36C25020B0030-007.pdf
PDF Posted
- Solicitation number
- 36C25020B0030
About this file
This pre-solicitation notice provides an overview for a new MRI site prep project at the Dayton VA Medical Center. The contractor shall prepare the site for a new building to house MRI equipment, completing all work within 365 calendar days of receiving the notice to proceed. The solicitation documents will be posted on March 20, 2020, with proposals due approximately 30 days later. This $2-5 million project designated under NAICS code 236220 has a 100% set-aside for service-disabled veteran-owned small businesses. Offerors must register on SAM.gov, VetBiz.gov, and other sites and ensure their registrations are accurate and active by the proposal due date. The solicitation will require bid, payment and performance bonds. A mandatory site visit will be scheduled. Amendments will be posted to FBO.gov and offerors must check for updates. Questions may be emailed by the deadline.
36C25020B0030 Project Drawings (Part 4 of 4).pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25020B0030-0002001.docx | DOCX document | |
| 36C25020B0030-0001000.docx | DOCX document | |
| 36C25020B0030-008.pdf | ||
| 36C25020B0030-004.pdf | ||
| 36C25020B0030-006.pdf | ||
| 36C25020B0030-005.pdf | ||
| 36C25020B0030-001.docx | DOCX document | |
| 36C25020B0030-002.pdf | ||
| 36C25020B0030-003.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TYP. @
SCREEN WALL
SIM.
R
Q.3
Q
P.8
P.5
O.8
O.7 O.7
6.5 6.86.25.24.5
P.81
9.7
9.7
8.8
8.8
7.9
7.9
6.4
6.4
6.9
6.9
P.9
Q.4
7.3
7.3
8'-3" 20'-3" 22'-3" 28'-8"
'-6
'-4
MFC-1
MFC-2
MFC-1
MFC-2
MFC-2
MFC-1
MFC-1
MFC-2
W
X3
W18X40W18X35W18X40
W18X40W18X35W18X40W18X40 W
X3
K4
KS
P4
KS
P4
KS
P4
KS
P1
KS
P1
KS
P1
KS
P2
KS
P3
KS
P3
KS
P3
(5 EQUAL SPACES) (4 EQUAL SPACES) (5 EQUAL SPACES)
6'-5 3/4" ±
2'-1 1/4" ±
6'-1 3/4" ±
1'-3 1/8" ±
14'-0" 26'-4" 8'-7" ± 7'-4 7/8" ±
'-3
9'
-9
'-2
'-1 0"
'-0
1' -2
/8
J/BRG. = (+15'-10 3/4")
S-5.1
S-5.1
S-5.1
(E ) W
(E) W21
(E) W14
(E ) W
RTU-1
2800#
CU-1
500# CHILLER
4300#
ROOF DRAINS,
SEE ARCH.
W10X22
W
X1
1/ 2"
W 8X
K1
2.
5K
K1
K1
K1
K1
(E ) W
(E) W10
(E ) W
(E ) W
(E) W14(E) W14
(E) W14 (E) W14
(E) W21
(E) W21
W12X35
K1
K1
W10X22 W12X14
K1
K1
K1
W
X1
1/ 2"
K1
W
X1
W12X14
W
X1
W 10X12
W8X10
K1
2.
5K
W
X1
1/ 2"
W
X2
W12X26
W
X1
W10X22
W10X12
C-1
C-1
J/BRG. = (+15'-3 1/2")
PROVIDE DUCT FRAMING AT
DUCT OPENING. SEE TYPICAL
DETAIL ON SHEET S5.0 TYPICAL
AT MECH. UNITS. GENERAL
CONTRACTOR TO COORDINATE
EXACT DIMENSIONS &
LOCATIONS OF FRAMING WITH
MECHANICAL CONTRACTOR
K1
K1
K1
H3.6-18 H3.6-18 H3.6-18 H6-18
H 6-
S-5.1
1' -0
/8
J/BRG. = (+15'-3 1/2")
J/BRG. = (+15'-3 1/2")
J/BRG. = (+15'-3 1/2")
H6-16
S-5.1 4
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
(E) HSS16x8 (LO)
TO BE DEMO'D
0"
0"
(2) CONT. HSS6x6x1/4 GALV. (HI)
(2) CONT. HSS6x6x1/4 GALV. (HI)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
(2) CONT. HSS6x6x1/4 GALV. (HI)(2) CONT. HSS6x6x1/4 GALV. (HI)(2) CONT.
HSS6x6x1/4
GALV. (HI)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
(2) CONT. HSS6x6x1/4 GALV. (HI)
(UP)
P-1 (UP)
P-1 (UP)
P-1 (U
P)P-1
(UP)
P-1(UP)
P-1
(UP)
P-1
(UP)
P-1
(UP)
P-1
(UP)
P-1
S-5.1
DESIGN JOIST FOR
2k POINT LOAD @
KICKER TYP.
C-1
C-1
C-1
KS
P4
KS
P4
K4
MC6x12 MC6x12
MC6x12
MC6x12
S-5.1
S-5.1
S-5.1
S-5.1
COORDINATE LOCATION OF
UNIT & EXTENTS OF CONCRETE
PAD W/ MECH. CONTRACTOR
HSS
1/2 x2
/2 x3 /1
'-4
/8
(E ) W
(E ) W
(E ) W
(E ) W
(E ) W
(E ) W
(E
) W
(E) W21
(2) CONT. HSS6x6x1/4 GALV. (HI)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
TY
P.
3' -0
TYP.
3'-0"
S-5.1
K1
K1
K1
K1
K1
K1
K1
ECU-1 BELOW, SEE
TYPICAL UNDERHUNG
UNIT SUPPORT DETAIL
2.5K1
2.
5K
2.
5K
2.
5K
SKYLIGHT,
SEE ARCH.
MC6x12 ON TOP OF DECK.
TYPICAL AT MECH. UNITS
SEE DETAIL ON SHEET S5.0
C4x7.25
C4x7.25
JOIST HDR
JOIST HDR
JOIST HDR
JOIST HDR
ANGLE FRAMING FOR
ROOF OPENING. SEE
TYPICAL ROOF OPENING
DETAIL ON S5.0
S-5.1
5"
5"
5"
W8X10
2.
5K
2.5 K2
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
1' -0
/8
1'-0 5/8"
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
BID & CONSTRUCTION
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:5 :4
P M
C R e vi t Lo c a l Fi le s\
S tr u c t _ R m d o ck m a n .r vt
ALTERNATE #1 ROOF FRAMING PLAN
S-2.0 ALT #1
Checker Designer
CSI-176
NEW MRI SITE PREP
02/20/2020
4100 WEST THIRD ST, DAYTON, OH 45428
18106
N SCALE: 1/4" = 1'-0"
ALTERNATE #1 ROOF FRAMING PLAN
TYPICAL ROOF DECK CONNECTION SCHEDULE
PERPENDICULAR
TO SUPPORT
MARK ATTACHMENT
PARALLEL
TO SUPPORT
SEAMS
PUDDLE WELD AT 12" O.C.
(36/4 PATTERN)
A PUDDLE WELD AT 12" O.C. (2)-#10 TEK SCREW PER SPAN
NOTES:
• ALL PUDDLE WELDS TO BE 5/8"Ø FUSION TYPE (UNO.).
WELDS TO BE MADE FOLLOWING AWS D1.3 SPECIFICATIONS BY
QUALIFIED WELDING OPERATORS.
• ALL DECK END LAPS TO BE A MINIMUM OF 2".
• SEE SECTIONS AND DETAILS FOR ADDITIONAL WELDS REQUIRED TYP. (UNO)
A
COLUMN SCHEDULE
MARK COLUMN SIZE BASEPLATE TYPE
ANCHOR
RODS
C-1 W8X31 PL3/4"x14"x1'-2" I (4)-3/4"Ø
MFC-1 W10X33 PL.1 1/4"x16"x1'-4" II (4)-3/4"Ø MFC-2 W10X45 PL.1 1/4"x16"x1'-4" III (4)-1"Ø
• MFC-X DENOTES MOMENT FRAME COLUMNS
• SEE SHEET S-5.0 FOR TYPICAL COLUMN BASE PLATES
• SEE SHEET S-3.0 FOR TYPICAL ANCHOR ROD DETAIL
NOTES:
• ROOF CONSTRUCTION: 1 1/2"x22GA. GALVANIZED WIDE RIB DECK (TYPE B) WELDED TO
SUPPORT STEEL, SEE TYPICAL ROOF DECK CONNECTION SCHEDULE. MINIMUM 3-SPAN
CONDITION (UNO).
• DENOTES 4" NWC SLAB ON 1 1/2"x20GA GALVANIZED WIDE RIB DECK (TYPE B)
• J/B = ROOF JOIST BEARING ELEVATION REFERENCED FROM SLAB ON GRADE ELEVATION OF
0'-0".
• ROOF BEAM ELEVATION NOTED THUS (±) INDICATE TOP OF BEAM ABOVE OR BELOW J/B
ELEVATION NOTED.
• PROVIDE JOIST BRIDGING IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE (UNO). SEE
TYPICAL DETAIL ON S-5.0.
• PROVIDE ADDITIONAL ROW OF BRIDGING AT 1st PANEL POINT OF ALL JOISTS SUBJECTED TO
NET UPLIFT LOADING--SEE GENERAL NOTES.
• PROVIDE L2 1/2"x2"x1/4 AT ALL CHANGES IN DECK DIRECTION AND ALL LOCATIONS WHERE
DECK IS CUT ON A SKEW (UNO).
• COORDINATE ALL OPENINGS AND EDGE CONDITIONS WITH ARCHITECTURAL AND MECHANICAL
DRAWINGS. SEE SHEET S-5.0 FOR TYPICAL OPENING DETAIL.
• DESIGN JOIST SUBSTITUTES FOR 400 PLF (UNO).
• SEE SHEETS S-0.1, S-0.2, & S-0.3 FOR GENERAL NOTES.
• SEE SHEET S-5.0 FOR TYPICAL DETAILS.
• C-X DENOTES COLUMNS. SEE THIS SHEET FOR SCHEDULE.
• MFC-X DENOTES MOMENT FRAME COLUMNS. SEE THIS SHEET FOR SCHEDULE.
• XXKSPX DENOTES SPECIAL JOISTS. SEE JOIST LOADING DIAGRAMS ON S-2.0.
• DENOTES FLEXIBLE MOMENT CONNECTION. SEE SHEET S-5.0 FOR DETAILS.
• DENOTES MOMENT CONNECTION. SEE SHEET S-5.0 FOR DETAILS.
• JOISTS ARE DESIGNED TO SUPPORT EQUIPMENT INDICATED ON PLAN. IF EQUIPMENT
LOCATION VARIES OR WEIGHT EXCEEDS THAT NOTED THEN NOTIFY ENGINEER.
