This document outlines a federal contract opportunity for constructing a generator docking station. The solicitation is identified as number 36C25021B0009 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. It is a Service Disabled Veteran Owned Small Business set-aside for a project to construct a generator docking station at the Chalmers P Wylie VAACC in Columbus, Ohio. The project magnitude is estimated between $250,000 and $500,000, it has a NAICS code of 238210 with a business size standard of $16.5 million, and the self-performance requirements for SDVOSBs adhere to applicable Federal Acquisition Regulation provisions. Bidders must be registered in the System for Award Management and Vendor Information Pages databases and ensure their registrations are accurate and not expired by the bid opening date. The performance period for the project is not to exceed 150 calendar days from receipt of the notice to proceed.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTINUATION PAGES
CONSTRUCT GENERATOR DOCKING STATION FOR THE CHALMERS P. WYLIE
VETERANS AFFAIRS AMBULATORY CARE CENTER (VAACC)—COLUMBUS, OH
PROJECT NUMBER: 757-20-205
QUESTIONS AND RESPONSES TO INVITATION FOR BID (IFB) NUMBER
36C25021B0009
IFB AMENDMENT NUMBER 00002
1. QUESTION – What are the specifications on the government furnished generator?
Response: Please see below.
2. QUESTION – What is the anticipated delivery date for the new government furnished equipment (Generator)?
Response: Currently scheduled for the first week of July, verified with Ohio CAT on 3/30/21. However this date could change.
3. QUESTION – Can a portion of the fence be removed to allow excavation equipment and material removal and placement?
Response: The fence may be removed to allow equipment and materials to be moved into the area, however the area must remain secured throughout construction and at the completion of each workday. At the completion of the project, the fence must be back in its existing condition.
4. QUESTION - Where can we place a concrete wash-out container?
Response: The contractor is responsible for proposing the location of the concrete washout container. VA will provide approval or denial of the proposed location.
5. QUESTION – Can you provide an approved location for the crane to set-up. Is the parking area rated for the load?
Response: The only known utility in the parking lot area are storm sewer. It is the contractors responsibility to develop the crane lift plan. Any crane lift that disrupts facility operation must be done off hours. The As-Builts for the existing facility can be provided to the contractor as needed.
6. QUESTION – The generator is owner furnished. Can a copy of the final approved generator shop drawings furnished by Ohio Cat be provided?
Response: Please see below.
7. QUESTION - The generator will be delivered broken down. What is the weight of the heaviest section?
Response: Please see below.
8. QUESTION - Can a list of the sections of the generator being delivered to the site be provided?
Response: Please see below.
9. QUESTION - Can a footprint of the assembled generator be provided?
Response: Please see below.
10. QUESTION - What are the dimensions of the assembled generator being furnished?
Response: Please see below.
11. QUESTION - How many gallons of fuel does the government furnished generator hold?
Response: Please see below.
12. QUESTION - Is the contractor to turn the project over with the tank full?
Response: Yes the project closeout should include the generator having a full tank of fuel after the conclusion of the generator start up and testing.
13. QUESTION - Can the VA provide further manufacturer details on the generator? Weights, Anchor points requirements?
Response: Please see below.
14. QUESTION - During the site visit, it was observed that the site is surrounded by fencing, with a single narrow gate. The gate is not wide enough for delivery of aggregate, concrete, and the new generator. How should the contractor access the site? If fencing is to be removed, can it be left out, or does it need to be secured at the end of each workday?
Response: Please see the answer to question # 3, above.
15. QUESTION - Is there a designated location for staging of materials?
Response: No there is not a specific designated area for staging. We would recommend that the contractor have their own trailer to store their materials for job. We would then designate a place where they can park the trailer.
16. QUESTION - During the site visit, it was observed there is a small electrical pull box with green lid approximately 10’ from the security fence. This pull box is not indicated on the plans.
Is the pull box to remain, or does it also need relocated?
Response: This electrical box is labeled as note #3 on ED-101. This pull box is to remain.
Ohio CAT
Power Systems Division 5232 Walcutt Court Columbus, Ohio 43228 888-443-4658 614-851-3501 fax
To: Chris Campbell
From: Jason Smith – Ohio CAT
RE: VA Columbus Returned Submittal Comments
1. Per VA specifications, batteries shall be capable of (5) attempts of 10s per attempt on 10sintervals for a total of 50s of cranking without damage. Provide oversized battery option and confirm they meet this required specification.
We will provide the oversized batteries
2. Provide externally-mounted, emergency stop button as required per VA master specifications and NFPA 110.
Externally mounted E stops have been added to both sides of the enclosure.
3. Provide copper-wound transformer in lieu of aluminum.
We have provided a copper-wound transformer per the change order.
4. Emergency lighting shall be outdoor rated, heavy-duty cast aluminum housing in lieu of thermoplastic as submitted. Provide additional emergency battery pack with lighting above each set of double doors on the exterior of the enclosure as indicated in generator purchase requirements.
We were asked to remove this from the list.
5. Provide silver-plated, copper bus-bars on panelboards.
The bus-bars on the panelboards will be silver-plated.
6. Startup testing to include 25%, 50%, 75% and 100% step load testing in addition to 4-hr loadbank test.
We will provide the requested step load testing during startup and commissioning.
7. EMT fittings shall be compression type. Fitting type is not indicated in electrical package details on page 5.
We will provide compression type EMT fittings.
Power Systems Division 5232 Walcutt Court Columbus, Ohio 43228 888-443-4658 614-851-3501 fax
8. 480V Panelboard and 480:208/120V transformer shall be fed from separate feeders. Therefore, connection between panelboard and transformer is not required to be pre-wired. Provide an additional stub-up location at transformer and a non-fused primary disconnect switch pre-wiredto the primary of the transformer. Contractor shall terminate feeder to disconnect input. 60Abreaker in 480V panelboard may remain as spare.
We have split the transformer from the load center, added an additional stub up area, and added a disconnect.
9. 208/120V panel shall be filled out with spare 20A-1P circuit breakers for use by owner. 18 circuit minimum.
We will provide the requested spare breakers.
