Drawings Part 3 of 3 C-SCA 621-22-106.pdf

PDF 5 MB Posted

Attached to
Y1DZ--621-22-106 - Construct Containment Segregated Compounding Area (C-CSCA)
Solicitation number
36C24922B0009
Issued by

About this file

This is a presolicitation notice for a construction project to build a Containment Segregated Compounding Area at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project scope includes demolition of existing structures and construction of a new compounding area and associated spaces. The estimated construction cost range is between $500,000 to $1,000,000. The requirement will use sealed bidding procurement per FAR Part 14.101 and is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses. The NAICS code is 236220 and the small business size standard is $39.5 million. The solicitation is expected to be posted on December 28, 2021 and close on January 26, 2022. Questions must be submitted in writing by email to the named Contract Specialist by the solicitation release date and include the project and solicitation numbers in the subject line. Offerors must have an active registration in the System for Award Management and Central Contractor Registration databases at time of offer submission and award. The awarded contractor must also enroll in VETS-4212.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VSMC

See Location on Floor Plans

H

L

AI - Supply Air Static Pressure

SA

BI - High Static Shutdown

H L

AI - Supply Air Humidity

H L

AI - MERV 13 Prefilter Differential Pressure

AI - Preheat Coil Leaving Air Temp

BO - Preheating ON/OFF Control Valve

LPR

LPS

STM

IFB

OA GENERAL EXHAUST

AI - Supply Air Temp

SF

AO - Cooling Valve

CHWS

CHWR

CHW

BO - Supply Fan Start/Stop

BI - Supply Fan Status

AO - Supply Fan VSMC Speed

BI - Supply Fan VSMC Fault

STM

H L

AI - MERV 8 Prefilter Differential Pressure

BO - Outside Air Damper

BI - Freezestat

30 PSIG STM

ZC

PDS PDS

AO - Humidifier Control Valve

BO - Humidifier Isolation Valve

TT TSL

NC

ZC ZC

ZC

ZC

AI - Chilled Water Coil

Leaving Air Temp

TT

IT

MT TT

HPS

SPSTT

AI - Cooling Coil Leaving Water Temperature

ZC

AO - Air to Air Heat Exchanger Bypass Damper

NC TO

BYPASS

LH

AI - MERV 8 Prefilter Differential Pressure

PDS

VSMC

EF

BO - Exhaust Fan Start/Stop

BI - Exhaust Fan Status

AO - Exhaust Fan VSMC Speed

BI - Exhaust Fan VSMC Fault

IT

AAHX-1

AO - IFB Damper ZC

AI - Entering Exhaust Air Temperature

TT

BO - Exhaust Air Damper

ZC

NC

AI - Outside Air Temperature

TT

AI - Air to Air Heat Exchanger Leaving Air Temperature

TT

TT

AI - Leaving Exhaust Air Temperature

C-SCA

G101E

AI - Space Humidity

MT

AI - Supply AirflowAI - Exhaust Airflow

30 5

AIR HANDLING UNIT SEQUENCE OF OPERATION: AHU-1

GENERAL

THE AIR HANDLING UNIT SHALL FUNCTION CONTINUOUSLY IN ORDER TO MAINTAIN TEMPERATURE, HUMIDITY AND PRESSURIZATION SETPOINTS IN THE NEW SEGREGATED COMPOUNDING PHARMACY. THE UNIT SHALL BE

CONTROLLED WITH DIRECT DIGITAL CONTROL ACCORDING TO THE FOLLOWING SEQUENCES.

H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF", THE OUTSIDE AIR DAMPER SHALL BE FULLY CLOSED. WHEN THE UNIT IS "ON" THE OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. THE AIR TO AIR HEAT EXCHANGER BYPASS DAMPER SHALL

BE CLOSED TO THE BYPASS.

ALL SETPOINTS SPECIFIED IN THIS SEQUENCE SHALL BE ADJUSTABLE.

FAN OPERATION

THE SUPPLY FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) SHALL CONTROL THE SUPPLY FAN SPEED TO

MAINTAIN 1" OF STATIC PRESSURE AT THE SUPPLY AIR STATIC PRESSURE SENSOR.

ENABLE STATIC PRESSURE RESET LOGIC 5 MINUTES AFTER THE SUPPLY FAN IS ON. REDUCE THE STATIC PRESSURE SETPOINT BY 0.04” EVERY 2 MINUTES. AS THE STATIC PRESSURE SETPOINT DROPS, THE VAV BOXES DOWNSTREAM WILL OPEN FURTHER. ONCE 1 VAV BOX OPENS MORE THAN 95%, INCREASE THE STATIC PRESSURE SETPOINT BY 0.06” EVERY 2 MINUTES UNTIL ALL VAV BOXES ARE LESS THAN 85% OPEN. BEGIN REDUCING THE STATIC PRESSURE

SETPOINT BY 0.04” EVERY 2 MINUTES TO RESTART THE CONTROL LOOP.

THE HIGH STATIC SHUTDOWN SENSOR SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" OF STATIC PRESSURE. IF STATIC PRESSURE EXCEEDS 3", THE SUPPLY FAN SHALL STOP AND THE UNIT SHALL BE SHUT DOWN.

THE HIGH STATIC SHUTDOWN SENSOR WILL REQUIRE MANUAL RESET AT THE DEVICE.

THE EXHAUST FAN VARIABLE SPEED MOTOR CONTROLLER (VSMC) SHALL CONTROL THE EXHAUST FAN SPEED TO MAINTAIN A CONSTANT EXHAUST AIRFLOW. REFER TO DRAWINGS FOR EXHAUST AIRFLOW SETPOINT.

TEMPERATURE CONTROL

THE AIR HANDLING UNIT SHALL ENTER "COOLING MODE" WHENEVER THE OUTDOOR AIR TEMPERATURE IS ABOVE 48

DEG F AND "HEATING MODE" WHENEVER THE OUTDOOR AIR TEMPERATURE IS BELOW 48 DEG F.

IN COOLING MODE, MODULATE THE COOLING VALVE TO MAINTAIN THE CHILLED WATER COIL LEAVING AIR TEMPERATURE SETPOINT, 48 DEG F. THE PREHEATING VALVE AND HUMIDIFIER ISOLATION VALVE SHALL BE CLOSED.

IN HEATING MODE, THE PREHEATING ON/OFF CONTROL VALVE SHALL OPEN. THE IFB DAMPER SHALL BE OPEN TO THE BYPASS AND SHALL MODULATE CLOSED TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT, 52 DEG F. THE

COOLING VALVE SHALL BE CLOSED AND THE HUMIDIFIER ISOLATION VALVE SHALL BE OPEN.

AIR TO AIR HEAT EXCHANGER BYPASS DAMPER OPERATION

IN COOLING MODE, WHEN THE OUTDOOR AIR TEMPERATURE IS ABOVE THE EXHAUST AIR TEMPERATURE, CLOSE THE BYPASS DAMPER TO THE BYPASS. WHEN THE OUTDOOR AIR TEMPERATURE IS BELOW THE EXHAUST AIR

TEMPERATURE, OPEN THE BYPASS DAMPER TO THE BYPASS.

IN HEATING MODE, MODULATE THE BYPASS DAMPER TO MAINTAIN THE AIR TO AIR HEAT EXCHANGER BYPASS

TEMPERATURE SETPOINT AT 48 DEG F.

AIR TO AIR HEAT EXCHANGER FROST CONTROL

WHENEVER THE LEAVING EXHAUST AIR TEMPERATURE IS BELOW 30 DEG F, MODULATE THE AIR TO AIR HEAT EXCHANGER BYPASS DAMPER OPEN TO THE BYPASS UNTIL THE LEAVING EXHAUST AIR TEMPERATURE RISES TO 35

DEG F, THEN RETURN TO NORMAL OPERATION.

HUMIDITY CONTROL

THE AIR HANDLING UNIT SHALL ENTER "HUMIDIFICATION MODE" WHENEVER THE AIR HANDLING UNIT IS IN HEATING

MODE AND THE SPACE HUMIDITY IN ROOM G101E C-SCA IS BELOW 35%.

IN HUMIDIFICATION MODE, OPEN THE HUMIDIFIER CONTROL VALVE UNTIL THE EXHAUST AIR HUMIDITY IS ABOVE 40%, THEN CLOSE THE HUMIDIFIER CONTROL VALVE.

THE AIR HANDLING UNIT SHALL ENTER "DEHUMIDIFICATION MODE" WHENEVER THE AIR HANDLING UNIT IS IN

COOLING MODE AND THE SPACE HUMIDITY IN ROOM G101E C-SCA IS ABOVE 55%.

IN DEHUMIDIFICATION MODE, FULLY OPEN THE COOLING COIL CONTROL VALVE UNTIL THE SPACE HUMIDITY IN ROOM

G101E C-SCA IS BELOW 50% THEN RETURN TO COOLING MODE VALVE OPERATION.

ALARMS

WHEN THE FREEZESTAT SENSES A TEMPERATURE BELOW 40F, CLOSE THE COOLING VALVE, OPEN THE PREHEATING VALVE AND SEND AN ALARM TO THE OPERATOR WORKSTATION. IF THE FREEZESTAT SENSES A TEMPERATURE BELOW 35 DEG F, SHUT DOWN THE UNIT. THE FREEZESTAT WILL REQUIRE MANUAL RESET AT THE DEVICE.

SEND ALARM TO THE OPERATOR WORKSTATION UPON FAILURE OF THE VSMC FOR THE SUPPLY AND EXHAUST FANS.

THE SUPPLY OR EXHAUST FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DIGITAL CONTROL PANEL OR THE

STARTER BY-PASS. THE FAN SHALL OPERATE AT CONSANT SPEED.

SEND ALARM TO THE OPERATOR WORKSTATION WHEN EITHER THE MERV 8 OR MERV 13 PREFILTER DIFFERENTIAL PRESSURE SENSOR READS A HIGHER DIFFERENTIAL PRESSURE THAN THE CHANGEOVER DIFFERENTIAL PRESSURE

DETERMINED BY THE AIR HANDLING UNIT MANUFACTURER.

IF COOLING MODE IS NOT ENABLED, SEND ALARM TO THE OPERATOR WORKSTATION IF THE SUPPLY AIR HUMIDITY IS

ABOVE 90%.

SEND ALARM TO THE OPERATOR WORKSTATION IF THE SPACE RELATIVE HUMIDITY IS ABOVE 60% DURING COOLING

MODE OR BELOW 30% DURING HEATING MODE.

SEND ALARM TO THE OPERATOR WORKSTATION WHENEVER THE LEAVING EXHAUST AIR TEMPERATURE IS BELOW 30

DEG F.

C-SCA

G101E

VESTIBULE

G101D

BIO-SAFETY

CABINET

P S2

P S1

P

VAV-1

VAV-2

VV-1

VV-2

SEGREGATED COMPOUNDING PHARMACY PRESSURIZATION AND AIRFLOW CONTROL

GENERAL

THE SEGREGATED COMPOUNDING PHARMACY REQUIRES CONTINUOUS AIRFLOW, TEMPERATURE, HUMIDITY, AND

PRESSURE MONITORING AND CONTROL TO MAINTAIN SPACE FUNCTIONALITY.

REFER TO "CV BOX SEQUENCE OF OPERATION" ON THIS SHEET FOR SPACE TEMPERATURE CONTROL.

ALL SETPOINTS SPECIFIED IN THIS SEQUENCE SHALL BE ADJUSTABLE.

ROOM CONTROL: G101E C-SCA

THE AIR FLOW CONTROL VALVE, VV-1, SHALL RESPOND TO UPSTREAM DUCT STATIC PRESSURE AND MODULATE TO

MAINTAIN A CONSTANT EXHAUST AIRFLOW FROM THE BIO-SAFETY CABINET.

THE VAV BOX, VAV-2, SHALL RESPOND TO UPSTREAM DUCT STATIC PRESSURE TO MAINTAIN ITS AIRFLOW SETPOINT.

THE TAB CONTRACTOR SHALL DETERMINE THE AIRFLOW OFFSET REQUIRED TO MAINTAIN -0.02" BETWEEN G101E C- SCA AND G101D VESTIBULE. UPDATE THE AIRFLOW SETPOINT FOR AIR FLOW CONTROL VALVE, VV-2, TO MAINTAIN THE AIRFLOW OFFSET. THE AIR FLOW CONTROL VALVE, VV-2, SHALL RESPOND TO UPSTREAM DUCT STATIC

PRESSURE TO MAINTAIN ITS AIRFLOW SETPOINT.

ROOM CONTROL: G101D VESTIBULE

THE AIRFLOW SETPOINT FOR THE VAV BOX, VAV-1, SHALL BE EQUAL TO THE AIRFLOW OFFSET. THE VAV BOX, VAV-1, SHALL RESPOND TO UPSTREAM DUCT STATIC PRESSURE TO MAINTAIN ITS AIRFLOW SETPOINT.

ALARMS

SEND ALARM TO THE OPERATOR WORKSTATION WHENEVER THE DIFFERENTIAL PRESSURE BETWEEN ROOM PRESSURE SENSOR 1 AND 2 IS BELOW 0.01" OR ABOVE 0.03". DISABLE ALARM WHENEVER THE DOOR SWITCH SENDS A SIGNAL THAT THE DOOR IS OPEN. ONCE THE DOOR IS CLOSED, PROVIDE A 5 MINUTE DELAY BEFORE ACTIVATING

THE ALARM AGAIN.

SEND ALARM TO THE OPERATOR WORKSTATION WHENEVER THERE IS A 10% DIFFERENCE BETWEEN A TERMINAL

UNIT'S AIRFLOW AND ITS SETPOINT.

BIO-SAFETY

CABINET EXHAUST

ROOM EXHAUST

TO AHU-1

TO AHU-1

PC

CRITICAL ENVIRONMENT

CONTROLLER

DOOR

SWITCH

ROOM THERMOSTAT/SENSOR

WALL MOUNTED

48" [1200mm] AFF.

CV BOX CONTROL SEQUENCE

TU

RHC

HWS

HWR

V-1

REHEAT

COIL

AIR

TERMINAL

UNIT

AIR

FLOW

TE

CRITICAL

ENVIRONMENT

CONTROLLER

PC

TT

A. UPON FALL IN SPACE TEMPERATURE BELOW SET

POINT VALVE V-1 WILL MODULATE TO MAINTAIN SET

POINT ± .5°, THE ADJUSTABLE TOLERANCE OF ± .5°

HAS BEEN SELECTED TO PREVENT VALVE HUNTING.

B. THE REVERSE SHALL OCCUR ON RISE IN SPACE

TEMPERATURE.

FE

P-1

NOTES:

1. PIPING DIAGRAM PROVIDES OVERVIEW OF SYSTEM AND MAJOR

COMPONENTS. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH

THIS DIAGRAM IN ADDITION TO EQUIPMENT DETAILS, SPECIFICATIONS, AND

MANUFACTURER'S INSTALLATION REQUIREMENTS.

2. IF BID ITEM #2 IS, ACCEPTED REMOVE WORK ENCLOSED IN BOX ALL

ASSOCIATED POINTS.

P-2

ACCH-1

TT

TT

FS

FT

BI - Pump 1 Status

BO - Pump 1 Start/Stop

AO - Pump 1 ECM Speed

BI - Pump 1 ECM Fault

IT

VSMC

To AHU-1

From AHU-1

BI - Chiller Flow Switch

AI - Chiller Flow

AI - Chiller Entering Water Temperature

AI - Chiller Leaving Water Temperature

BI - Chiller Status

IT

BO - Chiller Start/Stop

To Plant From Plant

NC

NC NC

NO

ZC

BO - Chiller Plant Bypass Valve

ZC

ZC

BO - Chiller Plant Supply Valve

BO - Chiller Plant Return Valve

ZC

BO - Chiller Bypass Valve

BI - Pump 2 Status

BO - Pump 2 Start/Stop

AO - Pump 2 ECM Speed

BI - Pump 2 ECM Fault

IT

VSMC

DP NC

ZC

AO - AHU Bypass Valve

AI - Cooling Coil Differential Pressure Sensor

CHILLED WATER LOOP SEQUENCE OF OPERATION

GENERAL

THE CHILLED WATER SYSTEM SHALL BE ENABLED WHENEVER AHU-1 CALLS FOR MECHANICAL COOLING. UPON RECEIVING THE SIGNAL, THE CHILLED WATER PUMP SHALL START. ONCE CHILLED WATER FLOW THROUGH THE CHILLER IS PROVEN BY THE CHILLER FLOW SWITCH, THE CHILLER SHALL START.

ALL SETPOINTS SPECIFIED IN THIS SEQUENCE SHALL BE ADJUSTABLE.

PUMP OPERATION

THE CHILLED WATER PUMPS, P-1 AND P-2, SHALL OPERATE IN LEAD/STANDBY CONFIGURATION. THE LEAD PUMP SHALL RUN FIRST. UPON FAILURE OF THE LEAD PUMP, THE STANDBY PUMP SHALL RUN AND THE LEAD PUMP SHALL TURN OFF. THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS: USER SELECTABLE MANUALLY THROUGH A SOFTWARE

SWITCH, IF PUMP RUNTIME IS EXCEEDED, AND SCHEDULED (DAILY / WEEKLY / MONTHLY).

THE ENABLED PUMP SHALL MODULATE ECM SPEED TO MAINTAIN A CONSTANT DIFFERENTIAL PRESSURE MEASURED BY THE COOLING COIL DIFFERENTIAL PRESSURE SENSOR. DIFFERENTIAL

PRESSURE SETPOINT SHALL BE DETERMINED IN THE FIELD BY THE TAB CONTRACTOR.

CHILLER OPERATION

THE CHILLER SHALL RESPOND TO CHANGES IN CHILLER ENTERING WATER TEMPERATURE AND STAGE COMPRESSORS ON AND OFF TO MAINTAIN CHILLER LEAVING WATER TEMPERATURE

SETPOINT.

MODULATE THE AHU BYPASS VALVE TO MAINTAIN THE CHILLER MINIMUM FLOW RATE. WHEN THE CHILLED WATER FLOW IS ABOVE THE CHILLER MINIMUM FLOW RATE, CLOSE THE AHU BYPASS

VALVE.

EMERGENCY CHILLED WATER CENTRAL PLANT OPERATION

THE NEW DEDICATED CHILLED WATER LOOP SHALL BE CONNECTED TO THE CENTRAL CHILLED WATER PLANT. UPON FAILURE OF THE NEW CHILLER, OPEN THE CHILLER BYPASS VALVE, OPEN THE CHILLER PLANT RETURN VALVE, OPEN THE CHILLER PLANT SUPPLY VALVE, CLOSE THE CHILLER PLANT BYPASS VALVE, AND CLOSE THE AHU BYPASS VALVE TO UTILIZE CENTRAL PLANT CHILLED

WATER DURING THE SHUTDOWN.

DURING EMERGENCY CHILLED WATER CENTRAL PLANT OPERATION, THE CHILLED WATER PUMP CONTROL SHALL REMAIN THE SAME.

ALARMS

SEND ALARM TO THE OPERATOR WORKSTATION WHEN THE CHILLER LEAVING WATER TEMPERATURE RISES 2 DEG F ABOVE SETPOINT. ACTIVATE ALARM 15 MINUTES AFTER THE CHILLER IS

COMMANDED TO RUN.

SEND ALARM TO THE OPERATOR WORKSTATION WHEN UPON FAILURE OF THE PUMPS OR CHILLER.

VFD

See Location on Floor Plans

EF-1

IT

SPS

BI - Exhaust Fan Status

BO - Exhaust Fan Start/Stop

AO - Exhaust Fan VFD Speed

BI - Exhaust Fan VFD Fault

AI - Exhaust Air Static Pressure

To VV-1

To VV-2

EXHAUST FAN SEQUENCE OF OPERATION: EF-1

GENERAL

THE EXHAUST FAN SHALL FUNCTION CONTINUOUSLY. THE UNIT SHALL BE CONTROLLED WITH DIRECT DIGITAL

CONTROL ACCORDING TO THE FOLLOWING SEQUENCES.

H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR

MAINTENANCE.

ALL SETPOINTS SPECIFIED IN THIS SEQUENCE SHALL BE ADJUSTABLE.

FAN OPERATION

THE EXHAUST FAN VARIABLE FREQUENCY DRIVE (VFD) SHALL CONTROL THE EXHAUST FAN SPEED TO MAINTAIN 0.5"

OF STATIC PRESSURE AT THE EXHAUST AIR STATIC PRESSURE SENSOR.

ALARMS

SEND ALARM TO THE OPERATOR WORKSTATION UPON FAILURE OF THE VSMC FOR THE EXHAUST FAN. THE EXHAUST FAN SHALL BE STARTED/STOPPED MANUALLY AT THE DIGITAL CONTROL PANEL OR THE STARTER BY-PASS. THE FAN

SHALL OPERATE AT CONSANT SPEED.

SEND ALARM TO THE OPERATOR WORKSTATION AND SHUT DOWN THE EXHAUST FAN IF THE EXHAUST AIR STATIC

PRESSURE FALLS BELOW -3".

EF-1 Hardware Points Software Points

Point # Point Name AI AO BI BO AV BV Loop Sched Trend Alarm Show On Graphic

1 Exhaust Air Static Pressure x x x x

2 Exhaust Fan VFD Speed x x x

3 Exhaust Fan Status x x x

4 Exhaust Fan VFD Fault x x x

5 Exhaust Fan Start/Stop x x x

- Exhaust Air Static Pressure Setpoint x x x

AIR TERMINAL UNITS Hardware Points Software Points

Point Name AI AO BI BO AV BV Loop Sched Trend Alarm Show On Graphic

VAV Box

Airflow x x x x

Zone Damper x x x

Discharge Air Temperature x x x

Control Valve x x x

Room Temperature x x x

Airflow Setpoint x x x

Air Flow Control Valve (VV-1)

Airflow x x x x

Actuator Position x x x

Airflow Setpoint x x x

Air Flow Control Valve (VV-2)

Airflow x x x x

Actuator Position x x x

Room Diffierential Pressure x x x x

Airflow Offset Setpoint x x x

AHU-1 Hardware Points Software Points

Point # Point Name AI AO BI BO AV BV Loop Sched Trend Alarm

Show On Graphic

1 MERV 8 Supply Prefilter Differential Pressure x x x

2 MERV 13 Supply Prefilter Differential Pressure x x x

3 MERV 8 Exhaust Prefilter Differential Pressure x x x

4 Entering Exhaust Air Temperature x x x

5 Leaving Exhaust Air Temperature x x x x

6 Outside Air Temperature x x x

7 Air to Air Heat Exchanger Leaving Air Temperature x x x

8 Preheat Coil Leaving Air Temp x x x

9 Cooling Coil Leaving Water Temperature x x x

10 Chilled Water Coil Leaving Air Temp x x x

11 Supply Air Humidity x x x

12 Supply Air Static Pressure x x x

13 Supply Air Temp x x x

14 Space Humidity x x x x

15 Supply Airflow x x x

16 Exhaust Airflow x x x

17 Air to Air Heat Exchanger Bypass Damper x x x

18 Cooling Valve x x x

19 Humidifier Control Valve x x x

20 IFB Damper x x x

21 Supply Fan VSMC Speed x x x

22 Exhaust Fan VSMC Speed x x x

23 Freezestat x x x x

24 High Static Shutdown x x x x

25 Supply Fan Status x x x

26 Supply Fan VSMC Fault x x x

27 Exhaust Fan Status x x x

28 Exhaust Fan VSMC Fault x x x

29 Outside Air Damper x x

30 Exhaust Air Damper x

31 Preheating ON/OFF Control Valve x x

32 Humidifier Isolation Valve x x

33 Supply Fan Start/Stop x x x

34 Exhaust Fan Start/Stop x x x

- Space Humidity Setpoint x x

- Supply Air Static Pressure Setpoint x x x

- Supply Air Temperature Setpoint x x x

- Mixed Air Temperature Setpoint x

- Exhaust Airflow Setpoint x

- Emergency Shutdown x x x x

- High Supply Air Humidity x

- High Supply Air Static Pressure x

- MERV 8 Supply Prefilter Change Required x x

- MERV 13 Supply Prefilter Change Required x x

- MERV 8 Exhaust Prefilter Change Required x x

CHILLED WATER SYSTEM Hardware Points Software Points

Point # Point Name AI AO BI BO AV BV Loop Sched Trend Alarm

Show On Graphic

1 Chiller Entering Water Temperature x x x

2 Chiller Leaving Water Temperature x x x x

3 Chiller Flow x x x x

4 Cooling Coil Differential Pressure Sensor x x x

5 AHU Bypass Valve x x x

6 Pump 1 ECM Speed x x x

7 Pump 2 ECM Speed x x x

8 Chiller Flow Switch x x x

9 Chiller Status x x x x

10 Pump 1 Status x x

11 Pump 2 Status x x

12 Pump 1 ECM Fault x x x x

13 Pump 2 ECM Fault x x x x

14 Pump 1 Start/Stop x x x

15 Pump 2 Start/Stop x x x

16 Chiller Start/Stop x x x

17 Chiller Bypass Valve x x x

18 Chiller Plant Bypass Valve x x x

19 Chiller Plant Supply Valve x x x

20 Chiller Plant Return Valve x x x

- Cooling Coil Differential Pressure Setpoint x x

- Chiller Leaving Water Temperature Setpoint x x

CONTROLS GENERAL NOTES

1. POINTS SHOWN ARE INTENDED AS AN AID TO THE CONTRACTOR INDICATING THE MINIMUM POINTS REQUIRED FOR CONTROL AND MONITORING. ALL INPUT AND OUTPUT POINTS, AND THEIR REQUIRED INTERFACE AND ACCESSORY HARDWARE, SHALL BE PROVIDED FOR A COMPLETE AND FUNCTION CONTROL SYSTEM. IF ADDITIONAL POINTS ARE REQUIRED TO ACCOMPLISH THE SEQUENCES OF CONTROL SPECIFIED, THESE POINTS, ALONG WITH ADDITIONAL DIRECT DIGITAL CONTROL PANEL(S) (IF REQUIRED), SHALL ALSO BE PROVIDED.

2. POWER SOURCE FOR ALL CONTROLS ASSOCIATED WITH CRITICAL SPACES SHALL BE THE "CRITICAL" BRANCH OF THE EMERGENCY POWER SYSTEM.

3. DIVISION 26 SCOPE OF WORK INCLUDES A POWER SOURCE TO THE MOTOR STARTERS. ALL HVAC POWER SOURCES REQUIRED BEYOND THESE STARTERS OR BEYOND SOURCES EXPLICITLY SHOWN ON THE DIVISION 26 DRAWINGS, SHALL BE PROVIDED UNDER THE TEMPERATURE CONTROLS

WORK.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C U s e rs

\c ra ig \D o c u m e n ts \F

F E

M t H o m e C

-S C

A c ra ig .l ie g ib e l@ ff e -s e rv

.c o m

.r v t

/1

/2

:3

:0

A

M

M701

MECHANICAL CONTROLS

09/15/2021 PDP JPG

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

AHU-1 CONTROLS DIAGRAM

EF-1 CONTROLS DIAGRAM

No. Revisions: Date:

BID DOCUMENTS 9/15/2021

CARD READER

AUTOMATIC DOOR MOTOR

HANDICAP DOOR OPERATOR - TOUCHLESS

ACTIVATION SENSORS

ELECTRIC LATCH

SECURITY CAMERA CCTV - DOME

DURESS/PANIC ALARM

PILOT LIGHT / CHIME

DOOR CONTACT

MD MOTION DETECTOR

CC

CR

EL

AP

X

DC

K

DM

HA

WIRELESS ACCESS POINT

KEY PAD

KC KEY PAD / CARD READER

FIRE ALARM CONTROL PANEL

FIRE ALARM ANNUNCIATOR PANEL

SMOKE DETECTOR

DUCT DETECTOR. "R" INDICATES RETURN DUCT. "S"

INDICATES SUPPLY DUCT.

FACP

FAA

S

S R

FIRE ALARM

DATA/TELEPHONE

SECURITY / ACCESS CONTROL

LIGHTING

POWER

GROUNDING

EMERGENCY LIGHT

EXTERIOR SITE

WIRING ABBREVIATIONS

DATA/TELEPHONE OUTLET. PROVIDE (2) CAT 6a CABLES WITHIN

CONDUIT OR OTHER APPROVED RACEWAY FROM OUTLET TO

NEAREST IT CLOSET OR CABLE TRAY. SUBSCRIPT INDICATES # OF

DATA CABLES.

1' x 4' FIXTURE. UPPERCASE INDICATES TYPE PER THE FIXTURE SCHEDULE.

LOWER CASE LETTER "a" INDICATES SWITCH ZONE.

2' x 4' FIXTURE.

WALL MOUNTED FIXTURE.

INDUSTRIAL FIXTURE.

WALL MOUNTED FIXTURE.

EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED

RECESSED FIXTURE, DOWNLIGHT

3-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.

4-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.

WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH

CEILING MOUNTED OCCUPANCY SENSOR

20 AMP, 125 VOLT SINGLE-POLE TOGGLE SWITCH MOUNTED 42" AFF.

a - CONTROLS LIGHTS WITH "a" DESIGNATION

LIGHTING CONTROLLER

20A, 125V DIMMER SWITCH MOUNTED 42" AFF

2' x 2' FIXTURE.

CEILING MOUNTED DAYLIGHT SENSOR

PHOTOCELL

A1 a a

OS

D

OS

DS

LC#

PC

FLUSH FLOOR MOUNTED NEMA 5-20 DUPLEX RECEPTACLE

UNLESS NOTED OTHERWISE

FLUSH FLOOR MOUNTED NEMA 5-20 QUAD RECEPTACLE

UNLESS NOTED OTHERWISE

NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

SUBSCRIPT: WP - WEATHERPROOF, GF - GROUND FAULT CIRCUIT

INTERRUPTER

NEMA 5-20 DOUBLE DUPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 44" AFF

UNLESS NOTED OTHERWISE

RECEPTACLE, (NEMA CONFIGURATION AS NOTED)

NEMA 5-20 DUPLEX RECEPTACLE WITH USB CHARGER MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

NEMA 5-20 DUPLEX SPLIT RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

NEMA 5-20 SIMPLEX RECEPTACLE MOUNTED 18" AFF

UNLESS NOTED OTHERWISE

JUNCTION BOX

POWER CONNECTION

MOTOR

NON-FUSED DISCONNECT SWITCH. SIZE AS SHOWN

FUSED DISCONNECT SWITCH. SIZE FUSES FOR EQUIPMENT

BASED ON MANUFACTURERS RECOMMENDATIONS

COMBINATION STARTER

SURFACE MOUNTED PANELBOARD OR AUTOMATIC TRANSFER

SWITCH AS INDICATED.

RECESSED MOUNTED PANELBOARD

UNDERGROUND

CONCEALED OR OPEN

FLEXIBLE CONDUIT CONNECTION

EXISTING UNDERGROUND ELECTRICAL LINE.EUP

WP/GF

6-30R

J

EXISTING OVERHEAD ELECTRICAL LINE.

EXISTING UNDERGROUND COMMUNICATION LINE

EXISTING OVERHEAD COMMUNICATION LINE

EXISTING ITEMS TO BE REMOVED

NEW UNDERGROUND PRIMARY

NEW UNDERGROUND SECONDARY

NEW UNDERGROUND COMMUNICATIONS

EXISTING SECTIONALIZER CABINET

NEW PAD MOUNTED TRANSFORMER

NEW ELECTRICAL HANDHOLE

EXISTING COMMUNICATIONS MANHOLE

NEW COMMUNICATIONS MANHOLE

EXISTING POLE MOUNTED LIGHTING FIXTURE

NEW POLE MOUNTED LIGHTING FIXTURE

NEW BOLLARD LIGHT FIXTURE.

EP

EUC

EC

E

UP

US

UC

S

T

H

E

M

M

C

C

AIR TERMINAL

GROUNDING ROD

STATIC GROUNDING RECEPTACLE

CONNECTION TO GROUND

GRID COUNTERPOISE CONDUCTOR

LIGHTNING PROTECTION ROOF CONDUCTOR

LIGHTNING PROTECTION DOWN CONDUCTOR

G

RC

DC

2' x 4' FIXTURE. SOLID FILL INDICATES FIXTURE ON LIFE SAFETY OR

EMERGENCY CIRCUIT.

(WHERE GENERATOR POWER IS NOT AVAILABLE PROVIDE A UNIT

BATTERY AT 1400 LM)

2' x 4' FIXTURE. DIAGONAL FILL INDICATES FIXTURE ON CRITICAL

CIRCUIT.

A AMPERE

AC ABOVE COUNTER, 42"AFF UNLESS OTHERWISE INDICATED

ADA MERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR - TO BOTTOM

AL ALUMINUM

1/C ONE CONDUCTOR

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CU COPPER

E EXISTING

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

EWC ELECTRIC WATER COOLER

FACP FIRE ALARM CONTROL PANEL

FM FREQUENCY MODULATION

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

HACR HEATING AIR CONDITIONING REFRIGERATION

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HT HEIGHT

HZ HERTZ

IDS INTRUSION DETECTION SYSTEM

J JUNCTION BOX

KWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

MCB MAIN CIRCUIT BREAKER

MH MOUNTING HEIGHT - TO CENTER

MLO MAIN LUGS ONLY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NF NON FUSED

NO. NUMBER

OS OCCUPANCY SENSOR

PH PHASE

PIR PASSIVE INFRARED

RGS RIGID GALVANIZED STEEL

SM SINGLE MODE

SPD SURGE PROTECTIVE DEVICE

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

UNO UNLESS NOTED OTHERWISE

V VOLT

VA VOLTAMPERE

VVD VARIABLE VOLUME DAMPER

W WATTS

WP WEATHERPROOF

XFMR TRANSFORMER

FIRE ALARM SPEAKER/STROBEF

NOTES

1. DATA - BLUE

2. PHONE - YELLOW

3. BLANK

4. BLANK

1 2

3 4

LABEL

LABEL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C

U s e rs \i s s a c \D o c u m e n ts

\F F

E

M t H o m e C

-S C

A is s a c h a r.

a n d e rs o n ff e

-s e rv .c o m

.r v t

/1

/2

:1

:3

A

M

E001

LEGEND AND ABBREVIATIONS

09/15/2021 JB IA

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

NOTES:

MOTOR & EQUIPMENT SCHEDULE

MOTOR ID

MOTOR STARTER DISCONNECT CONTROLS FEEDER

S E

E N

O T

E

DESCRIPTION H

O

R S

E P

O W

E R

H

P

CHARACTERISTICS

N E

M A

T Y

P E

TYPE LOCATION F

U

R N

IS

H

E D

B Y

D

IV

TYPE N

E

M A

T Y

P E

D

IS

C S

IZ

E

F U

S E

S

IZ

E

LOCATION F

U

R N

IS

H

E D

B Y

D

IV

TYPE F

U

R N

IS

H

E D

B Y

D

IV

S E

E N

O T

E

N U

M B

E R

O F

C O

N D

U C

T O

R S

W

IR

E S

IZ

E

G R

O U

N D

S

IZ

E

C O

N D

U

IT

S

IZ

E

V O

LT

A

G E

P O

LE

LO

A

D kV A

205-RTU-4-EF MOTOR 5 480 V 3 3.16 EC MOTOR 23 DISC SWITCH 3R 30A NF NEAR MOTOR 26 23 3 12 12 3/4

205-RTU-4-SF MOTOR 5 480 V 3 4.24 EC MOTOR 23 DISC SWITCH 3R 30A NF NEAR MOTOR 26 23 3 12 12 3/4

ACCH-1 MOTOR 2 480 V 3 18.29 EC MOTOR 23 DISC SWITCH 3R 30A NF NEAR MOTOR 26 23 3 10 10 3/4

EF-1 EXHAUST FAN 1 480 V 3 0.91 VFD DRIVE MECH RM

G101F

23 DISC SWITCH 3R 30A NF NEAR MOTOR 26 23 3 12 12 3/4

P-1 MOTOR 1 208 V 2 0.78 EC MOTOR 23 DISC SWITCH 1R 30A NF NEAR MOTOR 26 23 2 12 12 3/4"

P-2 MOTOR 1 208 V 2 0.78 EC MOTOR 23 DISC SWITCH 1R 30A NF NEAR MOTOR 26 23 2 12 12 3/4"

LIGHTING FIXTURE SCHEDULE

IMAGE TYPE DESCRIPTION LOAD LAMP(S)

LUMINOUS

FLUX

COLOR

TEMP.

MOUNTING

RECESSED

SUSPENDED

PENDANT

A1 FLUSH 2X4 LED FLAT PANEL WITH SEAMLESS WELDED AND MITERED FRAME ALUMINUM TRIM, DAMP LOCATION, SEALED FIXTURE, WHITE SATIN ACRYLIC LENS 0-10V DIMMING UNIVERSAL 120-277V 90CRI

74 VA 1 8500 lm 3200 K RECESSED

B1 4' SUSPENDED LED STRIPLIGHT, CODE COMPLIANT 22 GUAGE COLD-ROLLED STEEL, LONG-LIFE LEDS WITH HIGH-EFFICENCY DRIVER, LUMINAIRE SURGE LEVEL PROTECTION, DIFFUSE ACRYLIC LENS, HIGH-GLOSS AND BAKED WHITE ENAMEL, WHITE PAINT FINISH. 120V 80CRI.

72 VA 1 4000 lm 3200 K CHAIN HUNG

C1 LED EMERGENCY LIGHTING FIXTURE ESPECIALLY FOR STAIRWAYS AND HALLWAYS, MOLDED

THERMOPLASTIC WHITE HOUSING, WALL MOUNTED 120 OR 277V.

3 VA LED SURFACE

MOUNTED

No. Revisions: Date:

BID DOCUMENTS 9/15/2021

NTS

FACE PLATE DETAIL

09/15/2021

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C

U s e rs \i s s a c \D o c u m e n ts

\F F

E

M t H o m e C

-S C

A is s a c h a r.

a n d e rs o n ff e

-s e rv .c o m

.r v t

/1

/2

:1

:3

A

M

E500

ELECTRICAL DETAILS

09/15/2021 JB IA

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

Notes:

Total Est. Demand: 7 A

Lighting 148 VA 100.00% 148 VA Total Conn.: 7 A

Power 50 VA 100.00% 50 VA Total Est. Demand: 2662 VA

Receptacle 720 VA 100.00% 720 VA Total Conn. Load: 2468 VA

Motor 1550 VA 112.50% 1744 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 15 A 0 A 7 A

Total Load: 1643 VA 50 VA 775 VA

41 42

39 40

37 -- -- -- 775 VA 148 VA 1 20 A NEW EM LIGHTING FIXTURES 38

35 NEW REDUNDANT CHILLER PUMPS MECH R... 20 A 2 775 VA 0 VA 1 20 A NEW AUTOMATIC DOOR OPENER MOTORS 36

33 NEW PIPE HEAT REGULATOR / THERMOSTAT 20 A 1 0 VA 50 VA 1 20 A NEW SENSOR OPERATED FAUCET 34

31 NEW HOOD MOTOR VFD RM G101G 20 A 1 0 VA 720 VA 1 20 A NEW HOOD EM RECEPTACLE 32

29 (EXIST) 20 A 1 0 VA 0 VA 1 20 A (EXIST) 30

27 -- -- -- 0 VA 0 VA 1 20 A (EXIST) 28

25 (EXIST) 20 A 2 0 VA 0 VA 1 20 A (EXIST) 26

23 (EXIST) 20 A 1 0 VA 0 VA 1 20 A (EXIST) 24

21 (EXIST) 20 A 1 0 VA 0 VA 1 20 A (EXIST) AC-6 CONTROL PANEL SB-160 22

19 (EXIST) DENTAL AIR DRYER 20 A 1 0 VA 0 VA 1 20 A (EXIST) INCUBATOR 208 REC. 2ND FLOOR 20

17 (EXIST) DENTAL AIR DRYER 20 A 1 0 VA 0 VA -- -- -- 18

15 (EXIST) AC-6 CONTROL PANEL SB-160 20 A 1 0 VA 0 VA 2 20 A (EXIST) COLD ROOM 208 REC. 2ND FLOOR 16

13 -- -- -- 0 VA 0 VA 1 20 A (EXIST) COLD ROOM RECEPTACLES 14

11 (EXIST) SB - 160 WATER HEATERS / MECH R... 20 A 2 0 VA 0 VA 1 20 A (EXIST) ELECT. RM. FA REC. & BATTERY LIGHT 12

9 (EXIST) AHU - 4.5 DDC CONTROL PAN 20 A 1 0 VA 0 VA 1 20 A (EXIST) MECH RM. LIGHTING 2ND. FLOOR 10

7 (EXIST) FAN PHARMACY 20 A 1 0 VA 0 VA 1 20 A (EXIST) MECH. RM. RECPT.& BATT. LTS. 1ST ... 8

5 (EXIST) WALK IN INCUBATOR 2ND FLOOR 20 A 1 0 VA 0 VA 1 20 A (EXIST) SPARE 10-28-2015 6

3 (EXIST) WALK IN COLD ROOM 2ND FLOOR 20 A 1 0 VA 0 VA 1 20 A (EXIST) RECIR. PUMP MECH RM. SA 132 4

1 (EXIST) COLD RM. COMPRESSOR 2ND FLOOR 20 A 1 0 VA 0 VA 1 20 A (EXIST) WATER HT. MECH RM. SA 132 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

EXISTING 120V CRITICAL PANEL - CONTRACTOR TO PROVIDE NEW CIRCUIT BREAKERS FOR ALL NEW CIRCUITS

Notes:

Enclosure: Type 1 MCB Rating: 100 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: Phases: 3 Mains Type: MCB

Location: MECHANICAL 103 Volts: 120/208 Wye A.I.C. Rating: 20,000 A

Branch Panel: 77-1-EP

Notes:

Total Est. Demand: 6 A

Total Conn.: 6 A

Total Est. Demand: 2340 VA

Power 1440 VA 100.00% 1440 VA Total Conn. Load: 2340 VA

Receptacle 900 VA 100.00% 900 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 13 A 0 A 9 A

Total Load: 1440 VA 0 VA 900 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 NEW ACCH-1 RECEPTACLE CONNECTION 20 A 1 0 VA 0 VA 1 15 A NEW FIRST FLOOR FAN COIL UNITS 1 & 2 16

13 NEW THERMOSTATIC HANDWASHING HEATER 20 A 1 1440... -- 1 -- (EXIST) SPARE TO BE USED FOR BREAKER... 14

11 NEW RECEPTACLES 20 A 1 900 VA 0 VA -- -- -- 12

9 (EXIST) 120V DUPLEX RECEPTACLE + WIFI... 20 A 1 0 VA 0 VA -- -- -- 10

7 (EXIST) EXH. FAN 77-EF 21 -- 1 -- 0 VA 3 20 A (EXIST) SPARE TO BE USED FOR BREAKER... 8

5 (EXIST) SPARE 20 A 1 0 VA 0 VA 1 20 A (EXIST) MECHANICAL ROOM RECEPTACLES 6

3 (EXIST) MECHANICAL RM LIGHTING 1ST... 20 A 1 0 VA 0 VA 1 20 A (EXIST) OUTSIDE LIGHTING 4

1 (EXIST) MECHANICAL RM. LIGHTING 2ND... 20 A 1 0 VA 0 VA 1 20 A (EXIST) 2ND FLOOR MECHANICAL RM

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

EXISTING 120V PANEL - CONTRACTOR TO PROVIDE NEW CIRCUIT BREAKERS FOR ALL NEW CIRCUITS

Notes:

Enclosure: Type 1 MCB Rating: 70 A

Mounting: Surface Wires: 4 Mains Rating: 70 A

Supply From: Phases: 3 Mains Type: MCB

Location: MECHANICAL 103 Volts: 120/208 Wye A.I.C. Rating: 20,000 A

Branch Panel: 77-1-E

Notes:

Total Est. Demand: 38 A

Total Conn.: 32 A

Total Est. Demand: 31177 VA

Power 0 VA 0.00% 0 VA Total Conn. Load: 26604 VA

Motor 26604 VA 117.19% 31177 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 32 A 32 A 32 A

Total Load: 8868 VA 8868 VA 8868 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 SPACE -- 1 -- -- 1 -- Space 30

27 SPACE -- 1 -- -- 1 -- Space 28

25 SPACE -- 1 -- -- 1 -- Space 26

23 SPACE -- 1 -- -- 1 -- Space 24

21 SPACE -- 1 -- -- 1 -- Space 22

19 SPACE -- 1 -- -- 1 -- Space 20

17 SPACE -- 1 -- -- 1 -- SPACE 18

15 SPACE -- 1 -- -- 1 -- SPACE 16

13 SPACE -- 1 -- -- 1 -- SPACE 14

11 -- -- -- 305 VA 6097... -- -- -- 12

9 -- -- -- 305 VA 6097... -- -- -- 10

7 EF-1 20 A 3 305 VA 6097... 3 30 A ACCH-1 8

5 -- -- -- 1413... 1053... -- -- -- 6

3 -- -- -- 1413... 1053... -- -- -- 4

1 205-RTU-4-SF 15 A 3 1413... 1053... 3 15 A 205-RTU-4-EF 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

NEW 480V PANEL - CONTRACTOR TO PROVIDE NEW CIRCUIT BREAKERS FOR ALL NEW CIRCUITS AND SPARE BREAKERS SHOWN

Notes:

Enclosure: Type 1 MCB Rating: 200 A

Mounting: Surface Wires: 4 Mains Rating: 200 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELECTRICAL ROOM FA126A Volts: 480/277 Wye A.I.C. Rating: 10,000 A

New Branch Panel: 77-1-EQ

EXISTING

EXISTING

No. Revisions: Date:

D

D D F F

S

S

B

D

F

H

K

N

T

1 2 3 4 5 6

ZZ

YY

XX

7.1 6.1 5.2 4.2

G

AP

AP

AP

MD

EXISTING DATA RACKS

1 1

TELE COMM

FB137

NON-HAZARDOUS

PHARMACY STORAGE

G101

CORRIDOR

PRIVATE INFUSION

J144

PRIVATE INFUSION

J145

PATIENT TOILET

J146

MENS TOILET

J141

MECHANICAL ROOM

FB160

ELECTRICAL ROOM

FA126A

AHU-4 (E)

AHU-5 (E)

CC

CC

CC

77-HE1

77-1-E

77-1-EP

EXISTING MCC-77-1-EP

SQUARE D MODEL 6 MCC

B

D

F

H

K

1 2 3 4 5 6

ZZ

YY

XX

7.1 6.1 5.2 4.2

G

2459 SF

Room

G203H

9274 SF

WAREHOUSE

G201

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C

U s e rs \i s s a c \D o c u m e n ts

\F F

E

M t H o m e C

-S C

A is s a c h a r.

a n d e rs o n ff e

-s e rv .c o m

.r v t

/1

/2

:1

:3

A

M

ED101

FIRST & SECOND FLOOR

DEMOLITION PLAN

09/15/2021 JB IA

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

1/8" = 1'-0"

FIRST FLOOR ELECTRICAL DEMOLITION PLAN

D R A W I N G N O T E S :

1 TEMPORARILY REMOVE AND STORE LIGHTING FIXTURES IN A COOL AND DRY LOCATION WHILE PIPE AND DUCTWORK IS BEING INSTALLED. FIXTURE TO BE REINSTALLED IN SAME LOCATION WHEN MECHANICAL INSTALLATIONS ARE FINISHED.

INSTALL FIXTURE AS HIGH AS POSSIBLE TO THE CEILING. MAINTAIN EXISTING CIRCUIT FOR REINSTALLATION OF

LIGHTING FIXTURE.

2 REMOVE AND SALVAGE EXISTING CEILING MOUNTED WIRELESS ACCESS POINT. STORE IN A DRY, COOL LOCATION FOR

LATER INSTALLATION.

3 REMOVE CAMERA AND TERMINATE CABLING AND RETURN CAMERA TO THE VA HOSPITAL.

1/8" = 1'-0"

SECOND FLOOR ELECTRICAL DEMOLITION PLAN

No. Revisions: Date:

A

OS

OS

B

D

F

H

K

N

T

1 2 3 4 5 6

ZZ

YY

XX

7.1 6.1 5.2 4.2

G

77-1-EQ

A1

A1

B1 1 1

AHU-4 (E)

AHU-5 (E)

MECHANICAL ROOM

FB160

ELECTRICAL ROOM

FA126A

EQUIPMENT ROOM

G101F

C-SCA

G101E

VESTIBULE

G101D

NON-HAZARDOUS

PHARMACY STORAGE

G101

CORRIDOR

TELE COMM

FB137

PRIVATE INFUSION

J144

PRIVATE INFUSION

J145

PATIENT TOILET

J146

MENS TOILET

J141

E E

E

E

E

E

E

E

E

E

E

C1

EXISTING MCC-77-1-EP

SQUARE D MODEL 6 MCC

77-1-EP

77-1-E

77-HE1

77-1-EP-38

77-1-EP-38

E

E

E

E

B

D

F

H

K

1 2 3 4 5 6

ZZ

YY

XX

7.1 6.1 5.2 4.2

G

9274 SF

WAREHOUSE

G201

2459 SF

Room

G203H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C

U s e rs \i s s a c \D o c u m e n ts

\F F

E

M t H o m e C

-S C

A is s a c h a r.

a n d e rs o n ff e

-s e rv .c o m

.r v t

/1

/2

:1

:4

A

M

EL101

FIRST & SECOND FLOOR NEW

LIGHTING PLAN

09/15/2021 JB IA

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

1/8" = 1'-0"

FIRST FLOOR NEW LIGHTING PLAN

D R A W I N G N O T E S :

1 REINSTALL LIGHTING FIXTURE IN SAME LOCATION. INSTALL FIXTURE AS HIGH AS POSSIBLE TO THE CEILING. CLEAN AND RE-LAMP FIXTURE PRIOR TO INSTALLATION. CIRCUIT TO LOCAL EXISTING LIGHTING CIRCUIT MAINTAINED DURING

DEMOLITION.

2 CONNECT EMERGENCY LIGHTING FIXTURE TO NEARBY EXISTING LIGHTING FIXTURE CIRCUIT IN ROOM G101

1/8" = 1'-0"

SECOND FLOOR NEW LIGHTING PLAN

No. Revisions: Date:

GF

J J

B

D

F

H

K

N

T

1 2 3 4 5 6

ZZ

YY

XX

7.1 6.1 5.2 4.2

G

77-1-EQ

ADD NEW 200A BUCKET FOR 77-1-EQ.

PROVIDE 200A/3P CIRCUIT BREAKER.EXISTING MCC-77-1-EP

SQUARE D MODEL 6 MCC

P-1

77-1-EP - 31

77-1-E - 11

77-1-E - 11

77-1-EP - 32

77-1-EP - 32

77-1-E - 11

77-1-EP - 32

77-1-EP

77-1-E

77-HE1

EQUIPMENT ROOM

G101F

77-1-E - 11

MECHANICAL ROOM

FB160

ELECTRICAL ROOM

FA126A

77-1-EP - 34

C-SCA

G101E

VESTIBULE

G101D

77-1-E - 13

(3) 3/0, #6 GND, 2"C

77-1-E - 11

77-1-EP - 35,37 EF-1 VFD

77-1-EP - 36

77-1-EP - 36

TELE COMM

FB137

CORRIDOR

PRIVATE INFUSION

J144

PRIVATE INFUSION

J145

PATIENT TOILET

J146

MENS TOILET

J141

NON-HAZARDOUS

PHARMACY STORAGE

G101

77-1-E - 16

77-1-E - 16

77-1-EP - 35,37 P-2

AHU-4 (E)

AHU-5 (E)

77-1-EP - 32

E

E

E

E

E E

E

FCU-1

FCU-2

E

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C

U s e rs \i s s a c \D o c u m e n ts

\F F

E

M t H o m e C

-S C

A is s a c h a r.

a n d e rs o n ff e

-s e rv .c o m

.r v t

/1

/2

:1

:4

A

M

EP101

FIRST FLOOR NEW POWER PLAN

09/15/2021 JB IA

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

1/8" = 1'-0"

FIRST FLOOR NEW POWER PLAN

D R A W I N G N O T E S :

1 120V RECEPTACLE SUPPLIED FOR NEW PHARMACY HOOD.

2 LOW VOLTAGE TRANSFORMER (BY DIVISION 22) BELOW SINK FIXTURE FOR SENSOR OPERATED FAUCET. PROVIDE RECESSED SINGLE GANG J-BOX AT EACH SENSOR OPERATED FAUCET. PROVIDE 0.75" C. FROM J-BOX TO ABOVE ACCESSIBLE CEILING FOR LOW VOLTAGE WIRING. LOW VOLTAGE WIRING BY DIVISION 22. PROVIDE GROMMETED

OPENING. COORDINATE EXACT MOUNTING HEIGHT WITH DIVISION 22 PRIOR TO ROUGH-IN.

3 120V RECEPTACLE SUPPLIED FOR ELECTRONIC TRAP PRIMING DEVICE

4 PROVIDE 120V CIRCUIT TO SUPPLY THERMOSTATIC HANDWASHING HEATER LOCATED ABOVE THE CEILING ABOVE SINK

FIXTURE.

5 AUTOMATIC DOOR OPENER MOTOR CONNECTION

6 PROVIDE AN INTERNAL SPD (SURGE PROTECTIVE DEVICE) TO PANEL 77-1-EQ

7 PROVIDE CORD AND CAP WITH RECEPTACLE FOR DISCONNECT MEANS.

No. Revisions: Date:

D D F F

S

S

D

D 30 F

B

D

F

H

K

N

T

1 2 3 4 5 6

ZZ

YY

XX

7.1 6.1 5.2 4.2

G

AP

AP

MD

77-1-EQ

EXISTING DATA RACKS

DM

CC

CC

DM

E

E

E

E E

HA

HA

HA

HA

AP

TELE COMM

FB137

PRIVATE INFUSION

J144

PRIVATE INFUSION

J145

PATIENT TOILET

J146

MENS TOILET

J141

CORRIDOR

NON-HAZARDOUS

PHARMACY STORAGE

G101

MECHANICAL ROOM

FB160

ELECTRICAL ROOM

FA126A

EQUIPMENT ROOM

G101F

C-SCA

G101E

VESTIBULE

G101DE

E

E

E

E

CC

77-HE1

77-1-E

77-1-EPE

E

E

EXISTING MCC-77-1-EP

SQUARE D MODEL 6 MCC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C

U s e rs \i s s a c \D o c u m e n ts

\F F

E

M t H o m e C

-S C

A is s a c h a r.

a n d e rs o n ff e

-s e rv .c o m

.r v t

/1

/2

:1

:3

A

M

EY101

FIRST FLOOR NEW TECHNOLOGY

PLAN

09/15/2021 JB IA

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

1/8" = 1'-0"

FIRST FLOOR NEW TECHNOLOGY PLAN

D R A W I N G N O T E S :

1 VA PROVIDED AND VA INSTALLED FISHEYE CAMERA AND CABLING. CONTRACTOR TO PROVIDE DATA AND POWER OF

ETHERNET.

2 INSTALL SALVAGED WIRELESS ACCESS POINT IN NEW LOCATION TO DIV. 27 SPECIFICATIONS.

3 MATCH AND CONNECT NEW FIRE ALARM SPEAKER/STROBE WITH EXISTING FIRE ALARM SYSTEM

No. Revisions: Date:

B

F

H

K

N

T

1 2 3 4 5 6

ZZ

YY

XX

7.1 6.1 5.2

205-RTU-4-SF

205-RTU-4-EF

EF-1

ACCH-1

77-1-EQ - 1,3,5

77-1-EQ - 2,4,6

77-1-EQ - 7,9,11

77-1-EQ - 8,10,12

77-1-EP - 33

PIPE HEAT REGULATOR /

THERMOSTAT

RC

WP

77-1-E - 15

UP

UP

RC

RC

RC

RC

RC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

205/77

C

U s e rs \i s s a c \D o c u m e n ts

\F F

E

M t H o m e C

-S C

A is s a c h a r.

a n d e rs o n ff e

-s e rv .c o m

.r v t

/1

/2

:1

:4

A

M

EP103

ROOF NEW POWER PLAN

09/15/2021 JB IA

CONSTRUCT CONTAINMENT

SEGREGATED COMPOUNDING

AREA (C-SCA)

621-22-106

MOUNTAIN HOME, TENNESSEE

CONSTRUCTION

DOCUMENTS

JAMES H

QUILLEN VA

MEDICAL

CENTER

Approved: Owner

1/8" = 1'-0"

ROOF NEW POWER PLAN

D R A W I N G N O T E S :

1 CONNECTION POINT FEED TO ACCH-1 TO SUPPLY THE INCORPORATED RECEPTACLE

2 EXISTING LIGHTNING PROTECTION ROOF CONDUCTOR

3 CONNECT NEW CABLE TO EXISTING LIGHTNING ROOF CONDUCTOR

GENERAL NOTES

A. LIGHTNING TERMINALS TO BE INSTALLED ON TOP OF ALL ROOF MOUNTED EQUIPMENT AND INTERCONNECTED WITH EXISTING

LIGHTNING PROTECTION SYSTEM.

B. LIGHTNING TERMINALS TO BE INSTALLED BY SPLICING ON TO THE HORIZONTAL CONDUCTOR BETWEEN THE AIR TERMINALS

ALONG THE ROOF EDGE.

No. Revisions: Date:

File details come from the government source that posted it. Updated .