This document provides details on a federal contract opportunity for electrical maintenance, inspection, testing, and arc-flash services. The solicitation number is 36C24923Q0376 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 for services at the Lexington VA Medical Center Troy Bowling and Franklin R. Sousley Campuses. The opportunity is for electrical maintenance, inspection, testing, and arc-flash services and the required services include inspection, testing, maintenance, and arc-flash studies on equipment at the two specified medical campuses. The size of the related technical file on arc-flash studies is 14MB. The award is expected to be issued by the Veterans Affairs VISN 9 office.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Arc Flash Hazard AnalysesArc Flash Hazard Analyses

CoverCover

Submitted by

Veterans Affairs Medical Center Bowling Division

Lexington, Kentucky

Contract No. VA36C24920P0633

Contracting Officer: Michael Brown

Phone No: (615)225-5975

Jerry M. Parks Jr., Project Manager

Project Report - Volume 2

September 2020 – April 2021

845 Long Branch Circle

Sugar Hill, Georgia 30518

P - (678)546-9393, F – (678)828-5903

337 Sundance Trail

Liberty Hill, Texas 78642

P - (512)484-5594 in cooperation with

Slocum & Associates

Arc Flash Hazard Analyses Volume 2

Contract No. VA36C24920P0633

Veterans Affairs Medical Center – Bowling Division

Lexington, Kentucky September 2020 – April 2021

Section 1 Equipment Data Files (by building)

Table of Contents

Arc Flash Hazard Analyses, Contract No. 36C24920P0633 VA Medical Center – Bowling Division – Lexington, Kentucky

Equipment Data Schedules

Enclosed are the data schedules for each piece of equipment evaluated under this arc flash hazard analyses. Data schedules have been grouped by location. Each major group is separated by a red divider page to distinguish the groups.

The groups are categorized as follows:

Main Hospital

▪ Life Safety Bus Duct #1

▪ Life Safety Bus Duct #2

▪ ESB2

▪ ESB3

▪ ESB4

▪ Low Voltage Switchboard Bus #1

▪ Low Voltage Switchboard Bus #2

▪ Normal Power A & B

▪ Normal Power C & D

▪ Medium Voltage Equipment

Tower Building

▪ Generator

▪ Switchboard SBA

▪ Switchboard SBB

▪ Switchboard SBC

▪ Switchboard SBD

▪ Switchboard SBE

▪ Switchboard SBF

▪ Switchboard SBG

▪ Switchboard SBH

▪ Medium Voltage Equipment

Chiller Plant

▪ Low Voltage Switchgear

▪ Medium Voltage Equipment

Location: Main Hospital - LS Bus Duct #1

Source Load Phases Neutral Ground Phases Neutral Ground

Main Swgr Bus #1 ATS-LS ATS 250 kCMIL 250 kCMIL #1 AWG THHN 2 2 2 50'

ATS-LS ESB1 Switchboard 250 kCMIL 250 kCMIL #1 AWG THHN 2 2 2 25'

ESB1 LS Bus Duct #1 Busway Busway

LS Bus Duct #1 ELP1C Disconnect Bus Disconnect Busway

ELP1C Disconnect ELP1C Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 10'

ELP1C T-EPP1C LV Transformer #4 AWG #4 AWG #6 AWG THHN 1 1 1 5'

T-EPP1C EPP1C Panel #1 AWG #1 AWG #2 AWG THHN 1 1 1 10'

LS Bus Duct #1 ELP2C Disconnect Bus Disconnect Busway

ELP2C Disconnect ELP2C Panel #3 AWG #3 AWG #8 AWG THHN 1 1 1 10'

LS Bus Duct #1 ELP3C Disconnect Bus Disconnect Busway

ELP3C Disconnect ELP3C Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 5'

ELP3C T-EPP3C LV Transformer #8 AWG #8 AWG #10 AWG THHN 1 1 1 5'

T-EPP3C EPP3C Panel #3 AWG #3 AWG #6 AWG THHN 1 1 1 10'

LS Bus Duct #1 T-EPP3D Disconnect Bus Disconnect Busway

T-EPP3D Disconnect T-EPP3D LV Transformer #6 AWG #6 AWG #6 AWG THHN 1 1 1 180'

T-EPP3D EPP3D Panel #3 AWG #3 AWG #6 AWG THHN 1 1 1 10'

LS Bus Duct #1 ELP4C Disconnect Bus Disconnect Busway

ELP4C Disconnect ELP4C Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 5'

ELP4C T-EPP4C LV Transformer #8 AWG #8 AWG #8 AWG THHN 1 1 1 25'

T-EPP4C EPP4C Panel #1 AWG #1 AWG #8 AWG THHN 1 1 1 10'

LS Bus Duct #1 ELP5C Disconnect Bus Disconnect Busway

ELP5C Disconnect ELP5C Panel #2 AWG #2 AWG #8 AWG THHN 1 1 1 10'

ELP5C T-EPP5C LV Transformer #6 AWG #6 AWG #10 AWG THHN 1 1 1 10'

T-EPP5C EPP5C Panel 350 MCM 350 MCM #4 AWG THHN 1 1 1 10'

Cable Schedule

Power Qty Location Equipment Type

Size Type Distance

LS Bus Duct #1 - Cables

Location: Main Building

Load ID ELP1C Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP1C Siemens BQD 3 1

