36C25019B0022-005.pdf
PDF 8 MB Posted
- Attached to
- 4th Floor Pharmacy HVAC Construction Project no. 539-18-501 Federal contract opportunity
- Solicitation number
- 36C25019B0022
About this file
36C25019B0022 Attach 3 Drawings 4th Fl Comp Pharm 2019-1-16.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25019C0162-000.docx | DOCX document | |
| 36C25019B0022-0003003.docx | DOCX document | |
| 36C25019B0022-0002001.pdf | ||
| 36C25019B0022-0002002.pdf | ||
| 36C25019B0022-0002000.docx | DOCX document | |
| 36C25019B0022-0001000.docx | DOCX document | |
| 36C25019B0022-0001001.pdf | ||
| 36C25019B0022-0001002.pdf | ||
| 36C25019B0022-002.docx | DOCX document | |
| 36C25019B0022-003.docx | DOCX document | |
| 36C25019B0022-006.docx | DOCX document | |
| 36C25019B0022-007.docx | DOCX document | |
| 36C25019B0022-004.pdf | ||
| 36C25019B0022-001.docx | DOCX document | |
| 36C25019B0022-000.docx | DOCX document |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
N
EXTERIOR ELEVATION
INTERIOR ELEVATION
SEE 700 SERIES SHEETS
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
SEE SHEET A001
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
XXXX
X
SIM
XX
TOILET ACCESSORY TAGX SIGNAGE TAGX
Project Location
N
Ludlow Ave.
C lif to n A v e
CINCINNATI
STATE
TECH.
Hopple St.
M.L.K. Dr.
McMillan St.
UNIV. OF
CINCINNATI
W.H.T Rd.
VAMC
3200 VINE ST.
M.L.K. Dr.
V in e
St.
ZOO
Jefferson Ave.
UNIV.
HOSPITAL
Mitchell Ave.
R e ad in g
R d.
V ic to ry
P kw
y. XAVIER
UNIV.
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
JPA Project No.
Department of Veterans Affairs Medical Center
ARCHITECTURE PLANNING INTERIOR DESIGN
3131 NEWMARK DRIVE, SUITE 200
MIAMISBURG, OHIO 45342
937.461.3290 P
JOHN POE ARCHITECTS
HEAPY ENGINEERING
MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY
1400 WEST DOROTHY LANE
DAYTON, OH 45409
937.224.0861 P
937.224.5777 F
Dwg. of
4TH FLOOR COMPOUND
PHARMACY
1/14/2019
COVER SHEET
G001
CVJR
18009.00
539-18-501
Cincinnati VA
4TH FLOOR COMPOUND PHARMACY
3200 Vine St. Cincinnati, Ohio 45220 PROJECT #: 539-18-501
G001 COVER SHEET
G100 CODE DATA
A101 FLOOR PLANS
A601 DOOR SCHEDULE, WINDOW & MISCELLANEOUS DETAILS
AF101 FINISH PLANS
P001 LEGEND, INDEX & GENERAL NOTES
P104 PARTIAL FOURTH FLOOR PLAN - PLUMBING
M001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS
M104 PARTIAL FOURTH FLOOR PLAN - HVAC
M105 PARTIAL ROOF PLAN - HVAC
M501 DETAILS
M502 DETAILS
M601 SCHEDULES
M701 CONTROLS
M702 SCHEMATICS
M703 HOT WATER SYSTEM SCHEMATIC
M704 STEAM SYSTEM SCHEMATIC
E001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS
E104 PARTIAL FOURTH FLOOR PLAN - ELECTRICAL
E105 PARTIAL ROOF PLAN - ELECTRICAL
E501 DETAILS
E502 TECHNOLOGY DETAILS
E601 SCHEDULES
GENERAL CONSTRUCTION NOTES
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO
BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE
SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT
THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,
HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS
AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT
DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL
WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS SPECIFICALLY
NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS INDICATED AT SIMILAR
CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL SYSTEMS
WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE THE
OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE
NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR
SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED
WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF THE
WALL.
12. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO
AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER
RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS
RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS
IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY
FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE
CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,
INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA
PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE
ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,
TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND
DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13
WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS
TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT
EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED
WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH
ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT
ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF
NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO
REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT
SURFACES TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW
MATERIALS.
DRAWING INDEX
GRAPHIC SYMBOLS
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
N.T.S.Scale:
Building 1 - 4th Floor Key Plan
N.T.S.Scale:
Vicinity Map
Revisions Date
3 100% CD Owner Review 01-14-2019
2 DD Submittal 12-20-2018
1 SD Submittal 11-16-2018
30-HR Smoke Partition
1-HR Fire Barrier
2-HR Fire Barrier
Means of Egress
Existing Wall to Remain
New Wall
CODE LEGEND
Ante Room
B414C
Non-Hazardous Compounding
B414D
Work Station Area
B414
Hazardous Compounding
B414B
Hazardous Storage
B414A
HAC
B409
MEN
B407
WOMEN
B406
Corridor
C-4-5
Stair #4
S*4*4
Stair #3
S*4*3
Corridor
C-4-6
Corridor
C-4-1
Elevators
DN
DN
120'-6"
114'-6"
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
XX
JPA Project No.
Dwg. of
4TH FLOOR COMPOUND
PHARMACY
1/14/2019
CODE DATA
G100
CVJR
18009.00
539-18-501
Cincinnati VA
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
Chapter 39- Existing Business Occupancies:
39.1.1.1- The requirements of this chapter shall apply to existing buildings or portions thereof currently occupied as business occupancies.
39.2.2.7.- Sensor- release of electrical locking systems compling with
7.2.1.6.2 shall be permitted.
39.2.5.3- Limitations on common path of travel shall be in accordance with
39.2.5.3.1.
39.2.5.3.1.- Common path of travel shall not exceed 100 ft. on a story protected throughout by an approved automatic sprinkler system in accordance with 9.7.1.1 (1).
39.2.6- Travel distance to exits. Travel distance shall comply with 39.2.6.3 through 39.2.6.3.
39.2.6.3.- Travel distance shall not exceed 300 ft in business occupancies protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.
39.2.9.1- Emergency lighting shall be provided in accordance with Section
7.9 in any building where any one of the following conditions exists:
(1) The building is three or more stories in height.
(2) The occupancy is subject to 100 or more occupants above or below the level of exit discharge.
(3) The occupancy is subject to 1000 or more total occupancies.
39.3.3.1 - Interior finish shall be in accordance with Section 10.2.
39.3.3.2.1 - Interior wall and ceiling finish materials complying Section 10.2.
shall be Class A or Class B in exits and in exit access corridors.