• (E) DENOTES EXISTING CONSTRUCTION.
• P-1 DENOTES SCREEN WALL POST. SEE DETAIL 7 ON S-5.1.
• HX-XX DENOTES BUILT UP COLD FORMED BOX HEADER, SEE SCHEDULE.
TOTAL PEAK DRIFT LOAD
ROOF PROJECTION,
OBSTRUCTION, ETC.
DRIFT ZONE
ROOF
FLAT/SLOPED SNOW LOAD.
MARK
DRIFT LOADING PARAMETERS
FLAT/SLOPED
SNOW LOAD
PEAK DRIFT
LOAD (PSF)
TOTAL PEAK
LOAD
WIDTH OF
DRIFT NOTES
1 22 PSF 28 PSF 50 PSF 6'-8"
2 51 PSF 12'-1"
3 28 PSF 6'-8"
4 20 PSF 9'-6"
SNOW DRIFT SCHEDULE
DRIFT
WIDTH OF
4 2
NOTES:
• LOADS SHOWN ARE DRIFT AND SNOW LOADS ONLY. LOADING SHOWN DOES NOT INCLUDE DEAD LOADS.
• SLIDING SNOW LOADS AND UNBALANCED SNOW LOADS ARE NOT SHOWN IN THIS SCHEDULE. ANY DELEGATED DESIGN ENGINEER SHALL CONSIDER THE SLIDING SNOW AND UNBALANCED SNOW LOADS IN
THEIR DESIGN ALONG WITH CONSIDERING LOADING SHOWN IN THIS SCHEDULE.
73 PSF
50 PSF
43 PSF
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
CAM REVIEW 02/21/2020
mdockman
SIM.
R
Q.3
Q
P.8
P.5
O.8
O.7 O.7
6.5 6.86.2
P.81
9.78.87.96.4 6.9
P.9
Q.4
7.3
8'-3" 20'-3" 22'-3" 28'-8"
'-4
/8
'-6
'-4
MFC-1
MFC-2
MFC-1
MFC-2
MFC-2
MFC-1
MFC-1
MFC-2
W
X3
W18X40W18X35W18X40
W18X40W18X35W18X40W18X40
W
X3
K4
KS
P4
KS
P4
KS
P4
KS
P1
KS
P1
KS
P1
KS
P2
KS
P3
KS
P3
KS
P3
(5 EQUAL SPACES) (4 EQUAL SPACES) (5 EQUAL SPACES)
6'-5 3/4" ±
2'-1 1/4" ±
6'-1 3/4" ±
1'-3 1/8" ±
8'-7" ± 7'-4 7/8" ±
'-3
9'
-9
'-2
'-1 0"
'-0
1' -2
/8
J/BRG. = (+15'-10 3/4")
S-5.1
S-5.1
S-5.1
(E ) W
(E) W21
(E) W14
(E ) W
RTU-1
2800#
CU-1
500# CHILLER
4300#
ROOF DRAINS,
SEE ARCH.
W10X22
W
X1
W 8X
K1
2.
5K
K1
K1
K1
K1
(E ) W
(E) W10
(E ) W
(E ) W
(E) W14(E) W14
(E) W14 (E) W14
(E) W21
(E) W21
W12X35
K1
K1
W10X22 W12X14
K1
K1
K1
W
X1
1/ 2"
K1
W
X1
W12X14
W
X1
W 10X12
W8X10
K1
2.
5K
W
X1
1/ 2"
W
X2
W12X26
W
X1
W10X22
W10X12
C-1
C-1
J/BRG. = (+15'-3 1/2")
PROVIDE DUCT FRAMING AT
DUCT OPENING. SEE TYPICAL
DETAIL ON SHEET S5.0 TYPICAL
AT MECH. UNITS. GENERAL
CONTRACTOR TO COORDINATE
EXACT DIMENSIONS &
LOCATIONS OF FRAMING WITH
MECHANICAL CONTRACTOR
K1
K1
K1
H3.6-18 H3.6-18 H3.6-18 H6-18
H 6-
S-5.1
1' -0
/8
J/BRG. = (+15'-3 1/2")
J/BRG. = (+15'-3 1/2")
J/BRG. = (+15'-3 1/2")
H6-16
S-5.1 4
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
(E) HSS16x8 (LO)
TO BE DEMO'D
0"
0"
(2) CONT. HSS6x6x1/4 GALV. (HI)(2) CONT.
HSS6x6x1/4
GALV. (HI)
(2) CONT.
HSS6x6x1/4
GALV. (HI)
DESIGN JOIST FOR
2k POINT LOAD @
KICKER TYP.
C-1
C-1
C-1
W
X2
1/ 2"
W
X2
1/ 2"
W
X2
1/ 2"
(2) CONT. HSS6x6x1/4 GALV. (HI)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)(2) CONT. HSS6x6x1/4 GALV. (HI)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
S-5.1
S-5.1
TY
P.
3' -0
TYP.
3'-0"
S-5.1
K1
K1
K1
K1
K1
K1
K1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
0"
0"
S-5.1
ECU-1 BELOW, SEE
TYPICAL UNDERHUNG
UNIT SUPPORT DETAIL
2.5K1
2.
5K
2.
5K
2.
5K
SKYLIGHT,
SEE ARCH.
MC6x12 ON TOP OF DECK.
TYPICAL AT MECH. UNITS
SEE DETAIL ON SHEET S5.0
C4x7.25
C4x7.25
JOIST HDR
JOIST HDR
JOIST HDR
JOIST HDR
ANGLE FRAMING FOR
ROOF OPENING. SEE
TYPICAL ROOF OPENING
DETAIL ON S5.0
5"
5"
5"
W8X10
2.
5K
2.5 K2
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
1' -0
/8
1'-0 5/8"
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
BID & CONSTRUCTION
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:5 :5
P M
C R e vi t Lo c a l Fi le s\
S tr u c t _ R m d o ck m a n .r vt
ALTERNATE #2 ROOF FRAMING PLAN
S-2.0 ALT #2
Checker Designer
CSI-176
NEW MRI SITE PREP
02/20/2020
4100 WEST THIRD ST, DAYTON, OH 45428
18106
N SCALE: 1/4" = 1'-0"
ALTERNATE #2 ROOF FRAMING PLAN
TYPICAL ROOF DECK CONNECTION SCHEDULE
PERPENDICULAR
TO SUPPORT
MARK ATTACHMENT
PARALLEL
TO SUPPORT
SEAMS
PUDDLE WELD AT 12" O.C.
(36/4 PATTERN)
A PUDDLE WELD AT 12" O.C. (2)-#10 TEK SCREW PER SPAN
NOTES:
• ALL PUDDLE WELDS TO BE 5/8"Ø FUSION TYPE (UNO.).
WELDS TO BE MADE FOLLOWING AWS D1.3 SPECIFICATIONS BY
QUALIFIED WELDING OPERATORS.
• ALL DECK END LAPS TO BE A MINIMUM OF 2".
• SEE SECTIONS AND DETAILS FOR ADDITIONAL WELDS REQUIRED TYP. (UNO)
A
COLUMN SCHEDULE
MARK COLUMN SIZE BASEPLATE TYPE
ANCHOR
RODS
C-1 W8X31 PL3/4"x14"x1'-2" I (4)-3/4"Ø
MFC-1 W10X33 PL.1 1/4"x16"x1'-4" II (4)-3/4"Ø MFC-2 W10X45 PL.1 1/4"x16"x1'-4" III (4)-1"Ø
• MFC-X DENOTES MOMENT FRAME COLUMNS
• SEE SHEET S-5.0 FOR TYPICAL COLUMN BASE PLATES
• SEE SHEET S-3.0 FOR TYPICAL ANCHOR ROD DETAIL
NOTES:
• ROOF CONSTRUCTION: 1 1/2"x22GA. GALVANIZED WIDE RIB DECK (TYPE B) WELDED TO
SUPPORT STEEL, SEE TYPICAL ROOF DECK CONNECTION SCHEDULE. MINIMUM 3-SPAN
CONDITION (UNO).
• DENOTES 4" NWC SLAB ON 1 1/2"x20GA GALVANIZED WIDE RIB DECK (TYPE B)
• J/B = ROOF JOIST BEARING ELEVATION REFERENCED FROM SLAB ON GRADE ELEVATION OF
0'-0".
• ROOF BEAM ELEVATION NOTED THUS (±) INDICATE TOP OF BEAM ABOVE OR BELOW J/B
ELEVATION NOTED.
• PROVIDE JOIST BRIDGING IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE (UNO). SEE
TYPICAL DETAIL ON S-5.0.
• PROVIDE ADDITIONAL ROW OF BRIDGING AT 1st PANEL POINT OF ALL JOISTS SUBJECTED TO
NET UPLIFT LOADING--SEE GENERAL NOTES.
• PROVIDE L2 1/2"x2"x1/4 AT ALL CHANGES IN DECK DIRECTION AND ALL LOCATIONS WHERE
DECK IS CUT ON A SKEW (UNO).
• COORDINATE ALL OPENINGS AND EDGE CONDITIONS WITH ARCHITECTURAL AND MECHANICAL
DRAWINGS. SEE SHEET S-5.0 FOR TYPICAL OPENING DETAIL.
• DESIGN JOIST SUBSTITUTES FOR 400 PLF (UNO).
• SEE SHEETS S-0.1, S-0.2, & S-0.3 FOR GENERAL NOTES.
• SEE SHEET S-5.0 FOR TYPICAL DETAILS.
• C-X DENOTES COLUMNS. SEE THIS SHEET FOR SCHEDULE.
• MFC-X DENOTES MOMENT FRAME COLUMNS. SEE THIS SHEET FOR SCHEDULE.
• XXKSPX DENOTES SPECIAL JOISTS. SEE JOIST LOADING DIAGRAMS ON S-2.0.
• DENOTES FLEXIBLE MOMENT CONNECTION. SEE SHEET S-5.0 FOR DETAILS.
• DENOTES MOMENT CONNECTION. SEE SHEET S-5.0 FOR DETAILS.
• JOISTS ARE DESIGNED TO SUPPORT EQUIPMENT INDICATED ON PLAN. IF EQUIPMENT
LOCATION VARIES OR WEIGHT EXCEEDS THAT NOTED THEN NOTIFY ENGINEER.
• (E) DENOTES EXISTING CONSTRUCTION.
• P-1 DENOTES SCREEN WALL POST. SEE DETAIL 7 ON S-5.1.
• HX-XX DENOTES BUILT UP COLD FORMED BOX HEADER, SEE SCHEDULE.
TOTAL PEAK DRIFT LOAD
ROOF PROJECTION,
OBSTRUCTION, ETC.
DRIFT ZONE
ROOF
FLAT/SLOPED SNOW LOAD.
MARK
DRIFT LOADING PARAMETERS
FLAT/SLOPED
SNOW LOAD
PEAK DRIFT
LOAD (PSF)
TOTAL PEAK
LOAD
WIDTH OF
DRIFT NOTES
1 22 PSF 28 PSF 50 PSF 6'-8"
2 51 PSF 12'-1"
3 28 PSF 6'-8"
4 20 PSF 9'-6"
SNOW DRIFT SCHEDULE
DRIFT
WIDTH OF
4 2
NOTES:
• LOADS SHOWN ARE DRIFT AND SNOW LOADS ONLY. LOADING SHOWN DOES NOT INCLUDE DEAD LOADS.
• SLIDING SNOW LOADS AND UNBALANCED SNOW LOADS ARE NOT SHOWN IN THIS SCHEDULE. ANY DELEGATED DESIGN ENGINEER SHALL CONSIDER THE SLIDING SNOW AND UNBALANCED SNOW LOADS IN
THEIR DESIGN ALONG WITH CONSIDERING LOADING SHOWN IN THIS SCHEDULE.
73 PSF
50 PSF
43 PSF
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
SIM.
Q.3
Q
P.8
P.5
O.8
O.7 O.7
6.5 6.86.2
P.81
9.78.87.96.4 6.9
P.9
Q.4
7.3
8'-3" 20'-3" 22'-3" 28'-8"
'-4
/8
'-6
'-4
MFC-1
MFC-2
MFC-1
MFC-2
MFC-2
MFC-1
MFC-1
MFC-2
W
X3
W18X40W18X35W18X40
W18X40W18X35W18X40W18X40
W
X3
K4
KS
P4
KS
P4
KS
P4
KS
P1
KS
P1
KS
P1
KS
P2
KS
P3
KS
P3
KS
P3
(5 EQUAL SPACES) (4 EQUAL SPACES) (5 EQUAL SPACES)
6'-5 3/4" ±
2'-1 1/4" ±
6'-1 3/4" ±
1'-3 1/8" ±
8'-7" ± 7'-4 7/8" ±
'-3
9'
-9
'-2
'-1 0"
'-0
1' -2
/8
J/BRG. = (+15'-10 3/4")
S-5.1
S-5.1
S-5.1
(E ) W
(E) W21
(E) W14
(E ) W
W12X26
W12X26
W12X26
W
X1
W
X1
W
X1
W
X1
W 8X
K1
2.
5K
K1
K1
K1
K1
K1
K1
K1
K1
K110
K1
K1
K1
(E ) W
(E) W10
(E ) W
(E ) W
(E) W14(E) W14
(E) W14 (E) W14
(E) W21
(E) W21
C-1
C-1
J/BRG. = (+15'-3 1/2")
RTU-1
2800#
CU-1
500#
CHILLER
4300#
PROVIDE DUCT FRAMING AT
DUCT OPENING. SEE TYPICAL
DETAIL ON SHEET S5.0 TYPICAL
AT MECH. UNITS. GENERAL
CONTRACTOR TO COORDINATE
EXACT DIMENSIONS &
LOCATIONS OF FRAMING WITH
MECHANICAL CONTRACTOR
MC6x12 ON TOP OF DECK.
TYPICAL AT MECH. UNITS
SEE DETAIL ON SHEET S5.0
H3.6-18 H3.6-18 H3.6-18 H6-18
H 6-
H6-16
S-5.1
(E) HSS16x8 (LO)
TO BE DEMO'D
0"
0"
S-5.1
S-5.1
S-5.1
W
X2
1/ 2"
W
X2
1/ 2"
W
X2
1/ 2"
0"
(2) CONT. HSS6x6x1/4 GALV. (HI)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
0"
(2) CONT. HSS6x6x1/4 GALV. (HI)
(2 ) C
O N
T.
H
S S6 x6 x1
/4 G
AL
V.
(H I)
DESIGN JOIST FOR
2k POINT LOAD @
KICKER TYP.
(U P)P-1
(U P)P-1
(U P)P-1
(UP)
P-1 (U
P)P-1
(U P)P-1
TY
P.
3' -0
TYP.
3'-0"
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
S-5.1
ECU-1 BELOW, SEE
TYPICAL UNDERHUNG
UNIT SUPPORT DETAIL
C4x7.25
C4x7.25
5"
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
BOTTOM FLANGE
BRACING, SEE TYPICAL
DETAILS ON S5.1
1' -0
/8
1'-0 5/8"
W8X10
2.
5K
2.5 K2
5"
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
BID & CONSTRUCTION
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:5 :5
P M
C R e vi t Lo c a l Fi le s\
S tr u c t _ R m d o ck m a n .r vt
ALTERNATE #3 ROOF FRAMING PLAN
S-2.0 ALT #3
Checker Designer
CSI-176
NEW MRI SITE PREP
02/20/2020
4100 WEST THIRD ST, DAYTON, OH 45428
18106
TYPICAL ROOF DECK CONNECTION SCHEDULE
PERPENDICULAR
TO SUPPORT
MARK ATTACHMENT
PARALLEL
TO SUPPORT
SEAMS
PUDDLE WELD AT 12" O.C.
(36/4 PATTERN)
A PUDDLE WELD AT 12" O.C. (2)-#10 TEK SCREW PER SPAN
NOTES:
• ALL PUDDLE WELDS TO BE 5/8"Ø FUSION TYPE (UNO.).
WELDS TO BE MADE FOLLOWING AWS D1.3 SPECIFICATIONS BY
QUALIFIED WELDING OPERATORS.
• ALL DECK END LAPS TO BE A MINIMUM OF 2".
• SEE SECTIONS AND DETAILS FOR ADDITIONAL WELDS REQUIRED TYP. (UNO)
A
COLUMN SCHEDULE
MARK COLUMN SIZE BASEPLATE TYPE
ANCHOR
RODS
C-1 W8X31 PL3/4"x14"x1'-2" I (4)-3/4"Ø
MFC-1 W10X33 PL.1 1/4"x16"x1'-4" II (4)-3/4"Ø MFC-2 W10X45 PL.1 1/4"x16"x1'-4" III (4)-1"Ø
• MFC-X DENOTES MOMENT FRAME COLUMNS
• SEE SHEET S-5.0 FOR TYPICAL COLUMN BASE PLATES
• SEE SHEET S-3.0 FOR TYPICAL ANCHOR ROD DETAIL
N SCALE: 1/4" = 1'-0"
ALTERNATE #3 ROOF FRAMING PLAN
TOTAL PEAK DRIFT LOAD
ROOF PROJECTION,
OBSTRUCTION, ETC.
DRIFT ZONE
ROOF
FLAT/SLOPED SNOW LOAD.
MARK
DRIFT LOADING PARAMETERS
FLAT/SLOPED
SNOW LOAD
PEAK DRIFT
LOAD (PSF)
TOTAL PEAK
LOAD
WIDTH OF
DRIFT NOTES
1 22 PSF 28 PSF 50 PSF 6'-8"
2 51 PSF 12'-1"
3 28 PSF 6'-8"
4 20 PSF 9'-6"
SNOW DRIFT SCHEDULE
DRIFT
WIDTH OF
4 2
NOTES:
• LOADS SHOWN ARE DRIFT AND SNOW LOADS ONLY. LOADING SHOWN DOES NOT INCLUDE DEAD LOADS.
• SLIDING SNOW LOADS AND UNBALANCED SNOW LOADS ARE NOT SHOWN IN THIS SCHEDULE. ANY DELEGATED DESIGN ENGINEER SHALL CONSIDER THE SLIDING SNOW AND UNBALANCED SNOW LOADS IN
THEIR DESIGN ALONG WITH CONSIDERING LOADING SHOWN IN THIS SCHEDULE.
73 PSF
50 PSF
43 PSF
NOTES:
• ROOF CONSTRUCTION: 1 1/2"x22GA. GALVANIZED WIDE RIB DECK (TYPE B) WELDED TO
SUPPORT STEEL, SEE TYPICAL ROOF DECK CONNECTION SCHEDULE. MINIMUM 3-SPAN
CONDITION (UNO).
• DENOTES 4" NWC SLAB ON 1 1/2"x20GA GALVANIZED WIDE RIB DECK (TYPE B)
• J/B = ROOF JOIST BEARING ELEVATION REFERENCED FROM SLAB ON GRADE ELEVATION OF
0'-0".
• ROOF BEAM ELEVATION NOTED THUS (±) INDICATE TOP OF BEAM ABOVE OR BELOW J/B
ELEVATION NOTED.
• PROVIDE JOIST BRIDGING IN ACCORDANCE WITH THE STEEL JOIST INSTITUTE (UNO). SEE
TYPICAL DETAIL ON S-5.0.
• PROVIDE ADDITIONAL ROW OF BRIDGING AT 1st PANEL POINT OF ALL JOISTS SUBJECTED TO
NET UPLIFT LOADING--SEE GENERAL NOTES.
• PROVIDE L2 1/2"x2"x1/4 AT ALL CHANGES IN DECK DIRECTION AND ALL LOCATIONS WHERE
DECK IS CUT ON A SKEW (UNO).
• COORDINATE ALL OPENINGS AND EDGE CONDITIONS WITH ARCHITECTURAL AND MECHANICAL
DRAWINGS. SEE SHEET S-5.0 FOR TYPICAL OPENING DETAIL.
• DESIGN JOIST SUBSTITUTES FOR 400 PLF (UNO).
• SEE SHEETS S-0.1, S-0.2, & S-0.3 FOR GENERAL NOTES.
• SEE SHEET S-5.0 FOR TYPICAL DETAILS.
• C-X DENOTES COLUMNS. SEE THIS SHEET FOR SCHEDULE.
• MFC-X DENOTES MOMENT FRAME COLUMNS. SEE THIS SHEET FOR SCHEDULE.
• XXKSPX DENOTES SPECIAL JOISTS. SEE JOIST LOADING DIAGRAMS ON S-2.0.
• DENOTES FLEXIBLE MOMENT CONNECTION. SEE SHEET S-5.0 FOR DETAILS.
• DENOTES MOMENT CONNECTION. SEE SHEET S-5.0 FOR DETAILS.
• JOISTS ARE DESIGNED TO SUPPORT EQUIPMENT INDICATED ON PLAN. IF EQUIPMENT
LOCATION VARIES OR WEIGHT EXCEEDS THAT NOTED THEN NOTIFY ENGINEER.
• (E) DENOTES EXISTING CONSTRUCTION.
• P-1 DENOTES SCREEN WALL POST. SEE DETAIL 7 ON S-5.1.
• HX-XX DENOTES BUILT UP COLD FORMED BOX HEADER, SEE SCHEDULE.
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
1/8" WIDE x T/4 DEEP
SAWCUT
VAPOR BARRIER
GRANULAR FILL
SEE PLAN NOTES
VAPOR BARRIER
GRANULAR FILL
SEE PLAN NOTES
1/2"x18" SMOOTH ROD @ 24" O.C.
GREASE ONE END
COAT JOINT WITH
BOND BREAKER
CONTROL JOINT
CONSTRUCTION JOINT
(SEE PLAN FOR LOCATIONS)
SEE TABLE
GENERAL
NOTES
SEE TABLE
GENERAL
NOTES
T T
3T
36d
LAP
TRENCH FOOTING STEP DETAIL
SEE TABLE FOR
BAR CLEARANCES
SE
E
PL
AN
SE
E
PL
AN
2' -0
" M
AX
2'-0"
TYPICAL
TOP & BOT.
REINF.
2" COMPRESSIBLE
FILLERUNDERGROUND PIPE, CONDUIT, ETC.
COORDINATE LOCATION W/UTILITY
TRADE CONTRACTOR
(2)-#5
8" MIN.8" MIN.
1' -0
" M
IN
8" MIN.
TYPICAL DETAIL AT UNDERGROUND
UTILITY PENETRATION
SEE GENERAL NOTES
FOR BAR CLEARANCES
SE
E
PL
AN
1'-6" 1'-6"
6"
(2)-#5
IF CONTROL JOINT OR CONSTRUCTION
JOINT OCCURS RE-ENTRANT
REINFORCING MAY BE OMITTED
(2) #4x3'-0" LG.
(2) #4x3'-0" LG.
PROVIDE CONSTRUCTION OR
CONTROL JOINT AT
ALL DOOR WAYS, TYP.
(2) #4x3'-0"LG.
AT RE-ENTRANT
CORNERS
TYPICAL RE-ENTRANT AND DISCONTINUOUS
CONTROL JOINTS SLAB REINFORCING
RE-ENTRANT CORNERS
DISCONTINUOUS CONTROL JOINT
6"
(ASTM F1554 GR. 36)
FOUNDATION, PIER,
PILE CAP, ETC.
HEAVY HEX NUT WITH
OVERSIZED WASHER.
TACK WELD TO ROD.
BASE PL.
7" 10
FO
R
/4
"Ø A
.R
FO
R
"Ø
A .R
1/
2" N
O N
-S H
R
IN
K
G R
O U
T, U
N O
TYPICAL ANCHOR ROD DETAIL
• CONTRACTOR MAY USE LEVELING NUTS OR LEVELING PLATES AT
CONTRACTORS OPTION.
• AN INCREASE IN GROUT THICKNESS FOR LARGE BASE PLATES IS
PERMISSIBLE IF APPROVED BY THE ENGINEER. COORDINATION DUE TO
INCREASE IN GROUT THICKNESS FOR OTHER TRADES IS THE
REPONSIBILITY OF THE CONTRACTOR.
COLUMN COVER
SEE ARCH.
BOND BREAKER
ANCHOR RODS, SEE TYPICAL
ANCHOR ROD DETAIL,
TYPICAL BASE PLATE DETAILS
AND COLUMN SCHEDULE
SIDEWALK
3/4" CHAMFER
SEE PLAN OR
SCHEDULE FOR
PIER DETAIL
REINFORCING
SEE SCHEDULE
EXTERIOR COLUMN FOOTING WITH COL. COVER
EL. = 0'-0"
EQUAL EQUAL
SC
H
ED
U
LE
SE
E
(F R
O
ST
3' -0
" M
IN
FO
R
B
AR
C
LE
AR
AN
C E
SE
E
G
EN
ER
AL
N O
TE
S
G R
O U
T N
O N
-S H
R
IN
K
FOR CONC. PIER SIZE
SEE PLAN
SEE SCHEDULE
EXTERIOR WALL FOOTING
SIDEWALK OR
FINISH GRADE
SEE CIVIL
#4 @ 12" O.C.
FINISH
SEE ARCH.TRACK TO MATCH STUD SIZE.
ANCHOR W/1/2"Ø A.B. x8"LG.
W/2" HOOK @ 4'-0" O.C.
TOP OF SLAB
SEE PLAN
PREMOLDED
JOINT FILLER
SEE COLD FORMED METAL STUD
SCHEDULE, ELEVATION, AND
TYPICAL DETAILS ON SHEET S-4.0
FOR METAL STUD SIZE, GAUGE,
SPACING, AND ADD'L. INFO.
(2) #5 CONT.
TOP & BOT.
EQ. 11 3/8" EQ.
SE
E
PL
AN
SE
E
PL
AN
SEE PLAN
FO
R
B
AR
C
LE
AR
AN
C E
SE
E
G
EN
ER
AL
N O
TE
S
(F R
O
ST
3' -0
" M
IN
#4 @ 12" O.C.
RIGID INSULATION,
SEE ARCH.
FOUNDATION DRAINS
MAY OCCUR. SEE
CIVIL DRAWINGS FOR
DETAILS
SIDEWALK OR FINISH
GRADE, SEE CIVIL
ANCHOR RODS. SEE TYPICAL
ANCHOR RODS DETAIL, TYPICAL
BASE PLATE DETAILS AND
COLUMN SCHEDULE
WF COLUMN,
SEE PLAN
DIAMOND INFILL
BASE PLATE NOT
CENTERED ON
COLUMN
PREMOLDED
JOINT FILLER
TOP OF SLAB
SEE PLAN
WALL FOOTING
(BEYOND)
NON-SHRINK
GROUT
REINFORCING
SEE SCHEDULE
(F R
O
ST
3' -0
" M
IN
FO
R
B
AR
C
LE
AR
AN
C E
SE
E
G
EN
ER
AL
N O
TE
S
SEE SCHEDULE
SE
E
SC
H
ED
U
LE
SE
E
PL
AN
EQ EQ
#4 @ 12" O.C.
RIGID INSULATION,
SEE ARCH.
FLOOR DRAIN
SEE MECH. DWGS.
T/SLAB
SEE PLAN
TYPICAL FLOOR RECESS
PL
AN
SE
E
SEE ARCH. & MECH. DWGS.
RECESS DIMENSIONS VARY
AR
C
H
SE
E 6"
EMBED
8"
CLEAN SURFACE &
APPLY BONDING AGENT
(E) FTG.
#5 DOWELS TO MATCH CONT.
REINFORCMENT W/ HEAVY DUTY
ADHESIVE ANCHOR. PROVIDE LAP
SPLICE PER GENERAL NOTES
(N) FOOTING
CONT. FTG.
REINFORCING
(E) STEM WALL
(N) CONCRETE
STEM WALL
SLOPE
DOWN
WALL BEYOND
#4x6'-0" LG @ 12" O.C.
#4 @ 24" O.C.
TYP
#4 @ 12" O.C.
E.W. E.F. #4 @ 12" O.C.
E.W.
6" AIR SPACE
(2) #5 CONT
TOP & BOT
4" MIN. GRANULAR FILL
SEE ARCH & CIVIL
SIDEWALK, SEE CIVIL
#4x4'-0" LG @ 12" O.C.
2 1/2" CONC. SLAB W/
#4 @ 9" O.C. EA. WAY
BOTTOM ON 1 1/2"x22GA
FORM DECK (4" TOTAL
SLAB THICKNESS)
2'-0"
COORD. W/ ARCH
4'-6"
TYP
1'-6"
(F R
O
ST
3' -0
" M
IN
FO
R
B
AR
C
LE
AR
AN
C E
SE
E
G
EN
ER
AL
N O
TE
S
2' -8
(3) SIDES TYP
1'-4"
SE
E
PL
AN
D
EP
TH
T
O M
AT
C
H
BO
TT
O
M O
F W
AL
L
FT
G
. 8"
TYPICAL FROST SLAB DETAIL
NOTE: SLAB REINFORCING
TO BE CENTERED IN SLAB
EXTERIOR WALL FOOTING
WINDOW,
SEE ARCH
#4 @ 12" O.C.
TOP OF SLAB
SEE PLAN
#4x6'-0" LG @ 12" O.C.
(2) #4 CONT.
SIDEWALK, SEE CIVIL
4" MIN. GRANULAR FILL,
SEE ARCH & CIVIL
#4 @ 12" O.C.
(2) #5 CONT.
2'-0"
1' -2
SE
E
PL
AN
SE
E
PL
AN (F
R O
ST
3' -0
" M
IN
FO
R
B
AR
C
LE
AR
AN
C E
SE
E
G
EN
ER
AL
N O
TE
S
SEE PLAN
RIGID INSULATION,
SEE ARCH.
FOUNDATION DRAINS
MAY OCCUR. SEE
CIVIL DRAWINGS FOR
DETAILS
CORNER BARS TO MATCH
SIZE & SPACING OF
HORIZ. REINFORCING
CONSTRUCTION JOINT
DOWELS TO MATCH
SIZE SPACING OF
HORIZ. REINFORCING
36 BAR DIAMETER
LAP, TYP.
CONSTRUCTION JOINT
DOWELS TO MATCH
SIZE SPACING OF
HORIZ. REINFORCING
SINGLE LAYER REINFORCING TWO LAYER REINFORCING
CONCRETE WALL HORIZONTAL REINFORCING DETAILS
36 BAR DIAMETER
LAP, TYP.
ANCHOR RODS, SEE TYPICAL
ANCHOR ROD DETAIL, TYPICAL
BASE PLATE DETAILS AND
COLUMN SCHEDULE
T/SLAB
SEE PLAN
BOND BREAKER
DIAMOND OR
ROUND INFILL
REINFORCING
SEE SCHEDULE
N O
N -S
H R
IN
K
G R
O U
T
SE
E
G
EN
ER
AL
N O
TE
S
FO
R
C
LE
AR
AN
C E
S
TYPICAL INTERIOR COLUMN FOOTING
PL
AN
SE
E
SC
H
ED
U
LE
SE
E
SEE SCHEDULE
EQUAL EQUAL
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
BID & CONSTRUCTION
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:5 :5
P M
C R e vi t Lo c a l Fi le s\
S tr u c t _ R m d o ck m a n .r vt
FOUNDATION DETAILS
S-3.0 Checker Designer
CSI-176
NEW MRI SITE PREP
02/20/2020
4100 WEST THIRD ST, DAYTON, OH 45428
18106
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-1/2" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
COLD FORMED METAL STUD WALL SCHEDULE
EXTERIOR STUDS
INTERIOR STUDS
TYPICAL CORNER
6"x18GA. 6"x18GA. SEE ARCHITECTURAL
NOTES:
• HORIZONTAL BRIDGING REQUIRED AT 4'-0" O.C. MAX.
