This federal contract opportunity solicitation seeks electrical maintenance, inspection, testing, and arc-flash services for the Lexington Veterans Affairs Medical Center Troy Bowling and Franklin R. Sousley campuses. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is soliciting proposals under solicitation number 36C24923Q0376 to provide these services. Offerors should submit proposals by the deadline specified in the solicitation to be considered for award. The selected contractor will be responsible for performing all required electrical maintenance, inspections, testing, and arc-flash work at the two specified VA medical campuses for the period of performance defined in the solicitation documents.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Arc Flash Hazard AnalysesArc Flash Hazard Analyses

CoverCover

Submitted by

Veterans Affairs Medical Center Sousley Division

Lexington, Kentucky

Contract No. VA36C24920P0633

Contracting Officer: Michael Brown

Phone No: (615)225-5975

Jerry M. Parks Jr., Project Manager

Project Report - Volume 2

September 2020 – March 2021

845 Long Branch Circle

Sugar Hill, Georgia 30518

P - (678)546-9393, F – (678)828-5903

337 Sundance Trail

Liberty Hill, Texas 78642

P - (512)484-5594 in cooperation with

Slocum & Associates

Arc Flash Hazard Analyses Volume 2

Contract No. VA36C24920P0633

Veterans Affairs Medical Center – Sousley Division

Lexington, Kentucky September 2020 – March 2021

Section 1 Equipment Data Files (by building)

Table of Contents

Arc Flash Hazard Analyses, Contract No. 36C24920P0633 VA Medical Center – Sousley Division - Lexington, Kentucky

Equipment Data Schedules

Enclosed are the data schedules for each piece of equipment evaluated under this arc flash hazard analyses. Data schedules have been grouped by location. Each major group is separated by a red divider page to distinguish the groups.

The groups are categorized as follows:

Building 1

Building 2

Building 3

Building 4

Building 9

Building 12

Building 16

Building 17

Building 20

Building 22

Building 25

Building 27

Building 29

Building 32

Building 37

Building 39

Building 46

Building 47

Building 48

Building 67

Building 68

Building 74

Building 75

Building 76

Building 100

Building 112

Arc Flash Hazard Analyses, Contract No. 36C24920P0633 VA Medical Center – Sousley Division - Lexington, Kentucky

Equipment Data Schedules (Continued)

Building 117

Building 120

Building 122

Building 124

Hazmat Building

Medium Voltage Equipment

Location: Building 1

Source Load Phases Neutral Ground Phases Neutral Ground

PMT-1 MSB69 Switchboard 600 MCM 600 MCM 1/0 AWG THWN 8 8 8 50'

MSB69 MP1 DP Panel 500 MCM 500 MCM 1/0 AWG THWN 2 2 2 95'

MSB69 1LP1 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 110'

MSB69 1LP6 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 110'

MSB69 1LP11 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 130'

MSB69 1LP16 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 150'

MSB69 1LP19 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 205'

MSB69 1XP1 Panel 500 MCM 500 MCM 1/0 AWG THWN 2 2 2 240'

MSB69 Splice Box Splice Box 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 65'

Splice Box 1MCC-1 MCC 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 10'

Splice Box 1LP12 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 40'

MSB69 1MCC-2 MCC 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 215'

MSB69 1ATS-LS ATS 4/0 AWG 4/0 AWG #6 AWG THWN 1 1 1 35'

MSB69 1ATS-EM ATS 500 MCM 500 MCM #3 AWG THWN 1 1 1 30'

MSB69 1ATS-XR1E ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 25'

MSB69 2ATS/Elev 2-1 & 2-2 ATS 500 MCM 500 MCM 1/0 AWG THWN 1 1 1 25'

MSB69 69DP DP Panel 500 MCM 500 MCM 4/0 AWG THWN 3 3 3 15'

1LP1 1LP2 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 10'

1LP6 1LP7 Panel #2 AWG #2 AWG #10 AWG THWN 1 1 1 10'

1LP11 1LP10 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 10'

Not in Service 1LP16 1LP15 Panel - - - - - - - -

1LP19 1LP20 Panel #2 AWG #2 AWG #6 AWG THWN 1 1 1 10'

1LP19 1LP23 Panel #2 AWG #2 AWG #6 AWG THWN 1 1 1 65'

1XP1 T-1NR1 Disconnect Sw 4/0 AWG 4/0 AWG #8 AWG THWN 1 1 1 55'

T-1NR1 T-1NR1 LV Transformer 4/0 AWG 4/0 AWG #8 AWG THWN 1 1 1 10'

T-1NR1 1NR1 Panel 4/0 AWG 4/0 AWG #8 AWG THWN 1 1 1 10'

1XP1 T-1XR1 LV Transformer 250 kCMIL 250 kCMIL #2 AWG THWN 1 1 1 25'

T-1XR1 1XR1 Disconnect Disconnect Sw 1/0 AWG 1/0 AWG #4 AWG THWN 1 1 1 10'

1XR1 Disconnect 1XR1 Panel 1/0 AWG 1/0 AWG #4 AWG THWN 1 1 1 65'

MCC1-2 1MCC1LP Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 20'

MCC1-1 1LP25 Panel 1/0 AWG 1/0 AWG #8 AWG THWN 1 1 1 25'

MP1 1LP4 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 155'

MP1 1LP5 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 220'

Cable Schedule

Power Qty Location Equipment Type

Size Type Distance

Building 1 - TR-1 - Cables

MP1 1LP9 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 170'

MP1 1LP13 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 190'

MP1 1LP17 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 210'

Removed MP1 1LP24 Panel - - - - - - - -

MP1 1LP5A Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 250'

1LP4 1LP3 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 10'

1LP9 1LP8 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 10'

Not in Service 1LP13 1LP14 Panel - - - - - - - -

1LP17 1LP18 Panel #2 AWG #2 AWG #2 AWG THWN 1 1 1 10'

69DP 2ATS-EM ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 40'

69DP 3ATS/Elev 3-3 ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 45'

69DP 2ATS/LS ATS 1/0 AWG 1/0 AWG #6 AWG THWN 1 1 1 40'

69DP 4MCC MCC 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 510'

69DP DP4 DP Panel 250 kCMIL 250 kCMIL 1/0 AWG THWN 2 2 2 245'

DP4 4LP2 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 40'

DP4 4LP3 Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 110'

DP4 4LP4 (LP4A) Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 70'

3EM (Bldg. 3) 4EMCC MCC #2 AWG #2 AWG #8 AWG THWN 1 1 1 605'

3EM (Bldg. 3) 4LP1EM (Bldg. 4) Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 590'

4LP1EM (Bldg. 4) 74LP1EM (Bldg. 74) Panel #6 AWG #6 AWG #8 AWG THWN 1 1 1 200'

4EMCC 4EMCC1 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 15'

Gen Swbd 69EMCR Switchboard 600 kCMIL 600 kCMIL 1/0 AWG THWN 2 2 2 70'

Gen Swbd 69EMLS Switchboard 500 kCMIL 500 kCMIL #3 AWG THWN 1 1 1 70'

Gen Swbd 3EMDP Switchboard 500 kCMIL 500 kCMIL 1/0 AWG THWN 1 1 1 335'

69EMCR 2ATS/EM ATS 4/0 AWG 4/0 AWG 1/0 AWG THWN 1 1 1 40'

69EMCR 3ATS/Elev 3-3 ATS 4/0 AWG 4/0 AWG 1/0 AWG THWN 1 1 1 75'

69EMCR 1ATS/EM ATS 1/0 AWG 1/0 AWG #3 AWG THWN 1 1 1 45'

69EMCR 2ATS/Elev 2-1 & 2-2 ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 50'

69EMCR ATS-XR1E ATS 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 75'

69EMLS 2ATS/LS ATS 1/0 AWG 1/0 AWG #3 AWG THWN 1 1 1 35'

69EMLS 1ATS/LS ATS 1/0 AWG 1/0 AWG #3 AWG THWN 1 1 1 35'

Removed 69 EM 1ATS/Elev 1-1 & 1-2 ATS - - - - - - - -

69EM 1EM8 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 65'

1EM8 1EM6 Panel #6 AWG #6 AWG #8 AWG THWN 1 1 1 75'

1EM6 1EM4 Panel #6 AWG #6 AWG #10 AWG THWN 1 1 1 75'

1EMCC 1EM8 Panel #2 AWG #2 AWG #8 AWG THWN 1 1 1 90'

69EM Splice Box Splice Box 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'

Splice Box Elevator 1-1 Disconnect Sw 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 30'

69EM Splice Box Splice Box 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'

Splice Box Elevator 1-2 Disconnect Sw 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 30'

2ATS/EM 2EM (Bldg. 2) Panel 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 310'

3ATS/Elev 3-3 AP3B (Bldg. 3) Panel 3/0 AWG 3/0 AWG #3 AWG THWN 1 1 1 175'

AP3B (Bldg. 3) Elevator 3-3 VFD 3/0 AWG 3/0 AWG #3 AWG THWN 1 1 1 10'

Need to locate 2ATS/LS 2LS (Bldg. 2) Panel 1/0 AWG 1/0 AWG #1 AWG THWN 1 1 1 300'

Need to locate 2LS (Bldg. 2) 2LS1 (Bldg. 2) Panel #2 AWG #2 AWG #6 AWG THWN 1 1 1 25'

1ATS/LS 1EMLS1 Panel 1/0 AWG 1/0 AWG #6 AWG THWN 1 1 1 115'

1EMLS1 1EMLS2 Panel #6 AWG #6 AWG #10 AWG THWN 1 1 1 170'

1ATS/EM 69EM DP Panel 500 kCMIL 500 kCMIL #3 AWG THWN 1 1 1 30'

69EM 1EMCC-2 MCC 4/0 AWG 4/0 AWG #2 AWG THWN 1 1 1 215'

Need to locate 1EMCC-2 E1 Panel - 75'

69EM 1EM2 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 75'

1EM2 1ELR1 Panel #4 AWG #4 AWG #8 AWG THWN 1 1 1 175'

69EM 1EMRM30 Panel 3/0 AWG 3/0 AWG #3 AWG THWN 1 1 1 150'

1EMRM30 1EM1A Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 20'

Battery Bank 1EMRM30B Panel THWN 10'

69EM 1EM1 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 50'

69EM 1EM3 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 100'

69EM 1EM5 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 115'

69EM 1EM7 Panel #2 AWG #2 AWG #4 AWG THWN 1 1 1 155'

69EM 69EM1 Panel #3 AWG #3 AWG #4 AWG THWN 1 1 1 25'

ATS-XR1E T-XR1E LV Transformer 4/0 AWG 4/0 AWG #4 AWG THWN 1 1 1 20'

T-XR1E ST1 (Rm. 134) Disconnect Sw #2 AWG #2 AWG #2 AWG THWN 1 1 1 15'

2ATS/Elev 2-1 & 2-2 Splice Box Splice Box 300 kCMIL 300 kCMIL 1/0 AWG THWN 1 1 1 300'

Splice Box 2AP2A Disconnect Splice Box 300 kCMIL 300 kCMIL 1/0 AWG THWN 1 1 1 15'

2AP2A Disconnect 2AP2A Panel 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'

Splice Box 2AP2B Panel 2/0 AWG 2/0 AWG #4 AWG THWN 1 1 1 15'

Location: Building 1 (69)

Load ID

PMT-1

Trip Device Type Entelliguard

Breaker ID Main

Frame Size 3000A

Breaker Type

ICB

Rating 3000A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SSF30G330

IAC Rating 42 kAIC

Serial No P24000306600101

CT Ratio .5X C4 1.5X 4 2X .2X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

1LP16

Frame Size 400A.

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X 1X 4

Switchboard Schedule

Main Breaker #1

Trip Device Settings (as found)

Model Spectra Voltage 208

Long Time

IAC Rating 65 kAIC Buss

(Copper or Aluminum)

3000A

Switchboard Breaker Data

Short Time Ground Fault

Range

Settings

Equipment ID MSB69

General Switchboard Data

Power Source PMT-1 Floor 1st

Manufacturer General Electric Room Bldg. 69 Vault

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Feeder Breaker #1

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Building 69 - LV Swbds

Main

Trip Device Type MVT Plus

Breaker ID

ATSXR1E

Frame Size 400A

Breaker Type

MCB

Rating 250A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 3 10X 1X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

1XP1

Frame Size 800A

Breaker Type

MCB

Rating 800A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SKLL36BD0800

IAC Rating 100 kAIC

Serial No CT Ratio 1X 3 5X 1 10X .95X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

MP1

Frame Size 800A

Breaker Type

MCB

Rating 800A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SKLL36BD800

IAC Rating 100 kAIC

Serial No CT Ratio 1X 2 7.5X 1 10X 1X 4

Feeder Breaker No. 4

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker #2

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker #3

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Trip Device Type MVT Plus

Breaker ID

1LP12

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X 1X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

1LP19

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X 1X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

1LP6

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 4X 1 10X 1X 4

Feeder Breaker No. 5

Trip Device Settings (as found)

Feeder Breaker No. 6

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 7

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Trip Device Type MVT Plus

Breaker ID

1ATS/LS

Frame Size 400A

Breaker Type

MCB

Rating 150A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X .2X 1

Load ID Main

Trip Device Type MVT Plus

Breaker ID 1ATSA/Elev 1 & 2

Frame Size 400A

Breaker Type

MCB

Rating 300A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 4 10X 1X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

69DP

Frame Size 1200A

Breaker Type

MCB

Rating 1200A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SKHB36BD1200

IAC Rating 65 kAIC

Serial No CT Ratio 1X 2 4X 1 10X 1X 4

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 10

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 9

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 8

Trip Device Settings (as found)

Trip Device Type MVT Plus

Breaker ID

1ATS/EM

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X 1X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

1LP11

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X 1X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

MCC1

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X 1X 4

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 11

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 12

Trip Device Settings (as found)

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 11

Trip Device Settings (as found)

Trip Device Type MVT Plus

Breaker ID Spare

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 8X 3 10X .2X 4

Load ID Main

Trip Device Type MVT Plus

Breaker ID

1LP1

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BD0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X 1X 4

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 13

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Feeder Breaker No. 12

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Location: Building 1 (Bldg. 69)

MSB69

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Load ID

MSB69

Trip Device Type MVT Plus

Breaker ID

DP4

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGHB36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 4X 1 10X - -

Manufacturer General Electrtic Room Bldg. 69 Main Vault

Model Spectra Voltage 208V

Switchboard Schedule

Equipment ID 69DP

General Switchboard Data

Power Source MSB69 Floor 1st

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

IAC Rating 42 kAIC Buss

(Copper or Aluminum)

1200A

Switchboard Breaker Data

Main Breaker #1

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Main Breaker #2

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

MSB69

Trip Device Type MVT Plus

Breaker ID Spare

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGH36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 1 1.5X 1 1.5X - -

Load ID

MSB69

Trip Device Type MVT Plus

Breaker ID

2ATS/EM

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGH36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 8X 1 10X - -

Load ID

MSB69

Trip Device Type MVT Plus

Breaker ID 3ATS/Elev 3-3

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles Current Time Delay Current Time Delay Current Current Time Delay

Model

SGH36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio .65X 2 6X 1 4X - -

Main Breaker #3

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Main Breaker #4

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 1

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

MSB69

Trip Device Type MVT Plus

Breaker ID

MCC4

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGH36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 6.5X 1 10X - -

Load ID

MSB69

Trip Device Type MVT Plus

Breaker ID

2ATS/LS

Frame Size 400A

Breaker Type

MCB

Rating 150A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGH36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 1.5X - -

Feeder Breaker No. 2

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 3

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Generator Panel

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Load ID Generator Panel

Trip Device Type MVT Plus

Breaker ID Spare

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGLB36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 2 7X 1 10X - -

Switchboard Schedule

Equipment ID 69EMLS

General Switchboard Data

Power Source Generator Panel Floor 1st

Main Breaker #1

Manufacturer General Electrtic Room Bldg. 69 Main Vault

Model Spectra Voltage 208V

IAC Rating 100 kAIC Buss

(Copper or Aluminum)

600A

Switchboard Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker #2

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Generator Panel

Trip Device Type MVT Plus

Breaker ID Spare

Frame Size 400A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGLB36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 2 5X 1 10X - -

Load ID Generator Panel

Trip Device Type MVT Plus

Breaker ID

1ATS/LS

Frame Size 400A

Breaker Type

MCB

Rating 150A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGLB36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 9X 1 10X - -

Load ID Generator Panel

Trip Device Type MVT Plus

Breaker ID

2ATS/LS

Frame Size 400A

Breaker Type

MCB

Rating 150A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

SGLB36BB0400

IAC Rating 65 kAIC

Serial No CT Ratio 1X 3 4X 1 10X - -

Main Breaker #3

Main Breaker #4

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 1

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Generator Panel

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Load ID Generator Panel

Trip Device Type

RG310+

Breaker ID

2ATS/EM

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Eaton

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

FDE322532

IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -

Serial No CT Ratio 225A 2s 2X Inst. - - -

Switchboard Schedule

Equipment ID 69EMCR

General Switchboard Data

Power Source Generator Panel Floor 1st

Main Breaker #1

Manufacturer Eaton Room Bldg. 69 Main Vault

Model PRL4 Voltage 208V

IAC Rating Buss

(Copper or Aluminum)

800A

Switchboard Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker #2

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Type

RG310+

Breaker ID 3ATS/Elev 3-3

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Eaton

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

FDE322532

IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -

Serial No CT Ratio 225A 2s 2X Inst. - - -

Load ID Generator Panel

Trip Device Type

KES3400LSI

Breaker ID

1ATS/EM

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Eaton

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KD3400F

IAC Rating 65 kAIC 2-8X

Serial No CT Ratio 2X Inst.

Load ID Generator Panel

Trip Device Type

RG310+

Breaker ID

ATSXR1E

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Eaton

Poles 225A

Current Time Delay Current Time Delay Current Current Time Delay

Model

FDE322532

IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -

Serial No CT Ratio 225A 2s 2X Inst. - - -

Main Breaker #3

Main Breaker #4

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Feeder Breaker No. 1

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Type

RG310+

Breaker ID 2ATS/Elev 1 &2

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Eaton

Poles 225A

Current Time Delay Current Time Delay Current Current Time Delay

Model

FDE322532

IAC Rating 65 kAIC 100-225A 2-24s 2-12X - - -

Serial No CT Ratio 225A 2s 2X Inst. - - -

Feeder Breaker No. 1

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Generators 1,2,3,4

Trip Device Type MicroLogic 5.0

Breaker ID

69EMCR

Frame Size 800A

Breaker Type

MCB

Rating 800A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

PG800

IAC Rating 50 kAIC

Serial No CT Ratio 1X 8s 4X .4s On 8X - -

Load ID Generators 1,2,3,4

Trip Device Type MicroLogic 5.0

Breaker ID

3EMDP

Frame Size 800A

Breaker Type

MCB

Rating 800A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

PG800

IAC Rating 50 kAIC

Serial No CT Ratio 1X 8s 4X .4s On 8X - -

Main Breaker #2

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker #1

Manufacturer - Room -

Model - Voltage 208V

IAC Rating - Buss

(Copper or Aluminum)

Switchboard Breaker Data

Switchboard Schedule

Equipment ID 69Gen

General Switchboard Data

Power Source Generators 1,2,3,4 Floor Outside

Generators 1,2,3,4

Trip Device Type

STR23SP

Breaker ID

69EMLS

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

DGP36400E20

IAC Rating 65 kAIC

Serial No CT Ratio 1X - 6X - - - -

Miscellaneous Information Electrical or Manual Operation? (E or M) Current Limiter Fuse Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker #3

MSB69

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

1LP5 General Electric THHQB 3 1

1LP5A General Electric THHQB 3 1

1LP17 General Electric THQD32225 3 1

1LP13 General Electric THQD32225 3 1

1LP24 General Electric THHQB 3 1

1LP9 General Electric THQD32225 3 1

Circuit ID

MCB 225A 225A 22 kAIC

22 kAIC

MCB

MCB 225A 225A 22 kAIC

225A 225A 22 kAIC

MCB 100A 100A

MCB 100A 100A 22 kAIC

MCB 100A 100A 22 kAIC

Poles AIC Rating Instantaneous

Qty Range Setting

Breaker Type Manufacturer Model Frame Size Rating

Buss

(Copper, Aluminum, Bolt On, etc)

800A

Breaker Data

Main Breaker

Branch Breaker Data

Trip Device Settings (as found)

Distribution Panel Schedule

Panel ID

MP1

General Panel Data

Power Source MSB69 Floor Ground

Manufacturer General Electric Room 3a

Model Spectra Voltage 208V

Long Time Short Time Ground Fault

Range

Settings

IAC Rating

Building 1 - TR-1 - Distribution Panels

1LP4 General Electric THQD32225 3 1MCB 225A 225A 22 kAIC

1ATS/EM

Trip Device Type

KT3400T

Breaker ID Main

Frame Size 400A

Breaker Type

MCB

Rating 400A

Inst

Manufacturer Eaton

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KDB3400W

IAC Rating 65 kAIC 5-10X

Serial No CT Ratio 10X

1EM2 Eaton BA 3 1

1EM5 Eaton BA 3 1

1EM3 Eaton BA 3 1

1EM1 Eaton BA 3 1

1ESB1 Eaton BA 3 1

1EM7 Eaton BA 3 1

MCB 50A 50A 10 kAIC

MCB 50A 50A 10 kAIC

Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 50A 50A 10 kAIC

MCB 100A 100A 10 kAIC

MCB 50A 50A 10 kAIC

Distribution Panel Schedule

Panel ID

69EM

General Panel Data

Power Source 1ATS/EM Floor 1st

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

IAC Rating 10 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Main Breaker

Manufacturer Eaton Room Bldg. 69 Main Vault

Model PRL4 Voltage 208V

MCB 100A 100A 10 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size

Spare Eaton BA 3 1

Spare Eaton BA 3 1

69EM1 Eaton BA 3 1

1EMRM30 Eaton ED3225 3 1

Elevator 1-2 Eaton FD3150 3 1

1EMCC Eaton ED3150 3 1

Elevator 1-1 Eaton FD3150 3 1MCB 150A 150A 65 kAIC

50A 50A 10 kAIC

10 kAIC

MCB 150A 150A 65 kAIC

MCB 150A 150A

MCB 225A 225A 65 kAIC

65 kAIC

MCB 100A 100A 10 kAIC

MCB

MCB 50A 50A

1EM2

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

THHQB

IAC Rating 22 kAIC

Serial No CT Ratio

General Electric THHQB 1 12

Panel Schedule

Panel ID

1ELR1

General Panel Data

Power Source 1EM2 Floor 1st

Main Breaker

Manufacturer General Electric Room Rm. 138

Model QF3241CBX Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 22 kAIC

Building 1 - TR-1 - Panels

69EM

Trip Device Type T-M

Breaker ID Main

Frame Size 50A

Breaker Type

MCB

Rating 50A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

QOB

IAC Rating 10 kAIC

Serial No CT Ratio

Square D QOB 2 1

Square D QOB 1 19

Range Setting

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Rm. 3a

Model NQOB Voltage 208V

IAC Rating 10 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM1

General Panel Data

Power Source 69EM Floor Basement

1EMRM30

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric THHQB 3 1

General Electric THHQB 3 1

General Electric THHQB 2 2

General Electric THHQB 2 1

General Electric THHQB 2 2

General Electric THHQB 1 26

MCB 20A 20A 22 kAIC

MCB 20A 20A 22 kAIC

MCB 40A 40A 22 kAIC

MCB 30A 30A 22 kAIC

Range Setting

MCB 40A 40A 22 kAIC

MCB 30A 30A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer General Electric Room Hall by Rm. 31

Model AQF3421MTX Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Panel Schedule

Panel ID

1EM1A

General Panel Data

Power Source 1EMRM30 Floor Basement

69EM

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model Q1B

IAC Rating 22 kAIC

Serial No CT Ratio

1ELR1 Square D Q1B 3 1

Square D QOB 11 27

Range Setting

MCB 60A 60A 22 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 104

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM2

General Panel Data

Power Source 69EM Floor 1st

69EM

Trip Device Type T-M

Breaker ID Main

Frame Size 50A

Breaker Type

MCB

Rating 50A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model Q1B

IAC Rating 22 kAIC

Serial No CT Ratio

Square D QOB 1 2

Square D QOB 1 26

Range Setting

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 204

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM3

General Panel Data

Power Source 69EM Floor 2nd

1EM6

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 1 12

Range Setting

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 235

Model NOQB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM4

General Panel Data

Power Source 1EM6 Floor 2nd

69EM

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model Q1B

IAC Rating 22 kAIC

Serial No CT Ratio

Square D QOB 1 1

Square D QOB 1 19

Range Setting

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 305

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM5

General Panel Data

Power Source 69EM Floor 3rd

1EM8

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

1EM4 Square D QOB 2 1

Square D QOB 1 13

Square D QOB 1 5MCB 20A 20A 10 kAIC

Range Setting

MCB 50A 50A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 336

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM6

General Panel Data

Power Source 1EM8 Floor 3rd

69EM

Trip Device Type T-M

Breaker ID Main

Frame Size 50A

Breaker Type

MCB

Rating 50A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model Q1B

IAC Rating 22 kAIC

Serial No CT Ratio

Square D QOB 2 1

Square D QOB 1 15

Square D QOB 5MCB 20A 20A 10 kAIC

Range Setting

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Rm. 406

Model NOQB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM7

General Panel Data

Power Source 69EM Floor 4th

1EMCC

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

QOB

IAC Rating 10 kAIC

Serial No CT Ratio

1EM6 Square D QOB-VH 2 1

Square D QOB 1 5

Square D QOB 1 3

Square D QOB-VH 1 5

MCB 20A 20A 10 kAIC

MCB 15A 15A 22 kAIC

Range Setting

MCB 40A 40A 10 kAIC

MCB 30A 30A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Rm. 406

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EM8

General Panel Data

Power Source 1EMCC Floor 4th

1ATS/LS

Trip Device Type T-M

Breaker ID Main

Frame Size 150A

Breaker Type

MCB

Rating 150A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

THQD32150

IAC Rating 22 kAIC

Serial No CT Ratio

Pnl 1EMLS2 General Electric THHQB 3 1

General Electric THHQB 1 36

Range Setting

MCB 60A 60A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer General Electric Room Rm. 3A

Model AQF3422CTX Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

Breaker Data

Panel Schedule

Panel ID

1EMLS1

General Panel Data

Power Source 1ATS/LS Floor Basement

1EMLS2

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric THHQB 1 30

Range Setting

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer General Electric Room Mechanical Room

Model AQF3301MTX Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Panel Schedule

Panel ID

1EMLS2

General Panel Data

Power Source 1EMLS2 Floor Attic

69EM

Trip Device Type Thermal Magnetic

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KAL36225

IAC Rating 22 kAIC

Serial No CT Ratio

EM1A Square D QOB 3 1

Square D QOB 3 1

Square D QOB 3 1

Square D QOB 3 1

Square D QOB 3 1

Square D QOB 2 4

MCB 80A 80A 10 kAIC

MCB 50A 50A 10 kAIC

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

MCB 40A 40A 10 kAIC

100A 100A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Rm. 30

Model NQOD Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Panel Schedule

Panel ID

1EMRM30

General Panel Data

Power Source 69EM Floor Basement

Square D QOB 1 2

Square D QOB 1 3

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

Battery Charger

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 1 7

Range Setting

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Rm. 30

Model Q08-1GL-100DS Voltage 208V

IAC Rating 10 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1EMRM30B

General Panel Data

Power Source Battery Charger Floor Basement

69EM

Trip Device Type Thermal Magnetic

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

QOB

IAC Rating 10 kAIC

Serial No CT Ratio

Square D QOB 2 1

Square D QOB 1 10

Range Setting

MCB 20A 20A 10 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Mechanical Room

Model NQ Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1ESB1

General Panel Data

Power Source 69EM Floor Sub-Basement

Load ID

MSB69

Trip Device Type Thermal Magnetic

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KAL

IAC Rating 25 kAIC 1125-2250A

Serial No CT Ratio 1125A

Panel 1LP2 Square D Q1B 3 1

Square D Q2 3 1

Square D QOB 2 3

Square D QOB 2 3

Square D QOB 1 2MCB 30A 30A 10 kAIC

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

Range Setting

MCB 100A 100A 22 kAIC

MCB 30A 30A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Rm. 3a

Model NQOB Voltage 208V

Circuit ID

Panel Schedule

Panel ID

1LP1

General Panel Data

Power Source MSB69 Floor Basement

Main Breaker

Manufacturer Square D Room

Square D QOB 1 19

Square D QOB 1 1MCB 15A 15A 10 kAIC

MCB 20A 20A 10 kAIC

1LP11

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 1 26

Range Setting

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 220

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1LP10

General Panel Data

Power Source 1LP11 Floor 2nd

MSB69

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB69

Rating 225A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KAL36225

IAC Rating 25 kAIC 1125-2250A

Serial No CT Ratio 1125A

1LP10 Square D Q1B 3 1

Square D QOB 2 5

Square D QOB 1 26MCB 20A 20A 10 kAIC

Range Setting

MCB 100A 100A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 220

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Panel Schedule

Panel ID

1LP11

General Panel Data

Power Source MSB69 Floor 2nd

MSB69

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer General Electric

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

TQD3225

IAC Rating 10 kAIC

Serial No CT Ratio

General Electric THHQBB 1 39

Range Setting

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer General Electric Room Hall by Rm. 228

Model AQF3422DBX Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Panel Schedule

Panel ID

1LP12

General Panel Data

Power Source MSB69 Floor 2nd

MP1

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KAL36225

IAC Rating 25 kAIC

Serial No CT Ratio

Square D QOB 2 1

Square D QOB 1 32

Range Setting

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 231

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Panel Schedule

Panel ID

1LP13

General Panel Data

Power Source MP1 Floor 2nd

Load ID Trip Device Type

Breaker ID Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Panel Schedule

Panel ID 1LP14 (Not in Service)

General Panel Data

Power Source Floor 2nd

Main Breaker

Manufacturer Square D Room Hall by Rm. 231

Model Voltage

IAC Rating Buss

(Copper, Aluminum, Bolt On, etc)

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Breaker ID Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Panel Schedule

Panel ID 1LP15 (Not in Service)

General Panel Data

Power Source Floor 3rd

Main Breaker

Manufacturer Square D Room Hall by Rm. 321

Model Voltage

IAC Rating Buss

(Copper, Aluminum, Bolt On, etc)

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MSB69

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KAL36225

IAC Rating 25 kAIC

Serial No CT Ratio

Square D QOB 3 1

Square D QOB 1 1

Square D QOB 1 27

Square D QOB 1 1

Panel Schedule

Panel ID

1LP16

General Panel Data

Power Source MSB69 Floor 3rd

Main Breaker

Manufacturer Square D Room Hall by Rm. 321A

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 100A 100A 22 kAIC

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

MCB 20A 20A 10 kAIC

MP1

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KAL36225

IAC Rating 25 kAIC

Serial No CT Ratio

Pnl 1LP18 Square D QOB 3 1

Square D QOB 1 1

Square D QOB 1 29

Square D QOB 1 1

Panel Schedule

Panel ID

1LP17

General Panel Data

Power Source MP1 Floor 3rd

Main Breaker

Manufacturer Square D Room Hall by Rm. 333A

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

NCB 100A 100A 22 kAiC

NCB 50A 50A 22 kAiC

NCB 20A 20A 22 kAiC

NCB 20A 20A 10 kAIC

1LP17

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 1 2

Panel Schedule

Panel ID

1LP18

General Panel Data

Power Source 1LP17 Floor 3rd

Main Breaker

Manufacturer Square D Room Hall by Rm. 333A

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 10 kAIC

MSB69

Trip Device Type T-M

Breaker ID Main

Frame Size 225A

Breaker Type

MCB

Rating 225A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

KAL36225

IAC Rating 25 kAIC

Serial No CT Ratio

Pnl 1LP23 Square D QOB 3 1

Pnl 1LP20 Square D QOB 3 1

Square D QOB 2 3

Square D QOB 2 2

Square D QOB 1 12

Square D QOB 1 13

Panel Schedule

Panel ID

1LP19

General Panel Data

Power Source MSB69 Floor 4th

Main Breaker

Manufacturer Square D Room Hall by Rm. 421

Model NOQB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 100A 100A 22 kAIC

MCB 100A 100A 22 kAIC

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

MCB 20A 20A 10 kAIC

MCB 20A 20A 22 kAIC

1LP1

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 1 27

Square D QOB 1 3

Range Setting

MCB 20A 20A 10 kAIC

MCB 30A 30A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Rm. 3a

Model NQOB Voltage 208V

IAC Rating Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1LP2

General Panel Data

Power Source 1LP1 Floor Basement

1LP19

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 1 25

Square D QOB 1 1

Range Setting

MCB 20A 20A 22 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Hall by Rm. 421

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1LP20

General Panel Data

Power Source 1LP19 Floor 4th

1LP19

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 2 3

Square D QOB 1 10

Square D QOB 1 2MCB 20A 20A 10 kAIC

Range Setting

MCB 20A 20A 10 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Rm. 502

Model NQOB Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

1LP23

General Panel Data

Power Source 1LP19 Floor 5th

Breaker ID Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Range Setting

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room Crawl Space

Model Voltage

IAC Rating Buss

(Copper, Aluminum, Bolt On, etc)

Breaker Data

Panel Schedule

Panel ID 1LP24 (Removed)

General Panel Data

Power Source Floor Sub-Basement

MCC1-1

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric THQB 3 3

General Electric THHQB 3 1

General Electric THHQB 1 9MCB 20A 20A 22 kAIC

Range Setting

MCB 20A 20A 22 kAIC

MCB 15A 15A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Geneal Eelctric Room Rm. 12

Model AQF3241MTX Voltage 208V

IAC Rating Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Panel Schedule

Panel ID

1LP25

General Panel Data

Power Source MCC1-1 Floor Basement

1LP4

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric THHQB 1 30

Range Setting

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

T…