39.3.3.2.2 - Interior wall and ceiling shall be Class A, Class B, Class C in areas other than those specified in 39.3.3.2.1.
39.3.4.1 - A fire alarm system in accordance with Section 9.6 shall be provided in all business occupancies where any one of the following conditions exists:
(1) The building is three or more stories in height.
(2) The occupancy is subject to 100 or more occupants above or below the level of exist discharge.
(3) The occupancy is subject to 1,000 or more total occupants.
39.3.4.2 - Initiation of the required fire alarm system shall be by one of the following means:
(1) Manual means in accordance with 9.6.2.1(1)
(2) Approved automatic fire detection system in accordance with 9.6.2.1(2) that provides protection throughout the building and the provision of 9.6.2.6. shall apply.
(3) Approved automatic sprinkler system in accordance with 9.6.2.1. (3) that provides protection throughout the building and the provision on
9.6.2.6 shall provide.
39.3.5 - Extinguishment Requirements. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.
A. For temporay partition locations see Demolition Plans. Temporary partitions are suggested locations.Coordinate final location in field with C.O.R.
B. Verify all conditions in the field prior to fabrication, erection and construction.
C. All asbestos containing material (ACM) must be abated per the direction of the C.O.R. and project specification 017419 and local state and federal regulations. Abatement if required is to be scheduled in appropriate sequence with demolition, new construction and project phasing.
D. Coordinate phase completion and start-up with requirements as set forth by the C.O.T.R. to maintain daily operations to near as normal as possible.
E. Coordinate location of job dumpster with the C.O.R. so as to disrupt daily operations as little as possible.
F. Coordinate access to all phases of construction, deliveries, and debris removal with the C.O.R. See General Requirements.
G. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. Confirm all locations with the C.O.R.
H. Existing HVAC, medical gases, sprinklers and water supply to be maintained throughout as required during each phase of construction.Coordinate phasing with Mechanical and Plumbing contractor. Support and protect all lines during each phase of construction. See MEP Drawings.
J. Provide and maintain negative air pressure at all construction.
Coordinate with HVAC contractor. See HVAC plans for temporary venting requirements and duct locations.
K. Temporary partition to structural deck above. See A601 for temporary partition type.
L. Existing power must be maintained throughout as required during each phase of construction. Coordinate phasing with Electrical Contractor. Coordinate power turnover with requirements as dictated by the C.O.R. See Electrical Drawings.
M. Coordinate sequence construction with C.O.R. so that only one side of any corridor in use is obstructed at any one time.
N. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.
Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the C.O.R.
GENERAL CONSTRUCTION NOTES
Scale: 1/8" = 1'-0"
CODE PLAN - 4th FLOOR
2018 NFPA 101 Life Safety Code Review
Building 1, 4th Floor: Compound Pharmacy Space = 606 SF
Chapter 6- Classification of Occupancy and Hazard of Content
6.1.11 Business: Existing - No Change
6.2.2. Hazard Classification: Ordinary - No change
Chapter 7- Means of Egress: No Change
7.3.1 Occupant Load of Space:
Pharmacy = 606 SF (business / 50 x 606)= 12 max occupants
Chapter 8- Features of Fire Protection: No Change
Chapter 9- Building Service and Fire Protection Equipment: No Change
Chapter 10- Interior Finish, Contents, and Furnishes
10.2.3.1 - Interior wall and Ceiling Finish Materials tested in accordance with
NFPA 286.
10.2.3.1 - Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286 and comply with 10.2.3.2.
10.2.3.1.2 - Materials tested in accordance with 10.2.3.1.1 and complying with 10.2.3.2 shall be considered also to comply with the requirements of Class A, Class B, or Class C in accordance with 10.2.3.3.
(1) During the 40 kW expsure, flames shall not spread to the ceiling.
(2) The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
(3) Flashover, as described in NFPA 286, shall not occur.
(4) The peak heat release rate throughout the test shall not exceed 800 kW.
(5) For new installations, the total smoke released through-out the test shall not exceed 1000 m2.
10.2.3.3 - Wall and ceiling- Classifications characteristics.
(1) Class A: Flame Spread: 0-25; Smoke Dev. : 0-450.
(2) Class B: Flame Spread: 26-75; Smoke Dev. : 0-450
(3) Class C: Flame Spread: 76-200; Smoke Dev. : 0-450
10.2.7.3 - Interior Floor Finish- Shall be classified based on NFPA 253 or
ASTEM E 648.
10.2.3.4.- Interior Floor- Classifications Characteristics:
(1) Class I: Rad Flux: Fin .45 W/CM2
(2) Class II: Rad Flux: Fin .22 W/CM2, and max. .45 W/cm2
10.2.8.1- Wall and Ceiling finishes, where sprinkled:
Class C permitted in any location where Class B is req’d.
Class B permitted in any location where Class A is req’d.
10.2.8.2.- Floor Finishes, where sprinkled:
Class II permitted in any location where Class I is req’d.
No critical Rad. Flux permitted in any location where Class II is req’d.
CODE NOTES
Revisions Date
2.01
2.01
2.01
2.02
2.02
2.03
2.04
2.05
2.05
2.05
2.06 2.06
2.07 2.072.07
2.072.07
2.082.08
2.09
2.09
TYP. TYP.
2.10
2.11
2.10
2.11
2.12 2.132.14
TYP. TYP.TYP.
AF101
2.16
2.15
2.15
Ante Room
B414C
Non-Hazardous Compounding
B414D
Work Station Area
B414Hazardous Storage
B414A
Hazardous Compounding
B414B
B414A
B414C
B414D B141B
B414
Corridor
C-4-5
4 1/4" 1'-0" 4 1/4" 15'-10 7/8" 4 7/8" 9'-2 1/4" 4 7/8" 9'-0 3/4" 4 1/4" 10 1/2"
4 7/8" 9'-10" 4 7/8"
1'-7 3/4"
5'-0" 11" 7'-0" 3'-2 7/8" 3'-0" 1'-10" 3'-0"
1'-7 1/2"
/4
/8
/8
/8
/8
4" 3'-10"
A B B
S2.0 S2.0
S5.1
S2.0
S2.0
S2.0
S2.0
S4.0
S2.0
8.10
8.108.10
8.14
8.14
8.15
8.098.09
8.09
AF101
AF101
C
A
C
B
S5.2S5.2 S5.2
S5.0
S5.1
D
S5.2 8.14
8.14 8.148.14
B414A
B414B
B414C B414D
B414
9.13
9.13 9.13
9.13
TYP.
TYP. TYP.
TYP.
9' - 0"
9' - 0"
9' - 0" 9' - 0"
9' - 0"
8.18
8.18
8.18
8.18
REFLECTED CEILING PLAN LEGEND
Supply Air Diffuser
Return Air Grille
2' x 4' fluorescent
2' x 2' acoustical tile ceiling
Gypsum board / portland cement plaster ceiling / soffit - painted
Ceiling Access Panel
DEMO LEGEND
Wall to be Demolished
Existing Wall to Remain
New Wall
S1.0
FLOOR SLAB
FIN. CEILING
STRUCTURE ABOVE
4 7/8"
9.219.21
9.02
9.80
7.82
10'-0" AFF
7'-4" AFF
T.O. OPENING
9.16
S2.0
9.21
9.02
7.13
7.82
7.82
7.16
4 1/4"
9.80
@ EXTERIOR
WALL LOCATIONS
@ EXTERIOR
WALL LOCATIONS
@ INTERIOR
WALL LOCATIONS
S4.0
7.82
7.82
9.02
9.21
9.80
4 1/4"
4 7/8"
9.219.21
9.02
9.17
7.82
S5.0
4 1/4"
9.02
9.02
9.17
7.82
S5.1
3 1/8"
9.21
9.01
9.17
7.82
S5.2
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
XX
JPA Project No.
Dwg. of
4TH FLOOR COMPOUND
PHARMACY
1/14/2019
FLOOR PLANS
A101
CVJR
18009.00
539-18-501
Cincinnati VA
GENERAL DEMOLITION NOTES
A. Remove all existing partitions shown with dashed line. Repair wall and floor finishes to match adjacent surfaces at areas of removal or scheduled new surfaces as required.
B. Remove all existing borrowed lights, doors and hollow metal frames where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner.
C. Remove wall-hung toilet room accessories and medical equipment as required and turn over to Owner.
D. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
E. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.T.R.
F. Repair existing walls to match adjacent undisturbed wall where cabinets, countertops, etc. are shown to be removed.
G. Prepare walls and floor slabs as required to receive new fininsh materials where existing finish is indicated to be removed.
H. Remove existing corner guards in areas to be remodeled.
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
Scale: 1/4" = 1'-0"
DEMOLITION PLAN - 4TH FLOOR
Scale: 1/4" = 1'-0"
NEW WORK PLAN - 4TH FLOOR
GENERAL PLAN NOTES
A. All dimensions are taken to face of gypsum wallboard or unit masonry.
B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.
C. All wood blocking to be fire retardent treated.
D. First floor level 100'-0" equals 728'-0".
E. All partitions shall be type 'S1.0' unless noted otherwise.
Scale: 1/4" = 1'-0"
REFLECTED CEILING PLAN - 4TH FLOOR
PLAN NOTES
2.01 Remove existing wall partition
2.02 Remove existing door and frame.
2.03 Remove existing cased opening frame.
2.04 Remove existing window.
2.05 Remove existing lavatory, cap all lines.
2.06 Remove existing radiator, cap all lines.
2.07 Remove existing casework, Note: ACM in countertop mastic.
2.08 Remove existing shelving cabinets.
2.09 Remove existing wall shelving.
2.10 Remove existing flooring, Note: ACM in flooring mastic.
2.11 Remove existing ceiling tiles and grid.
2.12 All internal blinds in existing exterior windows shall be closed.
2.13 All vent openings in existing exterior windows shall be closed.
Caulk continuously around perimeter of vent opening to ensure air tight seal.
2.14 All existing roof drains lines and building utilities shall be inspected and replaced as necessary along exterior column wall bump-outs as they will not be accessible once new wall construcion is complete.
2.15 Remove existing metal stud furring and gypsum bd finish on interior side of existing cmu core corridor wall.
2.16 Cut new 3'-10"x7'-4" opening in existing corridor wall. Install new concrete bond beam at header. See door header Detail on Sheet A601.
7.13 Batt thermal wall insulation. R-11 min.
7.16 Vapor retarder. Seal all joints and penetratons.
7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.
8.09 Pass through window system with interlock feature. See
equipment schedule on Sheet AF101
8.10 4-1/2" natural anodized aluminum frame window with tempered glass.
8.14 Handwave motion sensor, install on both sides of operable sliding door jamb wall.
8.15 Card reader door lock, installed on corridor side.
8.18 Stainless steel ceiling access panel with continuous piano hinge and gasketed trim seal. Acudor Products Inc. model: ADWT 18x18
9.01 2 1/2" non-structural metal framing @ 16" o.c.
9.02 3 5/8" non-structural metal framing @ 16" o.c.
9.13 Installed coved corner molding continuous around ceiling perimeter. See Detail 1 on Sheet A601.
9.16 3 5/8" non-structural metal diagonal bracing @ 48" o.c. attached to structure above.
9.17 ClarkDietrich BM15, security metal barrier mesh attached to studs with ClarkDietrich barrier mesh clips (BM-Clip).
9.21 5/8" Type X gypsum board.
9.80 Acoustic insulation
GENERAL RCP NOTES
A. All wood blocking shall be fire retardant.
B. Light fixtures, sprinkler heads, speakers, and HVAC devices shall be located as close as possible to the center of acoustical ceiling panels.
Confirm any deviation from this with the Project Engineer.
C. See P, M, E and FP drawings for additional information regarding final information and quantites of fixtures/devices to be installed in ceiling.
D. See Electrical Drawings for lighting specifications.
E. All gypsum board ceilings to be painted EP-2 unless noted otherwise.
F. Ceiling height to be 9'-0" AFF, unless noted otherwise.
N.T.S.Scale:
WALL TYPES
@ CORRIDOR
SIDE OF WALL
Revisions Date
3 100% CD Owner Review 01-14-2019
SEE SCHED.
S E
E S
C H
E D
U L E
N
S E
E S
C H
E D
U L E
OF
SEE SCHEDULE
SD
breakout side
2"
SEE
SCHED. 2"
S E
E S
C H
E D
U L E
A
SEE PLAN
1/2" 1/2"
H1 J1
8.02
9.21
9.80
8.02
9.09
9.21
9.80
9.08
7.82 7.82 1/2" 1/2"
H2
SEE PLAN
J2
SEE PLAN
8.02
9.349.34
9.21
7.82
3.10
3.09
8.02
7.82
9.21
9.34
3.09
SEE PLAN
4.23
5'-0"
FINISH FLOOR
A
HAZARDOUS
COMPOUNDING
ROOM
A601
A601
A601
3'-0"
FINISH FLOOR
B
NON-HAZARDOUS
COMPOUNDING
ROOM
A601
A601
A601
9.21
9.80
7.83
SEE PLAN
9.08
6.09
9.21
9.80
6.01
9.02
9.14
1/2" 1/2"
8.26
7.83
SEE PLAN
S E
E P
L A
N
9.21
9.80
6.01
9.02
9.21
8.26
7.83
9.21
9.02
9.21
9.13
NOTE:
COVED MOLDING TO BE INSTALLED
AT CEILING PERIMETER IN ROOMS,
B414B, B414C & B414D. SEE PLAN FOR
WALL TYPE CONSTRUCTION.
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
XX
JPA Project No.
Dwg. of
4TH FLOOR COMPOUND
PHARMACY
1/14/2019
DOOR SCHEDULE, WINDOW &
MISCELLANEOUS DETAILS
A601 DesignerApprover
18009.00
539-18-501
Cincinnati VA
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
DOOR SCHEDULE
DOOR
BETWEEN DOOR DESCRIPTION FRAME DESCRIPTION
FIRE
RATING
HDWE
SET REMARKSRM RM TYPE MAT'L
SIZE
TYPE MAT'L HEAD JAMB# W H T
B414 C-4-5 B414 N WD 1 3' - 6" 7' - 2" 1 3/4" A HM H2 J2 20 MIN 1 Door Lite shall have security wire mesh embedded into glazing
B414A B414 B414A N WD 1 3' - 0" 7' - 0" 1 3/4" A HM H1 J1 20MIN 2
B141B B414B B414C 2 7' - 0" 7' - 8" 4 5/8" 3 Automatic Sliding Door w/ Handwave Sensor - Assa Abloy SL500 Clean Room Door
B414C B414C B414 2 7' - 0" 7' - 8" 4 5/8" 3 Automatic Sliding Door w/ Handwave Sensor - Assa Abloy SL500 Clean Room Door
B414D B414C B414D 2 7' - 0" 7' - 8" 4 5/8" 3 Automatic Sliding Door w/ Handwave Sensor - Assa Abloy SL500 Clean Room Door
N.T.S.Scale:
DOOR TYPES
N.T.S.Scale:
FRAME TYPES
N.T.S.Scale:
H.M. FRAME DETAILS
Scale: 1/2" = 1'-0"
WINDOW TYPES
Scale: 1 1/2" = 1'-0"4
HEAD DETAIL
Scale: 1 1/2" = 1'-0"2
SILL DETAIL
Scale: 1 1/2" = 1'-0"3
JAMB DETAIL
Scale: 1 1/2" = 1'-0"1
TYP. COVE CEILING DETAIL
GENERAL DOOR NOTES:
INTERIOR WOOD DOORS:
General:
1. Provide each product from one species and manufacturer throughout project
2. Install all products according to manufacturer's instructions and requirements
3. General Requirements
- ANSI/WDMA I.S. 1A, Extra Heavy Duty
- Adhesive: Type II
- Core: Structural composite lumber
- Thickness: 1-3/4 inches u.n.o.
4. Clearances between doors and frames and floors
- Maximum 1/8 inch clearance at jambs, heads and 3/4 inch clearance at bottom
Frames:
1. Welded frames only, No knockdowns.
2. Interior Door Frames to include Hospital stops (6” high cut at 45 degrees.)
3. Do NOT grout frames solid in drywall partitions – the moisture from the grout can get into the drywall, and cause mold to grow.
Doors:
1. Typical Interior door to be solid core wood doors: Natural Birch Veneer; Rotary cut “RA100”; 1 3/4” thick; ½” Maximum under cut. Grade A Prefinished.
2. All wood doors to be minimum 20 minute rating unless otherwise noted.
3. Window lites in doors to be rectangular shaped, 4”wide by 25” high - and have a metal frame. Make sure to include painting this frame in the finish schedule.
Hardware:
1. The following items shall be of the same manufacture: mortise locksets, hinges and closers
2. Hinges: Provide only three-knuckle hinges
- Quantity: 3 hinges per door
- Size: 3'-0"W. door = 4-1/2" x 4-1/2" hinges. 3'-6"W. door = 5" x 4-1/2" hinges
3. Closers:
- Minimum 50% adjustable closing force and adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
- Arm and brackets shall be steel, malleable iron or high strength cast iron.
- Equipped with full size metal cover.
- 1-1/2" min. piston diameter.
4. Door stops:
- Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction.
- Wall bumpers where installed, must be within 4 inches of the wall face and impact the door within the leading half of its width.
5. Kickplates:
- Shall be stainless steel, Type J100 series
6. Finishes:
- 626 or 630: all surfaces u.n.o.
- Hinges: 652 or 630
- Closers: factory applied paint finish. Dull or satin aluminum color
- Thresholds: mill finish aluminum
- Anti-microbial Coating: all hand-operated hardware shall be provided with an anti-microbial / anit-fungal coating (ASTM E2180) that consists of ionic silver (Ag+).
Silver ions surround bacterial cells, inhibiting growth of bacteria, mold and mildew.
7. Heights:
- Locksets and latch sets centerline of strike = 40-5/16 inches
- Locate all other hardware at standard commercial heights
AUTOMATIC POWER-OPERATED SLIDING DOORS:
General:
1. Source Limitations: Obtain sliding folding automatic entrances from single source from single manufacturer.
2. Electrical System Roughing-in: Coordinate layout and installation of automatic entrances with connections to power supplies and access-control system , remote activation devices, and remote monitoring systems.
Performance Requirements:
1. Air Infiltration: Maximum air leakage through fixed glazing and framing areas of 1.25 cfm/sq. ft. of fixed entrance-system area when tested according to ASTM E 283 at a minimum static-air-pressure difference of 1.57 lbf/sq. ft.
2. Opening Force: Power-Operated Doors: Not more than 50 lbf required to manually set door in motion if power fails, and not more than 15 lbf required to open door to minimum required width.
3. Entrapment-Prevention Force: Power-Operated Sliding Doors: Not more than 30 lbf required to prevent stopped door from closing.
Sliding Automatic Entrance:
1. Configuration: Single-sliding door with one sliding leaf (operable) and one sidelight (fixed)
2. Rollers: Min. of two ball-bearing roller wheels and two antirise rollers for each active leaf.
3. No Threshold to be installed
4. Activation Device: Touchless switch (Hand Wave) on each side of door to activate door operator. Adjustable detection from 4"-24" away from sensor.
5. Finish: Finish framing, door(s), and header with Class II, clear anodic finish.
6. Framing Members: Extruded aluminum, minimum 0.125 inch thick and reinforced as required to support imposed loads.
7. Glazing: Tempered safety glass
8. Joints: Fill and seal / caulk perimeter joint Controls:
1. Provide operators and controls, which include activation and safety devices, according to BHMA standards, for condition of exposure, and for long-term, maintenance-free operation under normal traffic load for type of occupancy indicated.
2. Touchless Switch: Hands-free-activation door-control switch with flat motion sensor faceplate.
3. Configuration: 2.77-by-4.56-inch (single gang) rectangular faceplate.
- Mounting: Meet ADA minimums.
- Faceplate Material: Stainless steel.
- Message: "Wave to Open" and wave symbol
4. Door Operators: Connect door operators to electrical power distribution system. Install and adjust activation and safety devices according to manufacturer's written instructions.
Installation:
1. Entrances: Install automatic entrances plumb and true in alignment with established lines and grades without warp or rack of framing members and doors. Anchor securely in place.
2. Install surface-mounted hardware using concealed fasteners to greatest extent possible.
3. Set headers, carrier assemblies, tracks, operating brackets, and guides level and true to location with anchorage for permanent support.
4. Guide Rails: Install rails according to BHMA A156.10, including Appendix A, and manufacturer's written instructions unless otherwise indicated.
Adjusting:
1. Adjust hardware, moving parts, door operators, and controls to function smoothly, and lubricate as recommended by manufacturer.
2. Adjust doors for tight closure.
DOOR HARDWARE SETS:
GENERAL LOCKSET NOTES:
1. Owner shall be responsible for providing additional information regarding these hardware sets
2. All locksets to come with blank cylinders and two (2) blank keys each. VA Locksmith will key each lockset upon project completion.
3. Locksets to be Corbin Russwin, 7 pin large format interchangeable cores (LFIC). Key way options are 59A1, 59A2, 59B1, 59B2, 59C1, 59C2, 59D1, & 59D2. Coordinate keyway type with VA Locksmith.
Handle to be “Newport” style.
4. Mortised guards are now permitted on rated doors – as long as the doors are mortised at the factory.
If surface mounted edge guards are specified for rated doors, they MUST go full height.
5. Wall stops are preferred over floor stops. All wall stops should be solid spheres, not hollow.
6. When Card Readers are called for – use an electronic lockset (in lieu of electronic strike or magnetic locks).
7. Card Reader: Door normally closed and locked. Presenting a valid credential to the reader will momentarily unlock the lock allowing access. Door to remain locked upon loss of power or activation of the fire alarm.
The request to exit feature of the lock to shunt the alarm output of the door contact. Door contact monitors whether the door is open or closed. Free egress at all times by depressing lock lever.
PLAN NOTES
3.09 Existing 4" CMU wall.
3.10 4" Concrete Lintel with #3 rebar top and bottom.
4.23 Masonry anchor.
6.01 2" x 4" wood blocking.
6.09 Wood blocking / shim
7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.
7.83 Cont. sealant each side.
8.02 Hollow metal frame.
8.26 [4-1/2"] Aluminum storefront window system.
9.02 3 5/8" non-structural metal framing @ 16" o.c.
9.08 Metal framing box header.
9.09 Double metal framing at jambs, typ.
9.13 Installed coved corner molding continuous around ceiling perimeter. See Detail 1 on Sheet A601.
9.14 Solid surface window sill trim.
9.21 5/8" Type X gypsum board.
9.34 Existing non-structural metal stud furring.
9.80 Acoustic insulation
SET #1 (Door B414)
- 2 ea. Hager Hinges Heavyweight B1168 5 x 4 ½ x US26D.
- 1 ea. Electric Hinge; 3CB1 4.5X4.5 TW4 (A8112-4 Wire Type)
- 1 ea. Electrified Storeroom Lockset - Card Reader; (F04 - Request to exit switch and fail secured). Corbin Russwin Lockset - 7 Pin;
Style NSA “Newport”’ ML2051 x US26D.
- 1 ea. Rockwood Door Edging 301 x 36” x US32D (For recessed installation - typ.)
- 1 ea. Rockwood #400 Series (wall type) Door Stop.
- 2 ea. Stainless Kickplate
- 3 ea. Silencers
- 1 ea. Closer LCN 4041P x AL
- 1 ea. Door Contact - Concealed
- 1 ea. Power Supply; Regulated, filtered, 24VDC, Amperage as req'd for Card Reader
Set #2 (Door B414A)
- 1 ½ Pr.Hager Hinges Heavyweight B1168 5 x 4 ½ x US26D.
- 1 ea. Corbin Russwin Lockset (F01) – 7 Pin; Style NSA “Newport"
ML2010 x US26D.
- 1 ea. Rockwood Door Edging 301 x 36” x US32D (For recessed installation - typ.)
- 1 ea. Rockwood #400 Series (wall type) Door Stop.
- 3 ea. Silencers
- 1 ea. Gasketing; 488S (R0E154)
- 1 ea. Power Supply; Regulated, filtered, 24VDC, Amperage as req'd for Card Reader
SET #3 (Doors B414B, B414C, B414D)
- Assa Abloy door model: SL500 Clean Room
- Overhead Concealed Full Breakout Narrow Stile Single Slide Door System
- Natural anodized aluminum finish
- Automatic operator
- Frames, doors and sidelites with Non-Shedding weatherstrip
- Emergency Breakaway - both operable and fixed doors swing open
- Motion / presence sensors (Handwave activated)
- (2) per door (one each side of door)
- Single sliding door with fixed sidelight
- (2) left hand slide opening (B414B & B414C)
- (1) right hand slide opening (B414D)
- Power Supply; see manufacturer's specifications and instructions
- 35-1/4" wide clear door opening
Revisions Date
3 100% CD Owner Review 01-14-2019
Ante Room
B414C Non-Hazardous Compounding
B414D
Work Station Area
B414Hazardous Storage
B414A
Hazardous Compounding
B414B
Corridor
C-4-5
RS
PF
PF PT
CC CC
RWPR
EHEH
EH
CS
DS
LP
SH
SH
SH
PC PCPC
BE
FC FC FC FC
12.3212.32
12.32
PL-1
RES-1
EP-1
2'-0" 5'-6" 2'-0"1'-6" 4'-6" 1'-6"
B1 B1
B414C
1 PTPF
8.14
Ante Room
B414C Non-Hazardous Compounding
B414D
Work Station Area
B414 Hazardous
Storage
B414A
Hazardous Compounding
B414B
Corridor
C-4-5
9.19
9.20
EP-1
RES-1
B
A
C
C
CS
D
8.14
8.14
B1
2'-1"
12.21
12.28
12.19
12.32
Ante Room
B414C
Non-Hazardous Compounding
B414D
Work Station Area
B414Hazardous Storage
B414A
Hazardous Compounding
B414B
B414A
B414C
B414DB141B
B414
Corridor
C-4-5
8 1/2"
/2
JOHN
A.
