36C25020B0030-006.pdf

PDF Posted

Attached to
Y1DB--552-CSI-176: New MRI Site Prep (VA-20-00027715)
Solicitation number
36C25020B0030
Issued by

About this file

This pre-solicitation notice announces a forthcoming solicitation for a New MRI Site Prep project at the Dayton VA Medical Center in Dayton, Ohio. The solicitation will require preparation of the site for a new building to house MRI equipment, including all labor, supervision, materials, and equipment, to be completed according to drawings and specifications within 365 calendar days of notice to proceed. The project value is estimated between $2 million and $5 million.

The solicitation will be issued pursuant to 38 U.S.C. 8127 and is a 100% set-aside for service-disabled veteran-owned small businesses. Interested SDVOSBs must be small businesses under the relevant NAICS code of 236220 and registered in verification websites including VIP.vetbiz.gov and SAM.gov. The SDVOSB prime contractor or subcontractor must perform a minimum of 15% of the construction work. Bid, payment and performance bonds will be required. The solicitation and specifications will be posted on March 20, 2020 at FBO.gov, with proposals due approximately 30 days later. A one-time site visit will be scheduled. Amendments will be posted at FBO.gov and questions should be directed to the specified contracting officer by email.

36C25020B0030 Project Drawings (Part 3 of 4).pdf

View the file

Other files

File Type Posted
36C25020B0030-0002001.docx DOCX document
36C25020B0030-0001000.docx DOCX document
36C25020B0030-008.pdf PDF
36C25020B0030-004.pdf PDF
36C25020B0030-007.pdf PDF
36C25020B0030-005.pdf PDF
36C25020B0030-001.docx DOCX document
36C25020B0030-002.pdf PDF
36C25020B0030-003.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TOP OF MANUF. STONE

18' - 0"

EXISTING FIRST FLOOR

0"

P.5 O.7P.81P.9

A110

EQUIPMENT

A111

MRI ROOM

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

1/4" / 1'-0"

ROOF SCREEN WALL ROOF SCREEN WALL

TOP OF MANUF. STONE

18' - 0"

EXISTING FIRST FLOOR

0"

6.29.7 8.8 7.9 6.46.97.3

A111

MRI ROOM

A112

CONTROL ROOM

A113

TOILET

A104

PREP AREA

A103

ENTRANCE

A102

ENTRANCE HALL

AE-501

AE-502

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

MILLWORK REMOVED IN MRI ROOM FOR CLARITY.

REFER TO FLOOR PLAN AND INTERIOR ELEVATIONS

CUBICLE

CURTAIN,

OFOI

TOP OF MANUF. STONE

18' - 0"

EXISTING FIRST FLOOR

0"

8.87.96.9 7.3

TOP OF ROOF (HIGH SIDE)

16' - 3"

A105

SUB WAITING

A112

CONTROL ROOM

A101

LOBBY/WAITING

A111

MRI ROOM

STRUCTURAL

UNI-STRUT

SUPPORT

SYSTEM

PATIENT LIFT

PATIENT RAIL

SYSTEM

SUPPORT RAIL

TIE-ROD BY PATIENT

RAIL MANUFACTURER

METAL

DETECTOR

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :5

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

BUILDING SECTIONS

AE-500

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/4" = 1'-0"AE-500

2 BUILDING SECTION - CROSS

SCALE: 1/4" = 1'-0"AE-500

1 BUILDING SECTION - LONGITUDINAL

SCALE: 1/4" = 1'-0"AE-500

3 BUILDING SECTION - PATIENT LIFT SYSTEM

Revisions Date

65% DD SUBMISSION 07/29/2019

95% CD SUBMISSION 10/07/2019

BID & CONSTRUCTION 12/19/2019

CAM REVIEW 02/21/2020

EXISTING FIRST FLOOR

0"

P.5 O.7P.81P.9Q.4

AE-501

AE-500

AE-510

A103

ENTRANCE

A101

LOBBY/WAITING

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

A100

VESTIBULE

GYP. BD.

SOFFIT POCKET

TOP OF MANUF. STONE

18' - 0"

EXISTING FIRST FLOOR

0"

6.2

6.4 6.9 7.3

A100

VESTIBULE

AE-501

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

A101

LOBBY/WAITING

NEW STOREFRONT SYSTEM

EXTEND STUD AND EXTERIOR

SHEATHING TO DECK

METAL PANEL

COLUMN COVER

PERFORATEDD METAL

PANEL SCREEN WALL

EXISTING ANGLED

MANUFACTURED STONE

VENEER WALL

CANOPY SKYLIGHT

AE-510

SIM

AE-510

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :0

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

BUILDING SECTIONS

AE-501

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/4" = 1'-0"AE-501

1 LOBBY SECTION

SCALE: 1/4" = 1'-0"AE-501

2 BUILDING SECTION - VESTIBULE

Revisions Date

95% CD SUBMISSION 10/07/2019

EXISTING FIRST FLOOR

0"

5/8" GYP. BD. ON 2X4 WOOD

STUD

1 3/4" RF SHIELD WALL

2" ISOLATION

SCHEDULED CEILING REFER

TO CEILING PLAN

RF CEILING

SCHEDULED WALL, REFER

TO FLOOR PLAN

A111

MRI ROOM

A110

EQUIPMENT

TOP OF MANUF. STONE

18' - 0"

EXISTING FIRST FLOOR

0"

9.7 8.8

AE-500

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

AE-511

AE-511

MILLWORK REMOVED FOR CLARITY. REFER TO

FLOOR PLAN AND INTERIOR ELEVATIONS

5/8" GYP. BD. ON 2X4 WOOD

STUD

1 3/4" RF SHIELD WALL

2" ISOLATION

SCHEDULED CEILING REFER

TO CEILING PLAN

RF CEILING

EXTERIOR WALL

AE-511

AE-511

C O

O R

D

IN

A T

E W

IT

H

M R

I M

A N

U F

A C

T U

R E

R

AE-511

RADIATION SHIELDING

(GAUSS LINE SHIELDING)

STRUCTURAL STEEL FRAMING,

PROVIDE 1HR FIREPROOFING (TYP.)

STRUCTURAL STEEL

FRAMING, PROVIDE 1HR

FIREPROOFING (TYP.)

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :0

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

BUILDING SECTIONS

AE-502

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/2" = 1'-0"AE-502

4 RF - Wall

SCALE: 1/2" = 1'-0"AE-502

1 ENLARGED MRI ROOM SECTION

Revisions Date

95% CD SUBMISSION 10/07/2019

EXISTING FIRST FLOOR

0"

P.81

1 3/8" STONE VENEER ON 2" RIGID

INSULATION ON 3/4" GLASS MAT SHEATHING

5/8" GYP. BD. ON 6" METAL STUD

WITH MIN. R-13 BATT INSULATION

TOP OF ROOF (HIGH SIDE)

16' - 3"

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

AE-510

AE-510

AE-510

FOUNDATION AND FOOTER, REFER

TO STRUCTURAL DRAWINGS

PERIMETER FOUNDATION DRAIN,

REFER TO CIVIL DRAWINGS

CANOPY ROOFING SYSTEM

PERFORATED METAL PANEL ROOF SCREEN WALL

METAL PANEL

TOP OF MANUF. STONE

18' - 0"

EXISTING FIRST FLOOR

0"

P.81P.9

AE-511

AE-511

R .O

TOP OF ROOF (HIGH SIDE)

16' - 3"

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

GYP. BD. SOFFIT @14'- 0 1/2" A.F.F.

TPO ROOFING MEMBRANE OVER

TAPERED POLYISOCYANURATE

INSULATION ON METAL DECK

METAL PANEL

AE-510

1 3/8" STONE VENEER ON 2" RIGID

INSULATION ON 3/4" GLASS MAT SHEATHING

5/8" GYP. BD. ON 6" METAL STUD

WITH MIN. R-13 BATT INSULATION

WINDOW SYSTEM

PERFORATED METAL PANEL ROOF SCREEN WALL

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :0

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

WALL SECTIONS

AE-505

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 3/4" = 1'-0"AE-505

1 Wall Section - Typical

SCALE: 3/4" = 1'-0"AE-505

2 Wall Section @ Window

FOUNDATION AND FOOTER, REFER

TO STRUCTURAL DRAWINGS

PERIMETER FOUNDATION DRAIN,

REFER TO CIVIL DRAWINGS

Revisions Date

65% DD SUBMISSION 07/29/2019

95% CD SUBMISSION 10/07/2019

P.81

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

45.00°

ALUMINUM PERFORATED,

CORRUGATED METAL PANELS WITH

ISOLATION TAPE (MT-2)

REFER TO STRUCTURAL DRAWINGS FOR

TUBE STEEL AND ANCHORING. REFER TO

ROOF PLAN FOR POST LOCATIONS

TUBE STEEL KICKER AND POST,

REFER TO STRUCTURAL DRAWINGS

6"

24' - 0"

AE-510

STRUCTURAL STEEL FRAMING

WITH 1HR FIREPROOFING (TYP.)

REFER TO STRUCT. DWGS.

SCHEDULED CEILING

SKYLIGHT ON 12" CURB PROVIDED

BY SKYLIGHT MANUFACTURER

MOISTURE RESISTANT GYP. BD. ON 3 5/8"

METAL STUDS FRAMED OPENING

AE-510

SCHEDULED CEILING

1HR SPRAY-ON

FIREPROOFING (TYP.)

