087113 AUTOMATIC DOOR OPERATORS.pdf

PDF 43 KB Posted

Attached to
Z1DA--621-23-104 - Relocate Police Dispatch
Solicitation number
36C24926B0002
Issued by

About this file

This is a specification document for automatic door operators for the James H. Quillen VA Medical Center Police Dispatch Relocation project (Project Number 621 23 104). The specification establishes requirements for institutional-type swing door operators with comprehensive performance, design, control, and safety standards.

The specification requires swing door operators that move doors from fully closed to fully open position in a maximum of five seconds when speed adjustment is at maximum setting, compliant with BHMA A156.10 and UL 325 standards. Operators must feature aluminum alloy housing (ASTM B209, Type 6063-T5) measuring 112 mm wide by 140 mm high by 3.2 mm thick, completely assembled and sealed units with gear drive transmission, mechanical springs, and special lubricant for extreme temperature conditions. Power operators must include interlock mechanisms to prevent operation when doors are electrically locked, self-contained electrical control units with transformers, relays, and rectifiers, and microprocessor controls providing adjustable hold-open time (1-30 seconds), fully adjustable opening speed, LED status indications, and safety circuits that monitor obstructions. Control devices include back-lit wave activation wall switches (stainless steel, minimum 100 mm by 100 mm) with basis of design BEA MS41S or approved equal, and motion detectors with 1500 mm detection area and 25 millisecond maximum response time. Safety devices include presence sensors on the pull side of swing doors and adjustable time delay switches (3 to 60 seconds). Manufacturers must demonstrate satisfactory service on five similar installations for a minimum five years, and provide a two-year warranty against material and manufacturing defects. All operators must be from a single manufacturer with one consistent type throughout the project. Installation requires coordination with related electrical work (Division 26) and access control systems (Division 28), with training provided by manufacturer-approved instructors for a minimum of two hours.

View the file

Other files

File Type Posted
S06_Amendment 0005_621-23-104.docx DOCX document
36C24926B0002 0004.docx DOCX document
36C24926B0002 0003.docx DOCX document
Pre Bid Sign In Sheet.pdf PDF
Original Roof Drawing Building 204.pdf PDF
RFIs Project 621-23-104_Relocate Police Dispatch.pdf PDF
2026 0223_TD102 - ENLARGED PLANS_Addendum 01.pdf PDF
36C24926B0002 0002.docx DOCX document
001011 MEDICAL CENTER REQUIREMENTS 2-5-2026.pdf PDF
087100 DOOR HARDWARE.pdf PDF
36C24926B0002 0001.docx DOCX document
36C24926B0002_1.docx DOCX document
Attachment 2 Drawings.pdf PDF
Attachment 3 Wage Determination TN20250191 12-12-2025.pdf PDF
Attachment 1 Specifications.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

James H. Quillen VA Medical Center

Relocate Police Dispatch

Project Number 621 23 104

01-01-21

AUTOMATIC DOOR OPERATORS

08 71 13 - 1

SECTION 08 71 13

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Automatic operators for swinging doors.

1.2 RELATED WORK

A. Section 08 71 00, DOOR HARDWARE: Door Hardware.

B. Division 26, ELECTRICAL: Electric General Wiring, Connections and

Equipment Requirements.

C. Division 28, ELECTRONIC SAFETY AND SECURITY: Physical Access Control

Systems.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. ASTM International (ASTM):

1. B209-14 - Aluminum and Aluminum-Alloy Sheet and Plate.

2. A1008/A1008M-20 - Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low-Alloy with Improved

Formability, Solution Hardened, and Baked Hardenable.

C. Builders Hardware Manufacturers Association (BHMA):

1. BHMA A156.10-11 - Power Operated Pedestrian Doors.

D. National Fire Protection Association (NFPA):

1. 101-15 - Life Safety Code.

E. Underwriters Laboratories (UL):

1. 325-13 - Standard for Doors, Drapery, Gate, Louver, and Window

Operators and Systems.

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Show size, configuration, and fabrication and installation details.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Installation instructions.

3. Warranty.

08 71 13 - 2

D. Sustainable Construction Submittals:

1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.

E. Test reports: Certify each product complies with specifications.

F. Qualifications: Substantiate qualifications comply with specifications.

G. Operation and Maintenance Data:

1. Care instructions for each exposed finish product.

2. Start-up, maintenance, troubleshooting, emergency, and shut-down instructions for each operational product.

1.5 QUALITY ASSURANCE

A. Manufacturer’s Qualifications:

1. Regularly manufactures specified products.

2. Manufactured specified products with satisfactory service on five similar installations for minimum five years.

a. Provide contact names and addresses for completed projects when requested by Contracting Officer's Representative.

B. Installer’s Qualifications: Experienced installer, approved by the manufacturer.

1.6 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

B. Manufacturer's Warranty: Warrant automatic door operators against material and manufacturing defects.

1. Warranty Period: Two years.

PART 2 - PRODUCTS

2.1 SYSTEM PERFORMANCE

A. Comply with requirements of BHMA A156.10. Provide operators that move doors from fully closed to fully opened position in five seconds maximum time interval, when speed adjustment is at maximum setting.

B. Equipment: Conforming to UL 325. Provide key operated power disconnect wall switch for each door installation.

C. Electrical Wiring, Connections and Equipment: Motors, starters, controls, associated devices, and interconnecting wiring required for installation. Equipment and wiring as specified in Division 26, ELECTRICAL.

08 71 13 - 3

2.2 PRODUCTS - GENERAL

A. Provide door operators from one manufacturer.

B. Provide one type of operator throughout project.

C. Sustainable Construction Requirements:

1. Steel Recycled Content: 30 percent total recycled content, minimum.

2. Aluminum Recycled Content: 80 percent total recycled content, minimum.

2.3 SWING DOOR OPERATORS

A. General:

1. Type: Institutional type.

2. Size: As recommended by manufacturer for door weight and sizes.

B. Function:

1. Provide operators, enclosed in housing, permitting opening of door by energizing motor and stopped by electrically reducing Voltage and stalling motor against mechanical stop.

2. Door to close by means of spring energy, and closing force controlled by gear system and motor being used as dynamic brake without power or controlled by hydraulic closer in electro-hydraulic operators.

3. Opening and Closing Speeds: Field adjustable.

4. Operators with checking mechanism providing cushioning action at last part of door travel, in both opening and closing cycle.

5. Operators capable of recycling doors instantaneously to full open position from any point in closing cycle when control switch is activated.

6. When automatic power is interrupted or shut-off, permit doors to easily open manually without damage to automatic operator system.

C. Connect hardware with drive arm attached to door with pin linkage rotating in a self-lubricating bearing. Prevent doors from pivoting on shaft of operator.

D. Operator Housing:

1. ASTM B209, Type 6063-T5 aluminum alloy, 112 mm (4-1/2 inches) wide by 140 mm (5.5 inches) high by 3.2 mm (0.125 inch) thick, aluminum extrusions with enclosed end caps for application to 100 mm

(4 inches) and larger frame systems.

E. Power Operator:

08 71 13 - 4

1. Completely assembled and sealed unit including gear drive transmission, mechanical spring and bearings, located in aluminum case and filled with special lubricant for extreme temperature conditions. Rubber mounted units with provisions for easy maintenance and replacement, without removing door from pivots or frame.

F. Motors:

1. Provide with interlock to prevent operation when doors are electrically locked from opening.

G. Electrical Control:

1. Self-contained electrical control unit, including necessary transformers, relays, rectifiers, and other electronic components for proper operation and switching of power operator.

2. Connecting Harnesses: Interlocking plugs.

H. Accessories:

1. Metal mounting supports, brackets and other accessories necessary for installation of operators at head of door frames.

I. Microprocessor Controls:

1. Multi-function microprocessor control providing adjustable hold open time (1-30 seconds) with fully adjustable opening speed, LED indications for sensor input signals and operator status and power assist close options. Control capable of receiving activation signals from any device with normally open dry contact output.

2. Hold doors held open by low Voltage applied to the continuous duty motor.

3. Controls:

a. Adjustable safety circuit that monitors door operation and stops opening direction of door if obstruction is sensed.

b. Recycle feature that reopens door if obstruction is sensed at any point during closing cycle.

c. Standard three position key switch with functions for ON, OFF, and HOLD OPEN, mounted on operator enclosure, door frame, or wall, as indicated on drawings.

2.4 POWER UNITS

A. Self-contained, electric operated and independent of door operator.

1. Capacity and size of power circuits according to automatic door operator manufacturer's specifications and Division 26 - ELECTRICAL.

08 71 13 - 5

2.5 DOOR CONTROLS

A. Control Devices: BHMA A156.10; control opening and closing functions.

B. Open doors when control device is actuated; hold doors in open positions; then, close doors after an adjustable time period, unless safety device or reactivated control interrupts operation.

C. Manual Controls:

1. Back-lit Wave Activation Wall Switch: Recessed type, stainless steel wave plate minimum 100 mm by 100 mm (4 inch by 4 inch), with 13 mm

(l/2 inch) high letters "To Operate Door-Wave" engraved on face of plate. Basis of Design: BEA BACK LIT WAVE ACTIVATION SWITCHES

MS41S or approved equal.

D. Motion Detector:

1. Mounting: Surface or concealed.

2. Detection Area: 1500 mm (60 inches) deep and 1500 mm (60 inches) across, plus or minus 150 mm (6 inches).

3. Response Time: 25 milliseconds, maximum.

4. Control Power: 24 Volt DC.

5. Design units to be unaffected by cleaning material, solvents, dust, dirt and outdoor weather conditions.

2.6 SAFETY DEVICES

A. Swing Doors: Install presence sensor on pull side of door to detect any person standing in door swing path and prevent door from opening.

1. Time delay Switches: Adjustable between 3 to 60 seconds and control closing cycle of doors.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

1. Verify door opening is correctly sized and within acceptable tolerances.

B. Protect existing construction and completed work from damage.

3.2 INSTALLATION

A. Install products according to manufacturer's instructions and approved submittal drawings.

08 71 13 - 6

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Coordinate door installation with other related work.

C. Install manual controls and power disconnect switches recessed or semi-flush mounted in partitions.

D. Secure operator components to adjacent construction with suitable fastenings.

E. Conceal conduits, piping, and electric equipment, in finish work.

F. Install power units.

1. Where units are mounted on walls, provide metal supports or shelves for units.

2. Ensure equipment, including time delay switches, are accessible for maintenance and adjustment.

G. Ensure operators are adjusted and function properly for type of expected traffic.

H. Synchronize each leaf of pair doors to open and close simultaneously.

Permit each door leaf to be opened manually, independent of other door leaf.

I. Install controls at positions shown and ensuring convenience for expected traffic.

J. Push Plate Wall Switches Mounting Height: 1000 mm (40 inches) maximum, unless otherwise approved by Contracting Officer's Representative.

3.3 DEMONSTRATION AND TRAINING

A. Instruct VA personnel in proper automatic door operator operation and maintenance.

1. Trainer: Manufacturer approved instructor.

2. Training Time: 2 hours minimum.

B. Coordinate instruction to VA personnel with VA Contracting Officer's

Representative.

- - E N D - -