Sousley Combined Data Files.pdf
PDF 14 MB Posted
- Solicitation number
- 36C24923Q0376
About this file
This federal contract opportunity solicitation seeks electrical maintenance, inspection, testing, and arc-flash services for the Lexington Veterans Affairs Medical Center Troy Bowling and Franklin R. Sousley campuses. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is soliciting proposals under solicitation number 36C24923Q0376 to provide these services. Offerors should submit proposals by the deadline specified in the solicitation to be considered for award. The selected contractor will be responsible for performing all required electrical maintenance, inspections, testing, and arc-flash work at the two specified VA medical campuses for the period of performance defined in the solicitation documents.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24923Q0376 0003.docx | DOCX document | |
| 36C24923Q0376 0002.docx | DOCX document | |
| Sousley-LEESTOWN MAP.pdf | ||
| BowlingTriennial Test List of Equipment.xlsx | XLSX spreadsheet | |
| Cooper-Bowling OneLine Drawings.pdf | ||
| Bowling Arc Flash Study Volume 2.pdf | ||
| Bowling VA Electrical Maintenance and Testing Report.pdf | ||
| Sousley - Leestown Combined Test Report.pdf | ||
| 36C24923Q0376 0001.docx | DOCX document | |
| Bowling Arc Flash Coordination Short Circuit Studies Volume 1_1.pdf | ||
| Sousley VA Arc Flash Study - 2021_1.pdf | ||
| Bowling VA Electrical Maint _ Testing Report _ Summary.pdf | ||
| Sousley Diagram EP001 4-23-20.pdf | ||
| 36C24923Q0376_1.docx | DOCX document |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Arc Flash Hazard AnalysesArc Flash Hazard Analyses
CoverCover
Submitted by
Veterans Affairs Medical Center Sousley Division
Lexington, Kentucky
Contract No. VA36C24920P0633
Contracting Officer: Michael Brown
Phone No: (615)225-5975
Jerry M. Parks Jr., Project Manager
Project Report - Volume 2
September 2020 – March 2021
845 Long Branch Circle
Sugar Hill, Georgia 30518
P - (678)546-9393, F – (678)828-5903
337 Sundance Trail
Liberty Hill, Texas 78642
P - (512)484-5594 in cooperation with
Slocum & Associates
Arc Flash Hazard Analyses Volume 2
Contract No. VA36C24920P0633
Veterans Affairs Medical Center – Sousley Division
Lexington, Kentucky September 2020 – March 2021
Section 1 Equipment Data Files (by building)
Table of Contents
Arc Flash Hazard Analyses, Contract No. 36C24920P0633 VA Medical Center – Sousley Division - Lexington, Kentucky
Equipment Data Schedules
Enclosed are the data schedules for each piece of equipment evaluated under this arc flash hazard analyses. Data schedules have been grouped by location. Each major group is separated by a red divider page to distinguish the groups.
The groups are categorized as follows:
Building 1
Building 2
Building 3
Building 4
Building 9
Building 12
Building 16
Building 17
Building 20
Building 22
Building 25
Building 27
Building 29
Building 32
Building 37
Building 39
Building 46
Building 47
Building 48
Building 67
Building 68
Building 74
Building 75
Building 76
Building 100
Building 112
Arc Flash Hazard Analyses, Contract No. 36C24920P0633 VA Medical Center – Sousley Division - Lexington, Kentucky
Equipment Data Schedules (Continued)
Building 117
Building 120
Building 122
Building 124
Hazmat Building
Medium Voltage Equipment
Location: Building 1
Source Load Phases Neutral Ground Phases Neutral Ground
PMT-1 MSB69 Switchboard 600 MCM 600 MCM 1/0 AWG THWN 8 8 8 50'
MSB69 MP1 DP Panel 500 MCM 500 MCM 1/0 AWG THWN 2 2 2 95'
MSB69 1LP1 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 110'
MSB69 1LP6 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 110'
MSB69 1LP11 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 130'
MSB69 1LP16 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 150'
MSB69 1LP19 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 205'
MSB69 1XP1 Panel 500 MCM 500 MCM 1/0 AWG THWN 2 2 2 240'
MSB69 Splice Box Splice Box 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 65'
Splice Box 1MCC-1 MCC 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 10'
Splice Box 1LP12 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 40'
MSB69 1MCC-2 MCC 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 215'
MSB69 1ATS-LS ATS 4/0 AWG 4/0 AWG #6 AWG THWN 1 1 1 35'
MSB69 1ATS-EM ATS 500 MCM 500 MCM #3 AWG THWN 1 1 1 30'
MSB69 1ATS-XR1E ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 25'
MSB69 2ATS/Elev 2-1 & 2-2 ATS 500 MCM 500 MCM 1/0 AWG THWN 1 1 1 25'
MSB69 69DP DP Panel 500 MCM 500 MCM 4/0 AWG THWN 3 3 3 15'
1LP1 1LP2 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 10'
1LP6 1LP7 Panel #2 AWG #2 AWG #10 AWG THWN 1 1 1 10'
1LP11 1LP10 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 10'
Not in Service 1LP16 1LP15 Panel - - - - - - - -
1LP19 1LP20 Panel #2 AWG #2 AWG #6 AWG THWN 1 1 1 10'
1LP19 1LP23 Panel #2 AWG #2 AWG #6 AWG THWN 1 1 1 65'
1XP1 T-1NR1 Disconnect Sw 4/0 AWG 4/0 AWG #8 AWG THWN 1 1 1 55'
T-1NR1 T-1NR1 LV Transformer 4/0 AWG 4/0 AWG #8 AWG THWN 1 1 1 10'
T-1NR1 1NR1 Panel 4/0 AWG 4/0 AWG #8 AWG THWN 1 1 1 10'
1XP1 T-1XR1 LV Transformer 250 kCMIL 250 kCMIL #2 AWG THWN 1 1 1 25'
T-1XR1 1XR1 Disconnect Disconnect Sw 1/0 AWG 1/0 AWG #4 AWG THWN 1 1 1 10'
1XR1 Disconnect 1XR1 Panel 1/0 AWG 1/0 AWG #4 AWG THWN 1 1 1 65'
MCC1-2 1MCC1LP Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 20'
MCC1-1 1LP25 Panel 1/0 AWG 1/0 AWG #8 AWG THWN 1 1 1 25'
MP1 1LP4 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 155'
MP1 1LP5 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 220'
Cable Schedule
Power Qty Location Equipment Type
Size Type Distance
Building 1 - TR-1 - Cables
MP1 1LP9 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 170'
MP1 1LP13 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 190'
MP1 1LP17 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 210'
Removed MP1 1LP24 Panel - - - - - - - -
MP1 1LP5A Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 250'
1LP4 1LP3 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 10'
1LP9 1LP8 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 10'
Not in Service 1LP13 1LP14 Panel - - - - - - - -
1LP17 1LP18 Panel #2 AWG #2 AWG #2 AWG THWN 1 1 1 10'
69DP 2ATS-EM ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 40'
69DP 3ATS/Elev 3-3 ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 45'
69DP 2ATS/LS ATS 1/0 AWG 1/0 AWG #6 AWG THWN 1 1 1 40'
69DP 4MCC MCC 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 510'
69DP DP4 DP Panel 250 kCMIL 250 kCMIL 1/0 AWG THWN 2 2 2 245'
DP4 4LP2 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 40'
DP4 4LP3 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 110'
DP4 4LP4 (LP4A) Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 70'
3EM (Bldg. 3) 4EMCC MCC #2 AWG #2 AWG #8 AWG THWN 1 1 1 605'
3EM (Bldg. 3) 4LP1EM (Bldg. 4) Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 590'
4LP1EM (Bldg. 4) 74LP1EM (Bldg. 74) Panel #6 AWG #6 AWG #8 AWG THWN 1 1 1 200'
4EMCC 4EMCC1 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 15'
Gen Swbd 69EMCR Switchboard 600 kCMIL 600 kCMIL 1/0 AWG THWN 2 2 2 70'
Gen Swbd 69EMLS Switchboard 500 kCMIL 500 kCMIL #3 AWG THWN 1 1 1 70'
Gen Swbd 3EMDP Switchboard 500 kCMIL 500 kCMIL 1/0 AWG THWN 1 1 1 335'
69EMCR 2ATS/EM ATS 4/0 AWG 4/0 AWG 1/0 AWG THWN 1 1 1 40'
69EMCR 3ATS/Elev 3-3 ATS 4/0 AWG 4/0 AWG 1/0 AWG THWN 1 1 1 75'
69EMCR 1ATS/EM ATS 1/0 AWG 1/0 AWG #3 AWG THWN 1 1 1 45'
69EMCR 2ATS/Elev 2-1 & 2-2 ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 50'
69EMCR ATS-XR1E ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 75'
69EMLS 2ATS/LS ATS 1/0 AWG 1/0 AWG #3 AWG THWN 1 1 1 35'
69EMLS 1ATS/LS ATS 1/0 AWG 1/0 AWG #3 AWG THWN 1 1 1 35'
Removed 69 EM 1ATS/Elev 1-1 & 1-2 ATS - - - - - - - -
69EM 1EM8 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 65'
1EM8 1EM6 Panel #6 AWG #6 AWG #8 AWG THWN 1 1 1 75'
1EM6 1EM4 Panel #6 AWG #6 AWG #10 AWG THWN 1 1 1 75'
1EMCC 1EM8 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 90'
69EM Splice Box Splice Box 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'
Splice Box Elevator 1-1 Disconnect Sw 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 30'
69EM Splice Box Splice Box 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'
Splice Box Elevator 1-2 Disconnect Sw 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 30'
2ATS/EM 2EM (Bldg. 2) Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 310'
3ATS/Elev 3-3 AP3B (Bldg. 3) Panel 3/0 AWG 3/0 AWG #3 AWG THWN 1 1 1 175'
AP3B (Bldg. 3) Elevator 3-3 VFD 3/0 AWG 3/0 AWG #3 AWG THWN 1 1 1 10'
Need to locate 2ATS/LS 2LS (Bldg. 2) Panel 1/0 AWG 1/0 AWG #1 AWG THWN 1 1 1 300'
Need to locate 2LS (Bldg. 2) 2LS1 (Bldg. 2) Panel #2 AWG #2 AWG #6 AWG THWN 1 1 1 25'
1ATS/LS 1EMLS1 Panel 1/0 AWG 1/0 AWG #6 AWG THWN 1 1 1 115'
1EMLS1 1EMLS2 Panel #6 AWG #6 AWG #10 AWG THWN 1 1 1 170'
1ATS/EM 69EM DP Panel 500 kCMIL 500 kCMIL #3 AWG THWN 1 1 1 30'
69EM 1EMCC-2 MCC 4/0 AWG 4/0 AWG #2 AWG THWN 1 1 1 215'
Need to locate 1EMCC-2 E1 Panel - 75'
69EM 1EM2 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 75'
1EM2 1ELR1 Panel #4 AWG #4 AWG #8 AWG THWN 1 1 1 175'
69EM 1EMRM30 Panel 3/0 AWG 3/0 AWG #3 AWG THWN 1 1 1 150'
1EMRM30 1EM1A Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 20'
Battery Bank 1EMRM30B Panel THWN 10'
69EM 1EM1 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 50'
69EM 1EM3 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 100'
69EM 1EM5 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 115'
69EM 1EM7 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 155'
69EM 69EM1 Panel #3 AWG #3 AWG #4 AWG THWN 1 1 1 25'
ATS-XR1E T-XR1E LV Transformer 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 20'
T-XR1E ST1 (Rm. 134) Disconnect Sw #2 AWG #2 AWG #2 AWG THWN 1 1 1 15'
2ATS/Elev 2-1 & 2-2 Splice Box Splice Box 300 kCMIL 300 kCMIL 1/0 AWG THWN 1 1 1 300'
Splice Box 2AP2A Disconnect Splice Box 300 kCMIL 300 kCMIL 1/0 AWG THWN 1 1 1 15'
2AP2A Disconnect 2AP2A Panel 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'
Splice Box 2AP2B Panel 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'
Location: Building 1 (69)
Load ID
PMT-1
Trip Device Type Entelliguard
Breaker ID Main
Frame Size 3000A
Breaker Type
ICB
Rating 3000A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SSF30G330
IAC Rating 42 kAIC
Serial No P24000306600101
CT Ratio .5X C4 1.5X 4 2X .2X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
1LP16
Frame Size 400A.
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X 1X 4
Switchboard Schedule
Main Breaker #1
Trip Device Settings (as found)
Model Spectra Voltage 208
Long Time
IAC Rating 65 kAIC Buss
(Copper or Aluminum)
3000A
Switchboard Breaker Data
Short Time Ground Fault
Range
Settings
Equipment ID MSB69
General Switchboard Data
Power Source PMT-1 Floor 1st
Manufacturer General Electric Room Bldg. 69 Vault
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Feeder Breaker #1
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Building 69 - LV Swbds
Main
Trip Device Type MVT Plus
Breaker ID
ATSXR1E
Frame Size 400A
Breaker Type
MCB
Rating 250A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 3 10X 1X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
1XP1
Frame Size 800A
Breaker Type
MCB
Rating 800A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SKLL36BD0800
IAC Rating 100 kAIC
Serial No CT Ratio 1X 3 5X 1 10X .95X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
MP1
Frame Size 800A
Breaker Type
MCB
Rating 800A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SKLL36BD800
IAC Rating 100 kAIC
Serial No CT Ratio 1X 2 7.5X 1 10X 1X 4
Feeder Breaker No. 4
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker #2
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker #3
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Trip Device Type MVT Plus
Breaker ID
1LP12
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X 1X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
1LP19
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X 1X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
1LP6
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 4X 1 10X 1X 4
Feeder Breaker No. 5
Trip Device Settings (as found)
Feeder Breaker No. 6
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 7
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Trip Device Type MVT Plus
Breaker ID
1ATS/LS
Frame Size 400A
Breaker Type
MCB
Rating 150A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X .2X 1
Load ID Main
Trip Device Type MVT Plus
Breaker ID 1ATSA/Elev 1 & 2
Frame Size 400A
Breaker Type
MCB
Rating 300A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 4 10X 1X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
69DP
Frame Size 1200A
Breaker Type
MCB
Rating 1200A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SKHB36BD1200
IAC Rating 65 kAIC
Serial No CT Ratio 1X 2 4X 1 10X 1X 4
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 10
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 9
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 8
Trip Device Settings (as found)
Trip Device Type MVT Plus
Breaker ID
1ATS/EM
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X 1X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
1LP11
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X 1X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
MCC1
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X 1X 4
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 11
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 12
Trip Device Settings (as found)
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 11
Trip Device Settings (as found)
Trip Device Type MVT Plus
Breaker ID Spare
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 8X 3 10X .2X 4
Load ID Main
Trip Device Type MVT Plus
Breaker ID
1LP1
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BD0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X 1X 4
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 13
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Feeder Breaker No. 12
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Location: Building 1 (Bldg. 69)
MSB69
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Load ID
MSB69
Trip Device Type MVT Plus
Breaker ID
DP4
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGHB36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 4X 1 10X - -
Manufacturer General Electrtic Room Bldg. 69 Main Vault
Model Spectra Voltage 208V
Switchboard Schedule
Equipment ID 69DP
General Switchboard Data
Power Source MSB69 Floor 1st
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
IAC Rating 42 kAIC Buss
(Copper or Aluminum)
1200A
Switchboard Breaker Data
Main Breaker #1
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Main Breaker #2
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
MSB69
Trip Device Type MVT Plus
Breaker ID Spare
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGH36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 1 1.5X 1 1.5X - -
Load ID
MSB69
Trip Device Type MVT Plus
Breaker ID
2ATS/EM
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGH36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 8X 1 10X - -
Load ID
MSB69
Trip Device Type MVT Plus
Breaker ID 3ATS/Elev 3-3
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles Current Time Delay Current Time Delay Current Current Time Delay
Model
SGH36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio .65X 2 6X 1 4X - -
Main Breaker #3
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Main Breaker #4
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 1
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
MSB69
Trip Device Type MVT Plus
Breaker ID
MCC4
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGH36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 6.5X 1 10X - -
Load ID
MSB69
Trip Device Type MVT Plus
Breaker ID
2ATS/LS
Frame Size 400A
Breaker Type
MCB
Rating 150A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGH36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 1.5X - -
Feeder Breaker No. 2
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 3
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Generator Panel
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Load ID Generator Panel
Trip Device Type MVT Plus
Breaker ID Spare
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGLB36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 2 7X 1 10X - -
Switchboard Schedule
Equipment ID 69EMLS
General Switchboard Data
Power Source Generator Panel Floor 1st
Main Breaker #1
Manufacturer General Electrtic Room Bldg. 69 Main Vault
Model Spectra Voltage 208V
IAC Rating 100 kAIC Buss
(Copper or Aluminum)
600A
Switchboard Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker #2
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Generator Panel
Trip Device Type MVT Plus
Breaker ID Spare
Frame Size 400A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGLB36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 2 5X 1 10X - -
Load ID Generator Panel
Trip Device Type MVT Plus
Breaker ID
1ATS/LS
Frame Size 400A
Breaker Type
MCB
Rating 150A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGLB36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 9X 1 10X - -
Load ID Generator Panel
Trip Device Type MVT Plus
Breaker ID
2ATS/LS
Frame Size 400A
Breaker Type
MCB
Rating 150A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
SGLB36BB0400
IAC Rating 65 kAIC
Serial No CT Ratio 1X 3 4X 1 10X - -
Main Breaker #3
Main Breaker #4
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 1
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Generator Panel
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Load ID Generator Panel
Trip Device Type
RG310+
Breaker ID
2ATS/EM
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Eaton
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
FDE322532
IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -
Serial No CT Ratio 225A 2s 2X Inst. - - -
Switchboard Schedule
Equipment ID 69EMCR
General Switchboard Data
Power Source Generator Panel Floor 1st
Main Breaker #1
Manufacturer Eaton Room Bldg. 69 Main Vault
Model PRL4 Voltage 208V
IAC Rating Buss
(Copper or Aluminum)
800A
Switchboard Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker #2
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Type
RG310+
Breaker ID 3ATS/Elev 3-3
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Eaton
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
FDE322532
IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -
Serial No CT Ratio 225A 2s 2X Inst. - - -
Load ID Generator Panel
Trip Device Type
KES3400LSI
Breaker ID
1ATS/EM
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Eaton
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KD3400F
IAC Rating 65 kAIC 2-8X
Serial No CT Ratio 2X Inst.
Load ID Generator Panel
Trip Device Type
RG310+
Breaker ID
ATSXR1E
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Eaton
Poles 225A
Current Time Delay Current Time Delay Current Current Time Delay
Model
FDE322532
IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -
Serial No CT Ratio 225A 2s 2X Inst. - - -
Main Breaker #3
Main Breaker #4
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Feeder Breaker No. 1
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Type
RG310+
Breaker ID 2ATS/Elev 1 &2
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Eaton
Poles 225A
Current Time Delay Current Time Delay Current Current Time Delay
Model
FDE322532
IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -
Serial No CT Ratio 225A 2s 2X Inst. - - -
Feeder Breaker No. 1
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Generators 1,2,3,4
Trip Device Type MicroLogic 5.0
Breaker ID
69EMCR
Frame Size 800A
Breaker Type
MCB
Rating 800A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
PG800
IAC Rating 50 kAIC
Serial No CT Ratio 1X 8s 4X .4s On 8X - -
Load ID Generators 1,2,3,4
Trip Device Type MicroLogic 5.0
Breaker ID
3EMDP
Frame Size 800A
Breaker Type
MCB
Rating 800A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
PG800
IAC Rating 50 kAIC
Serial No CT Ratio 1X 8s 4X .4s On 8X - -
Main Breaker #2
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker #1
Manufacturer - Room -
Model - Voltage 208V
IAC Rating - Buss
(Copper or Aluminum)
Switchboard Breaker Data
Switchboard Schedule
Equipment ID 69Gen
General Switchboard Data
Power Source Generators 1,2,3,4 Floor Outside
Generators 1,2,3,4
Trip Device Type
STR23SP
Breaker ID
69EMLS
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
DGP36400E20
IAC Rating 65 kAIC
Serial No CT Ratio 1X - 6X - - - -
Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker #3
MSB69
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
1LP5 General Electric THHQB 3 1
1LP5A General Electric THHQB 3 1
1LP17 General Electric THQD32225 3 1
1LP13 General Electric THQD32225 3 1
1LP24 General Electric THHQB 3 1
1LP9 General Electric THQD32225 3 1
Circuit ID
MCB 225A 225A 22 kAIC
22 kAIC
MCB
MCB 225A 225A 22 kAIC
225A 225A 22 kAIC
MCB 100A 100A
MCB 100A 100A 22 kAIC
MCB 100A 100A 22 kAIC
Poles AIC Rating Instantaneous
Qty Range Setting
Breaker Type Manufacturer Model Frame Size Rating
Buss
(Copper, Aluminum, Bolt On, etc)
800A
Breaker Data
Main Breaker
Branch Breaker Data
Trip Device Settings (as found)
Distribution Panel Schedule
Panel ID
MP1
General Panel Data
Power Source MSB69 Floor Ground
Manufacturer General Electric Room 3a
Model Spectra Voltage 208V
Long Time Short Time Ground Fault
Range
Settings
IAC Rating
Building 1 - TR-1 - Distribution Panels
1LP4 General Electric THQD32225 3 1MCB 225A 225A 22 kAIC
1ATS/EM
Trip Device Type
KT3400T
Breaker ID Main
Frame Size 400A
Breaker Type
MCB
Rating 400A
Inst
Manufacturer Eaton
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KDB3400W
IAC Rating 65 kAIC 5-10X
Serial No CT Ratio 10X
1EM2 Eaton BA 3 1
1EM5 Eaton BA 3 1
1EM3 Eaton BA 3 1
1EM1 Eaton BA 3 1
1ESB1 Eaton BA 3 1
1EM7 Eaton BA 3 1
MCB 50A 50A 10 kAIC
MCB 50A 50A 10 kAIC
Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 50A 50A 10 kAIC
MCB 100A 100A 10 kAIC
MCB 50A 50A 10 kAIC
Distribution Panel Schedule
Panel ID
69EM
General Panel Data
Power Source 1ATS/EM Floor 1st
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
IAC Rating 10 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
400A
Breaker Data
Main Breaker
Manufacturer Eaton Room Bldg. 69 Main Vault
Model PRL4 Voltage 208V
MCB 100A 100A 10 kAIC
Branch Breaker Data
Circuit ID Breaker Type Manufacturer Model Frame Size
Spare Eaton BA 3 1
Spare Eaton BA 3 1
69EM1 Eaton BA 3 1
1EMRM30 Eaton ED3225 3 1
Elevator 1-2 Eaton FD3150 3 1
1EMCC Eaton ED3150 3 1
Elevator 1-1 Eaton FD3150 3 1MCB 150A 150A 65 kAIC
50A 50A 10 kAIC
10 kAIC
MCB 150A 150A 65 kAIC
MCB 150A 150A
MCB 225A 225A 65 kAIC
65 kAIC
MCB 100A 100A 10 kAIC
MCB
MCB 50A 50A
1EM2
Trip Device Type T-M
Breaker ID Main
Frame Size 60A
Breaker Type
MCB
Rating 60A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
THHQB
IAC Rating 22 kAIC
Serial No CT Ratio
General Electric THHQB 1 12
Panel Schedule
Panel ID
1ELR1
General Panel Data
Power Source 1EM2 Floor 1st
Main Breaker
Manufacturer General Electric Room Rm. 138
Model QF3241CBX Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 22 kAIC
Building 1 - TR-1 - Panels
69EM
Trip Device Type T-M
Breaker ID Main
Frame Size 50A
Breaker Type
MCB
Rating 50A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
QOB
IAC Rating 10 kAIC
Serial No CT Ratio
Square D QOB 2 1
Square D QOB 1 19
Range Setting
MCB 30A 30A 10 kAIC
MCB 20A 20A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Rm. 3a
Model NQOB Voltage 208V
IAC Rating 10 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM1
General Panel Data
Power Source 69EM Floor Basement
1EMRM30
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
General Electric THHQB 3 1
General Electric THHQB 3 1
General Electric THHQB 2 2
General Electric THHQB 2 1
General Electric THHQB 2 2
General Electric THHQB 1 26
MCB 20A 20A 22 kAIC
MCB 20A 20A 22 kAIC
MCB 40A 40A 22 kAIC
MCB 30A 30A 22 kAIC
Range Setting
MCB 40A 40A 22 kAIC
MCB 30A 30A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer General Electric Room Hall by Rm. 31
Model AQF3421MTX Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Panel Schedule
Panel ID
1EM1A
General Panel Data
Power Source 1EMRM30 Floor Basement
69EM
Trip Device Type T-M
Breaker ID Main
Frame Size 100A
Breaker Type
MCB
Rating 100A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model Q1B
IAC Rating 22 kAIC
Serial No CT Ratio
1ELR1 Square D Q1B 3 1
Square D QOB 11 27
Range Setting
MCB 60A 60A 22 kAIC
MCB 20A 20A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 104
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM2
General Panel Data
Power Source 69EM Floor 1st
69EM
Trip Device Type T-M
Breaker ID Main
Frame Size 50A
Breaker Type
MCB
Rating 50A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model Q1B
IAC Rating 22 kAIC
Serial No CT Ratio
Square D QOB 1 2
Square D QOB 1 26
Range Setting
MCB 30A 30A 10 kAIC
MCB 20A 20A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 204
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM3
General Panel Data
Power Source 69EM Floor 2nd
1EM6
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Square D QOB 1 12
Range Setting
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 235
Model NOQB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM4
General Panel Data
Power Source 1EM6 Floor 2nd
69EM
Trip Device Type T-M
Breaker ID Main
Frame Size 100A
Breaker Type
MCB
Rating 100A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model Q1B
IAC Rating 22 kAIC
Serial No CT Ratio
Square D QOB 1 1
Square D QOB 1 19
Range Setting
MCB 30A 30A 22 kAIC
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 305
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM5
General Panel Data
Power Source 69EM Floor 3rd
1EM8
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
1EM4 Square D QOB 2 1
Square D QOB 1 13
Square D QOB 1 5MCB 20A 20A 10 kAIC
Range Setting
MCB 50A 50A 22 kAIC
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 336
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM6
General Panel Data
Power Source 1EM8 Floor 3rd
69EM
Trip Device Type T-M
Breaker ID Main
Frame Size 50A
Breaker Type
MCB
Rating 50A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model Q1B
IAC Rating 22 kAIC
Serial No CT Ratio
Square D QOB 2 1
Square D QOB 1 15
Square D QOB 5MCB 20A 20A 10 kAIC
Range Setting
MCB 30A 30A 22 kAIC
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Rm. 406
Model NOQB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM7
General Panel Data
Power Source 69EM Floor 4th
1EMCC
Trip Device Type T-M
Breaker ID Main
Frame Size 100A
Breaker Type
MCB
Rating 100A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
QOB
IAC Rating 10 kAIC
Serial No CT Ratio
1EM6 Square D QOB-VH 2 1
Square D QOB 1 5
Square D QOB 1 3
Square D QOB-VH 1 5
MCB 20A 20A 10 kAIC
MCB 15A 15A 22 kAIC
Range Setting
MCB 40A 40A 10 kAIC
MCB 30A 30A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Rm. 406
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EM8
General Panel Data
Power Source 1EMCC Floor 4th
1ATS/LS
Trip Device Type T-M
Breaker ID Main
Frame Size 150A
Breaker Type
MCB
Rating 150A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
THQD32150
IAC Rating 22 kAIC
Serial No CT Ratio
Pnl 1EMLS2 General Electric THHQB 3 1
General Electric THHQB 1 36
Range Setting
MCB 60A 60A 22 kAIC
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer General Electric Room Rm. 3A
Model AQF3422CTX Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
Breaker Data
Panel Schedule
Panel ID
1EMLS1
General Panel Data
Power Source 1ATS/LS Floor Basement
1EMLS2
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
General Electric THHQB 1 30
Range Setting
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer General Electric Room Mechanical Room
Model AQF3301MTX Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Panel Schedule
Panel ID
1EMLS2
General Panel Data
Power Source 1EMLS2 Floor Attic
69EM
Trip Device Type Thermal Magnetic
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KAL36225
IAC Rating 22 kAIC
Serial No CT Ratio
EM1A Square D QOB 3 1
Square D QOB 3 1
Square D QOB 3 1
Square D QOB 3 1
Square D QOB 3 1
Square D QOB 2 4
MCB 80A 80A 10 kAIC
MCB 50A 50A 10 kAIC
MCB 30A 30A 10 kAIC
MCB 20A 20A 10 kAIC
MCB 40A 40A 10 kAIC
100A 100A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Rm. 30
Model NQOD Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Panel Schedule
Panel ID
1EMRM30
General Panel Data
Power Source 69EM Floor Basement
Square D QOB 1 2
Square D QOB 1 3
MCB 30A 30A 10 kAIC
MCB 20A 20A 10 kAIC
Battery Charger
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Square D QOB 1 7
Range Setting
MCB 20A 20A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Rm. 30
Model Q08-1GL-100DS Voltage 208V
IAC Rating 10 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1EMRM30B
General Panel Data
Power Source Battery Charger Floor Basement
69EM
Trip Device Type Thermal Magnetic
Breaker ID Main
Frame Size 100A
Breaker Type
MCB
Rating 100A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
QOB
IAC Rating 10 kAIC
Serial No CT Ratio
Square D QOB 2 1
Square D QOB 1 10
Range Setting
MCB 20A 20A 10 kAIC
MCB 20A 20A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Mechanical Room
Model NQ Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1ESB1
General Panel Data
Power Source 69EM Floor Sub-Basement
Load ID
MSB69
Trip Device Type Thermal Magnetic
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KAL
IAC Rating 25 kAIC 1125-2250A
Serial No CT Ratio 1125A
Panel 1LP2 Square D Q1B 3 1
Square D Q2 3 1
Square D QOB 2 3
Square D QOB 2 3
Square D QOB 1 2MCB 30A 30A 10 kAIC
MCB 30A 30A 10 kAIC
MCB 20A 20A 10 kAIC
Range Setting
MCB 100A 100A 22 kAIC
MCB 30A 30A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Rm. 3a
Model NQOB Voltage 208V
Circuit ID
Panel Schedule
Panel ID
1LP1
General Panel Data
Power Source MSB69 Floor Basement
Main Breaker
Manufacturer Square D Room
Square D QOB 1 19
Square D QOB 1 1MCB 15A 15A 10 kAIC
MCB 20A 20A 10 kAIC
1LP11
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Square D QOB 1 26
Range Setting
MCB 20A 20A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 220
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1LP10
General Panel Data
Power Source 1LP11 Floor 2nd
MSB69
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB69
Rating 225A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KAL36225
IAC Rating 25 kAIC 1125-2250A
Serial No CT Ratio 1125A
1LP10 Square D Q1B 3 1
Square D QOB 2 5
Square D QOB 1 26MCB 20A 20A 10 kAIC
Range Setting
MCB 100A 100A 22 kAIC
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 220
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Panel Schedule
Panel ID
1LP11
General Panel Data
Power Source MSB69 Floor 2nd
MSB69
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer General Electric
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
TQD3225
IAC Rating 10 kAIC
Serial No CT Ratio
General Electric THHQBB 1 39
Range Setting
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer General Electric Room Hall by Rm. 228
Model AQF3422DBX Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Panel Schedule
Panel ID
1LP12
General Panel Data
Power Source MSB69 Floor 2nd
MP1
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KAL36225
IAC Rating 25 kAIC
Serial No CT Ratio
Square D QOB 2 1
Square D QOB 1 32
Range Setting
MCB 30A 30A 22 kAIC
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 231
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Panel Schedule
Panel ID
1LP13
General Panel Data
Power Source MP1 Floor 2nd
Load ID Trip Device Type
Breaker ID Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Panel Schedule
Panel ID 1LP14 (Not in Service)
General Panel Data
Power Source Floor 2nd
Main Breaker
Manufacturer Square D Room Hall by Rm. 231
Model Voltage
IAC Rating Buss
(Copper, Aluminum, Bolt On, etc)
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
Breaker ID Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Panel Schedule
Panel ID 1LP15 (Not in Service)
General Panel Data
Power Source Floor 3rd
Main Breaker
Manufacturer Square D Room Hall by Rm. 321
Model Voltage
IAC Rating Buss
(Copper, Aluminum, Bolt On, etc)
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MSB69
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KAL36225
IAC Rating 25 kAIC
Serial No CT Ratio
Square D QOB 3 1
Square D QOB 1 1
Square D QOB 1 27
Square D QOB 1 1
Panel Schedule
Panel ID
1LP16
General Panel Data
Power Source MSB69 Floor 3rd
Main Breaker
Manufacturer Square D Room Hall by Rm. 321A
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 100A 100A 22 kAIC
MCB 30A 30A 22 kAIC
MCB 20A 20A 22 kAIC
MCB 20A 20A 10 kAIC
MP1
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KAL36225
IAC Rating 25 kAIC
Serial No CT Ratio
Pnl 1LP18 Square D QOB 3 1
Square D QOB 1 1
Square D QOB 1 29
Square D QOB 1 1
Panel Schedule
Panel ID
1LP17
General Panel Data
Power Source MP1 Floor 3rd
Main Breaker
Manufacturer Square D Room Hall by Rm. 333A
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
NCB 100A 100A 22 kAiC
NCB 50A 50A 22 kAiC
NCB 20A 20A 22 kAiC
NCB 20A 20A 10 kAIC
1LP17
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Square D QOB 1 2
Panel Schedule
Panel ID
1LP18
General Panel Data
Power Source 1LP17 Floor 3rd
Main Breaker
Manufacturer Square D Room Hall by Rm. 333A
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty Range Setting
MCB 20A 20A 10 kAIC
MSB69
Trip Device Type T-M
Breaker ID Main
Frame Size 225A
Breaker Type
MCB
Rating 225A
Inst
Manufacturer Square D
Poles
Current Time Delay Current Time Delay Current Current Time Delay
Model
KAL36225
IAC Rating 25 kAIC
Serial No CT Ratio
Pnl 1LP23 Square D QOB 3 1
Pnl 1LP20 Square D QOB 3 1
Square D QOB 2 3
Square D QOB 2 2
Square D QOB 1 12
Square D QOB 1 13
Panel Schedule
Panel ID
1LP19
General Panel Data
Power Source MSB69 Floor 4th
Main Breaker
Manufacturer Square D Room Hall by Rm. 421
Model NOQB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
225A
Breaker Data
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
QtyCircuit ID Range Setting
MCB 100A 100A 22 kAIC
MCB 100A 100A 22 kAIC
MCB 30A 30A 22 kAIC
MCB 20A 20A 22 kAIC
MCB 20A 20A 10 kAIC
MCB 20A 20A 22 kAIC
1LP1
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Square D QOB 1 27
Square D QOB 1 3
Range Setting
MCB 20A 20A 10 kAIC
MCB 30A 30A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Rm. 3a
Model NQOB Voltage 208V
IAC Rating Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1LP2
General Panel Data
Power Source 1LP1 Floor Basement
1LP19
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Square D QOB 1 25
Square D QOB 1 1
Range Setting
MCB 20A 20A 22 kAIC
MCB 20A 20A 10 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Hall by Rm. 421
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1LP20
General Panel Data
Power Source 1LP19 Floor 4th
1LP19
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Square D QOB 2 3
Square D QOB 1 10
Square D QOB 1 2MCB 20A 20A 10 kAIC
Range Setting
MCB 20A 20A 10 kAIC
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Rm. 502
Model NQOB Voltage 208V
IAC Rating 65 kAIC Buss
(Copper, Aluminum, Bolt On, etc)
100A
Breaker Data
Panel Schedule
Panel ID
1LP23
General Panel Data
Power Source 1LP19 Floor 5th
Breaker ID Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
Range Setting
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Square D Room Crawl Space
Model Voltage
IAC Rating Buss
(Copper, Aluminum, Bolt On, etc)
Breaker Data
Panel Schedule
Panel ID 1LP24 (Removed)
General Panel Data
Power Source Floor Sub-Basement
MCC1-1
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
General Electric THQB 3 3
General Electric THHQB 3 1
General Electric THHQB 1 9MCB 20A 20A 22 kAIC
Range Setting
MCB 20A 20A 22 kAIC
MCB 15A 15A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
Trip Device Settings (as found)
Long Time Short Time Ground Fault
Range
Settings
Main Breaker
Manufacturer Geneal Eelctric Room Rm. 12
Model AQF3241MTX Voltage 208V
IAC Rating Buss
(Copper, Aluminum, Bolt On, etc)
125A
Breaker Data
Panel Schedule
Panel ID
1LP25
General Panel Data
Power Source MCC1-1 Floor Basement
1LP4
Trip Device Type
Breaker ID
MLO
Frame Size
Breaker Type Rating Inst
Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay
Model IAC Rating
Serial No CT Ratio
General Electric THHQB 1 30
Range Setting
MCB 20A 20A 22 kAIC
Branch Breaker Data
Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous
Qty
T…