Drawings Part 1 of 3 C-SCA 621-22-106 .pdf
PDF 3 MB Posted
- Solicitation number
- 36C24922B0009
About this file
This document provides details of a federal contract opportunity for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9 is seeking a contractor to construct a new Containment Segregated Compounding Area and associated spaces at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The estimated value of the construction is between $500,000 and $1,000,000. The solicitation is expected to be posted on December 28, 2021 and close on January 26, 2022. This requirement is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. The awarded contractor must be listed in the Center for Verification and Evaluation database and have an active System for Award Management registration. The contractor must also submit evidence of enrollment with VETS4212.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 77
2N D
S T
R E
E
TPROPOSED
CRANE LOCATION
PROPOSED
CONSTRUCTION
TRAILER AND
LAYDOWN AREA
1ST STREET
PROJECT LOCATION
BLDG 77 & 205
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:0
:2
P
M
GI000
COVER SHEET
09/15/2021 PRQ NHM
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
JAMES H. QUILLEN
VA MEDICAL CENTER
DRAWING LIST
Sheet
Number Sheet Name
GENERAL
GI000 COVER SHEET
GI001 ABBREVIATIONS AND GENERAL DETAILS
GI002 FIRST AND SECOND FLOOR OVERALL AND CODE PLANS
STRUCTURAL
S101 STRUCTURAL PLANS AND DETAILS
ARCHITECTURE
AD101 DEMOLITION PLANS
AE101 FLOOR, REFLECTED CEILING AND ROOF PLANS
AE601 DOOR DETAILS AND SCHEDULES
FIRE PROTECTION
FX101 FIRST FLOOR FIRE SUPPRESSION PLAN
PLUMBING
PL101 PLUMBING PLANS
PL501 PLUMBING DETAILS, SCHEDULES, & ISOMETRICS
MECHANICAL
M001 MECHANICAL LEGEND
MD101 FIRST FLOOR MECHANICAL DEMOLITION PLAN
MH101 FIRST FLOOR MECHANICAL PLAN - HVAC
MH102 SECOND FLOOR MECHANICAL PLAN - HVAC
MH103 MECHANICAL ROOF PLAN - HVAC
MP101 FIRST FLOOR MECHANICAL PLAN - PIPING
MP102 SECOND FLOOR MECHANICAL PLAN - PIPING
MP103 MECHANICAL ROOF PLAN - PIPING
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M601 MECHANICAL SCHEDULES
M602 MECHANICAL SCHEDULES
M701 MECHANICAL CONTROLS
ELECTRICAL
E001 LEGEND AND ABBREVIATIONS
ED101 FIRST & SECOND FLOOR DEMOLITION PLAN
EL101 FIRST & SECOND FLOOR NEW LIGHTING PLAN
EP101 FIRST FLOOR NEW POWER PLAN
EP103 ROOF NEW POWER PLAN
EY101 FIRST FLOOR NEW TECHNOLOGY PLAN
E500 ELECTRICAL DETAILS
CONSTRUCT CONTAINMENT SEGREGATED
COMPOUNDING AREA (C-SCA)
# 621-22-106
DEPARTMENT OF VETERANS AFFAIRS
LAMONT ST & VETERANS WAY, JOHNSON CITY, TN 37604
NTS
VICINITY MAP
A. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND FEDERAL AUTHORITIES, CODES, RULES AND REGULATIONS.
B. THESE DOCUMENTS SHOW THE MINIMUM CONSTRUCTION REQUIREMENTS AND THE MINIMUM QUALITY OF WORK EXPECTED. MORE STRINGENT REQUIREMENTS STIPULATED WITHIN RELEVANT MANUFACTURER’S INSTALLATION INSTRUCTIONS WILL SUPERSEDE.
C. DRAWINGS & SPECIFICATIONS ARE COMPLIMENTARY COMPONENTS OF THE CONTRACT DOCUMENTS. REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR THE COMPLETE SCOPE OF WORK. NOTIFY ARCHITECT AND COR IMMEDIATELY FOR CLARIFICATION IF INCONSISTENCIES, CONTRADICTIONS OR
OMISSIONS ARE DISCOVERED
D. DO NOT SCALE DRAWINGS, IF DIMENSIONAL INFORMATION IS REQUIRED & NOT FOUND, NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION
E. ANY UNFORESEEN OR UNCLEAR CONDITIONS SHALL BE REPORTED TO THE C.O.R. PRIOR TO PROCEEDING WITH WORK. CONTRACTOR SHALL
SUBMIT AN RFI FOR ANY DISCREPANCIES.
F. UNLESS OTHERWISE NOTED, ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED PER THE APPLICABLE PROVISIONS OF THESE DOCUMENTS AND
THE MANUFACTURER’S INSTRUCTIONS.
G. ALL MATERIALS USED SHALL BE NEW UNLESS OTHERWISE NOTED AND/OR OF A QUALITY TO MEET OR EXCEED ALL APPLICABLE INDUSTRY STANDARDS. WHERE SPECIFIED PRODUCTS OR MANUFACTURERS ARE NOT NOTED, THE CONTRACTOR IS REQUIRED TO NOTIFY THE COR TO
OBTAIN A MINIMUM STANDARD OF QUALITY.
H. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR CONSTRUCTION.
I. THE CONTRACTOR IS RESPONSIBLE FOR JOB-SITE SAFETY INCLUDING BUT NOT LIMITED TO THE ADHERENCE TO OSHA REGULATIONS.
J. ALL ELECTRICAL AND MECHANICAL WORK SHALL BE PERFORMED BY PERSONNEL LICENSED IN THE STATE WHERE THIS PROJECT IS LOCATED.
K. ALL CONTRACTORS ARE RESPONSIBLE FOR ANY DAMAGES CAUSED BY THEM DURING THE CONSTRUCTION PROCESS. IN THE EVENT OF ANY DAMAGES CONTRACTOR IS TO CONTACT THE COR IMMEDIATELY PRIOR TO THE END OF THE DAY OF CONSTRUCTION.
L. REMOVE ALL DEBRIS PROPERLY FROM THE SITE. LOAD DEBRIS DIRECTLY ONTO TRUCKS OR INTO DUMPSTERS FOR REMOVAL. DISPOSE OF DEBRIS LEGALLY. DO NOT BURN DEBRIS ON THE SITE. DO NOT ALLOW DEBRIS TO ENTER SEWERS. DO NOT ALLOW PILED DEBRIS TO ENDANGER STRUCTURES, BLOCK EXISTS OR ROADWAYS. COMBUSTIBLE WASTE WHICH COULD CREATE A FIRE HAZARD SHALL NOT BE PERMITTED TO
ACCUMULATE IN OR AROUND THE CONSTRUCTION SITE.
M. CONTRACTOR TO COORDINATE ALL WORK BETWEEN TRADES, INCLUDING BETWEEN FINISH CONTRACTOR AND ELECTRICAL, ON ALL LIGHT
FIXTURES, WIRING, AND FINISHES
N. EXACT SIZE AND LOCATION OF ALL ROOF AND FLOOR OPENINGS SHOWN ON ARCHITECTURAL DRAWINGS SHALL BE VERIFIED WITH THE ASSOCIATED SUB-CONTRACTORS PRIOR TO CONSTRUCTION. SEAL CONSTRUCTION TIGHT TO ALL PENETRATIONS AND CAULK.
O. ALL EXISTING OPENINGS IN CEILINGS, FLOORS AND WALLS DISCOVERED IN THE EXISTING STRUCTURE SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
P. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS OR CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS NECESSARY TO PROPERLY ACCOMMODATE THE NEW
MATERIALS.
Q. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED AND FIRE SAFE'D TO ACHIEVE THE REQUIRED FIRE RATING BY THE END OF CONSTRUCTION OPERATIONS FOR EACH DAY. ALL FIRE RATED WALL AND FLOOR PENETRATIONS MUST COMPLY WITH
ASTM-E814.
R. ALL CONCEALED WOOD SHALL BE FIRE RETARDANT TREATED.
S. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR DETAILED OTHERWISE.
T. ALL NEW MASONRY WORK INCLUDING NEW PARTITIONS, INFILL AND PATCHING; MATCH EXISTING COURSING AND TOOTH IN WITH EXISTING
ADJACENT CONSTRUCTION.
U. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR ANY REASON.
V. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
W. USE 5/8" FIRE RATED GWB AT ALL FIRE-RATED PARTITIONS, ANCHOR W/ SCREWS AT 8" O.C. ON EDGES AT 12" O.C. IN FIELD PER UL DESIGN
NUMBERS LISTED.
X. CONSTRUCTION RELATED COMPLAINTS BY PATIENTS OR EMPLOYEES SHALL BE DIRECTED TO THE FACILITY SAFETY OFFICE. THE SAFETY OFFICE SHALL INVESTIGATE THE COMPLAINTS AND MAKE RECOMMENDATIONS TO THE CONTRACTING OFFICER REPRESENTATIVE ON HOW TO PROCEED
WITH THE TASK.
Y. CONTRACTOR SHALL MAKE PROVISIONS TO ENSURE CONSTRUCTION NOISE DOES NOT EXCEED THE OSHA THRESHOLD IN AREAS ADJACENT TO CONSTRUCTION AS WELL AS TO ALLOW THE FACILITY TO OPERATE DURING CONSTRUCTION. ACTIONS THAT THE CONTRACTOR SHALL TAKE TO
MINIMIZE IMPACT INCLUDE
1. NOTIFYING THE COR TWO DAYS PRIOR TO TIME OF HIGH NOISE PRODUCING ACTIVITIES WHICH ARE TO BE COMPLETED BETWEEN THE
HOURS OF 5:00 PM AND 6:00 AM.
2. SCHEDULING HIGH NOISE ACTIVITIES DURING TIMES OF MINIMAL IMPACT.
G E N E R A L N O T E S
N N N
1/2" = 1'-0"
SITE PLAN - CONTRACTOR STAGING AREA
NTS
MT. HOME VA CAMPUS SITE PLAN
No. Revisions: Date:
BID DOCUMENTS 9/08/2021
5/8" GYPSUM BOARD
3-5/8" 16 GA COLD-FORMED
STEEL FRAMING
TYPE 1
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON EACH SIDE OF 3-5/8"
16 GA. COLD-FORMED STEEL
FRAMING @ 16" O.C. EXTEND STUDS
AND BOARD 10' 0" ABOVE FINISHED
FLOOR ELEVATION.
TYPE 2
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON OCCUPIED SIDE OF
3-5/8" 16 GA. COLD-FORMED STEEL
FRAMING @ 16" O.C. EXTEND STUDS
AND BOARD 10' 0" ABOVE FINISHED
FLOOR ELEVATION. HOLD OFF
EXISTING WALL 1" .
3-5/8" 16 GA COLD-FORMED
STEEL FRAMING
5/8" GYPSUM BOARD
3 1/2" ACOUSTIC INSULATION
1"
EXISTING WALL
CLIP TO EXISTING WALL AT
60" O.C.
5/8" GYPSUM BOARD
2-1/2" 16 GA COLD-FORMED
STEEL FRAMING
TYPE 3
ONE LAYER OF 5/8" GYPSUM
WALLBOARD ON OCCUPIED SIDE OF
2-1/2" 16 GA. COLD-FORMED STEEL
FRAMING @ 16" O.C. EXTEND STUDS
AND BOARD 10' 0" ABOVE FINISHED
FLOOR ELEVATION. HOLD OFF
EXISTING COLUMN 1".
4 7/8"
5 1/4" 4 1/8"
1" CLEARANCE AT COLUMN
CLIP TO EXISTING COLUMN
AT 60" O.C.
EXISTING COLUMN
1"
MIN
1'-3"
C
LR
K N
E E
S P
A C
E
2' -3
M
IN
M A
X T
O R
IM
2' -1
0"
MIN
8" DEEP
T O
R
IM
2' -1
0" M
A X
2'-1" MAX
1'-5" MIN
9" M
IN
9" M
IN
SIDE VIEW FRONT VIEW
CLEARANCE
6" MAX TOE
1'-5" MIN
LAVATORY
PLUMBING LINES
WITHIN HATCHED
AREA REQUIRED
TO BE INSULATED
LINES OF REQUIRED
CLEARANCE
FINISH FLOOR
4'-0" MIN CLR
2' -5
M
IN
5"
2' -3
M
IN
CLEAR SPACE
ALLOWABLE FOR
ACCESSIBILITY
MIRROR
2' -5
M
IN
LINES OF REQUIRED
CLEARANCE
5"
A101
SIM
A101
SIM
A101
SIM
A101
SIM
A B B R E V I A T I O N S
LEVEL NAME W/ ELEVATION
GRID HEAD
CALL OUT HEAD W/ SHEET NUMBER
ROOM NAME W/ ROOM NUMBER, AREA &
OCCUPANCY
BUILDING SECTION NUMBER W/ SHEET
NUMBER
WALL SECTION NUMBER W/ SHEET NUMBER
DOOR NUMBER
WALL TAG
KEYNOTE
REVISION TAG
CEILING TAG WITH HEIGHT
DETAIL SECTION NUMBER W/ SHEET NUMBER
NORTH ARROW
A.D.
A.C.T.
ACOUS.
A/C
A.C.P.
A.B.
AREA DRAIN
ACOUSTICAL CEILING TILE
ACOUSTIC
AIR CONDITIONING
ASPHALT CONCRETE
ANCHOR BOLT
PAVING
POUND OR NUMBER
PROPERTY LINE
FLOOR LINE
ANGLE
DIAMETER
CENTERLINE
AT
AND
BD.
APPROX.
ARCH.
ASPH.
ALT.
AL.
AGG.
BLDG.
BLK.
BLKG.
BM.
BRG.
BRK.
BOT.
BITUM.
CEM.
C.B.
CARP.
CAB.
B.U.R.
BTWN.
CLKG.
CLG.J.
CLG.
C.J.
CIR.
C.I.
CER.T.
CER.
BRZ.
COMB.
COL.
C.O.
CNTR.
CMU
CLS.
CLR.
C.W.
CTR.
CONV.O.
CONT.
CONST.
CONN.
CONC.
COMP.
DF.
D.F.
DIAG.
DIA.
DIM.
DISP.
DET.
DN.
D.O.
DR.
D.S.
D.T.
D.W.
DWR.
DIV.
CLO.
DOUGLAS FIR
DRINKING FOUNTAIN
DIAMETER
DIAGONAL
DIMENSION
DISPOSAL
DIVISION
DOWN
DOOR OPENING
DOOR
DOWN SPOUT
DRAIN TILE
DISHWASHER
DRAWER
DETAIL
COLD WATER
CENTER
CONVECTION OVEN
CONTINUOUS
CONSTRUCTION
CONNECTION
CONCRETE
COMPOSITION
BENCH MARK or BEAM
BOARD
BITUMINOUS
BUILDING
BLOCK
BLOCKING
APPROXIMATE
ARCHITECT
ASPHALT
CONCRETE MASONRY
COMBINATION
COLUMN
CLEAN OUT
COUNTER
CLOSURE
CLEAR
CLOSET
CAULKING
CEILING JOIST
UNIT
CEILING
BRICK
BEARING
CONSTRUCTION JOINT
CIRCLE
CAST IRON
CERAMIC TILE
CERAMIC
CEMENT
CATCH BASIN
CARPET
CABINET
BUILT-UP ROOFING
BETWEEN
BRONZE
BOTTOM
ALTERNATE
ALUMINUM
AGGREGATE
EA.
E.E.
E.F.
E.J.
ELEC.
ELEV.
E.N.
EXISTING
EACH
EACH END
EXHAUST FAN
EXPANSION JOINT
ELECTRICAL
ELEVATION
EDGE NAIL
(E)
ADJUSTABLEADJ.
LP
LC
LF
Ø
ABOVE FINISH FLOORAFF
CONTRACTOR FURNISH/
OWNER INSTALL
C.F.O.I.
C.F.C.I. CONTRACTOR FURNISH/
CONTRACTOR INSTALL
E.C. ELECTRICAL CONTRACTOR
C.HK. COAT HOOK
C.B.B. CEMENTITIOUS BACKER
BOARD
A.C.M. ASBESTOS CONTAINING
MATERIALS
CW. CURTAINWALL
DWG(S). DRAWING(S)
FACE OF BUILDINGF.O.B.
FIXTURE
FACE OF CONCRETE
FLOOR
FLOOR JOIST
FLOOR LINE
FLASHING
FACE NAIL
GAUGE
FOOTING
FUTURE
FACE OF STUD
FIRE RETARDANT
TREATED WOOD
FACE OF MASONRY
FACE OF FINISH
F.O.S.
F.R.T.W.
FTG.
FUT.
GA.
FIXT.
F.J.
F.L.
FLASH.
FLR.
F.N.
F.O.C.
F.O.F.
F.O.M.
BEAM
GLASS
GLUE LAMINATED
GALVANIZED IRON
GRATE ELEVATION
GRAB BAR
GARBAGE DISPOSAL
GRADE
HOSE BIB
SHEET METAL
GYPSUM BOARD
HANDICAPPED
GALVANIZED
GROUND
HC.
GYP.BD.
H.B.
G.B.
G.D.
G.S.M.
GR.
GND.
GLB.
GL.
G.I.
G.E.
HEIGHT
HOUR
HEATING
HIGH POINT
HORIZONTAL
HOLLOW METAL
HARDWARE
HARDWOOD
INTERIOR
INVERT
HOT WATER
INSULATION
INSIDE DIAMETER
& AIR CONDITIONING
HEATING, VENTILATION
H.W.
INV.
INT.
INSUL.
I.D.
HDWE.
HDWD.
H.V.A.C.
HTG.
HR.
H.P.
HORIZ.
H.M.
HGT.
HDR. HEADER
JOIST
JANITOR
KITCHEN
JOINT
LABORATORY
JOIST HANGER
LAG BOLT
LAVATORY
LAMINATE
J.H.
JAN.
L.B.
LAV.
LAM.
LAB.
KIT.
JT.
JST.
EQUIV.
E.S.
E.W.
EXP.
EXP.B.
EXPO.
EXT.
F.
ENCL.
F.B.
F.BD.
F.BELL
F.B.O.
F.D.
FDN.
F.E.
FH.M.S.
F.HORN
F.F.
F.G.
FGL.
F.H.
F.E.C.
F.A.
FH.W.S.
FIN.
F.H.S.
ENCLOSURE
EQUIVALENT
EACH SIDE
EACH WAY
EXPANSION
EXPANSION BOLT
EXPOSURE
EXTERIOR
FLAT HEAD MACHINE
SCREW
SCREW
FIRE HORN
FIRE HOSE STATION
FLAT HEAD WOOD
FINISH
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER
FINISH FLOOR
FINISH GRADE
FIBERGLASS
FIRE HYDRANT
CABINET
FIRE ALARM
FACE BRICK
FIREBOARD
FIRE BELL
FURNISHED BY OTHERS
FACE
GALV. GALVANIZED
HOLLOW STRUC. STL.H.S.S.
FLUORESCENTFLOUR.
GENERAL CONTRACTORG.C.
E.W.C. ELECTRIC WATER CLOSET
FIRE VALVE CABINETF.V.C.
FOOD SERVICE EQUIPMENT
CONTRACTOR
F.S.E.C.
H.V.A.C. CONTRACTORH.C.
FIRE SUPPRESSION
CONTRACTOR
F.S.C.
PLASTIC LAMINATEP.LAM.
O.H.W.S.
SCREW
OVAL HEAD WOOD
APPROVAL)
PAPER TOWEL DISPENSER
PAPER TOWEL
PARTITION
DOUGLAS FIR
PRESSURE TREATED
REFLECTED CEILING
RADIUS
RUBBER BASE
QUARRY TILE
POLYVINYL-CHLORIDE
RECEPTACLE
R.C.P.
Q.T.
RAD.
R.B.
P.T.D.
PTN.
P.T.R.
P.V.C.
P.T.D.F.
REDWOOD
REFERENCE
REINFORCING
ROOF HATCH
ROUND HEAD METAL
RESILIENT
REFRIGERATOR
ROOF DRAIN
SCREW
ROOM
RAIN WATER LEADER
ROUGH OPENING
ROUND HEAD WOOD
SCREW
RDWD.
R.H.W.S.
R.W.L.
R.O.
RM.
R.H.M.S.
R.H.
RESIL.
REINF.
REFR.
REF.
R.D.
LIGHT
MATERIAL
LOW POINT
LIVE LOAD
LEFT HAND
MAT.
LT.
L.P.
L.L.
L.H.
MANHOLE
MINIMUM
MEDIUM
MANUFACTURER
MEMBRANE
MECHANICAL
MEDICINE CABINET
MACHINE BOLT
METAL
MASONRY OPENING
METAL THRESHOLD
MISCELLANEOUS
MODULAR
MOISTURE RESISTANT
MIRROR
M.C.
M.B.
MIN.
MH.
MFG.
MEMB.
MED.
MECH.
MIR.
MISC.
M.O.
MOD.
M.R.
M.T.
MTL.
MAX. MAXIMUM
NORTH
NATURAL
OVER
NUMBER
NOMINAL
NOT TO SCALE
NOT IN CONTRACT
OBSCURE
OUTSIDE DIAMETER
STUD
OFFICE
OUTSIDE FACE OF
ON CENTER
OVERFLOW
OVERALL
N.T.S.
O/ O.A.
OBS.
O.C.
O.D.
O.F.
OFF.
O.F.S.
(NOT PART OF OSA
N.
NAT.
N.I.C.
NO.
NOM.
PAINT
PLATE
PERFORATED
FOOT
POUNDS PER CUBIC
PANEL EDGE NAILING
PRESSED METAL
PAIR
FRAME
FOOT
POUNDS PER LINEAR
PLYWOOD
POUNDS PER SQUARE
PROPERTY
PLASTER
P.
P.C.F.
P.E.N.
PERF.
PL.
PLAS.
P.L.F.
PLYWD.
P.M.F.
PR.
P.S.F.
PROP.
OPP. OPPOSITE
POINT
PULL STATION
POUNDS PER SQUARE
INCH
P.STA.
PT.
P.S.I.
FOOT
(N) NEW
PLAN
REQUIREDREQD.
NON-COMBUSTIBLENON/COM
PLUMBING CONTRACTORP.C.
MECHANICAL, ELECTRICAL,
PLUMBING
M.E.P.
FRAMED MIRRORMR.
ROBE HOOKR.HK.
MOP HOLDERMP.H.
MOUNTEDMTD.
PAINTEDPTD.
TONGUE AND GROOVE
DRAWINGS
SOUTH
SEE CIVIL DRAWINGS
STORM DRAIN
SOLID CORE WOOD DOOR
DRAWINGS
SHEET
SIMILAR
SLIDING
SHEATHING
SHOWER
SECTION
SEALANT
SEE ELECTRICAL
SOLID BLOCKING
SOAP DISPENSER
SEE ARCHITECTURAL
S.E.D.
SHR.
SHT.
SIM.
SL.
SHTG.
S.BLKG.
S.A.D.
S.
SECT.
SEAL.
S.DISP.
S.D.
S.C.D.
SCWD
SQUARE
DRAWINGS
SPECIFICATION
SOUNDPROOF
DRAWINGS
STATION
STEEL
STORAGE
STANDARD
SUSPENDED
STRUCTURAL
DRAWINGS
STAINLESS STEEL
SEE MECHANICAL
SANITARY SEWER
SEE STRUCTURAL
SQUARE FOOT (FEET)
THICK
TEMPERED
TELEPHONE
TERRAZZO
TACKBOARD
TOP OF CURB
TRANSOM
TOP OF PLATE
TOP OF WALL
TOILET PAPER DISPENSER
TOE NAIL
TOOL JOINT
TOP OF PAVEMENT
TOP AND BOTTOM
T.O.C.
T.O.P.
T.O.PL.
T.O.W.
T.P.D.
TRN.
S.M.D.
SPEC.
S.P.
SQ.
S.S.D.
S. STL.
STO.
STL.
STD.
STA.
S.S.
SQ. FT.
T.B.
T&B.
TEL.
TEMP.
TER.
T&G.
SUSP.
T.J.
T.N.
THK.
STRUC.
S.L.D. SEE LANDSCAPE
TYPICAL
UNLESS NOTED OTHERWISE
URINAL
UNFINISHED
TELEVISION
VENT TO ROOF
VERTICAL
VESTIBULE
VERIFY IN FIELD
VINYL TILE
VINYL COMPOSITION
TILE
VERTICAL GRAIN
WEST
WITH
WINDOW
WOOD
WATER CLOSET
VINYL WALL COVERING
WITHOUT
WEIGHT
YARD
WATER PROOF
WATER HEATER
WATER COOLER
WELDED WIRE FABRIC
WATER RESISTANT
W/O
W.W.F.
W.P.
W.R.
WT.
YD.
T.V.
TYP.
UNF.
U.N.O.
V.C.T.
VERT.
VEST.
V.G.
V.I.F.
UR.
V.W.C.
W.
W/
W.C.
V.T.R.
W.F.
W.H
WDW.
WD.
V.T.
T.S. TUBE STEEL
SELF ADHERED SHEET
MEMBRANE
S.A.S.M.
SELF ADHERED FLEXIBLE
FLASHING
S.A.F.F.
WITHINW/IN
UNDERSIDEU/S
SANITARY NAPKIN
DISPOSAL
S.N.D.
T.S.C.D. TOILET SEAT COVER
DISPENSER
SANITARY NAPKIN
DISPENSER
S.N.V.
TOP OF SEATT.O.S.
SOUND ATTENUATION
BATT
S.A.B.
Name
Elevation
150 SF
S Y M B O L S
N
V.A. FURNISHED / CONTRACTOR
INSTALLED
(VC)
V.A. FURNISHED AND INSTALLED(VV)
SOLID WOOD DOORS.W.D.
Room Name
0' - 0"
O P
E R
A T
IN
G
M E
C H
A N
IS
M
M A
X T
O
PAPER TOWEL DISPENSER
WALL MOUNTED
SOAP DISPENSER
O P
E R
A T
IN
G
M E
C H
A N
IS
M
M A
X T
O
O P
E R
A T
IN
G
M E
C H
A N
IS
M
M A
X T
O
M A
X A
F F
3'
-4
A B
O V
E S
IN
K
T O
B
/O R
E F
L.
S
U R
F A
C E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:0
:2
P
M
GI001
ABBREVIATIONS AND GENERAL
DETAILS
09/15/2021 PRQ NHM
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
1/2" = 1'-0"
TYP. ACCESSIBLE LAVATORY CLEARANCE
1/2" = 1'-0"
TYP FIXTURES AND ACCESSORIES
F
B
D
F
H
1 3 5
ZZ
YY
XX
7.1 6.1
G
ELECTRICAL ROOM
FA126A
MECHANICAL ROOM
FB160
ELEVATOR
E1
TELE COMM
FB137
PRIVATE INFUSION
J144
PRIVATE INFUSION
J145
PATIENT TOILET
J146
MENS TOILET
J141
CORRIDOR
80 SF
VESTIBULE
G101D
73 SF
C-SCA
G101E
76 SF
EQUIPMENT ROOM
G101F
1731 SF
NON-HAZARDOUS
PHARMACY STORAGE
G101
AE101
170' TRAVEL DISTANCE TO EXIT
FE
FE
' C
O M
M O
N P
A T
H O
F T
R A
V E
L
(M A
X
IM
U M
(MAXIMUM 300')
L E G E N D:
EXISTING 2-HOUR FIRE
RATED BARRIER
NOT IN CONTRACT
FE
EXISTING FIRE
EXTINGUISHER
EXISTING EXIT SIGN
A. EGRESS PATHS AND PATH OF TRAVEL SHALL NOT BE AFFECTED
DURING SCOPE OF WORK. CORRIDORS CLOSED FOR
CONSTRUCTION SHALL NOTE IMPEDE EGRESS IN CASE OF
EMERGENCY. REFER TO GI002 FOR CODE INFORMATION.
B. ALL EXISTING SPACES WITHIN THIS PROJECT MEET TRAVEL
DISTANCE REQUIREMENTS.
C. SEE FIRE PROTECTION, PLUMBING, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR MORE INFORMATION.
D. CONTRACTOR SHALL PROVIDE CONSTRUCTION AND INFECTION CONTROL
BARRIERS AROUND WORK ZONES IN ACCORDANCE WITH THE
SPECIFICATIONS.
G E N E R A L N O T E S:
2021 NFPA 101 LIFE SAFETY CODE REVIEW
BUILDINGS 77 / 205
SUMMARY: THE WORK IN THIS SPACE IS LIMITED TO ADDED THREE ROOMS WITHIN AN EXISTING BUSINESS USE TO CREATE PHARMACY STORAGE USES (NON-HAZARDOUS). ANCILLARY WORK WILL BE TO CONNECT THIS SPACE TO ITS DEDICATED MECHANICAL SYSTEM, WHICH INVOLVES FLOOR AND ROOF PENETRATIONS. A RATED FLOOR PENETRATION IS REQUIRED, BUT NO RATED WALLS ARE REQUIRED IN THIS PROJECT. THE SPRINKLER SYSTEM WILL BE MODIFIED TO ACCOMMODATE THE THREE
ROOMS CREATED.
AREA OF WORK = 820 SF
CHAPTER 3 DEFINITIONS
3.3.32.2 SMOKE BARRIER. A CONTINUOUS MEMBRANE, OR A MEMBRANE WITH DISCONTINUITIES CREATED BY PROTECTED OPENINGS, WHERE SUCH MEMBRANE IS DESIGNED AND CONSTRUCTED TO RESTRICT THE MOVEMENT OF SMOKE.
CHAPTER 6 -CLASSIFICATION OF OCCUPANCY AND HAZARD OF CONTENT
6.1.5 EXISTING BUSINESS OCCUPANCY (CHAPTER 39) – NO CHANGE
6.2.2 HAZARD CLASSIFICATION: ORDINARY - NO CHANGE
CHAPTER 7-MEANS OF EGRESS: NO CHANGE
7.3.1.2 OCCUPANT LOAD OF SPACE
BUSINESS USE: (150 GSF / OCCUPANT) EXISTING, NO CHANGE.
CHAPTER 8 -FEATURES OF FIRE PROTECTION: NO CHANGE
8.5.3. FIRE BARRIERS AS SMOKE BARRIERS
A FIRE BARRIER SHALL BE PERMITTED TO BE USED AS A SMOKE BARRIER, PROVIDED THAT IT MEETS THE REQUIREMENTS OF
SECTION 8.5.
CHAPTER 9 -BUILDING SERVICE AND FIRE PROTECTION EQUIPMENT:
MODIFICATION OF EXISTING SPRINKLER IN ACCORDANCE WITH SECTION 9.7.
CHAPTER 10 -INTERIOR FINISH, CONTENTS, AND FURNISHES
10.2.3.1 INTERIOR WALL AND CEILING FINISH MATERIALS TESTED IN ACCORDANCE WITH NFPA 286.
10.2.3.1.1 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE CLASSIFIED IN ACCORDANCE WITH NFPA 286 AND
COMPLY WITH 10.2.3.2.
10.2.3.1.2 MATERIALS TESTED IN ACCORDANCE WITH 10.2.3.1.1 AND COMPLYING WITH 10.2.3.2 SHALL BE CONSIDERED ALSO TO COMPLY WITH THE REQUIREMENTS OF CLASS A, CLASS B, OR CLASS C IN ACCORDANCE WITH 10.2.3.3
10.2.3.2. ACCEPTANCE CRITERIA FOR NFPA 286
(1) DURING THE 40 KW EXPOSURE, FLAMES SHALL NOT SPREAD TO THE CEILING.
(2) THE FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF THE SAMPLE ON ANY WALL OR CEILING.
(3) FLASHOVER, AS DESCRIBED IN NFPA 286, SHALL NOT OCCUR.
(4) THE PEAK HEAT RELEASE RATE THROUGHOUT THE TEST SHALL NOT EXCEED 800 KW.
(5) FOR NEW INSTALLATIONS, THE TOTAL SMOKE RELEASED THROUGH-OUT THE TEST SHALL NOT EXCEED 1000 M2.
10.2.3.3 INTERIOR WALL AND CEILING - CLASSIFICATIONS CHARACTERISTICS.
(1) CLASS A: FLAME SPREAD: 0-25; SMOKE DEV. : 0-450.
(2) CLASS B: FLAME SPREAD: 26-75; SMOKE DEV. : 0-450
(3) CLASS C: FLAME SPREAD: 76-200; SMOKE DEV. : 0-450
10.2.8.1 WALL AND CEILING FINISHES, WHERE SPRINKLED:
CLASS C PERMITTED IN ANY LOCATION WHERE CLASS B IS REQ’D.
CLASS B PERMITTED IN ANY LOCATION WHERE CLASS A IS REQ’D.
CHAPTER 39 -EXISTING BUSINESS OCCUPANCIES
39.2.5.2.1 COMMON PATH OF TRAVEL
COMMON PATH OF TRAVEL SHALL NOT EXCEED 100 FT ON A STORY PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC
SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1)
39.2.6.3. TRAVEL DISTANCE TO EXITS
TRAVEL DISTANCE SHALL NOT EXEED 300 FT IN BUSINESS OCCUPANCIES PROTECTED THOUGHOUT BY AN AUTOMATIC SPRINKLER
SYSTEM IN ACCORDANCE WITH SECTION 9.7.
C O D E N O T E S:
B
D
F
H
1 2 3 5
ZZ
YY
XX
7.1
G
ELEVATOR
E1
WAREHOUSE
G201
230' TRAVEL DISTANCE TO EXIT
30' COMMON PATH OF TRAVEL
FE
(MAXIMUM 100')
(MAXIMUM 300')
TO ROOF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:0
:2
P
M
GI002
FIRST AND SECOND FLOOR
OVERALL AND CODE PLANS
09/15/2021 PRQ NHM
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/8" = 1'-0"
FIRST FLOOR LIFE SAFETY PLAN
No. Revisions: Date:
BID DOCUMENTS 9/08/2021
N
1/8" = 1'-0"
SECOND FLOOR LIFE SAFETY PLAN
3 5
EX. W21X44
EX. W21X44
E X
W
X
E X
W
X
/8
/8
1' - 4"
1' - 2 1/2"
R E
F
/8
/2
NEW OPENING
COORDINATE W/ MECHANICAL
L4X4X1/4
C
S101
D
S101
D
F
H
K
3 5
NEW AHU
REFER TO MECHANICAL
NEW CHILLER
REFER TO MECHANICAL
R E
F
EX. W21X44
EX. W21X44
EX. W21X44
E X
G E
X
G
E X
G E
X
G
E X
G E
X
G
E X
G
EX. W21X44
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
24KCS3
REF.
1' - 0"
7' - 11"
33' - 0"
EX. CROSS BRACING
EX. CROSS BRACING
EX. CROSS BRACING
EX. CROSS BRACING
R E
F
/2
REF.
1' - 1"
9' - 5 1/2"
/2
R E
F
13' - 3 1/2"
REF.
1' - 5"
L4X4X1/4
(TYP. 4 PLACES)
L4X4X1/4
(TYP. 4 PLACES)
L4X4X1/4
(TYP. 4 PLACES)
A
S101
A
S101
A
S101
B
S101
NEW OPENING
NEW OPENING
NEW OPENING
B
S101
B
S101
EXISTING EXISTING
OPNG
SEE PLAN
L4
3/16
3/16
TIE ANGLE TO DECK W/ #12 TEK
SCREWS W/ NUT @ 12" O.C.
OPNG
SEE PLAN
(TYP.)
0' - 2 1/2"
EXISTING METAL
DECK
TIE ANGLE TO DECK W/ #12 TEK
SCREWS W/ NUT @ 12" O.C.
F
EXISTING EXISTING
3/16
3/16
L4
TIE ANGLE TO CONCRETE DECK W/
3/8" ANCHORS (HILTI KH-EZ C OR
EQUAL) W/ 2-1/2" EMBED. @ 12" O.C.
2' - 6 1/2"
OPENING
4' - 8 7/8"0' - 3 1/4"
EXISTING CONCRETE
ON METAL DECK
EXISTING CONCRETE
ON METAL DECK
TIE ANGLE TO CONCRETE DECK W/
3/8" ANCHORS (HILTI KH-EZ C OR
EQUAL) W/ 2-1/2" EMBED. @ 12" O.C.
EXISTING
1' - 2 1/2"1' - 4"(TYP.)
0' - 2 1/2"
L4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:0
:4
P
M
S101
STRUCTURAL PLANS AND
DETAILS
09/15/2021 PM CL
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
1/4" = 1'-0"
SECOND FLOOR FRAMING PLAN
1/4" = 1'-0"
ROOF FRAMING PLAN
A. COORDINATE ALL OPENING LOCATIONS AND SIZES WITH MECHANICAL.
B. ALL STRUCTURAL STEEL ANGLES TO BE ASTM A36. ALL BOLTED CONNECTIONS TO BE ASTM
A325N.
C. CONTRACTOR SHALL FEILD VERIFY ALL NEW ROOF AND FLOOR PENETRATIONS AVOID
EXISTING STRUCTURAL MEMBERS.
G E N E R A L N O T E S:
1/2" = 1'-0" A
SECTION
3/4" = 1'-0" B
SECTION
1/2" = 1'-0" C
SECTION
1/2" = 1'-0" D
SECTION
D
D D F F
B
D
F
3 5
ZZ
YY
XX
7.1
ELEVATOR
E1
CANTEEN RETAIL
G101 1
ELECTRICAL ROOM
FA126A
B
D
F
3 5
ZZ
YY
XX
7.1
ELEVATOR
E1
STORAGE
G201
ELECTRICAL ROOM
FA126A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:0
:1
P
M
AD101
DEMOLITION PLANS
09/15/2021 PRQ NHM
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/8" = 1'-0"
FIRST FLOOR DEMOLITION PLAN
N
1/8" = 1'-0"
SECOND FLOOR DEMOLITION PLAN
THESE NOTES APPLY TO ALL DEMOLITION DRAWINGS AND TO ALL CONTRACTORS AND / OR SUBCONTRACTORS THAT WORK WITHIN
THE BUILDING.
A. ALL MATERIALS INDICATED AS DASHED ARE TO BE REMOVED. THIS INCLUDES ALL FINISHES AND MATERIALS NOT SPECIFICALLY CALLED OUT BUT PERTAINING TO THE INTENDED SCOPE. CONTRACTOR TO COORDINATE ALL ASSOCIATED WORK BETWEEN ALL
TRADES.
B. CONTRACTORS SHALL BE RESPONSIBLE FOR VISITING THE SITE TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS. THESE DEMOLITION SHEETS SHALL SERVE TO AID THE CONTRACTOR IN THE EVALUATION OF THE EXTENT OF DEMOLITION: BUT SHALL
NOT BE HELD TO BE ALL INCLUSIVE.
C. CONTRACTORS SHALL FIELD INSPECT ALL DEMOLITION WORK PRIOR TO REMOVAL, TO ENSURE SUCH REMOVAL DOES NOT IMPAIR STRUCTURAL INTEGRITY OF THE EXISTING BUILDING. IF THE INSPECTION INDICATES THAT THE STRUCTURAL INTEGRITY MAY BE
COMPROMISED, NOTIFY THE COR IMMEDIATELY.
D. ALL CONSTRUCTION AREAS ASSOCIATED WORK AREAS SHALL BE KEPT CLEAN BY THE CONTRACTOR - DAILY.
E. CONTRACTOR SHALL COORDINATE EXTENT OF DEMOLITION WORK REQUIRED WITH WORK SHOWN ON PROPOSED FLOOR PLANS.
F. PROTECT ALL EXISTING WORK TO REMAIN & REPAIR DAMAGED AREAS TO MATCH EXISTING ADJACENT SURFACES UNLESS NOTED
OTHERWISE.
G. CONTRACTOR SHALL COORDINATE DEMOLITION ACTIVITIES WITH COR SO AS TO MAINTAIN FULL FUNCTIONALITY OF ADJACENT
OCCUPIED SPACES.
H. CONTRACTOR SHALL MAINTAIN MEANS OF EGRESS PATHWAYS AT ALL TIMES. COORDINATE ALTERNATE PROVISIONS AND OBTAIN APPROVAL FROM OWNER AND AUTHORITY HAVING JURISDICTION IF EXISTING MEANS OF EGRESS MUST BE COMPROMISED.
I. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK.
COORDINATE ALL DEMOLITION/CONSTRUCTION DEBRIS PATH OF TRAVEL AND INTERIM LIFE SAFETY MEASURES (ILSM) WITH THE COR. ALL INTERIOR DOORS THAT LEAD TO THE CONSTRUCTION SITE SHALL BE POSTED AS PER THE ILSM PLAN. THE ROUTES
MUST BE RETURNED TO THEIR ORIGINAL CONDITION AT THE END OF THE PROJECT.
J. HALF-TONED ITEMS INDICATE EXISTING CONSTRUCTION TO BE PROTECTED & REMAIN.
K. WHERE EXISTING FINISHES ARE TO BE REMOVED, PATCH & PREPARE SUBSTRATE TO RECEIVE NEW FINISHES IN ACCORDANCE
WITH NEW FINISH MATERIAL MANUFACTURER'S RECOMMENDATIONS.
L. UTILITIES THAT REMAIN, WITHIN EXISTING WALLS TO BE DEMOLISHED SHALL BE REROUTED AS REQUIRED TO FACILITATE THE
NEW PLAN CONFIGURATION.
M. ALL UTILITY SYSTEM & OTHER COMPONENTS THAT ARE SCHEDULED FOR DISCONNECTION AND REMOVAL SHALL BE REMOVED IN THEIR ENTIRETY. APPLIES TO ALL PENETRATIONS AT FLOORS, ROOF, ETC. "DISCONNECT CAP & ABANDON IN PLACE" IS NOT ACCEPTABLE - UNLESS SPECIFICALLY NOTED OTHERWISE ANY FIRE RESISTIVE 'MEMBER' OR 'THROUGH' PENETRATIONS RESULTING FROM SUCH DEMOLITION WORK SHALL BE FIRESTOPPED OR SEALED IN ACCORDANCE WITH NFPA FOR THE
NECESSARY RATING PROTECTIONS.
N. REFER TO FLOOR PLANS FOR NEW SINK LOCATION. COORDINATE LOCATION WITH EXISTING STRUCTURE AND AVOID DRILLING
THRU JOIST.
O. ALL CUTTING AND PATCHING REQUIRED FOR NEW MECHANICAL AND ELECTRICAL WORK IN ALL EXISTING SPACES SHALL BE BY
THE RESPECTIVE CONTRACTORS.
P. MATCH ALL FINISHED WALL THICKNESS WHERE NEW WALLS OCCUR IN LINE WITH EXISTING WALLS WHILE MAINTAINING REQUIRED
WALL RATING.
Q. CONTRACTOR TO PROVIDE FIRE, SMOKE, DIRT, DUST & NOISE CONTAINMENT BARRIERS BETWEEN THE WORK AREA & THE
ADJACENT OCCUPIED SPACES. FIRE BARRIERS SHALL BE 1-HR RATED.
R. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE STRUCTURAL INTEGRITY OF ALL STRUCTURAL FRAMING
MEMBERS AND SYSTEMS AT ALL TIMES.
S. REMOVAL OF A PARTICULAR ITEM SHALL INCLUDE ALL RELATED ITEMS, SUCH AS REMOVAL OF WALLS WOULD INCLUDE ASSOCIATED DOORS, HARDWARE, ELECTRICAL, PLUMBING, MECHANICAL, ETC. REFER TO DEMOLITION DRAWINGS FOR MORE INFORMATION. FOR ALL REMOVALS, THE GENERAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES INCLUDING
BUT NOT LIMITED TO MECHANICAL, ELECTRICAL AND PLUMBING.
T. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS REQUIRED UNTIL
PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.
U. NEW OPENINGS IN EXISTING ROOF STRUCTURES FOR NEW WORK MUST BE COORDINATED WITH THE EXISTING STRUCTURE SO
THAT CRITICAL STRUCTURAL MEMBERS ARE NOT DAMAGED.
G E N E R A L D E M O L I T I O N N O T E S:
D R A W I N G N O T E S :
1 STORAGE RACKS REMOVED BY VA PERSONNEL AHEAD OF CONSTRUCTION.
2 REMOVE EXISTING CHAIN LINK GATE, FENCE, AND ASSOCIATED CONNECTIONS - PATCH FLOOR AND MAKE SMOOTH.
3 REMOVE PORTION OF EXISTING COMPOSITE METAL DECK FLOOR SHOWN AS DASHED - COORDINATE OPENING WITH
EXISTING STRUCTURAL - SEE NEW WORK PLANS
BID DOCUMENTS 9/15/2021
A
A
A
F
A
F F
B
D
F
3 5
ZZ
YY
XX
7.1
9' - 6"
ELEVATOR
E1
VESTIBULE
G101D
C-SCA
G101E
NON-HAZARDOUS
PHARMACY STORAGE
G101
EQUIPMENT ROOM
G101F
1 2
AE101 57
D
F
3 5
ZZ
7.1
ELEVATOR
E1
WAREHOUSE
G201
AE101
AE101
AE101
D
F
H
3 5
ZZ
YY
7.1
AE601
AE601
Sim
18' - 2" +/-
18' - 7 1/2" +/-
B
D
F
2 3 5
ZZ
YY
XX
7.1
9' - 0"
9' - 0"
ELEVATOR
E1
NON-HAZARDOUS
PHARMACY STORAGE
G101
EQUIPMENT ROOM
G101F
2' - 9"
17' - 8"
7' - 7" 2
2' - 9"
73 SF
C-SCA
G101E
80 SF
VESTIBULE
G101D
B-2
31" 21" 56"
16"
P-2 P-2 P-2
B-2
P-2
B-2
P-2
EXISTING CMU WALL
L2X2X1/4
(4) 3/8 EXPANSION
ANCHORS W/ 3" EMBED.
3/16
(2) 3/8 EXPANSION ANCHORS
W/ 3" EMBED.ONE BOLT CONNECTION
3" FENCE POST
W/ BASE AND CAP
5' - 0"
3/16
1/8" X 24" HIGH KICKPLATE
BOTH SIDES
(4) 3/8 EXPANSION
ANCHORS W/ 3" EMBED.
(TYP. EACH POST)
TENSION BAR W/
TENSION BAND
3" FENCE POST
W/ BASE AND CAP
CHAIN LINK FABRIC
GATE LATCH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:0
:1
P
M
AE101
FLOOR, REFLECTED CEILING AND
ROOF PLANS
09/15/2021 PRQ NHM
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/4" = 1'-0"
ENLARGED FIRST FLOOR PLAN
N
1/4" = 1'-0"
ENLARGED SECOND FLOOR PLAN
N
1/8" = 1'-0"
ROOF PLAN
A. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION SCHEDULE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE
RESISTANCE DIRECTORY.
