36C25019B0041-004.pdf
PDF 14 MB Posted
- Solicitation number
- 36C25019B0041
About this file
36C25019B0041 Part 2 - Drawings - Pharmacy USP (541-19-103).pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25019B0041-0004000.docx | DOCX document | |
| 36C25019B0041-0003001.pdf | ||
| 36C25019B0041-0003005.pdf | ||
| 36C25019B0041-0003000.docx | DOCX document | |
| 36C25019B0041-0003003.pdf | ||
| 36C25019B0041-0003002.pdf | ||
| 36C25019B0041-0003004.pdf | ||
| 36C25019B0041-0003006.pdf | ||
| 36C25019B0041-0002000.docx | DOCX document | |
| 36C25019B0041-0002001.pdf | ||
| 36C25019B0041-0001000.docx | DOCX document | |
| 36C25019B0041-006.pdf | ||
| 36C25019B0041-002.pdf | ||
| 36C25019B0041-003.pdf | ||
| 36C25019B0041-007.pdf | ||
| 36C25019B0041-005.pdf | ||
| 36C25019B0041-001.docx | DOCX document | |
| 36C25019B0041-000.docx | DOCX document |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OPEN TO
BEYOND 2'
SS-1
PT-6
RB-3
7'
3' - 0" 3' - 0" 3' - 0"
PL-2
2'
2'
PL-2
2'
0"
2' - 0"
SS-1
1/4" THICK PLEXI-GLASS
DIVIDER PANEL,
BRACKETED TO WALL &
COUNTER
CG-1
CG-1
H
AS-3.1
E
AS-3.1
Sim
7' - 0"
EX, PAPER TOWEL
DISPENSER, SALVAGED
FROM DEMOLITION, TO
BE REINSTALLED WITH
TOWEL CUTOUT
LOCATED 6" ABOVE
BACKSPLASH
EX, SOAP DISPENSER,
SALVAGED FROM
DEMOLITION, TO BE
REINSTALLED WITH
PUSH BUTTON
OPERATOR LOCATED 6"
ABOVE BACKSPLASH
1. ALL FINISH MATERIALS SHALL BE INSTALLED PER MANUFACTURER'S DIRECTIONS.
2. SUBMIT ALL SAMPLES FOR ARCHITECT'S APPROVAL. REFER TO MATERIAL SPECIFICATIONS FOR
REQUIREMENTS.
3. REFER TO FINISH SCHEDULE FOR ALL ABBREVIATIONS AND MATERIAL SPECS. REFER TO FINISH PLAN FOR
ADDITIONAL MATERIAL/COLOR LOCATIONS.
4. ANY SPECIFIC BRAND NAMES LISTED, OR ITEMS NOTED AS "BASIS OF DESIGN," ARE INTENDED TO INDICATE THE QUANTITY, STYLE, AND/OR GENERAL APPEARANCE FOR A SPECIFIC PRODUCT, AND ARE NOT
INTENDED TO INDICATE SOLE SOURCING OF THAT PRODUCT. CONTRACTOR MAY USE PRODUCTS
FROM OTHER MANUFACTURERS THAT ARE EQUIVALENT IN STYLE, QUALITY, AND APPEARANCE TO
THOSE LISTED. SUBSTITUTIONS MUST BE SUBMITTED TO ARCHITECT FOR APPROVAL PRIOR TO
ORDERING SUCH MATERIALS.
5. CONTRACTOR RESPONSIBLE FOR APPROPRIATE TRANSITION STRIPS AT CENTERLINE OF DOOR THRESHOLD OR AS DELINEATED ON FINISH PLAN WHEREVER THERE IS A CHANGE IN FLOOR MATERIAL.
6. REFER TO REFLECTED CEILING PLAN FOR ADDITIONAL CEILING INFORMATION.
7. ALL OUTSIDE CORNERS OF QUARTZ OR SOLID SURFACE COUNTERTOPS SHALL RECEIVE 3/4" RADIUS.
8. CONTRACTOR TO PROVIDE SOLID FIRE RETARDANT TREATED WOOD BLOCKING IN STUD SPACE AND
PROVIDE ANCHORS THROUGH GYPSUM WALLBOARD AND WOOD BLOCKING. PLASTIC HANGERS AND
INSERTS TO BE AVOIDED.
9. ALL MILLWORK TO BE CONSTRUCTED OF 3/4" PLASTIC LAMINATE MATERIAL AS INDICATED IN SECTIONS, UNLESS NOTED OTHERWISE.
10. FASTENERS FOR KNEE BRACE SUPPORTS ARE TO BE FINISHED CHROME HEADED SCREWS.
11. DRAWER CONSTRUCTION, MATERIALS, AND JOINERY IS TO BE PREMIUM GRADE PER AWI STANDARDS.
12. ALL SURFACES, INCLUDING THOSE CONCEALED AFTER INSTALLATION, ARE TO BE FINISHED PER
SPECIFICATION. MIN. BACKER BK-20.
13. ALL CABINETS WITH DOORS SHALL RECEIVE CYLINDER LOCKS AT EACH DOOR LEAF. COORD. REQUIRED
KEYING W/VA.
14. EXPOSED WALL CLEATS ARE TO BE PAINTED FINISH. AT WORK SURFACES PROVIDE BEVELED CUT AND
HOLD BACK MIN. 4" FROM LEADING EDGE OF WORK SURFACE.
15. 1" OVERHANG TYPICAL @ COUNTERTOPS WITH BASE CABINETS BELOW UNLESS NOTED OTHERWISE.
16. SCRIBES AT CABINET BODY ARE TO BE FLUSH WITH BODY. SCRIBES/FILLERS AT DOORS AND DRAWER
FRONTS ARE TO BE FLUSH WITH DOOR OR DRAWER FRONTS.
17. DRAWERS ARE TO BE FULL-DEPTH OF COUNTER U.N.O.
18. ALL CABINET INTERIORS ARE TO BE PER SPECIFICATIONS. HPDL GP-28 (VERTICAL GRADE LAMINATE).
19. ALL COUNTERTOPS SHALL BE INSTALLED UPON MIN. 3/4" PLYWOOD SUBSTRATE.
20. REFER TO SPECIFICATIONS FOR HARDWARE GUIDELINES AND STANDARDS.
21. CONTRACTOR TO COORDINATE POWER/CABLE OUTLET LOCATIONS WITH VA-PROVIDED TV'S IN FIELD WHERE
APPLICABLE, TYP.
22. GROMMET LOCATIONS SHALL BE PROVIDED/DRILLED BY GC IN FIELD, AND FINAL LOCATIONS SHALL BE
COORDINATED WITH VA.
FINISH & CASEWORK NOTES:
PAINT NOTES:
1. STANDARD WALL FINISH SHALL BE SATIN OR EGGSHEL SHEEN.
2. ALL METAL TRIM ITEMS TO BE PAINTED (E.G. DOOR FRAMES, LOUVERS, ETC.) SHALL RECEIVE SEMI-GLOSS
SHEEN AND SHALL MATCH THE COLOR OF THE WALL IN WHICH THEY ARE INSTALLED.
3. CEILING SHALL RECEIVE FLAT PAINT FINISH. SEE FINISH SCHEDULE.
BASE MAT'L., SEE INT.
ELEVATIONS & FINISH
PLAN
PLAM-FACED DRAWER WITH
FULL EXTENSION GUIDES
AND WIRE PULL
PLAM-FACED ADJUSTABLE
SHELVES ON 1/4" HEAVY
DUTY STAINLESS STEEL PINS
QUARTZ BACKSPLASH W/ 1/4"
RAD. BULLNOSE, FINISH TO
MATCH COUNTERTOP
2'
1' - 0 3/4"
1'
0"
CLEAR SEALANT, TYP.
2'
0"
4"
3"
2' - 1"
4" 1 1/
2" 6"
PLAM-FACED UPPER WALL
CABINETS W/ADJUSTABLE
SHELVING, TYP. REFER TO
FINISH PLANS/SCHEDULE FOR
PLAM SPECS.
PAINTED GYP. BD. SOFFIT
OVER 3-5/8" MTL. STUD
FRAMING - SEE CLG. PLAN
PROVIDE 3/8" GAP @ SOFFIT
JT. W/PLAM FINISH, TYP.
CEILING
4" WIRE PULL, SATIN NICKEL
FINISH, TYP.
6" H BASE MAY OCCUR -
SEE INT. ELEVATIONS &
FINISH PLAN. ADJUST
MILLWORK BASE
ACCORDINGLYI
QUARTZ COUNTERTOP OVER
3/4" PLYWOOD SUBBASE
DRAWER
4" WIRE PULL, SATIN NICKEL
FINISH, TYP.
1/2" PLYWD. BACKER W/PLAM
FINISH, TYP.
PLAM-FACED BASE CABINETS
W/ADJUSTABLE SHELVING, TYP.
REFER TO FINISH
PLANS/SCHEDULE FOR PLAM
SPECS.
PROVIDE IN-WALL
STEEL STRAP
BLOCKING AS REQ'D.
IN STUD SPACE TO
SUPPORT ALL
CABINETS, TYP.
COORD. LOCATIONS
IN FIELD
1"
2'
1' - 0 3/4"
1'
0"
2'
0"
4"
3"
2' - 1"
4" 1 1/
2"
REFER TO SECTION
DETAIL A, THIS SHEET,
FOR TYPICAL
CABINET/MILLWORK
NOTES
SINK 6"
PLAM-FACED FIXED
PANEL - ALIGN WITH
ADJACENT
DRAWERS
1"
VERIFY W/MANUF.
SINK CUTOUT
SINK - REFER TO
PLUMB. DWGS. FOR
SPEC. COORD.
CUTOUTS IN
COUNTERTOPS
W/SINK & FAUCET
MANUF.
PASS-THRU CABINET
HEPA FILTER ENCLOSURE
COMPONENT (INTEGRAL TO
CABINET)
SPECIAL NOTE: TOP
ATTACHMENT FLANGES
FOR CABINET SHALL
OCCUR ABOVE ADJACENT
DRYWALL CEILINGS. GC
SHALL INSTALL CABINET
FIRST, AHEAD OF FINAL
GYP. CLG. INSTALLATION,
BOTH SIDES
BUFFER AREA
SIDE
OPEN WORK
AREA SIDE
18 GA. STRUCTURAL CSJ
STUD HEADER @ TOP OF
OPENING
CAULK ENTIRE PERIMETER
OF CABINET JOINT @ CLG.
W/FOOD-GRADE FUNGICIDE
SEALANT
GYP. BD. SOFFIT OVER
CABINET - SEE CLG. PLAN
TILE CEILING - SEE CLG. PLAN
3'
V E
R
IF
Y W
/M A
N U
F
4'
/4
18 GA. STRUCTURAL CSJ
STUD SILL HEADER @
BOTTOM OF OPENING
ALL STUDS FRAMING
SUPPORTING PARTITION OF
PASS-THRU CABINET SHALL BE
18 GA. STRUCTURAL CSJ
STUDS @ 16" O.C. UNIT
WEIGHS 400 LBS.
WALL PANELING - SEAL
JOINT BETWEEN WALL
PANELS & PASS THRU
CABINET
COVE BASE - SEE
ENLARGED DETAIL
LINE OF PARTITION
BEYOND
8"
3'
6"
DRAWER
4"
EQ. EQ.
INTEGRAL POURED
EPOXY COVE BASE -
PROVIDE 1/8"
PLYWD. BACKER
OVER WOOD
BLOCKING - SEE
ENLARGED BASE
DETAIL
QUARTZ BACKSPLASH
W/ 1/4" RAD.
BULLNOSE, FINISH TO
MATCH COUNTERTOP
CLEAR SEALANT, TYP.
QUARTZ
COUNTERTOP OVER
3/4" PLYWOOD
SUBBASE
REFER TO SECTION
DETAIL A, THIS SHEET,
FOR TYPICAL
CABINET/MILLWORK
NOTES
D
AS-3.1
PTD. GYP. BD. CEILING
CAULK ENTIRE PERIMETER
OF CABINET JOINT @ CLG.
W/FOOD-GRADE FUNGICIDE
SEALANT
NOTE: CEILING HEIGHT IS HIGHER IN
STERILE HD BUFFER AREA BC305.
PROVIDE WP-2 PANELING ABOVE PASS-
THRU AT THIS LOCATION
C
AS-3.1
PASS THRU CABINET
LINE OF PARTITION BELOW
AND ABOVE
ALL STUDS FRAMING
SUPPORTING PARTITION OF
PASS-THRU CABINET SHALL
BE 18 GA. STRUCTURAL CSJ
STUDS @ 16" O.C.
DOUBLE 18 GA.
STUDS @ JAMB
SEAL ENTIRE
PERIMETER OF
CABINET WHERE
ASSEMBLY MEETS
WALL PANELING,
TYP.
STAINLESS STEEL WINDOW
FRAME ASSEMBLY
8"
V E
R
IF
Y W
/M A
N U
F
2'
2"
2" 1'
BUFFER AREA
SIDE
OPEN WORK
AREA SIDE
SS-1
PT-6
PT-6
RB-3
E
AS-3.1
Sim
2'
PT-4
QB-1
EX. TO REMAIN
EX. TO REMAIN
ALIGN REVEALS, TYP. MATCH
EXISTING REVEAL PROFILE TO
EXISTING FOR NEW WALL
DRAWER
DRAWER
3'
1'
4" 1'
6"
3"
DRAWER
1/
2"
1"
2' - 7"
4"
DRAWER
DRAWER
DRAWER
1' - 1"1' - 6"
1'
1'
1'
1' - 0" TYP.
T Y
P
1/
2"
2' - 1"
3'
3'
6"
BASE MAT'L., SEE INT.
ELEVATIONS & FINISH
PLAN
PLAM-FACED
DRAWERS WITH FULL
EXTENSION GUIDES
AND WIRE PULL
QUARTZ BACKSPLASH W/ 1/4"
RAD. BULLNOSE, FINISH TO
MATCH COUNTERTOP
CLEAR SEALANT, TYP.
QUARTZ COUNTERTOP
OVER 3/4" PLYWOOD
SUBBASE
4" WIRE PULL, SATIN
NICKEL FINISH, TYP.
1/2" PLYWD. BACKER
W/PLAM FINISH, TYP.
PLAM-FACED ADJUSTABLE
SHELVING W/MIN. TWO (2)
ADJUSTABLE METAL STANDARD
BRACKETS PER SHELF
1" THICK PLAM-FACED END
PANEL BEYOND
1" THICK PLAM-
FACED END PANEL
BEYOND
3'
G Y
P . B
D
3'
P
LA
M P
A N
E L
5"
5/8" PLAM-FACED REAR
PANEL TO BE PROVIDED AT
ALL EXPOSED SURFACES
OF WORKSTATION
ASSEMBLY
3-5/8" MTL. STUDS @ 16"
O.C.
5/8" GYP. BD. REAR PANEL
TO BE PROVIDED AT ALL
CONCEALED SURFACES OF
WORKSTATION ASSEMBLY
PROVIDE PLAM PANEL @
TOP OF ASSEMBLY, TYP.
SEE NOTES & DIMS.
ON OTHER SIDE OF
DRAWING
TCGRX EQUIPMENT
SHOWN DASHED - FOR
REFERENCE ONLY
ALL PLAM ON
SECTIONS F & G
SHALL BE PL-3.
ALL QUARTZ
SURFACES SHALL
BE SQ-3.
1" THICK PLAM-
FACED END
PANEL BEYOND
1" THICK PLAM-
FACED END
PANEL BEYOND
3'
8" P
LA
M
4"
5"
1' - 1"
3'
4"
3"
2' - 7" 2' - 1"
4" 2"
P
LA
M
1/
2" 2'
-0
7"
PRINTER (BY VA)
BASE MAT'L., SEE
INT. ELEVATIONS &
FINISH PLAN
QUARTZ BACKSPLASH W/ 1/4"
RAD. BULLNOSE, FINISH TO
MATCH COUNTERTOP
CLEAR SEALANT, TYP.
QUARTZ
COUNTERTOP
OVER 3/4"
PLYWOOD
SUBBASE
1/2" PLYWD. BACKER
W/PLAM FINISH, TYP.
1" THICK PLAM-FACED
END PANEL BEYOND
PLAM FINISH @
INTERIOR FACES OF
PRINTER SHELF, TYP.
DRAWER
CASEWORK
BEYOND
1"
PLAM PANEL
5" X 5" SQ. PLAM-
CLAD POWER
POWER BEYOND
PROVIDE PLAM
PANEL @ TOP OF
WALL
HEAVY DUTY 20" X 20"
PAINTED METAL
COUNTER BRACKET.
BASIS OF DESIGN:
FEDERAL BRACKET #
PLAM FINISH
ENTIRE HEIGHT ON
TCGRX DESK SIDE
1" THICK PLAM-
FACED END PANEL
BEYOND
2'
1/
2"
QUARTZ
COUNTERTOP OVER
3/4" PLYWOOD
SUBBASE
BASE MAT'L.
TCGRX
DESK SIDE
5/8" GYP. BD.
BEHIND PRINTER
SHELF UNIT
PLAM FINISH TO BE
PROVIDED AT ALL EXPOSED
SURFACES OF
WORKSTATION ASSEMBLY
3-5/8" MTL. STUDS @ 16"
O.C.
2'
2' - 1"
4" 1 1/
2"
SINK 6"
SEE SECTION B,
THIS SHEET, FOR
TYP. SINK BASE
CABINET DETAIL
1"
1' - 0"1' - 0 3/4"
R 8"
1'
10"
1'
0"
SEE SECTION A,
THIS SHEET, FOR
TYP. UPPER
CABINET DETAIL
1/4" THICK PLEXI-
GLASS DIVIDER
PANEL W/RADIUSED
FRONT EDGE
STAINLESS STEEL L-
BRACKET, BOTH
SIDES OF DIVIDER
PANEL, SECURED @
8" O.C. VERTICALLY.
PROVIDE TWO (2)
SCREWS @ TOP LEG
AS SHOWN
CLEAR
SEALANT
SCRIBE PANEL AROUND
BACKSPLASH AS TIGHT
AS POSSIBLE, PROVIDE
CLEAR SEALANT
PROVIDE 3/4" H STAINLESS
STEEL CHANNEL @ BASE
OF PLEXI-GLASS PANEL
FOR FULL DEPTH OF
PANEL, SECURE TO
COUNTERTOP
2'
1/
2"
2' - 7"
4"
3'
3'
QUARTZ COUNTERTOP OVER
3/4" PLYWD. SUBBASE (NOTE:
SOLID SURFACE MATERIAL
MAY OCCUR, SEE FINISH
PLAN/SCHEDULE - DETAILS
SIMILAR)
QUARTZ BACK &
SIDESPLASHES (NOTE: SOLID
SURFACE MATERIAL MAY
OCCUR, SEE FINISH
PLAN/SCHEDULE - DETAILS
SIMILAR)
STAINLESS STEEL FRAMED
WINDOW ASSEMBLY W/ 1/4"
GLAZING
HEAVY DUTY 20" X 20"
PAINTED METAL COUNTER
BRACKET. BASIS OF
DESIGN: FEDERAL
BRACKET #390
COVE BASE, SEE FINISH
PLAN/SCHEDULE
PAINTED GYP. BD. FINISH
SEAL WINDOW
PERIMETER WITH FOOD
GRADE FUNGICIDE
SEALANT
BUFFER AREA
SIDE
OPEN WORK
AREA SIDE
PROVIDE IN-WALL STEEL
STRAP BLOCKING AS
REQ'D. IN STUD SPACE TO
SUPPORT ALL COUNTERS,
TYP. COORD. LOCATIONS
IN FIELD
WALL PANELING, SEE
ELEVATIONS
INTEGRAL EPOXY BASE,
SEE COVE BASE
DETAILS
WALL PANELING, SEE
ELEVATIONS
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project Number
Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch es o n e fo o t th re e in ch es o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
FULLY SPRINKLERED
ARCHITECT:CONSULTANTS:
Office of Construction and Facilities Management
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
E T
G
DE
I
RE
T
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
A
TE
I
T C
J.
O
O
FO
H
VETERANS AFFAIRS MEDICAL CENTER
RENOVATE PHARMACY TO COMPLY WITH
USP DIRECTIVES
5.30.19
INTERIOR ELEVATIONS & MILLWORK
DETAILS
AS-3.1
541-19-103
10701 EAST BLVD. CLEVELAND, OHIO
CJK DAK
INTERIOR ELEVATION
SCALE: 3/8" = 1'-0"AS-3.1
Q
MODULE J - NURSE STATION WEST
SECTION DETAIL
SCALE: 1" = 1'-0"AS-3.1
A
STAFF LOUNGE BC321 - TYP. COUNTER/BASE & UPPER CABINETS
SECTION DETAIL
SCALE: 1" = 1'-0"AS-3.1
B
STAFF LOUNGE BC321 - TYP. SINK DETAIL
SECTION DETAIL
SCALE: 1" = 1'-0"AS-3.1
C
OPEN WORK AREA BC327 - PASS-THRU WINDOW DETAIL
PLAN DETAIL
SCALE: 1" = 1'-0"AS-3.1
D
OPEN WORK BC327 - PASS THRU WINDOW
INTERIOR ELEVATION
SCALE: 3/8" = 1'-0"AS-3.1
R
PHARMACY OFFICE 2B461 - SOUTH
INTERIOR ELEVATION
SCALE: 3/8" = 1'-0"AS-3.1
P
MAINSTREET BD300A - EAST
SECTION DETAIL
SCALE: 1" = 1'-0"AS-3.1
F
FINAL CHECKING/TCGRX STATION
SECTION DETAIL
SCALE: 1" = 1'-0"AS-3.1
G
SCIRPTPRO/TCGRX STATION
SECTION DETAIL
SCALE: 1" = 1'-0"AS-3.1
H
MODULE J NURSE STATION - SINK DETAIL
Revisions Date
5 BID ISSUE SUBMISSION 5.30.19
4 100% CD's SUBMISSION 12.21.18
3 90% CD's SUBMSSION 11.16.18
2 65% CD's SUBMISSION 10.12.18
1 35% CD's 8.20.18
SECTION DETAIL
SCALE: 1" = 1'-0"AS-3.1
E
TYPICAL COUNTER/BRACKET DETAIL
DOOR SCHEDULE REMARKS:
1. KEY LOCK/CYLINDER - SPEC TO MATCH EXISTING BUILDING KEYING SYSTEM
2. TEMPERED SAFETY GLASS LITE TO BE PROVIDED IN DOOR - SEE DOOR ELEVATION
3. CLOSER - MATCH BUILDING STANDARD
4. WALL STOP
5. PRIVACY SET TO BE PROVIDED
6. CARD READER WITH SEPARATE, ADJACENT PROGRAMMABLE SCRAMBLE PAD ACCESS INTEGRATED INTO EXISTING BUILDING SYSTEM - READER SPEC: HID RP-40, 75-BIT (OR APPROVED EQUAL). DOOR SHALL BE SECURED WITH MAG-LOCK - MATCH
EXISTING DOOR HARDWARE. PROVIDE PUSH-TO-EXIT BUTTON ON OPPOSITE SIDE OF CARD READER
7. CARD READER ACCESS INTEGRATED INTO EXISTING BUILDING SYSTEM - SPEC: HID RP-40, 75-BIT (OR APPROVED EQUAL). DOOR SHALL BE SECURED WITH MAG-LOCK - MATCH EXISTING DOOR HARDWARE. PROVIDE PUSH-TO-EXIT BUTTON ON
OPPOSITE SIDE OF CARD READER
8. PUSH PAD OPERATION/AUTOMATIC DOOR OPERATOR TO BE PROVIDED. AUTOMATIC DOOR OPERATOR SHALL BE EQUIPPED WITH SAFETY DEVICES TO PREVENT DOORS FROM CLOSING ON STAFF/EQUIPMENT
9. FRAME GASKETING, AND BOTTOM SWEEP - MATCH BUILDING STANDARD
10. SMOKE PARTITION: DOOR SHALL COMPLY WITH NFPA 80 REQUIREMENTS
HM, PTD. -
SINGLE
HM, PTD. -
DOUBLE
ALUMINUM, PREFINISHED -
SLIDING CLEAN ROOM
FRAME
H.M., PTD. W/TEMP. SAFETY
GLASS SIDELITE
1' - 4"
6"
2"
2"
2"2"
2"
2"2" 2"
A
FLUSH SCWD
OR HM, SEE
SCHED.
B
ALUMINUM PUSH-PAD ACTIVATED SLIDING
CLEAN ROOM DOORS
BASIS OF DESIGN: STANLEY DURA-GLIDE
2000 SERIES CLEAN ROOM
C
HOLLOW METAL W/HALF
VISION LITE TEMP. SAFETY
GLASS
D
SOLID CORE WOOD
W/FULL VISION LITE TEMP.
SAFETY GLASS
5" 2' - 2" 5"
5" 2'
5" 2' - 2" 5"
E
SOLID CORE WOOD
W/HALF VISION LITE
TEMP. SAFETY GLASS
1'
ELEVATIONS DO NOT SHOW HARDWARE
OVERALL ROUGH OPENING DIMENSIONS INCLUDE SHIM / SEALANT JOINT (REFER TO LARGE SCALE DETAILS).
ALL DIMENSIONS ARE TO BE FIELD VERIFIED PRIOR TO SUBMITTAL OF SHOP DRAWINGS
VERTICAL GLASS SHALL COMPLY WITH LOAD REQUIREMENTS OF SECTIONS 2402.0 AND 2404.1 OBC.
SAFETY GLAZING SHALL COMPLY WITH REQUIREMENTS OF SECTIONS 2406.0 & 716.5 OBC, WHICH INCLUDES 45-
MINUTE RATED FIRE- PROTECTION RATED GLAZING.
ALL DOORS TO HAVE TEMPERED SAFETY GLASS.
PROVIDE TEMPERED SAFETY GLASS ADJACENT TO DOORS.
SEE ELECTRICAL DRAWINGS FOR SECURITY DEVICE SCOPE MATRIX (MAG LOCKS, CARD READERS, ETC.)
GLASS AND GLAZING NOTES:
BASE AS SCHEDULED, (TYP.)
MOISTURE RESISTANT "BLUE
BOARD" @ WET LOCATIONS.
DEFLECTION TRACK SYSTEM (TYP).
ACOUSTIC SEALANT @ UNDERSIDE OF
DECK, BOTH SIDES AND AROUND ALL
PENETRATIONS (TYP.)
