RFI JCI 002 HVAC_Response.pdf
PDF 1 MB Posted
- Solicitation number
- 36C25020B0070
About this file
This document contains a Request for Information (RFI) and related federal contract opportunity notice. The RFI seeks clarification on mechanical drawings for a project to construct a third floor on Building 2 and renovate the first floor at the Cincinnati VA Medical Center. Questions address issues such as economizer relief damper location, static pressure specifications, motor sizing, and equipment details. Responses provide clarifications and state that RFI answers will be by amendment.
The related federal contract opportunity is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses to construct the third floor and renovate the first floor. Offerors must be verified in VetBiz.gov and SAM.gov, with experience modification rates below 1.0 and no more than three serious or one repeat/willful OSHA/EPA violations in three years. The project value is between $5-10 million under NAICS 236220. The solicitation will be released on beta.SAM.gov on or around January 18, 2021. The work duration is 730 days from notice to proceed. Bonds will be required.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI - 2.A202-A.pdf | ||
| 36C25020B0070 0005.docx | DOCX document | |
| 539-333 ADDENDUM_1-2021.0322.pdf | ||
| Sole Source Justification - Corbin Russwin Locksets.pdf | ||
| Sole Source Justification - Johnson Controls PACS.pdf | ||
| RFI JCI 001 HVAC_Response.pdf | ||
| 36C25020B0070 0004.docx | DOCX document | |
| Sole Source Justification - Avigilon CCTV.pdf | ||
| Sole Source Justification - Honeywell Fire Alarm.pdf | ||
| Sole Source Justification - Valcom Overhead Paging System.pdf | ||
| RFI - Roofing.pdf | ||
| 36C25020B0070 0003.docx | DOCX document | |
| RFI - Repair Concrete Deck.pdf | ||
| 36C25020B0070 0002.docx | DOCX document | |
| Pre-Bid Site Visit Sign-In Sheet (3-2-21).pdf | ||
| 36C25020B0070 0001.docx | DOCX document | |
| RFI 1 Page 2.pdf | ||
| RFI 1.pdf | ||
| Solicitation And Attachments.zip | ZIP file |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQUEST FOR INFORMATION (RFI)
36C25020B0070
PROJECT NUMBER: 539-333 Please ensure that before submitting questions or requests for clarification that you thoroughly read the solicitation, specifications, drawings and other pertinent documents. When submitting questions on this project the Government requires contractors to specifically identify the specification and/or solicitation section(s) or drawing number(s) in reference to the question or request for clarification submitted. No question or request for clarification will be answered by the Government unless the above requirements are met. Failure to comply may prevent the Government from responding in a timely manner.
PROJECT TITLE: (Const) Construct 3rd Floor Bldg. 2 and Renovate 1st Floor
PROJECT LOCATION:
Department of Veterans Affairs Cincinnati VAMC 3200 Vine St.
Cincinnati, OH 45220
SUBMITTED BY: CITY/STATE:
PHONE:
TO:
Yvonne Demorest, Contract Specialist Department of Veterans Affairs NCO10 West Contracting Office 2780 Airport Dr., Suite 340 Columbus, OH 43219 Yvonne.demorest@va.gov
RFI NO.: 001 DATE: 3-9-21
SPEC/DWG. REFERENCE(s):HVAC Mechanical Drawing M601
REPLY NEEDED BY:
Question:
1) 2-AHU5 - Economizer relief air appears to open into the vestibule with no additional opening shown on the drawing to relieve to the outside completely. Where should that damper be located?
2) 2-AHU5 - Supply and Return static pressure shown of 4.9" and 1.9" on the schedule, is this the external static pressure or total static pressure? It doesn't seem to add up with all of the internal pressure drops as well as opening pressure drops.
3) 2-AHU5 - For the fan motors, Max BHP is that 2@8.8 = 17.6 total BHP at 4.9" TSP? More referring to the above, we need the external pressure drops to account for the proper motor sizing.
4) 2-AHU5 - For the Nom 2@11hp, there are no nominal horsepower motors at 11. 10, 15, 20 and so on, but not 11. What is this value referring to?
5) 2-AHU5 - Backdraft dampers are referenced but not shown on the drawings
6) 2-AHU5 - Overall unit length of 533" shown, is this to line up with existing openings, or is a shorter unit acceptable?
mailto:Yvonne.demorest@va.gov wjsamson Text Box Responses:
1) Motorized Damper shall be located at unit relief opening. Louvers and gravity backdraft dampers shall be provided in vestibule to relieve air to outside.
2) Total Static Pressure. External static pressures are listed on the Air Handling Unit Schedule.
3) See item #2.
4) The Basis Of Design Unit Selection has 11 HP fans.
5) Backdraft dampers are required.
6) A shorter unit is acceptable as long as specification requirements are met.
COPY TO: ATTACHMENTS:
DATE: REPLY FROM:
REPLY:
RFIs will be answered by amendment(s).
INFORMATION NEEDED: