This is a modification to a pre-solicitation notice for project number 757-20-205 to construct a generator docking station. The project magnitude is between $250,000 and $500,000 with a NAICS code of 238210 and business size standard of $16.5 million. This solicitation will be a Service Disabled Veteran Owned Small Business set-aside requiring bidders to be registered and verified on sam.gov and vip.vetbiz.va.gov. The duration of the project shall not exceed 150 calendar days from receipt of the notice to proceed. The agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2018 OHIO BUILDING CODE - AMBULATORY CARE CENTER
CHAPTER 3 - USE GROUP:
USE GROUP: B-BUSINESS AMBULATORY
B-BUSINESS
CHAPTER 4 - SPECIAL DETAILED REQUIREMENTS:
DETAILED REQUIREMENTS IF NEEDED
FIRE-RESISTANCE RATINGS REQUIREMENTS - TABLE 601:
CONSTRUCTION TYPE: 1A
STRUCTURAL FRAME: 3 HRS
BEARING WALLS:
EXTERIOR: 3 HRS
INTERIOR: 3 HRS
NON BEARING WALLS & PARTITIONS:
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 2 HRS
ROOF CONSTRUCTION: 1 1/2 HRS
CHAPTER 7 - FIRE-RESISTANCE-RATED CONSTRUCTION:
SHAFT ENCLOSURES: 2 HRS
EXIT ENCLOSURES: 2 HRS
EXIT PASSAGEWAYS: 0 HRS
CHAPTER 8 - INTERIOR FINISHES:
EXIT ENCLOSURES & PASSAGEWAYS: CLASS B
CORRIDORS: CLASS C
ROOMS & ENCLOSED SPACES: CLASS C
INTERIOR FLOOR FINISH: MINIMUM CLASS II
CHAPTER 9 - FIRE PROTECTION SYSTEMS:
SPRINKLER SYSTEM: FULLY SUPPRESSED
FIRE ALARM SYSTEM: YES
CHAPTER 10 - MEANS OF EGRESS:
DOOR WIDTH: 32" MINIMUM CLEAR WIDTH
CORRIDOR WIDTH: .2" PER OCCUPANT, BUT NOT LESS THAN 44"
LENGTH OF EXIT TRAVEL: 200'
2018 NFPA 101 LIFE SAFETY CODE - AMBULATORY CARE CENTER
OCCUPANCY (6.1.11):
BUSINESS - OUTPATIENT CLINIC (AMBULATORY)
AMBULATORY HEALTH CARE (CHAPTER 20/21)
BUILDING TYPE:
TYPE 1 (332)
FIRE-RESISTANCE RATING REQUIREMENTS - TABLE A8.2.1.2:
STRUCTURAL FRAME: 3 HRS
BEARING WALLS:
EXTERIOR: 3 HRS
INTERIOR: 3 HRS
NON BEARING WALLS AND PARTITIONS
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 2 HRS
ROOF CONSTRUCTION: 1 1/2 HOURS
FIRE-RESISTANCE RATED CONSTRUCTION - TABLE A8.6.5/7.1.3.2.1
SHAFT ENCLOSURES: 2 HRS
EXIT ENCLOSURES: 2 HRS
SMOKE BARRIERS (20.3.7.5):
1 HOUR
TRAVEL DISTANCE (20.2.6.2):
REMOTE POINT TO EXIT 200 FOOT MAX
2018 OHIO BUILDING CODE - BOILER PLANT
CHAPTER 3 - USE GROUP:
BOILER AND UTILITY ROOM F-1 - FACTORY INDUSTRIAL
OFFICE B - BUSINESS
STORAGE S-1 - STORAGE
CHAPTER 4 - SPECIAL DETAILED REQUIREMENTS:
DETAILED REQUIREMENTS IF NEEDED
FIRE-RESISTANCE RATINGS REQUIREMENTS - TABLE 601:
CONSTRUCTION TYPE: IIB
STRUCTURAL FRAME: 0 HRS
BEARING WALLS:
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
NON BEARING WALLS & PARTITIONS:
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 0 HRS
ROOF CONSTRUCTION: 0 HRS
CHAPTER 7 - FIRE-RESISTANCE-RATED CONSTRUCTION:
SHAFT ENCLOSURES: 2 HRS
EXIT ENCLOSURES: 2 HRS
EXIT PASSAGEWAYS: 0 HRS
CHAPTER 8 - INTERIOR FINISHES:
EXIT ENCLOSURES & PASSAGEWAYS: CLASS B
CORRIDORS: CLASS C
ROOMS & ENCLOSED SPACES: CLASS C
INTERIOR FLOOR FINISH: MINIMUM CLASS II
CHAPTER 9 - FIRE PROTECTION SYSTEMS:
SPRINKLER SYSTEM: FULLY SUPPRESSED
FIRE ALARM SYSTEM: YES
CHAPTER 10 - MEANS OF EGRESS:
DOOR WIDTH: 32" MINIMUM CLEAR WIDTH
CORRIDOR WIDTH: .2" PER OCCUPANT, BUT NOT LESS THAN 44"
LENGTH OF EXIT TRAVEL: 300' - BUSINESS
400' - ALL OPTHER OCCUPANCIES
2018 NFPA 101 LIFE SAFETY CODE - BOILER PLANT
OCCUPANCY (6.1.11):
BOILER AND UTILITY ROOMS SPECIAL-PURPOSE INDUSTRIAL
OFFICES BUSINESS
STORAGE STORAGE
BUILDING TYPE:
TYPE II (000)
FIRE-RESISTANCE RATING REQUIREMENTS - TABLE A8.2.1.2:
STRUCTURAL FRAME: 0 HRS
BEARING WALLS:
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
NON BEARING WALLS AND PARTITIONS
EXTERIOR: 0 HRS
INTERIOR: 0 HRS
FLOOR CONSTRUCTION: 0 HRS
ROOF CONSTRUCTION: 0 HOURS
FIRE-RESISTANCE RATED CONSTRUCTION - TABLE A8.6.5/7.1.3.2.1
SHAFT ENCLOSURES: 2 HRS
EXIT ENCLOSURES: 2 HRS
APPLICABLE CODED
INTERNATIONAL BUILDING CODE, 2018 EDITION
NFPA 101 LIFE SAFETY CODE, 2018 EDITION
NFPA 70 NATIONAL ELECTRICAL CODE, 2020 EDITION
NFPA 110, 2019 EDITION
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
Project Number
Building Number
Drawing Number
CHALMERS P. WYLIE ACC
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Farid F. Mehr, P.E.
Chief, Engineering Services
Phase
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
/1
/2
:4
:4
A M
C
R e v it L o c a l\
R
-G e n e ra to r
D o c k in g S ta ti o n
C e n tr a l_ s w e a v e r@ c b lh d e s ig n .c o m
. r v t
GI-001
757-20-205
CBLH CBLH
CONSTRUCT GENERATOR
DOCKING STATION
12/07/20
420 N. JAMES ROAD, COLUMBUS, OH 43219
COVER
PROJECT NUMBER:
SUBMITTAL FOR:
DRAWING INDEX: CODE DATA:LOCATION MAP:
CONSTRUCT GENERATOR DOCKING STATION
420 N. JAMES ROAD, COLUMBUS, OH 43219
757-20-205
BID AND CONSTRUCTION
DRAWING INDEX
SHEET NO. SHEET NAME
GENERAL
GI-001 COVER
ELECTRICAL
E-001 ELECTRICAL ONE LINE LEGEND AND GENERAL NOTES
ED-101 PARTIAL FIRST FLOOR AND SITE ELECTRICAL DEMOLITION PLAN
EP-101 PARTIAL SITE ELECTRICAL AND GENERATOR LAYOUT PLANS
EP-102 PARTIAL SITE ELECTRICAL PLAN
EP-501 ELECTRICAL DETAILS AND PANELBOARD SCHEDULE
EP-601 MAIN BUILDING EXISTING ONE-LINE DIAGRAM
EP-602 BOILER PLANT / FUTURE CHILLER PLANT ONE-LINE DIAGRAM
EP-603 GENERATOR CONTROL WIRING DETAIL
EP-604 ELECTRICAL GROUNDING SYSTEM DIAGRAM
Revisions Date
BID AND CONSTRUCTION 03/09/21
ABBREVIATIONS
GENERAL ELECTRICAL SPECIFICATION NOTES:
AC ABOVE COUNTER AT 9" UNLESS OTHERWISE NOTED
AF AMP FRAME
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AT AMP TRIP
BC BELOW COUNTER AT 18"AFF UNLESS OTHERWISE NOTED
BFC BELOW FINISHED CEILING
CM CEILING MOUNTED
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
IG ISOLATED GROUND
ITD INFORMATION TECHNOLOGY DEPARTMENT
PROVIDE DEFINITION: FURNISH, INSTALL AND CONNECT COMPLETE.
X EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO REMAIN
XB INDICATES EXISTING OUTLET, LIGHTING FIXTURE, CONDUIT, ETC - TO BE REMOVED.
PROVIDE BLANK COVER FOR OUTLET AND MAINTAIN CIRCUIT CONTINUITY.
XL NEW LOCATION OF EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC.
XN EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REPLACED WITH NEW OF
SPECIFIED TYPE
XR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO BE REMOVED COMPLETE-
MAINTAIN CIRCUIT CONTINUITY TO ADJACENT OUTLETS, EXTEND CONDUIT AND WIRING AS
REQUIRED.