FIN. FLOOR
FRAME AROUND ALL
STRUCTURAL STEEL AND
OTHER ITEMS. MAINTAIN
CONTINUITY OF
INSULATION
4 7/8"
3 5/8"
4 7/8"
4 7/8"
MINIMUM CHASE
12" CLEAR
CAULK TIGHT TO
UNDERSIDE OF
DECK,TYP. BOTH SIDES
EXTEND METAL STUDS TO
UNDERSIDE OF DECK ABOVE
SLIP TRACK AT
STRUCTURE, ABOVE
CEILING TYPE VARIES.
SEE REF. CEILING PLANS
5/8" GYP. BD. BOTH
SIDES
3 5/8" METAL STUDS @
16" O.C.
SEE FINISH SCHEDULE
FOR BASE AND FLOOR
MATERIAL
1B
UNDERSIDE OF
DECK
BASE AS
SCHEDULED,
(TYP.)
6 3/16"
2A
DEFLECTION TRACK
SYSTEM (TYP).
TWO (2) LAYERS 5/8" GYP. BD.
ONE (1) LAYER
5/8" GYP. BD.
HEAVY DASHED LINE INDICATES
3/4" EXPANDED METAL MESH @
ALL SECURED PERIMETER
WALLS
1A
6"
PUBLIC SIDE PUBLIC SIDE
RECESSED QUARTZ
BASE, BOTH SIDES
EXTEND STUD
FRAMING TO
UNDERSIDE OF
DECK ABOVE
ROOM SIDE SHAFT SIDE
CEILING TYPE VARIES.
SEE REF. CEILING PLANS
FIRE CAULK CAULK TIGHT
TO UNDERSIDE OF
DECK,TYP. BOTH SIDES
EXTEND METAL STUDS TO
UNDERSIDE OF DECK ABOVE
TWO (2) LAYERS 5/8"
GYP. BD.
2-1/2" C-H METAL
STUDS @ 16" O.C. W/1"
SOUND BATT INSUL.
SEE FINISH SCHEDULE
FOR BASE AND FLOOR
MATERIAL
1" GYPSUM LINER
PANEL
TYPE 2TYPE 2A
PUBLIC SIDE
ROOM SIDE
UNDERSIDE OF EX.
GYP. CEILING
TWO (2) LAYERS 5/8"
GYP. BD.
RECESSED QUARTZ
BASE
NEW CLG. TILE
EX. CLG. TILE
GRAY HATCHING
INDICATES EX. GYP. BD.
SOFFIT TO REMAIN,
SEE CLG. PLAN
EXTEND OUTER
LAYER OF GYP.
BD. JUST ABOVE
EX. CLG.
EXTEND INNER LAYER OF
GYP. BD. TO DECK, BOTH
SIDES OF WALL
FIRE CAULK @ TOP, BOTH
SIDES
HEAVY DASHED LINE
INDICATES 3/4"
EXPANDED METAL
MESH @ ALL
SECURED
PERIMETER WALLS
BASE AS SCHEDULED, (TYP.)
DEFLECTION TRACK SYSTEM (TYP).
ACOUSTIC SEALANT @ UNDERSIDE
OF DECK, BOTH SIDES TYPE 5 (ONE
SIDE TYPE 5A) AND AROUND ALL
PENETRATIONS (TYP.)
FRAME AROUND ALL
STRUCTURAL STEEL AND
OTHER ITEMS. MAINTAIN
CONTINUITY OF
INSULATION
7 1/4"
6 5/8"
FIN. FLOOR
4 7/8"
UNDERSIDE OF
DECK
EXTEND ALL TEMPORARY
PARTITIONS TO
UNDERSIDE OF EXISTING
STRUCTURAL SLAB/DECK
ABOVE AND AROUND ALL
STRUCTURAL AND UTILITY
PENETRATIONS. SEAL
AROUND ALL
PENETRATIONS AND @
TOP OF WALL, BOTH
SIDES
TYPICAL TEMPORARY "SOLID
BARRIER" CONSTRUCTION
PARTITION
PATCH ALL EXISTING
CEILINGS UPON
REMOVAL OF
TEMPORARY PARTITION,
TYP.
CONSTRUCTION
SIDE
HOSPITAL/PATIENT
SIDE
PROVIDE A LEVEL 4 FINISH,
PAINT THE WALL TO MATCH
ADJACENT PAINT AND
PROVIDE RUBBER BASE
ENSURE TIGHT SEAL @
BOTTOM OF WALL
ONE (1) LAYER 5/8"
TYPE X GYP. BD.
ON BOTH SIDES
OF 3-5/8" MTL.
STUDS @ 16" O.C.
3" SOUND BATT
INSULATION SHALL BE
PROVIDED IN
INPATIENT PHARMACY
CONSTRUCTION
AREAS ONLY
EXTEND ALL TEMPORARY
PARTITIONS TO UNDERSIDE OF
EXISTING STRUCTURAL SLAB/DECK
ABOVE AND AROUND ALL
STRUCTURAL AND UTILITY
PENETRATIONS. SEAL AROUND ALL
PENETRATIONS AND @ TOP OF WALL
TYPICAL TEMPORARY
"PLASTIC BARRIER"
CONSTRUCTION PARTITION
PATCH ALL
EXISTING
CEILINGS UPON
REMOVAL OF
TEMPORARY
PARTITION, TYP.
CONSTRUCTION
SIDE
HOSPITAL/PATIENT
SIDE
CORRUGATED PLASTIC
SHEETING - 4 X 8
SHEETS, FULLY
SEALED/TAPED @ ALL
SEAMS, ON 3-5/8" MTL.
STUDS @ 16" O.C.
CORRUGATED
PLASTIC SHEETING
SPEC: GLOBAL
PLASTIC SHEETING -
GPS ULTRA CORE
CORRUGATED
PLASTIC FR SHEETS -
OR APPROVED EQUAL
SEAL @ BASE,
TYP.
METAL STUD
HEADER
5/8" GWB - NOTE: DOUBLE
LAYER MAY OCCUR - SEE
WALL TYPES
STANDARD WELDED
HM FRAME FOR
DRYWALL
CAULK ALL AROUND
BOTH SIDES
H-1
D O O R S E E
S C H E D
J-1
DOOR SEE SCHED.
DOOR PANEL
DOUBLE MTL STUDS
BACK TO BACK
HM FRAME. 3 MTL
ANCHORS PER JAMB
STUD WIDTH
FRAMES IN METAL STUD
PARTITIONS
5/8" GWB - NOTE:
DOUBLE LAYER
MAY OCCUR - SEE
WALL TYPES
CAULK ALL AROUND
BOTH SIDES
WIDTH + 1/8" MIN.
THROAT OPG. = PARTITION
1/2" RET.1/2" RET.
2" F R
5/ 8" S T O P
VARIES VARIES
1 15/16" (DOOR SIDE)
ADD RETURN ON FRAME
WHERE DRYWALL
FINISH IS REQUIRED
FRAMES IN METAL STUD
PARTITIONS
STANDARD DOOR FRAME
H-2
J-2
WALL PANELING (WP-2)
METAL STUD
HEADER
CAULK ALL AROUND
FRAME PERIMETER WITH
FOOD GRADE FUNGICIDE
SEALANT, BOTH SIDES
ALUM. SLIDING DOOR
HEADER ASSEMBLY
WALL PANELING
(WP-2)
DOUBLE STUDS,
TYP.
CAULK ALL AROUND
FRAME PERIMETER WITH
FOOD GRADE FUNGICIDE
SEALANT, BOTH SIDES
ALUM. SLIDING DOOR
JAMB ASSEMBLY
CORNER CAP TRIM
BY WALL PANEL
SUPPLIER
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project Number
Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch es o n e fo o t th re e in ch es o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
FULLY SPRINKLERED
ARCHITECT:CONSULTANTS:
Office of Construction and Facilities Management
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
E T
G
DE
I
RE
T
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
A
TE
I
T C
J.
O
O
FO
H
VETERANS AFFAIRS MEDICAL CENTER
RENOVATE PHARMACY TO COMPLY WITH
USP DIRECTIVES
5.30.19
DOOR SCHEDULE, WALL TYPES, &
DETAILS
AS-7.0
541-19-103
10701 EAST BLVD. CLEVELAND, OHIO
CJK DAK
DOOR SCHEDULE
DOOR # FROM TO W H T MATERIAL FINISH TYPE
FRAME
MATERIAL
FRAME
TYPE HEAD JAMB
FIRE
RATING
HARDWARE
SET COMMENTS
2B461 Corridor Pharmacy Office 3' - 0" 7' - 0" 1 3/4" SCWD STD A HM 1 H-1 J-1 - NOTE #1, #3, #4, #6
BAC301A Storage HD Storage Room 3' - 0" 7' - 0" 1 3/4" SCWD STD A HM 1 H-1 J-1 -
BC301 Corridor Storage 6' - 0" 7' - 0" 1 3/4" SCWD STD A HM 2 H-1 J-1 - NOTE #1, #3, #4, #7, #8, #9, #10
BC304 Receiving Area Corridor 6' - 0" 7' - 0" 1 3/4" SCWD STD A HM 2 H-1 J-1 - NOTE #1, #3, #4, #7, #8, #9, #10
BC305 Sterile HD Buffer Area HD Garbing 6' - 0" 7' - 0" 1 3/4" ALUM/GL PREFIN. B ALUM. 3 H-2 J-2 - NOTE #8
BC306 Inpatient Pharmacy Office 3' - 0" 7' - 0" 1 3/4" SCWD STD A HM 4 H-1 J-1 - NOTE #1, #4
BC309A Receiving Area HD Storage 6' - 0" 7' - 0" 1 3/4" SCWD STD A HM 2 H-1 J-1 - NOTE #1, #3, #4, #7, #8, #9, #10
BC309B HD Storage Inpatient Pharmacy 3' - 0" 7' - 0" 1 3/4" SCWD STD A HM 1 H-1 J-1 - NOTE #1, #3, #7, #8, #9, #10
BC321 Staff Lounge Open Office 3' - 0" 7' - 0" 1 3/4" SCWD STD E HM 1 H-1 J-1 NOTE #1, #3, #4
BC322A Open Office Inpatient Pharmacy 3' - 0" 7' - 0" 1 3/4" SCWD STD A HM 1 H-1 J-1 - NOTE #1, #3, #6
BC323 Open Office Staff Toilet 3' - 0" 7' - 0" 1 3/4" SCWD STD A HM 1 H-1 J-1 - NOTE #1, #3, #4, #5
BC324 Non-HD Garbing Sterile Non-HD Buffer Area 6' - 0" 7' - 0" 1 3/4" ALUM/GL PREFIN. B ALUM. 3 H-2 J-2 - NOTE #8
BC326 Non-HD Anteroom Open Work Area 3' - 0" 7' - 0" 1 3/4" HM PTD C HM 4 H-1 J-1 - NOTE #1, #2, #3, #4, #8, #9
BC327 Inpatient Pharmacy Open Work Area 3' - 0" 7' - 0" 1 3/4" SCWD/GL STD D HM 4 H-1 J-1 - NOTE #1, #2, #3, #4, #7
BC328 Open Work Area HD Anteroom 3' - 0" 7' - 0" 1 3/4" HM PTD C HM 4 H-1 J-1 - NOTE #1, #2, #3, #4, #8, #9
BD300A Receiving Area Mainstreet 6' - 0" 7' - 0" 1 3/4" SCWD STD A HM 2 H-1 J-1 45 MIN. NOTE #1, #3, #4, #6, #8, #9
NOTE #1, #3, #4, #7, #8, #9, #10
SCALE: 1/4" = 1'-0"
DOOR FRAME TYPES
SCALE: 1/4" = 1'-0"
DOOR TYPES
SCALE: 1" = 1'-0"
WALL TYPES
TYPE 1 - INTERIOR PARTITION 20 GA. 3 5/8" MTL. STUDS
TYPE
FIRE
RATING CONSTRUCTION UL DES STC RATING
1 N/A ONE (1) LAYER OF 5/8" GYP. BD. ON EACH SIDE OF 3-5/8" METAL STUDS @
16"O.C. PROVIDE 3" SOUND BATT INSULATION IN STUD CAVITY
1B ONE (1) LAYER OF 5/8" GYP. BD. ON EACH SIDE OF 3-5/8" METAL STUD @
16"O.C. NO BATT INSULATION
1C ONE (1) LAYER OF 5/8" GYP. BD. ON ONE SIDE OF 3-5/8" METAL STUDS @
16" O.C. NO SOUND BATT INSULATION
1D SECURED PERIMETER/SMOKE PARTITION: ONE (1) LAYER OF 5/8" GYP. BD.
ON ONE SIDE OF 3-5/8" METAL STUDS @ 16" O.C. GYP. BD. SHALL EXTEND
TO UNDERSIDE OF DECK ABOVE, SEALED AT TOP. ALL NEW/EXISTING
UTILITY/MEP THROUGH-PENETRATIONS SHALL BE FULLY SEALED AROUND
THE ANNULAR SPACE. PROVIDE 3/4" EXPANDED METAL MESH ON ONE (1)
SIDE OF STUDS, FULL HEIGHT BEHIND DRYWALL FROM FLOOR TO DECK.
3" SOUND BATT INSULATION
1E SMOKE PARTITION: ONE (1) LAYER OF 5/8" GYP. BD. ON EACH SIDE OF
3-5/8" METAL STUDS @ 16"O.C. GYP. BD. SHALL EXTEND TO UNDERSIDE
OF DECK ABOVE, SEALED AT TOP. ALL NEW/EXISTING UTILITY/MEP
THROUGH-PENETRATIONS SHALL BE FULLY SEALED AROUND THE
ANNULAR SPACE. PROVIDE 3" SOUND BATT INSULATION IN STUD CAVITY
TYPE 2 - INTERIOR PARTITION 20 GA. 3 5/8" MTL. STUDS
TYPE
FIRE
RATING CONSTRUCTION UL DES STC RATING
2 TWO (2) LAYERS OF 5/8" GYP. BD. ON EACH SIDE OF 3-5/8"
METAL STUD @ 16"O.C. NO SOUND BATT INSULATION
2A 1 HR SECURED PERIMETER/ FIRE SMOKE BARRIER: TWO (2)
LAYERS OF 5/8" GYP. BD. ON PUBLIC SIDE, ONE (1) LAYER OF
5/8" GYP. BD. ON ROOM SIDE OF 3-5/8" METAL STUD @ 16"O.C.
PROVIDE 3/4" EXPANDED METAL MESH ON ONE SIDE OF
STUDS FULL HEIGHT FROM FLOOR TO DECK. PROVIDE 3"
SOUND BATT INSULATION IN STUD CAVITY
U473
TYPE 3 - INTERIOR CHASE WALL PARTITION 20 GA. 3 5/8" MTL. STUDS
TYPE
FIRE
RATING CONSTRUCTION UL DES STC RATING
3 TWO (2) SETS OF 3-5/8" METAL STUDS @ 16" O.C. W/ ONE (1)
LAYER OF 5/8" GYP. BD. ON ROOM SIDES OF WALL. VERIFY
REQUIRED CHASE DEPTH WITH TOILET CARRIER. PROVIDE
3" SOUND BATT IN BOTH STUD CAVITIES
TYPE 4 - INTERIOR SHAFT WALL PARTITION 20 GA. MTL. STUDS
TYPE
FIRE
RATING CONSTRUCTION UL DES STC RATING
4 2 HR TWO (2) LAYERS OF 5/8" GYP. BD. ON ONE SIDE OF 2-1/2" C-H
STUDS @ 16" O.C. W/1" GYPSUM LINER PANELS INSTALLED
ON SHAFT SIDE. PROVIDE 1" SOUND BATT INSULATION
U415, SYSTEM B
TYPE 5 - INTERIOR PARTITION 20 GA. 6" MTL. STUDS
TYPE
FIRE
RATING CONSTRUCTION UL DES STC RATING
5 N/A ONE (1) LAYER OF 5/8" GYP. BD. ON EACH SIDE OF 6" METAL
STUDS @ 16"O.C. PROVIDE 3" SOUND BATT INSULATION IN
STUD CAVITY
4A
Revisions Date
5 BID ISSUE SUBMISSION 5.30.19
4 100% CD's SUBMISSION 12.21.18
3 90% CD's SUBMSSION 11.16.18
2 65% CD's SUBMISSION 10.12.18
1 35% CD's 8.20.18
Printer Station
UP
UP
Tech Supv
BC311
IP Chief BC312 Alcove
BC313
Staff Entry
BC314
ELEC.
BC315
Assistant Chief
BC316
Secretary & Waiting
BC317
Chief Pharm.
BC318
Admin. Assist.
BC319
Clinic Coord.
BC320
IT
BB379
Open Office
BC322
Mainstreet Corridor
BC402
Closet BB375A Laminating
Paster Room
BB376
Conference
BB261
Corridor
BB260
Reception
BB262
Office
BB262A
Student Office
Inpatient Pharmacy
BC307
Corridor
BC307A
Narcotics Vault
BC310
EMS
BC302
Future Machine Room
BC303
Receiving Area
BC304
Storage
BC301
Mainstreet
BD300A
Lobby
BD300B
Lobby
BD300C
Mechanical
BC310A
BC403
Sterile HD Buffer Area
BC305
HD Garbing
BC308
Open Work Area
BC327
Non-HD Garbing
BC325
Sterile Non-HD Buffer Area
BC324
Staff Lounge
BC321
HD Storage
BC309
Office
BC306
HD Anteroom
BC328
Non-HD Anteroom
BC326
Staff Toilet
BC323
FURNITURE PHASE A
FURNITURE PHASE B
F U
R N
IT
U
R E
P H
A S
E A
F U
R N
IT
U
R E
P H
A S
E B
6'-4" 2"
2"
6'-4"
FINISH PLAN - INPATIENT
PHARMACY
Revisions: Date
35% CD'S SUBMISSION
AS-7.1
6.20.18
65% CD'S SUBMISSION 10.12.18
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT:
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
VETERANS AFFAIRS MEDICAL CENTER
RENOVATE PHARMACY TO COMPLY
WITH USP DIRECTIVES
10701 EAST BLVD. CLEVELAND, OHIO
541-19-103
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY. UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE. CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREESTBORO RD. RICHFIELD, OH 44286
P. 330.659.6688
5.30.19 CJK DAK
1/4" = 1'-0"
INTERIOR FINISH PLAN
INPATIENT PHARMACY
NORTH
ALL WALLS U.N.O.
PROVIDE 2" WIDE
CONTRASTING COLOR EPX
FLOORING W/INTEGRAL BASE
@ HATCHED DEMARCATION
LINE LOCATION. FINAL
COLOR TBD
PL-1
EPX-1
PT-1A
SQ-2
SQ-2
SQ-2
PL-1
CG-1
CG-1
PT-1
PT-3
PT-2
PT-2
LVT-1 RB-1
BASE BID
BASE BID - PHASE IV
DEDUCT ALT. #2
RB-1
LVT-1 RB-1
BASE BID
BASE BID - PHASE IV
DEDUCT ALT. #2
PT-1
WP-1
BELOW
RB-1
EPX-1
WP-2 FULL HT. ALL
WALLS
FLOOR + 6"
INTEGRAL BASE
EPX-1
WP-2 FULL HT. ALL
WALLS
FLOOR + 6"
INTEGRAL BASE
EPX-1
WP-2FULL HT. ALL
WALLS
FLOOR + 6"
INTEGRAL BASE
CG-1
PT-3
PT-1
PT-3
PCT-1
PCTW-1
PCTW-2
PT-1 ABOVE
LVT-1
RB-1
PT-2 ALL WALLS
PT-2
WP-1
BELOW
CG-1
LVT-1
RB-1
PT-2
PT-1
RB-1
RB-1
PT-1
WP-1 BELOW
CG-1
CG-1
PT-1
WP-1
BELOW
CG-2
CG-2
PT-2
WP-1 BELOW
CG-1
PT-1
WP-1 BELOW
PT-2
L
V
T
R
B
B
A
S
B
I
D
B
A
D
P
H
A
V
D
E
D
U
C
T
A
L
CG-2
PT-3
RB-1
PT-3
RB-1
WP-1
SV-1
PT-1 ABOVE
FLOOR + 4"
INTEGRAL BASE
WP-1 BELOW
CG-1
EPX-1
PT-1 ABOVE
FLOOR + 6"
INTEGRAL BASE
WP-1 BELOW
CG-2
CG-1
EPX-1 FLOOR + 6"
INTEGRAL BASE
(INFILL ONLY,
MAKE FLUSH
W/EXISTING)
CG-3
(2 - REINSTALL
EXISTING)
TERZ-1
PT-4
QB-1
CG-3
CG-3
(2)
PT-4
QB-1
PT-4
QB-1
QB-1
PT-4
RB-2
RB-2
PT-1
RB-2
RB-2
CPT-1
ALIGN WITH PHASE IA WALL
REMOVAL LOCATION - SEE
PHASE IA PLAN
ALIGN WITH PHASE II CONST.
WALL REMOVAL LOCATION -
SEE PHASE II PLAN
PT-1
RB-2
CG-1
PT-3
RB-2
PT-1
RB-2
FLOOR + 6"
INTEGRAL BASE
SQ-1
PL-1
CABS.
TYPICAL
QUARTER
TURN LVT-1
FLOORING
INSTALLATION
- TYP. ALL
SPACES
WHERE LVT-1
IS IDENTIFIED
90% CD'S SUBMISSION 11.16.18
CPT-1
FILLER PANEL TRIM TO BE
PROVIDED BY LOCKER
SUPPLIER, TYP.
FILLER PANEL TRIM TO BE
PROVIDED BY LOCKER
SUPPLIER, TYP.
REINSTALL
REMOVED
HANDRAIL UPON
PHASE II
CONSTRUCTION
COMPLETION
PT-4
PCTB-1
PT-9 GYP. BD. CEILING
PT-9
GYP. BD.
CEILING
PT-9
GYP. BD.
CEILING
PT-9
GYP. BD.
CEILING
CG-1
FINAL WORKSTATION PLAN SHOWN FOR
REFERENCE. ALL WORKSTATIONS
SHALL BE FURNISHED & INSTALLED BY
VA IN PHASES. VA/GC SHALL
COORDINATE FURNITURE
INSTALLATION SCHEDULING
SQ-3
SQ-3
PL-3
PL-3
PL-3
100% CD'S SUBMISSION 12.21.18
SQ-3
RB-1
SHALL BE PROVIDED
AROUND ENTIRE
PERIMETER OF
TCGRX / FINAL
CHECKING /
SCRIPTPRO
MILLWORK STATION
CG-1
BID ISSUE SUBMISSION 5.30.19
BC308 & BC328
EPX-1
WP-2 FULL HT. ALL
WALLS
FLOOR + 6"
INTEGRAL BASE
BC325 & BC326
SQ-2
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COPIER
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Printer Station
UP
UP
Tech Supv
BC311
IP Chief BC312 Alcove
BC313
Staff Entry
BC314
ELEC.
BC315
Assistant Chief
BC316
Secretary & Waiting
BC317
Chief Pharm.
BC318
Admin. Assist.
BC319
Clinic Coord.
BC320
IT
BB379
Open Office
BC322
Mainstreet Corridor
BC402
Closet BB375A Laminating
Paster Room
BB376
Conference
BB261
Corridor
BB260
Reception
BB262
Office
BB262A
Student Office
Inpatient Pharmacy
BC307
Corridor
BC307A
Narcotics Vault
BC310
EMS
BC302
Future Machine Room
BC303
Receiving Area
BC304
Storage
BC301
Mainstreet
BD300A
Lobby
BD300B
Lobby
BD300C
Mechanical
BC310A
BC403
Sterile HD Buffer Area
BC305
HD Garbing
BC308
Open Work Area
BC327
Non-HD Garbing
BC325
Sterile Non-HD Buffer Area
BC324
Staff Lounge
BC321
HD Storage
BC309
Office
BC306
HD Anteroom
BC328
Non-HD Anteroom
BC326
Staff Toilet
BC323
FURNITURE PHASE A
FURNITURE PHASE B
F U
R N
IT
U
R E
P H
A S
E A
F U
R N
IT
U
R E
P H
A S
E B
FINISH PLAN - PHASE IV -
INPATIENT PHARMACY
Revisions: Date
35% CD'S SUBMISSION
AS-7.1.4
6.20.18
65% CD'S SUBMISSION 10.12.18
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT:
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
VETERANS AFFAIRS MEDICAL CENTER
RENOVATE PHARMACY TO COMPLY
WITH USP DIRECTIVES
10701 EAST BLVD. CLEVELAND, OHIO
541-19-103
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY. UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE. CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREESTBORO RD. RICHFIELD, OH 44286
P. 330.659.6688
5.30.19 CJK DAK
1/4" = 1'-0"
INTERIOR FINISH PLAN
INPATIENT PHARMACY - PHASE IV
NORTH
QB-1
PT-4
PT-1
RB-2
ENTIRE SPACE
PHASE IA
BASE BID
PHASE IV - BASE BID
DEDUCT ALT. #2
PHASE IA
BASE BID
PHASE IV - BASE BID
DEDUCT ALT. #2
P
H
A
I
B
A
D
P
H
A
V
D
D
E
D
U
L
NOTE: CAROUSELS EXTEND
TO FLOOR AND CANNOT BE
MOVED. EXISTING FLOORING
MATERIAL SHALL BE CUT AS
CLOSE AS POSSIBLE TO
CAROUSEL BASE PERIMETER
PHASE IV:
PHASE IV SHALL INCLUDE
REMOVAL OF EXISTING FLOOR &
BASE, INSTALLATION OF NEW
FLOOR & BASE, AND REPAINTING
OF ALL WALLS THROUGHOUT
ENTIRE HATCHED INPATIENT
PHARMACY BC307 AREA.
DEMO/IMPROVEMENT WORK
SHALL BE INCLUDED IN THE BASE
BID. GC SHALL BE PERMITTED TO
USE SEALED VISQUEEN (OR
SIMILAR) BARRIERS TO SANCTION
OFF CONSTRUCTION AREAS FROM
THE SURROUNDING, ACTIVE
PHARMACY. GC SHALL
COORDINATE REQUIRED PHASING
WITH COR/VA PHARMACY STAFF
DEDUCT ALTERNATE #2:
ELIMINATE PHASE IV IN ITS
ENTIRETY
RB-1
LVT-1
ENTIRE SPACE
PT-3
PT-1
CG-1 CG-1
CG-1
CG-1
PT-2
PT-2
COL. ENCL.
PT-3
COL. ENCL.
PT-3
COL. ENCL.