Sincerely, Jason Smith
Jason Smith Project Manager
SUBMITTAL COVER PAGE
Power Systems Division
5232 Walcutt Court Columbus, Ohio 43228 888-443-4658 tel
PREPAIRED FOR: DEPARTMENT OF VETERAN AFFAIRS
PERCY JOHNSON
(614)-257-5534
PERCY.JOHNSON2@VA.GOV
PROJECT: DEPARTMENT OF VETERAN AFFAIRS- 2000 KW 3516
PROPOSED BY: OHIO CAT
5232 WALCUTT CT.
COLUMBUS, OHIO 43228
JOSH LINGNELL
ENGINE SALES REPRESENTATIVE
(614)-506-9606
JLINGNELL@OHIOCAT.COM
JASON SMITH
LEAD PROJECT MANAGER
(614)-851-3549
JSMITH@OHIOCAT.COM
mailto:JLINGNELL@OHIOCAT.COM mailto:JSMITH@OHIOCAT.COM
BILL OF MATERIAL
Power Systems Division
5232 Walcutt Court Columbus, Ohio 43228
PROJECT DEPARTMENT OF VETERAN AFFAIRS – 2000KW 13200V 3516
QUOTE # 3516 - # 30691581jtlrev6
QTY DESCRIPTION
60 Hz, 2000 EKW W/FAN
STANDBY POWER
EPA STATIONARY EMERGENCY
IBC SEISMIC CERTIFICATION
60HZ 13200 VOLT
3516CHD 60HZ HV PKG 2000 kW
EMCP 4.3 CONTROL PANEL
ENGLISH PANEL LANGUAGE
ENGLISH INSTRUCTION LANGUAGE
PLAT PLUS 3YR 1500HR STANDBY
CONTROL PANEL MOUNTING
ENGINE INTERFACE HARNESS EUI
GENERATOR TERMINAL BOX
RH CP/AUX MTG WITH RH EXT BOX
1ST LOCAL ANN NFPA
NEUTRAL GROUND CONNECTION
GROUND GROUP
CT 3000:5 RATIO
BUSS BAR CONNECTION
BOTTOM CABLE ENTRY
LUBE OIL DRAIN
SEISMIC VIBRATION ISOLATOR
RADIATOR
3516 RAIL GP 1602-164x FRAME
INTEGRATED VOLTAGE REGULATOR
SINGLE STAGE
PFF W/ FUEL WATER SEPARATOR
LUBE OIL
DUAL ELECT STARTING MOTOR
STARTER COVER(S)
OPEN CRANKCASE VENT SYSTEM
SPACE HEATER
SPACE HEATER CONTROL
BATTERY (X2) RACK AND CABLES
BATTERY CHARGER 20A NFPA
JACKET WATER HEATER W/ PUMP
WIRING GP-JW HEATER
Power Systems Division
5232 Walcutt Court Columbus, Ohio 43228
JWH CONTROL
PGS TEST REPORT @ 0.8 PF
ENGINE TEST CHARGE
ENCLOSURE WITH 4,000 GALLON SUB-BASE FUEL TANK
START UP DURING NORMAL BUSINESS HOURS
12 MONTHS STORAGE
----SEE ADDITIONAL PAGES BELOW FOR ENCLOSURE AND TANK INFO----
AS-BUILT DOCUMENT HOLDER MOUNTED ON ENCLOSURE WALL WITH THE
FOLLOWING:
GENERAL LAYOUT WITH ENGINE OUTLINE
PROPOSAL AND AS BUILT DRAWINGS
ELECTRICAL SCHEMATICS OF HARDIN MOUNTED COMPONENTS
RIGGING DIAGRAMS
INSTALLATION DRAWINGS WITH INSTRUCTIONS FOR SHIP LOOSE COMPONENTS.
ENCLOSURE PACKAGE FEATURES:
25 DB(A) REDUCTION @ 3FT. (FREE FIELD) 5FT. ABOVE GRADE – BASED OFF MECHANICAL
NOISE 109.3 DB(A) AT 3.3 FT.
DESIGNED IN COMPLIANCE WITH IBC, NEC
120 MPH WIND LOADING
40 LBS/SQ.FT. ROOF LOADING
200 LBS./SQ.FT. FLOOR LOAD
ENCLOSURE PACKAGE:
APPROXIMATE DIMENSIONS 384” L X 144” W X 132”H, 572” OVERALL LENGTH WITH TURN
HOODS
.10 GAUGE FORMED ALUMINUM BOLT TOGETHER CONSTRUCTION
ONE-PIECE SEAM WELDED ROOF, PEAKED TO PROMOTE WATER RUNOFF
WALLS TO BE 6” FORMED BOLT-TOGETHER PANELS
INTERIOR WALLS AND CEILING LINED WITH SOUND INSULATION COVERED WITH 22-
GAUGE GALVANIZED PERFORATED LINER. Interior liner will not be painted
ANGLE IRON MOUNTING FRAME
WEATHER SKIRTING AROUND EXTERIOR AT BASE AND ENCLOSURE SEAM
ENCLOSURE EXTERIOR TO BE COATED WITH A TWO-PART URETHANE PRIMER WITH TWO-
PART POLYURETHANE TOP COAT.
o CUSTOMER TO PROVIDE PAINT COLOR. HARDIN WILL MAIL YOU A HARD COPY OF
Power Systems Division
5232 Walcutt Court Columbus, Ohio 43228
OUR STANDARD COLORS AFTER A PO IS ISSUED. ADDITIONAL COSTS MAY APPLY IF
COLOR CHOSEN IS NOT ON THE STANDARD COLOR CHART
DOORS & ACCESSORIES:
TWO (2) SINGLE PERSONNEL DOORS, ONE EACH SIDE
TWO (2) SETS OF DOUBLE PERSONNEL DOORS, ONE SET IN FRONT OF GENSET CIRCUIT
BREAKER
ALL EXTERIOR DOORS SHALL BE EQUIPPED AS FOLLOWS:
o FORMED ALUMINUM CONSTRUCTION INSULATED TO MATCH ENCLOSURE o FULLY GASKETED PERIMETER o COOLER/FREEZER STYLE LATCHING MECHANISM, CHROME PLATED W/ STRIKER &
HANDLE
o KEY LOCKING WITH ADDITIONAL PAD LOCK PROVISION o DRIP LEDGES ABOVE EACH DOOR o INTERIOR PANIC RELEASE BUTTON, ALLOWS EXIT FROM INSIDE WHEN LOCKED
EXTERNALLY
o STAINLESS STEEL EXTERIOR HINGES o STAINLESS STEEL EXTERIOR HARDWARE o DOOR HOLDBACKS – TEE TYPE
AIR HANDLING SYSTEM
AIR INTAKE:
o AIR INTAKE HOOD ON END OF ENCLOSURE o .10 GAUGE FORMED ALUMINUM BOLT TOGETHER CONSTRUCTION o WALLS TO BE FORMED BOLT-TOGETHER PANELS o INTERIOR WALLS / CEILING LINED WITH SOUND INSULATION COVERED WITH 22-
GAUGE GALVANIZED PERFORATED LINER. INTERIOR LINER WILL NOT BE PAINTED
o SOUND BAFFLES LOCATED IN THE HOOD o SOUND BAFFLES AT REAR OF ENCLOSURE o RODENT SCREENS o MOTORIZED LOUVERS LOCATED INSIDE ENCLOSURE
AIR DISCHARGE:
o AIR DISCHARGE PLENUM DIRECTING AIR UP VERTICAL o .10 GAUGE FORMED ALUMINUM BOLT TOGETHER CONSTRUCTION o WALLS TO BE FORMED BOLT-TOGETHER PANELS o INTERIOR WALLS / CEILING LINED WITH ROCKWOOL INSULATION COVERED WITH
22-GAUGE PERFORATED LINER. INTERIOR LINER WILL NOT BE PAINTED
o HINGED KEY LOCKING ACCESS DOOR o TOP MOUNTED SCREEN o GRAVITY LOUVERS IN FRONT OF RADIATOR
Power Systems Division
5232 Walcutt Court Columbus, Ohio 43228 o AIR RECIRCULATION BELTING BETWEEN RADIATOR & WALL OPENING o TOP MOUNTED BAFFLES. BAFFLES MAY SHIP LOOSE FOR INSTALLATION ON SITE
BY OTHERS
FUEL TANK BASE, 4,000 GALLON, DOUBLE WALL UL-142 EQUIPPED AS FOLLOWS:
APPROXIMATE DIMENSIONS 490”L X 144”W X 24”H
UL-142 LISTED FUEL TANK
4,000 GALLON, USABLE
110% RUPTURE BASIN CONTAINMENT
FUEL FILL WITH O.F.P.V. SET AT 95% WITH SPILL BOX CONTAINMENT WITH LOCKABLE CAP
HIGH FUEL ALARM BOX INCLUDING:
o NEMA 1 ENCLOSURE o LOCATED NEAR THE FUEL FILL o AUDIBLE HORN WITH TEST AND RESET BUTTON o ROOF MOUNTED BEACON – SHIPPED LOOSE o 95% HIGH FUEL SWITCH WIRED TO A LIGHT IN THE BOX, HORN AND THE ROOF
MOUNTED BEACON
NORMAL AND EMERGENCY VENTS, SIZED PER UL REQUIREMENTS
ALL VENTS SHALL BE EXTENDED TO 12’ ABOVE GRADE
ENGINE SUPPLY & RETURN DROP TUBES, TO ½” OFF TANK BOTTOM, REMOVABLE
FLEXIBLE FUEL LINES FOR ENGINE PICK UP AND RETURN LINES TO TANK
LOW FUEL LEVEL ALARMS
HIGH FUEL LEVEL ALARMS
RUPTURE BASIN ALARM
2 SPARE FITTINGS
REMOTE FUEL INLET AND RETURN LINES PIPED TO EXTERIOR FOR CONNECTION TO
REMOTE FUEL SUPPLY ON SITE
o 2” FLANGED CONNECTIONS AT ENCLOSURE WALL
FUEL OVERFLOW LINE PIPED TO EXTERIOR FOR CUSTOMER CONNECTION
24VDC NC SOLENOID VALVE INSTALLED ON FUEL INLET OF REMOTE FUEL SUPPLY WITH
BYPASS VALVES
MECHANICAL FUEL GAUGE
MOUNTING PROVISIONS FOR GENSET
CUSTOMER MOUNTING HOLES IN LOWER FLANGE
CONDUIT STUB UPS FOR LOAD CABLE AND AC DISTRIBUTION PANEL
SHIPPING GLANDS PLATES ON STUB-UP HOLES
LIFTING PROVISIONS FOR COMPLETED PACKAGE WEIGHT
TWO GROUND PADS PROVIDED ON BASE AT DIAGONALLY OPPOSING CORNERS.
