRETY - PREP WALL FOR
NEW DOOR, FRAME, AND HARDWARE.
6. REMOVE ACOUSTIC PANEL CEILING ASSEMBLY IN ITS ENTIRETY.
7. GYPSUM CEILING ASSEMBLY TO REMAIN AS EXISTING. PATCH AND FINISH
NEW GYPSUM TO ACCOMMODATE NEW WORK.
8. INFECTION CONTROL BARRIER AND/OR CONSTRUCTION ACCESS DOOR -
REFER TO SHEET GI101.
9. REMOVE DOOR, FRAME, AND HARDWARE IN ITS ENTIRETY - PREP WALL FOR
INFILL CONSTRUCTION.
10. REMOVE EXISTING WALL FINISH. EXISTING WALLS TO REMAIN. SAND AND
PREP TO RECEIVE SCHEDULED FINISH, REFER TO AI101.
11. REMOVE CARPET FLOORING AND WALL BASE.
12. REMOVE INDICATED PORTION OF WALL TO ACCOMMODATE NEW WORK.
13. EXISTING WINDOW WELL BULKHEAD TO REMAIN - PREP TO COMBINE.
14. EXISTING WINDOW SHADES TO REMAIN.
15. SAW-CUT AND REMOVE PORTION OF CONCRETE FLOOR SLAB FOR REMOVAL
AND INSTALLATION OF NEW PLUMBING. COORDINATE WITH PLUMBING
CONTRACTOR FOR EXACT LOCATION AND SIZE.
16. REMOVE AND REPLACE CEILING ACCESS PANELS.
17. REMOVE 12x12 VCT FLOORING AND RUBBER BASE.
DEMOLITION GENERAL NOTES
DEMOLITION PLAN NOTES
DEMOLITION LEGEND
WALL TO BE REMOVED DOOR TO BE REMOVED
IMAGE REFERENCE
NUMBER
DIRECTION OF VIEW
DEMOLITION IMAGES
TEMPORARY ICRA WALL TEMPORARY CONSTRUCTION
ACCESS DOOR
OFFICE
OFFICE
TOILET
OFFICE
HAC
OFFICE
OFFICE
TOILET
OFFICE
HAC
N
KEY PLAN
PROJECT LOCATION-
FIRST FLOOR
SHADE INDICATES
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
JAMES GOODEN
BLDG 1HEAPY
3850 PRIORITY WAY S. DR. STE 204
INDIANAPOLIS, IN 46240
ALICIA WARREN
317.571.8795
C U s e rs
\l s p lic h a l\ D o c u m e n ts
\1 .1
.0
A v ls p lic h a l.
rv t
/3 /2
:3
:0
P M
AD101
FIRST FLOOR DEMOLITION PLANS Upgrade Lobby Restroom
2121 Lake Ave Fort Wayne, IN 46805
610A4-21-205BID DOCUMENTS
FULLY SPRINKLERED
JF LS03/05/2021
SCALE: 1/4" = 1'-0"AD101
1 E_01 - 141 - 145 RESTROOM DEMO PLAN
SCALE: 1/4" = 1'-0"AD101
5 E_01 - 177 & 178 RESTROOM DEMO PLAN
SCALE: 1/4" = 1'-0"AD101
3 E_01 - A165 & A166 DEMO ENLARGED PLAN
SCALE: 1/4" = 1'-0"AD101
2 RCP_01 - 141 - 145 RESTROOM RCP DEMO
SCALE: 1/4" = 1'-0"AD101
6 RCP_01 - 177 & 178 RESTROOM RCP DEMO
SCALE: 1/4" = 1'-0"AD101
4 RCP_01 - A165 & A166 RESTROOM RCP DEMO
N
N
NN
N
N
PHASE 1
PHASE 2
PHASE 3
HARDWARE, FINISHES, PLUMBING FIXTURES, ELECTRICAL
FIXTURES, AND INSTALLATION OF NEW PARITIONS, DOORS,
DOOR FRAMES, DOOR HARDWARE, FINISHES, PLUMBING
A141, A142, A143, A144, & 145. TIME FRAME FOR THIS PHASE
IS APPROXIMATELY 135 DAYS.
DOORS, FRAMES, HARDWARE, PLUMBING FIXTURES, NURSE
CALL, ELECTRICAL FIXTURES, AND INSTALLATION OF NEW
CHASE PLUMBING FIXTURES, NURSE CALL, AND ELECTRICAL
FIXTURES IN ROOMS A165 & A166. TIME FRAME FOR THIS
PHASE IS APPROXIMATELY 115 DAYS.
REMOVE EXISTING FLOORING, CHASE WALL, TOILET
PARTITIONS, DOORS, FRAMES, HARDWARE, PLUMBING
FIXTURES, NURSE CALL,…