This is a Door Hardware specification section for the James H. Quillen VA Medical Center Police Dispatch Relocation project (Project 621 23 104, dated 03-01-24). The specification establishes comprehensive requirements for all door hardware and related items necessary for complete installation and operation of doors throughout the project.

The specification requires hardware compliance with ABAAS (Architectural Barriers Act Accessibility Standards), the International Building Code (IBC), NFPA 80 and NFPA 101 standards, and UL listings where applicable. Key hardware components include: butt hinges (three-knuckle type, with stainless steel for high-humidity areas); continuous hinges per ANSI/BHMA A156.26 Grade 1-600; overhead closers conforming to ANSI A156.4 Grade 1 with 50 percent adjustable closing force and adjustable hydraulic back-check; door stops per ANSI A156.16; overhead stops and holders per ANSI A156.8; mortise and cylindrical locks per ANSI standards with removable core cylinders; keys stamped with change numbers; protective plates (kick plates, mop plates, armor plates) per ANSI A156.6; and miscellaneous hardware including access door locks. Hardware finishes must conform to ANSI A156.18, with finishes 626 or 630 as standard, stainless steel (630) for exterior/high-humidity applications, and all hand-operated hardware must include anti-microbial/anti-fungal coating per ASTM E2180. Warranty periods are two years for general items, five years for locks and panic hardware, and ten years for door closers and continuous hinges. The specification includes five detailed hardware sets (1.0–5.0) for specific door types (L024C, L024, L024D, L032, L024B) with electric strikes, automatic door operators, card readers, and related access control components furnished by other sections or trades. Installation must follow specified hardware heights, hinge requirements by door dimensions, and include preinstallation meetings, final inspection with re-adjustment, and demonstration of all mechanical and electrical hardware systems.

View the file

Other files

File Type Posted
S06_Amendment 0005_621-23-104.docx DOCX document
36C24926B0002 0004.docx DOCX document
36C24926B0002 0003.docx DOCX document
2026 0223_TD102 - ENLARGED PLANS_Addendum 01.pdf PDF
36C24926B0002 0002.docx DOCX document
Pre Bid Sign In Sheet.pdf PDF
Original Roof Drawing Building 204.pdf PDF
RFIs Project 621-23-104_Relocate Police Dispatch.pdf PDF
001011 MEDICAL CENTER REQUIREMENTS 2-5-2026.pdf PDF
36C24926B0002 0001.docx DOCX document
087113 AUTOMATIC DOOR OPERATORS.pdf PDF
36C24926B0002_1.docx DOCX document
Attachment 2 Drawings.pdf PDF
Attachment 1 Specifications.pdf PDF
Attachment 3 Wage Determination TN20250191 12-12-2025.pdf PDF
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

James H. Quillen VA Medical Center

Relocate Police Dispatch

Project Number 621 23 104

03-01-24

DOOR HARDWARE

08 71 00 - 1

SECTION 08 71 00

PART 1 - GENERAL

1.1 DESCRIPTION

Door hardware and related items necessary for complete installation and operation of doors.

1.2 RELATED WORK

Caulking: Section 07 92 00 JOINT SEALANTS.

Application of Hardware: Section 08 14 00, WOOD DOORS Section 08 11 13, HOLLOW METAL DOORS AND FRAMES, Section 08 34 53, SECURITY DOORS AND

FRAMES

Painting: Section 09 91 00, PAINTING.

Card Readers: Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS.

Electrical: Division 26, ELECTRICAL.

Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

All hardware shall comply with ABAAS, (Architectural Barriers Act

Accessibility Standard) unless specified otherwise.

Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).

Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.

Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

The following items shall be of the same manufacturer, except as otherwise specified:

1. Mortise locksets.

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

08 71 00 - 2

4. Exit devices.

5. Floor closers.

1.4 WARRANTY

Subject to the terms of FAR Clause 52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latch sets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

1.5 MAINTENANCE MANUALS

In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled

"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6 copies of the schedule per Section

01 33 23. Submit 2 final copies of the final approved schedules to VAMC

Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).

Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:

Hardware

Item

Quantity Size Reference

Publication

Type No.

Finish Mfr.

Name and

Catalog

No.

Key

Control

Symbols

UL Mark

(if fire rated and listed)

ANSI/BHMA

Finish

Designation

Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers

Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.

08 71 00 - 3

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.

1.7 DELIVERY AND MARKING

Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to

COR for reference purposes. Tag shall identify items by Project

Specification number and manufacturer's catalog number. These items shall remain on file in COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.

1.8 PREINSTALLATION MEETING

Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and

Hardware Manufacturer’s Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

08 71 00 - 4

1.9 INSTRUCTIONS

Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist of letters (e.g., "HW") followed by a number.

Each number designates a set of hardware items applicable to a door type.

Keying: Keying information shall be furnished at a later date by the

COR.

1.10 APPLICABLE PUBLICATIONS

The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

ASTM International(ASTM):

F883-13.................Padlocks

E2180-18................Standard Test Method for Determining the

Activity of Incorporated Antimicrobial Agent(s)

In Polymeric or Hydrophobic Materials

American National Standards Institute/Builders Hardware Manufacturers

Association (ANSI/BHMA):

A156.1-06...............Butts and Hinges

A156.2-03...............Bored and Pre-assembled Locks and Latches

A156.3-08...............Exit Devices, Coordinators, and Auto Flush Bolts

A156.4-08...............Door Controls (Closers)

A156.5-14...............Cylinders and Input Devices for Locks.

A156.6-05...............Architectural Door Trim

A156.8-05...............Door Controls-Overhead Stops and Holders

A156.11-14..............Cabinet Locks

A156.12-05 .............Interconnected Locks and Latches

A156.13-05..............Mortise Locks and Latches Series 1000

A156.14-07 .............Sliding and Folding Door Hardware

A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical

A156.16-08..............Auxiliary Hardware

A156.17-04 .............Self-Closing Hinges and Pivots

08 71 00 - 5

A156.18-06..............Materials and Finishes

A156.20-06 .............Strap and Tee Hinges, and Hasps

A156.21-09..............Thresholds

A156.22-05..............Door Gasketing and Edge Seal Systems

A156.23-04..............Electromagnetic Locks

A156.24-03..............Delayed Egress Locking Systems

A156.25-07 .............Electrified Locking Devices

A156.26-06..............Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.29-07 .............Exit Locks and Alarms

A156.30-03 .............High Security Cylinders

A156.31-07 .............Electric Strikes and Frame Mounted Actuators

A156.36-10..............Auxiliary Locks

A250.8-03...............Standard Steel Doors and Frames

National Fire Protection Association (NFPA):

80-10...................Fire Doors and Other Opening Protectives

101-09..................Life Safety Code

Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

Architectural Barriers Act Accessibility Standards (ABAAS)

PART 2 - PRODUCTS

2.1 BUTT HINGES

ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.

Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.

Provide quantity and size of hinges per door leaf as follows:

1. Doors up to 1210 mm (4 feet) high: 2 hinges.

08 71 00 - 6

2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm

(4-1/2 inches x 4-1/2 inches) hinges.

5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

7. Provide heavy-weight hinges where specified.

8. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.

See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 CONTINUOUS HINGES

ANSI/BHMA A156.26, Grade 1-600.

1. Listed under Category N in BHMA's "Certified Product Directory."

General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete

Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a

Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.

1. Base Metal for Interior Hinges: Steel.

2. Base Metal for Hinges for Fire-Rated Assemblies: Steel.

3. Provide with non-removable pin (hospital tip option) at lockable outswing doors.

4. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.

5. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.

6. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.

08 71 00 - 7

7. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.

2.3 DOOR CLOSING DEVICES

Closing devices shall be products of one manufacturer.

2.4 OVERHEAD CLOSERS

Conform to ANSI A156.4, Grade 1.

Closers shall conform to the following:

1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.

2. Where specified, closer shall have hold-open feature.

3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.

4. Material of closer body shall be forged or cast.

5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.

6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.

7. Closers shall have full size metal cover; plastic covers will not be accepted.

8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.

9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.

10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.

08 71 00 - 8

11. Provide parallel arm closers with heavy duty rigid arm.

12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.

13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.

14. All closers shall have a 1 ½” (38mm) minimum piston diameter.

2.5 DOOR STOPS

Conform to ANSI A156.16.

Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.

Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.

Provide floor stops (Type L02141 or L02161) in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.

Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.

Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.

Omit stops where floor mounted door holders are required and where automatic operated doors occur.

Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.

Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.

Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.

08 71 00 - 9

Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.

Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).

2.6 OVERHEAD DOOR STOPS AND HOLDERS

Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.

2.7 LOCKS AND LATCHES

Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type. Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.

In addition to above requirements, locks and latches shall comply with following requirements:

1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets, except on designated doors in Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel.

No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension.

Lock function F02 shall be furnished with emergency tools/keys for

08 71 00 - 10 emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.

2. Cylindrical Lock andLatch Sets: levers shall meet ADA (Americans with

Disabilities Act) requirements. Cylindrical locksets shall be series

4000 Grade I. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design. Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position.

(This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)

2.8 KEYS

Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks

100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

2.9 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

Conform to ANSI Standard A156.6.

Provide protective plates as specified below:

1. Kick plates, mop plates and armor plates of metal, Type J100 series.

2. Provide kick plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Kick plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all

08 71 00 - 11

4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.

3. Kick plates are not required on following door sides:

a. Armor plate side of doors;

b. Exterior side of exterior doors;

c. Closet side of closet doors;

d. Both sides of aluminum entrance doors.

4. Armor plates for doors are listed under Article "Hardware Sets".

Armor plates shall be thickness as noted in the hardware set, 875 mm

(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.

5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.

6. Provide stainless steel edge guards where so specified at wood doors.

Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.

08 71 00 - 12

2.10 MISCELLANEOUS HARDWARE

Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):

Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur,.

2.11 FINISHES

Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.

626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.

Miscellaneous Finishes:

1. Hinges interior doors: 652 or 630.

2. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.

3. Cover plates for floor hinges and pivots: 630.

4. Other primed steel hardware: 600.

Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces.

Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.

Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.

2.12 BASE METALS

Apply specified U.S. Standard finishes on different base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

08 71 00 - 13

Finish Base Metal

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.

Hardware Heights from Finished Floor:

1. Exit devices centerline of strike (where applicable) 1024 mm (40-5/16 inches).

2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).

3. Deadlocks centerline of strike 1219 mm (48 inches).

4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.

5. Centerline of door pulls to be 1016 mm (40 inches).

6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.

7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.

8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.

3.2 INSTALLATION

Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. Where closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws. Door opening force shall not exceed 22.2 N (5 pounds) maximum in accordance with ABAAS. Measure and adjust opening force for all doors equipped with closers.

Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

08 71 00 - 14

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

35 mm (1-3/8 inch)

(hollow core wood doors)

Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)

Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by

COR. Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.

Hinges Required Per Door:

Door Description Number butts

Doors 1500 mm (5 ft) or less in height 2 butts

Doors over 1500 mm (5 ft) high and not over 2280 mm

(7 ft 6 in) high

3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Dutch type doors 4 butts

Doors with spring hinges 1370 mm (4 feet 6 inches) high or less

2 butts

Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts

Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.

After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements.

(All keys, Master Key level and above shall be sent Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of

08 71 00 - 15 locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.

3.3 FINAL INSPECTION

Installer to provide letter to VA COR that upon completion, installer has visited the Project and has accomplished the following:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.4 DEMONSTRATION

Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of COR and VA Locksmith.

3.5 HARDWARE SETS

Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings. Door hardware must comply with Appendix B of PSRDM where applicable.

Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.

ELECTRIC HARDWARE ABBREVIATIONS LEGEND:

ADO = Automatic Door Operator

EMCH = Electro-Mechanical Closer-Holder

MHO = Magnetic Hold-Open (wall- or floor-mounted)

INTERIOR SINGLE DOORS

08 71 00 - 16

Hardware Sets

Set: 1.0

Doors: L024C

Continuous Hinge

(A51031BxHGxAS)

1200-600XHD 32D HA

1 Office Lock

45H7L3J-VIN

626 BE

1 Overhead Stop (C01541) 1ADJ-X36 652 RF

1 Kick Plate (J102) K1050 12" BEV CSK US32D RO

1 Mop Plate (J103) K1050 6" BEV CSK US32D RO

1 Edge Guard (J208M / J211) 310B / 302B US32D RO

3 Silencer (L03011) 608 RO

Notes:

Mop plate at in swinging doors only.

Edge guard at wood doors only.

Stone threshold by other trades.

Set: 2.0

Doors: L024

3 Hinge, Full Mortise, Hvy Wt T4A3786 4-1/2” x 4-1/2” US26D MK

1 Storeroom Lock 45H7D-3H

1 Interchangeable Core (E09241) Match Facility Standard 26 MC

1 Electric Strike (E09391) 1600-CDB 630 HS

1 SMART Pac Bridge Rectifier 2005M3 HS

1 Automatic Opener FURNISHED IN OTHER SECTION

1 Door Switch FURNISHED IN OTHER SECTION

1 Kick Plate (J102) K1050 12" BEV CSK US32D RO

08 71 00 - 17

1 Floor Stop (L02121) 470 US26D RO

1 Edge Guard (J208M / J211) 310B / 302B US32D RO

3 Silencer (L03011) 608 RO

1 Frame Harness QC-C1500P MK

1 Card Reader BY SECURITY INTEGRATOR

1 Pushbutton PB4L Series SU

1 Power Supply BPS-24-_ YA

Notes: Door typically closed and locked.

From Entrance Side: Utilize push button at dispatch desk to release electric strike and initiate auto door operator sequence allowing entry.

From Dispatch Side: Utilize door switch to release strike and initiate auto door operator sequence. In case of fire alarm or power loss, strike will remain engaged (fail secure). Free egress at all times.

Interconnect Door L024 with L2024D

Automatic door operator and controls by section 08 71 13 Automatic Door

Operators.

Power transfer for reactivation sensor wiring (reactivation sensors provided by section 08 71 13).

Card reader by division 28.

Set: 3.0

Doors: L024D

3 Hinge, Full Mortise, Hvy Wt T4A3786 4-1/2” x 4-1/2” US26D MK

1 Electric Strike (E09391) 1600-CDB 630 HS

1 SMART Pac Bridge Rectifier 2005M3 HS

08 71 00 - 18

1 Automatic Opener FURNISHED IN OTHER SECTION

1 Door Switch FURNISHED IN OTHER SECTION

1 Kick Plate (J102) K1050 12" BEV CSK US32D RO

1 Floor Stop (L02121) 470 US26D RO

1 Edge Guard (J208M / J211) 310B / 302B US32D RO

3 Silencer (L03011) 608 RO

1 Frame Harness QC-C1500P MK

1 Card Reader BY SECURITY INTEGRATOR

From Corridor Side: Presenting valid credential will momentarily release electric strike and initiate auto door operator sequence allowing entry.

From Entrance Side: Utilize door switch to release strike and initiate auto

Interconnect Door L024 with L2024D

Power transfer for reactivation sensor wiring (reactivation sensors provided

Set: 4.0

Doors: L032

3 Hinge, Full Mortise, Hvy Wt T4A3786 4-1/2” x 4-1/2” US26D MK

08 71 00 - 19

1 Electric Strike (E09391) 1600-CDB 630 HS

1 Automatic Opener FURNISHED IN OTHER SECTION

1 Door Switch FURNISHED IN OTHER SECTION

1 Armor Plate (J101) K1050 35" BEV CSK US32D RO

1 Floor Stop (L02121) 470 US26D RO

1 Edge Guard (J208M / J211) 310B / 302B US32D RO

3 Silencer (L03011) 608 RO

1 Frame Harness QC-C1500P MK

From Corridor Side: Presenting valid credential will momentarily release electric strike and initiate auto door operator sequence allowing entry.

From Entrance Side: Utilize door switch to release strike and initiate auto

Power transfer for reactivation sensor wiring (reactivation sensors provided

Set: 5.0

Doors: L024B

3 Hinge, Full Mortise, Hvy Wt T4A3786 4-1/2” x 4-1/2” US26D MK

1 Electric Power Transfer CEPT-10 630 SU

1 Fail Secure Lock 45HW7DEU-3H 626 BE

Surface Closer (C02011 /

C02021)

R 8501 M / PR 8501 M 626 NO

08 71 00 - 20

1 Kick Plate (J102) K1050 12" BEV CSK US32D RO

1 Edge Guard (J208M / J211) 310B / 302B US32D RO

3 Silencer (L03011) 608 RO

1 Frame Harness QC-C1500P MK

1 Door Harness QC-C___ MK

1 Position Switch (E08) DPS-M-BK SU

Notes: Door typically closed and locked. Presenting valid credential will momentarily release lever allowing entry. In case of fire alarm or power loss door will remain locked (fail secure). Free egress at all times.

120VAC, power, conduit, and wiring by division 26.

- - - E N D - - -