XRR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REMOVED AND REINSTALLED
AT NEW LOCATION - EXTEND CONDUIT AND WIRING AS REQUIRED
MC MECHANICAL CONTRACTOR
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
NF NOT FUSED
OFE OWNER FURNISHED EQUIPMENT
TC TELECOMMUNICATIONS CONTRACTOR
TCC TEMPERATURE CONTROLS CONTRACTOR
TV TELEVISION
VDC VOICE/DATA CONTRACTOR
VFD VARIABLE FREQUENCY DRIVE
WM WIREMOLD
WP WEATHERPROOF ENCLOSURE - NEMA 4
THE FOLLOWING ITEMS SUPERCEDE ITEMS WITHIN THE SPECIFICATIONS:
THE USE OF HOSPITAL GRADE HCF CABLE IS NOT PERMITTED.
THE FOLLOWING SYSTEM CABLING IS PERMITTED TO BE INSTALLED IN THE CABLE TRAY SYSTEM:
A. TEL/DATA CABLING
B. HOSPITAL PAGING SYSTEM
ALL OTHER SPECIAL SYSTEMS CABLING (FIRE ALARM, NURSE CALL, CATV) SHALL BE INSTALLED IN A COMPLETE CONDUIT SYSTEM. E.C SHALL
GROUND CABLE TRAY IN ACCORDANCE WITH N.E.C. ARTICLE 250.96.
GENERAL ELECTRICAL INSTALLATION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.
ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT
AND PATCH WALLS SHALL BE THE RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.
CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK. CONTRACTOR SHALL
REPLACE ANY DAMAGED CEILING TILES.
PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING MOUNTED DEVICES WITH
ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS.
COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS ("OFF-HOURS").
INCLUDE ALL PREMIUM TIME CHARGES IN BID.
CONTRACTOR SHALL CONNECT ALL EQUIPMENT COMPLETE PER MANUFACTURER'S WIRING DIAGRAMS AND INSTRUCTIONS. VERIFY INSTALLATION LOCATION, VOLTAGE, AMPS, NO. OF WIRES, AND PROTECTION REQUIREMENTS PRIOR TO ROUGH-IN. CONTACT ENGINEER
WITH ANY DISCREPANCIES FROM DESIGN DRAWINGS.
PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MECHANICAL EQUIPMENT OR OTHER EQUIPMENT WHICH
MAY PROPAGATE VIBRATION.
ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN
EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.
ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT. ALL COSTS
ASSOCIATED WITH THESE REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY LIGHTING TO ADEQUATELY LIGHT ALL CONSTRUCTION AREAS, TEMPORARILY PARTITIONED AREAS, AND EXIT CORRIDORS MAINTAINED DURING CONSTRUCTION.
PROJECT AND PHASING SCOPE LINES INDICATE WHERE GENERAL CONSTRUCTION BOUNDARIES OCCUR. ELECTRICAL WORK AND UTILITY
TIE-INS MAY OCCUR OUTSIDE OF SCOPE LINES.
GENERAL LEGEND:
CODED NOTE - "1" INDICATES NOTE NUMBER
REVISION REFERENCE NUMBER
MECHANICAL EQUIPMENT IDENTIFIER
DETAIL REFERENCE - "1" INDICATES DETAIL NUMBER, "E0.1" INDICATES DRAWING NUMBER
COLUMN REFERENCE GRID
INDICATES EXISTING CONSTRUCTION WALL TYPE
INDICATES DEMOLITION WALL TYPE
INDICATES NEW CONSTRUCTION WALL TYPE
AC
GB13
E0.1
A
POWER DISTRIBUTION EQUIPMENT
208/120V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
480/277V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
SPECIAL PANEL OR PULLBOX - SIZE AND TYPE AS NOTED
NON-FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED. PROVIDE WITH CONTROL INTERLOCK WHEN
CONNECTED TO VFD.
FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES
ELECTRICAL GROUNDING BUS BAR
EGB
1.
2.
3.
4.
FOR #10 AWG CONDUCTORS AND SMALLER, JOINTS AND SPLICES SHALL BE MADE WITH SCREW-ON WIRE CONNECTORS. CONNECTOR
JOINTS SHALL BE INSULATED WITH TAPE.
FOR #8 AWG AND LARGER WIRES SHALL BE MADE WITH COMPRESSION TYPE MECHANICAL CONNECTORS AND INSULATED WITH HEAT
SHRINK TUBING TO A 600V INSULATION LEVEL.
LABEL BOX COVER WITH SOURCE, CIRCUIT, AND LOAD INFORMATION. LABEL SHALL BE MADE WITH PERMANENT MARKER. STICK ON
LABELS ARE NOT ACCEPTABLE.
VERIFY PHASE ROTATION OF ALL LOADS PRIOR TO STARTING. CREATE REPORT OF PHASE ROTATION FOR EACH LOAD WITH 1) EXISTING PHASE ROTATION, 2) RECONNECTED PHASE ROTATION, 3) TIME AND DATE OF PHASE ROTATION TEST, 4) IDENTIFICATION INFORMATION
OF TECHNICIAN VERIFYING PHASE ROTATION.
ELECTRICAL CONTRACTOR SHALL OBTAIN WRITTEN APPROVAL FROM FACILITY FOR ALL SCHEDULED SHUTDOWNS A MINIMUM OF (60) DAYS FOR ALL DAYTIME WORK FOR ALL WEEKENDS AND WEEKDAYS, (14) DAYS PRIOR TO ACTUAL SHUTDOWN FOR ALL NIGHTTIME WORK.
CONTRACTOR SHALL COORDINATE WITH FACILITY WHICH CRITICAL LOADS MUST RECEIVED TEMPORARY POWER, IF ANY. CONDUCT SHUTDOWNS AFTER TYPICAL BUSINESS HOURS. CONTRACTOR SHALL SUBMIT AT A MINIMUM THE FOLLOWING INFORMATION FOR A
REQUESTED ELECTRICAL POWER SYSTEM SHUTDOWN.
• IDENTIFY ALL CONNECTED LOADS AFFECTED BY THE SHUTDOWN. CONTRACTOR SHALL VERIFY WITH FACILITY'S MAINTENANCE
DEPARTMENT THE ACCURACY OF EXISTING PANELBOARD CONNECTIONS DIRECTORY.
• PROPOSED DATE, TIME, AND ESTIMATED DURATION OF THE SHUTDOWN.
• METHOD OF TEMPORARY FEEDING OF CRITICAL LOADS THAT MUST BE MAINTAINED DURING SHUTDOWN.
CONTRACTOR SHALL MINIMIZE POTENTIAL SHUTDOWNS OF EQUIPMENT BY FURNISHING AND INSTALLING NEW FEEDERS PRIOR TO
SHUTDOWN WHENEVER POSSIBLE AND UTILIZING SHUTDOWNS FOR CUT-OVER TO NEW FEEDER.
1.
2.
JOINTS AND SPLICES SPECIFICATION
SHUTDOWN GENERAL NOTE:
CONDUIT ROUTING INDICATED ON DRAWINGS IS FOR REFERENCE ONLY, UNLESS OTHERWISE NOTED. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS WITH ELECTRICAL EQUIPMENT SUBMITTAL FOR APPROVAL. ROUTING DRAWINGS SHALL INCLUDE FIELD VERIFIED ROUTING, BENDS, PULLBOXES, CONDUIT BODIES, PENETRATIONS, ETC. CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE NECESSARY TO CONVEY ROUTING INFORMATION, MAINTAIN NEC REQUIRED ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION BOXES, ETC. TO REMAIN. ELECTRICAL EQUIPMENT SUBMITTAL WILL NOT BE APPROVED WITHOUT CONDUIT ROUTING SHOP
DRAWINGS.
CONDUIT ROUTING GENERAL NOTE:
225A
EXISTING EQUIPMENT, FEEDER/CIRCUIT - TO BE DEMOLISHED
NEW FEEDER/CIRCUIT AND FEEDER TAG
EXISTING EQUIPMENT, FEEDER/CIRCUIT - TO REMAIN
EQUIPMENT OUTLINE
BOLTED STATIONARY CIRCUIT BREAKER - 3-POLE UNLESS OTHERWISE NOTED
GF - EQUIP BREAKER WITH GROUND FAULT TRIP
GFA - EQUIP BREAKER WITH GROUND FAULT ALARM
LSI - EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS
400A-3Ø-4W
FUTURE EQUIPMENT, FEEDER/CIRCUIT - N.I.C.
NAME
POWER DISTRIBUTION ONE-LINE LEGEND
X
XR
NEW
1600AF
DRAW OUT CIRCUIT BREAKER - 3-POLE UNLESS OTHERWISE NOTED
GF - EQUIP BREAKER WITH GROUND FAULT TRIP
GFA - EQUIP BREAKER WITH GROUND FAULT ALARM
LSI -
NAME
RATING
PRI:SEC
VOLTAGE
TEMPERATURE
RISE
VOLTAGE
MAIN
AMPS
NAME
PANELBOARD.
REFER TO PANELBOARD SCHEDULES AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
TRANSFORMER. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
AF - AMP FRAME
AT - AMP TRIP
LSIG - EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS AND GROUND FAULT.
EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS
LSIG - EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS AND GROUND FAULT.
800 AT
GROUNDING TERMINATION POINT FOR AN EQUIPMENT GROUNDING CONDUCTOR.
CONNECTION SHALL BE MADE BY BONDING THE EQUIPMENT GROUNDING CONDUCTOR TO
THE GROUNDED SERVICE CONDUCTOR AND THE GROUNDING ELECTRODE CONDUCTOR.
DEDICATED NEUTRAL CONDUCTORS
DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH CIRCUITS WITH
SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED.
ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.