B. ALL WALLBOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
C. ALL DIMENSIONS ARE TO COLUMN CENTERLINES OR FINISHED ELEVATION OF WALLS OR SURFACES UNLESS NOTED OTHERWISE.
D. CONTRACTOR TO PROVIDE ALL RELATED FASTENERS, TRIM AND ACCESSORIES FOR INSTALL PRODUCTS PER MANUFACTURER'S
WRITTEN INSTRUCTIONS.
E. REFER TO DEMOLITION DRAWINGS, IF ANY, FOR WORK REQUIRED IN ADVANCE OF CONSTRUCTION AND COORDINATE
ACCORDINGLY.
F. ALL DOOR FRAMES ARE TO BE INSTALLED 4" AWAY OF ADJACENT PERPENDICULAR WALLS UNLESS NOTED OTHERWISE.
G. REFER TO LIFE SAFETY DRAWINGS FOR ADDITIONAL FIRE / SMOKE RATING REQUIREMENTS.
H. REFER TO M.E.P. DRAWINGS FOR ADDITIONAL M.E.P. SPECIFIC INFORMATION.
I. EXISTING CONSTRUCTION TO REMAIN. EXTERIOR WALLS AND COLUMN ENCLOSURES SHALL BE PATCHED AS REQUIRED TO
MATCH ADJACENT NEW CONSTRUCTION AND RECEIVE NEW FINISHES.
J. ALL SMOKE BARRIER WALLS ARE TO EXTEND FROM BACK SIDE OF EXTERIOR WALL SHEATHING OR ANOTHER SMOKE BARRIER
WALL
K. COLD-FORMED STEEL FRAMING SUPPLIER SHALL PROVIDE ENGINEERED DRAWINGS.
L. PATCH AND REPAIR FIREPROOFING AS NECESSARY TO MAINTAIN MINIMUM THICKNESS SET FORTH ON G001.
M. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE.
WHERE PARTITIONS OF DIFFERENT THICKNESS MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE FACES ARE STRAIGHT
AND CONTINUOUS, UNLESS NOTED OTHERWISE.
N. METAL STUD GAUGES SCHEDULED ARE THE MINIMUM REQUIRED, AND MAY BE INCREASED BY SPECIFICATIONS TO ACCOMMODATE LOADS, FINISHES, OR UNBRACED CEILING HEIGHT LIMITS. DO NOT CONSIDER CEILING SYSTEM(S) AS A PARTITION
BRACING ELEMENT.
O. PROVIDE DOUBLE 0.0312" STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN PARTITION ENDS, AND WHERE
PARTITION IS TO RECEIVE WALL MOUNTED SHELVES, CASEWORK, PLUMBING FIXTURES, ETC.
P. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL WALL STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
Q. REFER TO CEILING PLAN AND FINISH LEGEND FOR CEILING FINISH INFORMATION
R. ALL CEILINGS TO BE 9'-0" ABOVE FINISH FLOOR UNLESS NOTED OTHERWISE.
S. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
T. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
U. VERIFY CEILING HEIGHTS WITH STRUCTURE AND DUCTWORK.
V. ALL GYPSUM BOARD CEILINGS TO RECEIVE DESIGNATED CEILING PAINT.
G E N E R A L N O T E S :
D R A W I N G N O T E S :
1 PAPER TOWEL DISPENSER (VC).
2 SOAP DISPENSER (VC).
3 WALL-MOUNTED STAINLESS STEEL FRAMED MIRROR - 24" WIDE X 36" HIGH.
4 WALL MOUNTED LAVATORY WITH DRENCH HOSE EYE WASH - SEE PLUMBING DRAWINGS.
5 WASTE RECEPTACLE (VV).
6 FISHEYE CAMERA - SEE ELECTRICAL DRAWINGS (VV).
7 SINK SHROUD.
8 CLASS II TYPE A2 BIOLOGICAL SAFETY CABINET (VC).
9 PROVIDE FIRE STOP COMPOSITE SHEETS FOR RATED OPENING OVER UNISTRUT FRAMING - REFER TO STRUCTURAL FOR
SLAB OPENING SIZE AND LOCATION.
10 ROOFTOP MECHANICAL EQUIPMENT - REFER TO MECHANICAL AND MANUFACTURER DRAWINGS FOR DIMENSIONS.
11 TOUCHLESS AUTOMATIC DOOR OPERATOR - SEE ELECTRICAL AND TELECOMMUNICATIONS DRAWINGS.
12 MECHANICAL EQUIPMENT - REFER TO MECHANICAL DRAWINGS.
13 FLOOR PENETRATION ABOVE - REFER TO MECHANICAL AND STRUCTURAL DRAWINGS.
No. Revisions: Date:
BID DOCUMENTS 9/15/2021
N
1/4" = 1'-0"
FIRST FLOOR REFLECTED CEILING PLAN
1/4" = 1'-0"
G101D VESTIBULE - EAST ELEVATION
1/4" = 1'-0"
G101D VESTIBULE - NORTH ELEVATION
1/4" = 1'-0"
G101D VESTIBULE - WEST ELEVATION
1/2" = 1'-0"
SECTION
1/2" = 1'-0"
SECTION
03-ROOF
41' - 8"
EXISTING ROOF
SUBSTRATE
1 1/4" HOT DIPPED
GALVANIZED ROOF
NAILS
1/2" VINYL WEATHER
STRIP
BONDING ADHESIVE
WOOD NAILER
EXTRUDED ALUMINUM SUNWAVE
DAYLIGHTING FRAME
STAINLESS STEEL SCREWS WITH
RUBBER WASHER
CURB FLASHING OR MEMBRANE OR
SLEVE
INSULATED METAL CURB
LAP SPLICE
MECHANICAL EQUIPMENT
REFER TO
MANUFACTURER INFO.
EXISTING EPDM
ROOFING
INSULATION
S E
E S
C H
E D
U L E
SEE SCHEDULE
S E
E S
C H
E D
U L E
SEE SCHEDULE
F FG
6" 6"
TEMPERED
SCHEDULED PARTITION
METAL RUNNER
HOLLOW METAL FRAME 16G
DOOR AS SCHEDULED
1/2"
2"
1/2"
VARIES
SEE WALL TYPES
SCHEDULED PARTITION
DOUBLE METAL STUD AT JAMB, TYP.
HOLLOW METAL FRAME 16G
DOOR AS SCHEDULED
1/2" 1/2"
2"
VARIES
CAULK AT PERIMETER OF
DOOR FRAMES, TYP.
SEE WALL TYPES
S E
E S
C H
E D
U L E
SEE SCHEDULE 2"2"
G101
M A
X
M
IN
/2
MOUNT ON LATCH
SIDE OF DOOR 2"
5/8" GYPSUM BOARD
3-5/8" 16 GA COLD-FORMED
STEEL FRAMING AT 16" O.C.
3 1/2" ACOUSTIC
INSULATION
6" 16 GA. COLD-FORMED
STEEL FRAMING
9"
" Vestibule
G101D
CHARACTERS SHALL BE
ACCOMPANIED BY GRADE 2
BRAILLE.
CHARACTERS SHALL BE 5/8"
HIGH MINIMUM AND 2" HIGH
MAXIMUM.
SIGN SHALL HAVE 1/4"
BACKPLATE
REFER TO SIGNAGE SPEC
10 14 00.
5/8" GYPSUM WALLBOARD
" EPOXY BASE
1/2" CEMENT BOARD
J-BEAD TRIM
FLUSH EPOXY GYPSUM TRANSITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:0
:1
P
M
AE601
DOOR DETAILS AND SCHEDULES
09/15/2021 PRQ NHM
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
3" = 1'-0"
ROOF DETAIL
No. Revisions: Date:
BID DOCUMENTS 9/15/2021
B-1
F I N I S H L E G E N D
MARK DESCRIPTION BASIS OF DESIGN STYLE/COLOR COMMENTS
ROOM FINISH SCHEDULE NOTES:
1. ONLY ADD BASE AND PAINT TO THE NEWLY CONSTRUCTED WALLS IN THE SPACE.
B-2
P-1
P-2
RES
RUBBER BASE
EPOXY BASE
PAINT - TYPE 1
PAINT - TYPE 2
RESINOUS FLOORING
JOHNSONITE
TBD
SHERWIN WILLIAMS
SHERWIN WILLIAMS
TBD
MATCH EXISTING BROWN
TBD
LATEX EGGSHELL
LATEX FLAT
TBD
4" HEIGHT
4" INTEGRAL BASE; FLUSH
WITH VERTICAL SURFACE
GENERAL WALL PAINT
GENERAL CEILING PAINT
DOOR SCHEDULE NOTES:
1. REFER TO HARDWARE SPEC 08 71 00.
2. ALL DOOR FRAMES SHALL BE PAINTED P-4.
P-3 PAINT - TYPE 3
SHERWIN WILLIAMS WATERBASED SEMI-GLOSS GENERAL DOOR FRAME PAINTP-4 PAINT - TYPE 4
SHERWIN WILLIAMS TBD EPOXY WALL PAINT
D O O R S C H E D U L E
NUMBER
HARDWARE
SET QUANTITY WIDTH HEIGHT THICKNESS
FRAME
MATERIAL
FRAME
ELEVATION
DOOR
MATERIAL
DOOR
ELEVATION FIRE RATING NOTES
101 IR 1 3' - 0" 7' - 0" 0' - 1 3/4" HM 1 HM FG NONE
102 IR 1 3' - 0" 7' - 0" 0' - 1 3/4" HM 1 HM FG NONE
103 5B 1 3' - 0" 7' - 0" 0' - 1 3/4" HM 1 HM F NONE
R O O M F I N I S H S C H E D U L E
Number ROOM NAME
CEILING
FINISH
FLOOR
FINISH BASE FINISH
NORTH
WALL FINISH
EAST WALL
FINISH
SOUTH
WALL FINISH
WEST WALL
FINISH NOTES
G101 NON-HAZARDOUS
PHARMACY STORAGE
EXPOSED EXPOSED B-1 EXISTING P-1 P-1 EXISTING 1
G101D VESTIBULE P-3 RES B-2 P-2 P-2 P-2 P-2
G101E C-SCA P-3 RES B-2 P-2 P-2 P-2 P-2
G101F EQUIPMENT ROOM EXPOSED EXPOSED B-1 P-1 EXISTING EXISTING P-1
1/2" = 1'-0"
DOOR ELEVATIONS
3" = 1'-0"
DOOR HEAD DETAIL
3" = 1'-0"
DOOR JAMB DETAIL
1/2" = 1'-0"
FRAME ELEVATIONS
1/2" = 1'-0"
ACCESSIBLE DOOR SIGNAGE
1 1/2" = 1'-0"
DETAIL AT CEILING
3" = 1'-0"
SIGNAGE DETAILS
3" = 1'-0"
DETAIL AT EPOXY BASE
B
D
F
1 2 3 4 5 6
ZZ
YY
XX
7.1 6.1
NON-HAZARDOUS
PHARMACY STORAGE
G101F
VESTIBULE
G101D
C-SCA
G101E
EQUIP.
G101G
F I R E H A Z A R D L E G E N D
LIGHT HAZARD
ORDINARY HAZARD GROUP 1
ORDINARY HAZARD GROUP 2
(E) TEST
CONNECTION
(E) FP
(E) FP(E) FP
(E) FP
(E) FP
(E) FP
(E) FP
G E N E R A L N O T E S :
A. PROJECT AREA IS CURRENTLY PROTECTED WITH AN AUTOMATIC WET-PIPE FIRE SUPPRESSION SYSTEM.
INSTALL NEW SPRINKLERS AND REWORK PIPING FROM FROM EXISTING SYSTEM AS NECESSARY TO PROVIDE FIRE SUPPRESSION IN RENOVATED AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE
PROTECTION MANUAL.
B. LOCATIONS AND SIZES OF EXISTING PIPING SHOWN ON THIS DRAWING HAVE BEEN DETERMINED FROM A REVIEW OF EXISTING DRAWINGS AND/OR SITE INVESTIGATION WHERE POSSIBLE. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DRAWINGS WHICH MAY IMPACT THE PROGRESS OF WORK SHALL BE BROUGHT
TO THE ATTENTION OF THE VA IN WRITING BEFORE PROCEEDING WITH THE WORK.
C. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN SUCH EQUIPMENT
CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHAGRE PATTERN AND COVERAGE.
D. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO PROVIDE A
COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER CONSTRUCTION.
E. PIPE SIZES SHALL BE DETERMINED BY CONTRACTOR BY PIPE HYDRAULIC CALCULATION METHOD IN ACCORDANCE WITH NFPA 13. CONTRACTOR TO DETERMINE LOCATIONS OF SPRINKLER HEADS AND BRANCH
PIPING AND SUBMIT DESIGN FOR FIRE PROTECTION ENGINEER REVIEW.
F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THIS SHEET IS TO CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
G. COORDINATE SPRINKLER LOCATIONS IN AREAS WITH FINISHED CEILINGS WITH ALL CEILING DEVICES
(LIGHTS, DIFFUSERS, ETC.).
H. SPRINKLERS IN AREAS WITHOUT CEILINGS SHALL BE QUICK RESPONSE UPRIGHT TYPE WITH BRASS FINISH.
I. SYSTEM PIPING MUST BE PITCHED AND DRAINED IN ACCORDANCE WITH NFPA 13.
J. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE PARTITIONS, AND
FIRE EXTINGUISHER CABINETS.
K. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR WORK. PATCH TO MATCH SURROUNDING CONDITIONS WITH MATERIALS AND WORKMANSHIP ACCEPTABLE TO THE VA COR.
L. CONTRACTOR MAY PENETRATE WALLS AS REQUIRED FOR THE INSTALLATION OF THIS WORK. REFER TO SPECIFICATION SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS FOR PENETRATIONS THROUGH FIRE AND
SMOKE BARRIERS.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD
ORDINARY HAZARD
GROUP I
ORDINARY HAZARD
GROUP II
0.10 GPM/SF OVER 1500
SF
0.15 GPM/SF OVER 1500
SF
0.20 GPM/SF OVER 1500
SF
100 GPM
250 GPM
250 GPM
30 MIN
60 MIN
90 MIN
QR; K = 5.6 OR K = 8.0
QR; K = 5.6 OR K = 8.0
QR; K = 5.6 OR K = 8.0
BASE AREA
BASE AREA
BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
1 SPRINKLER PER 130 SF
1 SPRINKLER PER 130 SF
A B B R E V I A T I O N S :
COR CONTRACTING OFFICER'S REPRESENTATIVE
(E) EXISTING
GPM GALLONS PER MINUTE
FP FIRE PROTECTION (WET-PIPE)
MIN MINUTES
PSI POUNDS PER SQUARE INCH
QR QUICK RESPONSE
SF SQUARE FEET
L E G E N D :
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
PIPE UP
PIPE DOWN
PIPING CONTINUATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:1
:2
A
M
FX101
FIRST FLOOR FIRE SUPPRESSION
PLAN
09/15/2021 GP GP
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/4" = 1'-0"
FIRST FLOOR FIRE SUPPRESSION PLAN
No. Revisions: Date:
BID DOCUMENTS 9/15/2021
D R A W I N G N O T E S :
1 SPRINKLERS IN THIS ROOM SHALL BE QUICK RESPONSE INSTITUTIONAL PENDANT TYPE.
2 SPRINKLERS IN THIS ROOM SHALL BE QUICK RESPONSE CHROME PLATED PENDANT TYPE.
09/15/2021
A
A
B
D
F
3 4 5 6
ZZ
YY
XX
7.1 6.1
(E) 4" V UP
4" SAN UP
1/2" DCW UP
2" V UP
3/4" DCW UP
(E) 1 1/4" DCW
(E) 8" SAN
(E) 3" V UP
1 1/2" SAN UP
4" SAN
B
D
F
3 4 5 6
ZZ
YY
XX
7.1 6.1
NON-HAZARDOUS
PHARMACY STORAGE
G101F
VESTIBULE
G101D
C-SCA
G101E
EQUIP.
G101G
TP-1
4" FD-E
P-418
(E) 4" V UP & DN
(E) 3" V UP & DN
1/2" DCW DN
2" V DN
1 1/2" SAN DN
P-708
3/4" DCW DN
3/4" DCW
2" V
EWH-15
2" V
G E N E R A L N O T E S :
A. LOCATIONS AND SIZES OF EXISTING PIPING SHOWN ON THIS DRAWING HAVE
BEEN DETERMINED FROM A REVIEW OF EXISTING DRAWINGS AND/OR SITE
INVESTIGATION WHERE POSSIBLE. CONTRACTOR TO FIELD VERIFY EXISTING
CONDITIONS. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE
WORK SHOWN ON THE CONTRACT DRAWINGS WHICH MAY IMPACT THE
PROGRESS OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE VA IN
WRITING BEFORE PROCEEDING WITH THE WORK.
A B B R E V I A T I O N S :
COR CONTRACTING OFFICER'S REPRESENTATIVE
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
DN DOWN
(E) EXISTING
EWH ELECTRIC WATER HEATER
FD FLOOR DRAIN
NTS NOT TO SCALE
SAN SANITARY
TP TRAP PRIMER
V VENT
L E G E N D :
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
POINT OF CONNECTION BETWEEN NEW AND
EXISTING WORK
PIPE UP
PIPE DOWN
BALL VALVE
PIPING PENETRATION THROUGH FLOOR/ROOF
PIPING CONTINUATION
NEW PIPING
EXISTING PIPING
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DHW
DCW
VENT (SANITARY)
SANITARY SEWER
SAN
V
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:1
:2
A
M
PL101
PLUMBING PLANS
09/15/2021 GP GP
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
N
1/4" = 1'-0"
GROUND FLOOR PLUMBING PLAN
N
1/4" = 1'-0"
FIRST FLOOR PLUMBING PLAN
D R A W I N G N O T E S :
1 CONNECT DOMESTIC WATER PIPING TO EXISTING AT POINT SHOWN.
INSTALL BALL VALVE FOR ISOLATION.
2 CONNECT SANITARY PIPING TO EXISTING AT POINT SHOWN.
3 CONNECT VENT PIPING TO EXISTING AT POINT SHOWN.
4 CORE DRILL THROUGH FIRST FLOOR SLAB FOR INSTALLATION OF PIPING.
REFER TO SUPPORT/ANCHOR FOR PIPE RISERS DETAIL ON SHEET PL501.
5 INSTALL ELECTRIC WATER HEATER (EWH-1) ABOVE CEILING WITH
MANUFACTURER-SUPPLIED WALL MOUNTING BRACKET. WATER HEATER
DRAINS TO FD-E IN EQUIPMENT ROOM. REFER TO EWH DETAIL ON SHEET
PL501.
6 MOUNT EYE WASH ON LAVATORY BACKSPLASH. EYEWASH TO HAVE
SWING-DOWN ACTIVATION AND SWING OVER AND DRAIN TO LAVATORY.