• SEE TYPICAL COLD FORMED METAL STUD WALL ELEVATION ON THIS SHEET FOR
ADDITIONAL INFORMAITON.
• SEE COLD FORMED HEADER SCHEDULE ON THIS SHEET FOR ADDITIONAL INFORMATION.
• SEE TYPICAL COLD FORMED DETAIL ON THIS SHEET FOR ADDITIONAL INFORMATION.
• THE METAL STUD SIZES, GAUGE, AND SPACING SHOWN IN THE METAL STUD SCHEDULE
APPLIES ALL METAL STUDS ON THE PROJECT UNLESS THE SECTIONS OR PLANS INDICATE
DIFFERENT METAL STUD DESIGNS. THE METAL STUD SIZE, GUAGE, & SPACING SHOWN IN
THE SECTIONS ANS PLANS SUPERSEDES THE METAL STUD DESIGNS SHOWN IN THE WALL
SCHEDULE.
1/2"Ø ANCHOR BOLTS
@ 4'-0" O.C. TYP.
1'-0" MAX.
CONT. METAL
TRACK, TYP.
PROVIDE HORIZONTAL STUD
BRIDGING @ 4'-0" O.C. VERT.
MAX. SEE TYP. DETAIL ON
SHEET S-4.0
SEE TYPICAL SILL/JAMB
DETAIL
SEE COLD FORMED WALL
STUD SCHEDULE
HEADER AT OPENINGS
SEE PLAN AND SCHEDULE
WF (BEYOND)
CONT. METAL TRACK
T/PARAPET
JST. BRG.
SIDE OF OPENING
JAMB STUD TO SUPPORT
HEADER - TYPICAL SEACH
SEE TYPICAL BOX HEADER
TO JAMB CONN. DETAIL
ON SHEET S-4.0
TYPICAL COLD FORMED METAL STUD WALL ELEVATION
NOTES:
• AT WALL LOCATIONS WHERE MULTIPLE STUDS ARE REQUIRED TO SUPPORT VERTICAL
LOADS, A CONTINUOUS LOAD PATH SHALL BE PROVIDED TO SUPPORT THOSE LOADS
THROUGH THE STRUCTURE TO THE FOUNDATIONS. THIS MAY BE ACCOMPLISHED
THROUGH THE USE OF RIM JOISTS, SQUASH BLOCKS OR OTHER APPROPRIATE MEANS
BASED ON LOCATION AND DETAILING CONSIDERATIONS.
• SEE COLD FORMED STUD WALL SCHEDULE FOR SIZE AND SPACING OF LIGHT GAUGE
WALL STUDS.
TYPICAL METAL STUD TO
METAL STUD CONNECTION TYPICAL METAL STUD CONNECTION
TYPICAL CONNECTION TO
METAL STUD TRACK
TYPICAL METAL STUD CONNECTION DETAILS
4" METAL
STUD 8" METAL STUD
#10-16 SCREWS @
2'-0" O.C. MAX.
METAL STUD
METAL STUD
(4) #10-16 SELF-DRILLING
SHEET METAL SCREWS (UNO)
METAL STUD
TRACK#10-16 SDS EA
STUD FLANGE
JAMB STUDS ATTACHED W/
TRACK ATTACH TRACK TO JAMB W/
(1) #10-16 SCREW @ 16" O.C.
ON EA. LEG, & (2) #10-16 SCREW
INTO WEBS @ 16" O.C.
TYPICAL JAMB STUD DETAIL
OPENING
1 1/2"x1 1/2"x16GA. CLIP
ANGLE FASTEN TO STUD &
CRC W/(2) #10 PER CONN.
METAL STUD
SEE PLAN FOR
SIZE & GA.
1 1/2"x16GA. COLD ROLLED
CHANNEL (CRC). BRIDGING
SPACED @ 4'-0" O.C. MAX.
TYPICAL WALL BRIDGING DETAIL
(3) #12-24 TEKS-5
SD SCREWS
1/2"
PROPRIETARY
SCREWS BY
DIETRICH
3-1/2" FastClip SLIDE CLIPS
FastClip BY DIETRICH INDUSTRIES INC.
1/2"
TRACK EQUAL
TO STUD SIZE
AND GAUGE
(6) #12 TEKS
IF FastClip ID LOCATED AT
STANDARD WEB OPENING IN
METAL STUD
TYPICAL FastClip ATTACHMENT DETAILS
TYPICAL BOX HEADER TO JAMB CONNECTION
8"x18GA. TRACK
W/(6) #10-16 SCREWS
TO JAMB &(3) #10-16
SCREWS TO EA. SIDE
OF HEADER
BOX HEADER
SEE BOX HEADER
FOR ADD'L. INFO.
CONT. TRACK
WALL STUDS
SEE WALL
SCHEDULE
DIETRICH EASYCLIP S-SERIES TOP & BOT.
W/(2) #10-16 SCREWS TO JAMB
& (2) #10-16 SCREWS TO HEADER
8"x18GA. TRACK W/ (6)
#10-16 SCREWS
TO JAMB & (3) #10-16
SCREWS TO EA. SIDE
OF HEADER
HEADER ATTACHMENT
FOR ADD'L INFO
FULL HEIGHT JAMB STUDS.
SEE BOX HEADER SCHEDULE
COLD FORMED 6" HEADER SCHEDULE
FIELD
H6-18 6"x6" (3) 6"x18GA (2)
H3.6-18 6"x3 5/8" (3) 3 5/8"x18GA 6"x18GA (2)
HEADER SIZE METAL STUDS TOP & BOT. TRACK # OF JAMB STUDS AT
EACH END OF HEADER
H6-16 6"x6" (3) 6"x16GA (2)
6"x18GA
6"x16GA
COLD FORMED HEADER PROFILES
6" TRACK
3 5/8" STUD
(10) #10-16 TEKS
@ 16" O.C., TYP
6" TRACK
6" STUD
(10) #10-16 TEKS
@ 16" O.C., TYP
6x3 5/8 6x6
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
BID & CONSTRUCTION
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:5 :5
P M
C R e vi t Lo c a l Fi le s\
S tr u c t _ R m d o ck m a n .r vt
COLD FORMED DETAILS
S-4.0 Checker Designer
CSI-176
NEW MRI SITE PREP
02/20/2020
4100 WEST THIRD ST, DAYTON, OH 45428
18106
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
(4) 1 1/16"Ø HOLES FOR 3/4"Ø A.R.
(4) 1 5/16"Ø HOLES FOR 1"Ø A.R.
1 1/2" FOR 3/4"Ø A.R.
2" FOR 1"Ø A.R.
TYPICAL COLUMN BASE PLATE DETAILS
TYPE I
EQ. EQ.
EQ
EQ
5/16
TYP. EA.
FLANGE
5/16
(4) 1 1/16"Ø HOLES FOR 3/4"Ø A.R.
(4) 1 5/16"Ø HOLES FOR 1"Ø A.R.
(4) 1 1/16"Ø HOLES FOR 3/4"Ø A.R.
(4) 1 5/16"Ø HOLES FOR 1"Ø A.R. 1 1/2" FOR 3/4"Ø A.R.
2" FOR 1"Ø A.R.
1 1/2" FOR 3/4"Ø A.R.
2" FOR 1"Ø A.R.
TYPE IIITYPE II
5/16
5/16
TYP. EA
FLANGE
6"
6"
6"
EQ EQ
4"
5/16
TYP. EA
FLANGE
5/16
4"
STANDARD SHEAR
CONNECTION SCHEDULE
BEAM SIZE
W12 3
W14 3
W16 4
W18 5
MINIMUM NO. OF
ROWS OF A325
3/4"Ø BOLTS IN
DOUBLE SHEAR
W10 2
W8 2
L6x4x3/8x0'8"
(LLV)
L4x4x5/16 TYP. EACH
SIDE OF OPENING
TYPICAL ROOF OPENING DETAIL
* FOR ALL ROOF OPENINGS 12" OR GREATER.
COORD. OPENING SIZES AND LOCATIONS WITH
ARCHITECT & MECHANICAL CONTRACTOR.
BURGLAR BARS MAY OCCUR
COORD. WITH ARCH. &
MECH.
SEE PLAN
BEAM SPACING
OPENING*
ROOF
3/16
TYP
3/16
TYP
18GA. REINF. PL
(MAX. 2 WEBS CUT,
NO REINF. REQ'D)
(MAX. 3 WEBS CUT)
16GA. REINF. PL
(MAX. 4 WEBS CUT)
(2) SCREWS AT EA.
CUT DECK RIB,
TYP.
#10-16 TEKS @ 6" O.C. MAX.
AROUND PERIMETER
1 1/2" TYPE B DECK
TYPICAL ROOF DECK PENETRATION REINFORCING DETAILS
NOTES:
• HOLES ARE LIMITED TO ONE PER SPAN PER DECK SHEET. FOR MULTIPLE HOLES,
CONSULT ENGINEER OR PROVIDE SUPPORT FRAME PER TYPICAL ROOF
OPENING DETAIL.
• SEE TYPICAL ROOF OPENING DEATIL FOR OPENINGS GREATER THAN 12".
12" MAX
6" MIN EA SIDE OF OPG
EXTEND TO FIRST RIB 8" MAX
ANGLE CHORD SPLICE DETAIL
SPLICE PL. 7/16"x3"x0'-10"
CENTER ON SPLICE 1/4
L4x4 L4x4
OUTSIDE FACE OF BUILDING
OR OPENING, ETC
SEE SJI FOR ANGLE
SIZE REQUIREMENTS
TYPICAL BRIDGING DETAILS
NOTES:
• SEE STEEL JOIST INSTITUTE FOR NUMBER OF ROWS
OF BRIDGING PER BAY.
• JOIST SUPPLIER TO PROVIDE ADDITIONAL ROWS OF
BRIDGING AS REQUIRED FOR UPLIFT.
• EACH DISCONTINUOUS END OF EACH LINE OF
BRIDGING SHALL TERMINATE AT A BEARING WALL OR
WITH X-BRIDGING AS SHOWN. X-BRIDGING AND/OR
ANCHORAGE TO WALL SHALL BE INSTALLED DURING
JOIST ERECTION.
DIAGONAL 'X'
BRIDGING
TWO BAYS
HORIZONTAL
TOP & BOTT.
BRIDGING
TYP.
TYP.TYP.
METAL DECK
TYPICAL JOIST TO BEAM
CONNECTION DETAIL - ROOF
1/8 2"
TYP.
K-SERIES
TYPICAL JOIST REINFORCING DETAIL
L1 1/2x1 1/2x3/16
EACH SIDE
L1 1/2x1 1/2x3/16
EACH SIDE
CONCENTRATED LOAD
TO BOTTOM CHORD
CONCENTRATED
LOAD TO TOP CHORD
3/16
TYP.
L REINFORCEMENT
REQ'D WHEN GREATER
THAN 6"
L REINFORCEMENT
REQ'D WHEN GREATER
THAN 6"
* L REINFORCEMENT NOT REQUIRED WHEN SUM OF CONCENTRATED
LOADS WITHIN CHORD PANEL DOES NOT EXCEED 100 lbs AND THE
ATTACHMENTS ARE CONCENTRIC TO CHORD.TYPICAL ROOFTOP
MECHANICAL UNIT SUPPORTS
USE CAUTION WHEN WELDING AS NOT TO DAMAGE JOIST.*
SEE TYPICAL JOIST
REINFORCING
DETAIL
STEEL SHIMS AT 2'-0" O.C.
(NOT REQUIRED IF TAPERED
CURBS ARE PROVIDED,
COORD. WITH RTU
SUPPLIER)
MC6, EACH END OF RTU
CURB (SEE PLAN)
MECH. UNIT CURB. SEE MECH.
DRAWINGS. FASTEN MECH. UNIT
CURB TO CHANNEL W/(5) HILTI
#12-24 SELF DRILLING SCREWS
(TYP. @ EA. SIDE)
SEE TYPICAL JOIST
REINFORCING
DETAIL
3/16
3/16*TYP. @ EA.
JOIST
CL JOISTS
CL PIPING
CL PIPING
NOTES:
• DENOTES POSITION OF HANGER.
• ONE HANGER PER JOIST.
PIPING PARALLEL TO JOIST PIPING PERPENDICULAR TO JOIST
PIPE HANGER SPACING DIAGRAMS
(FOR PIPES HAVING DIAMETER OF 8" OR LARGER)
NOTES:
THIS DETAIL INDICATES HOW LARGE PIPES SHOULD BE SUPPORTED.
THIS DOES NOT PERMIT THE HANGING OF LARGE PIPES FROM JOISTS
UNLESS SHOWN ON STRUCTURAL DRAWINGS OR APPROVED BY THE
ENGINEER. CONTRACTOR TO COORDINATE LOCATION OF PIPES WITH
STRUCTURAL ENGINEER.
SPACE EQUALLY BETWEEN COL. CL's
MAX.
10'-0"
EQ
EQ
CL COLUMN OR GIRDER
CL JOISTS
CL COLUMN OR GIRDER
'-0
" M
AX
'-0
" M
AX
ANGLE REINFORCEMENT
REQ'D. WHEN GREATER
THAN 6"
L4x4x1/4 OR PROPRIETARY
METAL FRAMING DESIGNED BY
MFR., TO SPAN TO ADJACENT
JOIST WHEN HANGER IS NOT
CONCENTRIC TO JOIST.
SEE TYPICAL JOIST
REINFORCING DETAIL
HANGER ROD &
CARRIER BY TRADE
CONTRACTOR
WASHER &
(2) NUTS
PIPE HANGER DETAIL
MAX.
6"
HANGER ROD
CONCENTRIC TO
JOIST, BETWEEN
CHORD MEMBERS.
ECCENTRIC
CONNECTIONS
ARE PROHIBITED
SEE DETAIL 'B'
FOR TOP PLATE
WELDS & SIZE
STANDARD SHEAR
CONNECTION
WF COL.
CONDITIONS MAY
VARY THIS SIDE
OF COLUMN
3"
3"WF COL.
WELD
CL.
WIDE FLANGE COLUMN
WIDE FLANGE COLUMN
5/16"
FULL
LENGTH
ALONG TOP
PLATE
3"
BOTTOM PLATE MATCH TOP
PLATE THICKNESS x4"xBEAM
FLANGE WIDTH+1
4"
PL. TO
BEAM, TYP
5/16" N.S. F.S.
1/
2"
4 1/2" 3"
TYPICAL MOMENT CONNECTION
PL5/16"
L4x4x5/16 TYP. EACH
SIDE OF OPENING
TYPICAL ROOF OPENING DETAIL
FOR ALL ROOF OPENINGS 12" OR GREATER.
COORD. OPENING SIZES AND LOCATIONS WITH
ARCHITECT & MECHANICAL CONTRACTOR.
BURGLAR BARS MAY OCCUR
COORD. WITH ARCH. &
MECH.
L6x4x3/8x0'-6"
(LLV)
3/16
TYP.
3/16
TYP.
ROOF OPENING
JOIST SPACING - SEE PLAN
POUR
STOP
DECK
CLOSURE
INSULATING CONCRETE ROOF ON METAL DECK
MECH. UNIT CURB
SEE MECH. DWGS.
JOIST MANUF. TO
DESIGN JOIST
UNBRACED AT
RTU LOCATIONS
SEE TYPICAL JOIST
REINFORCING
DETAIL
L REINFORCEMENT REQ'D
WHEN GREATER THAN 6"
STEEL SHIMS @ 2'-0" O.C.
(NOT REQUIRED IF TAPERED
CURBS ARE PROVIDED)
C4x7.25 CONT.
TYPICAL ROOFTOP MECHANICAL
UNIT SUPPORTS FOR INSULATED
CONCRETE ROOF
1/4
*TYP. @EA.
JOIST
3/16
TYP.
USE CAUTION WHEN WELDING AS NOT TO DAMAGE JOIST.*
C4x7.25 CONT.
SEE PLAN
TYPICAL BEAM TO COLUMN
FULL CAPACITY MOMENT CONNECTIONS
STANDARD SHEAR
CONNECTION
BEAM 'A'BEAM 'A'
TOP & BOT.
TYP1/4
TYP
PROVIDE TOP & BOT. PLATES AND
FIELD WELD AS REQ'D. TO DEVELOP
BEAM 'A' MOMENT CAPACITY. TYP.
TOP PLATE WIDTH TO BE 1" LESS
THAN TOP FLANGE WIDTH.
BOTTOM PLATE WIDTH TO BE 1"
WIDER THAN BOTTOM FLANGE
WIDTH.
CAP PL. 1/2" WELD
ALL AROUND TO
COLUMN
1/4
TYP
WT
TYPICAL BEAM TO BEAM
MOMENT CONNECTIONS
STANDARD SHEAR
CONNECTION
PROVIDE TOP & BOT. PLATES AND FIELD WELD AS REQ'D.
TO DEVELOP BEAM 'A' MOMENT CAPACITY. TYP. TOP PLATE
WIDTH TO BE 1" LESS THAN TOP FLANGE WIDTH. BOTTOM
PLATE WIDTH TO BE 1" WIDER THAN BOTTOM FLANGE
WIDTH.
BEAM 'A'BEAM 'B'
STANDARD SHEAR
CONNECTION
PROVIDE TOP & BOT. PLATES AND FIELD WELD AS REQ'D.
TO DEVELOP BEAM 'A' MOMENT CAPACITY. TYP. TOP PLATE
WIDTH TO BE 1" LESS THAN TOP FLANGE WIDTH. BOTTOM
PLATE WIDTH TO BE 1" WIDER THAN BOTTOM FLANGE
WIDTH. PROVIDE SLOT THRU BEAM 'B' WEB FOR THRU
PLATE & WELD ALL AROUND.
BEAM 'A'
PROVIDE TOP & BOT. PLATES AND FIELD WELD AS REQ'D.
TO DEVELOP BEAM 'A' MOMENT CAPACITY. TYP. TOP
PLATE WIDTH TO BE 1" LESS THAN TOP FLANGE WIDTH.
BOTTOM PLATE WIDTH TO BE 1" WIDER THAN BOTTOM
FLANGE WIDTH.
BEAM 'A'BEAM 'B'
STANDARD SHEAR
CONNECTION
BEAM 'B'
ALL TUBE TO TUBE CONNECTIONS
TO BE WELDED ALL AROUND, UNO
SHOP INSTALLED
ERECTION SEAT
(ALTERNATE
LOCATION)
SHOP INSTALLED ERECTION SEAT
(ANGLE REMOVED TO COMPLETE
FIELD WELDING)
TYPICAL TUBE TO TUBE CONNECTION
1/4 T&B
1/4
IF POST IS
WIDER THAN
BEAM
POST & BEAM
OF EQUAL
WIDTH
WF COLUMN
TYPICAL BEAM OVER COLUMN DETAIL
CAP PL3/4"
(4) 3/4"Ø BOLTS
BEAM 'A'
XXX WEB PL N.S. & F.S. WITH
SHORT SLOTTED HOLES
SIZE FOR BEAM 'A' MAX
REACTION
(3) SIDES
TYP
2"
ERECTION BOLTS
BY STEEL
SUPPLIER
METAL DECK
PL 6"x6" MIN. W/13/16"Ø HOLE.
COORDINATE PL THICKNESS
WITH JOIST SUPPLIER
WIDE FLANGE COLUMN
ORIENTATION MAY
VARY
STANDARD SHEAR CONNECTION
DO NOT WELD
CAP PL 1/2"
TYPICAL JOIST TO COLUMN
CONNECTION DETAIL - ROOF
NOTE: BOLT TOP CHORD OF JOIST TO COLUMN. PLUMB
BUILDING. FIELD WELD TOP CHORD AS INDICATED.
K-SERIES-
LH & DLH - SERIES - 1/4 2"
1/8 2"
TYP.
3/16
TYP.
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
BID & CONSTRUCTION
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:5 :0
P M
C R e vi t Lo c a l Fi le s\
S tr u c t _ R m d o ck m a n .r vt
STEEL DETAILS
S-5.0 Checker Designer
CSI-176
NEW MRI SITE PREP
02/20/2020
4100 WEST THIRD ST, DAYTON, OH 45428
18106
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
T/ WALL
SEE ARCH. T/ WALL
SEE ARCH.
T/ WALL
SEE ARCH.
METAL DECK
CONT. L4x4x5/16. SPLICE TO
DEVELOP FULL CAPACITY
OF ANGLE (SEE ANGLE
CHORD SPLICE DETAIL)
6"x18GA CSJ
METAL STUDS
@ 16" O.C.
3 1/2" FastClip SLIDE CLIP
ATTACH TO ANGLE W/
(3) #12-24 TEKS-5
SCREWS
3/16
1/2"
SEE PLAN
METAL DECK
CONT. L4x4x5/16. SPLICE TO
DEVELOP FULL CAPACITY
OF ANGLE (SEE ANGLE
CHORD SPLICE DETAIL)
6"x18GA CSJ
METAL STUDS
@ 16" O.C.
3 1/2" FastClip SLIDE CLIP
ATTACH TO ANGLE W/
(3) #12-24 TEKS-5
SCREWS
BRIDGING PER SJI
(BOLTED BRIDGING
MAY OCCUR)
3/16 3-12
1/2"
SEE PLAN
METAL DECK
CONT. L4x4x5/16. SPLICE TO
DEVELOP FULL CAPACITY
OF ANGLE (SEE ANGLE
CHORD SPLICE DETAIL)
6"x18GA CSJ
METAL STUDS
@ 16" O.C.
SLIDE CLIP, SEE
TYP. DETAIL
3/16
TYP.
1/2"
WF, SEE PLAN
(N) BUILT UP COLD
FORMED BOX
HEADER, SEE PLAN
1/2"
3/16
TYP.
JOIST BEYOND
METAL DECK
6" METAL STUDS
3/16
TYP.
1/2" 1/2"
CONT. L4x4x5/16. SPLICE TO
DEVELOP FULL CAPACITY
OF ANGLE (SEE ANGLE
CHORD SPLICE DETAIL)
METAL STUD
WALL BEYOND
JOIST BEYOND
WF, SEE PLAN
JOIST MAY ALIGN, ADJUST
SEATS ACCORDINGLY
METAL DECK
CONT. BENT PL.5/16. SPLICE
TO DEVELOP FULL
CAPACITY OF THE ANGLE.
(SEE ANGLE CHORD SPLICE
DETAIL)
3 5/8" METAL
STUDS @ 16" O.C.
RIGID CLIP
SEE ARCH.
WF, SEE PLAN
3/16
3/16
L2 1/2"x2 1/2"x3/16"
METAL DECK
3 5/8" METAL
STUDS @ 16" O.C.
RIGID CLIP
WF, SEE PLAN
3/16 3-12
3/16
L3x3x3/16 KICKERS
@ 6'-0" O.C. MAX
CONT. L4x4x5/16. SPLICE TO
DEVELOP FULL CAPACITY
OF ANGLE (SEE ANGLE
CHORD SPLICE DETAIL)
3/16
TYP.
CONT. L4x4x5/16
PL.3/8"
CONT. MC6x12
3/16
6' -0
3' -0
TYP.
PL.1/2"
PL.3/4"
SCREEN WALL
ATTACHMENT TO
STRUCTURE BY MFR.
CONT. GALV.
HSS6x6x1/4
(4) 3/4"Ø
A325 BOLTS
HSS4x4x1/4 GALV.
KICKER, SEE PLAN
HSS6x6x1/4 GALV.
POST, SEE PLAN
PROVIDE HSS6x6x1/4 GALV.
VERTICALS BETWEEN CONT.
MEMBERS @ 6'-0" O.C.
L4x4x5/16x1'-0" LG. W/
3/8" STIFFENER PL.
1/4 N.S. F.S.
CLIP HORIZ. LEG OF L4x4 EDGE
ANGLE AROUND VERT. POST.
PROVIDE PL. 7/16" SPLICE PER
THE ANGLE CHORD SPLICE
DETAIL ON THE VERTICAL LEG
B S-5.1
FABREEKA-TIM PAD
W/ WASHERS AND
BUSHINGS TYP.
PL.1/2"x10"x0'-10"
W/(4) 1/2"Ø HILTI KWIK
BOLT TZ W/ 2" EMBED
3/16
6' -0
3' -0
PL.3/4"x12"x1'-0" W/ (4)
1/2"Ø HILTI KWIK
BOLT TZ W/ 2" EMBED
SCREEN WALL
ATTACHMENT TO
STRUCTURE BY MFR.
CONT. GALV.
HSS6x6x1/4
HSS4x4x1/4 GALV.
KICKER, SEE PLAN
HSS6x6x1/4 GALV.
POST, SEE PLAN
PROVIDE HSS6x6x1/4 GALV.
VERTICALS BETWEEN CONT.
MEMBERS @ 6'-0" O.C. MAX
1' -0
(E) SLAB DECK
DIRECTION MAY VARY
1/2"
(E) WALL BEYOND
CONT. BENT PL.5/16" SPLICE
TO DEVELOP FULL CAPACITY
OF ANGLE, (SEE ANGLE
CHORD SPLICE DETAIL)
METAL DECK
(N) W10
(E) WF
(E) SLAB
DBL L3x3x1/4x0'-5 1/2"
LG. W/(2) 3/4"Ø A325
BOLTS
1/
4" 3"
PLAN
SEE
MC6x12x0'-8" LG.
3/16
6' -0
3' -0
TYP.
PL.1/2"
PL.3/4"
SCREEN WALL
ATTACHMENT TO
STRUCTURE BY MFR.
CONT. GALV.
HSS6x6x1/4
(4) 3/4"Ø
A325 BOLTS
HSS4x4x1/4 GALV.
KICKER, SEE PLAN
HSS6x6x1/4 GALV.
POST, SEE PLAN
PROVIDE HSS6x6x1/4 GALV.
VERTICALS BETWEEN CONT.
MEMBERS @ 6'-0" O.C.
TYP.
L2 1/2x2 1/2x1/4
X-BRIDGING
PL.3/8"x4"x0'-4"
B S-5.1
FABREEKA-TIM PAD
W/ WASHERS AND
BUSHINGS TYP.
3/16
PL.1/2"
PL.3/4"
HSS,
SEE PLAN
TYP.
3/16
WF, SEE PLAN L2 1/2x2 1/2x3/16
BRACES, TYP.
FABREEKA-TIM PAD
W/ WASHERS AND
BUSHINGS TYP.
STEEL JOIST METAL DECK
L4x4 (SEE PLAN) TO
CLEAR JOIST PANEL
POINTS. SIMILAR TO PIPE
HANGER CONN. DETAIL
5/8"Ø
THREADED
ROD, MIN. W/
WASHERS &
(2)-NUTS EA.
END, TYP.
L4x4 W/PREDRILLED HOLES
FOR TEK SCREWS, SEE PLAN
PL.1/4"x5"x0'-5" WELDED ALL AROUND TO L4x4
(2) #12-24 TEK5
SCREWS, TYP.
(2) #12-24
TEK5 SCREWS
L4x4x1/4 W/PREDRILLED
HOLES FOR TEK SCREWS.
FIT SNUGLY BETWEEN JOIST
TOP AND BOTTOM CHORDS,
BEAR ON JOIST BOT.
CHORD AT PANEL POINT
L3x3 BRACE, SEE PLANATTACHMENT OF
TRANSFORMER
TO C6 BY MFR.
(2) C6x8.2. EA.
END OF UNIT
L3x3x1/4, TYP.
UNIT
BRACE PLAN
3/16
TYP.
TYP. 1/4
A S-5.1
EA EDGE OF UNIT
6" MIN. TYP. 3/16
3-SIDES
TYPICAL UNDERHUNG MECHANICAL
UNIT SUPPORT DETAIL
L3x3
L3x3 L3x3
L3x3 BRACE
L4x4 L4x4
HORIZONTAL LEG
CLIPPED AROUND
POST
PL.3/16"x3"x0'-10" 1/4
TYPICAL BOTTOM FLANGE BRACING DETAILS
6" METAL STUDS
@ 16" O.C.
FastClip SLIDE CLIP
SEE TYP. DETAIL
METAL DECK
L3x3x5/16 @ JOIST
NEAREST THIRD POINTS
OF MOMENT FRAME
BEAM (UNO) PL 3/8"
PL 3/8"
T/WALL
SEE ARCH.
3/16
3/16
SEE PLAN
1/2"
6" METAL STUDS
@ 16" O.C.
FastClip SLIDE CLIP
SEE TYP. DETAIL
L3x3x5/16 @ THIRD
POINTS OF MOMENT
FRAME BEAM
PL 3/8",
TYP.
T/WALL
SEE ARCH.
3/16
3/16
SEE PLAN
1/2"
JOIST,
SEE PLAN
3/16
TYP.
CONT. L4x4x5/16. SPLICE TO
DEVELOP FULL CAPACITY
OF ANGLE. SEE ANGLE CHORD
SPLICE DETAIL
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
BID & CONSTRUCTION
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:5 :0
P M
C R e vi t Lo c a l Fi le s\
S tr u c t _ R m d o ck m a n .r vt
FRAMING SECTIONS
S-5.1 Checker Designer
CSI-176
NEW MRI SITE PREP
02/20/2020
4100 WEST THIRD ST, DAYTON, OH 45428
18106
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE:
SECTION
-3/4" = 1'-0"
SCALE: -
DETAIL
3/4" = 1'-0"
A
SCALE:
SECTION
-3/4" = 1'-0"
B
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
S.1
Q.3
Q
P.8
P.5
O.8
O.7
5.2 6.2 6.5 6.8
6.4 6.9 7.9 8.8 9.7
P.81
P.9
Q.4
A100
A101
A113
A106 A107 A108 A110
A111A112
X130
X127
X126
X125
X124
X129
X128
X112
X110
X114X115X116
X120 X121X119
A102E131
A105
A104
A103
E113
E132
X111
X122
X123
X117
X118
A109
CODED NOTES
1. EXTEND EXISTING AUTOMATIC SPRINKLER SYSTEM TO WITHIN OUTLINE AREA. SYSTEM TO BE
INSTALLED IN ACCORDANCE WITH NFPA 13 (2015 EDITION).
2. ALL MATERIALS INSTALLED BELOW SHIELDING SHALL BE NON-FERROUS. SPRINKLER HEADS IN
MRI ROOM SHALL BE NON-FERROUS CONCEALED HEADS.
WALL SECTION
FURNISH AND INSTALL
FIRESTOP MATERIALS IN
ACCORDANCE WITH
APPROPRIATE U.L. SYSTEMS
TO MAINTAIN FIRE RESISTANCE
RATING
PIPE SLEEVE SEE ARCHITECTURAL
DRAWINGS FOR WALL
CONSTRUCTION AND FIRE
RATING
PIPING WITH FREEZE PROTECTION
SELF-REGULATING HEATING CABLE
(WHERE SPECIFIED)
PIPE INSULATION WITH PVC
JACKET (WHERE SPECIFIED)
NOTES:
1. WHERE PIPES, DUCTS AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN
TESTED IN ACCORDANCE WITH U.L. 1479 OR ASTM E814.
2. GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING
MATERIALS AND U.L. SYSTEMS.
3. FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT
CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.
4. THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION
RESULTING FROM HIS WORK.
5. CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ARCHITECT, INCLUDING U.L. RATED SYSTEM
NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.
6. THE FIRESTOPPING SYSTEMS ARE TO BE INSTALLED BY EXPERIENCED, MANUFACTURER TRAINED, AND
UL CERTIFIED OR FM CERTIFIED PERSONNEL.
7. ALL FIRESTOPPING MATERIAL IS TO BE PROVIDED FROM A SINGLE MANUFACTURER FOR ALL
APPLICATIONS.
8. CONTRACTOR SHALL CONSULT MANUFACTURER'S TECHNICAL EXPERTS FOR ASSISTANCE IN SELECTING
APPROPRIATE FIRESTOPPING SYSTEM FOR EACH APPLICATION.
THROUGH FIRE-RATED CONSTRUCTIONS
N.T.S.
FIRESTOPPING DETAIL FOR PENETRATIONS
FIRE PROTECTION NEW WORK GENERAL NOTES
1. THE GENERAL NOTES LISTED HERE APPLY TO ALL FIRE PROTECTION DRAWINGS IN ADDITION TO ANY
ADDITIONAL DRAWING NOTES ON THE INDIVIDUAL DRAWINGS.
2. SEE CODED NOTES ON INDIVIDUAL DRAWING SHEETS FOR SPECIFIC INSTRUCTIONAL NOTES.
3. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF CONSTRUCTION.
4. COORDINATE WITH GENERAL TRADES WORK, HVAC WORK, PLUMBING WORK, ELECTRICAL WORK AND
OTHER WORK.
5. SEE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE WALLS AND RATED
STRUCTURES. SEE DETAILS AND SPECIFICATIONS FOR PIPE PENETRATION SEAL REQUIREMENTS.
6. REFER TO ARCHITECTURAL DRAWINGS FOR ROOM DESIGNATIONS INCLUDING ALL STORAGE AREAS.
ALL STORAGE AREAS ARE TO BE SPRINKLERED AS ORDINARY HAZARD PER N.F.P.A.
7. IT IS RECOGNIZED THAT DRAWINGS MAY BE PLOTTED AT DIFFERENT SCALES, SUCH THAT PLOTTED
DRAWINGS MAY VARY FROM ACTUAL OR INTENDED DIMENSIONS. THEREFORE, DRAWINGS ARE
DIAGRAMMATIC AND ARE NOT TO BE SCALED. SBM TAKES NO RESPONSIBILITY FOR ERRORS REGARDING DISCREPANCIES FROM THE ORIGINAL DRAWINGS DRAWN AT THE PROPER SCALE AND THOSE DRAWINGS
THAT HAVE BEEN PLOTTED.
8. THE FIRE PROTECTION DESIGN DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EXACT LOCATION OF EQUIPMENT AND PIPING UNLESS DIMENSIONS ARE GIVEN OR OTHERWISE IMPLIED FOR CLEARANCES, ETC. PIPING AND FIRE PROTECTION EQUIPMENT ARE TO BE INSTALLED ALONG THE GENERAL PLANS SHOWN ON THE DRAWINGS, BUT KEEPING IN MIND ACTUAL BUILDING CONDITIONS WHICH MUST BE CONFORMED WITH IN THE ACTUAL WORK. THIS CONTRACTOR TO BE AWARE OF LIMITED
SPACE ABOVE CEILING FOR NEW WORK AND SHOULD MODIFY HIS WORK TO ACCOMMODATE OTHER
TRADES. COORDINATE WORK WITH OTHER TRADES PRIOR TO MAKING THE FINAL INSTALLATION DRAWING OR SYSTEM INSTALLATION. THE CONTRACTORS IN THEIR BIDS ARE REQUIRED TO INCLUDE ALL LABOR
AND MATERIALS AND OTHER RELATED WORK NECESSARY TO PROVIDE MINOR OFFSETS IN FIRE
PROTECTION WORK AS REQUIRED TO AVOID CONFLICT WITH OTHER WORK ON THIS PROJECT, OR AS
REQUIRED IN ORDER TO OBTAIN MAXIMUM HEAD ROOM OR EQUIPMENT ACCESS IN SPACES.
9. THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING, PATCHING, REMOVAL, AND RE-INSTALLATION OF WALL, CEILING, FLOORS, ETC. AND NEW MATERIALS FOR THE INSTALLATION OF THEIR RESPECTIVE WORK AS SHOWN ON THE DRAWINGS OR SPECIFICATIONS FOR AREAS OTHERWISE
NOT INVOLVED IN THE GENERAL CONSTRUCTION WORK.
10. ALL SPRINKLER HEADS ARE TO BE QUICK RESPONSE TYPE.
11. ALL FIRE PROTECTION PIPING AND CONDUIT SHALL FOLLOW THE INSTALLATION REQUIREMENTS AS
LISTED BELOW:
A. INSTALL TIGHT AGAINST BOTTOM OF ROOF AND FLOOR STRUCTURE.
B. INSTALL PARALLEL AND PERPENDICULAR TO BUILDING STRUCTURE.
C. INSTALL CONCEALED ABOVE CEILINGS OR INSIDE WALLS, UNLESS OTHERWISE NOTED.
1. SPRINKLER PIPING IS TO AVOID EQUIPMENT IN MECHANICAL ROOM. COORDINATE WITH H.C. AND E.C.
2. USE INTERMEDIATE LEVEL SPRINKLERS BELOW DUCTWORK AND STRUCTURAL MEMBERS, WHERE
APPLICABLE.
3. GENERAL CONTRACTOR SHALL PAINT ALL EXPOSED FIRE PROTECTION PIPING INSIDE AND OUTSIDE
BUILDING WITH COLOR AS SELECTED BY ARCHITECT.
4. ALL VALVES, FLOW SWITCHES, AND ETC. ABOVE THE CEILING SHALL BE LABELED WITH ENGRAVED LAMINATE TAG ATTACHED TO CEILING GRID WITH PRESSURE SENSITIVE TAPE. THE (RED) LAMINATE TAG
SHALL BE 1/2" WIDE WITH 1/4" HIGH ENGRAVED (WHITE) LETTERS.
5. FIRE PROTECTION CONTRACTOR TO COORDINATE FINAL PLACEMENT OF SPRINKLER HEADS WITH REFLECTED CEILING PLANS. SPRINKLER HEADS SHALL BE INSTALLED IN STRAIGHT AND PARALLEL LINES CENTERED IN A SYMMETRICAL AND UNIFORM PATTERN IN THE CEILING TILES (TYP ALL HEADS).
6. SPRINKLER HEADS TO BE PROVIDED IN TYPES AND FINISHES TO MATCH EXISTING AREAS.
7. ALL WORK IS TO COMPLY WITH DESIGN AND INSTALLATION REQUIREMENTS PER NATIONAL FIRE PROTECTION AGENCY 13, VA FIRE PROTECTION DESIGN MANUAL, AND THE OWNER'S INSURANCE
COMPANY. THE MOST STRINGENT REQUIREMENTS SHALL APPLY.
8. FIRE PROTECTION CONTRACTOR SHALL PERFORM WATER FLOW TEST PRIOR TO PERFORMING
HYDRAULIC CALCULATIONS AND SPRINKLER LAYOUT. TEST TO MEET N.F.P.A. REQUIREMENTS.
CONTRACTOR SHALL COORDINATE WHEN TEST IS TO BE PERFORMED WITH OWNER AND COPY TEST
RESULTS TO PROJECT ENGINEER AND OWNER.
9. FIRE PROTECTION CONTRACTOR SHALL HYDRAULICALLY CALCULATE AUTOMATIC SPRINKLER SYSTEM AND INSTALL NEW SYSTEM AS REQUIRED BY NEW CALCULATIONS AND DESIGN. THE FIRE PROTECTION
CONTRACTOR SHALL DESIGN THE SYSTEM, SUBMIT AND ETC. AS LISTED BELOW:
A. COMPLETE AND RETURN A/E AND STATE OF OHIO, DEPARTMENT OF INDUSTRIAL RELATIONS A COPY OF
THE AUTOMATIC SPRINKLER SYSTEM SUPPLEMENT FORM FB-13; THE SUBMITTED PLANS AND
CALCULATIONS MUST ALSO INDICATE THE CERTIFIED INDIVIDUAL INSTALLING THE SPRINKLER SYSTEM
WILL COMPLY WITH VA FIRE PROTECTION DESIGN MANUAL.
B. PLANS FOR THE SPRINKLER SYSTEM SHALL CONTAIN THE FOLLOWING INFORMATION RELATIVE TO THE
WATER SUPPLY:
1. THE PLANS SHALL SHOW THE WATER SUPPLY REQUIREMENTS FOR THE HYDRAULICALLY MOST
DEMANDING AREA. THE DESIGN CALCULATIONS SHALL SUBSTANTIATE THAT THE AVAILABLE WATER
SUPPLY WILL FULFILL THE SYSTEM REQUIREMENTS.
2. THE WATER SUPPLY REQUIREMENTS SHALL BE DETERMINED ACCORDING TO HAZARD CLASSIFICATION
AS OUTLINED IN N.F.P.A. 13.
3. WHEN SPRINKLER SYSTEMS ARE CONNECTED TO CITY WATER MAINS, FLOW TEST RESULTS SHALL BE SUBMITTED. THE PLANS SHALL SHOW THE FOLLOWING INFORMATION ON WATER FLOW DATA WITH
EXISTING OR PROPOSED WATER SUPPLY, DEAD END OR CIRCULATING:
a. LOCATION AND ELEVATION OF STATIC AND RESIDUAL TEST GAGE WITH RELATION TO THE RISER
REFERENCE POINT.
b. FLOW LOCATION.
c. STATIC PRESSURE, PSI
d. RESIDUAL PRESSURE, PSI
e. FLOW, GPM
f. DATE
g. TIME
h. TEST CONDUCTED BY OR INFORMATION SUPPLIED BY
i. PLOTTED GRAPH SHOWING WATER SUPPLY CURVES AND SYSTEM REQUIREMENTS IN ACCORDANCE
WITH SECTIONS 6-3, 6-2.4, AND A-7-2.1 OF N.F.P.A. 13, APPROVED ADDITION.
10. FIRE MAIN TO BE HYDRAULICALLY CALCULATED AND SIZED TO DESIGN INSTALLATION REQUIREMENTS
AS PER N.F.P.A., SECTIONS 13, 14, AND 24.
11. ALL OCCUPIED AREAS OF THE BUILDING ARE TO HAVE A WET PIPE SPRINKLER SYSTEM,
HYDRAULICALLY CALCULATED AND SIZED TO DESIGN INSTALLATION REQUIREMENTS OF N.F.P.A.
SECTIONS 13, 14 AND 24 FOR LIGHT HAZARD OCCUPANCY.
12. IF THE FIRE PROTECTION CONTRACTOR REQUIRES ACCESS PANELS, THE FIRE PROTECTION CONTRACTOR SHALL FURNISH THE ACCESS PANELS WITH INSTALLATION COSTS ASSUMED BY THE FIRE PROTECTION CONTRACTOR, BUT INSTALLED BY THE GENERAL CONTRACTOR.