PT-3
PT-3
PT-1
PHASE IV:
PHASE IV SHALL INCLUDE
REMOVAL AND REPLACEMENT OF
EXISTING BASE AND REPAINTING
OF ALL WALLS THROUGHOUT
ENTIRE HATCHED OPEN OFFICE
BC322 AREA. EXISTING CARPET
SHALL REMAIN.
DEMO/IMPROVEMENT WORK
SHALL BE INCLUDED IN THE BASE
BID. GC SHALL BE PERMITTED TO
USE SEALED VISQUEEN (OR
SIMILAR) BARRIERS TO SANCTION
OFF CONSTRUCTION AREAS FROM
THE SURROUNDING, ACTIVE
PHARMACY. GC SHALL
COORDINATE REQUIRED PHASING
WITH COR/VA PHARMACY STAFF
DEDUCT ALTERNATE #2:
ELIMINATE PHASE IV IN ITS
ENTIRETY
90% CD'S SUBMISSION 11.16.18
100% CD'S SUBMISSION 12.21.18
BID ISSUE SUBMISSION 5.30.19
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
COPIER
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
Storage
BAC301
. Mail r
Corridor
BAC327
HAC
BAC302
HD Storage Room
BAC301A
Nurse Intake
Storage 2B435
Corridor 2B459
Recpt.
2B462
Pharmacy Office 2B461
Staff Toilet 2B460
Patient Toilet 2B438
EMS
2B436
Family/ Consult 2B437
Patient Toilet 2B439
Private Infusion
2B440
Med Room 2B456
Soiled 2B457Infusion 1
2B441
Infusion 2 2B442
Infusion 3 2B443
Infusion 4 2B444
Infusion 5 2B445
Infusion 6 2B446
Infusion 7 2B447
Infusion 8 2B448 Infusion 9
2B449
Infusion 10 2B450
Infusion 11 2B451
Nurse Station 2B455
Corridor 2B459
Corridor 2B458
Infusion 12 2B452
Infusion 13 2B453
Infusion 14 2B454
Infusion 15 2B454A
6'-2"
OUTPATIENT PHARMACY & MODULE J
FINISH PLANS & OVERALL FINISH
SCHEDULE/DETAILS
Revisions: Date
35% CD'S SUBMISSION
AS-7.2
6.20.18
65% CD'S SUBMISSION 10.12.18
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
CONSULTANTS: ARCHITECT:
Office of
Construction and Facilities
Management
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
E T
G
DE
I
RET
S
HCRA
I
KACZMAR
STANLEY
NO. 4988
T
E R
S
ATE
I
T C
J.
O
O
FO
H
VETERANS AFFAIRS MEDICAL CENTER
RENOVATE PHARMACY TO COMPLY
WITH USP DIRECTIVES
10701 EAST BLVD. CLEVELAND, OHIO
541-19-103
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY. UNIONTOWN, OH 44685
P. 330.526.2700
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE. CLEVELAND, OH 44111
P. 440.667.5120
FULLY SPRINKLERED
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREESTBORO RD. RICHFIELD, OH 44286
P. 330.659.6688
5.30.19 CJK DAK
1/4" = 1'-0"
INTERIOR FINISH PLAN
OUTPATIENT PHARMACY
NORTH
ALIGN SHEET VINYL
TRANSITION LINE WITH
EXISTING CHAIR
STATIONS
CG-1
1/4" = 1'-0"
INTERIOR FINISH PLAN
SECOND FLOOR - MODULE J
NORTH
SV-1
WP-1
PT-1
BELOW, ALL
WALLS
ABOVE, ALL
WALLS
FLOOR + 4"
INTEGRAL BASE
E
X
O
N
S
T
R
M
A
I
N
E
N
S
T
M
A
I
N
E
N
S
T
M
A
I
N
SV-1
WP-1
PT-1
BELOW, ALL
WALLS
ABOVE, ALL
WALLS
FLOOR + 4"
INTEGRAL BASE
PT-6
RB-3
PT-6
RB-3
PT-6
RB-3
ALL WALLS
PT-6
RB-3
CG-1
CG-1
PT-6
RB-3
CG-1
(2)
PL-2
CABINETS
SS-1
SS-1
SV-2
GRAIN
SV-2
G R
A I N
E X
C
O N
S T
M
A I N
EX. CONST.
TO REMAIN
SV-2
GRAIN
CG-1
3" = 1'-0"
ENLARGED COVE BASE DETAILS
EPOXY FLOORING
SYSTEM, INCLUDING
ALL GROUND, SEAL,
UNDERLAYMENT AND
TOP COATS
POURED EPOXY
FLOORING EPX-1:
TYP. DETAIL @ WALLS
RECEIVING FULL
WALL PANELING
POURED EPOXY
FLOORING EPX-1:
TYP. DETAIL @
PAINTED WALLS
" THK. PLYWOOD
BACKER BEHIND
INTEGRAL EPOXY BASE
INTEGRAL COVE
FULL-HEIGHT WALL
PANELING ABOVE
" GYP. BD.
INTEGRAL COVE
STANDARD METAL COVE
STRIP BY FLOORING
SUPPLIER, TYP.
PAINTED GYP. BD.
FINISH
E
N
S
T
M
A
I
N
LINE OF SV-2 GRAIN
PATTERN
TRANSITION
90% CD'S SUBMISSION 11.16.18
INTENT IS FOR WALL
PANELING AND FACE OF
COVE BASE TO BE
FLUSH WITHOUT ANY LIP
AREA. BUILD UP
THICKNESS OF EPOXY
AS REQUIRED TO
ACHIEVE SAME
SHEET VINYL FLOORING SV-1:
TYP. DETAIL @ WALLS
RECEIVING WALL PANELING
SHEET VINYL FLOORING
INTEGRAL COVE
COVE FORMER BY
FLOORING SUPPLIER
STANDARD METAL COVE
STRIP BY FLOORING
SUPPLIER, TYP.
CLEAR SEALANT, TYP.
WALL PANELING
3" = 1'-0"
CORNER GUARD DETAIL
WALL PANELING
STAINLESS STEEL
CORNER GUARD CG-1
WALL PANELING
100% CD'S SUBMISSION 12.21.18
PT-6
RB-3
PT-6
RB-3
ALL THREE
(3) SIDES OF
WING WALL
CG-1
LVT FLOORING/EX. PLANK
FLOORING:
TYP. FLOOR TRANSITION DETAIL
PROVIDE SLIMLINE
TRANSITION STRIP @
FLOORING MATERIAL
TRANSITIONS. VERIFY
MATERIAL THICKNESSES
IN FIELD AND PROVIDE
APPROPRIATE
TRANSITION STRIP AS
REQUIRED
LVT FLOORING/POURED EPOXY
FLOORING:
TYP. FLOOR TRANSITION DETAIL
METAL
" X
" "L" STRIP
OR SIMILAR SCHLUTER
TYPE (OR APPROVED
EQUAL)
SLIGHT SLOPE AS
REQUIRED TO
TRANSITION STRIP
EPOXY FLOORINGVINYL
FLOORING
BID ISSUE SUBMISSION 5.30.19
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text D
AutoCAD SHX Text E
AutoCAD SHX Text F
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
VA FORM 08-6231
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONCRETE ANCHORS
(CRACKED AND UNCRACKED CONCRETE)
ANCHOR TYPE ADHESIVE TYPE ROD TYPE
Adhesive Hilti HIT-HY200 SafeSet System Hilti HIT-Z Rod
Mechanical - Hilti KWIK HUS-EZ SafeSet
Mechanical - Hilti KWIK Bolt-TZ SafeSet
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project Number
Drawing Number on e-ei gh th i nc h o ne f oo t on e-qu ar te r in ch o ne f oo t th re e-ei gh th s in ch o ne f oo t on e-ha lf in ch o ne f oo t th re e-qu ar te rs i nc h o ne fo ot on e in ch o ne f oo t on e an d on e-ha lf in ch es o ne f oo t th re e in ch es o ne f oo t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
ARCHITECT:CONSULTANTS:
Office of
Construction and Facilities Management
STRUCTURAL ENGINEERING:
THORSON BAKER + ASSOCIATES
3030 WEST STREETSBORO RD.
RICHFIELD, OH 44286
P. 330.659.6688
MECHANICAL/ELECTRICAL/PLUMBING ENGINEERING:
SCHEESER BUCKLEY MAYFIELD, LLC
1540 CORPORATE WOODS PKWY.
UNIONTOWN, OH 44111
P. 330.526.2700
HAZARDOUS MATERIALS ASSESSMENT:
STEPHEN J. SEBESTA & ASSOCIATES, INC.
30628 DETROIT RD., NO. 258
WESTLAKE, OH 44145
P. 216.781.0060
COST ESTIMATING:
MCGUINESS UNLIMITED, INC.
15724 STILLWOOD AVE.
CLEVELAND, OH 44111
P. 440.667.5120
1468 WEST 9TH STREET #400 CLEVELAND, OH 44113
P. 216.687.1555 F. 216.687.1558
C :\R ev it
Lo ca l F ile s\
-0
S tru ct _R
_b ow le r8
.rv t
5/
/2
1:
:5
P
M
VETERANS AFFAIRS MEDICAL CENTER
RENOVATE PHARMACY TO COMPLY WITH
USP DIRECTIVES
5.30.19
GENERAL NOTES AND SPECIFICATIONS
S-IP.0
541-19-103
10701 EAST BLVD. CLEVELAND, OHIO
TBA TBA
GENERAL NOTES
Applicable Building Code: 2015 International Building Code
1. Design live loads
A. Floor loads
1.1. Office Building
1.1.a. First floor =100 psf 1.1.b. Upper floors = 80 psf
2. Design wind loads
A. Basic interior wind pressure (3 second gust) (Ultimate) = 5 mph
3. Seismic
S = 0.180
S = 0.058
S = 0.192
S = 0.093
Seismic importance factor (le) 1.2 Risk Category III Seismic site class D Seismic design category B
Design Criteria
1. The term General Contractor (G.C.) as used in these documents refers to the Contractor / Construction Manager in responsible charge of the project in terms of coordination, scheduling, subcontractor coordination, etc. This term refers to, but is not limitd to, General Contractor, Construction Manager, Design Build Contractor, Prime Contractor, etc. The term is referencing the entity that coordinates the work of other trades.
2. The structure or its modifications are designed to be self-supporting and stable after the building or its modifications are fully completed. It is solely the contractor's responsibility to determine erection procedure and sequence and insure the safety of the construction personnel, public, building and its component parts, and adjacent buildings and properties. This includes the addition of whatever temporary or permanent shoring, bracing, needling, underpinning, or sheet piling, etc. that may be necessary to brace new construction, adjacent buildings, existing walls, and framing to remain so that the structure is braced for wind, seismic, gravity, construction loads, etc. and that no horizontal or vertical settlement or any damage occurs to the adjacent existing structures. Temporary supports shall be maintained in place until permanent supports and/or shoring and bracing are installed. Design of these supports shall be by a registered engineer registered in the state where the project is located in the employ of the contractor.
3. Fall protection support from perimeter columns shall be provided in accordance with OSHA requirements as required. Such material shall remain the contractor's property after completion of the project.
4. It is the contractors responsibility to enforce all applicable safety codes and regulations during all phases of construction.
5. The contractor shall perform all construction for the project in a manner and sequence that are based on accepted industry standards that recognize the interaction of the components that comprise the structure, without causing distress, unanticipated movements or irregular load paths as a result of the construction means and methods employed.
6. Construction loads shall not exceed design live loads. The contractor shall be responsible for all design required to support construction equipment used in constructing this project. Shoring and re-shoring is the responsibility of the contractor.
7. Principal openings through the framing are shown on these drawings. The general contractor shall examine the structural and mechanical drawings for the required openings and shall verify size and location of all openings with the mechanical contractor. Providing all openings required by the mechanical, electrical, plumbing, or other trades shall be a part of the general contract, whether or not shown in the structural drawings. Any deviation from the openings shown on the structural drawings shall be brought to the engineer's attention for review.
8. The existing conditions shown on these documents were based upon existing drawings prepared by Dalton-Dalton Associates dated 2/1/1961. The drawings illustrate the existing structure, structural elements and framing details based on either the original construction drawings and/or site observation.
Prior to initiating material procurement and construction it is the contractor's responsibility to verify existing conditions are consistent with the contract documents. This may required the removal of existing finishes and possibly selective demolition to verify the as-built condition.The contractor is responsible for field verifying all existing conditions; any discrepancies are to be immediately reported to the engineer and architect prior to proceeding with any of the work in question.
9. Contractor shall field verify slab on grade floor construction type prior to cutting. Under no circumstances shall the contractor cut a structural floor slab thicker than four (4") inches without prior written approval from Engineer of Record. Notify Engineer of Record of any slab thickness greater than four (4") inches prior to proceeding with any sawcutting.
10. All mechanical and electrical duct work, plumbing, piping, wiring, lighting and all architectural items that need to be removed during the modification of, or reinforcing of, existing structure shall be replaced in kind. The contractor shall keep all existing systems in operation during the construction phase of the project.
11. All contractors are required to examine the drawings and specifications carefully, visit the site and fully inform themselves as to all existing conditions and limitations, prior to agreeing to perform the work. Failure to visit the site and familiarize themselves with the existing conditions and limitations will in no way relieve the contractor from furnishing any materials or performing any work in accordance with drawings and specifications without additional cost to the owner.
12. Details labeled "Typical Details" on drawings apply to situations occurring on the project that are the same or similar to those specifically detailed. Such details apply whether or not details are referenced at each location. Notify engineer of clarifications regarding applicability of "Typical Details".
13. Work these drawings with architectural, mechanical, and electrical drawings.
14. Do not scale drawings.
15. Any discrepancies between structural and architectural drawings shall be brought to the attention of the architect and structural engineer.
16. Should any of the general notes conflict with any details or instructions on plans, or in the specifications, the strictest provision shall govern.
17. Shop drawings and submittals:
A. These drawings shall be checked and coordinated with other materials and contracts by the general contractor and shop drawings and submittals shall bear the contractor's review stamp with the checker's initials before being submitted to the architect for approval.
B. When the fabricator has been authorized to use the architect and engineer's drawings as erection drawings, the fabricator must remove all title blocks, professional seals and any other references to the architect and engineer from that erection drawing. The fabricator's name and title shall be placed on the erection drawings.
C. Where dimensions and elevations of existing construction could affect the new construction, it is the contractor's responsibility to make field measurements in time for their incorporation in the shop drawings.
General (Existing Structures)
7. All fill materials shall be free of organic contaminations and other deleterious matter.
8. For back fill against basement walls, retaining walls, footings, etc., place in 8" thick layers, with each lift compacted at near optimum moisture content, until a minimum in place density of 95% of the maximum density as determined by ASTM D698 is achieved.
9. All soil surrounding and under footings shall be protected from frost action and freezing during the course of construction.
10. Notify structural engineer of any unusual soil conditions.
Existing Foundation
Concrete
Minimum Cementitious Content lb./cu.yd.
Maximum Water Cement Ratio
Specified 28-day Compressive Strength psi
Specified Slump Range for Placement (with W.R.)
inches
Specified Air Content Range
% by volume
Maximum Size Aggregate inches
Concrete Types Schedule Type of Concrete
Spread Footings Piers below grade 470 0.60 3000 5 0-3
Entrapped 1 1/2
1. All concrete construction shall conform to ACI 301, "Specifications for Structural Concrete" and ACI 302, 305 and 306 unless noted otherwise for the year referenced in the applicable building code.
2. All detailing, fabrication and placing of reinforcing bars, unless otherwise noted, shall conform to ACI 318, "Building Code Requirements for Structural Concrete" ACI 117 as referenced in the applicable building code, and the latest ACI detailing manual.
3. Concrete production: General as per ACI 301, Section 4, Article 4.3, except as noted.
4. Ready-mixed Concrete: use for all work, except that when small quantities (not over 1/2 cubic yard) are needed for isolated or relatively unimportant items.
5.
Notes: A. All cement shall be Type I or Type III Portland Cement per ASTM C150.
Types IA and IP are not acceptable. Use one brand of cement throughout the project.
B. Minimum cementitious content shall consist of 100% cement or a combination of cement and flyash per Note C, or a combination of cement and ground granulated blast furnace slag (GGBFS) per Note D. Flyash shall not be used in combination with GGBFS as a substitute for cement.
C. Flyash is permitted and shall conform to ASTM C618 Type C or F, but shall not exceed 20% of cementitious content by weight indicated above on a substitution basis and shall be included in the water-to-cement ratio. If flyash is used, the mix design submittals shall have tests using the same amount of flyash. The contractor's schedule shall account for the use of flyash.
D. Ground granulated blast furnace slag (GGBFS) is permitted and shall conform to ASTM C989, but shall not exceed 15% of cementitious content by weight indicated above on a substitution basis and shall be included in the water-to-cement ratio.
If GGBFS is used, the mix design submittals shall have tests using the same amount of GGBFS. The contractor's schedule shall account for the use of
GGBFS.
E. All light weight concrete shall conform to ACI 211.2 as referenced in the applicable building code and shall meet the unit weight requirements of the specified UL classification, as specified on the architectural drawings, except where otherwise specified.
F. Concrete used for floors shall have 1800 psi, 3 day strength. Mixes to be pumped shall be so identified on the mix design submittal. All pumped mixes shall have a mid-range or high-range water reducer.
G. All admixtures other than superplasticizers shall be added at the batch plant.
Superplasticizers, designed for addition to the mix at the plant, may be added at the batch plant with verifications from the structural engineer and verifications that the water-to-cement ratio has not been exceeded. Superplasticizers added at the site shall be sent in pre-measured containers from the batch plant.
H. All concrete used for cast-in-place concrete slabs shall contain the specified water reducing or water reducing/retarding admixture.