7 INSTALL ELECTRONIC TRAP PRIMER (TP-1) ON WALL TO SERVE TRAP FOR
FD-E.
8 INSTALL 3/4" REDUCED PRESSURE BACKFLOW PREVENTER FOR HVAC
MAKE-UP WATER. REFER TO HVAC DRAWINGS FOR PIPING CONTINUATION.
No. Revisions: Date:
[2100]
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
SIDE VIEW TRAPEZE HANGER FOR UP
TO 1000 LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS
HANGER TYPE 1 - SEE
SPECIFICATIONS
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8"
[200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA. HANGER RODS WITH 36" [900mm] MAX. SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD AT
HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF MIN.
DENSITY) UNDER INSULATION
SHIELD
INSULATION (VAPOR BARRIER TYPE
IS REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
[2 5m m
1" M
A X
NOTES:
SEE SPECIFER FOR DETAILED
HANGER REQUIREMENTS
ADJUSTABLE CLEVIS
HANGER TYPE 43 - SEE
SPECIFICATIONS
THRU 3/4
THRU [20]
5 FT
[1500]
[25]
[2100]
[1800]
1 1/4 [32]
[2100]
[2100]
1 1/2 [40]
[2700]
[2400]
[50]
[3000]
[2400]
2 1/2 [65]
[3400]
[2700]
[75]
[3700]
[3000]
[100]
[4100]
[3700]
[125]
[4900]
[4000]
[150]
[200]
[250]
[300]
[350]
[400]
[450]
[500]
[600]
[5200]
[5800]
[4100]
[4900]
[6700]
[7000]
[7600]
[8200]
[8500]
[9100]
[9600]
STEEL EXPANSION SHIELD FOR EXISTING CONSTRUCTION
AND INSERTS FOR NEW CONSTRICTION THIS TYPE SHALL
BE USED ONLY IN SLABS OR BEAMS OF 4" [100mm] MIN
DEPTH
3/8" [10mm] MIN DIA EXPANSION BOLTS FOR
EXISTING CONSTRUCTION AND INSERTS FOR NEW
CONSTRUCTION
CONCRETE
FLOOR SLAB
CLIP
ANGLE
NUTS & WASHERS
3/8" [10mm] MIN DIA
HANGER RODS
FOR PIPES UNDER 2" [50mm] IN SIZE USE 1-1/2"x1-1/2"x1/4" [40x40x6.4mm] ANGLE. ALL PIPES 2" [50mm] & LARGER USE 3"x3"x1/4" [75x75x6.4mm] ANGLE
TURNBUCKLE
3/8" [10mm] MIN DIA
HANGER RODS
3/8" [10mm] MIN DIA INSERTS
NEW CONSTRUCTION ONLY.
INSULATION
BOLT (TYPICAL)
FLOOR
SLAB
FIRE-STOPPING
MATERIAL
BOLT
PIPE
PIPE SLEEVE
WHERE SPECIFIED
RISER CLAMP
PIPE
PIPE SLEEVE WHERE
SPECIFIED RISER CLAMP. BOTTOM
CLAMP REQUIRED AT
ANCHOR POINTS ONLY.
ELEVATION
PLAN
RISER CLAMP
NOTES:
1. PROVIDE ANCHORS ONLY WHERE SHOWN ON
DRAWINGS.
2. EXTEND SLEEVE ABOVE FLOOR WHERE SPECIFIED.
MINIMUM 16 GAGE GALVANIZED STEEL
PLATE 12"x48" [300x1200mm] MIN.
SECURED TO A MIN. 4 STUDS PER
LAVATORY
1/4" [6mm]∅ MOLLY BOLT HOLLOW WALL
ANCHOR (1 EA. SIDE OF LAV)
MIN. (3) 1/4" [6mm]
MACHINE BOLTS
W/DOUBLE LOCK NUTS
ON BACK SIDE
MIN. 5 1/4" [131mm]∅
GALV. MACHINE BOLTS
WELDED TO PLATE
1/4" [6mm]
TYP. 1/8"
TYP. [3mm]
A A
PLAN
SECTION A
NOTES:
1.
2.
AT LAVS WITH FOOT PEDAL CONTROLS PROVIDE
AN ADDITIONAL 16 GAGE GALVANIZED STEEL
PLATE 12"x16" [300x600mm] SECURED TO A
MINIMUM OF 2 STUDS PER FOOT PEDAL.
PROVIDE 20 GAGE STUDS WHEN HEIGHT
EXCEEDS 12'-0" [3600mm]
STEEL HANGER BY LAV MFGR
STEEL WALL PLATE
WALL ANCHOR
STUDS
FOR FIXTURE
HEIGHT SEE
ARCHITECTURAL
DRAWINGS
V A
R
IE
S
3' -3
[9 m m
T
O F
LO
O
R
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION
WASTE PIPE VENT PIPE COLD WATER HOT WATER WASTE
FIXTURE UNITS
WATER FIXTURE
UNITS
WRIST BLADE
HANDLES
ELECTRIC
SENSOR
REMARKS
IN [mm] IN [mm] IN [mm] IN [mm]
P-418
LAVATORY, WALL MOUNTED,
SENSOR OPERATED
1.25 [ 30 ] 1.5 [ 40 ] .5 [ 15 ] .5 [ 15 ] 1 2 NO YES 1
P-708 EYE WASH, WALL MOUNTED .5 [ 15 ] .5 [ 15 ] 0 0 N/A NO 2, 3
REMARKS:
1. PROVIDE WITH THERMOSTATIC MIXING VALVE TO LIMIT HOT WATER TEMPERATURE TO 85 °F.
2. PROVIDE WITH THERMOSTATIC MIXING VALVE TO LIMIT HOT WATER TEMPERATURE TO 110 °F.
3. MOUNT ON BACKSPLASH OF P-418. SWING-DOWN ACTIVATION. EYEWASH TO DRAIN TO P-418.
ELECTRIC WATER HEATER SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
SYSTEM AND/OR
SERVICE
TYPE
STORAGE CAPACITY RECOVERY @ 70 °F [21°C] RISE
TIME TO RECOVER
CONTENTS, MINUTES
RELIEF VALVE SETTING
NO OF
ELEMENTS
ELECTIRCAL INPUT
REMARKS
GAL [L] GAL/HR [L/HR] PSIG [kPa]
TOTAL
kW kW PER
ELEMENT
PHASE VOLT
EWH-1 G101D VESTIBULE
DOMESTIC HOT
WATER
POINT OF USE
ELECTRIC TANK
2.5 [ 10 ] 8.8 [ 33 ] 17 150 [ 1000 ] 1 1440 1440 1 120 1, 2, 3, 4
REMARKS:
1. MOUNT ABOVE CEILING ON WALL WITH MANUFACTURER-SUPPLIED WALL BRACKET. REFER TO EWH-1 DETAIL ON THIS SHEET.
2. INSTALL PER WATER HEATER MANUFACTURER'S INSTRUCTIONS.
3. ROUTE DRAIN LINES FOR DRAIN PAN AND T&P RELIEF ABOVE CEILING TO FD-E IN ROOM G101G. PROVIDE AIR GAP OF MINIMUM (2) WATER HEATER DRAIN PIPE DIAMETERS ABOVE FD-E.
4. SET OUTLET WATER TEMPERATURE TO 130 °F [54°C].
EWH-1
P-708
P-418
TP-1
(E) 1 1/4" DCW
3/4" DCW
3/4" DCW
1/2" DHW
3/4" DCW
FIRST FLOOR
TO FD-E TRAP
FIRST FLOOR
THERMOSTATIC MIXING
VALVE FOR EYEWASH
1/2" DCW
3/4" HVAC MAKE-UP
WATER
3/4" REDUCED PRESSURE
BACKFLOW PREVENTER
(E) 8" SAN
(E) 8" SAN
4" SAN
2" V
FD-E 4" SAN
1 1/2" SAN
P-418
1 1/2" SAN
(E) 3" V
2" V
1 1/2" V
1 1/2" V FIRST FLOOR
FIRST FLOOR
FIRST FLOOR
2" V
1 1/2" WALL
CLEANOUT
DRAIN VALVE
EWH-1
DRAIN PAN
1/2" DCW
1/2" DHW
TEMPERATURE & PRESSURE
RELIEF VALVE
HEAT TRAP
(6" MINIMUM)
ROUTE TO FD-E, PROVIDE
MINIMUM AIR GAP OF (2) PIPE
DIAMETERS
UNION (TYPICAL)
SHUT OFF VALVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
205/77
C U s e rs
\c ra ig \D o c u m e n ts \F
F E
M t H o m e C
-S C
A c ra ig .l ie g ib e l@ ff e -s e rv
.c o m
.r v t
/1
/2
:1
:2
A
M
PL501
PLUMBING DETAILS, SCHEDULES,
& ISOMETRICS
09/15/2021 GP GP
CONSTRUCT CONTAINMENT
SEGREGATED COMPOUNDING
AREA (C-SCA)
621-22-106
MOUNTAIN HOME, TENNESSEE
CONSTRUCTION
DOCUMENTS
JAMES H
QUILLEN VA
MEDICAL
CENTER
Approved: Owner
NTS
PIPE HANGERS
NTS
SECURING HANGER RODS IN CONCRETE
NTS
SUPPORT/ANCHOR FOR PIPE RISERS
NTS
LAVATORY MOUNTING DETAIL
NTS
DOMESTIC WATER ISOMETRIC DIAGRAM
NTS
SANITARY & VENT ISOMETRIC DIAGRAM
NTS
EWH-1 DETAIL
No. Revisions: Date: