This pre-solicitation notice is for a new MRI site prep project at the Dayton VA Medical Center. The Department of Veterans Affairs seeks a contractor to provide all labor, materials, equipment, and supervision to prepare the site for a new building to house MRI equipment. The project performance period is 245 calendar days from notice to proceed.
The solicitation will be issued on or around March 20, 2020 via www.fbo.gov. Proposals are due approximately 30 days later. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The NAICS code is 236220 with a small business size standard of $39.5 million. The contractor must perform a minimum of 15% of construction work. Bid, payment and performance bonds will be required. A one-time site visit will be scheduled. Amendments will be posted to www.fbo.gov and offerors must check for updates. The estimated contract value is between $2-5 million. Questions may be emailed to the point of contact listed.
36C25020B0030 Project Drawings (Part 1 of 4).pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25020B0030-0002001.docx | DOCX document | |
| 36C25020B0030-0001000.docx | DOCX document | |
| 36C25020B0030-008.pdf | ||
| 36C25020B0030-006.pdf | ||
| 36C25020B0030-007.pdf | ||
| 36C25020B0030-005.pdf | ||
| 36C25020B0030-001.docx | DOCX document | |
| 36C25020B0030-002.pdf | ||
| 36C25020B0030-003.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REFER TO STATEMENT OF BID ITEMS IN SECTION 01 00 00 AND DEDUCT ALTERATE SHEETS
FOR ADDITIONAL INFORMATION
TOTAL PROJECT DURATION 245 DAYS
DEDUCT DESCRIPTION DURATION (IN CALENDAR DAYS)
ALTERNATE #1 NO SKY LIGHTS ABOVE SUB-WAITING 0 DAYS
ALTERNATE #2 RTU SCREEN WALL 0 DAYS
ALTERNATE #3 SMALLER CANOPY 0 DAYS
ALTERNATE #4 RESURFACE PARKING LOT FOR ADDITION ONLY (-7) DAYS
NFPA 101 LIFE SAFETY CODE (2018)
PROJECT AREA: **3,220 SF
FIRE SUPPRESSION: FULLY SPRINKLERED
TRAVEL DISTANCE (18.2.6): 200 FT MAX. REMOTE POINT TO EXIT
FIRE-RESISTANCE RATINGS REQUIREMENTS - TABLE A.8.2.1.2:
CONSTRUCTION TYPE: TYPE II (222)
STRUCTURAL FRAME: 2 HOURS; 1 HOUR FOR ROOF SUPPORT ONLY
BEARING WALLS:
EXTERIOR:
INTERIOR:
NON BEARING WALLS & PARTITIONS:
EXTERIOR: 0 HOURS
INTERIOR: 0 HOURS
FLOOR CONSTRUCTION: 2 HOURS
ROOF CONSTRUCTION: 1 HOURS
2 HOURS; 1 HOUR FOR ROOF SUPPORT ONLY
2 HOURS; 1 HOUR FOR ROOF SUPPORT ONLY
INTERIOR FINISHES - TABLE A.10.2.2: CLASS A
STORAGE ROOMS (18.3.2.1.2):
LARGER THAN 100 SF STORING COMBUSTIBLE MATERIAL:
EXIT ENCLOSURES (7.1.3.2.1): 1 HOUR
COMMON PATH OF TRAVEL (18.2.5.3): 100 FT MAX.
CORRIDOR WALLS (18.3.6.2.3): LIMIT TRANSFER OF SMOKE
SHAFT ENCLOSURES (8.6.5):
CONNECTING 4 STORIES OR MORE:
CONNECTING LESS THAN 4 STORIES:
2 HOURS
1 HOUR
SMOKE BARRIERS (18.3.7.3): 1 HOUR
EXIT ACCESS CORRIDORS (8.3.3.2.2): 1 HOUR
OCCUPANCY (6.1.6): AMBULATORY HEALTH CARE
1 HR RATING
DEAD-END LIMIT (TABLE A7.6): 30'-0" (SPRINKLERED)
PATIENT CARE NON-SLEEPING SUITES (18.2.5.7.3):
MAXIMUM SIZE (18.2.5.7.3.2): 12,500 SF
TRAVEL DISTANCE (18.2.5.7.3.3): 100 FT MAX. WITHIN SUITE REMOTE POINT TO EXIT
200 FT MAX. SUITE REMOTE POINT TO EXIT
NFPA 101 LIFE SAFETY CODE 2018
NFPA 1 NATIONAL FIRE CODE 2018
NFPA 70 NATIONAL ELECTRICAL CODE 2017
PG 18-15 A/E SUBMISSION REQUIREMENTS
VOLUME C - MINOR AND NRM PROJECTS November 2008 PG 18-13 VA BARRIER FREE DESIGN STANDARD November 2018 MRI DESIGN GUIDE April 2008 HVAC DESIGN MANUAL May 2019 PLUMBING DESIGN MANUAL May 2018 FIRE PROTECTION DESIGN MANUAL December 2015
STRUCTURAL
S-0.1 GENERAL NOTES
S-0.2 GENERAL NOTES
S-0.3 GENERAL NOTES
S-1.0 FOUNDATION PLAN
S-1.0 ALT ALTERNATE FOUNDATION PLAN
S-2.0 BASE ROOF FRAMING PLAN
S-2.0 ALT #1 ALTERNATE #1 ROOF FRAMING PLAN
S-2.0 ALT #2 ALTERNATE #2 ROOF FRAMING PLAN
S-2.0 ALT #3 ALTERNATE #3 ROOF FRAMING PLAN
S-3.0 FOUNDATION DETAILS
S-4.0 COLD FORMED DETAILS
S-5.0 STEEL DETAILS
S-5.1 FRAMING SECTIONS
FIRE PROTECTION
FX100 NEW WORK - FIRST FLOOR PLAN - FIRE PROTECTION
MECHANICAL
MH0.1 HVAC GENERAL NOTES AND SYMBOL LEGEND
MH1.1 DEMO/NEW WORK - FIRST FLOOR PLAN - DUCTWORK
MH2.1 NEW WORK - ROOF PLAN - HVAC
MH3.1 DETAILS - HVAC
MH3.2 DETAILS AND TEMPERATURE CONTROLS - HVAC
MH4.1 SCHEDULES - HVAC
PLUMBING
PL0.1 PLUMBING GENERAL NOTES AND SYMBOL LEGEND
PL1.1 NEW WORK - FIRST FLOOR PLAN - SANITARY/VENT
PL2.1 NEW WORK - FIRST FLOOR PLAN - WATER AND MED GAS
PL3.1 DETAILS AND SCHEDULES - PLUMBING
PL4.1 DETAILS AND SCHEDULES - PLUMBING
ELECTRICAL
ES1.0 ELECTRICAL GENERAL NOTES AND SYMBOL LEGEND
ES2.0 LIGHTING - PARTIAL FIRST FLOOR PLAN - ELECTRICAL
ES2.0A LIGHTING - FIRST FLOOR REFLECTED CEILING PLAN DEDUCT #1 -
LONG CANOPY
ES2.0B LIGHTING - FIRST FLOOR REFLECTED CEILING PLAN DEDUCT #3 -
SHORT CANOPY
ES2.1 POWER - PARTIAL BASEMENT FLOOR PLAN - ELECTRICAL