Siemens BQD 2 1

Siemens BQD 1 12

Panel Schedule

Panel ID

ELP1C

General Panel Data

Power Source ELP1C Bus Disconnect Floor 1st Floor

Main Breaker

Manufacturer ITE Room CU100

Model CDP-7 Voltage 480V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 40A 40A 18 kAIC

MCB 50A 50A 18 kAIC

MCB 20A 20A 18 kAIC

Building 1 - TR-1 - Panels

ELP1C

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

QJH

IAC Rating 22 kAIC

Serial No CT Ratio

Siemens BQH 1 6

Siemens BQH 2 2

Siemens BQ 1 31MCB 20A 20A 22 kAIC

Range Setting

MCB 20A 20A 22 kAIC

MCB 30A 30A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Siemens Room CU100

Model CDO-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

200A

Breaker Data

Panel Schedule

Panel ID

EPP1C

General Panel Data

Power Source ELP1C Floor 1st Floor

ELP2C Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Siemens E4 1 9

Range Setting

MCB 20A 20A 18 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Ite Room C200

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

ELP2C

General Panel Data

Power Source ELP2C Bus Disconnect Floor 2nd Floor

ELP3C Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP3C Siemens E4 3 1

Siemens E4 1 9

Range Setting

MCB 35A 35A 18 kAIC

MCB 20A 20A 18 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room CU300

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

ELP3C

General Panel Data

Power Source ELP3C Bus Disconnect Floor 3rd Floor

ELP3C

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating 22 kAIC

Serial No CT Ratio

Siemens BQH 3 1

Siemens BQH 2 2

Siemens BQH 1 14

Siemens BQ 1 3

MCB 20A 20A 22 kAIC

MCB 20A 20A 10 kAIC

Range Setting

MCB 40A 40A 22 kAIC

MCB 30A 30A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room CU300

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP3C

General Panel Data

Power Source ELP3C Floor 3rd Floor

EPP3D Bus Disc

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating

Serial No CT Ratio

Siemens BQH 2 1

Siemens BQ 2 2

Siemens BQH 1 16MCB 20A 20A 22 kAIC

Range Setting

MCB 30A 30A 22 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room C316

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP3D

General Panel Data

Power Source EPP3D Bus Disconnect Floor 3rd Floor

ELP4C Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP4C Siemens E4 3 1

Siemens E4 1 9

Range Setting

MCB 35A 35A 18 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room CU400

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

ELP4C

General Panel Data

Power Source ELP4C Bus Disconnect Floor 4th Floor

ELP4C

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating 22 kAIC

Serial No CT Ratio

Siemens BQH 2 3

Siemens BQH 1 9

Range Setting

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room CU400

Model CEP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP4C

General Panel Data

Power Source ELP4C Floor 4th Floor

ELP5C Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP5C Siemens BQD 3 1

Siemens BQD 1 21

Panel Schedule

Panel ID

ELP5C

General Panel Data

Power Source ELP5C Bus Disconnect Floor 5th Floor

Main Breaker

Manufacturer Siemens Room C584

Model P1 Voltage 480V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

250A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 45A 45A 14 kAIC

MCB 20A 20A 14 kAIC

ELP5C

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BL

IAC Rating 10 kAIC

Serial No CT Ratio

Siemens BL 2 1

Siemens BL 2 1

Siemens BL 1 38

Panel Schedule

Panel ID

EPP5C

General Panel Data

Power Source ELP5C Floor 5th Floor

Main Breaker

Manufacturer Siemens Room C584

Model P1 Voltage 208V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

250A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 40A 40A 10 kAIC

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

Main CU100 ELP1C 100A

ITE CLE 3 1

Main C200 ELP2C 100A

ITE CLE 3 1

IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

Range Setting

Fused Disconnect Switch Data

Qty

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

LS Bus Duct #1 ITE 65 kAIC REC4100G 480V

Voltage

Disconnect No. 1

Building Location Feeder ID Circuit ID Manufacturer

MCB 100A 100A 200 kAIC

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Disconnect No. 2

Fuse Class Manufacturer Model Amperage Poles AIC Rating

Range Setting

IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #1 ITE 65 kAIC REC4100G 480V

Voltage

100A 100A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Disconnect Schedule

Building Location Feeder ID Circuit ID Manufacturer

NCB

LV Bus Duct #1 - Disconnects

Main CU300 ELP3C 100A

ITE CLE63B100 3 1

Main CU300 EPP3D 100A

ITE CED63B050 3 1

Voltage

Disconnect No. 3

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #1 ITE 65 kAIC REC4100G

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 100A 100A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Disconnect No. 4

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #1 ITE REC3100G REC3100G 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 50A 50A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Main CU400 ELP4C 100A

ITE CLE 3 1

Main C584 ELP5C 125A

ITE BQD 3 1MCB 100A 100A 18 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #1 Siemens 65 kAIC SLEC401250 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 6

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

MCB 100A 100A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #1 ITE 65 kAIC REC4100G 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 5

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

Building Location Model KVA Type

Main CU100 - 37.5 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.10%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main CU300 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main C316 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main DU400 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Voltage Winding Configuration

Transformer No. 3

Feeder ID Transformer ID Manufacturer

LS Bus Duct #1 T-EPP3D ITE

LV Dry-Type Transformer Schedule

Winding Configuration

Transformer No. 1

Feeder ID Transformer ID Manufacturer

ELP1C T-EPP1C Siemens

Voltage

Voltage Winding Configuration

Transformer No. 2

Feeder ID Transformer ID Manufacturer

ELP3C T-EPP3C ITE

Voltage Winding Configuration

Transformer No. 4

Feeder ID Transformer ID Manufacturer

ELP4C T-EPP4C ITE

LV Bus Duct #1 - LV Xfmers

Main C584 3F3Y030L13CB16BA 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 4.00%

Secondary 208/120 ∆ Y X

Voltage Winding Configuration

Transformer No. 5

Feeder ID Transformer ID Manufacturer

ELP5C T-E5C Siemens

LV Bus Duct #1 - LV Xfmers

Location: Main Hospital - LS Bus Duct #2

ESB1 LS Bus Duct #2 Busway

LS Bus Duct #2 E1 Disconnect Bus Disconnect

E1 Disconnect E1 Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 175'

E1 T-E2 LV Transformer #6 AWG #6 AWG #8 AWG THHN 1 1 1 5'

T-E2 EPP4C Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 10'

LS Bus Duct #2 Temp MRI Disconnect Bus Disconnect Busway

Temp MRI Disconnect Temp MRI Panel #1 AWG #1 AWG #6 AWG THHN 1 1 1 300'

LS Bus Duct #2 ELPGA Disconnect Bus Disconnect

ELPGA Disconnect ELPGA Panel #1 AWG #1 AWG #4 AWG THHN 1 1 1 10'

ELPGA T-EPPGA LV Transformer #6 AWG #6 AWG #8 AWG THHN 1 1 1 10'

T-EPPGA EPPGA Panel #2 AWG #2 AWG #4 AWG THHN 1 1 1 10'

EPPGA EPPGB Panel #10 AWG #10 AWG #10 AWG THHN 1 1 1 15'

LS Bus Duct #2 ELP1A Disconnect Bus Disconnect Busway

ELP1A Disconnect ELP1A Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 25'

ELP1A T-EPP1A LV Transformer #6 AWG #6 AWG #8 AWG THHN 1 1 1 35'

T-EPP1A EPP1A Panel #2 AWG #2 AWG #8 AWG THHN 1 1 1

LS Bus Duct #2 T-EPP1B Disconnect Bus Disconnect Busway

T-EPP1B Disconnect T-EPP1B LV Transformer #6 AWG #6 AWG #10 AWG THHN 1 1 1 170'

T-EPP1B EPP1B Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 5'

LS Bus Duct #2 ELP2A Disconnect Bus Disconnect Busway

ELP2A Disconnect ELP2A Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 10'

ELP2A T-EPP2A LV Transformer #6 AWG #6 AWG #6 AWG THHN 1 1 1 10'

T-EPP2A EPP2A Panel #2 AWG #2 AWG #4 AWG THHN 1 1 1 10'

LS Bus Duct #2 T-EPP2B Disconnect Bus Disconnect Busway

T-EPP2B Disconnect T-EPP2B LV Transformer #6 AWG #6 AWG #6 AWG THHN 1 1 1 250'

T-EPP2B EPP2B Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 5'

LS Bus Duct #2 ELP3A Disconnect Bus Disconnect Busway

ELP3A Disconnect ELP3A Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 10'

ELP3A T-EPP3A LV Transformer #8 AWG #8 AWG #8 AWG THHN 1 1 1 5'

T-EPP3A EPP3A Panel #8 AWG #8 AWG #8 AWG THHN 1 1 1 5'

EPP3A EPP3A-1 Panel #2 AWG #2 AWG #6 AWG THHN 1 1 1 10'

LS Bus Duct #2 T-EPP3B Disconnect Bus Disconnect Busway

T-EPP3B Disconnect T-EPP3B LV Transformer #6 AWG #6 AWG #10 AWG THHN 1 1 1 150'

Cable Schedule

Power Qty Location Equipment Type

Size Type Distance

LS BD 2 - Cables

T-EPP3B EPP3B Panel #3 AWG #3 AWG #6 AWG THHN 1 1 1 10'

LS Bus Duct #2 ELP4A Disconnect Bus Disconnect Busway

ELP4A Disconnect ELP4A Panel #3 AWG #3 AWG #6 AWG THHN 1 1 1 10'

ELP4A T-EPP4A LV Transformer #3 AWG #3 AWG #10 AWG THHN 1 1 1 5'

T-EPP4A EPP4A Panel #1 AWG #1 AWG #6 AWG THHN 1 1 1 10'

LS Bus Duct #2 ELP5A Disconnect Bus Disconnect Busway

ELP5A Disconnect ELP5A Panel #2 AWG #2 AWG #8 AWG THHN 1 1 1 10'

ELP5A T-EPP5A LV Transformer #6 AWG #6 AWG #10 AWG THHN 1 1 1 10'

T-EPP5A EPP5A Panel #1 AWG #1 AWG #6 AWG THHN 1 1 1 10'

LS BD 2 - Cables

E1 Bus Disc

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

CLE

IAC Rating

Serial No CT Ratio

EPP4C Siemens ED4 3 1

Range Setting

MCB 60A 60A

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Siemens Room Chiller Plant

Model Voltage 480V

IAC Rating Buss

(Copper, Aluminum, Bolt On, etc)

Breaker Data

Panel Schedule

Panel ID E1

General Panel Data

Power Source E1 Bus Disconnect Floor Ground Floor

LS Bus Duct #2 - Panels

ELP1 Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP1A ITE HE4 3 1

ITE E4 1 9

Qty Range Setting

MCB 45A 45A 65 kAIC

MCB 20A 20A 18 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room DU121

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

ELP1A

General Panel Data

Power Source ELP1 Bus Disconnect Floor 1st Floor

ELP1A

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQ

IAC Rating 10 kAIC

Serial No CT Ratio

Siemens BQH 2 1

Siemens BQ 1 1

Siemens BQH 1 21MCB 20A 20A 22 kAIC

Qty Range Setting

MCB 30A 30A 22 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room DU121

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP1A

General Panel Data

Power Source ELP1A Floor 1st Floor

ELP2A Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP2A Siemens E4 3 1

Siemens E4 1 9

Qty Range Setting

MCB 35A 35A 18 kAIC

MCB 20A 20A 18 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room DU229

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

ELP2A

General Panel Data

Power Source ELP2A Bus Disconnect Floor 2nd Floor

ELP2A

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

QBH

IAC Rating 22 kAIC

Serial No CT Ratio

Siemens BQ 2 1

Siemens BQH 1 20

Qty Range Setting

MCB 30A 30A 10 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room DU229

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP2A

General Panel Data

Power Source ELP2A Floor 2nd Floor

ELPGA Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPPGA Siemens E4 3 1

Siemens HE 3 1

Siemens E4 3 1

Siemens HE4 1 3

Siemens E4 1 18MCB 20A 20A 22 kAIC

MCB 20A 20A 18 kAIC

MCB 20A 20A 65 kAIC

Qty Range Setting

MCB 35A 35A 18 kAIC

MCB 20A 20A 25 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room D001

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Panel Schedule

Panel ID

ELPGA

General Panel Data

Power Source ELPGA Bus Disconnect Floor Basement

ELPGA

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating

Serial No CT Ratio

EPPGB Siemens BQH 3 1

Siemens BQ 3 1

Siemens BQH 2 1

Siemens BQH 1 1

Siemens BQH 1 16MCB 20A 20A 22 kAIC

MCB 30A 30A 22 kAIC

MCB 30A 30A 22 kAIC

Qty Range Setting

MCB 30A 30A 22 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Siemens Room D001

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPPGA

General Panel Data

Power Source ELPGA Floor Basement

EPPGA

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

General Electric THQB 2 1

General Electric THHQB 1 9

Qty Range Setting

MCB 30A 30A 10 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer General Electric Room D001

Model AQU3241MB Voltage 208V

IAC Rating Buss

(Copper, Aluminum, Bolt On, etc)

125A

Breaker Data

Panel Schedule

Panel ID

EPPGB

General Panel Data

Power Source EPPGA Floor Basement

EPP1B Bus Disc

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating 22 kAIC

Serial No CT Ratio

Siemens BQH 1 14

Siemens BQH 1 1

Siemens BQ 1 10MCB 20A 20A 10 kAIC

Qty Range Setting

MCB 20A 20A 22 kAIC

MCB 30A 30A 22 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room C115

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP1B

General Panel Data

Power Source EPP1B Bus Disc Floor 1st Floor

EPP2B Bus Disc

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating

Serial No CT Ratio

Siemens BQH 3 1

Siemens BQH 2 1

Siemens BQH 1 34MCB 20A 20A 22 kAIC

Qty Range Setting

MCB 20A 20A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room C257

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP2B

General Panel Data

Power Source EPP2B Bus Disconnect Floor 2nd Floor

ELP2A Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP3A Siemens BQ 3 1

Siemens BQ 1 9

Qty Range Setting

MCB 35A 35A 18 kAIC

MCB 20A 20A 18 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room D312

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

ELP3A

General Panel Data

Power Source ELP3A Bus Disconnect Floor 3rd Floor

ELP3A

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating 22 kAIC

Serial No CT Ratio

EPP3A-1 Siemens BQ 2 1

Siemens BQ 3 1

Siemens BQH 1 19MCB 20A 20A 22 kAIC

Qty Range Setting

MCB 50A 50A 10 kAIC

MCB 40A 40A 22 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room D312

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

Breaker Data

Panel Schedule

Panel ID

EPP3A

General Panel Data

Power Source ELP3A Floor 3rd Floor

EPP3A

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Square D QOB 2 2

Square D QOB 2 2

Square D QOB 1 8MCB 20A 20A 10 kAIC

Qty Range Setting

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Square D Room D312

Model QOC16U Voltage 208V

IAC Rating Unknown Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

EPP3A-1

General Panel Data

Power Source EPP3A Floor 3rd Floor

ELP4A Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP4A Siemens E4 3 1

Siemens E4 1 5

Qty Range Setting

MCB 45A 45A 22 kAIC

MCB 20A 20A 22 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room D424

Model CDP-7 Voltage 480V

IAC Rating 30 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

ELP4A

General Panel Data

Power Source ELP4A Bus Disconnect Floor 4th Floor

ELP4A

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating

Serial No CT Ratio

Siemens BQ 2 1

Siemens BQH 3 1

Siemens BQH 2 3

Siemens BQH 1 11

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

Qty Range Setting

MCB 20A 20A 10 kAIC

MCB 30A 30A 22 kAIC

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room D424

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

100A

Breaker Data

Panel Schedule

Panel ID

EPP4A

General Panel Data

Power Source ELP4A Floor 4th Floor

EPP3B Bus Disc

Trip Device Type T-M

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BQH

IAC Rating 22 kAIC

Serial No CT Ratio

Siemens BQH 3 1

Siemens BQH 2 1

Siemens BQ 2 4

Siemens BQH 1 11

MCB 20A 20A 10 kAIC

MCB 20A 20A 22 kAIC

Qty Range Setting

MCB 40A 40A 22 kAIC

MCB 30A 30A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer ITE Room CU320

Model CDP-7 Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

60A

Breaker Data

Panel Schedule

Panel ID

EPP3B

General Panel Data

Power Source EPP3B Bus Disconnect Floor 3rd Floor

ELP5A Bus Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

EPP5A Siemens BQD 3 1

Siemens E4 3 2

Siemens E4 1 12

Panel Schedule

Panel ID

ELP5A

General Panel Data

Power Source ELP5A Bus Disconnect Floor 5th Floor

Main Breaker

Manufacturer Siemens Room C521

Model P1 Voltage 480V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

250A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 45A 45A 14 kAIC

MCB 20A 20A 14 kAIC

MCB 20A 20A 14 kAIC

ELP5A

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

NGB

IAC Rating 100 kAIC

Serial No CT Ratio

Siemens BL 2 1

Siemens BL 1 27

Siemens BL 1 1

Panel Schedule

Panel ID

EPP5A

General Panel Data

Power Source ELP5A Floor 5th Floor

Main Breaker

Manufacturer Siemens Room C521

Model P2 Voltage 208V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

250A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Circuit ID Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

MCB 25A 25A 10 kAIC

Main D001 E1 100A

ITE CLE 3 1

Main DU121 ELP1A 100A

ITE CLE 3 1

IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

Range Setting

Fused Disconnect Switch Data

Qty

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

LS Bus Duct #2 Siemens 65 kAIC REC4100G 480V

Voltage

Disconnect No. 1

Building Location Feeder ID Circuit ID Manufacturer

MCB 100A 100A 200 kAIC

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Disconnect No. 2

Fuse Class Manufacturer Model Amperage Poles AIC Rating

Range Setting

IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 Siemens 65 kAIC REC4100G 480V

Voltage

100A 100A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Disconnect Schedule

Building Location Feeder ID Circuit ID Manufacturer

MCB

LS Bus Duct #2 - Disconnects

Main DU229 ELP2A 100A

Main D001 ELPGA 100A

ITE/Siemens CLE 3 1

Voltage

Disconnect No. 3

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 ITE 65 kAIC REC4100G 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 100A 100A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Disconnect No. 4

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 ITE 65 kAIC REC4100G 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 100A 100A 25 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Main DU121 EPP1B 100A

ITE CED 3 1

Main DU229 EPP2B 100A

ITE CED 3 1MCB 50A 50A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 ITE 65 kAIC REC3100G 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 6

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

MCB 50A 50A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 Siemens 65 kAIC REC3100 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 5

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

Main D312 ELP3A 100A

Main D424 ELP4A 100A

ITE CLE 3 1MCB 100A 100A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 Siemens 65 kAIC RECL4100G 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 8

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

MCB 100A 100A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 ITE 65 kAIC REC4100G 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 7

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

Main D312 EPP3B 100A

ITE CED 3 1

Main C521 ELP5A 125A

Siemens BQD 3 1MCB 100A 100A 25 kAIC - -

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 Siemens 65 KAIC SLEC401250 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 10

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

MCB 50A 50A 200 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

LS Bus Duct #2 ITE 65 kAIC REC3100 480V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 9

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

Main 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 6.10%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main DU121 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main DU229 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

1 D001 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Voltage Winding Configuration

Transformer No. 4

Feeder ID Transformer ID Manufacturer

ELPGA T-EPPGA ITE

Voltage Winding Configuration

Transformer No. 2

Feeder ID Transformer ID Manufacturer

ELP1A T-EPP1A ITE

LV Dry-Type Transformer Schedule

Winding Configuration

Transformer No. 1

Feeder ID Transformer ID Manufacturer

E1 T-E2 Siemens

Voltage

Voltage Winding Configuration

Transformer No. 3

Feeder ID Transformer ID Manufacturer

ELP2A T-EPP2A ITE

LS Bus Duct #2 - LV Xfmers

Main C115 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main C257 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main D312 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main D424 - 37.5 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.10%

Secondary 208/120 ∆ Y X

Voltage Winding Configuration

Transformer No. 8

Feeder ID Transformer ID Manufacturer

ELP4A T-EPP4A Siemens

ELP3A T-EPP3A ITE

Voltage Winding Configuration

Voltage Winding Configuration

Transformer No. 7

Feeder ID Transformer ID Manufacturer

Transformer No. 6

Feeder ID Transformer ID Manufacturer

EPP2B Bus Disconnect T-EPP2B Siemens

EPP1B Bus Disconnect T-EPP1B ITE

Voltage Winding Configuration

Transformer No. 5

Feeder ID Transformer ID Manufacturer

Main CU320 3F3Y030 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main C521 3F3Y030K13CD16BA 30 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 4.00%

Secondary 208/120 ∆ Y X

EPP3B Bus Disconnect T-EPP3B Siemens

Voltage Winding Configuration

Transformer No. 9

Feeder ID Transformer ID Manufacturer

Voltage Winding Configuration

Transformer No. 9

Feeder ID Transformer ID Manufacturer

ELP5A T-ELP5A Siemens

Location: Main Hospital - ESB2 Cables

LV Swg Bus #1 ATS-CR ATS 500 kCMIL 500 kCMIL #1 AWG THHN 2 2 2 75'

ATS-CR ESB2 Switchboard 500 kCMIL 500 kCMIL #1 AWG THHN 2 2 2 20'

ESB2 T-MOR LV Transformer #4 AWG #4 AWG #10 AWG THHN 1 1 1 320'

T-MOR MOR-2 Panel #1 AWG #1 AWG #6 AWG THHN 1 1 1 20'

T-MOR Spare Disconnect Sw #1 AWG #1 AWG #6 AWG THHN 1 1 1 20'

ESB2 MCC3E Motor Control Ctr 500 kCMIL - #1 AWG THHN 2 - 2 355'

MCC3E T-EPP-3E LV Transformer #2 AWG #2 AWG THHN 1 1 1 3'

T-EPP-3E EPP-3E Disconnect Disconnect Sw 1/0 AWG 1/0 AWG THHN 1 1 1 8'

EPP-3E Disconnect EPP-3E-1 Panel #2 AWG #2 AWG THHN 1 1 1 8'

EPP-3E Disconnect EPP-3E-2 Panel #2 AWG #2 AWG THHN 1 1 1 8'

ESB2 MCC4E Motor Control Ctr 500 kCMIL - #1 AWG THHN 2 - 2 370'

MCC4E T-EPP-4E LV Transformer #4 AWG #4 AWG THHN 1 1 1 5'

T-EPP-4E EPP-4E Disconnect Disconnect Sw 1/0 AWG 1/0 AWG THHN 1 1 1 8'

EPP-4E Disconnect EPP-4E Panel 1/0 AWG 1/0 AWG THHN 1 1 1 10'

ESB2 1HCR Panel 3/0 AWG 3/0 AWG #6 AWG THHN 1 1 1 300'

1HCR T-1LCR LV Transformer #1 AWG #1 AWG #6 AWG THHN 1 1 1 10'

T-1LCR 1LCR Panel 4/0 AWG 4/0 AWG #6 AWG THHN 1 1 1 10'

Cable Schedule

Power Qty Location Equipment Type

Size Type Distance

ESB2 - Cables

ESB2

Trip Device Type T-M

Breaker ID Main

Frame Size 100A

Breaker Type

MCB

Rating 100A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

QOB

IAC Rating

Serial No CT Ratio

Square D QOB 2 1

Square D QOB 2 1

Square D QOB 1 1

Square D QOB 1 2

Panel Schedule

Panel ID

MOR-2

General Panel Data

Power Source ESB2 Floor Basement

Main Breaker

Manufacturer Square D Room D183A

Model QOC30US Voltage 208V

IAC Rating Unknown Buss

(Copper, Aluminum, Bolt On, etc)

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

MCB 30A 30A 10 kAIC

MCB 20A 20A 10 kAIC

ESB2 - Panels

MCC3C

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Siemens BQH 1 42

Panel Schedule

Panel ID

EPP-3E-1

General Panel Data

Power Source MCC3C Floor 3rd Floor

Main Breaker

Manufacturer Siemens Room CM328

Model UBA42-24L Voltage 208V

IAC Rating 100 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 22 kAIC

MCC3C

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

Siemens BQH 3 1

Siemens BQH 2 1

Siemens BQH 1 2

Siemens BQH 1 36

MCB 30A 30A 22 kAIC

MCB 20A 20A 22 kAIC

Range Setting

MCB 20A 20A 22 kAIC

MCB 30A 30A 22 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Siemens Room CM328

Model UBA42-24L Voltage 208V

IAC Rating 100 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Panel Schedule

Panel ID

EPP-3E-2

General Panel Data

Power Source MCC3C Floor 3rd Floor

MCC4E via Disc

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

ITE BQH 3 3

ITE BQH 1 12

Panel Schedule

Panel ID

EPP-4E

General Panel Data

Power Source MCC4E via Disconnect Floor 4th Floor

Main Breaker

Manufacturer ITE Room CM408

Model UB830-24L Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 20A 20A 22 kAIC

MCB 20A 20A 22 kAIC

ESB2

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

1LCR Square D EDB34100 3 1

Square D EDB14020 1 7

Panel Schedule

Panel ID

1HCR

General Panel Data

Power Source ESB2 Floor Basement

Main Breaker

Manufacturer Square D Room D183B

Model NF Voltage 480V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

250A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 100A 100A 18 kAIC

MCB 20A 20A 18 kAIC

1HCR

Trip Device Type T-M

Breaker ID Main

Frame Size 200A

Breaker Type

MCB

Rating 200A

Inst

Manufacturer Square D

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

QDL32200

IAC Rating 25 kAIC

Serial No CT Ratio

Square D QOB 3 2

Square D QOB 1 3

Panel Schedule

Panel ID

1LCR

General Panel Data

Power Source 1HCR Floor Basement

Main Breaker

Manufacturer Square D Room D183B

Model NQ Voltage 208V

IAC Rating 65 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

225A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 125A 125A 22 kAIC

MCB 20A 20A 10 kAIC

Main CM328 T-EPP-3E Sec Disc 150A

Siemens F6 3 1

Main CM408 T-EPP-4E Disc -

ITE E4 3 1

IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

Range Setting

Fused Disconnect Switch Data

Qty

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

MCC3C Siemens 208V

Voltage

Disconnect No. 1

Building Location Feeder ID Circuit ID Manufacturer

MCB 150A 150A

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Disconnect No. 2

Fuse Class Manufacturer Model Amperage Poles AIC Rating

Range Setting

IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

MCC4E ITE - 208V

Voltage

45A 45A 18 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Disconnect Schedule

Building Location Feeder ID Circuit ID Manufacturer

MCB

ESB2 - Disconnects

Main CM408 T-EPP-4E Sec. Disc -

ITE F63F250 3 1

Main CM328 T-EPP-3E Disc -

ITE E4 3 1

MCB 250A 125A 25 kAIC 800-1500A 800A

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

MCC4E Siemens 208V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 4

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

Voltage

Disconnect No. 2

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Amperage (NEMA Size 1,4, etc.)

MCC3E ITE - - 208V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 100A 100A 18 kAIC

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Main CM328 T-EPP-3E Sec. Disc -

ITE F63F250 3 1

Main D183A Spare 100A

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Amperage (NEMA Size 1,4, etc.)

ESB2 via T-MOR2 ITE 10 kAIC NF353 208V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

Disconnect No. 5

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage

Disconnect No. 4

Building Location Feeder ID Circuit ID Manufacturer IAC Rating Enclosure Type

Voltage Amperage (NEMA Size 1,4, etc.)

MCC3E Siemens - - 208V

Main Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty Range Setting

MCB 150A 150A 25 kAIC 800-1500A 800A

Fused Disconnect Switch Data

Fuse Class Manufacturer Model Amperage Poles AIC Rating Qty

Main D183A - 37.5 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 5.10%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main CM328 DGP 45 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 2.80%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main CM408 DGP 37.5 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 4.60%

Secondary 208/120 ∆ Y X

Building Location Model KVA Type

Main D183B EE75T3HCU 75 AA

Rise (°C) Tap Impedance (%)

Primary 480 ∆ X Y 3 3.70%

Secondary 208/120 ∆ Y X

Voltage Winding Configuration

Transformer No. 4

Feeder ID Transformer ID Manufacturer

1HCR T-1LCR Siemens

Voltage Winding Configuration

Transformer No. 2

Feeder ID Transformer ID Manufacturer

MCC3C T-EPP-3E Siemens

LV Dry-Type Transformer Schedule

Winding Configuration

Transformer No. 1

Feeder ID Transformer ID Manufacturer

ESB2 T-MOR Siemens

Voltage

Voltage Winding Configuration

Transformer No. 3

Feeder ID Transformer ID Manufacturer

MCC3C T-EPP-4E ITE

ESB2 - LV Xfmers

T-EPP-3E

Siemens E4 3 1

Manufacturer Siemens Room CM328

Model - Voltage/Amperage 480V

Motor Control Center (MCC) Schedule

MCC ID

MCC3E

General MCC Data

Power Source ESB2 Floor 3rd Floor

IAC Rating - Amperage/Section -

Starter Data

Circuit ID VFD/Starter Starter Size (NEMA) HP Voltage FLA LRA

1EF-5 NEMA 1 480V

1P-10 NEMA 1 480V

1EF-6 NEMA 1 480V

1EF-12 NEMA 1 480V

1EF-9 NEMA 1 480V

1P-11 NEMA 1 480V

1EF-10 NEMA 1 480V

Lab Air VFD

1EF-19 NEMA 1 480V

Branch Breaker Data

Circuit Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instanteneous

Qty Range Setting

MCB 100A 100A

ESB2 - MCC

T-EPP-4E

Siemens E4 3 1

Manufacturer Siemens Room CM408

Model - Voltage/Amperage 480V

Motor Control Center (MCC) Schedule

MCC ID

MCC4E

General MCC Data

Power Source ESB2 Floor 4th Floor

IAC Rating - Amperage/Section -

Starter Data

Circuit ID VFD/Starter Starter Size (NEMA) HP Voltage FLA LRA

Med Vacuum NEMA 1

1SF8 VFD

1P7 NEMA 1

AHU2 RF VFD

1SF2 VFD

1P6 NEMA 1

Branch Breaker Data

Circuit Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instanteneous

Qty Range Setting

MCB 45A 45A

ESB2 - MCC

Location: Main Hospital - ESB3 Cables

Generator Main ESB3 DP Panel Bus Connected 10'

ESB3 ESB1 DP Panel 500 MCM 500 MCM #1 AWG THHN 2 2 2 15'

ESB3 ESB2 DP Panel 500 MCM 500 MCM #1 AWG THHN 2 2 2 40'

ESB3 ESB4 Panel 500 MCM 500 MCM #1 AWG THHN 2 2 2 40'

ESB3 Remote Rad Em Gen Starter #1 AWG #1 AWG #10 AWG THHN 1 1 1 150'

Cable Schedule

Power Qty Location Equipment Type

Size Type Distance

ESB3 - Cables

Location: Main Hospital - ESB4 Cables

LV Swg Bus #1 ATS-EM ATS 500 kCMIL 500 kCMIL #1 AWG THHN 2 2 2 50'

ATS-EM ESB4 Switchboard 500 kCMIL 500 kCMIL #1 AWG THHN 2 2 2 10'

ESB4 LPE2 Panel 4/0 AWG 4/0 AWG #4 AWG THHN 1 1 1 215'

LPE2 P5 Controller #3 AWG - #6 AWG THHN 1 1 1 20'

LPE2 P4 Controller #3 AWG - #6 AWG THHN 1 1 1 20'

ESB4 LPE1 Panel 500 kCMIL 500 kCMIL #1 AWG THHN 1 1 1 400'

LPE1 T-PPE1 LV Transformer #10 AWG #10 AWG #10 AWG THHN 1 1 1 5'

T-PPE1 PPE1 Panel #4 AWG #4 AWG #8 AWG THHN 1 1 1 5'

LPE1 P6 Controller #2 AWG #2 AWG #6 AWG THHN 1 1 1 65'

LPE1 P7 Controller #2 AWG #2 AWG #6 AWG THHN 1 1 1 65'

ESB4 LPE3 Panel 500 kCMIL 500 kCMIL #1 AWG THHN 1 1 1 200'

LPE3 S6 Controller #1 AWG #1 AWG #4 AWG THHN 1 1 1 75'

LPE3 S7 Controller #1 AWG #1 AWG #4 AWG THHN 1 1 1 65'

LPE3 T-PPE3 LV Transformer #6 AWG #6 AWG #8 AWG THHN 1 1 1 10'

T-PPE3 PPE3 Panel #4 AWG #4 AWG #8 AWG THHN 1 1 1 10'

ESB4 EBDP3 Panel 4/0 AWG 4/0 AWG #6 AWG THHN 1 1 1 350'

EBDP3 Chiller Disconnect Disconnect Sw 2/0 AWG 2/0 AWG #8 AWG THHN 1 1 1 90'

Chiller Disconnect Chiller VFD 2/0 AWG 2/0 AWG #8 AWG THHN 1 1 1 10'

Cable Schedule

Power Qty Location Equipment Type

Size Type Distance

ESB4 - Cables

ESB4

Trip Device Type

Breaker ID

MLO

Frame Size

Breaker Type Rating Inst

Manufacturer Poles Current Time Delay Current Time Delay Current Current Time Delay

Model IAC Rating

Serial No CT Ratio

P5 Siemens BQD 3 1

P4 Siemens BQD 3 1

T-PPE3 Siemens BQD 2 1

Siemens BQD 3 1

Siemens BQD 1 3MCB 20A 20A

MCB 45A 45A

MCB 40A 40A

Range Setting

MCB 100A 100A

MCB 100A 100A

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Main Breaker

Manufacturer Siemens Room

Model P1 Voltage 480V

IAC Rating 250A Buss

(Copper, Aluminum, Bolt On, etc)

250A

Breaker Data

Panel Schedule

Panel ID

LPE2

General Panel Data

Power Source ESB4 Floor 2nd Floor

ESB4 - Panels

ESB4

Trip Device Type Thermal Magnetic

Breaker ID Main

Frame Size 300A

Breaker Type

MCB

Rating 300A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

JXD63B300

IAC Rating 35 kAIC 1250-2500A

Serial No CT Ratio 2000A

Elevator P6 Siemens NGB 3 1

Elevator P7 Siemens NGB 3 1

T-PPE1 Siemens BQD 3 1

Siemens BQD 3 1

Siemens BQD 3 1

Siemens BQD 1 6

Panel Schedule

Panel ID

LPE1

General Panel Data

Power Source ESB4 Floor 6th Floor

Main Breaker

Manufacturer Siemens Room 602

Model P2 Voltage 480V

IAC Rating 200 kAIC Buss

(Copper, Aluminum, Bolt On, etc)

400A

Breaker Data

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Range

Settings

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

QtyCircuit ID Range Setting

MCB 110A 100A

MCB 110A 100A

MCB 30A 30A

MCB 25A 25A

MCB 20A 20A

MCB 20A 20A

Location: Main

LPE1

Trip Device Type Thermal Magnetic

Breaker ID Main

Frame Size 60A

Breaker Type

MCB

Rating 60A

Inst

Manufacturer Siemens

Poles

Current Time Delay Current Time Delay Current Current Time Delay

Model

BL

IAC Rating 10 kAIC

Serial No CT Ratio

Siemens BL 2 1

Siemens BL 1 8

Range Setting

MCB 50A 50A 10 kAIC

MCB 20A 20A 10 kAIC

Branch Breaker Data

Breaker Type Manufacturer Model Frame Size Rating Poles AIC Rating Instantaneous

Qty

Trip Device Settings (as found)

Long Time Short Time Ground Fault

Ran…