POE
IO
HO
FOET
A T
S
R E G
IS
E T
R
ED RA
C H
TI
E C T
Drawing Title
Approved: Project Director
Location
Building Number
Project Title
Checked DrawnDate
Project No.
Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t
F E
D C
B A
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
F E
D C
B A
VA Project No.
FULLY SPRINKLERED
ARCHITECT/ENGINEERS:CONSULTANTS:
Office of Construction and Facilities Management
XX
JPA Project No.
Dwg. of
4TH FLOOR COMPOUND
PHARMACY
1/14/2019
FINISH PLANS
AF101
DesignerApprover
18009.00
539-18-501
Cincinnati VA
3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290
Scale: 1/4" = 1'-0"
EQUIPMENT / FURNITURE PLAN
EQUIPMENT SCHEDULE
R o o m
N u m b e r
T a g
D e s c ri p ti o n
M a n u fa c tu re r
M o d e l
C o u n t
S u p p lie r In s ta lle r
W id th
D e p th
H e ig h t
V o lt
A m p
E m
D a ta
R e m a rk s
Comments B414
Work Station Area
B414 FC 15" x 18" 4 on Casters
B414 LP Label Printer Zebra ZM600 1 V V 13" 19" 13" 0 X X Existing
B414 PC Worstation Computer 3 V V X X
B414 PR Multi-function Printer Lexmark CX820dtfe 1 V V 25 1/2" 23 1/8" 44 3/4" X Existing
B414 PT Pass-Thru System, Non-filtered Clean Air Products CAP18WFB-SST-12Wx12Hx12D 1
B414 RW Refrigerator - Work Station Helmer HPR125 1 V V 29 1/2" 35 1/2" 78 3/4" 115 15 X
B414 SH 24x60 Shelving Unit 1 V V 60" 24" 74" on Casters
B414A
Hazardous Storage
B414A PF Pass-Thru System - HEPA Filtered Atmos-Tech Ind. PT1212-12 1 V V 18" 12" 14"
B414A RS Refrigerator - Haz Str Helmer HPR111 1 V V 24 1/2" 24 1/2" 70 1/2" 115 15 X Existing
B414A SH 24x60 Shelving Unit 2 V V 60" 24" 74" on Casters
B414B
Hazardous Compounding
B414B CC Compound Rm Shelving Cart 1 V V 18" 24" 36" on Casters
B414B EH Class II Type A2 Biosafety Cabinet Nuaire - Labgard Air NU-543-400 2 V V 54" 31 1/2" 61" 115 X on Casters
B414B PF Pass-Thru System - HEPA Filtered Atmos-Tech Ind. PT1212-12 1 V V 18" 12" 14"
B414C
Ante Room
B414C 8.14 HS- Handwave Sensor X 2 48" A.F.F. TO
CENTERLINE
B414C BE BE - Ante Rm Bench 1 V V 30" 18" 14"
B414C CS 24x24 Clean Shelving Cart 1 V V 24" 24" 36" on Casters
B414C DS 24x24 Dirty Shelving Cart 1 V V 18" 30" 36" on Casters
B414D
Non-Hazardous Compounding
B414D CC Compound Rm Shelving Cart 1 V V 18" 24" 36" on Casters
B414D EH Class II Type A2 Biosafety Cabinet Nuaire - Labgard Air NU-543-400 1 V V 54" 31 1/2" 61" 115 X on Casters
Note:
All equipment and furniture listed in schedule above shall be verified as specified (or equal to) and coordinated with owner.
C C - CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
V V - OWNER FURNISHED, OWNER INSTALLED
EQUIPMENT LEGEND
Scale: 1/2" = 1'-0"2
WORKSTATION ELEVATION
Scale: 1/4" = 1'-0"
FLOOR FINISH PLAN
Scale: 1/2" = 1'-0"1
ANTE ROOM
Scale: 1" = 1'-0"3
CASEWORK SECTIONS
PLAN NOTES
8.14 Handwave motion sensor, install on both sides of operable sliding door jamb wall.
9.19 Clean/dirty demarcation line painted on floor.
9.20 Rubber transition strip TS-1 from resinous flooring to existing corridor flooring.
12.19 Applied backsplash. Plastic laminate over 3/4" particle board.
Provided by Owner.
12.21 Plastic laminate over 3/4" particle board. Provided by Owner.
12.28 Surface mounted countertop support bracket. Provided by Owner.
12.32 Wire management grommet. Provided and coordinated by Owner.
TOILET ACCESSORIES SCHEDULE
MARK DESCRIPTION PRODUCT # MOUNTING HEIGHT COMMENTS
8.14 X 48" A.F.F. TO CENTERLINE
A LINT FREE WIPE DISPENSER BOX CLEANROOM CDW-99-W 54" A.F.F. TO TOP
B SOAP DISPENSER BY OWNER 50" A.F.F. TO TOP
C COAT HOOK BOBRICK B-6717 54" TO CENTER
D EYE WASH BY OWNER FAUCET MOUNTED
FINISH LEGEND
CODE FINISH TYPE MANUFACTURER PRODUCT / COLOR COMMENTS
CASEWORK FINISHES
PL-1 PLASTIC LAMINATE WILSONART 7919-60 AMBER CHERRY
CEILING FINISHES
EP-2 PRECATALYZED EPOXY PAINT GLIDDEN CEILING WHITE GLOSS LEVEL 1
FLOOR FINISHES
RES-1 RESINOUS FLOORING SIKA INDUSTRIAL FLOORING PURCEM 22NA, RAL 7042 TRAFFIC GREY 6" HIGH INTEGRAL COVE BASE
TS-1 TRANSITION STRIP JOHNSONITE 49 BEIGE WB
WALL FINISHES
EP-1 PRECATALYZED EPOXY PAINT GLIDDEN WATER CHESTNUT 30YY 62/127 GLOSS LEVEL 3
EP-3 PRECATALYZED EPOXY PAINT GLIDDEN MUSHROOM CAP 20YY 55/151 GLOSS LEVEL 5
ROOM FINISH SCHEDULE
ROOM # ROOM NAME FLOOR BASE
WALLS CASEWORK
CEILINGNorth South East West Cabinet Countertop
B414 Work Station Area RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - PL-1 ACT-1
B414A Hazardous Storage RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2
B414B Hazardous Compounding RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2
B414C Ante Room RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2
B414D Non-Hazardous Compounding RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2
GENERAL INT. ELEVATION NOTES
A. All hollow metal doors and door frames to be painted EP-3.
Scale: 1/4" = 1'-0"
SIGNAGE PLAN
SIGNAGE SCHEDULE
MARK MOUNTING LOCATION
1 54" A.F.F. TO TOP
GENERAL EQUIPMENT NOTES
A. Coordinate with owner and verify owner-provided equipment.
N.T.S.Scale:
SIGNAGE DETAILS
Revisions Date
3 100% CD Owner Review 01-14-2019
A1
P1 P1OR
A1
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD
CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO
SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER
DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN
UNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
10" 10"
ELEV: 8' - 0"ELEV: 8' - 0"
TOE: 3' - 0"
BOE: 0' - 6"
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR
BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERWISE
APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE
OF PIPE, UNLESS NOTED OTHERWISE
FIRE SUPPRESSION SYMBOLS
CONCEALED PENDENT SPRINKLER
FS
PIV
S
FIRE HYDRANT
FLOW SWITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE WALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
PIPING SYMBOLS
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT
PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
EXISTING PIPE TO BE REMOVED
EXISTING PIPE TO REMAIN
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
D
R
SPECIALTY GAS SYMBOLS
AIR OUTLET - LAB TYPE
VC
VC
CARBON DIOXIDE OUTLET - HOSPITAL TYPE
MEDICAL AIR OUTLET - HOSPITAL TYPE
MEDICAL VACUUM INLET - HOSPITAL TYPE
NITROGEN OUTLET - HOSPITAL TYPE
NITROUS OXIDE OUTLET - HOSPITAL TYPE
OXYGEN OUTLET - HOSPITAL TYPE
WAGD INLET - HOSPITAL TYPE
NATURAL GAS OUTLET - LAB TYPE
VACUUM OUTLET - LAB TYPE
VACUUM CLEANING STATION - WALL
VACUUM CLEANING STATION - FLOOR
PIPING DESIGNATIONS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT WATER PIPE (140 DEGS. F.)
HOT WATER PIPE (180 DEGS. F.)
HOT WATER RETURN PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
MEDICAL CARBON DIOXIDE PIPE
COMBINATION FIRE SUPPRESSION AND DOMESTIC
WATER SERVICE
DIESEL FUEL PIPE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)
FIRE SERVICE
FUEL OIL FLOW LINE
FUEL OIL GAUGE LINE
FUEL OIL RETURN LINE
FUEL OIL SUPPLY LINE
NATURAL GAS PIPE
GARAGE DRAINAGE PIPE
GAS SERVICE
HYDROGEN PIPE
HELIUM PIPE
MEDICAL INSTRUMENT AIR PIPE
KITCHEN WASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY WASTE PIPE
MEDICAL NITROGEN PIPE
MEDICAL COMPRESSED AIR PIPE
MEDICAL-SURGICAL VACUUM PIPE
GASOLINE PIPE (NON-LEAD)
MEDICAL NITROUS OXIDE PIPE
NON-POTABLE
MEDICAL OXYGEN PIPE
(OVERFLOW) SECONDARY STORM DRAINAGE PIPE
PROPANE GAS PIPE
PUMP DISCHARGE PIPE
PRE-ACTION / DELUGE SPRINKLER PIPE
PURE WATER PIPE
SPRINKLER PIPE (WET)
SANITARY DRAINAGE PIPE
SOFT COLD WATER
SPRINKLER DRAIN PIPE
STORM DRAINAGE PIPE
FUEL TANK VENT PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED WATER PIPE
SANITARY SEWER VENT
WASTE ANESTHESIA GAS DISPOSAL PIPE
WATER SERVICE
LV
140R
180R
AR
CA
CO2
CWS
DF
DS
F
FS
FOF
FOG
FOR
FOS
G
GD
GS
H2
HE
IA
IV
IW
LA
LV
LW
N2
MA
MV
NG
NO
NPW
O2
OD
P
PD
PS
PW
S
SAN
SCW
SD
STM
T
TP
TW
V
WAGD
WS
INDIRECT VENT PIPE
INDIRECT WASTE PIPE
K
CHECK VALVE
T
P
FOB
FOT
SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE GAUGE
TEMPERATURE GAUGE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER WITH A BLOW DOWN VALVE AND HOSE
CONNECTION
DRAIN VALVE WITH HOSE END CONNECTION
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG
IN AND OUT
EXPANSION JOINT
PRESSURE REGULATING VALVE
SAFETY RELIEF VALVE. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERWISE.
PRESSURE AND TEMPERATURE TEST PLUG
TRAP PRIMER
VACUUM GAUGE WITH STOP
CLEANOUT TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
PLUG VALVE
SHUTOFF VALVE AND BOX
SHUTOFF VALVE ON RISER
V
VB
TP
CO
COMBINATION SHUTOFF AND BALANCING
VALVE (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
BALL VALVE, BUTTERFLY VALVE, GATE VALVE
VALVES AND FITTINGS
SOLENOID VALVE
S
P/T PRESSURE AND TEMPERATURE SAFETY RELIEF
VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR
DRAIN UNLESS NOTED OTHERWISE.
FIRE DEPARTMENT VALVE
WATER METERM
ACID VENT PIPEAV
ACID WASTE PIPEAW
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACC - ACCESS
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
AR - AIR RECEIVER OR ARGON
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
AV - ACID VENT
AW - ACID WASTE
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BT - BATHTUB
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTWN - BETWEEN
CA - COMPRESSED AIR
CB - CATCH BASIN
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED WATER SUPPLY
CHR - CHILLED WATER RETURN
CI - CAST IRON
CK - CLINICAL SINK
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - MEDICAL CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CS - CLINICAL SINK OR COLD SOFT WATER
CTR - CENTER
CU - COPPER
CW - COLD WATER
CWS - COMBINATION WATER SERVICE
OR CONDENSER WATER SUPPLY
CWR - CONDENSER WATER RETURN
D - DEPTH OR DRAIN LINE
DD - DECK DRAIN
DET - DETAIL
DF - DRINKING FOUNTAIN OR WATER COOLER
OR DIESEL FUEL
DFU - DRAINAGE FIXTURE UNIT
DI - DEIONIZED WATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DS - DOWN SPOUT OR SPRINKLER (DRY)
DT - PERFORATED DRAIN TILE
DWG - DRAWING
EA - EACH
EC - ELECTRICAL CONTRACTOR (DIVISION 26)
EEW - EMERGENCY EYE WASH
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
ES - EMERGENCY SHOWER
EQS - EQUIPMENT SUPPLIER
EWC - ELECTRICAL WATER COOLER
EXH - EXHAUST AIR
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FM - FORCE MAIN
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FLOOR SINK OR FIRE SERVICE
FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES CONTRACTOR
GD - GARAGE DRAINAGE
GPM - GALLONS PER MINUTE
GS - GAS SERVICE
GW - GREASE WASTE
H2 - HYDROGEN
HB - HOSE BIBB
HC - HVAC CONTRACTOR (DIVISION 23)
HD - HUB DRAIN
HE - HELIUM
HG - REFRIGERANT HOT GAS
HP - HORSEPOWER OR HIGH POINT
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HPW - HIGH PURITY WATER
HPWR - HIGH PURITY WATER RETURN
HR - HOSE REEL
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
HW - HOT WATER
HWR - HEATING HOT WATER RETURN
HWS - HEATING HOT WATER SUPPLY
IA - MEDICAL INSTRUMENT AIR
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
IV - INDIRECT VENT
IW - INDIRECT WASTE
JS - JANITOR SINK
K - KITCHEN WASTE
KEC - KITCHEN EQUIPMENT CONTRACTOR
L - LENGTH
LA - LABORATORY COMPRESSED AIR
LAV - LAVATORY
LBS - POUNDS
LCW - LABORATORY COLD WATER
LEC - LABORATORY EQUIPMENT CONTRACTOR
LHW - LABORATORY HOT WATER
LHWR - LABORATORY HOT WATER RETURN
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LV - LABORATORY VACUUM OR LABORATORY VENT
LW - LABORATORY WASTE
MA - MEDICAL COMPRESSED AIR
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL CONTRACTOR (DIVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - WATER MAKE-UP
MV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGEN
N/C - NORMALLY CLOSED
NG - GASOLINE (NON-LEAD)
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NO - MEDICAL NITROUS OXIDE
NOM - NOMINAL
NPW - NON-POTABLE WATER
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
02 - MEDICAL OXYGEN
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER OR OVERFLOW DRAIN
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GAS
PC - PLUMBING CONTRACTOR (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PD - PUMP DISCHARGE OR PARAPET DRAIN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
PW - PURE WATER
RA - RETURN AIR
RAD - RADIUS
RCP - REINFORCED CONCRETE PIPE
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS WATER SUPPLY
ROR - REVERSE OSMOSIS WATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RV - RELIEF VALVE
S - SPRINKLER (WET)
SA - SHOCK ARRESTOR OR SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD WATER
SD - SPRINKLER DRAIN OR SUBSOIL DRAIN
SH - SHOWER
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SS - SANITARY STACK (SOIL OR WASTE) OR
STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENT
TD - TRENCH DRAIN
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TF - TRAP FILLER
TP - TRAP PRIMER OR TRAP PRIMER DISCHARGE
TW - TEMPERED WATER
TYP - TYPICAL
UR - URINAL
UNO - UNLESS NOTED OTHERWISE
V - VENT OR SANITARY SEWER VENT
VAC - VACUUM
VC - VACUUM CLEANING
VCV - VACUUM CLEANING VALVE
VE - VACUUM EXHAUST
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
VP - VACUUM PUMP
VS - VENT STACK
VTR - VENT THROUGH ROOF
VR - VENT RISER
W/ - WITH
W/0 - WITHOUT
W - WASTE
WAGD - WASTE ANESTHESIA GAS DISPOSAL
WC - WATER CLOSET
WCO - WALL CLEANOUT
WH - WALL HYDRANT OR WATER HEATER
WIV - WALL INDICATOR VALVE
WS - WATER SERVICE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
PIPE RISER
A PROVIDE A COMPLETE FIRE SUPPRESSION SPRINKLER SYSTEM
AS INDICATED ON THE DRAWINGS.
B COORDINATE WORK WITH VAMC, PHASING PLAN AND OTHER TRADES.
EACH CONTRACTOR SHALL BE RESPONSIBLE FOR OFFSETTING AND/ OR
RELOCATING SERVICES TO ACCOMMODATE NEW WORK OF
OTHER TRADES.
C VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEW PIPING
REQUIRED TO COMPLETE THIS WORK.
D ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM
OF STRUCTURE IN EXPOSED STRUCTURAL AREAS) UNLESS OTHERWISE
INDICATED.
E THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRE
SUPPRESSION SPRINKLER SYSTEM SHALL BE FOR A WET PIPE SYSTEM
HYDRAULICALLY CALCULATED FOR A:
1 LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER
SPRINKLER WITH THE DENSITY OF 0.10 GPM/ SQ. FT. OVER THE
MOST REMOTE 1500 SQ. FT. PROVIDE AN ADDITION OF 100 GPM
HOSE ALLOWANCE.
2 ALL MECHANICAL, ELECTRICAL AND SIMILAR SPACE AREAS SHALL
BE ORDINARY HAZARD (GROUP 1) LIMITED TO A MAXIMUM OF
130 SQ. FT. PER SPRINKLER WITH A DENSITY OF 0.15 GPM/ SQ. FT.
PROVIDE AN ADDITION OF 250 GPM HOSE ALLOWANCE.
3 ALL STORAGE, TRASH, FILE STORAGE AND SIMILAR SPACE AREAS
SHALL BE ORDINARY HAZARD (GROUP 2) LIMITED TO A MAXIMUM OF
130 SQ. FT. PER SPRINKLER WITH A DENSITY OF 0.20 GPM/ SQ. FT.
PROVIDE AN ADDITION OF 250 GPM HOSE ALLOWANCE.
F THE ENTIRE SPRINKLER SYSTEM SHALL CONFORM TO VAMC, LOCAL
STATE AND NFPA STANDARDS, RULES AND REGULATIONS.
G CAREFULLY COORDINATE THE LOCATION OF ALL SPRINKLERS AND
PIPING WITH ALL OTHER TRADES AND THE ARCHITECT.
H VERIFY THE LOCATION OF ALL LIGHTING FIXTURES AND AIR DEVICES
BEFORE INSTALLATION OF SPRINKLERS.
I ALL SPRINKLER PIPING LAYOUT AND SIZING SHALL BE BY THE
CONTRACTOR.
J ALL SPRINKLER LOCATIONS MUST BE COORDINATED WITH ALL EQUIPMENT
KINDRED TO OTHER TRADES. SPRINKLER LOCATIONS MUST BE
APPROVED BY THE ARCHITECT BEFORE WORK COMMENCES. REFER TO
THE ARCHITECTURAL AND…