ES2.2 POWER - PARTIAL FIRST FLOOR PLAN - ELECTRICAL
ES2.3 POWER - PARTIAL ROOF PLAN - ELECTRICAL
ES2.4 SYSTEMS - PARTIAL FIRST FLOOR PLAN - ELECTRICAL
ES3.0 PANELBOARD SCHEDULES
ES4.0 DETAILS - ELECTRICAL
ES4.1 DETAILS - ELECTRICAL
ES4.2 DETAILS - ELECTRICAL
ES5.0 DAYTON VAMC SIEMENS REFERENCE DRAWINGS
ES5.1 DAYTON VAMC SIEMENS REFERENCE DRAWINGS
ES5.2 DAYTON VAMC SIEMENS REFERENCE DRAWINGS
FOR REFERENCE ONLY
A-101 SIEMENS DRAWING
A-102 SIEMENS DRAWING
A-501 SIEMENS DRAWING
A-502 SIEMENS DRAWING
S-101 SIEMENS DRAWING
E-101 SIEMENS DRAWING
E-102 SIEMENS DRAWING
E-501 SIEMENS DRAWING
M-101 SIEMENS DRAWING
M-501 SIEMENS DRAWING
GENERAL
GI-100 COVER
GI-101 NOTES AND SYMBOLS
GI-102 FIRST FLOOR LIFE SAFETY PLAN
GI-110 FIRE STOPPING DETAILS
GI-111 FIRE STOPPING DETAILS
GI-112 FIRE STOPPING DETAILS
GI-113 FIRE STOPPING DETAILS
GI-114 FIRE STOPPING DETAILS
GI-115 FIRE STOPPING DETAILS
CIVIL
1 OF 1 TOPOGRAPHIC SURVEY (FOR REFERENCE ONLY)
C-1.0 SITE PREPARATION PLAN
C-1.1 GEOMETRIC PLAN
C-2.0 GRADING & UTILITY PLAN
C-3.0 GENERAL NOTES
C-4.0 SITE DETAILS
C-4.1 SITE DETAILS
C-5.0 EROSION AND SEDIMENTATION CONTROL NOTE DETAILS
ARCHITECTURE
AD-100 ARCHITECTURAL SITE DEMOLITION PLAN
AD-101 DEMOLITION PLANS AND ELEVATIONS
AE-200 ARCHITECTURAL SITE PLAN
AE-210 ARCHITECTURAL SITE PLAN - DEDUCT ALTERNATE #4
AE-300 FIRST FLOOR PLAN
AE-301 FIRST FLOOR FINISH PLAN
AE-305 FIRST FLOOR EQUIPMENT PLAN
AE-310 OVERALL ROOF PLAN
AE-311 ROOF PLAN
AE-320 ROOF PLAN - DEDUCT ALTERNATE #1
AE-321 ROOF PLAN - DEDUCT ALTERNATE #2
AE-322 ROOF PLAN - DEDUCT ALTERNATE #3
AE-400 EXTERIOR ELEVATIONS
AE-401 EXTERIOR ELEVATIONS
AE-410 EXTERIOR ELEVATIONS - DEDUCT ALTERNATE #2
AE-411 EXTERIOR ELEVATIONS - DEDUCT ALTERNATE #3
AE-500 BUILDING SECTIONS
AE-501 BUILDING SECTIONS
AE-502 BUILDING SECTIONS
AE-505 WALL SECTIONS
AE-510 DETAILS
AE-511 DETAILS
AE-700 INTERIOR DETAILS AND SECTIONS
AE-701 MILLWORK SECTIONS
AE-800 INTERIOR ELEVATIONS
AE-801 INTERIOR ELEVATIONS
AE-900 REFLECTED CEILING PLANS
AE-910 REFLECTED CEILING PLAN - DEDUCT ALTERNATE #1
AE-911 REFLECTED CEILING PLAN - DEDUCT ALTERNATE #3
AE-1000 PARTITION TYPES, FINISH SCHEDULE, LEGEND AND DETAILS
AE-1001 DOOR & WINDOW SCHEDULES AND DETAILS
AE-1002 INTERIOR SIGNAGE
MICHAEL DWAYNE
LIEZERT
S
TATE OF OHIO
R E
G
ISTERED ARCHIT
E C
T9939
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:3 :3
P M
C U s e rs jc h o D o c u m e n ts R
N E W
M R I S
IT
E
P R E P C e n tr a l_ jc h o .r v t
COVER
GI-100
BH Designer
552-CSI-176
NEW MRI SITE PREP
02/21/2020
4100 WEST THIRD STREET, DAYTON, OHIO 45428
18106
BID & CONSTRUCTION
PROJECT NUMBER:
SUBMITTAL FOR:
DRAWING INDEX: CODE DATA:LOCATION MAP:
DAYTON VA MEDICAL CENTER
CBLH Design, Inc.
Scheeser Buckley Mayfield
Thorson Baker
Architectural & Interior Design
Mechanical & Electrical Engineer
Structural & Civil Engineer Richfield, Ohio
Uniontown, Ohio
Cleveland, Ohio
NEW MRI SITE PREP
4100 WEST THIRD STREET, DAYTON, OHIO 45428
552-CSI-176
BID & CONSTRUCTION
4100 WEST THIRD STREET,
DAYTON, OH 45428
NORTH
PROJECT DURATION SUMMARY
BUILDING CODES / PROJECT MANUALS
Revisions Date
35% SD SUBMISSION 05/22/2019
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
BID & CONSTRUCTION 12/19/2019
CAM REVIEW 02/21/2020
FINISHED CONTOURS
EXISTING CONTOURS
CONTRACT LIMIT LINE
PROPERTY LINE
ELEVATION INDICATORS
FINISH ELEVATION
EXISTING ELEVATION
FENCE
STRUCTURAL GRID COLUMN TAG (NEW)
STRUCTURAL GRID COLUMN TAG (EXISTING)
CENTERLINE
REVISION INDICATOR
DRAWING BREAK LINE
MATCH LINE INDICATOR
HIDDEN LINE
1. ITEMS ABOVE OR BEYOND
2. ITEMS NOT IN CONTRACT (N.I.C.)
3. ITEMS BEING DEMOLISHED
ELEVATION DATUM
WINDOW & LOUVER SYMBOL
(SEE WINDOW SCHEDULE)
DOOR SYMBOL
(SEE DOOR SCHEDULE)
EQUIPMENT SYMBOL
(SEE EQUIPMENT SCHEDULE)
WALL TYPE SYMBOL
(SEE PARTITION TYPES)
PARTITION NUMBER
WORK POINT
ROOM NUMBER SYMBOL
ELEVATION VIEW INDICATOR
DETAIL INDICATOR
SECTION INDICATOR
DRAWING TITLE
SCALE:
1 View Name 1/8" = 1'-0"A101
DETAIL NO.
DRAWING NO.
1'-0"
1'-0"
INTERIOR 01
INTERIOR 02
ELEVATION NO.
DRAWING NO. A101
ELEVATION NO.
A
A
NEW
EXISTING
SECTION NO.
DRAWING NO.
X
B
Room name
X
/1 A101
/1 A101
A101
A101
NEW PARTITION
PATCH TO MATCH EXISTING PARTITION
EXISTING PARTITION TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE REMOVED
NEW DOOR AND FRAME
POCKET DOOR
CASED OPENING
BIFOLD DOOR
SLIDING DOOR
Room name
Room name
AIR CONDITIONED
ACOUSTICAL CEILING TILE
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ALTERNATE
AUDIO VISUAL
ARCHITECTURAL WOODWORK
AC
A.C.T.
A.C.U.
A.F.F.
ALT
A.V.
A.W.
BD
BLDG
BLK
BLKG
BOT
BR
BRG
BSMT
CONC
CAB
C.B.B.
C.C.T.
C.G.
C.J.
CLR
CLG
C.M.U.
COL
COMM
CONF
CONN
CONST
CONT
CONTR
COORD
CORR
C.R.
C.W.
CYL
DBL
DEMO
DEPT
DET
D.F.
DIA
DIAG
DIM
DISP
DN
DR
D.S.
D.W.