1'-6"

STRUCTURAL STEEL

FRAMING, SEE

STRUCT. DWGS.

COMPOSITE METAL

WALL SYSTEM

SHIM AS REQUIRED

3 5/8" COLD-FORMED

FRAMING

/2

ALUMINUM EXTRUSION

JOINT SYSTEM BY

PANEL MFG.

P.9

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

1'-0"

/2

/2

COMPOSITE METAL

WALL SYSTEM

METAL FASCIA

TPO ROOF MEMBRANE

3/4" PLYWOOD

COLD-FORMED METAL

FRAMING

8" 5/8"

TAPERED INSULATION

STRUCTURAL STEEL

FRAMING, SEE

STRUCT. DWGS.

TPO ROOF MEMBRANE

ROOF DECK, SEE

STRUCT. DWGS.

5/8" EXTERIOR

GYPSUM BOARD

COLD-FORMED METAL

FRAMING

COLD- FORMED

ANCHOR - GRAVITY &

LATERAL

COLD- FORMED

ANCHOR - LATERAL

BENT STEEL PLATE -

SEE STRUCT. DWGS.

VAPOR PERMEABLE

BARRIER

TOP OF MANUF. STONE

18' - 0"

P.81

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

THIN CALCIUM

SILICATE UNIT

STAINLESS STEEL

FLASHING

WATER-RESISTIVE

BARRIER

TPO ROOF MEMBRANE

TAPERED INSULATION

ROOF DECK, SEE

STRUCT. DWGS.

5/8" EXTERIOR

GYPSUM BOARD

BAR JOIST, SEE

STRUCT. DWGS.

2 5/8" 2"3/4" 6"

1'-6"

STRUCTURAL STEEL

FRAMING WITH 1HR

FIREPROOFING (TYP.),

SEE STRUCT. DWGS.

/2

/2

4" RIGID INSULATION

METAL COPING

BLOCKING AS

REQUIRED

ROOF SCREEN PANEL

TPO ROOF MEMBRANE

5/8" ROOFING COVER

BOARD

6" COLD-FORMED

METAL FRAMING

TAPERED INSULATION

CRICKET - SEE ROOF

PLAN

STRUCTURAL STEEL

FRAMING, SEE

STRUCT. DWGS.

TPO ROOF MEMBRANE

TPO ROOF MEMBRANE

SEALANT AND BACKER

ROD

TPO ROOF MEMBRANE

RIGID INSULATIONRIGID INSULATION

ROOF VAPOR BARRIER

PANEL STARTER CLIP

P.81

T.O.S. SCREENWALL

24'-0"

ROOF SCREEN PANEL

STRUCTURAL STEEL

FRAMING, SEE

STRUCT. DWGS.

SHIM AS REQUIRED

CONCEALED

FASTENER

SUPPORT Z

J CHANNEL

S.S. RIVET PAINTED TO

MATCH PANEL

5/8" 3 5/8" 5/8"

2"

/2

'J' BEAD

BLOCKING AS

REQUIRED

EXTERIOR GYPSUM

SHEATHING

CLOSURE TRIM

SKYLIGHT SILL

EXTRUSION

INSULATED LAMINATED

GLASS

GASKET

SEALANT AND BACKER

ROD

WEEP HOLES AT EACH

RAFTER & HIP

SKYLIGHT SILL

EXTRUSION

SKYLIGHT BASE PLATE

0.032" ALUMINUM

APRON

FLEXIBLE FLASHING

ROOF VAPOR BARRIER

TPO ROOF MEMBRANE

RIGID INSULATION

RIGID INSULATION

COVER BOARD

TPO ROOF MEMBRANE

RIGID INSULATION

ROOF VAPOR BARRIER

COLD-FORMED METAL

FRAMING

EXTERIOR GYPSUM

SHEATHING

ROOF DECKING

R13 INSULATION

S K

Y L

IG

H

T M

A N

U F

A C

T U

R E

R

(C

O O

R D

IN

A

T E

W

IT

H

6.8

TOP OF STEEL (LOW SIDE)

15' - 3 1/2"

WATER-RESISTIVE

BARRIER

EXISTING CORE &

SHELL INSULATING

GLASS

WINDOW HEAD

FRAMING MEMBER

5/8" EXTERIOR

GYPSUM BOARD

COLD-FORMED METAL

FRAMING

TPO ROOF MEMBRANE

TAPERED INSULATION

ROOF VAPOR BARRIER

ROOF DECK, SEE

STRUCT. DWGS.

FLEXIBLE FLASHING

5 1/8"

/2

SEALANT AND BACKER

ROD

STAINLESS STEEL

FLASHING

FLEXIBLE FLASHING

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :0

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

DETAILS

AE-510

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1" = 1'-0"AE-510

1 ROOF TOP SCREEN WALL

SCALE: 1" = 1'-0"AE-510

2 SKYLIGHT SECTION

SCALE: 3" = 1'-0"AE-510

6 COLUMN COVER

SCALE: 1 1/2" = 1'-0"AE-510

8 CANOPY METAL PANEL

SCALE: 1 1/2" = 1'-0"AE-510

4 CANOPY ROOF @ WALL

SCALE: 1 1/2" = 1'-0"AE-510

5 SCREEN WALL TOP

SCALE: 3" = 1'-0"AE-510

3 SKYLIGHT CURB

SCALE: 1 1/2" = 1'-0"AE-510

7 STOREFRONT HEAD @ CANOPY

Revisions Date

95% CD SUBMISSION 10/07/2019

EXISTING FIRST FLOOR

0"

P.81

CONCRETE FOUNDATION,

REFER TO STRUCTURAL

DRAINGS

CONCRETE SLAB ON

GRADE, REFER TO

STRUCTURAL DRAWINGS

MIN. R13 BATT

INSULATION

/8

1 3/8"

1 3/8"

2" 5/8" 6" 5/8"

1'-6"

1'-0"

INSULATED SPANDREL

GLASS UNIT

WINDOW SILL FRAMING

MEMBER & SILL

RECEPTOR

BLOCKING AS

REQUIRED

5/8" GYPSUM BOARD

6" COLD-FORMED

METAL FRAMING

1 5/8" LIGHT GAUGE

METAL FRAMING

WATER-RESISTIVE

BARRIER

EXTERIOR GYPSUM

SHEATHING

THIN CALCIUM

SILICATE UNIT

RIGID INSULATION

ALUMINUM STARTER

CHANNEL

STAINLESS STEEL

FLASHING

SEALANT AND BACKER

ROD W/ WEEP VENTS

@ 24"O.C. TO ALIGN W/

CHANNEL WEEPS

FLEXIBLE FLASHING

SEALANT AND BACKER

ROD

STAINLESS STEEL

FLASHING

PLASTIC ISOLATING

SHIM AS REQUIRED

ALUMINUM

INGTERMEDIATE

CHANNEL

(2'X2') 2" PERIMETER

INSULATION

PERIMETER FOUNDATION

DRAIN, REFER TO CIVIL

DRAWINGS

POROUS FILL

FLUID APPLIED

WATERPROOFING

P.81

SCHEDULED CEILING

MIN. R13 BATT

INSULATION

WINDOW HEAD

9'-0"

STAINLESS STEEL

FLASHING

WINDOW HEAD

FRAMING MEMBER

INSULATED GLAZING

UNIT

WINDOW HORIZONTAL

FRAMING MEMBER

INSULATED SPANDREL

GLASS UNIT

/8

/8

5/8" GYPSUM BOARD

6" COLD-FORMED

METAL FRAMING

SEALANT AND BACKER

ROD

SEALANT AND BACKER

ROD - BEHIND

CHANNEL WEEPS

ALUMINUM STARTER

CHANNEL

BLOCKING AS

REQUIRED

THIN CALCIUM

SILICATE UNIT

RIGID INSULATION

WATER-RESISTIVE

BARRIER

2" COLD-FORMED "Z"

EXTERIOR GYPSUM

SHEATHING

PLASTIC ISOLATING

SHIM AS REQUIRED

SEALANT AND BACKER

ROD

1 3/8"

1 3/8"

2" 5/8" 6" 5/8"

1'-0"

1'-6"

COLD-FORMED BOX

HEADER, SEE STRUCT.

DWGS.

MULLION EXTENSION

'J' BEAD

5/8" GYPSUM BOARD

1 5/8" LIGHT GAUGE

METAL FRAMING

EXISTING FIRST FLOOR

0"

8.8

RECESSED RF FLOORING, REFER

TO RF FLOORING DETAIL

PARENT WALL, REFER TO

FLOOR PLAN FOR WALL TYPE

RF WALL, REFER TO RF WALL DETAIL 2" ISOLATION

SCHEDULED BASE

R F

W A

L L P

A N

E L

RECESSED REINFORCED SLAB ON

GRADE, REFER TO STRUCTURAL

DRAWINGS

CONCRETE SLAB ON

GRADE, REFER TO

STRUCTURAL DRAWINGS

SCHEDULED BASE

-1 7/8"

RECESSED FLOOR RF FLOOR PANEL 1

FINISH FLOOR, REFER TO FINISH

SCHEDULE

EXISTING FIRST FLOOR

0"

9.7

WALL FOOTING, REFER TO

STRUCTURAL DRAWINGS

RECESSED RF FLOORING,

REFER TO RF FLOORING DETAIL

RF SHIELDED WALL; REFER TO RF WALL

DETAIL

1" FILLER

2" ISOLATION SPACE

SCHEDULED BASE

CONCRETE SIDEWALK;

REFER TO CIVIL DRAWINGS

-1 7/8"

RECESSED FLOORRF FLOOR PANEL

FINISH FLOOR, REFER TO FINISH

SCHEDULER

F W

A L L P

A N

E L

/8

THIN CALCIUM

SILICATE UNIT

ALUMINUM

INGTERMEDIATE

CHANNEL

SHIM AS REQUIRED

SEALANT AND BACKER

ROD

RIGID INSULATION

2" COLD-FORMED "Z"

FLEXIBLE FLASHING

ALUMINUM STARTER

CHANNEL

STAINLESS STEEL

FLASHING

WATER-RESISTIVE

BARRIER

3/4" PLYWOOD

6" COLD-FORMED

METAL FRAMING

6"3/4"2"

1 1/4"

1 3/8"

1'-6"

PERIMETER FOUNDATION

DRAIN

(2'X2') 2" PERIMETER

INSULATION

FLUID APPLIED

WATERPROOFING

POROUS FILL

CONCRETE SLAB ON GRADE

BRONZE SPRAYED STRUCTURAL

AND ELECTRICAL SEAM CLAMP

1/4 - 20 FLAT HEAD SELF THREADING SCREW

POLYETHYLENE UNDERLAYMENT

(2 LAYERS MIN. 4MIL EACH)

3/4" RF FLOOR PANEL WITH 3OZ

COPPER ON TOP SIDE

1/8" SUB -FLOOR

1/8" VINYL FILLER TILE

1/8" HARDBOARD LEVELING LAYER

COORDINATE OVERALL FLOOR DEPTH WITH RF

PANEL MANUFACTURER AND MRI MANUFACTURER

FINISH FLOOR, REFER TO FINISH SCHEDULE

MRI EQUIPMENT BASEPLATE AND

HARDBOARD LEVELING LAYER, COORDINATE

WITH MRI EQUIPMENT MANUFACTURER

8.8

R F

W A

L L P

A N

E L

SOLID SURFACE SILL,

COORDINATE WITH RF VENDOR

RF WINDOW

CONTROL ROOM COUNTER WITH

BACKSPASH, REFER TO INTERIOR

ELEVATIONS

2" ISOLATION SPACE

PARENT WALL, REFER TO

FLOOR PLAN FOR WALL TYPE

RF WALL, REFER TO RF WALL

WALL DETAIL

MRI ROOM COUNTER WITH

BACKSPASH; REFER TO

INTERIOR ELEVATIONS

SOLID SURFACE SILL,

COORDINATE WITH RF VENDOR

5/8" 3 5/8"

2"1 3/4"

3 1/2" 5/8"

SHIM AS REQ'D. BY RF

MANUFACTURER

8.8

R F

W A

L L P

A N

E L

MRI ROOM LAY-IN CEILING, REFER

TO REFLECTED CEILING PLAN AND

FINISH SCHEDULE

RF WINDOW

CONTROL ROOM LAY-IN

CEILING, REFER TO

REFLECTED CEILING PLAN AND

FINISH SCHEDULE

CLIPS & FASTENERS PER SHIELDING

MANUFACTURER'S RECOMMENDATION.

TYPICAL. DO NOT PENETRATE THROUGH

SHIELDING.

RF CEILING PANEL BY RF

SHIELDING MANUFACTURER

RADIATION SHIELDING (GAUSS LINE

SHIELDING). REFER TO SIEMENS SHIELDING

REPORT FOR ADDITIONAL INFORMATION

SCHEDULED CEILING. REFER TO

FINISH SCHEDULE

SUPPORT SYSTEM TO STRUCTURE

ABOVE PER MANUFACTURER'S

RECOMMENDATION

EXTERIOR WALL CONSTRUCTION, REFER

TO WALL SECTIONS

C O

O R

D

IN

A T

E W

IT

H

M R

I M

A N

U F

RF SHIELD WALL PANEL

5/8" GYP. BD. ON 2X4 WOOD STUD

2" ISOLATION

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :0

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

DETAILS

AE-511

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1 1/2" = 1'-0"AE-511

1 WINDOW - DETAIL @ SILL

SCALE: 1 1/2" = 1'-0"AE-511

2 WINDOW - DETAIL @ HEAD

SCALE: 1 1/2" = 1'-0"AE-511

3 ENLARGED RF FLOOR/WALL SHIELD SECTION

SCALE: 1 1/2" = 1'-0"AE-511

6 ENLARGED RF FLOOR SHIELD SECTION

SCALE: 6" = 1'-0"AE-511

8 RF FLOORING

SCALE: 1 1/2" = 1'-0"AE-511

4 ENLARGED RF WINDOW SILL SECTION

SCALE: 1 1/2" = 1'-0"AE-511

5 ENLARGED RF WINDOW HEAD SECTION

SCALE: 1 1/2" = 1'-0"AE-511

7 ENLARGED RF CEILING DETAIL

Revisions Date

95% CD SUBMISSION 10/07/2019

4'

- 0

1/ 4"

/4

1"

NOTES:

1. SEE RCP FOR CEILING HEIGHTS.

2. CEILING TRACKS TO BE LOCATED 3"

OFF OF WALL, UNLESS OTHERWISE

NOTED

STEEL L 1"x1"x1/8"x4'-0"

LONG W/ LEGS TURNED

DOWN 3/4" ANCHOR TO

MAIN

TEES W/ #8 SHEET METAL

SCREWS

SPACER

FASTEN 30" O.C. MAX.

CEILING GRID

CUBICLE TRACK

CEILING TILE

NOTE:

PATIENT LIFT TRACK TO BE SUPPORTED ABOVE CEILING BY

ENGINEERED MEDICAL SUPPORT SYSTEM, COORDINATE WITH

ALL TRADES FOR LOCATIONS AND MOUNTING INSTRUCTIONS.

CL STRAIGHT SECTION

TRACK, RCP FOR LOCATIONS

SCHEDULED CEILING

NOTE: SEE RCP FOR CEILING HEIGHTS

M

IN

M

IN

4 7/8"

ACOUSTICAL

CEILING PANEL

ACOUSTICAL

CEILING PANEL

ALIGN WITH EDGE

OF WALL BEYOND

1/2" MAX

3 1/8"

1 7/8"

METAL CONTROL JOINT

DOUBLE STUD @ DOORS

GYP. BOARD, SEE

PARTITION TYPES

METAL STUD

1/2" FIRE RESISTIVE GYP.

BD.

(FULL HEIGHT OF PARTITION)

NOTE:

CONTROL JOINT TO OCCUR AT CORNERS OF ALL GYPSUM

BOARD OPENINGS AND 30'-0" MAX. AT ALL GYPSUM BOARD

PARTITIONS TO STRUCTURE ABOVE.

CONTINUOUS

SEALANT ON

ALL SIDES

P L A

N

S E

E

PLAN

SECTION

CONTINUOUS SEALANT

ALL SIDES

CONTINUOUS SEALANT

ALL SIDES

METAL STUD FRAMING

METAL STUD FRAMING

FIRE EXTINGUISHER

CABINET (F.E.C.)

SEMI RECESSED

CABINET

3x3x3/8 STEEL POST AND

1/4" BASE PLATE FROM

FLOOR TO DECK ABOVE

WOOD BLOCKING

SCHEDULED PARTITION

NEW GRAB BAR

CL

P.81

7.9

10 1/4" 1'-1 3/8"

G

C

G

(2)

LOCKER

UNITS

(L-1)

STRUCTURAL STEEL WITH

1HR FIREPROOFING (TYP.)

P.81

8.8

/4

2'-11 1/8" 10 1/4"

CG-1

G

G C

G

OVERFLOW

DOWNSPOUT WITH

REMOVABLE

SCREEN

ROOF DRAIN PIPING STRUCTURAL STEEL WITH

1HR FIREPROOFING (TYP.)

P.81

1'-3"

CG-1

OVERFLOW

DOWNSPOUT WITH

REMOVABLE

SCREEN

G

G

G

C

ROOF DRAIN PIPING

P.81

9.7

G

G

/4

1'-4 1/4"

CG-1

STRUCTURAL STEEL WITH

1HR FIREPROOFING (TYP.)

O.7

7.9

/4

8" 8"

C

G

G

GG

STRUCTURAL STEEL WITH

1HR FIREPROOFING (TYP.)

O.7

8.8

G

10 1/4"

2'-3 7/8"

/4

2'-2"

10 1/4" 1 7/8"

STRUCTURAL STEEL WTH

1HR FIREPROOFING (TYP.)

O.7

9.7

/4

1'-0 7/8"

11 5/8"

MANUFACTURED

STONE VENEER WALL

STRUCTURAL STEEL WITH

1HR FIREPROOFING (TYP.)

P.81

THIN CALCIUM

SILICATE UNIT -

FINISHED END UNIT

RIGID INSULATION

2" COLD-FORMED "Z"

WATER-RESISTIVE

BARRIER

3/4" PLYWOOD

6" COLD FORMED

STRUCTURAL FRAMING

AT 16" O.C MAX.

INSULATED SPANDREL

GLASS UNIT

WINDOW JAMB

FRAMING MEMBER

/8

/4

/4

/8

5/8" GYPSUM BOARD

BLOCKING AS

REQUIRED -

LIGHT GAUGE

FRAMING -

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :1

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

INTERIOR DETAILS AND SECTIONS

AE-700

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1 1/2" = 1'-0"AE-700

1 CURTAIN TRACK ISOMETRIC

SCALE: 3" = 1'-0"AE-700

2 CEILING_UNISTRUT

SCALE: 1 1/2" = 1'-0"AE-700

3 CEILING_GYPSUM BOARD

SCALE: 3" = 1'-0"AE-700

4 GYPSUM BOARD CONTROL JOINT

SCALE: 1" = 1'-0"AE-700

5 FEC CABINET_SEMI RECESSED

SCALE: 1 1/2" = 1'-0"AE-700

6 GRAB BAR SUPPORT

SCALE: 1" = 1'-0"AE-700

8 PLAN DETAIL

SCALE: 1" = 1'-0"AE-700

9 PLAN DETAIL

SCALE: 1" = 1'-0"AE-700

7 PLAN DETAIL

SCALE: 1" = 1'-0"AE-700

10 PLAN DETAIL

SCALE: 1" = 1'-0"AE-700

12 FIRST FLOOR PLAN - Callout 5

SCALE: 1" = 1'-0"AE-700

13 FIRST FLOOR PLAN - Callout 6

SCALE: 1" = 1'-0"AE-700

14 FIRST FLOOR PLAN - Callout 7

SCALE: 1 1/2" = 1'-0"AE-700

11 WINDOW JAMB DETAIL

Revisions Date

65% DD SUBMISSION 07/29/2019

95% CD SUBMISSION 10/07/2019

PLASTIC LAMINATE ON

MDF

BASE CABINET

PLASTIC

LAMINATE

ADJUST. SHELF

DRAWER

/2

/8

/8

/8

/8

3" SCHEDULED BASE

PROVIDE COMMON

BLOCKING, FURRING AND

HANGING DEVICES

SOLID SURFACE MATERIAL

COUNTERTOP AND

BACKSPLASH

25"

1/2" 25"

/2

/2

" SOLID SURFACE MATERIAL

COUNTERTOP AND

BACKSPLASH

METAL SUPPORT

BRACKET

PENCIL DRAWER

1/2"

1"

PROVIDE COMMON

BLOCKING, FURRING AND

HANGING DEVICES

SCHEDULED BASE

PLASTIC

LAMINATE

FASCIA

PANEL

METAL SUPPORT

BRACKET

SCHEDULED BASE

PROVIDE COMMON

BLOCKING, FURRING AND

HANGING DEVICES

GROMMET,

COORD.

LOCATIONS WITH

OWNER

25"

/2

SOLID SURFACE MATERIAL

COUNTERTOP AND

BACKSPLASH

1/2"

PLASTIC LAMINATE ON

MDF

BASE CABINET

DRAWER

SCHEDULED BASE

PROVIDE COMMON

BLOCKING, FURRING AND

HANGING DEVICES

/8

/8

/8

/8

/8

/8

/2

3"

DRAWER

DRAWER

SOLID SURFACE MATERIAL

COUNTERTOP AND

BACKSPLASH

25"

1/2"

PLASTIC LAMINATE ON

MDF

BASE CABINET

SINK

/2

/8

/8

/8

/8

SCHEDULED BASE

PROVIDE COMMON

BLOCKING, FURRING AND

HANGING DEVICES

3"

SOLID SURFACE

MATERIAL

COUNTERTOP AND

BACKSPLASH WITH

INTEGRAL SINK

25"

1/2"

/2

1/2" SOLID SURFACE

MATERIAL

1 1/2"

EASED

EDGE

SUBSTRAT

E

/2

1/2" SOLID SURFACE

MATERIAL

EASED

EDGE

DOOR/DRAW

ER MAY

OCCUR

1"

SUBSTRAT

E

SUBSTRAT

E

/2

1/2" SOLID SURFACE

MATERIAL

EASED

EDGE

DOOR/DRAW

ER MAY

OCCUR

1"

3/4"

1 1/2" DEPTH 1" DEPTH 3/4" DEPTH

PLASTIC LAMINATE ON ALL

EXPOSED SURFACES

UNDER CABINET LIGHTING

MAY OCCUR; REFER TO

ELECTRICAL DWGS.

PLASTIC LAMINATE ON MDF

ADJUST. SHELVES

14"

PROVIDE COMMON BLOCKING,

FURRING AND HANGING DEVICES

CEILING. SEE REFLECTED

CEILING PLANS FOR HEIGHTS.

GYP. BD. SOFFIT, REFER TO

INTERIOR ELEVATIONS

1"

PROVIDE COMMON BLOCKING,

FURRINGAND HANGING DEVICES

PROVIDE COMMON BLOCKING,

FURRING AND HANGING

DEVICES

SCHEDULED BASE

PLASTIC LAMINATE ON ALL

EXPOSED SURFACES

PLASTIC LAMINATE ON MDF

ROLLING SHELVES

PROVIDE COMMON BLOCKING,

FURRING AND HANGING

DEVICES

24"

CEILING. SEE REFLECTED

CEILING PLANS FOR HEIGHTS.

GYP. BD. SOFFIT, REFER TO

INTERIOR ELEVATIONS

1"

U .O

.N

/1

MIN.

8 1/4"

U.O.N.

24 1/4"

NOTE: LOOSE

BACKSPLASH TO

OCCUR ONLY AT

WET LOCATIONS

SOLID SURFACE

TOP W/ INTEGRAL

SINK BOWL, NO

DRIP EDGE

PLYWOOD

SUBSTRATE

REMOVABLE HIGH

PRESSURE

DECORATIVE

LAMINATE PANEL

CONCEALED

COUNTERTOP

SUPPORT

BRACKETS, TYP.

SCHEDULED WALL

BASE, TYP.

MAX.

6".

PROVIDE COMMON BLOCKING,

FURRING AND HANGING

DEVICES

PLASTIC LAMINATE ON ALL

EXPOSED SURFACES

PROVIDE COMMON BLOCKING,

FURRING AND HANGING

DEVICES

36"

FULL LENGTH CABINET

DOORS

CEILING. SEE REFLECTED

CEILING PLANS FOR HEIGHTS.

GYP. BD. SOFFIT, REFER TO

INTERIOR ELEVATIONS

1"

PLASTIC LAMINATE ON ALL

EXPOSED SURFACES

PROVIDE COMMON

BLOCKING, FURRING AND

HANGING DEVICES

CEILING. SEE REFLECTED

CEILING PLANS FOR HEIGHTS.

PLASTIC LAMINATE ON MDF

ADJUST. SHELVES

SCHEDULED BASE

24"

R F

S H

IE

L D

O

P E

N

IN

G

C O

O R

D

W

IT

H R

F V

E N

D O

R

PLASTIC LAMINATE ON ALL

EXPOSED SURFACES

COODINATE TOP OF

CABINET WITH RF & MRI

MANUFACTURER

1. ALL BASE CABINETS, WALL CABINETS, AND TALL CABINETS SHALL BE

PLASTIC LAMINATE WITH FINISHED ENDS WHERE REQUIRED, UNLESS

OTHERWISE NOTED.

2. ALL WALL CABINETS SHALL HAVE PLASTIC LAMINATE FACE RAIL TO

CONCEAL UNDERCABINET LIGHT FIXTURE UNLESS OTHERWISE NOTED.

3. ALL COUNTERS AND SPLASHES SHALL BE PLASTIC LAMINATE WITH

FINISHED ENDS, UNLESS OTHERWISE NOTED.

4. ALL SPLASHES SHALL BE 4" HIGH, UNLESS OTHERWISE NOTED. RETURN ALL

SPLASHES AT SIDE WALLS.

5. ALL SHELVING INDICATED SHALL BE ADJUSTABLE, PLASTIC LAMINATE WITH

FINISHED EDGES, UNLESS OTHERWISE NOTED.

6. ALL FILLER PANELS, COUNTER SUPPORT PANELS, BACK PANELS, END

PANELS, AND CLOSURE PANELS SHALL BE PLASTIC LAMINATE, UNLESS

OTHERWISE NOTED.

7. ALL BACK PANELS AT KNEE SPACES SHALL BE REMOVABLE.

8. ALL DOORS AND DRAWERS MARKED WITH "L" INDICATED SHALL HAVE

LOCKS. SEE INTERIOR ELEVATIONS.

9. ALL FILE DRAWERS (FD) SHALL HAVE "SUSPENSION FILE" RACKS. SEE

INTERIOR ELEVATIONS.

GYP. BD. SOFFIT, REFER TO

INTERIOR ELEVATIONS

PLASTIC LAMINATE ON ALL

EXPOSED SURFACES

EQUIPMENT (N.I.C.)

COORDINATE WITH END USER

PROVIDE COMMON BLOCKING,

FURRING AND HANGING

DEVICES

OUTLET, SEE ELECTRICAL

DWGS.

14"

CEILING. SEE REFLECTED

CEILING PLANS FOR HEIGHTS.

1"

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :1

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

MILLWORK SECTIONS

AE-701

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 3/4" = 1'-0"AE-701

3 BASE CABINET w/ DRAWER

SCALE: 3/4" = 1'-0"AE-701

2 COUNTERTOP with DRAWER

SCALE: 3/4" = 1'-0"AE-701

1 COUNTERTOP

SCALE: 3/4" = 1'-0"AE-701

5 DRAWER (3)

SCALE: 3/4" = 1'-0"AE-701

4 SINK BASE

SCALE: 3" = 1'-0"AE-701

20 06_EASED EDGE 1 1/2"_SSM

SCALE: 3/4" = 1'-0"AE-701

7 WALL with TASK

SCALE: 3/4" = 1'-0"AE-701

8 TALL CABINET

SCALE: 1" = 1'-0"AE-701

19 SINK BASE W/ REMOVABLE PANEL

SCALE: 3/4" = 1'-0"AE-701

9 TALL CABINET NO SHELF

SCALE: 3/4" = 1'-0"AE-701

10 FILTER CABINET WITH CABINET BELOW

MILLWORK GENERAL NOTES

SCALE: 3/4" = 1'-0"AE-701

6 OPEN CABINET

Revisions Date

65% DD SUBMISSION 07/29/2019

95% CD SUBMISSION 10/07/2019

RF VIEW WINDOW

AE-701

SCHEDULED

BASE, TYP.

END PANEL

SS-2

PL-12

AE-701

METAL SUPPORT

BRACKET

2'-0"

AE-701

1'-3" 1'-3"

AE-500

FECSCHEDULED

BASE, TYP.

RF SHIELDED DOOR

IRWC-1

IRWC-1

B

COUNTER

TOP

F L U

S H

V

A L V

E

ROBE

HOOK

(RH)

FRAMED

MIRROR

(FM)

SHOWER

CURTAIN

ROD

(SCR)

TOWEL

BAR

(TB)

ACCESSORIES

PAPER

TOWEL

DISPENSER

(PTD)

GRAB BAR

(GB), SEE

DET.6/AE700

TOILET

TISSUE

DISPENSER

(TTD)

SANITARY

NAPKIN

DISPOSAL

(SND)

URINAL

PLUMBING

LAVATORY TOILET DUPLEX RECEPT.,

DATA, INTERCOM

OR TELEPHONE

OUTLET

WALL SWITCH

OR DUPLEX

OUTLET

AT COUNTER

TOP

WALL SWITCH,

T-STAT,

PUSH PLATE

ELECTRICAL

TOILET

SEAT

COVER

DISPENSER

(SCD)

NOTE:

MOUNTING HEIGHTS ARE AS INDICATED UNLESS OTHERWISE NOTED.

NOT ALL ACCESSORIES / FIXTURES MAY BE USED.

BABY

CHANGING

STATION

(BCS)

FIRE

EXTINGUISHER

CABINET

(FEC), SEE

DET. 5/AE-700

A D

A

A D

A

S T

A N

D A

R D

C O

O R

D w

" 6

A

D A

S T

A N

D A

R D

" 4

CL

(39"- 41")

40"

(3

CL

MAX

12"

FINISHED WALL

CL

18"

36" MIN.

42"

C O

O R

D

W F

L U

S H

V A

L V

E

FLUSH

CONTROL

8"

24"

M

IN

M

A X

M

IN

24" TOILET TISSUE

DISPENSER

FINISHED

WALL

7"

SANITARY NAPKIN

DISPOSAL

GRAB BAR

GRAB BAR

M A

X

GLOVE

DISPENSER

SPECIMEN

PASS - THRU

CABINET

(SPC)

M

A X

M

IN

MOP BASIN

SERVICE FAUCET

& CONTROLS

MOP BROOM HOLDER

UTILITY SHELF

MOP AND BROOM

HOLDER WITH SHELF

WATER

COOLER

STANDING

A D

A

S T

A N

D A

R D

CLEARANCE

60" MIN.

CLEARANCE

56" MIN.

MOP AND BROOM

HOLDER WITH SHELF

(MBH)

FINISHED

WALL

18"

CL

COMBINATION

TOWEL

DISP. AND

WASTE

RECEPT.

(CTD)

S T

A N

D A

R D

M

A X

A

D A

TOILET

SCHEDULED BASE, TYP.

OPEN TO

BEYOND

4'-4 1/8"

MED-GAS

ZONE VALVE,

REFER TO

PLUMB. DWGS.

METAL

DETECTOR

IRWC-1

IRWC-1

AE-701

AE-701

SCHEDULED BASE, TYP.

OMNICELL (OFOI)

SS-2

PL-12

PL-12

OPEN SHELF

WITH TASK

LIGHT

1'-3" 2'-0" 1'-3"

1'-3" 2'-0" 1'-3"

L L

L

L

L

L

L

L

AE-500

L = LOCKABLE

GYP. BD. SOFFIT

OPENING FOR PATIENT LIFT,

COORDINATE WITH PATIENT

LIFT MANUFACTURER

MED GAS ALARM

PANEL, REFER TO

PLUMB. DWGS.

METAL

DETECTOR, OFCI

MFD (OFOI)

IRWC-1

SCHEDULED BASE, TYP.

SS-2 SS-2

HTD-1

TR-2

TR-1

CT-1

CT-3

TR-3

PT-2/A

CT-1

TR-2

PT-2/A

TR-1

GB-2

GB-3

TTD-1

PT-2/A

CT-1

TR-2

TR-1

GB-1

GB-3

FM-1

SF-1

2'-0"

1'-6" 8"

CT-3 TR-3

TR-1

RF VIEW WINDOW

AE-701

AE-701

SCHEDULED BASE, TYP.END

PANEL

SS-2

SUPPORT BRACKET,

TYP.

AE-500

B

FILTER PANEL CABINET

SCHEDULED BASE, TYP.

4'-4"

SS-2

SUPPORT BRACKET,

TYP.

AE-701

OUTLINE OF IMAGE. OWNER

PROVIDED CONTRACTOR INSTALLED.

COORDINATE WITH COR

PL-12

PL-12

OUTLINE OF

10'-0"W X 8'-0"H

KNOCK OUT PANEL

SCHEDULED

BASE, TYP.

AE-701

AE-701

SCHEDULED BASE, TYP.

SS-2

PL-12

PL-12

PL-12

AE-701

3'-0 1/8" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"

PL-12PL-12PL-12PL-12PL-12

3 EQ. SPACES

7'-3"

GYP. BD. SOFFIT

AE-701

AE-701

AE-501

2 EQ.

42"

2 EQ.

42"

SCHEDULED BASE, TYP.

SS-2

PL-12

PL-12

IRWC-1

SCHEDULED BASE, TYP.

SS-2

IRWC-1

OPEN TO BEYOND

SCHEDULED BASE, TYP.

TV (OFOI)

IRWC-1

OUTLINE CASE WORK

REMOVED FOR CLARITY

ISOCENTER

OF MAGNET

ISOCENTER

OF MAGNET

IRWC-1

SCHEDULED BASE

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :1

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

INTERIOR ELEVATIONS

AE-800

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/4" = 1'-0"AE-800

3 CONTROL ROOM / CORRIDOR - SOUTH

MOUNTING HEIGHTS LEGEND

SCALE: 1/4" = 1'-0"AE-800

2 CONTROL ROOM - EAST

SCALE: 1/4" = 1'-0"AE-800

1 CONTROL ROOM / CORRIDOR - NORTH

SCALE: 1/4" = 1'-0"AE-800

4 CONTROL ROOM - WEST

SCALE: 1/4" = 1'-0"AE-800

6 TOILET - NORTH

SCALE: 1/4" = 1'-0"AE-800

7 TOILET - EAST

SCALE: 1/4" = 1'-0"AE-800

8 TOILET - SOUTH

SCALE: 1/4" = 1'-0"AE-800

9 TOILET - WEST

SCALE: 1/4" = 1'-0"AE-800

10 MRI - NORTH

SCALE: 1/4" = 1'-0"AE-800

11 MRI - EAST

SCALE: 1/4" = 1'-0"AE-800

12 MRI - SOUTH

SCALE: 1/4" = 1'-0"AE-800

13 MRI - WEST

SCALE: 1/4" = 1'-0"AE-800

16 PREP AREA - WEST

SCALE: 1/4" = 1'-0"AE-800

15 PREP AREA - SOUTH

SCALE: 1/4" = 1'-0"AE-800

14 PREP AREA - EAST

SCALE: 1/4" = 1'-0"AE-800

5 CORRIDOR - EAST

Revisions Date

65% DD SUBMISSION 07/29/2019

95% CD SUBMISSION 10/07/2019

SCHEDULED WALL BASE, TYP.

PATIENT LIFT

PATIENT RAIL

SYSTEM

TV (OFOI)

IRWC-1

SCHEDULED BASE, TYP.

PATIENT LIFT

IRWC-1

SCHEDULED WALL BASE, TYP.

IRWC-1

AE-500

SCHEDULED WALL BASE, TYP.

AE-500

IRWC-1

AE-501

SCHEDULED WALL

BASE, TYP.

STOREFRONT

WINDOW SYSTEM

OPEN TO

BEYOND

SCHEDULED

WALL BASE, TYP.

AE-500

EQ EQ

CL

LINEAR WALL DIFFUSER,

REFER TO MECH. DWGS.

AE-501

SCHEDULED WALL BASE, TYP.

3'-10" CL

TV (OFOI)

LINEAR WALL DIFFUSER,

REFER TO MECH. DWGS.

(2)

LOCKER

UNITS

(L-1)

SCHEDULED BASE, TYP.

SPANDREL PANEL

BEHIND

AE-701

AE-701

2 EQ.

42"

2 EQ.

42"

SCHEDULED BASE, TYP.

SS-2

PL-12

PL-12

GYP. BD. SOFFIT

(2)

LOCKER

UNITS

(L-1)

SCHEDULED BASE, TYP.

SPANDREL PANEL

BEHIND

AE-701

AE-701

2 EQ.

42"

2 EQ.

42"

SCHEDULE BASE, TYP.

SS-2

PL-12

PL-12

GYP. BD. SOFFIT

STOREFRONT

WINDOW SYSTEM

MANUFACTURED

STONE VENEER

WALL SYSTEM

SCHEDULED BASE, TYP.

TV (OFOI)

IRWC-1

SCHEDULED BASE, TYP.

TV (OFOI)

IRWC-1

AE-501

OPEN TO

BEYOND

IRWC-1

SCHEDULED BASE

OUTLINE OF NEW

MANUFACTURED STONE

VENEER WAL SYSTEM

EXISTING MANUFACTURED

STONE SYSTEM

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :2

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

INTERIOR ELEVATIONS

AE-801

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/4" = 1'-0"AE-801

1 SUB WAITING - EAST

SCALE: 1/4" = 1'-0"AE-801

2 SUB WAITING - SOUTH

SCALE: 1/4" = 1'-0"AE-801

3 SUB WAITING - WEST

SCALE: 1/4" = 1'-0"AE-801

4 SUB WAITING - NORTH

SCALE: 1/4" = 1'-0"AE-801

5 LOBBY/WAITING - EAST

SCALE: 1/4" = 1'-0"AE-801

6 LOBBY/WAITING - SOUTH

SCALE: 1/4" = 1'-0"AE-801

7 LOBBY/WAITING - WEST

SCALE: 1/4" = 1'-0"AE-801

11 DRESSING 107 - EAST

SCALE: 1/4" = 1'-0"AE-801

12 DRESSING 107 - WEST

SCALE: 1/4" = 1'-0"AE-801

9 DRESSING 106 - EAST

SCALE: 1/4" = 1'-0"AE-801

10 DRESSING 106 - WEST

SCALE: 1/4" = 1'-0"AE-801

15 VESTIBULE - WEST

SCALE: 1/4" = 1'-0"AE-801

8 DRESSING 106 - SOUTH

SCALE: 1/4" = 1'-0"AE-801

13 DRESSING 107 - NORTH

SCALE: 1/4" = 1'-0"AE-801

14 ENTRANCE - EAST

SCALE: 1/4" = 1'-0"AE-801

16 VESTIBULE - NORTH

Revisions Date

95% CD SUBMISSION 10/07/2019

P.5

O.7

6.25.2

P.81

9.78.87.96.4 6.9

P.9

Q.4

AE-500

AE-505

10' - 0"

AE-505

SIM.

AE-700

AE-700

7.3

13' - 0"

AE-501

AE-500

AE-510

AE-501

8'-6"

CL

ISOCENTER OF MAGNET

CL

EQ EQ

2'-6"

5'-0" 2'-0"

.0

30.00°

15.00°

.0

13'-5" 8'-10"

/8

ELLIPTICAL DISPLAY

LIGHTING8'-0"

QUENCH VENT; COORDINATE

WITH MRI VENDOR AND

MECHANICAL DAWINGS

"9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

OPEN TO

ABOVE

2'-0"

E Q

E Q

EQ EQ

EQ EQ

E Q

E Q

EQ EQ

6'-6" 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"

/4

E Q

E Q

EQ EQ

1'-10"

MATCH CELING HEIGHT

AND DIRECTION

EXISTING CEILING

SYSTEM TO REMAIN

MATCH CELING HEIGHT

AND DIRECTION

PATIENT LIFT RAIL

SYSTEM

/8

/8

4'-2" 4'-1"

2'-1" 4'-2"

R 25'-0"

14' - 0"

EXISTING CEILING

SYSTEM TO REMAIN

6'-4 1/2" 6'-5 1/8" 6'-5 1/8" 6'-5 1/8" 6'-5 1/8"

EXPOSED TO

STRUCTURE ABOVE

E Q

E Q

7' - 2" 7' - 2"

7' - 2"

7' - 2"

7' - 2"

9' - 0"

8' - 6"

EXISTING SOFFIT TO

REMAIN

EXISTING SOFFIT TO

REMAIN

OPENING FOR

FILTER CABINET

5'-0"

/8

/8

/8

6'-5 3/4" 8'-3" 20'-3" 22'-3" 28'-8"

4'-5 1/8"

EQ EQ

E Q

E Q

AE-500

E Q

'A

E Q

'A

ALIGN CEILING GRID

" 9'-1" 9'-1"

14' - 0"

13' - 0"

13' - 0"

CUBICLE CURTAIN TRACK

RETURN AIR DIFFUSER; REFER TO MECH. DWGS.

NEW ACOUSTICAL LAY-IN CEILING

2x4 RECESSED LED FIXTURE; REFER

TO ELECT. DWGS.

RECESSED LED DOWN LIGHT;

REFER TO ELECT. DWGS.

SUSPENDED DIRECT/INDIRECT LINEAR

FIXTURE; REFER TO ELECT. DWGS.

GYPSUM BOARD CEILING OR SOFFIT

SUPPLY AIR DIFFUSER; REFER TO MECH. DWGS.

EXISTING ACOUSTICAL LAY-IN CEILING

2x2 RECESSED LED FIXTURE; REFER

TO ELECT. DWGS.

CEILING HEIGHT SYMBOL

EXIT LIGHT; REFER TO ELECT. DWGS.

7'-10"

LINEAR DIFFUSER

1.

2.

3.

4.

5.

6.

7.

8.

CENTERLINES OF ROOM SHALL BE STARTING POINT OF CEILING GRID LAYOUT,

UNLESS OTHERWISE NOTED.

SPRINKLER HEADS, INCANDESCENT DOWNLIGHTS, DIFFUSERS, ETC. SHALL BE

CENTERED IN CEILING PANELS IN BOTH DIRECTIONS, UNLESS OTHERWISE

INDICATED.

DIFFUSERS AND RETURN GRILLES NOT SHOWN IN ROOMS WITHOUT CEILINGS.

ALL CEILING HEIGHTS SHALL BE 9'-0" A.F.F. UNLESS OTHERWISE NOTED.

REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF EXIT LIGHTS.

ALL SOFFITS AND VERTICAL SURFACES CONNECTING CEILINGS AND/OR

SOFFITS AT DIFFERENT ELEVATIONS SHALL BE CONSTRUCTED OF METAL

STUDS/FURRING AND GYPSUM WALLBOARD, UNLESS OTHERWISE INDICATED.

P&M DENOTES PATCH TO MATCH EXISTING CONSTRUCTION AND FINISHES. ALL

PATCHING OF EXISTING MATERIAL SHALL BE DONE WITH MATERIALS AND

WORKMANSHIP MATCHING ADJACENT SURFACES.

NO ATTEMPT HAS BEEN MADE TO INDICATE ALL AREAS REQUIRING CUTTING

AND PATCHING DUE TO MECHANICAL AND/OR ELECTRICAL WORK.

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :2

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

REFLECTED CEILING PLANS

AE-900

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/4" = 1'-0"AE-900

1 FIRST FLOOR REFLECTED CEILING PLAN

REFLECTED CEILING PLAN LEGEND

REFLECTED CEILING PLAN GENERAL NOTES

Revisions Date

65% DD SUBMISSION 07/29/2019

95% CD SUBMISSION 10/07/2019

O.7

6.25.2

P.81

9.78.87.96.4 6.9

P.9

Q.4

AE-500

AE-505

AE-505

SIM.

7.3

AE-501

AE-500

AE-501

10' - 0"

AE-700

AE-700

13' - 0"

8'-6"

CL

ISOCENTER OF MAGNET

CL

EQ EQ

2'-6"

5'-0" 2'-0"

.0

30.00°

15.00°

.0

13'-5" 8'-10"

/8

ELLIPTICAL DISPLAY

LIGHTING8'-0"

QUENCH VENT; COORDINATE

WITH MRI VENDOR AND

MECHANICAL DAWINGS

"9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

9' - 0"

OPEN TO

ABOVE

2'-0"

E Q

E Q

EQ EQ

EQ EQ

E Q

EQ EQ

6'-6" 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"

/4

E Q

E Q

EQ EQ

1'-10"

MATCH CELING HEIGHT

AND DIRECTION

EXISTING CEILING

SYSTEM TO REMAIN

MATCH CELING HEIGHT

AND DIRECTION

/8

/8

4'-2" 4'-1"

2'-1" 4'-2"

R 25'-0"

14' - 0"

EXISTING CEILING

SYSTEM TO REMAIN

6'-4 1/2" 6'-5 1/8" 6'-5 1/8" 6'-5 1/8" 6'-5 1/8"

EXPOSED TO

STRUCTURE ABOVE

E Q

E Q

7' - 2"

7' - 2"

7' - 2"

7' - 2"

7' - 2"

9' - 0"

8' - 6"

EXISTING SOFFIT TO

REMAIN

EXISTING SOFFIT TO

REMAIN

ALIGN CEILING GRID

OPENING FOR

FILTER CABINET

5'-0"

/8

/8

/8

6'-5 3/4" 8'-3" 20'-3" 22'-3" 28'-8"

4'-5 1/8"

EQ EQ

E Q

AE-500

13' - 0"

13' - 0"

CUBICLE CURTAIN TRACK

RETURN AIR DIFFUSER; REFER TO MECH. DWGS.

NEW ACOUSTICAL LAY-IN CEILING

2x4 RECESSED LED FIXTURE; REFER

TO ELECT. DWGS.

RECESSED LED DOWN LIGHT;

REFER TO ELECT. DWGS.

SUSPENDED DIRECT/INDIRECT LINEAR

FIXTURE; REFER TO ELECT. DWGS.

GYPSUM BOARD CEILING OR SOFFIT

SUPPLY AIR DIFFUSER; REFER TO MECH. DWGS.

EXISTING ACOUSTICAL LAY-IN CEILING

2x2 RECESSED LED FIXTURE; REFER

TO ELECT. DWGS.

CEILING HEIGHT SYMBOL

EXIT LIGHT; REFER TO ELECT. DWGS.

7'-10"

LINEAR DIFFUSER

1. SEE SHEET AE-900 FOR GENERAL REFLECTED CEILING PLAN NOTES

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :2

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

REFLECTED CEILING PLAN - DEDUCT

ALTERNATE #1

AE-910

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/4" = 1'-0"AE-910

1 FIRST FLOOR REFLECTED CEILING PLAN DEDUCT #1

REFLECTED CEILING PLAN LEGEND

REFLECTED CEILING PLAN GENERAL NOTES

Revisions Date

R

O.7

6.25.2

P.81

9.78.87.96.4 6.9

P.9

Q.4

AE-500

AE-505

AE-505

SIM.

7.3

AE-501

AE-500

AE-510

AE-501

10' - 0"

AE-700

AE-700

13' - 0"

E Q

E Q

8'-6"

CL

ISOCENTER OF MAGNET

CL

EQ EQ

/8

PATIENT LIFT

SYSTEM

DEDUCT ALTERNATE #3 (SHORT CANOPY)

EXISTING CEILING

SYSTEM TO REMAIN

MATCH CELING HEIGHT

AND DIRECTION

EXISTING CEILING

SYSTEM TO REMAIN

MATCH CELING HEIGHT

AND DIRECTION

/8

/8

/8

6'-5 3/4" 8'-3" 20'-3" 22'-3" 28'-8"

AE-500

ALIGN CEILING GRID

7' - 2"

7' - 2" 7' - 2"

9' - 0" 9' - 0" 9' - 0"

13' - 0"

10' - 0"

9' - 0"

9' - 0"

9' - 0"

6'-4 1/2" 6'-5 1/8" 6'-5 1/8" 6'-5 1/8" 6'-5 1/8"

14' - 0"

13' - 0"

CUBICLE CURTAIN TRACK

RETURN AIR DIFFUSER; REFER TO MECH. DWGS.

NEW ACOUSTICAL LAY-IN CEILING

2x4 RECESSED LED FIXTURE; REFER

TO ELECT. DWGS.

RECESSED LED DOWN LIGHT;

REFER TO ELECT. DWGS.

SUSPENDED DIRECT/INDIRECT LINEAR

FIXTURE; REFER TO ELECT. DWGS.

GYPSUM BOARD CEILING OR SOFFIT

SUPPLY AIR DIFFUSER; REFER TO MECH. DWGS.

EXISTING ACOUSTICAL LAY-IN CEILING

2x2 RECESSED LED FIXTURE; REFER

TO ELECT. DWGS.

CEILING HEIGHT SYMBOL

EXIT LIGHT; REFER TO ELECT. DWGS.

7'-10"

LINEAR DIFFUSER

1. SEE SHEET AE-900 FOR GENERAL REFLECTED CEILING PLAN NOTES

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :2

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

REFLECTED CEILING PLAN - DEDUCT

ALTERNATE #3

AE-911

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

SCALE: 1/4" = 1'-0"AE-911

1 FIRST FLOOR REFLECTED CEILING PLAN DEDUCT #3

REFLECTED CEILING PLAN LEGEND

REFLECTED CEILING PLAN GENERAL NOTES

Revisions Date

95% CD SUBMISSION 10/07/2019

FLOOR

CPT CARPET TILE

CT CERAMIC TILE

LVT LUXURY VINLY TILE

WSF WELDED VINYL SHEET FLOORING

ROOM FINISH LEGEND

WALL

P PAINT

WP IMPACT RESISTANT WALLCOVERING

BASE

RB RUBBER COVE BASE

WSF WELDED SHEET VINYL, INTEGRAL COVE BASE

CEILINGS

ACT ACOUSTICAL CEILING TILE

P PAINT

GENERAL NOTES

1. SEE REFLECTED CEILING PLAN FOR CEILING HEIGHTS.

2. SEE DRAWINGS FOR LOCATION AND ELEVATIONS OF

ARCHITECTURAL WOODWORK.

3. GYPSUM BOARD SOFFITS: UNLESS NOTED, HORIZONTAL SURFACES

SHALL BE SAME AS ANY CONNECTING WALL SURFACE. SEE

REFLECTED CEILING PLAN FOR SOFFIT HEIGHT.

4. PAINT ALL NEW METAL DOORS AND DOOR FRAMES (INCLUDING

VISION PANELS IN DOORS) UNLESS NOTED. SEE PAINT

SPECIFICATIONS FOR FINISH.

5. P&M DENOTES PATCH AND MATCH TO EXISTING ADJACENT

MATERIALS, FINISHES AND COLORS

SUBSTRATE

C CONCRETE

CBB CEMENTITIOUS BACKER BOARD

GWB GYPSUM BOARD

MRGB MOISTURE RESISTANT GYPSUM BOARD

ARCHITECTURAL WOODWORK

PL PLASTIC LAMINATE

SS SOLID SURFACE MATERIAL

SCHEDULE NOTES

1. SEE DRAWINGS FOR LOCATION OF CORNER GUARDS, CRASH RAILS,

AND BUMPER GUARDS.

2. REFER TO FLOOR PATTERN PLANS FOR FLOOR PATTERN

INFORMATION ON DRAWINGS.

3. SEE DRAWINGS FOR WALL ELEVATIONS

EXISTING OR

SCHEDULED

PARTITION

BLOCKING AS

REQUIRED

CONTINUOUS

ALUMINUM

RETAINER

VINYL CRASH RAIL

EDGE OF WALL,

DOOR FRAME, OR

CORNER GUARD

ELEVATION SECTION

2"

S E

E E

L E

V A

T

IO

N S

V A

R

IE

SATTACH PER

MANUFACTURER'S

STANDARDS

METAL STUD

FRAMING, SEE

PARTITION TYPE

VINYL EXTRUSION

BACK-UP SHEET

VINYL ACRYLIC

CORNER GUARD

CONT. ALUM.

RETAINER2

2"

ATTACH PER

MANUFACTURER'S

STANDARDS

METAL STUD

FRAMING, SEE

PARTITION TYPE

VINYL ACRYLIC

CORNER GUARD

3"

" CONT. ALUM.

RETAINER

PARTITION TYPE 'C'

NON-RATED SMOKE PARTITION

(1) LAYER OF 5/8" GYP. BD. ON EACH SIDE

OF 3 5/8" METAL STUDS @ 16" O.C.

PARTITION TYPE 'D'

NON-RATED

(1) LAYER OF 5/8" GYP. BD. ON EACH

SIDE OF 3 5/8" METAL STUD @ 16"O.C.

PARTITION AT FLOOR PARTITION AT FLOOR

PARTITION AT CEILING

STRUCTURE ABOVE

DEFLECTION JOINT

CONTINUOUS

RUNNER TRACK

CONTINUOUS

ACOUSTICAL

SEALANT

CEILING SYSTEM

CONT. RUNNER

TRACK

CORRIDOR SIDE

INFILL VOID AREAS

W/ SOUND

BLANKET

CONTINUOUS

ACOUSTICAL

SEALANT

CONTINUOUS

RUNNER TRACK

CEILING

STRAP BRIDGING

STRUCTURE ABOVE

EXTEND GYP.

BD. 6" ABOVE

CEILING

DEFLECTION JOINT

CONT. RUNNER TRACK

STRUCTURE ABOVE

SMOKESTOP ALL VOID

AREAS TIGHT TO

UNDERSIDE OF

STRUCTURE W/ SAFING

14 GA. STL PLATE

AS REQ.

EXISTING CONSTR.

OR NEW MASONRY

CONSTR. (SEE PLANS

FOR SPECIFIC

CONDITIONS)

SOUND ATTENUATION

BLANKET

HEAD OF PARTITION

METAL DECK PERPENDICULAR TO FLUTES

HEAD OF PARTITION

METAL DECK PARALLEL TO FLUTES

HEAD OF PARTITION

CONCRETE SLAB

HEAD OF PARTITION

METAL DECK PERPENDICULAR TO FLUTES

HEAD OF PARTITION

METAL DECK PARALLEL TO FLUTES

4 7/8" 4 7/8"

3 1/2" SOUND

ATTENUATION

BLANKET

CONTINUOUS

ACOUSTICAL

SEALANT EACH SIDE

STRUCTURE ABOVE

3 1/2" SOUND

ATTENUATION

BLANKET

CONTINUOUS

RUNNER TRACK

CONTINUOUS

RUNNER

TRACK DEFLECTION JOINT

STRUCTURE ABOVE

CONTINUOUS

RUNNER TRACK

DEFLECTION JOINT

3 1/2" SOUND

ATTENUATION

BLANKET

DEFLECTION JOINT

14 GA. STEEL

PLATE AS

REQUIRED

CONTINUOUS

ACOUSTICAL SEALANT

EACH SIDE

STRUCTURE ABOVE

CONTINUOUS

RUNNER TRACK

3 1/2" SOUND

ATTENUATION

BLANKET

CONTINUOUS

RUNNER TRACK

3 1/2" SOUND

ATTENUATION

BLANKET

EXTEND GYP. BD. 6"

ABOVE CEILING, THIS

SIDE

3 1/2" SOUND

ATTENUATION

BLANKET

CONTINUOUS

ACOUSTICAL SEALANT

EACH SIDE

3 1/2" SOUND

ATTENUATION

BLANKET

3 1/2" SOUND

ATTENUATION

BLANKET

4 1/4"

EXISTING CONSTR.

OR NEW MASONRY

CONSTR. (SEE PLANS

FOR SPECIFIC

CONDITIONS)

PARTITION TYPE 'G'

NON-RATED

(1) LAYER OF 5/8" GYP. BD. ON ONE SIDE OF

3 5/8" METAL STUD FURRING @ 16" O.C.

PARTITION AT FLOOR

PARTITION AT CEILING

HEAD OF PARTITION

4 7/8"

PARTITION TYPE 'A'

ONE HOUR RATED (U.L. #U419)

(1) LAYER OF 5/8" FIRE RESISTIVE GYP. BD. ON

EACH SIDE OF 3 5/8" METAL STUDS @ 16" O.C.

HEAD OF PARTITION

METAL DECK PERPENDICULAR TO FLUTES

HEAD OF PARTITION

METAL DECK PARALLEL TO FLUTES

PARTITION AT FLOOR

HEAD OF PARTITION

CONCRETE SLAB

STRUCTURE ABOVE

CONTINUOUS

RUNNER TRACK

FIRESTOP JOINT

BETWEEN TOP OF FIRE-

RATED PARTITION AND

STRUCTURE ABOVE W/

U.L. OR W.H.I. PPROVED

(1) HR. JOINT FIRESTOP

SYSTEM.

SOUND

ATTENUATION

BLANKET

CONTINUOUS

ACOUSTICAL SEALANT

EACH SIDE

CONTINUOUS

ACOUSTICAL

SEALANT

DEFLECTION JOINT

CONTINUOUS

RUNNER TRACK

STRUCTURE ABOVE

STRUCTURE ABOVE

DEFLECTION JOINT

DEFLECTION JOINT

SOUND

ATTENUATION

BLANKET

SOUND

ATTENUATION

BLANKET

CONTINUOUS

RUNNER TRACK

CONTINUOUS RUNNER

TRACK

FIRESTOP JOINT

BETWEEN TOP OF FIRE-

RATED PARTITION AND

STRUCTURE ABOVE W/

U.L. OR W.H.I. PPROVED

(1) HR. JOINT FIRESTOP

SYSTEM.

EXISTING CEILING

EXISTING FLOOR

(SLAB)

METAL TRACK

FOR 3 5/8" STUD

OR 2X TOP PLATE

METAL RUNNER

FOR 3 5/8" METAL

STUD OR 2X SILL

PLATE

5/8" EXTERIOR

GRADE PLYWOOD

OR 5/8" GYP. BD.

WITH LEVEL 4 FINISH

PUBLIC SIDE CONSTRUCTION SIDE

MAX GAP OF 1/4"

BETWEEN EXISTING

CEILING AND TOP OF

WALL

TEMPORARY CONSTRUCTION

BARRIER DETAIL

EXISTING CEILING

EXISTING FLOOR (SLAB)

METAL TRACK FOR 8"

STUD OR 2X TOP PLATE

METAL RUNNER FOR 8" METAL

STUD OR 2X SILL PLATE

5/8" GYP. BD. WITH

LEVEL 4 FINISH

PUBLIC SIDE CONSTRUCTION SIDE

MAX GAP OF 1/4"

BETWEEN EXISTING

CEILING AND TOP OF

WALL

SPRAY APPLIED VAPOR

BARRIER ON EXTERIOR

GRADE PLYWOOD

TEMPORARY CONSTRUCTION BARRIER

WHERE EXPOSED TO ELEMENTS

4 7/8"

TEMPORARY

CONSTRUCTION BARRIER

HEAD OF PARTITION

METAL DECK PARALLEL TO FLUTES

PARTITION AT FLOOR

SOUND ATTENUATION

BLANKET CONTINUOUS ACOUSTICAL

SEALANT EACH SIDE

STRUCTURE ABOVE

DEFLECTION JOINT

SOUND ATTENUATION

BLANKET

CONTINUOUS RUNNER TRACK

CONTINUOUS RUNNER TRACK

FIRESTOP JOINT BETWEEN TOP

OF FIRE-RATED PARTITION AND

STRUCTURE ABOVE W/ U.L. OR

W.H.I. PPROVED (1) HR. JOINT

FIRESTOP SYSTEM.

ONE HOUR RATED (U.L. #U419)

(1) LAYER OF 5/8" FIRE RESISTIVE GYP. BD. ON

EACH SIDE OF 3 5/8" METAL STUDS @ 16" O.C.

PUBLIC SIDE CONSTRUCTION SIDE

5/8" GYP. BD. WITH

LEVEL 4 FINISH

MICHAEL DWAYNE

LIEZERT

S

TATE OF OHIO

R E

G

ISTERED ARCHIT

E C

T9939

Project Number

Office of Construction and Facilities Management

Building Number

Drawing Number

VA FORM 08-6231

CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #

VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o

F

E

D

C

B

A

F

E

D

C

B

A

987654321

987654321

Project Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

KEY PLAN

Dwg. of

FULLY SPRINKLERED

PHILIP P. KIRK

CHIEF ENGINEER

:2 :2

A M

C U s e rs jc h o D o c u m e n ts R

N E W

M R I S

IT

E

P R E P C e n tr a l_ jc h o .r v t

PARTITION TYPES, FINISH SCHEDULE,

LEGEND AND DETAILS

AE-1000

BH Designer

552-CSI-176

NEW MRI SITE PREP

02/21/2020

4100 WEST THIRD STREET, DAYTON, OHIO 45428

18106

BID & CONSTRUCTION

ROOM FINISH SCHEDULE

ROOM FLOOR BASE WALLS CEILING ARCH.

WOODWORK NOTESNUMBER NAME SUBSTR. FINISH SUBSTR. FINISH SUBSTR. NORTH SOUTH EAST WEST SUBSTR. FINISH

A100 VESTIBULE C CPT-8 GWB RB-1 GWB - P-2/A - P-2/A* MRGB PT-32/A - *WITHSTONE VENEER

A101 LOBBY/WAITING C LVT-3/LVT-8* GWB RB-1 GWB - P-16/A P-2/A P-2/A - ACT-1 - REWORK EXISTING FLOORING AND CELING TILE WITH NEW TILE AND PATTERN

A102 ENTRANCE HALL C LVT-8 GWB RB-1 GWB - P-2/A P-2/A P-2/A - ACT-1 - *SEE FINISH FLOOR PLAN

A103 ENTRANCE C LVT-8 GWB RB-1 GWB P-2/A - P-2/A P-16/A - ACT-1 -

A104 PREP AREA C LVT-8 GWB RB-1 GWB P-2/A P-2/A* P-2/A P-16/A - ACT-1 SS-2/PL12 *WITH/ IRWC1A WAINSCOT

A105 SUB WAITING C LVT-3/LVT-8* GWB RB-1 GWB P-2/A P-16/A P-2/A P-16/A - ACT-1 - *SEE FINISH FLOOR PLAN

A106 DRESSING C LVT-8 GWB RB-1 GWB P-2/A P-2/A P-16/A P-2/A - ACT-1 SS-2/PL12 WINDOW SILL: SS-2

A107 DRESSING C LVT-8 GWB RB-1 GWB P-2/A P-2/A P-16/A P-2/A - ACT-1 SS-2/PL12 WINDOW SILL: SS-2

A108 OFFICE C LVT-8 GWB RB-1 GWB P-2/A P-2/A P-16/A P-2/A - ACT-1 - WINDOW SILL: SS-2

A109 CORRIDOR C LVT-8 GWB RB-1 GWB P-2/A P-2/A P-2/A - - ACT-1 -

A110 EQUIPMENT C LVT-8 GWB RB-1 GWB P-2/A P-2/A P-2/A P-2/A - ACT-1 -

A111 MRI ROOM C WSF-10 GWB WSF-10 GWB P-2/A P-16/A P-2/A P-16/A - ACT-1 SS-2/PL12

A112 CONTROL ROOM C LVT-8 GWB RB-1 GWB P-2/A P-2/A P-2/A P-16/A - ACT-1 SS-2/PL12

A113 TOILET C CT-1 CBB -- CBB *CT-1 *CT-1 *CT-1 ct-3 - ACT-1 - *WITH PT2/A ABOVE

E113 EX. CORRIDOR C LVT-8 GWB RB-1 ETR P-2/A P-2/A P-2/A P-2/A - GWB* - *PT2/A: SOFFITS

E131 EX.