AF - AMP FRAME
AT - AMP TRIP
STRUCTURAL LEGEND
12" SLAB ON GRADE W/#5@12" ON-CENTER EACH WAY TOP AND BOTTOM. CONCRETE SHALL HAVE f'c = 5,000 PSI AIR- ENTRAINED 6%+/- 1% W/ 650 POUNDS CEMENT PER YARD AND MAXIMUM W/C = 0.40. TOP REINFORCING IN SLAB TO BE EPOXY
COATED; INCLUDING TOP DOWEL FROM FOOTING INTO SLAB.
S-12
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
Project Number
Building Number
Drawing Number
CHALMERS P WYLIE VA
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
20007
100% CONSTRUCTION
DOCUMENTS
/9
/2
:0
:4
P
M Z
M y D o c u m e n ts
\2
F
F H
C F
R lv ili m o n o v ic
Q
F F
.r v t
E-001
757-20-205
SPC CPC
CONSTRUCT GENERATOR
DOCKING STATION
12/07/2020
420 N. JAMES ROAD, COLUMBUS, OH 43219
ELECTRICAL ONE LINE LEGEND AND
GENERAL NOTES
CODES AND STANDARDS
1.
2.
DESIGN LOADS
GENERATOR ESTIMATED WEIGHT W/FUEL: 110,000 LBS
DESIGN STRESSES
CONCRETE (STRENGTH DESIGN) MINIMUM COMPRESSIVE STRENGTH IN 28 DAYS:
CONCRETE SUBJECT TO FREEZING AND THAWING -------------------------------------------- f'c = 5,0000 PSI REINFORCING BARS (ASTM A615, GRADE 60) ----------------------------------------------------- Fy = 60,000 PSI
SOIL BEARING PRESSURE FOR FOUNDATIONS (PERIMETER TRENCH) FOOTING
ASSUMED -------------------------------------------------------------------------------------------------------- 1,500 PSF
GENERATOR PAD FOUNDATION
1.
2.
3.
4.
5.
6.
7.
8.
9.
CONCRETE CONSTRUCTION
1.
2.
3.
4.
5.
6.
7.
8.
GENERAL
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
NEW CONSTRUCTION HAS BEEN DESIGNED TO, AND SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE FOLLOWING BUILDING CODES
AND STANDARDS:
A: 2018 OHIO BUILDING CODE (OBC 2018)
B. ASCE 7-10, MINIMUM DESIGN LOADS FOR BUILDING AND OTHER STRUCTURES.
UNLESS EXPLICITLY MODIFIED IN THE CONTRACT DRAWINGS AND SPECIFICATIONS, THE CONTRACTOR SHALL COMPLY WITH
PROVISIONS OF:
FOUNDATION FOR THIS PROJECT IS DESIGNED IN ACCORDANCE WITH THE PRESUMPTIVE LOAD BEARING VALUES OF SOILS AS DEFINED IN OHIO BUILDING CODE SECTION 1806. CONTRACTOR SHALL HIRE A TESTING AGENCY OR GEOTECHNICAL ENGINEER TO VERIFY PRESUMED BEARING CAPACITY. CONTRACTOR SHALL SUBMIT REPORT TO THE COR PRIOR TO PLACEMENT OF FOUNDATIONS.
ELEVATION GIVEN IS TO TOP OF FOUNDATION.
GENERATOR PAD FOUNDATION MUST BE SUPPORTED ON UNDISTURBED SOIL CAPABLE OF ACHIEVING THE DESIGN SOIL BEARING PRESSURE WITHOUT APPRECIABLE SETTLEMENT. WHERE ADDITIONAL EXCAVATION IS REQUIRED TO ATTAIN THE DESIGN BEARING PRESSURE, BACKFILL THE OVER EXCAVATED AREA WITH LEAN CONCRETE UP TO THE DESIGN BEARING ELEVATION.
COMPACT ALL FILL UNDER GENERATOR PAD FOUNDATION ON GROUND TO 98% OF OPTIMUM LABORATORY DENSITY IN ACCORDANCE WITH ASTM D698 STANDARD PROCTOR METHOD. PLACE TILL IN 6" TO 8" LAYERS AND COMPACT WITH VIBRATORY TAMPING EQUIPMENT.
IN GRANULAR SOILS (SANDS AND GRAVEL) THE SOILED SHALL BE MECHANICALLY TAMPED TO A HARD SURFACE IMMEDIATELY PRIOR TO
PLACING FOUNDATION.
EXISTING FOUNDATIONS:
LOCATE EXISTING UNDERGROUND UTILITIES IN AREAS OF CONSTRUCTION. COORDINATE WITH UTILITY COMPANIES FOR ANY SHUT-OFF REQUIREMENTS OF STILL ACTIVE LINES. CALL THE OHIO UTILITIES PROTECTION SERVICE AT 800-362-2764.
WHEN EXCAVATIONS APPROACH THE GROUND WATER LEVEL, THE WATER LEVEL SHALL BE LOWERED BY AN ACCEPTABLE DEWATERING SYSTEM SO THAT THE WATER LEVEL IS MAINTAINED CONTINUOUSLY A MINIMUM OF 2'-0" BELOW THE EXCAVATION.
THE BOTTOM OF FOUNDATIONS SHALL BE PROTECTED AGAINST FREEZING UNTIL BACKFILL OR OTHER PERMANENT PROTECTIVE COVER
IS IN PLACE.
ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE ACI 318 AND ACI DETAILING MANUAL, EXCEPT THAT CONSTRUCTION AND REMOVAL OF FORMS AND RESHORING SHALL BE
INSPECTED BY THE CONTRACTOR'S ENGINEER.
REINFORCING STEEL SHALL HAVE THE FOLLOWING MINIMUM COVERAGE. PLACE BARS AS NEAR TO THE CONCRETE SURFACE AS THESE
MINIMA PERMIT WHEREVER POSSIBLE, UNLESS NOTED OTHERWISE.
FURNISH BAR SUPPORTS WHERE NECESSARY DURING CONSTRUCTION.
PROVIDE PIPE SLEEVES AND INSERTS IN CONCRETE WORK WHERE REQUIRED.
DRAWINGS SHOW TYPICAL REINFORCING CONDITIONS. CONTRACTOR SHALL PREPARE DETAILED PLACEMENT DRAWINGS OF ALL CONDITIONS SHOWING QUANTITY, SPACING, SIZES, CLEARANCES, LAPS, INTERSECTIONS, AND COVERAGE REQUIRED BY THE STRUCTURAL DETAILS, APPLICABLE CODE, AND TRADE STANDARDS. CONTRACTOR SHALL NOTIFY REINFORCING INSPECTOR OF ANY ADJUSTMENTS FROM TYPICAL CONDITIONS WHICH ARE PROPOSED IN PLACEMENT DRAWINGS TO FACILITATE FIELD PLACEMENT OF
REINFORCING STEEL AND CONCRETE.
BAR BENDS SHALL BE MADE COLD. BARS SHALL NOT BE BENT AFTER AND PORTION OF THE BAR IS ENCASED IN CONCRETE.
SPLICES (GRADE 60 DEFORMED BARS)
SEAL EXPOSED SURFACES OF CONCRETE WITH A CLEAR, NON-STAINING, WATER-BASED, PENETRATING CONCRETE SEALER. BASIS OF
DESIGN OR EQUAL:
INTERGUARD BY W.R.MEADOWS OR
AQUANIL PLUS 100 BY CHEM MASTERS.
FOLLOW MANUFACTURER'S RECOMMENDATIONS FOR SURFACE PREPARATION AND INSTALLATION.
ALL NEW CONSTRUCTION SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND THE BUILDING CODE.
THE STRUCTURAL DRAWINGS ILLUSTRATE STRUCTURAL MEMBERS. REFER TO ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR NON-STRUCTURAL ITEMS WHICH REQUIRE SPECIAL PROVISIONS DURING THE CONSTRUCTION OF THE STRUCTURAL
MEMBERS.
DRAWINGS ARE NOT TO BE SCALED.
REFER TO PLANS FOR CONDUIT, PIPES, DUCTS, EQUIPMENT, ETC. THAT MAY REQUIRE SLEEVES.
THE CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS WHICH IMPACT THE WORK REQUIRED.
FIELD VERIFY SIZES, ELEVATIONS, HOLE LOCATIONS, ETC. PRIOR TO FABRICATION.
THE CONTRACTOR SHALL CAREFULLY REVIEW THE DRAWINGS TO IDENTIFY THE SCOPE OF WORK REQUIRED, VISIT THE SITE TO RELATE THE SCOPE OF WORK TO EXISTING CONDITIONS AND DETERMINE THE EXTENT TO WHICH THOSE CONDITIONS AND PHYSICAL
SURROUNDINGS WILL IMPACT THE WORK.
EXISTING CONDITIONS AS SHOWN ON THESE PLANS ARE FOR REFERENCE ONLY. THE CONTRACTOR IS REQUIRED TO FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
THE CONTRACTOR SHALL RESOLVE ANY CONFLICTS ON THE DRAWINGS OR IN THE SPECIFICATIONS WITH THE A/E BEFORE
PROCEEDING WITH THE WORK.
ANY DEVIATION, MODIFICATION, OR SUBSTITUTION FROM THE APPROVED SET OF DRAWINGS SHALL BE SUBMITTED TO THE OWNER, ARCHITECT, AND ENGINEER FOR REVIEW/APPROVAL PRIOR TO ITS USE OR INCLUSION IN THE SHOP DRAWINGS.
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY SHORES, BRACES, AND GUYS REQUIRED TO SUPPORT ALL LOADS TO WHICH THE STRUCTURE AND COMPONENTS, SOILS, OTHER STRUCTURES, AND UTILITIES MAY BE SUBJECTED DURING CONSTRUCTION. SHORING
SYSTEMS SHALL BE DESIGNED.
THE CONTRACTOR SHALL PROVIDE MEANS, METHOD, TECHNIQUES, SEQUENCE, AND PROCEDURE OF CONSTRUCTION AS REQUIRED.
THE CONTRACTOR SHALL PROTECT ALL WORK, MATERIALS, AND EQUIPMENT FROM DAMAGE AND SHALL PROVIDE PROPER STORAGE
FACILITIES FOR MATERIALS AND EQUIPMENT DURING CONSTRUCTION.
SITE VISITS PERFORMED BY THE A/E DO NOT CONSTITUTE INSPECTIONS OF MEANS AND METHODS OF CONSTRUCTION PERFORMED BY
THE CONTRACTOR.
STRUCTURAL OBSERVATIONS PERFORMED BY THE A/E DURING CONSTRUCTION ARE NOT THE CONTINUOUS AND SPECIAL INSPECTION SERVICES AND DO NOT WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS REQUIRED OF THE BUILDING DEPARTMENT INSPECTOR OR THE TESTING AGENCY. OBSERVATIONS ALSO DO NOT GUARANTEE THE CONTRACTOR'S PERFORMANCE AND SHALL NOT BE
CONSIDERED AS SUPERVISION OF CONSTRUCTION.
THE CONTRACTOR SHALL REVIEW SHOP DRAWINGS FOR COMPLETENESS AND COMPLIANCE WITH CONTRACT DOCUMENTS. THE
CONTRACTOR SHALL STAMP SHOP DRAWINGS PRIOR TO SUBMISSION TO THE A/E.
REVIEW OF THE SHOP DRAWINGS BY THE A/E SHALL NOT BE CONSTRUED AS AN AUTHORIZATION TO DEVIATE FROM THE CONTRACT
DOCUMENTS.
SHOP DRAWINGS WILL NOT BE PROCESSED IF THEY ARE INCOMPLETE, LACK COORDINATION WITH RELEVANT PORTION OF CONTRACT DOCUMENTS, LACK CALCULATIONS IF REQUIRED, OR IF DEVIATIONS MODIFICATIONS, AND SUBSTITUTIONS ARE INDICATED WITHOUT
PRIOR WRITTEN APPROVAL FROM THE A/E.
NO PIPES OR DUCTS SHALL BE EMBEDDED INTO STRUCTURAL MEMBERS UNLESS SO SHOWN ON THE PLANS AND APPROVED BY THE
ENGINEER.
BAR
SIZE
#3 #4 #5 #6 #7 #8
TOP
28" 37" 47" 56" 81" 93"
OTHER
22" 29" 36" 43" 63" 72" f'c = 3000 PSI
CLASS B TENSION LAP SPLICE
TOP
28" 37" 47" 56" 81" 93"
OTHER
22" 29" 36" 43" 63" 72" f'c = 3000 PSI
TOP
24" 33" 41" 49" 71" 81"
OTHER
19" 25" 31" 37" 54" 62" f'c = 4000 PSI
TOP
28" 37" 47" 56" 81" 93"
OTHER
22" 29" 36" 43" 63" 72"
TOP
22" 29" 35" 43" 63" 72"
OTHER
17" 23" 28" 34" 49" 56" f'c = 5000 PSI
BAR
SIZE
#3 #4 #5 #6 #7 #8
TOP
22" 29" 36" 43" 63" 72"
OTHER
17" 22" 28" 33" 48" 55" f'c = 3000 PSI
CLASS A DEVELOPMENT LENGTH, Id
TOP
28" 37" 47" 56" 81" 93"
OTHER
22" 29" 36" 43" 63" 72" f'c = 3000 PSI
TOP
19" 25" 31" 37" 54" 62"
OTHER
15" 19" 24" 29" 42" 48" f'c = 4000 PSI
TOP
28" 37" 47" 56" 81" 93"
OTHER
22" 29" 36" 43" 63" 72"
TOP
17" 23" 28" 34" 49" 56"
OTHER
13" 17" 22" 26" 38" 43" f'c = 5000 PSI
Revisions Date
BID AND CONSTRUCTION 03/09/21
STRUCTURAL GENERAL NOTES
A. ACI 301-10, SPECIFICATIONS FOR STRUCTURAL CONCRETE
B. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE.
A. EXISTING FOUNDATIONS SHOWN ON DRAWINGS ARE APPROXIMATE. EXACT CONDITIONS MUST BE VERIFIED AT THE TIME OF
CONSTRUCTION
B. UNLESS OTHERWISE NOTED, NEW FOUNDATION SHALL NOT BEAR BELOW EXISTING FOUNDATIONS.
A. CONCRETE POURED AGAINST EARTH: 3"
B. FORMED CONCRETE IN CONTACT WITH EARTH: 2"
A. LAP ALL COMPRESSION SPLICES 30 BAR DIAMETERS OF THE LARGER BAR.
B. LAP ALL TENSION SPLICES IN ACCORDANCE WITH THE FOLLOWING TABLES. PROVIDE CLASS B TENSION LAP SPLICES UNLESS
OTHERWISE NOTED.
C. INCREASE TENSION OR COMPRESSION SPLICE LENGTHS BY THE FOLLOWING FACTORS. INCREASES ARE CUMULATIVE:
1) EPOXY-COATED TOP BARS: 1.3
2) EPOXY-COATED OTHER BARS: 1.5
D. TOP BARS ARE DEFINED AS HORIZONTAL BARS WITH MORE THAN 12" OF FRESH CONCRETE BELOW.
EARTHQUAKE DESIGN DATA ----------------------------------------------------------------------------- Per ASCE 7-16 COMPONENT IMPORTANCE FACTOR (ASCE 7, 13.1.3) ------------------------------------------ Ip = 1.5 RISK CATEGORY ---------------------------------------------------------------------------------------------- IV
MAPPED SPECTRAL RESPONSE ACCELERATIONS/PARAMETERS
SHORT PERIOD ------------------------------------------------------------------------------------------------ Ss = 0.117 g 1-SECOND PERIOD ------------------------------------------------------------------------------------------- S1 = 0.061 g SITE CLASS (PER GEOTECHNICAL REPORT) ------------------------------------------------------- D
DESIGN SPECTRAL RESPONSE ACCELERATONS/PARAMETERS
SHORT PERIOD ------------------------------------------------------------------------------------------------ SDS = 0.125 g 1-SECOND PERIOD ------------------------------------------------------------------------------------------- S1 = 0.098 g SEISMIC DESIGN CATEGORY ----------------------------------------------------------------------------- C
SEISMIC DESIGN DATA
UP
Tectonic Copyright 2007
CO
D
D
D
653.1
E.3
C.3
B.8
B.5
B.2
A
A.2
B
B.4
C
D
E
F
G
1 1.8 2.6 2.7 3 4
D.4
BOILER
ROOM
CONTROL
ROOM
CORRIDOR
STORAGE
CORRIDOR
STORAGE
STORAGE
ELEC.
ROOM
EMERGENCY
PARALLEL
SWITCHGEAR
NORMAL
PARALLEL
SWITCHGEAR
BOILER
ROOM
MANAGER'S
OFFICE
VESTIBULE
JANITOR
TELE/
DATA
ROOM
TOILET
FUTURE CHILLER PLANT ADDITION
(NOT IN CONTRACT)
PSG - NORMAL
P S
G C
O N
T R
O L S
H1T1
X X
FUTURE
P S
G
E M
E R
G E
N C
Y
EXISTING CHP
BREAKER
LOCKER/SHOWER
X
X
X
X
X
X X X X XX
EXISTING CHP
CONTROL CUBICLE
X X
X
X X
X
X
XXX
X
X
X
X
FUTURE
X
FUTURE
EXISTING
FUEL OIL
SYSTEM
LOCATION OF NEW
EMERGENCY
GENERATOR CUBICLE
(SEE NEW WORK)
X
X
X
X
X
IN-GRADE ELECTRICAL BOX
XR
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
(APPROX ELEVATION
784' AT WEST END AND
781' AT EAST END PER
RECORD DRAWINGS)
EX. STORM DRAIN
EX. STORM DRAIN
X
P R
ELI
M
IN
AR
Y
N O T F
O R
C O N S
TR
U C
TIO
N
C B
LH
D E
SIG
N
IN
C
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
FOR CONSTRUCTION
Project Number
Building Number
Drawing Number
CHALMERS P WYLIE ACC
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
FULLY SPRINKLERED
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
200073 /9
/2
:0
:5
P
M Z
M y D o c u m e n ts
\2
F
F H
C F
R lv ili m o n o v ic
Q
F F
.r v t
ED-101
757-20-205
SPC CPC
CONSTRUCT GENERATOR
DOCKING STATION
12/07/2020
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTIAL FIRST FLOOR AND SITE
ELECTRICAL DEMOLITION PLAN
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR AND SITE
ELECTRICAL DEMOLITION PLAN 1N
ELECTRICAL DEMO CODED NOTES
1 EXISTING 24"SQ. CONCRETE-POLYMER, IN-GRADE ELECTRICAL BOX TO BE REMOVED AND REPLACED WITH NEW AT A NEW LOCATION. REFER TO NEW PLAN FOR ADDITIONAL INFORMATION. EXISTING CONDUITS ARE STUBBED FROM PARALLELING SWITCHGEAR LOCATION TO BOX. EXISTING ROUTING SHOWN IS FOR REFERENCE ONLY. CONDUIT IS SHOWN ROUTED STRAIGHT TO BOX BUT FIELD CONDITIONS MAY VARY AND MAY IMPACT PULLING CONDITIONS SHOULD THE CONTRACTOR ELECT TO UTILIZE THE EXISTING CONDUIT FOR THE NEW GENERATOR FEEDER. CONTRACTOR IS RESPONSIBLE FOR VERIFYING EXISTING ROUTING AND PULL CONDITIONS PRIOR TO ANY ATTEMPT TO UTILIZE EXISTING CONDUIT AND SHALL BE RESPONSIBLE FOR PULL
FAILURES AND/OR DAMAGE TO CABLE DURING PULLING.
APPROXIMATE EXISTING GROUND ROD, GROUND TEST WELL, (1) #4/0 BARE COPPER GROUND WIRE TO STRUCTURAL STEEL, AND (1) #4/0 BARE COPPER COUNTERPOISE GROUND CABLE. CONTRACTOR SHALL MAINTAIN INTEGRITY OF GROUND RING AROUND BUILDING DURING CONSTRUCTION AND REPAIR ANY
INCURRED DAMAGES.
EXISTING UNDERGROUND ELECTRICAL FEEDER FOR FUTURE CONSTRUCTION TRAILER SERVICE. FEEDER IS CURRENTLY ROUTED FROM PANEL H1N1 IN EXISTING ELECTRICAL ROOM #109 TO COLUMN 'G3' VIA OPEN AIR PORTABLE POWER CABLE. EXACT ROUTING UNDERGROUND HAS NOT BEEN VERIFIED AND IS SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL REMOVE EXISTING CABLING AND PROVIDE NEW CONDUIT FROM
PANELBOARD TO EXISTING COLUMN MOUNTED PULLBOX. CONTRACTOR SHALL EXTEND/RELOCATE
UNDERGROUND PORTION OF FEEDER TO THE SOUTH, OUTSIDE OF THE EXTENT OF THE NEW PAD. VERIFY EXISTING LOCATION AND COORDINATE DESIRED NEW TERMINATION LOCATION WITH VA COR PRIOR TO CONSTRUCTION. PROVIDE NEW CABLING FROM SOURCE TO TERMINATION LOCATION. TERMINATE CONDUIT IN A NEW CONCRETE-POLYMER, IN-GRADE SITE ELECTRICAL BOX. NEW FEEDER SHALL BE 2"C - 4#1 AND 1#8EG.
SITE UTILITY GENERAL NOTES
CONTRACTOR SHALL SUBMIT SITE UTILITY VERIFICATION SURVEY TO THE VA COR FOR REVIEW. SITE UTILITY VERIFICATION SURVEY SHALL BE PERFORMED AND THE REPORT SHALL BE SUBMITTED WITHIN 30 DAYS OF THE
CONTRACTOR'S NOTICE-TO-PROCEED.
ALL SITE UTILITIES SHALL BE IDENTIFIED WITH ADDITIONAL ATTENTION GIVEN TO LOCATIONS WHERE EXISTING UTILITIES DEVIATE FROM THE CONTRACT DOCUMENTS OR WHERE EXISTING UTILITIES IMPEDE NEW CONSTRUCTION.
THE UTILITIES SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, THE FOLLOWING: NATURAL GAS, IRRIGATIONS, IRRIGATION CONTROLS, ELECTRICAL, SANITARY AND STORM SEWERS, DOMESTIC WATER, ETC.
SITE UTILITY GENERAL NOTES
S1.
S2.
S3.
S4.
S5.
S6.
S7.
S8.
ALL SITE CONDUITS SHALL BE 18"-30" BELOW GRADE AND SHALL BE RIGID STEEL (MINIMUM 1"C) UNLESS OTHERWISE NOTED. CONDUITS INSTALLED UNDER PAVED DRIVE AREAS SHALL BE ENCASED IN CONCRETE - 3"
MINIMUM COVER.
PROVIDE ALL TRENCHING, BACKFILL, SAW-CUTTING, ETC. NECESSARY TO INSTALL NEW CONDUITS. PROVIDE ALL NECESSARY BACKFILL, GRAVEL, GRASS, CONCRETE, ASPHALT, ETC. TO RESTORE AREA TO EXISTING
CONDITION.
NEW ELECTRICAL CONDUIT LINES SHALL CROSS STORM SEWERS, GAS, AND WATER LINES AT
PERPENDICULAR ANGLES AND SHALL NOT RUN ADJACENT TO THEM AT ANY TIME.
MAINTAIN 12" SEPARATION BETWEEN ELECTRICAL CONDUITS AND TELEPHONE LINES.
EXISTING UNDERGROUND UTILITY AND BRANCH CIRCUITS ARE SHOWN AT APPROXIMATE LOCATIONS FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL IDENTIFY ALL UNDERGROUND SERVICE UTILITIES BY
HAND DIGGING PRIOR TO ANY EXCAVATION.
CONTRACTOR SHALL REPAIR ANY UTILITIES DAMAGED WHILE EXCAVATING AND RESTORE SYSTEMS TO
EXISTING CONDITION.
THE CONTRACTOR SHALL NOTIFY OHIO UTILITIES PROTECTION SERVICE (PH. 1-800-362-2764) AT LEAST (48) HOURS PRIOR TO ANY EXCAVATING TO INSURE THAT PUBLIC UTILITIES WILL NOT BE DAMAGED BY CONSTRUCTION WORK. MAKE ANY ADDITIONAL NOTIFICATIONS TO OTHER UTILITIES SERVICES AS REQUIRED.
REFER TO SPECIFICATIONS FOR ANY ADDITIONAL REQUIREMENTS.
Revisions Date
Tectonic Copyright 2007
UP
EX GATE
CO
EX CONCRETE PVMT
EX CHAIN LINK FENCE
D
D
D
D
D
D
D D
D
UP
BOILER
ROOM
CONTROL
ROOM
CORRIDOR
STORAGE
CORRIDOR
STORAGE
112 STORAGE
ELEC.
ROOM
EMERGENCY
PARALLEL
SWITCHGEAR
NORMAL
PARALLEL
SWITCHGEAR
BOILER
ROOM
MANAGER'S
OFFICE
VESTIBULE
JANITOR
TELE/
DATA
ROOM
TOILET
FUTURE CHILLER
PLANT ADDITION
(NOT IN CONTRACT)
LOCKER/SHOWER
NEW GENERATOR
EXISTING
FUEL OIL
SYSTEM
EXISTING UNDERGROUND FUEL
STORAGE TANK
EXISTING UNDERGROUND FUEL
STORAGE TANK
EXISTING OXYGEN
STORAGE TANK
EXISTING 1750KW
EMERGENCY GENERATOR
653.1
E.3E.3
C.3 C.3
B.8B.8
B.5B.5
B.2
A
A.2
B
B.4
C
D
E
F
G
1 1.8 2 2.6 2.7 3 4
D.4D.4
IN-GRADE ELECTRICAL BOX
NEW
EP-101
EP-101
EP-102
PARKING
EX.
RETENTION POND
(APPROX ELEVATION
784' AT WEST END AND
781' AT EAST END PER
RECORD DRAWINGS)
EX. STORM DRAIN
EX. STORM DRAIN
EX. STORM DRAIN
E X
IS
T
IN
G
U N
D E
R G
R O
U N
D E
L E
C T
R
IC
A L
(F E
E D
E R
S T
O A
N D
F R
O M
M A
IN
B
U
IL
D
IN
G A
N D
E X
IS
T
IN
G
G E
N E
R A
T O
R
CORRIDOR
ELEC.
ROOM
H1NAH1N1H1EBH1EA H1EA H1E1
H1CA
H1C1
H1TC1
H1TE1
UPS-1
H1TS1
H1SAH1S1
CPDP1CPDP2
H1TN1
X
X X
X X XX X X
X
X
X
X
X
X
FUTURE FUTURE
D
2.6 2.7 3
D.4
LIGHTING
CONTROL
X
3.1
E.3
F
G
3 4
3' - 8"
12' - 0"
NEW
GENERATOR
NEW
NGRFUTURE
CONTROLS
CABINETS
X
X
X
GENERATOR INTAKE
HOOD OVERHANG
3' - 8"
/3
/3
/8
/4
/3
/4
/1
/3
/3
3' - 7 3/4"
4' - 0"
0' - 6"
1' - 1"
1' - 7"
1' - 2"
GENERATOR
FEEDER/CONTROLS
STUB-UP LOCATION
ACCESSORY
POWER STUB-
UP LOCATIONS
FUTURE
CHILLER PLANT ADDITION
(NOT IN CONTRACT)
24' - 3 1/8"
T Y
P
TYP.
S.O.G.
OUTLINE OF PERIMETER
TRENCH FOOTING (TYP.)
EDGE OF NEW GENERATOR
SUPPORT PAD 2
S-12
2' - 4 3/8"
7' - 3 3/4"
3' - 7 3/4"
1' - 2"
6"
S.O.G.
6"
CJ CJ
CJ CJ
CJ CJ
C J
C J
C J
C J
S.O.G.
6"
/3
(SAWCUT - TYP)
1' - 8"1' - 8"
EP-501
EP-501
SECTION 1 SECTION 2
X
X
X
PULLBOX
DC PANEL
BATTERY RACK
TYP.
TYP.
H1S2
H1TS2
H1EC(ABOVE)
AA
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
Project Number
Building Number
Drawing Number
CHALMERS P WYLIE VA
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
20007
100% CONSTRUCTION
DOCUMENTS
/9
/2
:0
:3
P
M Z
M y D o c u m e n ts
\2
F
F H
C F
R lv ili m o n o v ic
Q
F F
.r v t
EP-101
757-20-205
SPC CPC
CONSTRUCT GENERATOR
DOCKING STATION
12/07/2020
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTIAL SITE ELECTRICAL AND GENERATOR
LAYOUT PLANS
0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'
1/16" = 1'-0"
PARTIAL FIRST FLOOR
AND SITE ELECTRICAL PLAN 1N
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
ENLARGED ELECTRICAL ROOM 109 PLAN 2
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL ENLARGED
SITE GENERATOR LAYOUT PLAN 3N
N
ELECTRICAL CODED NOTES
1 NEW GENERATOR CONCRETE SUPPORT PAD. FINISHED ELEVATION = 795'-0".
DIMENSIONS INDICATED ARE PER GENERATOR SHOP DRAWINGS AS RECEIVED FROM OHIOCAT IN SEPTEMBER 2020. CONTRACTOR SHALL OBTAIN THE LATEST, APPROVED GENERATOR SHOP DRAWINGS AND SHALL VERIFY DIMENSIONS WITH GENERATOR AS CONSTRUCTED PRIOR TO CONSTRUCTION OF NEW CONCRETE SUPPORT PAD. CONTACT THE VA COR SHOULD ANY DISCREPANCY ARISE BETWEEN DOCUMENTS AND GENERATOR AS-
BUILD CONDITIONS.
EXISTING BOILER PLANT BUILDING FOUNDATION AS INDICATED ON CONSTRUCTION DOCUMENTS RECORD DRAWINGS. CONTRACTOR SHALL VERIFY AS-BUILT FOUNDATIONS AND NOTIFY VA COR OF ANY DISCREPANCY PRIOR TO INSTALLATION OF NEW GENERATOR SUPPORT PAD. FOUNDATION OF PAD MUST BE ADJUSTED TO ACCOMMODATE EXISTING BUILDING FOUNDATIONS. REFER TO GENERATOR PAD DETAIL ON ELECTRICAL
DETAILS SHEET FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.
PROVIDE PROTECTIVE STEEL BOLLARD, TYPICAL. COORDINATE LOCATIONS WITH UNDERGROUND UTILITIES.
REFER TO PROTECTIVE STEEL BOLLARD DETAIL FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.
APPROXIMATE LOCATION OF EXISTING GENERATOR/PARALLELING EQUIPMENT REMOTE ALARM PANELS.
INSTALL NEW GENERATOR ALARM PANEL AT SAME LOCATION. COORDINATE WITH VA COR PRIOR TO ROUGH- IN. EXTEND POWER FROM LOCAL ALARM PANELS TO NEW ALARM PANEL AND CONNECT COMPLETE VIA 3/4"C -
2#12 AND 1#12 EG.
PARKING SPACES WITHIN A 50' RADIUS OF THE NEW GENERATOR SHALL BE RESTRIPED TO INDICATE NO
PARKING. COORDINATE WORK WITH THE VA COR PRIOR TO RESTRIPING.
PROVIDE WET LOCATION, LED, REMOTE HEAD, EMERGENCY LIGHTING FIXTURE FOR ABOVE THE EXTERIOR SIDE OF THE GENERATOR. LIGHTING FIXTURE SHALL HAVE TWO LED HEADS, WHITE IN COLOR. FLAME RESISTANT, IMPACT RESISTANT WITH A UNIVERSAL MOUNTING PLATE. COORDINATE MOUNTING HEIGHT IN THE FIELD PRIOR TO ROUGH-IN AND CONNECT COMPLETE TO NEW LIGHTING CIRCUIT INSIDE GENERATOR
VESTIBULE VIA 3/4"C - 2#12 AND 1#12EG.
SITE UTILITY GENERAL NOTES
S1.
S2.
S3.
S4.
S5.
S6.
S7.
S8.
ALL SITE CONDUITS SHALL BE 18"-30" BELOW GRADE AND SHALL BE RIGID STEEL (MINIMUM 1"C) UNLESS OTHERWISE NOTED. CONDUITS INSTALLED UNDER PAVED DRIVE AREAS SHALL BE ENCASED IN CONCRETE -
3" MINIMUM COVER.
PROVIDE ALL TRENCHING, BACKFILL, SAW-CUTTING, ETC. NECESSARY TO INSTALL NEW CONDUITS.
PROVIDE ALL NECESSARY BACKFILL, GRAVEL, GRASS, CONCRETE, ASPHALT, ETC. TO RESTORE AREA TO
EXISTING CONDITION.
NEW ELECTRICAL CONDUIT LINES SHALL CROSS STORM SEWERS, GAS, AND WATER LINES AT
PERPENDICULAR ANGLES AND SHALL NOT RUN ADJACENT TO THEM AT ANY TIME.
MAINTAIN 12" SEPARATION BETWEEN ELECTRICAL CONDUITS AND TELEPHONE LINES.
EXISTING UNDERGROUND UTILITY AND BRANCH CIRCUITS ARE SHOWN AT APPROXIMATE LOCATIONS FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL IDENTIFY ALL UNDERGROUND SERVICE UTILITIES BY
HAND DIGGING PRIOR TO ANY EXCAVATION.
CONTRACTOR SHALL REPAIR ANY UTILITIES DAMAGED WHILE EXCAVATING AND RESTORE SYSTEMS TO
EXISTING CONDITION.
THE CONTRACTOR SHALL NOTIFY OHIO UTILITIES PROTECTION SERVICE (PH. 1-800-362-2764) AT LEAST (48) HOURS PRIOR TO ANY EXCAVATING TO INSURE THAT PUBLIC UTILITIES WILL NOT BE DAMAGED BY CONSTRUCTION WORK. MAKE ANY ADDITIONAL NOTIFICATIONS TO OTHER UTILITIES SERVICES AS
REQUIRED.
REFER TO SPECIFICATIONS FOR ANY ADDITIONAL REQUIREMENTS.
Revisions Date
BID AND CONSTRUCTION 03/09/21
J
653.1
E.3
D
E
F
G
1 1.8 2 2.6 2.7 3 4
D.4
CORRIDOR
STORAGE
STORAGE
ELEC.
ROOM
EMERGENCY
PARALLEL
SWITCHGEAR
NORMAL
PARALLEL
SWITCHGEAR
FUTURE CHILLER PLANT ADDITION
(NOT IN CONTRACT)
PSG - NORMAL
P S
G C
O N
T R
O L S
H1T1
X
X
FUTURE
GENERATOR
CUBICLE LOCATIONS
P S
G
E M
E R
G E
N C
Y
EXISTING CHP
BREAKER
X
X
X
X
X
X X X X XX
X
X
X
X
X
X
X
XX
X
XX
X
X FUTURE
X
NEW GENERATOR
NEW
NGRFUTURE
NEW EMERGENCY
GENERATOR CUBICLE
IN-GRADE
ELECTRICAL BOX
NEW
X
X
X
EP-101
GENERATOR INTAKE
HOOD OVERHANG
X
X
X
X
EXISTING CHP
GENERATOR
CONTROL CUBICLE
EP-501
X
BATTERY
RACK
X
DC
PANELBOARD
X
PULLBOX
H1S2 - 10
X
FUTURE
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
Project Number
Building Number
Drawing Number
CHALMERS P WYLIE VA
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
20007
100% CONSTRUCTION
DOCUMENTS
/9
/2
:0
:0
P
M Z
M y D o c u m e n ts
\2
F
F H
C F
R lv ili m o n o v ic
Q
F F
.r v t
EP-102
757-20-205
SCP CPC
CONSTRUCT GENERATOR
DOCKING STATION
12/07/2020
420 N. JAMES ROAD, COLUMBUS, OH 43219
PARTIAL SITE ELECTRICAL PLAN
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL FIRST FLOOR AND SITE
ENLARGED ELECTRICAL PLAN 1N
ELECTRICAL GENERAL NOTES
CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, STUB-UP LOCATIONS, AND
CONNECTION REQUIREMENTS WITH EQUIPMENT VENDOR(S) PRIOR TO ROUGH-IN.
A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTI-
WIRE BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.
PROVIDE #10 SIZE CONDUCTORS FOR ALL 20A-120V CIRCUITS WITH DISTANCE LENGTHS THAT EXCEED 100 FT.
1.
2.
3.
ELECTRICAL CODED NOTES
1 NEW 24"SQ. CONCRETE-POLYMER, IN-GRADE ELECTRICAL BOX SHALL BE INSTALLED APPROXIMATELY AT LOCATION INDICATED. BOX SHALL BE CLEAR OF THE EASTERNMOST WALL OF THE PROPOSED CHILLER PLANT ADDITION TO ACCOMMODATE A SECOND GENERATOR PAD. EXTEND EXISTING 4" CONDUITS THAT STUB FROM PARALLELING SWITCHGEAR ROOM TO NEW BOX, PROVIDE NEW PULLWIRE AND CAP. EXISTING CONDUIT BURIAL DEPTH IS UNKNOWN. CONTRACTOR SHALL COORDINATE NEW DUCT BANK BURIAL WITH EXISTING
CONDUITS.
NEW EMERGENCY GENERATOR (2MVA, 13.2kV-3∅-3W, DIESEL) SHALL BE FURNISHED BY OWNER AND
INSTALLED BY CONTRACTOR. PROVIDE NEW CONCRETE MOUNTING PAD PER DETAILS, INSTALL NEW
GENERATOR AND CONNECT COMPLETE TO EXISTING PARALLELING SWITCHGEAR AND CONTROLS.
CONTRACTOR SHALL OBTAIN GENERATOR PURCHASE INFORMATION FROM THE VA COR AND RETAIN GENERATOR AND PARALLELING EQUIPMENT MANUFACTURERS AS NECESSARY TO INSTALL, CONNECT
COMPLETE, PROGRAM, AND TEST GENERATOR PER DRAWINGS AND SPECIFICATIONS.
EXISTING COMBINED HEATING AND POWER (CHP) GENERATOR BREAKER SECTION IN EXISTING NORMAL PARALLELING SWITCHGEAR (PSG-N). CONTRACTOR SHALL REMOVE CIRCUIT BREAKER ASSEMBLY FROM EXISTING SECTION FOR USE IN NEW EMERGENCY GENERATOR SECTION. MAINTAIN EXISTING RELAYS AND
ACCESSORIES IN CHP GENERATOR SECTION FOR FUTURE USE.
PROVIDE NEW EMERGENCY GENERATOR SECTION AND CONNECT COMPLETE TO EXISTING EMERGENCY PARALLELING SWITCHGEAR. NEW SECTION SHALL MATCH EXISTING GENERATOR SECTION (DRAW-OUT, POWER CIRCUIT BREAKER WITH ELECTRONIC POWER METER). EXISTING SWITCHGEAR IS RUSSELECTRIC.
PROVIDE NEW RELAYS, ACCESSORIES AND PROGRAMMING AS REQUIRED TO CONNECT NEW EMERGENCY GENERATOR COMPLETE. REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION AND
WORK REQUIREMENTS.
PROVIDE NEW NEUTRAL GROUND RESISTOR (NGR) IN A OUTDOOR, NEMA 3R ENCLOSURE. PAD MOUNT NGR ADJACENT TO GENERATOR ENCLOSURE AND CONNECT COMPLETE TO CONCRETE-ENCASED GROUNDING
ELECTRODE (GENERATOR SUPPORT PAD) AND GENERATOR'S NEUTRAL CONNECTION. NGR SHALL:
• BE 13.2KV RATED,
• BE 76.2 OHMS RESISTANCE,
• BE 100A CURRENT RATING,
• HAVE 15KV (200:5 RATIO) CURRENT TRANSFORMER,
• HAVE MAXIMUM ON TIME OF 10 SECONDS,
• HAVE MAXIMUM TEMPERATURE RISE OF 760 DEG C.
• HAVE AN ENCLOSURE HEATER (APPROX. 100W) FOR CONDENSATION MITIGATION
• BASIS OF DESIGN OR EQUAL: ASCO POWER TECHNOLOGIES
CONTRACTOR SHALL RETAIN RUSSELECTRIC FOR PROGRAMMING OF THE NEW PARALLELING SWITCHGEAR
SECTION AND REPROGRAMMING OF THE EXISTING PARALLELING SWITCHGEAR TO CONNECT NEW
EMERGENCY GENERATOR COMPLETE AND PARALLEL/LOAD SHARE WITH EXISTING 1750KW GENERATOR.
ROUTE POWER AND CONTROL CONDUITS FROM CEILING SPACE OF EXISTING BOILER PLANT, DOWN EXTERIOR WALL TO BELOW CONCRETE SLAB AND OVER TO STUB-UP LOCATION WITHIN GENERATOR ENCLOSURE.
COORDINATE EXACT STUB-UP LOCATION WITH GENERATOR MANUFACTURER PRIOR TO ROUGH-IN. SLEEVE CONDUITS THROUGH NEW SLAB FOOTERS AS REQUIRED. CONDUITS AND BOXES SHALL BE MOUNTED AS HIGH AS POSSIBLE IN BOILER PLANT CEILING SPACE TO ALLOW FOR FUTURE FLOOR MOUNTED EQUIPMENT TO BE INSTALLED BELOW AND FUTURE CONDUITS TO BE ROUTED DOWN TO EQUIPMENT. PROVIDE FLEXIBLE INNER DUCT IN CONTROLS CONDUITS TO SEPARATE CONTROLS BY TERMINATION LOCATION AND PRESERVE
SPACE FOR FUTURE PULLS. PROVIDE PULL WIRE IN SPARE INNER DUCT(S)
FUTURE CONDUIT AND WIRING AS INDICATED ON GENERATOR CONTROL DIAGRAM FOR FUTURE CONNECTION TO FUEL OIL TRANSFER SYSTEM. PROVIDE 2" CONDUIT PENETRATION THROUGH WALL WITH PULLWIRE AND SEAL FOR FUTURE EXTENSION. NEW GENERATOR SHALL BE CONNECTED TO FUEL OIL TRANSFER SYSTEM
UNDER A FUTURE PROJECT.
PROVIDE FEEDERS FROM EXISTING EQUIPMENT AND LIFE SAFETY PANELBOARDS TO NEW PANELBOARD AND TRANSFORMER, RESPECTIVELY, THAT ARE PROVIDED WITH GENERATOR ENCLOSURE. REFER TO ONE-LINE DIAGRAM FOR FEEDER SIZING. COORDINATE STUB UP LOCATION WITH GENERATOR MANUFACTURER.
ROUTE CONDUIT TO NEW GENERATOR ANNUNCIATOR PANEL AND CONNECT COMPLETE. REFER TO
GENERATOR CONTROLS DIAGRAM FOR SIZING AND CONDUCTORS. REFER TO DRAWING EP-101 FOR
PROPOSED ANNUNCIATOR LOCATION.
PROVIDE 12"(L) x 12"(W) x 24"(H) (MINIMUM) NEMA 4X RATED PULLBOX FOR GENERATOR POWER IN LOCATION INDICATED ON PLANS. PULLBOX IS SIZED BASED ON A MEDIUM VOLTAGE CABLE WITH A 12" MINIMUM BENDING RADIUS. THE CONTRACTOR IS RESPONSIBLE TO VERIFY THE BENDING RADIUS OF THE APPROVED MEDIUM VOLTAGE CONDUCTOR PRIOR TO CONSTRUCTION AND MODIFY PULLBOX SIZE AS REQUIRED PER NEC.
COORDINATE THE EXACT CONDUIT ROUTE PRIOR TO INSTALLATION.
PROVIDE 28"(L) x 12"(W) x 28"(H) (MINIMUM) NEMA 4X RATED PULLBOX FOR GENERATOR CONTROL WIRING IN LOCATION INDICATED ON PLANS. PROVIDE FLEXIBLE INNER DUCT IN CONTROLS CONDUITS TO SEPARATE CONTROLS BY TERMINATION LOCATION AND PRESERVE SPACE FOR FUTURE PULLS. PROVIDE PULL WIRE IN
SPARE INNER DUCT(S). COORDINATE THE EXACT CONDUIT ROUTE PRIOR TO INSTALLATION.
PROVIDE 9"(L) x 4"(W) x 9"(H) (MINIMUM) NEMA 4X RATED PULLBOX FOR PANELBOARD FEEDERS IN LOCATION
INDICATED ON PLANS. COORDINATE THE EXACT CONDUIT ROUTE PRIOR TO INSTALLATION.
Revisions Date
BID AND CONSTRUCTION 03/09/21
WALL SECTION
FLOOR SECTION
WHERE CONDUIT, CABLES AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN TESTED IN ACCORDANCE WITH U.L.
1479 OR ASTM E814.
GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING
MATERIALS AND U.L. SYSTEMS.
FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT
CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.
THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION
RESULTING FROM HIS WORK.
CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ENGINEER, INCLUDING U.L. RATED SYSTEM
NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.
SLEEVES USED FOR CABLE RISERS THROUGH FLOORS OR WALLS SHALL BE INSTALLED PER THE ABOVE FLOOR OR WALL SECTIONS. IN ADDITION, FIRESTOP MATERIAL SHALL BE PROVIDED INSIDE SLEEVE AFTER
CABLES ARE COMPLETELY INSTALLED.
PIPE SLEEVE
FURNISH AND INSTALL FIRESTOP
MATERIALS IN ACCORDANCE WITH
APPROPRIATE U.L. SYSTEMS TO
MAINTAIN FIRE RESISTANCE RATING
PENETRATING CONDUIT, ETC.
FLOOR SLAB; SEE
ARCHITECTURAL DRAWINGS
FOR FLOOR CONSTRUCTION
AND FIRE RATING
DAMMING MATERIAL
(PER U.L. TESTED SYSTEM DESIGN)
SEE ARCHITECTURAL DRAWINGS FOR
WALL CONSTRUCTION AND FIRE RATING
PENETRATING CONDUIT, ETC.
FURNISH AND INSTALL FIRESTOP MATERIALS IN
ACCORDANCE WITH APPROPRIATE U.L. SYSTEMS
TO MAINTAIN FIRE RESISTANCE RATING
SEAL JOINT BETWEEN SLEEVE AND FLOOR
SLAB WITH MIN. 1/2" BEAD FIRESTOP CAULK
PIPE SLEEVE (SLEEVE TO EXTEND 2" ABOVE
FLOOR IN MECHANICAL EQUIPMENT
ROOMS.)
1.
2.
3.
4.
5.
6.
GENERAL NOTES
NOT TO SCALE
FIRESTOPPING FOR PENETRATIONS DETAIL
3"
CLR.
1'-8"
(MIN. TYP.)
4'-0" +/-
FROM EXISTING
COLUMN LINE '3'
M
IN
F
R O
M T
O P
O F
G R
A D
E
C L R
3"
CLR.
1'-8"
(MIN. TYP.)
REINF. - SEE SECTION 2
S-12
EXISTING
WALL
6" THICK
SLAB ON GRADE
1/2" FLEXIBLE
JOINT FILLER
12" COMPACTED
FREE DRAINING
GRANULAR FILL
EXISTING
GRADE BEAM
S-12
SECTION 1 SECTION 2
NOT TO SCALE
EXISTING WALL
REINFORCEMENT
3'-0" +/-
APPROXIMATE
OUTLINE OF EX.
PILECAP BEYOND
HOLD 6"
CLEAR
GENERATOR
C L R
. REINF. DETAIL -
SEE STRUCTURAL LEGEND
3" CLR
COMPACTED SUB BASE
#5@12"
4' 2'
EXISTING S.O.G.
1'-4" +/-
GENERATOR - CONTRACTOR IS
RESPONSIBLE FOR UNLOADING
AND ANCHORING TO PAD
3 - #5
CONT.
6" Ø PIPE BOLLARD.
PAINT OWNER APPROVED COLOR
FILL WITH CONCRETE
AND CONE TOP
POURED CONCRETE BASE.
DO NOT FORM BELOW GRADE.
/2
GRADE
NOT TO SCALE
(4) CONCRETE BRICKS 2"x8"x16"
CONDUIT(S) WITH BELL ENDS
(TYP). SIZE, QUANTITY AND
WIRING AS INDICATED ON
PLANS
CLEAN 3/4" CRUSHED ROCK
GRADE,FEATHER, AND TAMPED
BACKFILL TO CREATE FLUSH
INSTALLATION AND POSITIVE
DRAINAGE AWAY FROM BOX
V A
R
IE
S
PULLBOX (SEE PLANS)
12"
NOT TO SCALE NOT TO SCALE
CONDUIT SCHEDULE (X-X)
TAG SIZE FROM TO
FOR
' M
IN
IM
U M
FINISHED PAD ELEVATION
RIGID STEEL
CONDUIT
(TYPICAL)
PROVIDE DETECTABLE
UNDERGROUND TAPE.
TAPE SHALL READ
"CAUTION BURIED
ELECTRICAL LINE",
6" WIDE.
PREMIUM FILL
UNDER CONCRETE
SLAB ON GRADE
7.5" 6"
4 532
7.5"7.5"
CONCRETE
GENERATOR
SUPPORT PAD
6" 7.5"
PSG-E
NEW GEN. CUBICLE
GENERATOR
MAIN
1-1/2" H1SA
GEN. ACC.
STUB UP
4"
PSG CONTROLS
GENERATOR
ENCLOSURE
4"
INTERIOR OF
BOILER PLANT
GENERATOR
ENCLOSURE
4"
GENERATOR
OUTPUT
PRIMARY GEN.
ACC. XFMR FEED
FUEL CONTROLS *
GENERATOR
CONTROLS
1-1/2" H1EA
GEN. ACC.
STUB UP
480V GEN. ACC.
PANEL FEED
* - CONDUIT PROVIDED FOR FUTURE FUEL OIL TRANSFER SYSTEM.
PROVIDE (4) 1.5" INNER DUCT WITH (1) PULLWIRE IN EACH. UP TO (2)
INNER DUCTS MAY BE USED FOR GENERATOR CONTROLS OVERFLOW
WIRING AS NECESSARY. MAINTAIN (2) SPARE INNER DUCT FOR
FUTURE USE.
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
VA FORM 08 - 6231
F
E
D
C
B
A
987654321 10
F
E
D
C
B
A
987654321 10
Project Number
Building Number
Drawing Number
CHALMERS P WYLIE VA
Project Title
Location
Issued Date Checked Drawn
Drawing Title
Approved: Project Director
Phase
Office of Construction and Facilities Management
STAMPARCHITECT / ENGINEER OF RECORD
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
CONSULTANT
20007
100% CONSTRUCTION
DOCUMENTS
/9
/2
:0
:5
P
M Z
M y D o c u m e n ts
\2
F
F H
C F
R lv ili m o n o v ic
Q
F F
.r v t
EP-501
757-20-205
SPC CPC
CONSTRUCT GENERATOR
DOCKING STATION
12/07/2020
420 N. JAMES ROAD, COLUMBUS, OH 43219
ELECTRICAL DETAILS AND PANELBOARD
SCHEDULES
FIRE STOPPING DETAIL 1 GENERATOR PAD SECTION DETAIL 2
PROTECTIVE STEEL BOLLARD DETAIL 3 UNDERGROUND CONCRETE PULLBOX 4
GENERATOR DUCT BANK DETAIL 5
Total New Demand Amps: 35 A
Total New Amps: 35 A 35 A 35 A
Total New Load: 9.7 kVA 9.7 kVA 9.7 kVA
41 SPARE 20 A 1 0.0 9.7 42
39 SPARE 20 A 1 0.0 9.7 40
37 SPARE 20 A 1 0.0 9.7
3 60 A H1EC
35 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 36
33 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 34
31 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 32
29 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 30
27 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 28
25 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 26
23 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 24
21 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 22
19 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 20
17 SPARE 20 A 1 0.0 0.0 18
15 SPARE 20 A 1 0.0 0.0 16
13 SPARE 20 A 1 0.0 0.0
3 15 A
EXISTING DA-1
PUMP #3
11 SPARE 20 A 1 0.0 0.0 12
9 SPARE 20 A 1 0.0 0.0 10
7 SPARE 20 A 1 0.0 0.0
3 15 A
EXISTING DA-1
PUMP #2
5 0.0 0.0 6
3 0.0 0.0 4
ROP-1 15 A 3
0.0 0.0
3 15 A
EXISTING DA-1
PUMP #1
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: EX PANEL A.I.C Rating: 65,000
Mounting: Surface Main: MLO
Location: ELEC. ROOM 109 OCP: 400 A
H1EB-480/277 Wye-3Φ-4W
Total New Demand Amps: 35 A
Total New Amps: 35 A 35 A 35 A
Total New Load: 9.7 kVA 9.7 kVA 9.7 kVA
11 3.0 0.0 12
9 3.0 0.0 10
ENCLOSURE
SPACE HEATER #1
20 A 3
3.0 0.0
3 60 A SPARE
5 3.3 3.3 6
3 3.3 3.3 4
ENCLOSURE
SPACE HEATER #1
20 A 3
3.3 3.3
3 20 A
GEN. JACKET
WATER HEATER
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: PROVIDED WITH GEN. A.I.C Rating: 65,000
Mounting: Surface Main: MAIN LUG ONLY
Location: OCP: 100 A
H1EC-480/277 Wye-3Φ-4W
Total New Demand Amps: 4 A
Total New Amps: 5 A 5 A 5 A
Total New Load: 1.3 kVA 1.5 kVA 1.4 kVA
29 0.0 1.4 30
27 0.0 1.5 28
EX. XFMR H1S1 30 A 3
0.0 1.3
3 60 A H1TSB
23 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 24
21 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 22
19 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 20
17 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 18
15 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 16
13 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 14
11 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 12
9 SPARE 20 A 1 0.0 0.0 10
7 SPARE 20 A 1 0.0 0.0
2 25 A
EX. BATTERY
CHARGER #2
5 SPARE 20 A 1 0.0 0.0 6
3 EX. LIGHTING 20 A 1 0.0 0.0
2 25 A
EX. BATTERY
CHARGER #1
1 EX. LIGHTING 20 A 1 0.0 0.0 1 20 A EX. LIGHTING 2
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: EX PANEL A.I.C Rating: 65,000
Mounting: Surface Main: MAIN LUG ONLY
Location: ELEC. ROOM 109 OCP: 100 A
H1SA-480/277 Wye-3Φ-4W
Total New Demand Amps: 10 A
Total New Amps: 11 A 12 A 11 A
Total New Load: 1.3 kVA 1.5 kVA 1.4 kVA
17 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 18
15 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 16
13 GEN. BATT. CHRGR 20 A 1 0.5 0.0 1 20 A SPARE 14
11 SPARE 20 A 1 0.0 0.0 1 20 A SPARE 12
9 SPARE 20 A 1 0.0 0.1 1 20 A NGR HTR 10
7 GEN. LOUVERS 20 A 1 0.4 0.4 1 20 A GEN. RECS 8
5 OTHER 20 A 1 0.4 1.0 6
3 GEN. RECS 20 A 1 0.4 1.0
2 20 A GEN. SPACE HTR
1 GEN. E. LTG 20 A 1 0.0 0.1 1 20 A GEN. LTG 2
CKT Circuit Description Trip Poles
A
(KVA)
B
(KVA)
C
(KVA)
Poles Trip Circuit Description CKT
Comments: PROVIDED WITH GEN A.I.C Rating: 10,000
Mounting: Surface Main: MCB
Location: OCP: 100 A
H1S2-120/208 Wye-3Φ-4W
# ONE-LINE CODED NOTES
1 REMOVE (3) EXISTING 20A-1P CIRCUIT BREAKERS AND PROVIDE (1) NEW 60A-3P CIRCUIT BREAKER IN EXISTING
LIFE SAFETY PANEL AND CONNECT COMPLETE TO DISCONNECT ON THE PRIMARY SIDE OF THE
TRANSFORMER PROVIDED WITH GENERATOR.
REMOVE (3) EXISTING 20A-1P CIRCUIT BREAKERS AND PROVIDE (1) NEW 60A-3P CIRCUIT BREAKER IN EXISTING ESSENTIAL EQUIPMENT PANEL. CONNECT COMPLETE TO NEW PANELBOARD PROVIDED WITH GENERATOR.
PANELBOARDS ARE PROVIDED WITH GENERATOR ENCLOSURE. CONNECTED LOADS ARE PRE-WIRED.