DWG(S)
EXIST
E
EA EACH
EAST
EXISTING
DRAWING(S)
DUMBWAITER
DOWNSPOUT
DOOR
DOWN
DISPENSER
DIMENSION
DIAGONAL
DIAMETER
DRINKING FOUNTAIN
DETAIL
DEPARTMENT
DEMOLITION
DOUBLE
CYLINDER
COLD WATER
CRASH RAIL
CORRIDOR
COORDINATE
CONTRACTOR
CONTINUOUS
CONSTRUCTION
CONNECTION
CONFERENCE
COMMUNICATION
COLUMN
CONCRETE MASONRY UNIT
CEILING
CLEAR
CONTROL JOINT
CORNER GUARD
CUBICAL CURTAIN TRACK
CEMENTITIOUS BACKER BOARD
CABINET
CONCRETE
BASEMENT
BEARING
BRICK
BOTTOM
BLOCKING
BLOCK
BUILDING
BOARD
POUND OR NUMBER #
DIAMETER OR ROUND
CENTERLINE
AT
ANGLE
AND
EXPANSION JOINT
ELECTRICAL
E.I.F.S.
E.J.
ELECT
EL
ELEV
EMER
ENCL
EQ
EQUIP
E.T.R.
EVAC
E.W.C.
EXT
F.B.
F.C.
F.C.U.
F.D.
F.D.V.C.
F.E.
F.E.C.
F.H.C.
FIN
FIXT
FLR
FLEX
FLUOR
F.R.T.
FT
FTG
FURN
FUT
G
GA
GALV
G.C.
G.F.M.U.
GL
GR
GRND
GYP
H.B.
HD
HDWD
H.M.
HOSP
H.P.
HR
H.R.
HORIZ
HT
HTG
HTR
H.V.A.C.
H.W.
HW
HYD
I.D.
ILLUM
INCIN
INCAND
INCL
INFO
INSUL
INT
I.P.S.
ISOL
IV
JT
KITCH
K.O.
K.P.
K.S. KNEE SPACE
KICK PLATE
KNOCK OUT
KITCHEN
JOINT
INTRAVENOUS
ISOLATION
INSIDE PIPE SIZE
INTERIOR
INSULATION
INFORMATION
INCLUDE
INCINERATOR
INCANDESCENT
ILLUMINATION
INSIDE DIAMETER (DIM)
HYDRANT
HARDWARE
HOT WATER
HEATING, VENTILATION, AIR CONDITIONING
HEATER
HEATING
HEIGHT
HORIZONTAL
HANDRAIL
HOUR
HIGH POINT
HOSPITAL
HOLLOW METAL
HEAD
HOSE BIBB
GYPSUM
GROUND
GRADE
GLASS
GROUND FACE MASONRY UNITS
GENERAL CONTRACTOR
GALVANIZED
GAGE
GAS
FUTURE
FURNITURE
FOOTING
FOOT OR FEET
FIRE RESISTANT TREATED
FLUORESCENT
FLEXIBLE
FLOOR
FIXTURE
FINISH
FIRE HOSE CABINET
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE DEPARTMENT VALVE CABINET
FLOOR DRAIN
FAN COIL UNIT
FOOT CONTROL
FACE BRICK
EXTERIOR
ELECTRIC WATER COOLER
EVACUATION
EXISTING TO REMAIN
EQUIPMENT
EQUAL
ENCLOSURE
EMERGENCY
ELEVATOR
ELEVATION
L
LAB
LAM
LIB
LIN
LOC
L.P.
LT.WT.
LTG
MACH
MAS
MATL
MAX
MECH
MED
MED.CAB.
MEMB
MEZZ
MFR
MH
MIN
MISC
MKR.BD.
MLDG
M.O.
MOD
M.R.G.B.
MTD
MTL
N
N.C.
NEG
N.I.C.
NO
N.T.S.
O
O.C.
O.D.
OFF
OPNG
OPP
O.F.C.I.
PART.BD.
P.C.
P.C.D.
PERIM
PERP
PLWD
PORT
PR
PREFAB
PREFIN
PROJ
PROP
P.T.
PTD
R
R.A.
REC
RECEP
RECT
REF REFRIGERATOR
RECTANGULAR
RECEPTACLE
RECESSED
RETURN AIR
RADIUS
PAINTED
PNEUMATIC TUBE
PROPERTY
PROJECT
PREFINISHED
PREFABRICATED
PAIR
PORTABLE
PLYWOOD
PERPENDICULAR
PERIMETER
PAPER CUP DISPENSER
PRECAST CONCRETE
PARTICLEBOARD
OWNER FURNISHED, CONTRACTOR INSTALLED
OPPOSITE
OPENING
OFFICE
OUTSIDE DIAMETER(DIM)
ON CENTER
OXYGEN
NOT TO SCALE
NOMINAL
NUMBER
NOT IN CONTRACT
NEGATIVE
NURSE CALL
NITROGEN/NORTH
METAL
MOUNTED
MOISTURE RESISTANT GYPSUM BOARD
MODIFIED, MODULAR
MASONRY OPENING
MOULDING
MARKERBOARD
MISCELLANEOUS
MINIMUM
MANHOLE
MANUFACTURER
MEZZANINE
MEMBRANE
MEDICINE CABINET
MEDICINE/MEDICAL
MECHANICAL
MAXIMUM
MATERIAL
MASONRY
MACHINE
LIGHTING
LIGHTWEIGHT
LOW POINT
LOCATION/LOCATE
LINEAR
LIBRARY
LAMINATE
LABORATORY
LOCK
REFL REFLECTED
REINF REINFORCED
REM REMOVABLE
REQ'D REQUIRED
REV REVISION
R.F. RADIO FREQUENCY
RM
RND
R.O.
R.S.T. RUBBER STAIR TREADS
ROUGH OPENING
ROUND
S
S.S.
S.A.
SAN
SCHED
S.C.R.
S.D.
SECT
SGL
SH
SHR
SHT
SIM
S.O.G.
SPEC (S)
S&R
S.P.T.
SQ
S.F.
S.I.
S.Y.
S.T.C.
STD
STL
STOR
STRUCT
SURF
SUSP
T
T&B
T&G
TAN
TEL
TEMP
THRESH
THRU
TK.BD.
TLT
T.O.P.
TV
TYP
U.C.
UNFIN
U.O.N.
UTIL
V, VAC
VENT
VERT
VEST
VIT
W
W/
W/O
W.C.
W/C
WD
W.P.
YD YARD
WORKPOINT
WOOD
WHEEL CHAIR
WATER CLOSET
WITHOUT
WITH
WEST/WATER
VITREOUS
VESTIBULE
VERTICAL
VENTILATION
VACUUM
UTILITY
UNLESS OTHERWISE NOTED
UNFINISHED
UNDER COUNTER
TYPICAL
TELEVISION
TOP OF PAVEMENT
TOILET
TACKBOARD
THROUGH
THRESHOLD
TEMPERATURE
TELEPHONE
TANGENT
TONGUE AND GROOVE
TOP AND BOTTOM
THERMOSTAT
SUSPENDED
SURFACE
STRUCTURAL
STORAGE
STEEL
STANDARD
SOUND TRANSMISSION CLASS / COEFFICIENT
SQUARE YARD
SQUARE INCH
SQUARE FOOT
SQUARE
SPECIMEN PASS-THRU
SHELF & ROD
SPECIFICATION(S)
SLAB ON GRADE
SIMILAR
SHEET
SHOWER
SHELVING, SHELF
SINGLE
SECTION
SUPPLY DIFFUSER
SHOWER CURTAIN ROD
SCHEDULE
SANITARY
SUPPLY AIR
STAINLESS STEEL
SOUTH
LT LIGHT
LAV LAVATORY
W.W.F. WELDED WIRE FABRIC
EXTERIOR INSULATION FINISH SYSTEM
HARDWOOD
NOM
ROOM
V.I.F. VERIFY IN FIELD
ALUMINUMAL
F.P. FIRE PROTECTION
F.P.G. FIRE PROTECTED GLAZING
CL
O.F.O.I. OWNER FURNISHED, OWNER INSTALLED
SSM SOLID SURFACE MATERIAL
NOTE: ALL ITEMS/MATERIALS MAY NOT OCCUR IN THIS PROJECT. LIST
PROVIDED FOR REFERENCE ONLY.
UNDISTURBED EEARTH OR
UNDISTURBED SUBGRADE
COMPACTED EARTH OR
COMPACTED SUBGRADE
ROCK
POROUS FILL OR SUBBASE
IMPERVIOUS FILL
DRAINAGE FILL
CAST-IN-PLACE CONCRETE
PRECAST CONCRETE
TOPSOIL
CEMENTITIOUS DECKS AND
TOPPINGS
GROUT
BRICK
GLAZED BRICK
STRUCTURAL CLAY TILE
UNIT MASONRY
GLAZED STRUCTURAL CLAY TILE
UNIT MASONRY
CONCRETE UNIT MASONRY
GLAZED CONCRETE UNIT MASONRY
GLAZED UNIT MASONRY
CUT STONE
FIREBRICK
CAST STONE
STEEL
ALUMINUM
ORNAMENTAL
METAL/STAINLESS STEEL
CONTINUOUS WOOD FRAMING
WOOD BLOCKING
PLYWOOD
PARTICLE BOARD
FINISHED LUMBER FOR
ARCHITECTURAL WORK
BATT INSULATION
RIGID INSULATION
LOOSE FILL INSULATION
EXTERIOR INSULATION AND
FINISH SYSTEM
FIBROUS FIRE SAFING
GLASS
CARPET
LATH AND PLASTER
GYPSUM BOARD
PLASTIC GLAZING
TERRAZZO
ACOUSTICAL CEILING
RESILIENT TILE
CERAMIC TILE
GRAPHIC SYMBOLS
FLOOR PLAN LEGEND
STANDARD ABBREVIATIONS
MATERIALS LEGEND
MICHAEL DWAYNE
LIEZERT
S
TATE OF OHIO
R E
G
ISTERED ARCHIT
E C
T9939
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:2 :3
A M
C U s e rs jc h o D o c u m e n ts R
N E W
M R I S
IT
E
P R E P C e n tr a l_ jc h o .r v t
NOTES AND SYMBOLS
GI-101
BH Designer
552-CSI-176
NEW MRI SITE PREP
02/21/2020
4100 WEST THIRD STREET, DAYTON, OHIO 45428
18106
BID & CONSTRUCTION
Revisions Date
35% SD SUBMISSION 05/22/2019
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
P.5
O.7
6.25.2
P.81
9.78.87.96.4 6.9
P.9
Q.4
A106
DRESSING
A107
DRESSING
A108
OFFICE
A110
EQUIPMENT
A111
MRI ROOM
A112
CONTROL
ROOMA113
TOILET
A101
LOBBY/WAITING
A100
VESTIBULE
X130
TOILET
X129
TOILET
X127
TOILET
X126
STAFF WORK
X112
RECEPTION
X124
DRESSING
X125
DRESSING
X128
SUB WAIT
X114
DATA
X115
ELECTRICAL
X116
VIEW/CONSULT
X120
STAFF
RADIOLOGIST
X121
PROF.
NON-PHYSICIAN
X119
EQUIPMENT
A102
ENTRANCE
HALL
E131
EX.
CORRIDOR
A105
SUB WAITING
A104
PREP AREA
A103
ENTRANCE
E132
EX.
CORRIDOR
E113
EX.
CORRIDOR
X123
CORRIDOR
X122
CORRIDOR
X117
CLEAN
SUPPLY
X118
CLEAN
SUPPLY
T O
B
U
IL
D
IN
G E
X
IT
7.3
44'-0" COMMON
PATH OF TRAVEL
FEC
91'-7" TO
SUITE EXIT
BUILDING
EXIT
NON-RATED SMOKE PARTITION
RATED SMOKE BARRIER
1 HOUR FIRE SEPARATION
2 HOUR FIRE SEPARATION
3 HOUR FIRE SEPARATION
FIRE EXTINGUISHER CABINET
TRAVEL DISTANCE
EXIT SIGN
AREA NOT IN CONTRACT
F.E.C.
MICHAEL DWAYNE
LIEZERT
S
TATE OF OHIO
R E
G
ISTERED ARCHIT
E C
T9939
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:0 :5
P M
C U s e rs jc h o D o c u m e n ts R
N E W
M R I S
IT
E
P R E P C e n tr a l_ jc h o .r v t
FIRST FLOOR LIFE SAFETY PLAN
GI-102
BH Designer
552-CSI-176
NEW MRI SITE PREP
02/21/2020
4100 WEST THIRD STREET, DAYTON, OHIO 45428
18106
BID & CONSTRUCTION
SCALE: 1/4" = 1'-0"GI-102
1 LIFE SAFETY PLAN
LIFE SAFETY LEGEND
NORTH
Revisions Date
65% DD SUBMISSION 07/29/2019
95% CD SUBMISSION 10/07/2019
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
CIRCULAR BLANK OPENINGS
SYSTEM NO. C-AJ-0055
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F RATING - 3 HR
FT RATING - 0 HR
FH RATINGS - 3 HR
FTH RATING - 0HR
F RATING - 3 HR
T RATING - 0 HR
1. FLOOR OR WALL ASSEMBLY- MIN 4-112 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PEL) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL
CLASSIFIED CONCRETE BLOCKS'. MAX DIAM OF OPENING IS 4 IN. (102 MM).
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES
OF MANUFACTURERS.
2. METALLIC SLEEVE- NOM 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL
PIPE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH
FLOOR OR WALL SURFACES. SLEEVE MAY EXTEND MAX 3 IN. (76 MM) ABOVE TOP SURFACE OF
FLOOR.
3. FILL, VOID OR CAVITY MATENAL'- FIRE BLOCK MIN 2 IN. (51 MM) THICK CUT TO A DIAM 1/2 IN. (13
MM) LARGER THAN THE OPENING, FLUSH WITH BOTTOM SURFACE
OF FLOOR OR WITH BOTH SURFACES OF WALL.
'BEARING THE UL CLASSIFICATION MARK
A
A
SECTION A-A
GENERAL NOTES:
1. REFER TO SECTION 078413 OF THE SPECIFICATIONS.
FOR QUALITY CONTROL REQUIREMENTS.
2. DETAILS SHOWN ARE FOR TYPICAL APPLICATIONS AND MAY NOT
BE INCLUSIVE OF ALL PROJECT REQUIREMENTS. SOME DETAILS
COULD BE USED FOR EITHER WALL OR FLOOR APPLICATIONS. IF
FIELD CONDITIONS DO NOT MATCH REQUIREMENTS OF TYPICAL
DETAILS, CONTRACTOR SELECTED MANUFACTURER APPROVED
ALTERNATE DETAILS SHALL BE UTILIZED. FIELD CONDITIONS AND
DIMENSIONS NEED TO BE VERIFIED FOR COMPLIANCE WITH THE
DETAILS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: *
MINIMUM AND MAXIMUM WIDTH OF JOINTS * TYPE AND THICKNESS
OF FIRE-RATED CONSTRUCTION. THE MINIMUM ASSEMBLY RATING
OF THE FIRESTOP ASSEMBLY SHALL MEET OR EXCEED THE
HIGHEST RATING OF THE ADJACENT CONSTRUCTION.
3. IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS ARE
NOT AVAILABLE, MANUFACTURER'S ENGINEERING JUDGMENT
DRAWINGS ARE ACCEPTABLE. DRAWINGS SHALL FOLLOW THE
INTERNATIONAL FIRESTOP COUNCIL (IFC) GUIDELINES FOR
EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS.
PROVIDE ARCHITECT WITH REQUIRED SUBMITTALS.
4. FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS OF
ASTM E-814 (UL 1479) TESTED ASSEMBLIES THAT PROVIDE A FIRE
RATING EQUAL TO THAT OF CONSTRUCTION BEING PENETRATED.
5. ALL RATED THROUGH-PENETRATION ASSEMBLIES
SHALL BE PROMINENTLY LABELED.
6. FOR OUTLET BOXES REQUIRING PROTECTION, USE ONLY WALL
OPENING PROTECTIVE MATERIALS, CATEGORY CLIV AS CLASSIFIED
BY UNDERWRITER'S LABORATORIES, FIRE RESISTANCE DIRECTORY.
++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN. DIAM PIPE IN 2" DEVICE ETC.) L RATING DOES NOT APPLY TO CP 680N DEVICES.
4. FIRESTOP DEVICE* — (NOT SHOWN) -TOP SEAL PLUG FOR USE WITH CP 680-75/2.5"N DEVICES AND NOM PIPE OR CONDUIT SIZES 3/4 IN. (19 MM) TO 2 IN. (51 MM), INSTALLED IN ACCORDANCE WITH THE MANUFACTURER\'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38
MM). W RATING APPLIES ONLY WHEN THE CPS OR IPS TOP SEAL PLUGS ARE USED.
4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - APPLIES TO NOM 2", 3" AND 4" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3" AND CP 680-P 4" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF
DEVICE. W RATING APPLIES ONLY WHEN WATER BARRIER MODULE IS USED.
*BEARING THE UL CLASSIFICATION MARK
+BEARING THE UL LISTING MARK
1. FLOOR ASSEMBLY — MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150
PCF OR 1600-2400 KG/M3) CONCRETE.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:
A. CONCRETE — MIN 2-1/2 IN (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR
1600-2400 KG/M3) CONCRETE.
B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP GALV STEEL
FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN.
2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS. THE 3, 4 AND 6 IN. DEVICES MAY EXTEND A MAX 2 IN. (51 MM) ABOVE THE TOP SURFACE OF THE CONCRETE. THE MAX EXTENSION ABOVE THE SLAB FOR THE 2 AND 2.5 IN. DEVICES IS NOT RESTRICTED.
3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE
FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR
VENT) PIPING SYSTEMS.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SDR11 OR
SDR13.5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
C. RIGID NONMETALLIC CONDUIT+ — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT
INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:
NOM PIPE DIAMETER FIRESTOP DEVICE
CP 680-75/2.5"N
CP 680 -P 2"
CP 680-P 3"
CP 680-1 10/4"N
CP 680-P 4"
CP 680-160/6"N
CP 680-P 6"
1/2 IN. TO 2 IN. (19 MM TO 51 MM)
3 IN.(76 MM)
3 IN. TO 4 IN. (76 MM TO 102 MM)
6 IN. (152 MM)
2 3
A
A
SECTION A-A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. F-A-2053
F RATING - 2 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)
SINGLE NON-METALLIC PIPE OR CONDUIT
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
MIXED PENETRANTS
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F RATING - 3 HR
FT RATING - 0 HR
FH RATING - 3 HR
FTH RATING - 0HR
L RATING AT AMBIENT - 5 CFM/SQ FT
L RATING AT 400 F - 2 CFM/SQ FT
F RATING - 3 HR
T RATING - 0 HR
L RATING AT AMBIENT - 5 CFM/SQ FT
L RATING AT 400 F - 2 CFM/SQ FT
1. FLOOR OR WALL ASSEMBLY- 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PEL) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*.
MAX AREA OF OPENING IS 1296 IN. SQ (8361 CM2) WITH MAX DIMENSION OF 36 IN. (914 MM). SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. CABLE TRAY*- MAX 18 IN. (457 MM) WIDE BY MAX 6 IN. (152 MM) DEEP OPEN-LADDER OR SOLID-BACK CABLE TRAY WITH CHANNEL-SHAPED SIDE RAILS FORMED OF 0.060 IN. (1.52 MM) THICK ALUMINUM OR STEEL AND WITH 1-1/2 IN. (38 MM) WIDE BY 1 IN. (25 MM) CHANNEL SHAPE RUNGS SPACED 9 IN. (229 MM) OC OR A 0.029 IN.
(0.74 MM) THICK STEEL SOLID BACK, RESPECTIVELY. ONE CABLE TRAY TO BE INSTALLED IN THE OPENING. THE MAX ANNULAR SPACE BETWEEN THE CABLE TRAY AND ADJACENT PENETRANTS IS 9 IN. (229 MM) AND
BETWEEN THE CABLE TRAY AND PERIPHERY OF THE OPENING SHALL BE MIN 1-112 IN. (38 MM) TO MAX 4-1/2 IN. (114 MM). CABLE TRAY TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
3. CABLES -AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN CABLE TRAY TO BE MAX 30 PERCENT OF THE CROSS-SECTIONAL AREA OF THE CABLE TRAY BASED ON A MAX 3 IN. (76 MM) CABLE LOADING DEPTH WITHIN THE CABLE TRAY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF COPPER CONDUCTOR OR
FIBER OPTIC CABLES MAY BE USED:
A. 7/C NO. 12 AWG WITH POLYVINYL CHLORIDE (PVC) INSULATION AND PVC JACKET.
B. 300 PAIR- NO. 24 AWG CABLE WITH PVC INSULATION AND JACKET.
C. 1/C, 350 KCMIL WITH CROSS-LINKED POLYETHYLENE (XLPE) INSULATION AND JACKET.
D. 1/C, 500 KCMIL WITH THERMO PLASTIC INSULATION AND POLYVINYL CHLORIDE (PVC) JACKET.
E. TWENTY FOUR FIBER OPTIC CABLE WITH PVC SUB UNIT AND JACKET.
4. THROUGH-PENETRANTS- ONE OR MORE PIPE, CONDUIT OR TUBE TO BE INSTALLED WITHIN THE OPENING.
THE TOTAL NUMBER OF THROUGH-PENETRANTS IS DEPENDENT ON THE SIZE OF THE OPENING AND TYPES AND SIZES OF THE PENETRANTS. ANY COMBINATION OF THE PENETRANTS DESCRIBED BELOW MAY BE USED PROVIDED THAT THE FOLLOWING PARAMETERS RELATIVE TO THE ANNULAR SPACES AND THE SPACINGS BETWEEN THE PIPES ARE MAINTAINED. THE SPACE BETWEEN PIPES, CONDUITS OR TUBING AND BETWEEN THE PERIPHERY OF THE OPENING AND THE PIPES OR CONDUITS SHALL BE MIN 1 IN. (25 MM) TO MAX 4-1/2 IN.
(114 MM). PIPE, CONDUIT OR TUBE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. NOM 6 IN. (152 MM) DIAM (OR SMALLER) RIGID GALV STEEL CONDUIT.
B. NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
C. NOM 4 IN. (102 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
D. NOM 4 IN. (102 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.
E. NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
F. NOM 6 IN. (152 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
5. PIPE COVERING- NOM 1-1/2 IN. (38 MM) THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PEL) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. SEE PIPE AND EQUIPMENT COVERING
AND MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF
MANUFACTURERS. ANY PIPE
COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 MAY BE USED.
6. CABLES- MAX 2 IN. (51 MM) DIAM TIGHT BUNDLE OF CABLES CENTERED IN OPENING AND RIGIDLY SUPPORTED ON BOTH SURFACES OF FLOOR AND WALL. ANY COMBINATION OF THE FOLLOWING TYPES AND
SIZES OF CABLES MAY BE USED:
A. 7/C NO. 12 AWG WITH POLYVINYL CHLORIDE (PVC) INSULATION AND PVC JACKET.
B. 25 PAIR- NO. 24 AWG CABLE WITH PVC INSULATION AND JACKET.
C. 2/C NO. 10 AWG WITH PVC INSULATION AND JACKET.
D. 3/C NO. 8 AWG ALUMINUM CLAD CABLE WITH CROSS-LINKED POLYETHYLENE (XLPE) INSULATION AND
PVC JACKET.
E. TYPE RC- 62 AIU COAXIAL CABLE WITH AIR CORE AND PVC JACKET.
F. 24 FIBER OPTIC CABLE WITH PVC SUB UNIT AND OUTER JACKET.
7. FIRESTOP SYSTEM- THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. FILL, VOID OR CAVITY MATERIAL'- FIRE BLOCKS INSTALLED WITH LONG DIMENSION PASSED THROUGH
THE OPENING AND CENTERED WITHIN THE THICKNESS OF THE FLOOR OR WALL. BLOCKS TO BE FIRMLY PACKED AND COMPLETELY FILL THE ENTIRE AREA AND THICKNESS OF OPENING. EITHER ONE OR A
COMBINATION OF THE BLOCK TYPES SPECIFIED BELOW MAY BE USED.
B. FILL, VOID OR CAVITY MATERIAL'- (NOT SHOWN) FILL MATERIAL TO BE FORCED INTO INTERSTICES OF CABLES AND BETWEEN CABLES AND CABLE TRAYS TO MAX EXTENT POSSIBLE ON BOTH SURFACES OF THE
PENETRATION.
C. WIRE MESH (NOT SHOWN)- WHEN THE ANNULAR SPACE EXCEEDS 4-1/2 IN. (114 MM) TO THE PERIPHERY, A NOM 2 IN. SQ (51 MM SQ.) WIRE FENCING SHALL BE USED TO KEEP THE FIRE BLOCKS IN PLACE. THE WIRE FENCING IS FABRICATED FROM MIN NO. 16 SWG (0.060 IN.) (1.52 MM) GALV STEEL WIRE. THE WIRE IS CUT TO FIT THE CONTOUR OF THE PENETRATING ITEM WITH A MIN 3 IN. (76 MM) LAP BEYOND THE PERIPHERY OF THE OPENING. WIRE FENCING SECURED TO TOP SURFACE OF FLOOR AND BOTH SURFACES OF WALL ASSEMBLY BY MEANS OF 1/4 IN. (6 MM) DIAM BY 1 IN. (25 MM) LONG CONCRETE ANCHORS AND 1/4 IN. (6 MM) BY 1-112 IN. (38
MM) DIAM FENDER WASHERS SPACED MAX 8 IN. (203 MM) OC.
'BEARING THE UL CLASSIFICATION MARK
SYSTEM NO. C-AJ-8056
A
A
2 5
SECTION A-A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. F-A-2054
F RATING - 3 HR
T RATING - 0 AND 3 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)
1. FLOOR ASSEMBLY — MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL
WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND
STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER
SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND AS
SUMMARIZED BELOW:
A. CONCRETE — MIN 4-1/2 IN (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT
(100-150 PCF OR 1600-2400 KG/M3) CONCRETE.
B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM)
DEEP GALV STEEL FLUTED UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN.
2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING
CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH
ACCOMPANYING INSTALLATION INSTRUCTIONS. THE DEVICES MAY EXTEND A MAX 2 IN. (51 MM) ABOVE
THE TOP SURFACE OF THE CONCRETE.
3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE
FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR
ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — PIPE-NOM 6 IN. (152 MM) DIAM (OR
SMALLER) SDR11 OR SDR13.5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING
SYSTEMS.
C. RIGID NONMETALLIC CONDUIT+ — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40
PVC CONDUIT INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:
+3 HR T RATING APPLIES WHEN CP 680-P 3" AND CP 680-P 4" DEVICES ARE USED. 3 HR T RATING ALSO APPLIED WHEN CP 680-110/4"N DEVICE IS USED PROVIDED THAT MIN 4 IN. (102 MM) THICKNESS OF NOM 4 PCF (64 KG.M3) MINERAL WOOL BATT INSULATION TIGHTLY PACKED WITHIN ANNULUS BETWEEN PIPE AND WALL OF CP 680-110/4"N DEVICE. ++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN. DIAM PIPE IN 2" DEVICE ETC.) L RATING DOES NOT APPLY
TO CP 680N DEVICES.
4. FIRESTOP DEVICE — TOP SEAL PLUG FOR USE WITH CP 680-P 2" DEVICE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38 MM). W RATING APPLIES ONLY TO THE IPS TOP SEAL PLUG AND NOM 2 IN. DIAM PENETRANTS
AND CPS TOP SEAL PLUG FOR NOM ½ TO 2 IN. (13 TO 51 MM) DIAM PENETRANTS.
4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - ALTERNATE TO TOP SEAL PLUG (ITEM 4). APPLIES TO NOM 2", 3", 4" AND 6" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3", CP 680-P 4" AND CP 680-P 6" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF DEVICE. W RATING APPLIES ONLY WHEN
WATER BARRIER MODULE IS USED AND NOM DIAM OF PENETRANT EQUALS SIZE OF DEVICE.
*BEARING THE UL CLASSIFICATION MARK
+BEARING THE UL LISTING MARK
NOM PIPE DIAMETER FIRESTOP DEVICE T RATING - HR
1/2 IN. TO 2 IN.
(19 MM TO 51 MM)
3 IN. (76 MM)
4 IN. (102 MM)
6 IN. (152 MM)
CP 680-75/2.5"N
CP 680-P 2"
CP 680-110-P 4"
CP 680-110/4"N
CP 680-P 3", CP 680-P 4"
CP 680-P 4"
CP 680-160/6"N
CP 680-P 6"
0 AND 3+
SINGLE NON-METALLIC PIPE OR CONDUIT
A A
SECTION A-A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
SINGLE INSULATED PIPES
SYSTEM NO. C-BJ-5006
F RATING - 4 HR
T RATING - 1/2 HR
1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL
WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED
CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 29 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
2. THROUGH-PENETRANTS — ONE METALLIC PIPE TO BE INSTALLED EITHER CONCENTRICALLY
OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH
SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES
MAY BE USED:
A. STEEL PIPE — NOM 20 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
3. PIPE COVERING — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS
SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE.TRANSVERSE
JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT.
PIPE COVERING TO TERMINATE MIN 6 IN. FROM EACH SIDE OF FLOOR OR WALL ASSEMBLY. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS
DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE
ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD
INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
4. FIRESTOP SYSTEM — THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PIPE COVERING* — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 5.2 PCF) UNFACED MINERAL WOOL UNITS EXTENDING MIN 6 IN. BEYOND EACH SURFACE OF THE FLOOR OR WALL. PIPE COVERING SECURED WITH NO. 18 GAUGE TIE WIRE 3 IN. BEYOND EACH SURFACE OF THE CONCRETE SLAB. THE ANNULAR SPACE SHALL BE MIN 1 IN. TO MAX 2-1/4 IN. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY
FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE
SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX
OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
B. SHEATHING MATERIAL* — ALL SERVICE JACKET MATERIAL SHALL BE WRAPPED AROUND
THE OUTER CIRCUMFERENCE OF THE PIPE COVERING MATERIAL (ITEM 4A) WITH KRAFT FACING
EXPOSED. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS. SEE SHEATHING MATERIAL
(BVDV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS.
ANY SHEATHING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL
CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE
DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
C. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT
INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE
RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
D. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL
APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE COVERING AND METAL COVER PLATE (ITEM NO. 4E) AND OVER BUTTED SEAMS OF METAL COVER
PLATE.
E. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D.
SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES
OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE, PENETRATING
THE SHEATHING MATERIAL AND PIPE COVERING (ITEM NOS. 4B AND 4A) TO FULLY CONTACT THE PIPE. SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN. FROM EACH SIDE OF EACH SEAM
AND A MAX OF 4 IN. OC THROUGHOUT.
*BEARING THE UL CLASSIFICATION MARK
A
A
SECTION A-A
4E 4D
4C
4D
4A
4B
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. C-BJ-1034
F RATING - 4 HR
T RATING - 0 HR
1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF
OPENING IS 10-1/2 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 3/4 IN. TO MAX 3 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE — NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT — NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
3. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF
FILL MATERIAL.
4. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE, CONDUIT OR TUBING AND METAL COVER PLATE (ITEM
NO. 5) AND OVER BUTTED SEAMS OF METAL COVER PLATE.
5. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D. SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE OR CONDUIT AND SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN. FROM EACH SIDE OF EACH SEAM AND A MAX OF 4 IN. OC THROUGHOUT.
*BEARING THE UL CLASSIFICATION MARK
A
A SECTION A-A
SINGLE INSULATED PIPES
MICHAEL DWAYNE
LIEZERT
S
TATE OF OHIO
R E
G
ISTERED ARCHIT
E C
T9939
Project Number
Office of Construction and Facilities Management
Building Number
Drawing Number
VA FORM 08-6231
CONSULTANTS: ARCHITECTS/ENGINEERS: ARCHITECTURAL PROJECT #
VA Building th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o
F
E
D
C
B
A
F
E
D
C
B
A
987654321
987654321
Project Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
KEY PLAN
Dwg. of
FULLY SPRINKLERED
PHILIP P. KIRK
CHIEF ENGINEER
:2 :3
A M
C U s e rs jc h o D o c u m e n ts R
N E W
M R I S
IT
E
P R E P C e n tr a l_ jc h o .r v t
FIRE STOPPING DETAILS
GI-110
BH Designer
552-CSI-176
NEW MRI SITE PREP
02/21/2020
4100 WEST THIRD STREET, DAYTON, OHIO 45428
18106
BID & CONSTRUCTION
Revisions Date
95% CD SUBMISSION 10/07/2019
FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE FLOOR. MIN 5 IN. (127 MM) THIC REINFORCD LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS. MAX SIZE OF OPENING IS 1440 IN.² (9,290 CM²) WITH A MAX DIMENSION FO 48 IN. (1219 MM). SEE CONCRETE BLOCKS CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
THROUGH-PENETRANT - ONE CABLE TRAY AND ONE OR MORE PIPES, TUBES OR CABLE BUNDLES MAY BE INSTALLED WITHIN THE OPENING, THE TOTAL NUMBER OF THROUGH-PENETRANTS DESCIBED BELOW MAY BE USED PROVIDED THAT THE FOLLOWING PARAMETERS RELATIVE TO THE ANNULAR SPACES ARE MAINTAINED. THE ANNULAR SPACE BETWEEN INDIVIDUAL CABLES AND CABLE BUNDLES SHALL BA A MIN 1/2 IN. (13 MM). THE ANNULAR SPACE BETWEEN INDIVIDUAL CABLES AND CABLE BUNDLES AND OTHER PENETRANTS SHALL BE A MIN 1/2 IN. ( 13 MM) EXCEPT THAT A MIN 2 IN. (51 MM) SHALL BE MAINTAINED BETWEEN THE CABLES AND COPPER PIPES AND TUBES GREATER THAN A NOM 3 IN. (76 MM) DIAM AND STEEL AND IRON PIPES AND CONDUITS GREATER THAN A NOM 4 IN. (102 MM) DIAM. THE ANNULAR SPACE BETWEEN METALLIC PIPES, CONDUIT AND TUBES AND INSULATED PIPES AND TUBES SHALL BE A MIN 2 IN. (51 MM). THE ANNULAR SPACE BETWEEN NOM 3 IN. (76MM) DIAM (AND SMALLER) COPPER PIPES SHALL BE MIN 1/2 IN. (13 MM). THE ANNULAR SPACE BETWEEN NOM 2 IN. (51 MM) DIAM (AND SMALLER) METALLIC PIPES AND CONDUITS SHALL BE MIN 1/2 IN. (13 MM). THE ANNULAR SPACE BETWEEN NOM 2. IN (51 MM) DIAM (AND SMALLER) METALLIC PIPES AND CONDUITS SHALL BE MIN 0 IN. (POINT CONTACT). THE ANNULAR SPACE BETWEEN INSULATED PENETRANTS OR THE CABLE TRAY AND THE PERIPHERY OF OPENING SHALL BE MIN 1/2 IN. (13 MM). THE ANNULAR SPACE BETWEEN ALL OTHER PENETRANTS AND THE PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT). A MAX ANNULAR SPACE IN THE SYSTEM SHALL BE 12 IN. (305 MM). THE FOLLOWING TYPES AND SIZES OF PENETRANTS MAY BE USED.
SYSTEM NO. C-AJ-8143
F RATING - 2 HR
T RATING - 0 HR
MIXED PENETRANTS
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
SECTION A-A
4A 4B
4B
2 2 2
A A
A. METALLIC PIPES - THE FOLLOWING TYPES OF METALLIC PIPES, TUBES OR CONDUITS MAY BE USED:
1. COPPER TUBING - NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBE.
2. COPPER PIPE - NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. STEEL PIPE - NOM 24 IN. (610 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE.
4. IRON PIPE - NOM 24. IN. (610 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
5. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) ELECTRIC METALLIC TUBING (EMT) OR NOM 6 IN.
(152 MM) DIAM (OR SMALLER) RIGID STEEL CONDUIT.
B. CABLES BUNDLES - MAX 4 IN. (102 MM DIAM TIGHTLY BUNDLED CABLES. ANY COMBINATION OF THE
FOLLOWING TYPES AND SIZES OF CABLES MAY BE USED:
1. MAX 500 KCMIL SINGLE COPPER OR ALUMINUM CONDUCTOR POWER CABLE WITH THERMOPLASTIC
INSULATION AND POLYVINYL CHLORIDE (PVC) JACKET.
2. MAX 300 PAIR NO. 24 AWG COPPER OR ALUMINUM CONDUCTOR POWER CABLE WITH
THERMOPLASTIC INSULATION AND POLYVINYL CHLORIDE (PVC) JACKET.
3. MAX 7/C COPPER CONDUCTOR NO. 12 AWG MULTI-CONDUCTOR POWER AND CONTROL CABLES
WITH PVC OR CROSS-LINKED POLYETHYLENE (XLPE) INSULATION AND PVC JACKET.
4. MULTIPLE FIBER OPTICAL COMMUNICATION CABLES JACKETED WITH PVC AND HAVING A MAX
OUTSIDE DIAM OF 1/2 IN.
5. MAX 3/C NO. 12 AWG STEEL CLAD CABLE WITH COPPER CONDUCTORS AND PVC INSULATION
MATERIAL.
C. INDIVIDUAL CABLES - ANY OF THE FOLLOWING TYPES AND SIZES OF INDIVIDUAL (NON-BUNDLED) CABLES
MAY BE USED:
1. MAX 3/C NO. 2/0 AWG (OR SMALLER) COPPER CONDUCTOR PVC JACKETED ALUMINUM CLAD OR
STEEL CLAD TECK 90 CABLE.
2. THROUGH PENETRATING PRODUT (XHLY) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR
NAMES OF MANUFACTURERS.
3. MAX 500 K CMIL SINGLE COPPER OR ALUMINUM CONDUCTOR POWER CABLE WITH THERMOPLASTIC
INSULATION AND POLYVINYL CHLORIDE (PVC) JACKET.
4. MAX 300 PAIR NO. 24 AWG COPPER CONDUCTOR TELECOMMUNICATION CABLES WITH PVC
INSULATION AND JACKET MATERIAL.
5. MAX 7/C COPPER CONDUCTOR NO. 12 AWG MULTI-CONDUCTOR POWER CONTROL CABLES WITH
PVC OR CROSS-LINKED POLYETHYLENE (XLPE) INSULATION AND PVC JACKET.
6. MULTIPLE FIBER OPTICAL COMMUNICATION CABLES JACKETED WITH PVC AND HAVING A MAX
OUTSIDE DIAM OF 1/2 IN.
7. MAX 4C/750 KCMIL (OR SMALLER) ALUMINUM OR COPPER CONDUCTOR METAL CLAD CABLE WITH
ALUMINUM OR STEEEL ARMOR, WITH OR WITHOUT PVC JACKET.
D. CABLE TRAY* - (NOT SHOWN) - MAX 24 IN. (610 MM) WIDE BY 6 IN. (152 MM) DEEP OPEN-LADDER STEEL OR ALUMINUM CABLE TRAY. AGGREGATE CROSS-SECTIONAL AREA OF CABLE TRAY TO BE MAX 40% OF THE CROSS- SECTIONAL AREA OF THE CABLE TRAY BASED ON A MAX 3 IN. BALE LOADING DEPTH. ANY COMBINATION OF THE TYPES AND SIZES OF CABLES DESRIBED IN ITEM 2B MAY BE USED. CABLE TRAY TO BE RIGIDLY SUPPORTED ON
BOTH SIDES OF FLOOR OR WALL ASSEMBLY.
1.
2.
3.
4.
PIPE INSULATION - (OPTIONAL) - PIPES AND TUBES OF THE SIZES NOTED BELOW MAY BE PROVIDED WITH ONE OF THE
FOLLOWING TYPES OF PIPE INSULATIONS:
A. PIPE COVERING* - NOM 1-1/2 IN. (38 MM) THICK (OR THINNER) HOLLOW CYLINDRYCAL HEAVY DENSITY GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET FOR PIPES WITH A NOM DIAM OF 8 IN. (203 MM)(OR SMALLER) OR TUBES WITH A NOM DIAM OF 4 IN. (102 MM)(OR SMALLER).
LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE.
TRANVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. SEE PIPE AND EQUIPMENT COVERING-MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICTIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF
25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
B. PIPE COVERIN* - NOM 2 IN. (51 MM) THICK (OR THINNER) HOLLOW CYLINDRICAL HEAVY DENSITY GLASS FIBER UNITS JCKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET FOR PIPES OR TUBES WITH A NOM DIAM OF 2 IN. (51 MM) (OR SMALLER). LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. SEE PIPE AND EQUIPMENT COVERING-MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERICAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICTION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS
MAY BE USED.
C. TUBE INSULATION-PLASTICS+ - NOM 1 IN. (25 MM) THICK (OR THINNER) ACRYLONITRILE BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE FOAM FURNISHED IN THE FORM OF TUBING FOR PIPES OR TUBES WITH A NOM DIAM OF 2 IN. (51 MM)(OR SMALLER). SEE NAMES OF MANUFACTURERS. ANY RECOGNIZED COMPONENT TUBE INSULATION MATERIAL MEETING THE ABOVE SPECIFICATIONS AND
AHAVING A UL 94 FLAMMABILITY CLASSIFICATION OF 94-5VA MAY BE USED.
FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL - MIN 4 IN. (102 MM) THICKNESS OF 4 PCF (64 KG/M³) MINERAL WOOL BATT INSULATION
TIGHTLY PACKED INTO THE OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL TO ACCOMMODATE THE REQUIRED THICKNESS OF
FILL MATERIAL.
B. FILL, VOID, OR CAVITY MATERIAL - SEALANT* - MIN 1/2 IN. (13 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS FLUSH WITH THE TOP SURFACE OF THE FLOOR OR BOTH SURFACES OF THE WALL
*BEARING THE UL CLASSIFICATION MARK
SYSTEM NO. C-AJ-8095
F RATING - 4 HR
T RATING - 0 HR
L RATING AT AMBIENT - 14 CFM/SQ FT
L RATING A 400 F - 14 CFM/SQ FT
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
B
B
A A
SECTION A-A
SECTION B-B
5B
5B
5B
3 2
MIXED PENETRANTS
FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL
CLASSIFIED CONCRETE BLOCKS*. MAX AREA OF OPENING 1024 SQ IN. WITH MAX DIMENSION OF
32 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR
NAMES OF MANUFACTURERS.
CABLE TRAY+ - A MAX OF TWO CABLE TRAYS MAY BE INSTALLED WITHIN THE OPENING.
ANNULAR SPACE BETWEEN CABLE TRAY AND PERIPHERY OF OPENING SHALL BE MIN OF 2 IN.
CABLE TRAYS SHALL BE SPACED A MIN OF 5 IN. APART AND RIGIDLY SUPPORTED ON BOTH
SIDES OF THE FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES OF CABLE TRAYS MAY BE
USED:
1.
2.
3.
4.
5.
A. MAX 24 IN. WIDE BY MAX 6 IN. DEEP OPEN LADDER CABLE TRAY WITH
CHANNEL-SHAPED SIDE RAILS FORMED OF MIN 0.050 IN. THICK (NO. 18
MSG) GALV STEEL AND WITH 7/8 IN. WIDE BY 7/8 IN. DEEP RUNGS SPACED
9 IN. O.C.
B. MAX 24 IN. WIDE BY MAX 6 IN. DEEP OPEN LADDER CABLE TRAY WITH
CHANNEL-SHAPED SIDE RAILS FORMED OF MIN 0.073 IN. THICK ALUMINUM
AND WITH 1 IN. WIDE BY 1 IN. DEEP RUNGS SPACED 9 IN. O.C.
CABLES - AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN CABLE TRAY TO BE MAX 27
PERCENT OF THE CROSS-SECTIONAL AREA OF THE CABLE TRAY BASED ON THE FULL LOADING
DEPTH WITHIN THE CABLE TRAY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF
COPPER CONDUCTOR CABLES MAY BE USED:
A. MAX 1/C 500 KCMIL POWER CABLE WITH NYLON JACKET.
B. MAX 1/C 300 KCMIL POWER CABLE WITH NYLON JACKET.
C. MAX 25 PAIR NO. 24 AWG (OR SMALLER) POLYVINYL CHLORIDE (PVC)
INSULATED AND JACKETED TELEPHONE CABLES.
D. MAX 3/C W/GROUND NO. 12 AWG CABLE WITH PVC INSULATION AND
JACKET.
E. MULTIPE 2 LEAD FIBER OPTICAL COMMUNICTION CABLE JACKETED WITH
PVC AND HAVING AMAX OUTSIDE DIMENSION OF 0.12 x 0.24 IN.
THROUGH-PENETRANTS - A MAX OF 4 PIPES, CONDUITS OR TUBING TO BE INSTALLED WITHING THE OPENING. THE SPACE BETWEEN PIPES, CONDUITS OR TUBING SHALL BE MIN 2-1/2 IN. THE
SPACE BETWEEN PIPES, CONDUITS OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 5
IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL
ASSEMBLY. THE FOLLOWING TYPE AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY
BE USED:
A. STEEL PIPE - NOM 26 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER)
STEEL PIPES.
B. IRON PIPE - NOM 15 IN DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRIC METALLIC
TUBING.
D. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) RIGID STEEL CONDUIT.
E. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER)
COPPER TUBING.
F. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER)
COPPER PIPE.
FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. FORMS - (NOT SHOWN) - USED AS A FORM TO PREVENT LEAKAGE OF FILL
MATERIAL DURING INSTALLATION. FORMS TO BE A RIGID SHEET
MATERIAL, CUT TO FIT THE CONTOUR OF THE PENETRATING ITEMS AND
LOCATED WHERE NECESSARY FOR INSTALLATION OF FILL MATERIAL.
FORMS TO BE REMOVED AFTER FILL MATERIAL HAS CURED.
B. FILL, VOID OR CAVITY MATERIAL* - MORTAR - MIN 4-1/2 IN. THICKNESS OF
FILL MATERIAL TO MAX EXTENT POSSIBLE. MORTAR IS MIXED AT A RATE
OF 2-1/2 PARTS DRY MIX TO ONE PART WATER BY BOLUME IN
ACCORDANCE WITH THE FILL MATERIAL MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
*BEARING THE UL CLASSIFICATION MARK
SYSTEM NO. C-AJ-1226
F RATING -…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .