4th Floor Pharmacy HVAC Construction Project no. 539-18-501 Federal contract opportunity
Solicitation number
36C25019B0022
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

36C25019B0022 0002 HVAC Scope Drawings 4-3-2019.pdf

View the file

Other files for this federal contract opportunity

Other files attached to 4th Floor Pharmacy HVAC Construction Project no. 539-18-501, newest first.
File Type Posted
36C25019C0162-000.docx DOCX document
36C25019B0022-0003003.docx DOCX document
36C25019B0022-0002001.pdf PDF
36C25019B0022-0002000.docx DOCX document
36C25019B0022-0001000.docx DOCX document
36C25019B0022-0001001.pdf PDF
36C25019B0022-0001002.pdf PDF
36C25019B0022-005.pdf PDF
36C25019B0022-003.docx DOCX document
36C25019B0022-006.docx DOCX document
36C25019B0022-002.docx DOCX document
36C25019B0022-007.docx DOCX document
36C25019B0022-004.pdf PDF
36C25019B0022-001.docx DOCX document
36C25019B0022-000.docx DOCX document
Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

N

EXTERIOR ELEVATION

INTERIOR ELEVATION

SEE 700 SERIES SHEETS

SECTION/DETAIL NUMBER

DRAWING NUMBER

EQUIPMENT TAG

COLUMN GRID

NOTE

WINDOW OPENING

DOOR OPENING

ROOM NAME

ROOM NUMBER

WALL TYPE

SEE SHEET A001

CEILING HEIGHT

FINISH DESIGNATION

X

10'-8"

X

X

XX.X-X

XX

X

1/A101

X

XXXX

X

SIM

XX

TOILET ACCESSORY TAGX SIGNAGE TAGX

Project Location

N

Ludlow Ave.

C lif to n A v e

CINCINNATI

STATE

TECH.

Hopple St.

M.L.K. Dr.

McMillan St.

UNIV. OF

CINCINNATI

W.H.T Rd.

VAMC

3200 VINE ST.

M.L.K. Dr.

V in e St.

ZOO

Jefferson Ave.

UNIV.

HOSPITAL

Mitchell Ave.

R e ad in g

R d.

V ic to ry

P kw

y. XAVIER

UNIV.

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G

IS

E T

R

ED RA

C H

TI

E C T

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

JPA Project No.

Department of Veterans Affairs Medical Center

ARCHITECTURE PLANNING INTERIOR DESIGN

3131 NEWMARK DRIVE, SUITE 200

MIAMISBURG, OHIO 45342

937.461.3290 P

JOHN POE ARCHITECTS

HEAPY ENGINEERING

MECHANICAL ELECTRICAL COMMISSIONING TECHNOLOGY

1400 WEST DOROTHY LANE

DAYTON, OH 45409

937.224.0861 P

937.224.5777 F

Dwg. of

4TH FLOOR COMPOUND

PHARMACY

3/13/2019

COVER SHEET

G001

CVJR

18009.00

539-18-501

Cincinnati VA

4TH FLOOR COMPOUND PHARMACY

3200 Vine St. Cincinnati, Ohio 45220 PROJECT #: 539-18-501

G001 COVER SHEET

G100 CODE DATA

A101 FLOOR PLANS

A601 DOOR SCHEDULE, WINDOW & MISCELLANEOUS DETAILS

AF101 FINISH PLANS

P001 LEGEND, INDEX & GENERAL NOTES

P104 PARTIAL FOURTH FLOOR PLAN - PLUMBING

M001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS

M104 PARTIAL FOURTH FLOOR PLAN - HVAC

M105 PARTIAL ROOF PLAN - HVAC

M501 DETAILS

M502 DETAILS

M601 SCHEDULES

M701 CONTROLS

M702 SCHEMATICS

M703 HOT WATER SYSTEM SCHEMATIC

M704 STEAM SYSTEM SCHEMATIC

E001 LEGEND, ABBREVIATIONS & INDEX OF DRAWINGS

E104 PARTIAL FOURTH FLOOR PLAN - ELECTRICAL

E105 PARTIAL ROOF PLAN - ELECTRICAL

E501 DETAILS

E502 TECHNOLOGY DETAILS

E601 SCHEDULES

GENERAL CONSTRUCTION NOTES

7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO

BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE

SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT

THROUGH FINISHED OPENINGS.

8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,

HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS

AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT

DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL

WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.

9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS SPECIFICALLY

NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS INDICATED AT SIMILAR

CONDITIONS.

10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL SYSTEMS

WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE THE

OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE

NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR

SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.

11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED

WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF THE

WALL.

12. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO

AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER

RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS

RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS

IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY

FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.

* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE

CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE.

1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,

INTERNATIONAL BUILDING CODE, AND OTHER COES AS IDENTIFIED IN VHA

PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND EXECUTIVE

ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERAN AFFAIRS,

TECHNICAL INFORMATION LIBRRARY WEBSITE.

2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST

ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND

DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13

WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS

TECHNICAL INFORMATION LIBRARY WEBSITE.

3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT

EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED

WITH THE CONTRACTING OFFICER'S REPRESENTATIVE.

4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH

ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT

ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.

5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF

NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO

REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT

SURFACES TO REMAIN.

6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND

DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW

MATERIALS.

DRAWING INDEX

GRAPHIC SYMBOLS

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290

N.T.S.Scale:

Building 1 - 4th Floor Key Plan

N.T.S.Scale:

Vicinity Map

Revisions Date

3 100% CD Owner Review 01-14-2019

2 DD Submittal 12-20-2018

1 SD Submittal 11-16-2018

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Highlight

VHACINKreimT Typewritten Text HIGHLIGHTED SHEETS CONTAIN HVAC SCOPE. DRAWINGS OUTLINED IN RED BOXES ARE WITHIN HVAC SCOPE. ADDITIONALLY ALL APPLICABLE DRAWING NOTES, INCLUDING "GENERAL NOTS" MAY BE WITHIN SCOPE IF THE PERTAIN TO AREAS OUTLINED IN RED BOXES.

30-HR Smoke Partition

1-HR Fire Barrier

2-HR Fire Barrier

Means of Egress

Existing Wall to Remain

New Wall

CODE LEGEND

Ante Room

B414C

Non-Hazardous Compounding

B414D

Work Station Area

B414

Hazardous Compounding

B414B

Hazardous Storage

B414A

HAC

B409

MEN

B407

WOMEN

B406

Corridor

C-4-5

Stair #4

S*4*4

Stair #3

S*4*3

Corridor

C-4-6

Corridor

C-4-1

Elevators

DN

DN

120'-6"

114'-6"

ISO CLASS 5

CLEAN ROOMS

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G

IS

E T

R

ED RA

C H

TI

E C T

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

XX

JPA Project No.

Dwg. of

4TH FLOOR COMPOUND

PHARMACY

3/13/2019

CODE DATA

G100

CVJR

18009.00

539-18-501

Cincinnati VA

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290

Chapter 39- Existing Business Occupancies:

39.1.1.1- The requirements of this chapter shall apply to existing buildings or portions thereof currently occupied as business occupancies.

39.2.2.7.- Sensor- release of electrical locking systems compling with

7.2.1.6.2 shall be permitted.

39.2.5.3- Limitations on common path of travel shall be in accordance with

39.2.5.3.1.

39.2.5.3.1.- Common path of travel shall not exceed 100 ft. on a story protected throughout by an approved automatic sprinkler system in accordance with 9.7.1.1 (1).

39.2.6- Travel distance to exits. Travel distance shall comply with 39.2.6.3 through 39.2.6.3.

39.2.6.3.- Travel distance shall not exceed 300 ft in business occupancies protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7.

39.2.9.1- Emergency lighting shall be provided in accordance with Section

7.9 in any building where any one of the following conditions exists:

(1) The building is three or more stories in height.

(2) The occupancy is subject to 100 or more occupants above or below the level of exit discharge.

(3) The occupancy is subject to 1000 or more total occupancies.

39.3.3.1 - Interior finish shall be in accordance with Section 10.2.

39.3.3.2.1 - Interior wall and ceiling finish materials complying Section 10.2.

shall be Class A or Class B in exits and in exit access corridors.

39.3.3.2.2 - Interior wall and ceiling shall be Class A, Class B, Class C in areas other than those specified in 39.3.3.2.1.

39.3.4.1 - A fire alarm system in accordance with Section 9.6 shall be provided in all business occupancies where any one of the following conditions exists:

(1) The building is three or more stories in height.

(2) The occupancy is subject to 100 or more occupants above or below the level of exist discharge.

(3) The occupancy is subject to 1,000 or more total occupants.

39.3.4.2 - Initiation of the required fire alarm system shall be by one of the following means:

(1) Manual means in accordance with 9.6.2.1(1)

(2) Approved automatic fire detection system in accordance with 9.6.2.1(2) that provides protection throughout the building and the provision of 9.6.2.6. shall apply.

(3) Approved automatic sprinkler system in accordance with 9.6.2.1. (3) that provides protection throughout the building and the provision on

9.6.2.6 shall provide.

39.3.5 - Extinguishment Requirements. Portable fire extinguishers shall be provided in every business occupancy in accordance with Section 9.9.

A. For temporay partition locations see Demolition Plans. Temporary partitions are suggested locations.Coordinate final location in field with C.O.R.

B. Verify all conditions in the field prior to fabrication, erection and construction.

C. All asbestos containing material (ACM) must be abated per the direction of the C.O.R. and project specification 017419 and local state and federal regulations. Abatement if required is to be scheduled in appropriate sequence with demolition, new construction and project phasing.

D. Coordinate phase completion and start-up with requirements as set forth by the C.O.T.R. to maintain daily operations to near as normal as possible.

E. Coordinate location of job dumpster with the C.O.R. so as to disrupt daily operations as little as possible.

F. Coordinate access to all phases of construction, deliveries, and debris removal with the C.O.R. See General Requirements.

G. Temporary door locations and sizes are as required by the General Contractor. Doors will interfere with daily operations as little as possible. Confirm all locations with the C.O.R.

H. Existing HVAC, medical gases, sprinklers and water supply to be maintained throughout as required during each phase of construction.Coordinate phasing with Mechanical and Plumbing contractor. Support and protect all lines during each phase of construction. See MEP Drawings.

J. Provide and maintain negative air pressure at all construction.

Coordinate with HVAC contractor. See HVAC plans for temporary venting requirements and duct locations.

K. Temporary partition to structural deck above. See A601 for temporary partition type.

L. Existing power must be maintained throughout as required during each phase of construction. Coordinate phasing with Electrical Contractor. Coordinate power turnover with requirements as dictated by the C.O.R. See Electrical Drawings.

M. Coordinate sequence construction with C.O.R. so that only one side of any corridor in use is obstructed at any one time.

N. Coordinate all work involving the generation of excessive noise so as to occur during non-peak operating hours, 1000 to 1600 daily.

Activities to occur during this time include, but are not limited to saw cutting, jack hammering, hammer drilling and core drilling. If there is any question as to whether an operation should occur during this time the Contractor will contact the C.O.R.

GENERAL CONSTRUCTION NOTES

Scale: 1/8" = 1'-0"

CODE PLAN - 4th FLOOR

2018 NFPA 101 Life Safety Code Review

Building 1, 4th Floor: Compound Pharmacy Space = 606 SF

Chapter 6- Classification of Occupancy and Hazard of Content

6.1.11 Business: Existing - No Change

6.2.2. Hazard Classification: Ordinary - No change

Chapter 7- Means of Egress: No Change

7.3.1 Occupant Load of Space:

Pharmacy = 606 SF (business / 50 x 606)= 12 max occupants

Chapter 8- Features of Fire Protection: No Change

Chapter 9- Building Service and Fire Protection Equipment: No Change

Chapter 10- Interior Finish, Contents, and Furnishes

10.2.3.1 - Interior wall and Ceiling Finish Materials tested in accordance with

NFPA 286.

10.2.3.1 - Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286 and comply with 10.2.3.2.

10.2.3.1.2 - Materials tested in accordance with 10.2.3.1.1 and complying with 10.2.3.2 shall be considered also to comply with the requirements of Class A, Class B, or Class C in accordance with 10.2.3.3.

(1) During the 40 kW expsure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

(3) Flashover, as described in NFPA 286, shall not occur.

(4) The peak heat release rate throughout the test shall not exceed 800 kW.

(5) For new installations, the total smoke released through-out the test shall not exceed 1000 m2.

10.2.3.3 - Wall and ceiling- Classifications characteristics.

(1) Class A: Flame Spread: 0-25; Smoke Dev. : 0-450.

(2) Class B: Flame Spread: 26-75; Smoke Dev. : 0-450

(3) Class C: Flame Spread: 76-200; Smoke Dev. : 0-450

10.2.7.3 - Interior Floor Finish- Shall be classified based on NFPA 253 or

ASTEM E 648.

10.2.3.4.- Interior Floor- Classifications Characteristics:

(1) Class I: Rad Flux: Fin .45 W/CM2

(2) Class II: Rad Flux: Fin .22 W/CM2, and max. .45 W/cm2

10.2.8.1- Wall and Ceiling finishes, where sprinkled:

Class C permitted in any location where Class B is req’d.

Class B permitted in any location where Class A is req’d.

10.2.8.2.- Floor Finishes, where sprinkled:

Class II permitted in any location where Class I is req’d.

No critical Rad. Flux permitted in any location where Class II is req’d.

CODE NOTES

Revisions Date

2 DD Submittal 12-20-2018

1 SD Submittal 11-16-2018

2.01

2.01

2.01

2.02

2.02

2.03

2.04

2.05

2.05

2.05

2.06 2.06

2.07 2.072.07

2.072.07

2.082.08

2.09

2.09

TYP. TYP.

2.10

2.11

2.10

2.11

2.12 2.132.14

TYP. TYP.TYP.

AF101

2.16

2.15

2.15

Ante Room

B414C

Non-Hazardous Compounding

B414D

Work Station Area

B414Hazardous Storage

B414A

Hazardous Compounding

B414B

B414A

B414C

B414D B141B

B414

Corridor

C-4-5

4 1/4" 1'-0" 4 1/4" 15'-10 7/8" 4 7/8" 9'-2 1/4" 4 7/8" 9'-0 3/4" 4 1/4" 10 1/2"

4 7/8" 9'-10" 4 7/8"

1'-7 3/4"

5'-0" 11" 7'-0" 3'-2 7/8" 3'-0" 1'-10" 3'-0"

1'-7 1/2"

/4

/8

/8

/8

/8

4" 3'-10"

A B B

S2.0 S2.0

S5.1

S2.0

S2.0

S2.0

S2.0

S4.0

S2.0

8.10

8.108.10

8.14

8.14

8.15

8.098.09

8.09

AF101

AF101

C

A

C

B

S5.2S5.2 S5.2

S5.0

S5.1

D

S5.2 8.14

8.14 8.148.14

B414A

B414B

B414C B414D

B414

9.13

9.13 9.13

9.13

TYP.

TYP. TYP.

TYP.

9' - 0"

9' - 0"

9' - 0" 9' - 0"

9' - 0"

8.18

8.18

8.18

8.18

REFLECTED CEILING PLAN LEGEND

Supply Air Diffuser

Return Air Grille

2' x 4' fluorescent

2' x 2' acoustical tile ceiling

Gypsum board / portland cement plaster ceiling / soffit - painted

Ceiling Access Panel

DEMO LEGEND

Wall to be Demolished

Existing Wall to Remain

New Wall

S1.0

FLOOR SLAB

FIN. CEILING

STRUCTURE ABOVE

4 7/8"

9.219.21

9.02

9.80

7.82

10'-0" AFF

7'-4" AFF

T.O. OPENING

9.16

S2.0

9.21

9.02

7.13

7.82

7.82

7.16

4 1/4"

9.80

@ EXTERIOR

WALL LOCATIONS

@ EXTERIOR

WALL LOCATIONS

@ INTERIOR

WALL LOCATIONS

S4.0

7.82

7.82

9.02

9.21

9.80

4 1/4"

4 7/8"

9.219.21

9.02

9.17

7.82

S5.0

4 1/4"

9.02

9.02

9.17

7.82

S5.1

3 1/8"

9.21

9.01

9.17

7.82

S5.2

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G

IS

E T

R

ED RA

C H

TI

E C T

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

XX

JPA Project No.

Dwg. of

4TH FLOOR COMPOUND

PHARMACY

3/13/2019

FLOOR PLANS

A101

CVJR

18009.00

539-18-501

Cincinnati VA

GENERAL DEMOLITION NOTES

A. Remove all existing partitions shown with dashed line. Repair wall and floor finishes to match adjacent surfaces at areas of removal or scheduled new surfaces as required.

B. Remove all existing borrowed lights, doors and hollow metal frames where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner.

C. Remove wall-hung toilet room accessories and medical equipment as required and turn over to Owner.

D. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.

E. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of area to be remodeled shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.T.R.

F. Repair existing walls to match adjacent undisturbed wall where cabinets, countertops, etc. are shown to be removed.

G. Prepare walls and floor slabs as required to receive new fininsh materials where existing finish is indicated to be removed.

H. Remove existing corner guards in areas to be remodeled.

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290

Scale: 1/4" = 1'-0"

DEMOLITION PLAN - 4TH FLOOR

Scale: 1/4" = 1'-0"

NEW WORK PLAN - 4TH FLOOR

GENERAL PLAN NOTES

A. All dimensions are taken to face of gypsum wallboard or unit masonry.

B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.

C. All wood blocking to be fire retardent treated.

D. First floor level 100'-0" equals 728'-0".

E. All partitions shall be type 'S1.0' unless noted otherwise.

Scale: 1/4" = 1'-0"

REFLECTED CEILING PLAN - 4TH FLOOR

PLAN NOTES

2.01 Remove existing wall partition

2.02 Remove existing door and frame.

2.03 Remove existing cased opening frame.

2.04 Remove existing window.

2.05 Remove existing lavatory, cap all lines.

2.06 Remove existing radiator, cap all lines.

2.07 Remove existing casework, Note: ACM in countertop mastic.

2.08 Remove existing shelving cabinets.

2.09 Remove existing wall shelving.

2.10 Remove existing flooring, Note: ACM in flooring mastic.

2.11 Remove existing ceiling tiles and grid.

2.12 All internal blinds in existing exterior windows shall be closed.

2.13 All vent openings in existing exterior windows shall be closed.

Caulk continuously around perimeter of vent opening to ensure air tight seal.

2.14 All existing roof drains lines and building utilities shall be inspected and replaced as necessary along exterior column wall bump-outs as they will not be accessible once new wall construcion is complete.

2.15 Remove existing metal stud furring and gypsum bd finish on interior side of existing cmu core corridor wall.

2.16 Cut new 3'-10"x7'-4" opening in existing corridor wall. Install new concrete bond beam at header. See door header Detail on Sheet A601.

7.13 Batt thermal wall insulation. R-11 min.

7.16 Vapor retarder. Seal all joints and penetratons.

7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.

8.09 Pass through window system with interlock feature. See

equipment schedule on Sheet AF101

8.10 4-1/2" natural anodized aluminum frame window with tempered glass.

8.14 Handwave motion sensor, install on both sides of operable sliding door jamb wall.

8.15 Card reader door lock, installed on corridor side.

8.18 Stainless steel ceiling access panel with continuous piano hinge and gasketed trim seal. Acudor Products Inc. model: ADWT 18x18

9.01 2 1/2" non-structural metal framing @ 16" o.c.

9.02 3 5/8" non-structural metal framing @ 16" o.c.

9.13 Installed coved corner molding continuous around ceiling perimeter. See Detail 1 on Sheet A601.

9.16 3 5/8" non-structural metal diagonal bracing @ 48" o.c. attached to structure above.

9.17 ClarkDietrich BM15, security metal barrier mesh attached to studs with ClarkDietrich barrier mesh clips (BM-Clip).

9.21 5/8" Type X gypsum board.

9.80 Acoustic insulation

GENERAL RCP NOTES

A. All wood blocking shall be fire retardant.

B. Light fixtures, sprinkler heads, speakers, and HVAC devices shall be located as close as possible to the center of acoustical ceiling panels.

Confirm any deviation from this with the Project Engineer.

C. See P, M, E and FP drawings for additional information regarding final information and quantites of fixtures/devices to be installed in ceiling.

D. See Electrical Drawings for lighting specifications.

E. All gypsum board ceilings to be painted EP-2 unless noted otherwise.

F. Ceiling height to be 9'-0" AFF, unless noted otherwise.

N.T.S.Scale:

WALL TYPES

@ CORRIDOR

SIDE OF WALL

Revisions Date

3 100% CD Owner Review 01-14-2019

2 DD Submittal 12-20-2018

1 SD Submittal 11-16-2018

VHACINKreimT Rectangle

VHACINKreimT Typewritten Text CONTRACTOR RESPONSIBLE FOR CEILING SUPPLY AIR DIFFUSERS AND RETURN AIR GRILLS. VA WILL INSTALL CEILING GRID, LIGHTING, ACCESS PANELS AND ACOUSTIC CEILING TILE.

SEE SCHED.

S E

E S

C H

E D

U L E

N

S E

E S

C H

E D

U L E

OF

SEE SCHEDULE

SD

breakout side

2"

SEE

SCHED. 2"

S E

E S

C H

E D

U L E

A

SEE PLAN

1/2" 1/2"

H1 J1

8.02

9.21

9.80

8.02

9.09

9.21

9.80

9.08

7.82 7.82 1/2" 1/2"

H2

SEE PLAN

J2

SEE PLAN

8.02

9.349.34

9.21

7.82

3.10

3.09

8.02

7.82

9.21

9.34

3.09

SEE PLAN

4.23

5'-0"

FINISH FLOOR

A

HAZARDOUS

COMPOUNDING

ROOM

A601

A601

A601

3'-0"

FINISH FLOOR

B

NON-HAZARDOUS

COMPOUNDING

ROOM

A601

A601

A601

9.21

9.80

7.83

SEE PLAN

9.08

6.09

9.21

9.80

6.01

9.02

9.14

1/2" 1/2"

8.26

7.83

SEE PLAN

S E

E P

L A

N

9.21

9.80

6.01

9.02

9.21

8.26

7.83

9.21

9.02

9.21

9.13

NOTE:

COVED MOLDING TO BE INSTALLED

AT CEILING PERIMETER IN ROOMS,

B414B, B414C & B414D. SEE PLAN FOR

WALL TYPE CONSTRUCTION.

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G

IS

E T

R

ED RA

C H

TI

E C T

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

XX

JPA Project No.

Dwg. of

4TH FLOOR COMPOUND

PHARMACY

3/13/2019

DOOR SCHEDULE, WINDOW &

MISCELLANEOUS DETAILS

A601 DesignerApprover

18009.00

539-18-501

Cincinnati VA

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290

DOOR SCHEDULE

DOOR

BETWEEN DOOR DESCRIPTION FRAME DESCRIPTION

FIRE

RATING

HDWE

SET REMARKSRM RM TYPE MAT'L

SIZE

TYPE MAT'L HEAD JAMB# W H T

B414 C-4-5 B414 N WD 1 3' - 6" 7' - 2" 1 3/4" A HM H2 J2 20 MIN 1 Door Lite shall have security wire mesh embedded into glazing

B414A B414 B414A N WD 1 3' - 0" 7' - 0" 1 3/4" A HM H1 J1 20MIN 2

B141B B414B B414C 2 7' - 0" 7' - 8" 4 5/8" 3 Automatic Sliding Door w/ Handwave Sensor - Assa Abloy SL500 Clean Room Door

B414C B414C B414 2 7' - 0" 7' - 8" 4 5/8" 3 Automatic Sliding Door w/ Handwave Sensor - Assa Abloy SL500 Clean Room Door

B414D B414C B414D 2 7' - 0" 7' - 8" 4 5/8" 3 Automatic Sliding Door w/ Handwave Sensor - Assa Abloy SL500 Clean Room Door

N.T.S.Scale:

DOOR TYPES

N.T.S.Scale:

FRAME TYPES

N.T.S.Scale:

H.M. FRAME DETAILS

Scale: 1/2" = 1'-0"

WINDOW TYPES

Scale: 1 1/2" = 1'-0"4

HEAD DETAIL

Scale: 1 1/2" = 1'-0"2

SILL DETAIL

Scale: 1 1/2" = 1'-0"3

JAMB DETAIL

Scale: 1 1/2" = 1'-0"1

TYP. COVE CEILING DETAIL

GENERAL DOOR NOTES:

INTERIOR WOOD DOORS:

General:

1. Provide each product from one species and manufacturer throughout project

2. Install all products according to manufacturer's instructions and requirements

3. General Requirements

- ANSI/WDMA I.S. 1A, Extra Heavy Duty

- Adhesive: Type II

- Core: Structural composite lumber

- Thickness: 1-3/4 inches u.n.o.

4. Clearances between doors and frames and floors

- Maximum 1/8 inch clearance at jambs, heads and 3/4 inch clearance at bottom

Frames:

1. Welded frames only, No knockdowns.

2. Interior Door Frames to include Hospital stops (6” high cut at 45 degrees.)

3. Do NOT grout frames solid in drywall partitions – the moisture from the grout can get into the drywall, and cause mold to grow.

Doors:

1. Typical Interior door to be solid core wood doors: Natural Birch Veneer; Rotary cut “RA100”; 1 3/4” thick; ½” Maximum under cut. Grade A Prefinished.

2. All wood doors to be minimum 20 minute rating unless otherwise noted.

3. Window lites in doors to be rectangular shaped, 4”wide by 25” high - and have a metal frame. Make sure to include painting this frame in the finish schedule.

Hardware:

1. The following items shall be of the same manufacture: mortise locksets, hinges and closers

2. Hinges: Provide only three-knuckle hinges

- Quantity: 3 hinges per door

- Size: 3'-0"W. door = 4-1/2" x 4-1/2" hinges. 3'-6"W. door = 5" x 4-1/2" hinges

3. Closers:

- Minimum 50% adjustable closing force and adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.

- Arm and brackets shall be steel, malleable iron or high strength cast iron.

- Equipped with full size metal cover.

- 1-1/2" min. piston diameter.

4. Door stops:

- Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction.

- Wall bumpers where installed, must be within 4 inches of the wall face and impact the door within the leading half of its width.

5. Kickplates:

- Shall be stainless steel, Type J100 series

6. Finishes:

- 626 or 630: all surfaces u.n.o.

- Hinges: 652 or 630

- Closers: factory applied paint finish. Dull or satin aluminum color

- Thresholds: mill finish aluminum

- Anti-microbial Coating: all hand-operated hardware shall be provided with an anti-microbial / anit-fungal coating (ASTM E2180) that consists of ionic silver (Ag+).

Silver ions surround bacterial cells, inhibiting growth of bacteria, mold and mildew.

7. Heights:

- Locksets and latch sets centerline of strike = 40-5/16 inches

- Locate all other hardware at standard commercial heights

AUTOMATIC POWER-OPERATED SLIDING DOORS:

General:

1. Source Limitations: Obtain sliding folding automatic entrances from single source from single manufacturer.

2. Electrical System Roughing-in: Coordinate layout and installation of automatic entrances with connections to power supplies and access-control system , remote activation devices, and remote monitoring systems.

Performance Requirements:

1. Air Infiltration: Maximum air leakage through fixed glazing and framing areas of 1.25 cfm/sq. ft. of fixed entrance-system area when tested according to ASTM E 283 at a minimum static-air-pressure difference of 1.57 lbf/sq. ft.

2. Opening Force: Power-Operated Doors: Not more than 50 lbf required to manually set door in motion if power fails, and not more than 15 lbf required to open door to minimum required width.

3. Entrapment-Prevention Force: Power-Operated Sliding Doors: Not more than 30 lbf required to prevent stopped door from closing.

Sliding Automatic Entrance:

1. Configuration: Single-sliding door with one sliding leaf (operable) and one sidelight (fixed)

2. Rollers: Min. of two ball-bearing roller wheels and two antirise rollers for each active leaf.

3. No Threshold to be installed

4. Activation Device: Touchless switch (Hand Wave) on each side of door to activate door operator. Adjustable detection from 4"-24" away from sensor.

5. Finish: Finish framing, door(s), and header with Class II, clear anodic finish.

6. Framing Members: Extruded aluminum, minimum 0.125 inch thick and reinforced as required to support imposed loads.

7. Glazing: Tempered safety glass

8. Joints: Fill and seal / caulk perimeter joint Controls:

1. Provide operators and controls, which include activation and safety devices, according to BHMA standards, for condition of exposure, and for long-term, maintenance-free operation under normal traffic load for type of occupancy indicated.

2. Touchless Switch: Hands-free-activation door-control switch with flat motion sensor faceplate.

3. Configuration: 2.77-by-4.56-inch (single gang) rectangular faceplate.

- Mounting: Meet ADA minimums.

- Faceplate Material: Stainless steel.

- Message: "Wave to Open" and wave symbol

4. Door Operators: Connect door operators to electrical power distribution system. Install and adjust activation and safety devices according to manufacturer's written instructions.

Installation:

1. Entrances: Install automatic entrances plumb and true in alignment with established lines and grades without warp or rack of framing members and doors. Anchor securely in place.

2. Install surface-mounted hardware using concealed fasteners to greatest extent possible.

3. Set headers, carrier assemblies, tracks, operating brackets, and guides level and true to location with anchorage for permanent support.

4. Guide Rails: Install rails according to BHMA A156.10, including Appendix A, and manufacturer's written instructions unless otherwise indicated.

Adjusting:

1. Adjust hardware, moving parts, door operators, and controls to function smoothly, and lubricate as recommended by manufacturer.

2. Adjust doors for tight closure.

DOOR HARDWARE SETS:

GENERAL LOCKSET NOTES:

1. Owner shall be responsible for providing additional information regarding these hardware sets

2. All locksets to come with blank cylinders and two (2) blank keys each. VA Locksmith will key each lockset upon project completion.

3. Locksets to be Corbin Russwin, 7 pin large format interchangeable cores (LFIC). Key way options are 59A1, 59A2, 59B1, 59B2, 59C1, 59C2, 59D1, & 59D2. Coordinate keyway type with VA Locksmith.

Handle to be “Newport” style.

4. Mortised guards are now permitted on rated doors – as long as the doors are mortised at the factory.

If surface mounted edge guards are specified for rated doors, they MUST go full height.

5. Wall stops are preferred over floor stops. All wall stops should be solid spheres, not hollow.

6. When Card Readers are called for – use an electronic lockset (in lieu of electronic strike or magnetic locks).

7. Card Reader: Door normally closed and locked. Presenting a valid credential to the reader will momentarily unlock the lock allowing access. Door to remain locked upon loss of power or activation of the fire alarm.

The request to exit feature of the lock to shunt the alarm output of the door contact. Door contact monitors whether the door is open or closed. Free egress at all times by depressing lock lever.

PLAN NOTES

3.09 Existing 4" CMU wall.

3.10 4" Concrete Lintel with #3 rebar top and bottom.

4.23 Masonry anchor.

6.01 2" x 4" wood blocking.

6.09 Wood blocking / shim

7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.

7.83 Cont. sealant each side.

8.02 Hollow metal frame.

8.26 [4-1/2"] Aluminum storefront window system.

9.02 3 5/8" non-structural metal framing @ 16" o.c.

9.08 Metal framing box header.

9.09 Double metal framing at jambs, typ.

9.13 Installed coved corner molding continuous around ceiling perimeter. See Detail 1 on Sheet A601.

9.14 Solid surface window sill trim.

9.21 5/8" Type X gypsum board.

9.34 Existing non-structural metal stud furring.

9.80 Acoustic insulation

SET #1 (Door B414)

- 2 ea. Hager Hinges Heavyweight B1168 5 x 4 ½ x US26D.

- 1 ea. Electric Hinge; 3CB1 4.5X4.5 TW4 (A8112-4 Wire Type)

- 1 ea. Electrified Storeroom Lockset - Card Reader; (F04 - Request to exit switch and fail secured). Corbin Russwin Lockset - 7 Pin;

Style NSA “Newport”’ ML2051 x US26D.

- 1 ea. Rockwood Door Edging 301 x 36” x US32D (For recessed installation - typ.)

- 1 ea. Rockwood #400 Series (wall type) Door Stop.

- 2 ea. Stainless Kickplate

- 3 ea. Silencers

- 1 ea. Closer LCN 4041P x AL

- 1 ea. Door Contact - Concealed

- 1 ea. Power Supply; Regulated, filtered, 24VDC, Amperage as req'd for Card Reader

Set #2 (Door B414A)

- 1 ½ Pr.Hager Hinges Heavyweight B1168 5 x 4 ½ x US26D.

- 1 ea. Corbin Russwin Lockset (F01) – 7 Pin; Style NSA “Newport"

ML2010 x US26D.

- 1 ea. Rockwood Door Edging 301 x 36” x US32D (For recessed installation - typ.)

- 1 ea. Rockwood #400 Series (wall type) Door Stop.

- 3 ea. Silencers

- 1 ea. Gasketing; 488S (R0E154)

- 1 ea. Power Supply; Regulated, filtered, 24VDC, Amperage as req'd for Card Reader

SET #3 (Doors B414B, B414C, B414D)

- Assa Abloy door model: SL500 Clean Room

- Overhead Concealed Full Breakout Narrow Stile Single Slide Door System

- Natural anodized aluminum finish

- Automatic operator

- Frames, doors and sidelites with Non-Shedding weatherstrip

- Emergency Breakaway - both operable and fixed doors swing open

- Motion / presence sensors (Handwave activated)

- (2) per door (one each side of door)

- Single sliding door with fixed sidelight

- (2) left hand slide opening (B414B & B414C)

- (1) right hand slide opening (B414D)

- Power Supply; see manufacturer's specifications and instructions

- 35-1/4" wide clear door opening

Revisions Date

3 100% CD Owner Review 01-14-2019

Ante Room

B414C Non-Hazardous Compounding

B414D

Work Station Area

B414Hazardous Storage

B414A

Hazardous Compounding

B414B

Corridor

C-4-5

RS

PF

PF PT

CC CC

RWPR

EHEH

EH

CS

DS

LP

SH

SH

SH

PC PCPC

BE

FC FC FC FC

12.3212.32

12.32

PL-1

RES-1

EP-1

2'-0" 5'-6" 2'-0"1'-6" 4'-6" 1'-6"

B1 B1

B414C

1 PTPF

8.14

Ante Room

B414C Non-Hazardous Compounding

B414D

Work Station Area

B414 Hazardous

Storage

B414A

Hazardous Compounding

B414B

Corridor

C-4-5

9.19

9.20

EP-1

RES-1

B

A

C

C

CS

D

8.14

8.14

B1

2'-1"

12.21

12.28

12.19

12.32

Ante Room

B414C

Non-Hazardous Compounding

B414D

Work Station Area

B414Hazardous Storage

B414A

Hazardous Compounding

B414B

B414A

B414C

B414DB141B

B414

Corridor

C-4-5

8 1/2"

/2

JOHN

A.

POE

IO

HO

FOET

A T

S

R E G

IS

E T

R

ED RA

C H

TI

E C T

Drawing Title

Approved: Project Director

Location

Building Number

Project Title

Checked DrawnDate

Project No.

Drawing Number o n e-ei g h th in ch o n e fo o t o n e-q u a rt er in ch o n e fo o t th re e-e ig h th s in c h o n e fo o t o n e-h a lf in c h o n e fo o t th re e-q u a rt er s in ch o n e fo o t o n e in c h o n e fo o t o n e a n d o n e-h a lf in ch e s o n e fo o t th re e in ch es o n e fo o t

F E

D C

B A

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

F E

D C

B A

VA Project No.

FULLY SPRINKLERED

ARCHITECT/ENGINEERS:CONSULTANTS:

Office of Construction and Facilities Management

XX

JPA Project No.

Dwg. of

4TH FLOOR COMPOUND

PHARMACY

3/13/2019

FINISH PLANS

AF101

DesignerApprover

18009.00

539-18-501

Cincinnati VA

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 | www.johnpoe.com| 937.461.3290

Scale: 1/4" = 1'-0"

EQUIPMENT / FURNITURE PLAN

EQUIPMENT SCHEDULE

R o o m

N u m b e r

T a g

D e s c ri p ti o n

M a n u fa c tu re r

M o d e l

C o u n t

S u p p lie r In s ta lle r

W id th

D e p th

H e ig h t

V o lt

A m p

E m

D a ta

R e m a rk s

Comments B414

Work Station Area

B414 FC 15" x 18" 4 on Casters

B414 LP Label Printer Zebra ZM600 1 V V 13" 19" 13" 0 X X Existing

B414 PC Worstation Computer 3 V V X X

B414 PR Multi-function Printer Lexmark CX820dtfe 1 V V 25 1/2" 23 1/8" 44 3/4" X Existing

B414 PT Pass-Thru System, Non-filtered Clean Air Products CAP18WFB-SST-12Wx12Hx12D 1

B414 RW Refrigerator - Work Station Helmer HPR125 1 V V 29 1/2" 35 1/2" 78 3/4" 115 15 X

B414 SH 24x60 Shelving Unit 1 V V 60" 24" 74" on Casters

B414A

Hazardous Storage

B414A PF Pass-Thru System - HEPA Filtered Atmos-Tech Ind. PT1212-12 1 V V 18" 12" 14"

B414A RS Refrigerator - Haz Str Helmer HPR111 1 V V 24 1/2" 24 1/2" 70 1/2" 115 15 X Existing

B414A SH 24x60 Shelving Unit 2 V V 60" 24" 74" on Casters

B414B

Hazardous Compounding

B414B CC Compound Rm Shelving Cart 1 V V 18" 24" 36" on Casters

B414B EH Class II Type A2 Biosafety Cabinet Nuaire - Labgard Air NU-543-400 2 V V 54" 31 1/2" 61" 115 X on Casters

B414B PF Pass-Thru System - HEPA Filtered Atmos-Tech Ind. PT1212-12 1 V V 18" 12" 14"

B414C

Ante Room

B414C 8.14 HS- Handwave Sensor X 2 48" A.F.F. TO

CENTERLINE

B414C BE BE - Ante Rm Bench 1 V V 30" 18" 14"

B414C CS 24x24 Clean Shelving Cart 1 V V 24" 24" 36" on Casters

B414C DS 24x24 Dirty Shelving Cart 1 V V 18" 30" 36" on Casters

B414D

Non-Hazardous Compounding

B414D CC Compound Rm Shelving Cart 1 V V 18" 24" 36" on Casters

B414D EH Class II Type A2 Biosafety Cabinet Nuaire - Labgard Air NU-543-400 1 V V 54" 31 1/2" 61" 115 X on Casters

Note:

All equipment and furniture listed in schedule above shall be verified as specified (or equal to) and coordinated with owner.

C C - CONTRACTOR FURNISHED, CONTRACTOR INSTALLED

V V - OWNER FURNISHED, OWNER INSTALLED

EQUIPMENT LEGEND

Scale: 1/2" = 1'-0"2

WORKSTATION ELEVATION

Scale: 1/4" = 1'-0"

FLOOR FINISH PLAN

Scale: 1/2" = 1'-0"1

ANTE ROOM

Scale: 1" = 1'-0"3

CASEWORK SECTIONS

PLAN NOTES

8.14 Handwave motion sensor, install on both sides of operable sliding door jamb wall.

9.19 Clean/dirty demarcation line painted on floor.

9.20 Rubber transition strip TS-1 from resinous flooring to existing corridor flooring.

12.19 Applied backsplash. Plastic laminate over 3/4" particle board.

Provided by Owner.

12.21 Plastic laminate over 3/4" particle board. Provided by Owner.

12.28 Surface mounted countertop support bracket. Provided by Owner.

12.32 Wire management grommet. Provided and coordinated by Owner.

TOILET ACCESSORIES SCHEDULE

MARK DESCRIPTION PRODUCT # MOUNTING HEIGHT COMMENTS

8.14 X 48" A.F.F. TO CENTERLINE

A LINT FREE WIPE DISPENSER BOX CLEANROOM CDW-99-W 54" A.F.F. TO TOP

B SOAP DISPENSER BY OWNER 50" A.F.F. TO TOP

C COAT HOOK BOBRICK B-6717 54" TO CENTER

D EYE WASH BY OWNER FAUCET MOUNTED

FINISH LEGEND

CODE FINISH TYPE MANUFACTURER PRODUCT / COLOR COMMENTS

CASEWORK FINISHES

PL-1 PLASTIC LAMINATE WILSONART 7919-60 AMBER CHERRY

CEILING FINISHES

EP-2 PRECATALYZED EPOXY PAINT GLIDDEN CEILING WHITE GLOSS LEVEL 1

FLOOR FINISHES

RES-1 RESINOUS FLOORING SIKA INDUSTRIAL FLOORING PURCEM 22NA, RAL 7042 TRAFFIC GREY 6" HIGH INTEGRAL COVE BASE

TS-1 TRANSITION STRIP JOHNSONITE 49 BEIGE WB

WALL FINISHES

EP-1 PRECATALYZED EPOXY PAINT GLIDDEN WATER CHESTNUT 30YY 62/127 GLOSS LEVEL 3

EP-3 PRECATALYZED EPOXY PAINT GLIDDEN MUSHROOM CAP 20YY 55/151 GLOSS LEVEL 5

ROOM FINISH SCHEDULE

ROOM # ROOM NAME FLOOR BASE

WALLS CASEWORK

CEILINGNorth South East West Cabinet Countertop

B414 Work Station Area RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - PL-1 ACT-1

B414A Hazardous Storage RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2

B414B Hazardous Compounding RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2

B414C Ante Room RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2

B414D Non-Hazardous Compounding RES-1 RES-1 EP-1 EP-1 EP-1 EP-1 - - EP-2

GENERAL INT. ELEVATION NOTES

A. All hollow metal doors and door frames to be painted EP-3.

Scale: 1/4" = 1'-0"

SIGNAGE PLAN

SIGNAGE SCHEDULE

MARK MOUNTING LOCATION

1 54" A.F.F. TO TOP

GENERAL EQUIPMENT NOTES

A. Coordinate with owner and verify owner-provided equipment.

N.T.S.Scale:

SIGNAGE DETAILS

Revisions Date

3 100% CD Owner Review 01-14-2019

A1

P1 P1OR

A1

OH

P2

B

P2

GENERAL FLOOR PLAN NOTES

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

P2 = SHEET WHERE DETAIL IS LOCATED

FIRE SUPPRESSION HAZARD CLASSIFICATION AND HAZARD

CLASSIFICATION GROUP

SECTION: 1 = SECTION DESIGNATION

P2 = SHEET WHERE DETAIL IS LOCATED

EQUIPMENT REFERENCE. LETTER DESIGNATION VARIES. REFER TO

SCHEDULES.

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK. LETTER

DESIGNATIONS REFER TO SCHEDULES.

CONNECT TO EXISTING

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH IT IS SHOWN

UNLESS NOTED OTHERWISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)

10" 10"

ELEV: 8' - 0"ELEV: 8' - 0"

TOE: 3' - 0"

BOE: 0' - 6"

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO TOP OR

BOTTOM OF EQUIPMENT, UNLESS NOTED OTHERWISE

APPROXIMATE DIMENSION ABOVE FINISHED FLOOR TO CENTERLINE

OF PIPE, UNLESS NOTED OTHERWISE

FIRE SUPPRESSION SYMBOLS

CONCEALED PENDENT SPRINKLER

FS

PIV

S

FIRE HYDRANT

FLOW SWITCH

GATE VALVE OS&Y

INSTITUTIONAL PENDENT SPRINKLER

PENDENT SPRINKLER

POST INDICATOR VALVE

RECESSED PENDENT SPRINKLER

SIDE WALL SPRINKLER

SUPERVISED VALVE

UPRIGHT SPRINKLER

PIPING SYMBOLS

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE: BULLHEAD TEE'S ARE NOT

PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOWN

ELBOW UP

EXISTING PIPE TO BE REMOVED

EXISTING PIPE TO REMAIN

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

D

R

SPECIALTY GAS SYMBOLS

AIR OUTLET - LAB TYPE

VC

VC

CARBON DIOXIDE OUTLET - HOSPITAL TYPE

MEDICAL AIR OUTLET - HOSPITAL TYPE

MEDICAL VACUUM INLET - HOSPITAL TYPE

NITROGEN OUTLET - HOSPITAL TYPE

NITROUS OXIDE OUTLET - HOSPITAL TYPE

OXYGEN OUTLET - HOSPITAL TYPE

WAGD INLET - HOSPITAL TYPE

NATURAL GAS OUTLET - LAB TYPE

VACUUM OUTLET - LAB TYPE

VACUUM CLEANING STATION - WALL

VACUUM CLEANING STATION - FLOOR

PIPING DESIGNATIONS

DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER RETURN

EXISTING PIPE TO REMAIN

EXISTING PIPE TO BE REMOVED

HOT WATER PIPE (140 DEGS. F.)

HOT WATER PIPE (180 DEGS. F.)

HOT WATER RETURN PIPE (140 DEGS. F.)

HOT WATER RETURN PIPE (180 DEGS. F.)

ARGON PIPE

COMPRESSED AIR PIPE

MEDICAL CARBON DIOXIDE PIPE

COMBINATION FIRE SUPPRESSION AND DOMESTIC

WATER SERVICE

DIESEL FUEL PIPE

SPRINKLER PIPE (DRY)

FIRE SUPPRESSION (STANDPIPE / SPRINKLER MAIN)

FIRE SERVICE

FUEL OIL FLOW LINE

FUEL OIL GAUGE LINE

FUEL OIL RETURN LINE

FUEL OIL SUPPLY LINE

NATURAL GAS PIPE

GARAGE DRAINAGE PIPE

GAS SERVICE

HYDROGEN PIPE

HELIUM PIPE

MEDICAL INSTRUMENT AIR PIPE

KITCHEN WASTE PIPE

LABORATORY COMPRESSED AIR PIPE

LABORATORY VENT PIPE

LABORATORY VACUUM PIPE

LABORATORY WASTE PIPE

MEDICAL NITROGEN PIPE

MEDICAL COMPRESSED AIR PIPE

MEDICAL-SURGICAL VACUUM PIPE

GASOLINE PIPE (NON-LEAD)

MEDICAL NITROUS OXIDE PIPE

NON-POTABLE

MEDICAL OXYGEN PIPE

(OVERFLOW) SECONDARY STORM DRAINAGE PIPE

PROPANE GAS PIPE

PUMP DISCHARGE PIPE

PRE-ACTION / DELUGE SPRINKLER PIPE

PURE WATER PIPE

SPRINKLER PIPE (WET)

SANITARY DRAINAGE PIPE

SOFT COLD WATER

SPRINKLER DRAIN PIPE

STORM DRAINAGE PIPE

FUEL TANK VENT PIPE

TRAP PRIMER DISCHARGE PIPE

TEMPERED WATER PIPE

SANITARY SEWER VENT

WASTE ANESTHESIA GAS DISPOSAL PIPE

WATER SERVICE

LV

140R

180R

AR

CA

CO2

CWS

DF

DS

F

FS

FOF

FOG

FOR

FOS

G

GD

GS

H2

HE

IA

IV

IW

LA

LV

LW

N2

MA

MV

NG

NO

NPW

O2

OD

P

PD

PS

PW

S

SAN

SCW

SD

STM

T

TP

TW

V

WAGD

WS

INDIRECT VENT PIPE

INDIRECT WASTE PIPE

K

CHECK VALVE

T

P

FOB

FOT

SHUTOFF VALVE (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

PRESSURE GAUGE

TEMPERATURE GAUGE OR THERMOMETER

UNION

CLEANOUT

STRAINER

STRAINER WITH A BLOW DOWN VALVE AND HOSE

CONNECTION

DRAIN VALVE WITH HOSE END CONNECTION

AUTOMATIC FLOW CONTROLLER WITH P/T PLUG

IN AND OUT

EXPANSION JOINT

PRESSURE REGULATING VALVE

SAFETY RELIEF VALVE. PIPE DISCHARGE AIR

GAPPED TO FLOOR DRAIN UNLESS NOTED

OTHERWISE.

PRESSURE AND TEMPERATURE TEST PLUG

TRAP PRIMER

VACUUM GAUGE WITH STOP

CLEANOUT TO GRADE OR FINISHED FLOOR

END CAP

MIXING FAUCET

PLUG

HOSE BIB

WALL HYDRANT

PLUG VALVE

SHUTOFF VALVE AND BOX

SHUTOFF VALVE ON RISER

V

VB

TP

CO

COMBINATION SHUTOFF AND BALANCING

VALVE (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

BALL VALVE, BUTTERFLY VALVE, GATE VALVE

VALVES AND FITTINGS

SOLENOID VALVE

S

P/T PRESSURE AND TEMPERATURE SAFETY RELIEF

VALVE. PIPE DISCHARGE AIR GAPPED TO FLOOR

DRAIN UNLESS NOTED OTHERWISE.

FIRE DEPARTMENT VALVE

WATER METERM

ACID VENT PIPEAV

ACID WASTE PIPEAW

ABBREVIATIONS

AAP - AREA ALARM PANEL (MEDICAL GAS)

AC - AIR COMPRESSOR OR AIR CONDITIONER

ACC - ACCESS

ACCU - AIR COOLED CONDENSING UNIT

AD - ACCESS DOOR OR AREA DRAIN

ADB - ACID DILUTION BASIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

AR - AIR RECEIVER OR ARGON

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

AV - ACID VENT

AW - ACID WASTE

BDD - BACK DRAFT DAMPER

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BT - BATHTUB

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNIT PER HOUR

BTWN - BETWEEN

CA - COMPRESSED AIR

CB - CATCH BASIN

CBD - COUNTER BALANCED BACKDRAFT DAMPER

CFCI - CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CFM - CUBIC FEET PER MINUTE

CHS - CHILLED WATER SUPPLY

CHR - CHILLED WATER RETURN

CI - CAST IRON

CK - CLINICAL SINK

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CO - CLEAN OUT

CO2 - MEDICAL CARBON DIOXIDE

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CS - CLINICAL SINK OR COLD SOFT WATER

CTR - CENTER

CU - COPPER

CW - COLD WATER

CWS - COMBINATION WATER SERVICE

OR CONDENSER WATER SUPPLY

CWR - CONDENSER WATER RETURN

D - DEPTH OR DRAIN LINE

DD - DECK DRAIN

DET - DETAIL

DF - DRINKING FOUNTAIN OR WATER COOLER

OR DIESEL FUEL

DFU - DRAINAGE FIXTURE UNIT

DI - DEIONIZED WATER

DIA - DIAMETER

DIM - DIMENSION

DN - DOWN

DS - DOWN SPOUT OR SPRINKLER (DRY)

DT - PERFORATED DRAIN TILE

DWG - DRAWING

EA - EACH

EC - ELECTRICAL CONTRACTOR (DIVISION 26)

EEW - EMERGENCY EYE WASH

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATOR

EQ - EQUAL

EQUIP - EQUIPMENT

ET - EXPANSION TANK

ETR - EXISTING TO REMAIN

ES - EMERGENCY SHOWER

EQS - EQUIPMENT SUPPLIER

EWC - ELECTRICAL WATER COOLER

EXH - EXHAUST AIR

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)

FCE - FIRE CONTROL EQUIPMENT

FCO - FLOOR CLEANOUT

FD - FLOOR DRAIN

FDC - FIRE DEPARTMENT CONNECTION

FDV - FIRE DEPARTMENT VALVE

FF - FINISHED FLOOR ELEVATION

FHC - FIRE HOSE CABINET

FLR - FLOOR

FM - FORCE MAIN

FOB - FLAT ON BOTTOM

FOF - FUEL OIL FLOW

FOG - FUEL OIL GAUGE

FOR - FUEL OIL RETURN

FOS - FUEL OIL SUPPLY

FOT - FLAT ON TOP

FPM - FEET PER MINUTE

FR - FIRE RISER

FS - FLOOR SINK OR FIRE SERVICE

FSC - FIRE SUPPRESSION CONTRACTOR (DIVISION 21)

FT - FEET

FTG - FOOTING

G - GAS OR NATURAL GAS

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES CONTRACTOR

GD - GARAGE DRAINAGE

GPM - GALLONS PER MINUTE

GS - GAS SERVICE

GW - GREASE WASTE

H2 - HYDROGEN

HB - HOSE BIBB

HC - HVAC CONTRACTOR (DIVISION 23)

HD - HUB DRAIN

HE - HELIUM

HG - REFRIGERANT HOT GAS

HP - HORSEPOWER OR HIGH POINT

HPC - HIGH PRESSURE CONDENSATE RETURN

HPS - HIGH PRESSURE STEAM SUPPLY

HPW - HIGH PURITY WATER

HPWR - HIGH PURITY WATER RETURN

HR - HOSE REEL

HT - HEAT TRACE

HTR - HEATER

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

HW - HOT WATER

HWR - HEATING HOT WATER RETURN

HWS - HEATING HOT WATER SUPPLY

IA - MEDICAL INSTRUMENT AIR

ID - INSIDE DIAMETER

INV - INVERT ELEVATION

IN - INCHES

IV - INDIRECT VENT

IW - INDIRECT WASTE

JS - JANITOR SINK

K - KITCHEN WASTE

KEC - KITCHEN EQUIPMENT CONTRACTOR

L - LENGTH

LA - LABORATORY COMPRESSED AIR

LAV - LAVATORY

LBS - POUNDS

LCW - LABORATORY COLD WATER

LEC - LABORATORY EQUIPMENT CONTRACTOR

LHW - LABORATORY HOT WATER

LHWR - LABORATORY HOT WATER RETURN

LPC - LOW PRESSURE CONDENSATE RETURN

LPS - LOW PRESSURE STEAM SUPPLY

LV - LABORATORY VACUUM OR LABORATORY VENT

LW - LABORATORY WASTE

MA - MEDICAL COMPRESSED AIR

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MB - MOP BASIN

MC - MECHANICAL CONTRACTOR (DIVISION 23)

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

MPC - MEDIUM PRESSURE CONDENSATE RETURN

MPS - MEDIUM PRESSURE STEAM SUPPLY

MU - WATER MAKE-UP

MV - MEDICAL SURGICAL VACUUM

N2 - MEDICAL NITROGEN

N/C - NORMALLY CLOSED

NG - GASOLINE (NON-LEAD)

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NO - MEDICAL NITROUS OXIDE

NOM - NOMINAL

NPW - NON-POTABLE WATER

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

02 - MEDICAL OXYGEN

OA - OUTDOOR AIR

OD - OUTSIDE DIAMETER OR OVERFLOW DRAIN

OFCI - OWNER FURNISHED CONTRACTOR

INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

P - PROPANE GAS

PC - PLUMBING CONTRACTOR (DIVISION 22)

OR PUMPED CONDENSATE RETURN

PD - PUMP DISCHARGE OR PARAPET DRAIN

PIV - POST INDICATOR VALVE

PLBG - PLUMBING

PS - PRE-ACTION/DELUGE SPRINKLER

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSV - PRESSURE SUSTAINING VALVE

PSIG - POUNDS PER SQUARE INCH GAUGE

PW - PURE WATER

RA - RETURN AIR

RAD - RADIUS

RCP - REINFORCED CONCRETE PIPE

RD - ROOF DRAIN

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RL - REFRIGERANT LIQUID

ROS - REVERSE OSMOSIS WATER SUPPLY

ROR - REVERSE OSMOSIS WATER RETURN

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTION

RV - RELIEF VALVE

S - SPRINKLER (WET)

SA - SHOCK ARRESTOR OR SUPPLY AIR

SAN - SANITARY OR SANITARY DRAIN

SCH - SCHEDULE

SCW - SOFT COLD WATER

SD - SPRINKLER DRAIN OR SUBSOIL DRAIN

SH - SHOWER

SHT - SHEET

SK - SINK

SPEC - SPECIFICATIONS

SQ - SQUARE

SR - SUPPLY RISER

SS - SANITARY STACK (SOIL OR WASTE) OR

STAINLESS STEEL

STD - STANDARD

STM - STORM OR STORM DRAINAGE

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

T - FUEL TANK VENT

TD - TRENCH DRAIN

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TF - TRAP FILLER

TP - TRAP PRIMER OR TRAP PRIMER DISCHARGE

TW - TEMPERED WATER

TYP - TYPICAL

UR - URINAL

UNO - UNLESS NOTED OTHERWISE

V - VENT OR SANITARY SEWER VENT

VAC - VACUUM

VC - VACUUM CLEANING

VCV - VACUUM CLEANING VALVE

VE - VACUUM EXHAUST

VEL - VELOCITY

VIB - VALVE IN BOX

VOL - VOLUME

VP - VACUUM PUMP

VS - VENT STACK

VTR - VENT THROUGH ROOF

VR - VENT RISER

W/ - WITH

W/0 - WITHOUT

W - WASTE

WAGD - WASTE ANESTHESIA GAS DISPOSAL

WC - WATER CLOSET

WCO - WALL CLEANOUT

WH - WALL HYDRANT OR WATER HEATER

WIV - WALL INDICATOR VALVE

WS - WATER SERVICE

YCO - YARD CLEANOUT

ZVC - ZONE VALVE CABINET

PIPE RISER

A PROVIDE A COMPLETE FIRE SUPPRESSION SPRINKLER SYSTEM

AS INDICATED ON THE DRAWINGS.

B COORDINATE WORK WITH VAMC, PHASING PLAN AND OTHER TRADES.

EACH CONTRACTOR SHALL BE RESPONSIBLE FOR OFFSETTING AND/ OR

RELOCATING SERVICES TO ACCOMMODATE NEW WORK OF

OTHER TRADES.

C VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEW PIPING

REQUIRED TO COMPLETE THIS WORK.

D ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM

OF STRUCTURE IN EXPOSED STRUCTURAL AREAS) UNLESS OTHERWISE

INDICATED.

E THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRE

SUPPRESSION SPRINKLER SYSTEM SHALL BE FOR A WET PIPE SYSTEM

HYDRAULICALLY CALCULATED FOR A:

1 LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER

SPRINKLER WITH THE DENSITY OF 0.10 GPM/ SQ. FT. OVER THE

MOST REMOTE 1500 SQ. FT. PROVIDE AN ADDITION OF 100 GPM

HOSE ALLOWANCE.

2 ALL MECHANICAL, ELECTRICAL AND SIMILAR SPACE AREAS SHALL

BE ORDINARY HAZARD (GROUP 1) LIMITED TO A MAXIMUM OF

130 SQ. FT. PER SPRINKLER…