BASE TO BE COATED WITH A TWO-PART URETHANE PRIMER WITH TWO-PART
POLYURETHANE TOP COAT
o CUSTOMER TO PROVIDE PAINT COLOR. HARDIN WILL MAIL YOU A HARD COPY OF
OUR STANDARD COLORS AFTER A PO IS ISSUED. ADDITIONAL COSTS MAY APPLY IF
Power Systems Division
5232 Walcutt Court Columbus, Ohio 43228
COLOR CHOSEN IS NOT ON THE STANDARD COLOR CHART
o PLEASE NOTE: IF BASE COLOR DIFFERS FROM THE ENCLOSURE COLOR, A $750.00
ADDER WILL BE APPLIED TO JOB.
EXHAUST SYSTEM (INTERNAL)
CARBON STEEL INTERIOR SILENCER BRACKETS
CRITICAL GRADE EXHAUST SILENCER
STAINLESS STEEL EXHAUST FLEX WITH MANOMETER TEST PORTS
EXHAUST BLANKETS ON SILENCER AND ALL INTERIOR PIPING
2-1/2” GAP BETWEEN ROOF AND SILENCER
OUTLET EXTENSION WITH RAIN CAP
EXHAUST THIMBLE FOR ENCLOSURE PENETRATION
ROOF MOUNTED EQUIPMENT MAY SHIP LOOSE FOR INSTALLATION ON SITE BY OTHERS
ELECTRICAL PACKAGE – INCLUDING:
30KVA 480V – 208V STEP DOWN TRANSFORMER WITH DISCONNECT FOR INCOMING POWER
480V/277 AC DISTRIBUTION PANELBOARD: 100 AMP MAIN AND BRANCH BREAKERS FOR ALL
AC INTERIOR ITEMS.
o 3PH, 4 WIRE o 65KAIC RATING o FEED JWH, STEP DOWN TRANSFORMER, HVAC
AC DISTRIBUTION PANEL: 100 AMP MAIN AND BRANCH BREAKERS FOR ALL AC INTERIOR
ITEMS.
o 10KAIC o ALL BREAKERS TO BE BOLT ON STYLE o 120/208V, THREE PHASE, 4 WIRE
ALL HARDIN SUPPLIED WIRING TO BE IN EMT THIN WALL CONDUIT AND FITTINGS
o NOTE: MINIMUM ¾” EMT CONDUIT
(6) AC INTERIOR MOUNTED LED VAPOR TIGHT LIGHTS
(4) 3-WAY SWITCHES – AT EACH DOOR
(4) GFCI RECEPTACLES
(2) DUAL HEAD EMERGENCY EXIT LIGHTS WITH BATTERY BACKUP
(2) 5KW 480V SPACE HEATER WITH BUILT IN THERMOSTAT AND ENGINE CUT OUT RELAY
WIRE GENERATOR STRIP HEATER TO AC DISTRIBUTION PANEL
WIRE JACKET WATER HEATER TO AC DISTRIBUTION PANEL
MOUNT BATTERY CHARGER AND WIRE AC AND DC SIDES
INSTALL BATTERIES, RACK, AND CABLES
GROUND GENERATOR TO BASE
Power Systems Division
5232 Walcutt Court Columbus, Ohio 43228
ENGINE KIT – INCLUDING:
INSTALL GENSET ON BASE UTILIZING CUSTOMER SUPPLIED SPRING TYPE VIBRATIONS
ISOLATORS
o HARDIN TO PROVIDE SHIPPING BLOCKS FOR TRANSPORTATION WITH REMOVABLE
SHIMS & BOLTS
o SHIMS AND BOLTS TO BE REMOVED AT SITE PRIOR TO ISOLATOR ADJUSTMENT
EXTEND OIL AND WATER DRAINS TO EXTERIOR OF ENCLOSURE. SHUT OFF VALVES
INSTALLED ON INTERIOR
EXTEND FUMES DISPOSAL TO OUTSIDE ENCLOSURE OR INTO THE DISCHARGE PLENUM
FIELD INSTALLATION SEALANT & COLOR KIT INCLUDING:
QTY 1 - TUBE OF SEALANT FOR EXHAUST OUTLET ROOF SKIRT
QTY 2 – TUBES OF CLEAR SILICONE SEALANT FOR MISCELLANEOUS ROOF PENETRATIONS
1 GAL. EXTERIOR FINISH & 1 QUART ACTIVATOR
ALL COMPONENTS BOX PACKAGED, LABELED, AND SHIPPED LOOSE INSIDE ENCLOSURE
GALVANIZED PLATFORM, STAIRS, AND RAILING – OSHA COMPLIANT:
APPROXIMATELY 240”L X 42”W X 24”H
GRIP TRAC PLATFORM AND STEPS
4-INCH TOE BOARDS
RAILING SYSTEM
CORROSION RESISTANT URETHANE PAINTING DIAMOND VOGEL LINE – CUSTOMER TO
PROVIDE PAINT COLOR
ASSEMBLY TO SHIP LOOSE FOR INSTALLATION ON SITE BY OTHERS
EXCEPTIONS AND CLARIFICATIONS:
1. OHIO CAT IS QUOTING AN ALUMINUM ENCLOSURE, HOWEVER, THE PANELS ARE NOT PRE-PAINTED. THEY’RE PAINTED AFTER
THE ENCLOSURE IS ASSEMBLED.
2. INSTALLATION AND ENGINEERING DRAWINGS BY OTHERS
3. OHIO CAT HAS NOT INCLUDED RUSSELECTRIC TECHNICIANS IN THIS PROPOSAL.
4. OHIO CAT HAS NOT INCLUDED A NEUTRAL GROUNDING RESISTOR.
5. THE PRICING ABOVE NOW INCLUDES 12 MONTHS STORAGE OF THE GENSET.
QUOTATION ALSO INCLUDES:
DELIVERY TO JOB SITE (UNLOADING/ANCHORING BY OTHERS)- FOB SHIPPING POINT
START-UP SERVICE WITH 4 HOUR LOAD BANK TEST
NOTE:
THREE WEEK NOTICE REQUIRED FOR START-UP SCHEDULING.
START UP TO TAKE PLACE DURING NORMAL BUSINESS HOURS MON - FRI.
COORDINATION STUDY IS NOT INCLUDED IN QUOTE.
TERMS: DUE UPON RECEIPT
FOB: JOBSITE
Table of Contents
GENERATOR SPEC_______________________________________________________________TAB 1
Generator Spec Sheet Engine Controller Engine Performance Data Systems Data Sound Data
GENERATOR DRAWING_________________________________________________________ _TAB 2
Genset Layout Drawing Rigging Drawing Load Center Drawing
ENCLOSURE SPEC SHEETS_____________________________________________________ _TAB 3
Louvers Rain Cap Silencer
FUEL TANK SPEC SHEETS______________________________________________________ _TAB 4
Vents
TMS 2000
Overfill Prevention Valve Spill Bucket
ENCLOSURE ELECTRICAL SPEC SHEETS________________________________________ _TAB 5
Transformer Space Heater Lights Panelboard
ENCLOSRUE PAINT/WARRANTY_________________________________________________ _TAB 6
Paint Spec Sheets Enclosure Warranty Statement
GENERATOR DATA_____________________________________________________________ _TAB 7
Voltage Regulator Generator Data
GENERATOR ACCESSORIES ______________________________________________________TAB 8
Jacket Water Heater Battery Charger Batteries Starters
EMCP 4.3 Control Panel IO Module Remote Annunciator
ELECTRICAL DRAWINGS_______________________________________________________ _TAB 5
Electrical Drawings
INSTALLATION AND STARTUP___________________________________________________TAB 10
Foundations Contractors Pre Startup Checklist Startup Checklist Training Caterpillar Warranty Statement
2000 (2500) 2000 (2500) 1825 (2281) 1650 (2063) U.S. EPA Stationary Emergency Use Only (Tier 2)
Bore – mm (in) 170 (6.69)
Stroke – mm (in) 190 (7.48)
Displacement – L (in3) 69 (4210.64)
Compression Ratio 14.7:1
Aspiration TA
EUI
Governor Type ADEM™ A3
• Meets U.S. EPA Stationary Emergency Use Only (Tier 2) emission standards applications worldwide
• Accepts 100% block load in one step and meets
• Conforms to ISO 8528-5 G3 load acceptance characteristics of Cat diesel engines
• Cooling systems available to operate in ambient
• User-friendly interface and navigation
• Scalable system to meet a wide range of mission critical ratings
• Extended service protection is available to provide extended coverage options repair agreements excellence line of credit
JGoyer Rectangle
Air Cleaner Single element
Muffler
Starting Standard batteries
Standard electric starter(s)
Air starter(s)
Jacket water heater Block heater
Output voltage 380V 6300V 440V 6600V 480V 6900V 600V 12470V 2400V 13200V 4160V 13800V
Temperature Rise (over 40°C ambient)
Winding type
Excitation Internal excitation (IE) Permanent magnet (PM)
Attachments Anti-condensation heater monitoring and protection
Type
LSI
1600A 2000A 2500A 3000A 3200A 4000A 5000A
IEC UL
3-pole 4-pole
Electrically operated
Trip Unit
LSI-G
LSIG-P
Controller
EMCP 4.2B
EMCP 4.3
EMCP 4.4
Attachments
Remote monitoring software
Battery charger – 10A Battery charger – 20A Battery charger – 35A
Spring Seismic rated
Connectivity Ethernet
Satellite
Terms 2 year (prime) 3 year 5 year 10 year
Coverage Silver Gold
(ATS)
(UPS)
Paralleling switchgear Paralleling controls
UL 2200
CSA
IBC seismic certification OSHPD pre-approval
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle
JGoyer Rectangle jsmith
Standby Mission Critical Prime
Gen set power rating with fan 2000 ekW 2000 ekW 1825 ekW 1640 ekW Gen set power rating with fan @
0.8 power factor 2500 kVA 2500 kVA 2281 kVA 2050 kVA
Emissions EPA ESE (TIER 2) EPA ESE (TIER 2) EPA ESE (TIER 2) EPA ESE (TIER 2)
EM1896-01 EM1897-01 DM8264-05 DM8265-04
100% load with fan – L/hr (gal/hr) 522.5 (138.0) 522.5 (138.0) 480.9 (127.0) 441.9 (116.7)
75% load with fan – L/hr (gal/hr) 406.8 (107.5) 406.8 (107.5) 378.8 (100.1) 349.4 (92.3)
50% load with fan – L/hr (gal/hr) 293.6 (77.5) 293.6 (77.5) 269.9 (71.3) 246.2 (65.0)
25% load with fan – L/hr (gal/hr) 169.7 (44.8) 169.7 (44.8) 159.2 (42.1) 148.9 (39.3)
Radiator air flow restriction (system) – kPa (in. water) 0.12 (0.48) 0.12 (0.48) 0.12 (0.48) 0.12 (0.48)
Radiator air flow – m3/min (cfm) 2 (7 ) 2 ( )
Engine coolant capacity – L (gal) 233.2 (61.6) 233.2 (61.6)
Radiator coolant capacity – L (gal) ( ) ( )
Total coolant capacity – L (gal) 4 (1 ) 4 (1 )
3/min (cfm) 185.5 (6548.9) 185.5 (6548.9) 180.0 (6357.6) 174.3 (6155.8)
400.1 (752.1) 400.1 (752.1) 382.8 (721.1) 370.7 (699.3) 3/min (cfm) 433.1 (15292.8) 433.1 (15292.8) 408.1 (14410.4) 385.3 (13605.7)
6.7 (27.0) 6.7 (27.0) 6.7 (27.0) 6.7 (27.0)
759 (43150) 759 (43150) 715 (40666) 673 (38277)
1788 (101696) 1788 (101696) 1645 (93554) 1522 (86577)
672 (38240) 672 (38240) 612 (34784) 553 (31421) Heat rejection to atmosphere from engine – 133 (7564) 133 (7564) 127 (7230) 123 (6983)
96 (5464) 96 (5464) 86 (4895) 76 (4326)
NOx mg/Nm3 (g/hp-h) 2754.3 (5.46) 2754.3 (5.46) 2488.9 (5.05) 2202.3 (4.37)
CO mg/Nm3 (g/hp-h) 143.3 (0.30) 143.3 (0.30) 129.7 (0.27) 112.3 (0.24)
HC mg/Nm3 (g/hp-h) 44.7 (0.11) 44.7 (0.11) 55.6 (0.13) 67.4 (0.16)
PM mg/Nm3 (g/hp-h) 10.4 (0.03) 10.4 (0.03) 10.9 (0.03) 12.0 (0.03)
NOx mg/Nm3 (g/hp-h) 3305.2 (6.56) 3305.2 (6.56) 2986.6 (6.06) 2642.7 (5.24)
CO mg/Nm3 (g/hp-h) 258.0 (0.54) 258.0 (0.54) 233.4 (0.49) 202.1 (0.43)
HC mg/Nm3 (g/hp-h) 59.5 (0.14) 59.5 (0.14) 73.9 (0.18) 89.6 (0.22)
PM mg/Nm3 (g/hp-h) 14.6 (0.04) 14.6 (0.04) 15.3 (0.04) 16.8 (0.04)
2 (7 ) 2 ( )
233.2 (61.6) 233.2 (61.6)
4 (1 ) 4 (1 )
JGoyer
(2 ) 23 9 (9 ) 29 (11 ) of Average rating. Typical
Typical peak demand is 100% of prime rated ekW www.cat.com/electricpower ©20 Caterpillar
All rights reserved.
3516 PGFL
LEHE1376-0 ( )
A B
C
Note:
Applicable Codes and Standards AS 1359, CSA C22.2 No. 100-04, UL 142, UL 489, UL 869, UL 2200, NFPA 37, NFPA 70, NFPA 99, NFPA 110, IBC, IEC 60034-1, ISO 3046, ISO 8528, NEMA MG1-22, NEMA MG1-33, 2014/35/EU, 2006/42/EC, 2014/30/EU.
Note: Codes may not be available in all model
Data Center Applications
Fuel Rates
ADEM™ III
ENGINE CONTROLLER
FEATURES
RELIABLE, DURABLE
All ADEM III controllers are designed to survive the harshest environments.
● Environmentally sealed, die-cast aluminum housing isolates and protects electronic components from moisture and dirt contamination.
● Rigorous vibration testing ensures product reliability and durability.
● Accuracy maintained from –40° C to +85° C
● Electrical noise immunity to 100 volts/meter
● Internal circuits are designed to withstand shorts to +battery and –battery.
SIMPLE SERVICING
Each ADEM III system works in combination with the Caterpillar ET service tool software to keep the engine operating at peak performance.
● Displays measured parameters
● Retrieves active and logged event codes documenting abnormal system operation
● Performs calibrations and diagnostic tests
● Supports flash programming of new software into the ADEM III ECM
SELF DIAGNOSTICS
Each ADEM III ECM has a full compliment of self diagnostics. The ECM can detect faults in the electrical system and report those faults to the service technician for quick repair.
● Self-diagnostic capability pinpoints operational problems in need of attention.
ADVANCED FEATURES
● Isochronous or droop speed control
● Enhanced performance from fuel injection timing and limiting
● J1939 Communications
● Adjustable monitoring of vital engine parameters
● Idle/rated speed setting
● Programmable speed acceleration ramp rate
● Adjustable cooldown duration
● Data link interfaces
OPTIONAL FEATURES
● Integrated ether control system
● Remote monitoring and control
The ADEM III controller is the main Electronic Control Module (ECM) used on select diesel engines.
The ADEM III control is designed to control/ interface Electronic Unit Injector (EUI) equipped engines. The ADEM III controller is composed of the ADEM III ECM, control software, sensors, actuators, fuel injectors, and interface to the generator system.
The prime benefit of an ADEM III engine system is to better control and maintain the particulate emissions, both steady state and transient, while improving engine performance over the Mechanical Unit Injector (MUI) engines.
A D E M ™ I I I E N G I N E C O N T R O L L E R
W H E R E T H E W O R L D T U R N S F O R P O W E R
LEHE4747-00
The ECM is housed in an environmentally sealed casting. All wiring connections to the ECM are made at the two sealed seventy-pin connectors.
ENGINE SPEED GOVERNING
Desired engine speed is calculated by the ECM and held within +/–0.2 Hz for isochronous and droop mode. The ECM accounts for droop that is requested. The proper amount of fuel is sent to the injectors due to these calculations.
The ECM also employs cooldown/shutdown strategies, acceleration delays on startup, acceleration ramp times, speed reference and a low/high idle switch is also available via communications to the EMCP 3.
FUEL LIMITING
Warm and cold fuel-air ratio control limits are controlled by the ECM. Electronic monitoring system derates, torque limit, and cranking limit, programmable torque scaling, and cold cylinder cutout mode are standard features.
FUEL INJECTION TIMING
Master timing for injection is controlled by the ECM control. Temperature dependencies are accounted for in the fuel injection calculations.
ELECTRONIC MONITORING
Electronic monitoring of vital engine parameters can be programmed. Warning, derate, and shutdown event conditions may be customized by the user.
INFORMATION MANAGEMENT
The ECM stores information to assist with electronic troubleshooting. Active and logged diagnostic codes, active events, logged events, fuel consumption, engine hours, and instantaneous totals aid service technicians when diagnosing electronic faults and scheduling preventive maintenance.
CALIBRATIONS
Engine performance is optimized through injection timing. Auto/manual sensor calibrations are standard features.
ON-BOARD SYSTEM TESTS
System tests are available to assist in electronic troubleshooting. These tests include: injector activation, injector cutout, and override of control outputs.
CAT® J1939 DATA LINK INTERFACES
The ADEM III controller communicates with the EMCP 3 via the J1939 Communication network. Additionally, the ADEM III controller can communicate with other electronic modules over the Cat Data Link. These modules include:
Caterpillar Monitoring System, Electronic Modular Control Panels (EMCP II and EMCP II+), Programmable Relay Control Module (PRCM), electronic service tools, and Customer Communication Module (CCM).
ELECTRONIC SENSORS
The following sensing is available on the ADEM III controller: oil pressure, fuel pressure, fuel temperature, atmospheric pressure, air inlet temperature, turbo outlet pressure, engine coolant temperature, engine speed, throttle speed, droop position, exhaust temperature, engine control switch position, oil filter pressure differential, fuel filter pressure differential, air filter pressure differential, crankcase pressure, and remote e-stop switch position.
ELECTRONIC ACTUATORS
Electronic Unit Injectors are driven by the ECM.
Actuators to control ether are optional.
DESCRIPTION
A D E M ™ I I I E N G I N E C O N T R O L L E R
A D E M ™ I I I E N G I N E C O N T R O L L E R
SPECIFICATIONS
Humidity
0 to 90% relative humidity Impervious to:
salt spray, fuel, oil and oil additives, coolant, spray cleaners, chlorinated solvents, hydrogen sulfide and methane gas, and dust
Input and output protection all inputs and outputs are protected against short circuits to +battery and –battery
Input voltage range (24 VDC nominal) 18 to 32 VDC
Mounting engine mounted
Reverse polarity protected Shock, withstands 20 g Temperature range
Operating: –40° C to 85° C (–40° F to 185° F) Storage: –50° C to 120° C (–58° F to 248° F)
Vibration withstands 2.0 g @ 18 to 500 Hz
Hardin Industries LLC 400 Commercial St.
Lacon, IL 61540 Phone (309)246-8456 Fax (309)246-3117
Hardin Submittal For Ohio Cat
Job # 1756 Ref: Columbus VA
Quote # 13495C mailto:mail@hardin-inc.com
Lacon, IL 61540 Phone (309)246-8456 Fax (309)246-3117
ENCLOSURE SPEC SHEETS
MODEL NO. W38-1000
2-11/16” (68mm)
1-29/32” (48mm)
3-7/32” (82mm)
2-17/32” (64.3mm)
2-9/32” (57.9mm)
29/32” (22.9mm)
9/16” (14mm)
3-23/32” (94mm)
3-3/8” (85.7mm)
3-3/16” (81mm)
11-5/32” (283mm)
7-1/16” (179mm)
2-3/32” (53mm)
2-1/8” (54mm)
2-1/2” (63.5mm)
2-7/32” (57mm)
5-11/16” (145mm)
2” (51mm)
(4) CSK HOLES FOR 1/4”
FLAT HEAD SCREWS (6mm)
(4) CSK HOLES FOR 1/4”
FLAT HEAD SCREWS (6mm)
800-333-5151 www.pdiatlanta.com Fax: 404-350-0781
Item # H-5539, Hinge 8" Stainless Steel
Also Available in Aluminum or Stainless Steel
Strap 8 Ga. x 2" x 8"
Bracket 8 Ga. x 4 1/2" x 3" from center of pin
Pin 1/2" Dia. Steel
Finish Embossed steel - Stainless Steel
Mounting Holes on Strap C. to C. 2 7/16"
Weight 2 lb
Orr & Orr Inc.
7301 So Meade Ave.
Bedford Park, IL 60638 Phone: (708) 496-9800 Fax: (708) 496-9819 Email: sales@orrorr.com Website: www.orrorr.com
Speci�cations
3/1/2019 | Page 1 of 1 mailto:sales@orrorr.com http://truck-hardware.orrorr.com/plp/htm/ibot.htm
Conklin Metal Industries 236 Moore Street Atlanta, GA 30312
PHONE: 800-282-7386
FAX: 404-522-7439
www.conklinmetal.com
Atlanta, GA ● Greenville, SC ● Birmingham, AL ● Sanford, FL ● Mobile, AL ● Jackson, MS
● New Orleans, LA ● Memphis, TN ● Nashville, TN ● Norcross, GA
Serving the sheet metal industry in the Southeast since 1874
Material Specification Sheet Galvanneal Steel
Description Galvanneal is a carbon steel coated with zinc on both sides by a continuous hot‐dip process. Immediately as the strip exits the coating bath, the molten zinc coating is subjected to an in‐line heat treatment that converts the entire coating to a zinc‐iron alloy. (The iron diffuses from the steel into the coating). The galvannealed surface has a non‐spangled matte finish. One of the primary attributes of the galvannealed coating is that the surface accepts paint very readily. It can be painted without the application of a pretreatment, although a pretreatment will enhance the performance after painting. Other attributes are the zinc‐iron alloy coating can be welded more easily than galvanized and the coating is harder than a galvanized coating and is thus more resistant to scratching and manufacturing damage. During fabrication there is almost always some degree of powdering of the coating. For this reason, typical galvannealed coatings are thinner than most galvanized coatings. Additionally the coating is less reactive when exposed to the atmosphere, and as a result, the dissolution that occurs during corrosion occurs more slowly than for a galvanized coating. Galvannealed steel sheet can be readily post‐painted, and is not intended to be pre‐painted. The brittle nature of the coating makes forming after painting a difficult task to avoid degradation of the corrosion performance in subsequent service. Galvannealed sheet is specifically designed to be used in the painted condition. It can be joined by various methods including riveting, soldering, welding, spot welding and adhesives. For more info on Galvanneal visit http://www.galvinfo.com/ginotes/GalvInfoNote_1_3.pdf
ASTM Specifications ASTM Designation A924 outlines the general requirements for carbon steel sheet metal coated by the hot‐dipped process. A924 designates tolerances for thickness, width, camber, shape, etc.
ASTM Designation A653 outlines the general requirements for the hot‐dipped coated galvanized steel or zinc‐iron alloy‐coated galvannealed sheet. Included in this specification are steel chemistry requirements and typical mechanical properties of the various metallurgical grades. ASTM A653 also includes the coating weight requirements for the different coating designations.
Coating Thickness Coating thickness is measured as the coating weight in ounces per square foot. For example the coating designation G‐90 specifies there is a minimum coating weight of .90 ounces per square foot on both sides of the sheet. For more info on zinc coatings visit http://galvinfo.com/ginotes/GalvInfoNote_1_6.pdf
Surface Treatment The “chem‐treat dry” surface treatment consists of an application of a thin, invisible, corrosion inhibiting, inorganic, chemical film on the zinc surface. This film is applied at the galvanizing line by dipping into an aqueous solution of corrosion inhibiting chemicals. The chemically treated surface is much more resistant to “white rust” ‐ the corrosion of zinc that typically occurs in humid conditions during storage or transportation.
Source: US Steel
California Georgia Indiana Missouri Pennsylvania
800.821.3520 800.821.1664 800.220.8118 800.821.3520 800.634.4293
Texas 800.527.5640
Wisconsin 800.220.8118
H
IN
G
ES
www.austinhardware.com
Product Number Gauge Open Width Pin Dia. Knuckle Length Overall Length
A804 HINGE 16 2 3/16 1/2 72
A813 HINGE 16 2 1/2 1/8 1/2 72
A815 HINGE 16 2 1/2 3/16 1/2 72
A814 HINGE 16 3 1/8 1/2 72
A816 HINGE 16 3 3/16 1/2 72
A821 HINGE 16 4 1/8 1/2 72
A825 HINGE 14 2 3/16 1 72
A805 HINGE 14 2 1/4 1 72
A837 HINGE 14 2 1/2 3/16 1 72
A820 HINGE 14 2 1/2 1/4 1 72
A826 HINGE 14 3 3/16 1 72
A806 HINGE 14 3 1/4 1 72
A827 HINGE 14 4 3/16 1 72
A822 HINGE 14 4 1/4 1 72
A828 HINGE 13 2 1/4 1 72
A829 HINGE 13 3 1/4 1 72
A830 HINGE 13 4 1/4 1 72
A870 HINGE 11 2 3/8 2 72
A875 HINGE 11 3 3/8 2 72
A880 HINGE 11 4 3/8 2 72
A885 HINGE 11 5 3/8 2 72
A886 HINGE 11 6 3/8 2 72
Note: Standard lengths for continuous hinges are 72” and 96” (some also available in 84” lengths). Consult customer service for available lengths for your specific part.
Additional Note: Other available options for Stainless Steel Continuous Hinges include with Type 316 Stainless Steel Pin, Punched Holes, Reverse Assembly, and Reverse Swage. Consult customer service.
All dimensions EXCEPT GAUGE expressed in inches.
CONTINUOUS HINGES
STAINLESS STEEL CONTINUOUS HINGES
Drafting Rectangle
Drafting Line
Dennis
Thermafiber® Commercial Products
3711 Mill Street, Wabash, IN 46992 | 888-TFIBER1 [834-2371] | [260] 563-2111 | www.thermafiber.comTF692/REV. 02-14 Copyright 2014, Thermafiber, Inc. All Rights Reserved
R-Value Chart
Conserves Energy
Reduces greenhouse Gas Emissions from Buildings
Saves Money
R* Values
Insulation Thickness
VersaBoard® 35** UltraBattTM
FireSpan® 40 & 90 Safing™ Insulation
RainBarrier® 45 & HD VersaBoard® 40 & 60
VersaBoard® 80***
1” 4.2 4.2
1½” 6.0 6.3
2” 8.0 8.3
2½” 10.0 10.0 10.4
3” 12.0 12.5
3½” 14.0 15.0 14.6
4” 16.0 16.7
4½” 18.0 18.8
5” 20.0 20.8
5½” 22.0 23.0 22.9
6” 24.0 24.0 25.0
6 ½” 26.0 27.1
7” 28.0 29.2
7.1” 30.0
*R = thickness – thermal conductivity (R = t ). R-Value is a measure of insulating ability.
“R” means resistance to heat flow. The higher the R-Value, the greater insulation power.
**VersaBoard® 35 minimum thickness is 1½”.
***VersaBoard® 80 is not available in a thickness of 6 ½” or 7”.
k
Minimum
70% Recycled Content
Dennis Highlight
Highlight dorwig
BERGARI
SOLUTIONS
member of the mandersgroup
RELEASED FOR CUSTOMER APPROVAL01/20/2020
INFORMATION
±1°
.XXXX = ±0.03125
.XXX = ±0.0625
.XX = ±0.125
.X = ±0.25 ALL ANGLES
OTHERWISE SPECIFIED
ENGINEERING
DRAWN BY
CHECKED BY
MANUFACTURING
CUSTOMER
TOLERANCES DO NOT APPLY TO
TOLERANCES UNLESS
REV
DESCRIPTION
COMMERCIAL FEATURES
permission from Bergari Solutions, LLC.
DESCRIPTION
DATE
DATE
DATE
GAGE THICKNESS OR
copied or shared in any form without the express
DATE
ENGINE
INFORMATION
RESONATOR ALPHA
SILENCER Km
ENGINE MAKE
ENGINE MODEL
DISPLACEMENT
EXHAUST FLOW
EXHAUST TEMPERATURE
MAX BACK PRESSURE
RAW SOUND PRESSURE
CONSTRUCTION MATERIAL
FINISH
WEIGHT (LBS)
SHEET SIZE
THIRD ANGLE PROJECTION
RESONATOR FREQUENCY
SCALE (DO NOT SCALE)
A
B
C
D
2 3 4 5 6
PART NUMBER
C175-16
HKO
500-012381
CATERPILLAR
894.9
HKO
HKO
24495.8
6456.31
DE-E 16.00-24.00
1:30 B
HIGH TEMP BLACK PAINT
HKO---
CS
SIL: DISK HOSP CS
01/20/2020
01/20/2020
SILENCER IL
SHEET
01/20/2020
01 HKO
CUSTOMER P/N
ECO
Ø120.00 X 40.50 OAH
01/20/2020
REV. BY DATE This drawing and the information contained is confidential and the property of Bergari
Solutions, LLC. None of this information is to be
SILENCER
TYP
1.25
120.00 NOM
29.47
124.00 BC
14.69
TYP
23.50
2 PLCS
4x
87.68
45°
36.00
2 PLCS
W/ 1.00-8 WELD NUTS
CL
16x 1.13
EQ SPACED
STRADDLING
21.25 BC
2 PLCS
0.50-14.00 NPT DRAIN
72.00
29.50 BC
(2)
36.00
32.00
20x 1.38
EQ SPACED
STRADDLING CL
W/ 1.13-7 WELD NUTS
40.50
16.00
36.00
0.50 TYP
4.00
OD
24.00
OD
Date 1/20/2020
Engine Exhaust Acoustics 23 Approximate Divergence Loss 0 dB(A)
Frequency 63 125 250 500 1000 2000 4000 8000 Overall
88.0 90.8 94.2 97.7 99.1 101.5 99.5 98.3 106.8
63.6 57.3 57.7 57.1 56.5 59.9 59.9 59.7 68.6
24.4 33.5 36.5 40.6 42.6 41.6 39.6 38.6 38.2
*63Hz Raw Sound Estimated - Not Provided By Engine Manufacturer Silencer Backpressure in H₂O 17.9 Silencer Sizing
Part Number Nominal Diameter Body Height Inlet Size Outlet Size 500-012381 120" 36" 2x 16" Pipe 24" Pipe
Application Data
Unsilenced distance from source (ft)
Caterpillar C175-16
Engine Manufacturer Engine Model
Engine Displacement
Maximum Exhaust Temperature
Silenced distance from source (ft)
3000 KW
6456.31 in³
Lacon
IL, 61540
Customer Data
Customer Contact
Phone Number Street
Hardin 1717Project Name
309-246-8456 Ext 104 Dave Orwig
400 N Commercial St
The above performance curve represents the theoretical sound reduction expected from the silencer specified based on the provided raw engine noise data.
Ambient conditions, pre and post silencer piping and other contributing factors beyond our control may affect the actual resulting sound performance of the silencer.
kW Rating
24495.8 CFM
894.9 °F 27 in H₂O
Insertion Loss dB(A)
Maximum Exhaust Flow
Maximum Silencer Back Pressure
Silenced Sound Pressure Levels at 23 feet dB(A) Raw Sound Pressure Levels at 23 feet dB(A)
City State
0.0
20.0
40.0
60.0
80.0
100.0
120.0
63 125 250 500 1000 2000 4000 8000
So un d Pr es su re Le ve l ( dB (A
Octave Band Center Frequency (Hz)
Expected Silencer Performance
Raw Sound Pressure Levels at 23 feet dB(A)
Silenced Sound Pressure Levels at 23 feet dB(A)
Insertion Loss Curve
Lacon, IL 61540 Phone (309)246-8456 Fax (309)246-3117
BASE TANK SPEC SHEETS
• Emergency Vents
• UL US and Canada Listed
• Improved Design with increased Airflow
• Spring Loaded – Pressure Relief set at .5 PSI, full open by 2.5 PSI
• Buna-N-Gasket provides a vapor-tight seal
• Black Painted Steel Construction – Custom Colors Available
• Private Labeling Available
SIZE PART # VENTING CAPACITY AT 2.5 PSIG
2″ 1002FT 25,669 CFH
3″ 1003FT 74,677 CFH
4″ 1004FT 134,563 CFH
5″ 1005FT 215,473 CFH
6″ 1006FT 282,694 CFH
8″ 1008FT 519,596 CFH
WARNING: Emergency Vents are designed for “Emergency Venting” and must be used in conjunction with other venting devices. Emergency Vents must be sized per UL requirements.
Emergency Vents - Female NPT | Global Tank Components, LLC omponents.net/ emergency-vents/ emergency-vents-female-npt/ drafting
OIL EQUIPMENT
MANUFACTURING LLC
VENT CAPS
• Available in threaded and slip-on designs
• Slip-On design solves clearance problems
Visit us on-line at:
www.oil-equip-mfg.com
• Rust-resistant zinc plated cast iron, as-well-as rust-proof aluminum and zinc castings
• Available in sizes from 3/4" to 4"
• Each cap includes a screen, to prevent debris from entering the vent pipe
Mushroom Vent Caps
• This popular style is used in the majority of installations in the United States, Alaska, and Canada
• Available in female NPT sizes from 3/4" to 4"
• Each cap is designed with a 30 mesh screen, to prevent debris from entering the vent pipe
Mushroom Vent Caps Part No. Male NPT 4021 3/4"
4022 1"
4023 1-1/4 "
4024 1-1/2"
4025 2"
4027 3"
4028 4"
Slip-On Vent Caps
• Zinc plated steel with screen
• Lightweight and economical
Slip-On Vent Caps Part No. Pipe Size 4036 1"
4037 1-1/4"
4038 1-1/2"
4039 2"
Part No.
Part No.
Part No.
Zinc Slip-On Cap
• OEM's most economical design
• Zinc alloy won't rust
• Slip-on design only requires
N 1/16" pipe-to-wall clearance
• Supplied with set screw and wire screen
• Available in sizes from 3/4" to 1-1/2"
Zinc Slip-On Vent Caps Part No. Pipe Size 4006 3/4" - 1"
4008 1-1/2"
Aluminum Slip-On Cap
Part No.
• These caps are ideal for "close-to-wall" Installations. Requires only N1/8" pipe-to wall clearance
• Rust proof cast aluminum design includes an integral screen
• Cap is secured to pipe using a single set screw
Aluminum Slip-On Vent Caps Part No. Pipe Size 4009 2"
4010 3/4"
4011 1"
4012 1-1/4"
Part No.
Oil Equipment Manufacturing LLC 4 Hershey Drive· Ansonia, CT 06401 • 203.736.8886· Fax 800.532.3073 • www.oil-equip-mfg.com
Dennis Highlight
Installed at the inlet of a suction line normally at the bottom of the storage tank as a prime holding valve.
Features
• Metal to metal seat for long life
• Screen helps fi lter debris from collecting on the seats
Construction Details
• Brass body and poppet
• 20 mesh stainless steel screen
• 335A— Dual seats provide twice the prime holding capability as single poppet designs
Model 334 Series Single Poppet Foot Valve & Model 335A Double Poppet Foot Valve SPECIFICATION SHEET
570 E. 7th Street, P.O. Box 238 | Dubuque, IA 52004-0238
t. 563.583.5701 | 800.553.4840 | f. 563.583.5028 www.morbros.com
Fig. 334 (1”)
Fig. 335A (1½”)
Fig. 334 Drawing
SPECIFICATION OPTIONS:
A—Thread size OD—Outside diameter of valve Height—Height of valve Weight—Shipping weight in lbs.
I.D. Number A OD Height Weight
334---0100 AV .75” 1.62” 3.03” 1
334---0200 AV 1” 2.04” 3.52” 1.25
334---0300 AV 1.5” 2.78” 4.19” 2.25
334---0400 AV 2” 3.45” 5.06” 4.75
334BP-0100 AV 1.5” 2.78” 3.88” 2.5
335A--0100 AV 1.5” 2.75” 5.88” 4.5
335A--0200 AV 2” 3.38” 6.78” 6.5
dorwig
Pneumercator Company, Inc. Tel: 631-293-8450 1785 Expressway Drive North Fax: 631-293-8533 Hauppauge, New York 11788 http://www.pneumercator.com
LS600LDxx Leak Sensor Specifications
Secondary Containment Leak Sensor
Product Description
The LS600LD float-actuated leak sensor provides secondary containment leak detection for above ground and underground storage tank applications. The sensor assembly may be suspended at the desired point of actuation via the sensor cable and compression fitting, or allowed to rest at the bottom of the containment area being monitored. The compact size and favorable displacement properties of the LS600LD make it ideal for monitoring shallow liquid levels. The LS600LD Leak Switch is available with a Buna-N or stainless steel float for monitoring in most petrochemical and chemical storage tank applications. The LS600LD optionally supports Pneumercator’s FAULT-DETECT supervised wiring technology, which automatically detects field wiring faults when connected with a TMS series controller.
Applications
Containment, Manway and Piping Sumps
Dispenser Pan
Turbine Enclosure
Double-Wall Steel Tank
Specifications
Technology: Magnetic Float, Hermetically Sealed Reed Switch Wetted Materials: Float: Buna-N (BN, SN), 316SS (SS)
Housing: 304SS and Nylon, (304SS and PTFE Teflon for SS) Stem: Brass, (316SS for SN, SS)
Cable: 22AWG, 2-Conductor, 25’ (7.5 m) Length, PVC-jacketed, (FEP Teflon-jacketed for SS) Operating Temperature: -20 ºF to 175 ºF (-30 ºC to 80 ºC), -40 ºF to 220 ºF (-40 ºC to 100 ºC) for SS Pass-thru Opening Size: Minimum 1-1/2” NPT (43 mm), (2” NPT (55 mm) for SS) Location Approval*: UL Class I, Div 1, Groups C and D; cUL Class I, Zone 0, Group IIB
Installation
Sensor may be suspended by its cable or placed on the containment or sump floor.
Certifications/Approvals
UL/cUL Approved*, File #E139464 Third-Party EPA Listed*
Ordering
LS600LDBN-1(-F,-FL) Buna-N Float, Brass Shaft, and PVC wiring LS600LDSN-1(-F,-FL) Buna-N Float, 316 SS Shaft, and PVC wiring LS600LDSS(-F,-FL) 316 SS Float, 316 SS Shaft, and Teflon wiring
(-F) denotes Fault-Detect Option for LC2000/TMS2000/3000 (-FL) denotes Fault Detect Option for TMS1000/TMS2000W/WiDAM
*When used in conjunction with the LC2000/TMS series controllers or TMS2000W series WiDAM Wireless Data Acquisition Module Note: Specifications subject to change without notice. 04-01-2013 http://www.pneumercator.com/
Application ���������������������������������f
Features
• Fill adaptor and shut-off mechanism are factory-assembled
• Straight female threaded adaptor facilitates valve installation to a precise set point
• Minimum shut-off height is 1” from the tank top
• ����������f point, cushioned closure eliminates shock
• Integral pressure relief
• 305C--2000 cap included with 1100 and 2200 models
Options
• Mechanical Test Mechanism
Verify the operation of the valve by activating the test
Available on all models
Materials of Construction
• ����������...passivated aluminum
• ����������...powder coated ductile iron & stainless steel
• Shaft, linkage and hardware...stainless steel
• Lower pipe nipple...e-coated steel
• Body... passivated aluminum
• Drop tube adaptor... passivated aluminum
Operational Criteria
• Maximum operating pressure is 100 PSI
• Maximum viscosity of 300 centistokes
• A������������������������������
• The estimated ���rate is 230 GPM at 10 PSI pressure drop (See ���curve on next page)
Code Compliance ULC-S661-10 listed, NFPA 30, 30A, UFC, IFC, PEI/RP 200, PEI/RP 600, Florida DEP EQ-858, and California EVR models available
NEW PRODUCT ANNOUNCEMENT
Model 9095X 2” Overfill Prevention Valve
Item numbers, diagrams, and flow curve on next page.
9095X-1100 (2”)
9095X-2200 (2”)
9095X-6200 (2”)
9095X-6800 (2”) (shown with optional
9095ATM1000 AK
Test Mechanism)
Application ���������������������������������f
Features
• Fill adaptor and shut-off mechanism are factory-assembled
• Straight female threaded adaptor facilitates valve installation to a precise set point
• Minimum shut-off height is 1” from the tank top
• ����������f point, cushioned closure eliminates shock
• Integral pressure relief
• 305C--2000 cap included with 1100 and 2200 models
Options
• Mechanical Test Mechanism
Verify the operation of the valve by activating the test
Available on all models
Materials of Construction
• ����������...passivated aluminum
• ����������...powder coated ductile iron & stainless steel
• Shaft, linkage and hardware...stainless steel
• Lower pipe nipple...e-coated steel
• Body... passivated aluminum
• Drop tube adaptor... passivated aluminum
Operational Criteria
• Maximum operating pressure is 100 PSI
• Maximum viscosity of 300 centistokes
• A������������������������������
• The estimated ���rate is 230 GPM at 10 PSI pressure drop (See ���curve on next page)
Code Compliance ULC-S661-10 listed, NFPA 30, 30A, UFC, IFC, PEI/RP 200, PEI/RP 600, Florida DEP EQ-858, and California EVR models available
NEW PRODUCT ANNOUNCEMENT
Model 9095X 2” Overfill Prevention Valve
Item numbers, diagrams, and flow curve on next page.
9095X-1100 (2”)
9095X-2200 (2”)
9095X-6200 (2”)
9095X-6800 (2”) (shown with optional
9095ATM1000 AK
Test Mechanism)
NEW PRODUCT ANNOUNCEMENT
570 E. 7th Street, P.O. Box 238 | Dubuque, IA 52004-0238
t. 563.583.5701 | 800.553.4840 | f. 563.583.5028 www.morbros.com
0 5 10 15 20 25
F L O W
G P M)
Differential Pressure (PSI)
2 INCH 9095GBT FLOW CURVE (CV=74)
2 INCH 9095GBT FLOW CURVE
2 INCH 9095X FLOW CURVE (CV=74)
2 INCH 9095X FLOW CURVE
Model 9095X Overfill Prevention Valve (continued)
Minimum tank depth
8½”
1” minimum shut-off height Integrated spill container
9095X-1100 AV
5.28
TO
7.00
5.88
TO
7.60 16.0
9095X-1100 AV
CONFIDENTIAL: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MORRISON BROS. CO. TO BE USED ONLY FOR PURPOSE EXPLICITLY DIRECTED BY MORRISON BROS. CO. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF MORRISON BROS. CO. IS PROHIBITED.
5.28
TO
10.63
5.88
TO
11.23
CONFIDENTIAL: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MORRISON BROS. CO. TO BE USED ONLY FOR PURPOSE EXPLICITLY DIRECTED BY MORRISON BROS. CO. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF MORRISON BROS. CO. IS PROHIBITED.
9095X-2200 AV
20.3
TO
6.31
18.44
5.71
TO
17.84
9095X-6800 AV
SOLID WORKS CONFIDENTIAL: THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF MORRISON BROS. CO. TO BE USED ONLY FOR PURPOSE EXPLICITLY DIRECTED BY MORRISON BROS. CO. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF MORRISON BROS. CO. IS PROHIBITED.
29.4
9095X-1100 (shown) or 9095X-6100
9095X-2200 (shown) or 9095X-6200
9095X-2800 or 9095X-6800 (shown)
5.03
TO
6.75
4.53
TO
6.25 5.03
TO
10.21
4.53
TO
9.71 6.51
TO
19.05
5.91
TO
18.45
TOP OF TANK RISER
1.72”
11.2
4.8 4.8 4.1
15.5
Field Adjustability Range
5.18”
Field Adjustability Range
Field Adjustability Range
12.54”
25.7
Item Number Inlet Size
Tank Connection
Size Drop Tube
Fill Connection
Cap Included
Test Mechanism Available Application
Weight (lbs) List Price
9095X-1100 AV 2” 4” No ������ Y Y Generator base tanks with integrated spill container 6.50
9095X-6100 AV 2” 4” No ������ N Y Generator base tanks with integrated spill container 8.00
9095X-2200 AV 2” 4” Yes ������ Y Y ����������������������� 15.00
9095X-6200AVEVR 2” 4” Yes ������ N Y ����������������������� 10.50
9095X-2800 AV 2” 4” Yes ������ N Y General purpose and aviation 14.80
9095X-6800AVEVR 2” 4” Yes ������ N Y General purpose and aviation 15.00
9095ATM1000 AK Test mechanism for 9095X series
E RV
E RV
drafting o ~ ROCHESTER '- GAUGE5,INC. Magnetic
Liquid-Level Gauges
ISO 9001 :2000 REGISTERED
Application The 6500 Series SeniorN gauges are designed for use in low pressure tanks 0-25 psig [0-1,7Bar] containing diesel fuel, gasoline, fuel oil and lubricating oils.
Used in many applications such as construction equipment, sta-tionary generators, boats, farm equipment and home heating.
General Information & Features The 6500 Series SeniorN gauges are available in gear-action models for top, centerline or angle mounting. In lever-action models centerline mounting is only available.
The standard float is nitrile rubber. Aluminum or stainless steel floats are available at extra cost. The gauge is mounted to a mating SeniorN flange 2 W' bolt circle [63,5mm] using fou~ 11."-28 x 0/,6" long screws. The gasket is Buna-N.
Model # Action Mounting Dial, Sender or Switch Data 6540 Top Senior™ TwinSite TM Sender in choice of 0-30, Gear 6543 C/lorAngle 0-90, or 240-30 Ohm ranges. #5002S00062 direct-l6543 lever C/l reading dials may also be used.
6550 Top Standard switch #5023S00778 S.P.S.T., 150 VAC/50 Gear VOC M Amp. Please furnish tank drawings and 6553 C/lorAngle switch points so proper gauge and calibration can l6553 lever C/l be supplied. Other switches available, see OS-364.
6560 #5025S00570 Senior™ side-reading fractional
6580 Gear Top
6583 C/lorAngle #5002S00062 Senior™ direct-reading fractional l6583 lever C/l #5002S00547 Senior™ direct-reading fractional
6583-00093 Gear Top #5002S00062 direct-reading fractional
Top Mounting Adjustable Liquid-Level Gauges Model # Mounting Dial or Sending Data
• #5002S01379 Senior direct-reading fractional dial 6580-0151 Top • #P5880S02547 Senior TwinSite TM dial 0-90 Ohms
• #P5648S02547 Senior TwinSite™ dial 240-30 Ohms
• Also available witll 0-90…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .