Attachment 6 Pages from Pkg 1B Combined Record Drawings.pdf
PDF 298 KB Posted
- Attached to
- J061--Electrical Repair - Medium Voltage Underground Circuit Federal contract opportunity
- Solicitation number
- 36C24826Q0422
About this file
These are electrical legend and abbreviation sheets for the Central Energy Plant of a new hospital facility at VAMC Orlando, Florida. The documents serve as standardized reference guides for interpreting electrical construction drawings and include comprehensive symbol definitions, equipment identification codes, and technical abbreviations used throughout the project's electrical design documentation.
The sheets define identification codes for electrical panels, equipment, and branches (life safety, critical, and normal), along with detailed legends for wiring devices, luminaires, lightning protection systems, occupancy sensors, and control diagrams. Key symbols include circuit breakers, disconnect switches, motor starters, transformers, automatic transfer switches, and various monitoring relays. The documentation establishes conventions for conduit and conductor sizing, branch circuit specifications, and device mounting heights. Additionally, the sheets provide comprehensive abbreviations for electrical terms, equipment types, and construction-related terminology. The record drawings are dated October 29, 2009, with updates recorded as of December 1, 2015, and are prepared by the design professional based on information furnished by others, with a disclaimer that no field verification of correctness has occurred.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 4 Medium Voltage Cables-Splices Terminations.pdf | ||
| Attachment 9 PWS rev1 03-20-2026.docx | DOCX document | |
| Attachment 7 Single Conductor 15KV Shielded MV105 existing cable.pdf | ||
| 36C24826Q0422 0001.docx | DOCX document | |
| Attachment 8 Duct Bank schedule.png | PNG image | |
| Attachment 5 BP 1A Electrical As Builts.pdf | ||
| Attachment 3 Load Interrupter Switchgear info.pdf | ||
| Attachment 01 DOL WD 2015-4553 Rev32 12-03-2025.pdf | ||
| 36C24826Q0422.docx | DOCX document | |
| Attachment 2 LOS Certification.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IDENTIFICATION CODES
SEQUENCE OF PANELS
LIFE SAFETY BRANCH
CRITICAL BRANCH
EQUIPMENT BRANCH
1,2,3 -
S - C - E -
GENERATOR DISTRIBUTIONG -
H - 480Y/277 VOLT
ZONE DESIGNATION (IF ANY)
FLOOR LEVEL (FOR MULTISTORY BUILDINGS ONLY)
C 1 A H S 1
NORMAL BRANCHN -
DISTRIBUTION PANEL (IF PRESENT)D -
UPSU -
H - HOSPITAL
C - CLINIC
W - WAREHOUSE
P - PARKING GARAGE
E - CENTRAL ENERGY PLANT
D - DOMICILIARY
N - NURSING HOME
PANEL CODE:
L - 208Y/120 VOLT
ATS - AUTOMATIC TRANSFER SWITCH
C D ATS - S 1
BUILDING IDENTIFIER
H - HOSPITAL
C - CLINIC
W - WAREHOUSE
P - PARKING GARAGE
E - CENTRAL ENERGY PLANT
D - DOMICILIARY
N - NURSING HOME
EQUIPMENT CODE:
CB - ENCLOSED CIRCUIT BREAKER
DS - DISCONNECT SWITCH
ST - COMBINATION MOTOR STARTER/DISCONNECT SWITCH
1,2,3 - SEQUENCE OF EQUIPMENT (OR EQUIPMENT SERVED)
LIFE SAFETY BRANCH
CRITICAL BRANCH
EQUIPMENT BRANCH
S - C - E -
UPSU -
FOR AUTOMATIC TRANSFER SWITCHES
ZONE DESIGNATION (IF PRESENT)
DB - BUS DUCT CIRCUIT BREAKER
BUILDING IDENTIFIER
VFD - VARIABLE FREQUENCY DRIVE
MCC - MOTOR CONTROL CENTER
SB - SWITCHBOARD
R - CHAPEL
1ALN1-
CONDUIT AND CONDUCTORS
BRANCH CIRCUIT WIRING IN CONDUIT. NO TICK MARKS INDICATE 2#12 AWG
CONDUCTORS AND 1#12 AWG GND IN 3/4" CONDUIT UNLESS OTHERWISE
NOTED. WHEN SHOWN, TICK MARKS INDICATE THE NUMBER OF #12 AWG
CONDUCTORS IN 3/4" CONDUIT. SHORT TICK MARKS INDICATED PHASE
CONDUCTORS, LONG TICK MARKS INDICATE NEUTRAL CONDUCTORS.
GROUND CONDUCTOR NOT SHOWN, PROVIDE #12 AWG GROUND IN EACH
CONDUIT UNLESS OTHERWISE NOTED. EACH BRANCH CIRCUIT SHALL BE
PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. SHARING OF A
NEUTRAL CONDUCTOR BETWEEN TWO OR MORE BRANCH CIRCUITS IS NOT
ACCEPTABLE.
1,3,5
FEEDER SIZE, SEE FEEDER SCHEDULE ON SHEET E-EP7.001.
MOTOR BRANCH CIRCUIT SIZE, SEE MOTOR BRANCH CIRCUIT SCHEDULE
ON SHEET E-EP7.001.
CONDUIT TERMINATION, (C) CAPPED, (B) BUSHED, (G) GROUND BUSHING.
14012
14012
BRANCH CIRCUIT CONCEALED IN CEILING SPACE OR WALL.
PANELBOARD DESIGNATION.
CIRCUIT DESIGNATION. "1,3" INDICATES A TWO-POLE CIRCUIT BREAKER.
"1,3,5" INDICATES A THREE-POLE CIRCUIT BREAKER.
HOMERUN TO PANELBOARD.
LIGHTNING PROTECTION SYSTEM
AIR TERMINAL.
SUBSCRIPTS INDICATE THE FOLLOWING:
A - PARAPET MOUNTED AIR TERMINAL. REFER TO 1/E-EQ5.001 FOR DETAIL.
B - PARAPET MOUNTED AIR TERMINAL. REFER TO 2/E-EQ5.001 FOR DETAIL.
LIGHTNING PROTECTION SYSTEM ROOF CONDUCTOR.
LIGHTNING PROTECTION SYSTEM GROUND LOOP CONDUCTOR. BURY AT 24"
BELOW FINISHED GRADE.
LIGHTNING PROTECTION SYSTEM THRU-ROOF CONNECTOR. SUBSCRIPTS INDICATE
THE FOLLOWING:
THREE GROUND ROD(S), SPACED 10'-0" APART. REFER TO 7/E-EQ5.002 FOR DETAIL.
BONDING CONNECTION.
GL
C1 - AIR TERMINAL MOUNTED ON ROOFTOP EXHAUST FAN. REFER TO 3/E-EQ5.001
FOR DETAIL.
A
DN1
G
D - FLAT ROOF MOUNTED AIR TERMINAL. REFER TO 5/E-EQ5.001 FOR DETAIL.
C2 - AIR TERMINAL MOUNTED ON ROOFTOP SUPPLY FAN. REFER TO 4/E-EQ5.001 FOR
DETAIL.
E - AIR TERMINAL MOUNTED ON COOLING TOWER FAN CYLINDER. REFER TO
6/E-EQ5.001 FOR DETAIL.
DN1 - CONDUCTOR ROUTED FROM CONCRETE PARAPET DOWN TO GRADE. REFER TO
1/E-EQ5.002 FOR DETAIL.
DN2 - CONDUCTOR ROUTED FROM STEEL PARAPET DOWN TO FLAT ROOF. REFER TO 2/E-
EQ5.002 FOR DETAIL.
DN3 - CONDUCTOR ROUTED FROM COOLING TOWER DOWN TO GRADE. REFER TO
3/E-EQ5.002 FOR DETAIL.
20A, 125V SIMPLEX RECEPTACLE. WALL MOUNT AT 18" AFF TO CENTER UON.
WIRING DEVICES
SUBSCRIPTS INDICATE THE FOLLOWING: (FOR ALL RECEPTACLES)
DUPLEX RECEPTACLE WITH INTEGRAL GROUND
FAULT CIRCUIT INTERRUPTER (GFCI).
MOUNT DEVICE ABOVE THE COUNTER TOP. SEE SHEET
NOTE #4 ON THIS SHEET FOR REQUIREMENTS.
TAMPER RESISTANT RECEPTACLE
MOUNT DEVICE AT 48" AFF TO CENTER. OTHER
MOUNTING HEIGHTS AS INDICATED.
G -
OC -
TR -
+48" -
20A, 125V DUPLEX RECEPTACLE FOR ENTERTAINMENT TELEVISION. MOUNT
RECEPTACLE ADJACENT TO THE CABLE TELEVISION OUTLET. SEE
COMMUNICATIONS PLANS FOR EXACT LOCATION AND MOUNTING HEIGHT.
SEE 3/E-ET5.001 FOR DETAIL.
TV
SPECIAL RECEPTACLE WITH NEMA CONFIGURATION AS INDICATED. WALL
MOUNT AT 18" AFF TO CENTER UON.
NEMA
FLUSH FLOOR BOX WITH SEPARATE POWER AND COMMUNICATIONS
COMPARTMENTS. SEE DETAIL 4/E-ET5.001.
20A, 125V SIMPLEX RECEPTACLE CONNECTED TO EMERGENCY POWER.
WALL MOUNT AT 18" AFF TO CENTER UON.
20A, 125V DUPLEX RECEPTACLE CONNECTED TO EMERGENCY POWER. WALL
MOUNT AT 18" AFF TO CENTER UON.
20A, 120/277V SINGLE POLE SWITCH. WALL MOUNT AT 48" AFF TO CENTER
UON. SUBSCRIPTS INDICATE THE FOLLOWING:
THREE WAY3 -
FOUR WAY4 -
INDICATES SWITCH LEGSa,b,c... -
FLUORESCENT DIMMING CONTROLLERFD -
KEY OPERATED SWITCHK -
EXPLOSION PROOFEXP -
WEATHER PROOF COVERWP -
FAN SPEED CONTROLLERF -
MANUAL MOTOR STARTER WITH MELTING ALLOY HEATER ELEMENTSM -
MOMENTARY CONTACT TOGGLE SWITCHMC -
SWITCH WITH PILOT LIGHTP -
WEATHERPROOF SWITCHWP -
CEILING MOUNT OR SUSPENDED FLUORESCENT LUMINAIRE (NORMAL
BRANCH)
CEILING MOUNT OR SUSPENDED FLUORESCENT LUMINAIRE (CRITICAL OR
EQUIPMENT BRANCH)
LUMINAIRES
CEILING MOUNT OR SUSPENDED FLUORESCENT LUMINAIRE (LIFE SAFETY
BRANCH)
WALL MOUNTED FLUORESCENT LUMINAIRE (NORMAL BRANCH)
WALL MOUNTED FLUORESCENT LUMINAIRE (CRITICAL OR EQUIPMENT BRANCH)
WALL MOUNTED FLUORESCENT LUMINAIRE (LIFE SAFETY BRANCH)
RECESSED DOWN LIGHT (NORMAL BRANCH)
RECESSED DOWN LIGHT (CRITICAL OR EQUIPMENT BRANCH)
RECESSED DOWN LIGHT (LIFE SAFETY BRANCH)
EXIT SIGN, CEILING OR PENDANT MOUNTED. SHADED PORTION DENOTES
FACE(S). DIRECTIONAL ARROWS AS INDICATED.
EXIT SIGN, WALL MOUNTED. SHADED PORTION DENOTES FACE(S).
DIRECTIONAL ARROWS AS INDICATED. MOUNT AT 6" ABOVE TOP OF DOOR JAMB
TO BOTTOM OF FIXTURE.
WALL MOUNTED LUMINAIRE (NORMAL BRANCH)
WALL MOUNTED LUMINAIRE (CRITICAL OR EQUIPMENT BRANCH)
WALL MOUNTED LUMINAIRE (LIFE SAFETY BRANCH)
FLUORESCENT STRIP OR INDUSTRIAL LUMINAIRE (LIFE SAFETY BRANCH)
FLUORESCENT STRIP OR INDUSTRIAL LUMINAIRE (CRITICAL OR EQUIPMENT
BRANCH)
FLUORESCENT STRIP OR INDUSTRIAL LUMINAIRE (NORMAL BRANCH)
POLE MOUNTED AREA LIGHT, SINGLE HEAD. (NORMAL BRANCH)
PHOTOELECTRIC CONTROLLER.
KEY NOTE SYMBOL. (SEE KEY NOTES ON INDIVIDUAL DRAWINGS).
CONDUCTOR CONNECTION
ELECTRICAL GROUND
MISCELLANEOUS
LOW VOLTAGE CABLE TRAY FOR COMMUNICATIONS SYSTEMS WIRING ONLY.
PROVIDE A MINIMUM 5" SEPARATION BETWEEN FLUORESCENT LIGHTING
FIXTURES AND CABLE TRAY. WIDTH SHALL BE 12" UNLESS OTHERWISE NOTED.
SEE 7/E-ET5.001 FOR DETAIL.
PE
BC BATTERY CHARGER, MOUNT AT 72" AFF TO TOP.
SUBSCRIPTS AS FOLLOWS:
G - BATTERY CHARGER FOR GENERATOR BATTERIES.
S - BATTERY CHARGER FOR SWITCHGEAR STATION BATTERIES.
GENERATOR SCADA SYSTEM OUTLET, SEE 8/E-ET5.001 FOR DETAIL.
S
GRAP
GENERATOR REMOTE ALARM PANEL. MOUNT AT 72" AFF TO TOP.
CLOSED CIRCUIT TELEVISION
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTOMATIC TRANSFER SWITCH
BELOW FINISHED GRADE
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
ELECTRICAL METALLIC TUBING
ENGINE GENERATOR SET
BELOW FINISHED CEILING
EWH
FLUOR
FA
GEN
EXP, XP
EXH
EQUIP
EWC
EUH
EMT
EF
FLUORESCENT
FIRE ALARM
EXHAUST
EXPLOSION PROOF
EXHAUST FAN
EQUIPMENT
CLG
DISC
DWG
EA
CU
CL
CAB
CCTV
CKT
BFG
CEILING
CENTERLINE
DISCONNECT(ING)
DRAWING(S)
EACH
COPPER
CABINET
CIRCUIT
CONDUIT
AFG
ATS
BFC
A
AFF
NATIONAL ELECTRICAL CODE
POLYVINYL CHLORIDE
UNLESS OTHERWISE NOTED
MANUAL TRANSFER SWITCH
WT
V
WP
VA
TEL
UON
WATER TIGHT
TELEPHONE
VOLT-AMPERES
WEATHER PROOF
VOLTAGE
MTS
PVC
PNL
RECEPT
NEC
NC
MTR
MTG
MTD
MISC
MIN
NURSE CALL
RECEPTACLE
PANEL
MINIMUM
MISCELLANEOUS
MOUNTED
MOUNTING
MOTOR
KILO-VOLTS-AMPERES
KILO-WATT-HOURS
MOTOR CONTROL CENTER
LOCAL AREA NETWORKLAN
MCC
MH
MFR
MAX
LTG
KVA
KWH
KW
KV
MANHOLE
LIGHTING
MANUFACTURER
MAXIMUM
KILO-VOLTS
KILO-WATTS
INCAND INCANDESCENT
FLA FULL LOAD AMPERES
ABOVE FINISHED CEILINGAFC
W WIRE
TYP TYPICAL
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
CURRENT TRANSFORMERSCT's
KILO-VOLTS-AMPERES REACTIVEKVAR
RGS RIGID GALVANIZED STEEL
GOVERNMENT FURNISHEDGFGI
GOVERNMENT INSTALLED
C m METER mm MILLIMETER
AIC AMPERES INTERRUPTING
CAPACITY
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
SEE REFLECTED CEILING PLAN ON SHEET E-AI1.10 FOR EXACT LOCATION OF LUMINAIRES AND
CEILING MOUNTED DEVICES.
LUMINAIRES INDICATED AS FOLLOWS: UPPER CASE LETTER WITH NUMERAL DENOTES FIXTURE
TYPE (SEE LUMINAIRE SCHEDULE), LOWER CASE LETTER (IF SHOWN) DENOTES SWITCHING
ARRANGEMENT AND NUMERAL BY ITSELF (IF SHOWN) DENOTES CIRCUIT NUMBER.
WHERE DEVICES ARE INDICATED TO BE MOUNTED ABOVE A COUNTERTOP, MOUNT DEVICE
SUCH THAT BOTTOM OF COVER PLATE IS 51mm (2") ABOVE TOP OF BACK SPLASH. IF THERE IS NO BACK SPLASH, MOUNT DEVICE 51mm (2") ABOVE FINISHED COUNTER TOP SURFACE TO
BOTTOM OF DEVICE COVER PLATE.
1.
2.
3.
4.
5.
HIGH INTENSITY DISCHARGEHID
G, GND
HGT
GROUND
HEIGHT
GFP GROUND FAULT PROTECTION
NOTES:
SHEET NOTES:
AMPERES
INSTALL ALL EQUIPMENT AND DEVICES AT THE HEIGHT INDICATED ON THIS SHEET UNLESS
OTHERWISE NOTED. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS FOR SPECIAL
MOUNTING HEIGHTS AND LOCATIONS OF ELECTRICAL DEVICES. MOUNTING HEIGHTS AND
LOCATIONS INDICATED ON ARCHITECTURAL ELEVATIONS TAKE PRECEDENCE OVER
MOUNTING HEIGHTS AND LOCATIONS INDICATED ON ELECTRICAL PLANS.
WHERE MULTIPLE TOGGLE SWITCHES ARE SHOWN TO BE MOUNTED ADJACENT TO ONE
ANOTHER, MOUNT SWITCHES IN A SINGLE BOX UP TO 4-GANG (NORMAL AND EMERGENCY
CIRCUITS SHALL NOT OCCUPY THE SAME ENCLOSURE).
ABBREVIATIONS
ALL MATERIALS AND EQUIPMENT SHALL BE LISTED AS COMPLYING WITH THE
APPLICABLE STANDARDS OF UNDERWRITERS LABORATORIES, INC.
6.
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME
AMPERE TRIPAT
BARE COPPERBC
BOILER PLANT INSTRUMENTATION
PANEL
BRIP
CIRCUIT BREAKERCB, C/B
BREAKERBKR
DB DIRECT BURIED
EC EMPTY CONDUIT
EG EQUIPMENT GROUND
EXPANSION JOINTEJ
EX EXISTING
EMERGENCYEMERG
ELECTRICELEC
ELECTRIC STRIP MOLDESM
FACP FIRE ALARM CONTROL PANEL
FCU
FILM ILLUMINATORFI
FAN COIL UNIT
FIXT FIXTURE
FSCP FLAME SAFEGUARD CONTROL PANEL
FSS FUSED SAFETY SWITCH
GFI GROUND FAULT INTERRUPTER
GTB GROUND TERMINAL BOX
HH HANDHOLE
HAND-OFF-AUTOMATICHOA
JB JUNCTION BOX
LTCP LOCAL TEMPERATURE CONTROL
PANEL
LTS LIGHTS
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION
MCP MOTOR CIRCUIT PROTECTOR
MLO MAIN LUGS ONLY
MTG HGT MOUNTING HEIGHT
NON-FUSED SAFETY SWITCHNFSS
POLEP
PULL BOXPB
PREFABRICATED BEDSIDE
PATIENT POWER UNIT
PBPU
POD POWER OPERATED DAMPER
POWER TYPE ROOF VENTILATIONPTRV
POWERPWR
RGIP REMOTE GROUND INDICATOR PANEL
SIG SIGNAL
SS SAFETY SWITCH
STA STATION
TV TELEVISION
UNIT HEATERUH
VP VAPOR PROOF
W/ WITH
XFMR TRANSFORMER
HV HIGH VOLTAGE
HPS HIGH PRESSURE SODIUM
HP HORSEPOWER
NORMALLY OPENN.O.
>= GREATER THAN OR EQUAL TO
LESS THAN OR EQUAL TO<=
CEILING MOUNTED LINE VOLTAGE OCCUPANCY SENSOR. SEE
7/E-EL5.003 FOR WIRING DIAGRAM.
U a
PATTERN TYPE. SCHEDULE BELOW.
SWITCH LEG
TECHNOLOGY TYPE. SEE SCHEDULE BELOW.
SENSOR ORIENTATION
PATTERN TYPE SCHEDULE:
1 90' x 10' 2 40' x 40' 3 20' x 20'
OCCUPANCY SENSING WALL SWITCH. WITH MANUAL OVERRIDE. MOUNT AT 48" AFF TO
CENTER.
OCCUPANCY SENSORS
U
TECHNOLOGY TYPE. SEE SCHEDULE BELOW.
CEILING/WALL SENSORS
WALL SWITCHES
TECHNOLOGY TYPE SCHEDULE:
U ULTRASONIC
R INFRARED
D DUAL TECHNOLOGY(INFRARED & ULTRASONIC)
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS:
OFFICE OF
FACILITIES
MANAGEMENT
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot
6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
BUILDING IS FULLY SPRINKLERED
A NEW HOSPITAL FOR
VAMC ORLANDO, FLORIDA
Orlando, Florida
673-950
Professional Seals:
THESE RECORD DRAWINGS HAVE BEEN PREPARED
BY THE DESIGN PROFESSIONAL BASED ON
INFORMATION FURNISHED BY OTHERS. NO FIELD
VERIFICATION OF THEIR CORRECTNESS HAS
OCCURED. THE DESIGN PROFESSIONAL CANNOT
ASSURE THE ACCURACY OR INFORMATION
INCORPORATED INTO THESE RECORD DRAWINGS.
REFER TO SUPPLEMENTAL SHOP DRAWINGS
INCLUDED WITH THE RECORD DOCUMENT SET FOR
ADDITIONAL INFORMATION.
No. Description Date
RECORD DRAWINGS 12-01-2015
29 OCTOBER, 2009 KLM EB/RLF
CENTRAL ENERGY PLANT
E-EG0.001
ELECTRICAL LEGEND AND ABBREVIATIONS
SITE WORK
A1-E1
NA1-1
T-1
MANHOLE, SEE 1/E-ES5.004 FOR DETAIL. SEE 3/E-ES5.004 FOR GROUNDING
TELECOMMUNICATIONS MANHOLE. SEE 1/E-ES5.004 FOR MANHOLE
DETAILS. SEE 3/E-ES5.0004 FOR GROUNDING DETAIL.
CONDUIT TERMINATION WITH CAP FOR FUTURE USE. EXTEND CONDUITS
DETAIL. SUBSCRIPTS INDICATES THE FOLLOWING:
N A 1 - 1
MANHOLE SEQUENCE
SWITCHGEAR SECTION (SECTION 1 OR 2)
SOURCE IDENTIFICATION ("A" SYSTEM OR "B" SYSTEM)
SERVICE IDENTIFICATION:
N - NORMAL POWER.
E - EMERGENCY POWER.
G - GENERATOR CONTROLS.
DUCT BANK. SEE DUCT BANK SCHEDULES ON SHEETS E-ES7.001, E-ES7.002
SWITCHGEAR SECTION WHERE APPLICABLE (SECTION 1 OR 2)
SOURCE IDENTIFICATION WHERE APPLICABLE ("A" SYSTEM OR "B" SYSTEM)
DUCT SEQUENCE
SERVICE IDENTIFICATION:
E - EMERGENCY POWER, SEE DUCT BANK SCHEDULE SHEET E-ES7.001.
G - GENERATOR CONTROLS, SEE DUCT BANK SCHEDULE SHEET E-ES7.002.
N - NORMAL POWER, SEE DUCT BANK SCHEDULE SHEET E-ES7.001.
T - TELECOMMUNICATIONS, SEE DUCT BANK SCHEDULE SHEET E-ES7.002.
12" BEYOND CONCRETE ENCASEMENT FOR FUTURE EXTENSION.
AND E-ES7.003 FOR REQUIREMENTS.
C
NA1-1
EXISTING MANHOLE PROVIDED UNDER A SEPARATE CONSTRUCTION PACKAGE.
DUCT BANK PROVIDED UNDER A SEPARATE CONSTRUCTION PACKAGE. SEE
DUCT BANK SHEDULES ON SHEET E-ES7.001, E-ES7.002 , AND E-ES7.003.
A1-E1
TEMPORARY OVERHEAD PRIMARY POWER LINE PROVIDED UNDER A SEPARATE
CONSTRUCTION PACKAGE 1.
OHP
TEMPORARY POWER POLE PROVIDED UNDER A SEPARATE CONSTRUCTION
PACKAGE 1.
UL1 UNDERGROUND SITE LIGHTING CONDUIT, SEE SCHEDULE ON SHEET E-ES7.003
FOR REQUIREMENTS.
COMBINATION VOICE/DATA OUTLET. SEE 2/E-ET6.001 FOR OUTLET CONFIGURATION.
MOUNT AT 18" AFF TO CENTER UNLESS OTHERWISE NOTED.
TELEPHONE / DATA SYSTEM
WALL MOUNTED TELEPHONE OUTLET. SEE 2/E-ET6.001 FOR OUTLET CONFIGURATION.
MOUNT 54" TO CENTER UON.
TELECOMMUNICATIONS EQUIPMENT CABINET WITH HORIZONTAL AND VERTICAL
CABLE MANAGEMENT.
COMBINATION VOICE/DATA OUTLET MOUNTED ABOVE COUNTER TOP. SEE 2/E-ET6.001
FOR OUTLET CONFIGURATION.
OC
TV
TELEVISION SYSTEM
CABLE TELEVISION OUTLET FOR FLAT PANEL MONITOR. WALL MOUNT AT 60"
AFF TO CENTER, UON. SEE 3/E-ET5.001 FOR DETAIL
AMPLIFIER.
LINE TERMINATOR.
FOUR-OUTPUT CABLE TELEVISION MULTI-TAP DEVICE WITH TAP DOWN
VALUES AS REQUIRED TO MEET PERFORMANCE CRITERIA AS INDICATED IN
THE SPECIFICATIONS.
POWER DISTRIBUTION
PANELBOARD, FLUSH MOUNTED AT 72" AFF TO TOP.
PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP.
DISTRIBUTION PANELBOARD, SURFACE MOUNTED AT 72" AFF TO TOP.
DISCONNECT SWITCH, SEE DISCONNECT SWITCH SCHEDULE ON
SHEET E-EP7.003. MOUNT AT 72" AFF TO TOP
COMBINATION MAGNETIC STARTER/DISCONNECT SWITCH. SEE
MOTOR STARTER SCHEDULE ON SHEET E-EP7.002. MOUNT AT 72"
AFF TO CENTER.
VARIABLE FREQUENCY DRIVE. SEE VARIABLE FREQUENCY DRIVE
SCHEDULE ON SHEET E-EP7.002.
PARALLEL CONNECTED SURGE SUPPRESSOR. SEE SURGE
SUPPRESSOR SCHEDULE ON SHEET E-EP7.002.
DS1
ST-1
SS
TVSS-1
VFD
VFD-1
GENERATOR
MOTOR CONNECTION.
JUNCTION BOX OR PULL BOX
DESCRIPTION
J
G
CONNECTION TO EQUIPMENT LEADS, TERMINAL STRIPS OR CONTROL
PANEL INCLUDING ALL CONDUCTORS, CONDUIT, FLEXIBLE CONDUIT,
JUNCTION BOXES, CONNECTORS, FITTINGS, ETC. REQUIRED FOR
PROPER CONNECTION. SUBSCRIPT INDICATES EQUIPMENT
CONNECTION NUMBER. SEE EQUIPMENT CONNECTION SCHEDULE ON
SHEETE-EP7.002.
E E1
H
A
O
OVERLOAD RELAY CONTACT.
PILOT LIGHT "R" INDICATES RED, "G" INDICATES GREEN
NORMALLY CLOSED CONTACT (N.C.)
NORMALLY OPEN CONTACT (N.O.)
OL
CONTROL CIRCUIT FUSE.
OPERATING COIL
NORMALLY OPEN PUSH BUTTON.
NORMALLY CLOSED PUSH BUTTON.
NORMALLY OPEN MUSHROOM HEAD PUSH BUTTON.
CONDUCTOR CONNECTION.
HAND-OFF-AUTOMATIC SELECTOR SWITCH
NORMALLY CLOSED MUSHROOM HEAD PUSH BUTTON.
C
R
CONTROL DIAGRAM
SINGLE LINE DIAGRAM
CIRCUIT BREAKER WITH NUMBER OF POLES AND TRIP RATING AS
INDICATED. SUBSCRIPTS INDICATE THE FOLLOWING:
ELECTRONIC TRIP, SOLID STATE CIRCUIT BREAKER.
CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND
FAULT PROTECTION.
ET -
GFP -
CIRCUIT BREAKER WITH SHUNT TRIP COIL AND WITH NUMBER OF
POLES AND TRIP RATING AS INDICATED. SUBSCRIPTS INDICATE THE
FOLLOWING:
ELECTRONIC TRIP, SOLID STATE CIRCUIT BREAKER.
CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND
FAULT PROTECTION.
ET -
GFP -
DRAW-OUT TYPE CIRCUIT BREAKER WITH NUMBER OF POLES AND
TRIP RATING AS INDICATED. SUBSCRIPTS INDICATE THE FOLLOWING:
ELECTRONIC TRIP, SOLID STATE CIRCUIT BREAKER.
CIRCUIT BREAKER EQUIPPED WITH INTEGRAL GROUND
FAULT PROTECTION.
ET -
GFP -
DRY TYPE TRANSFORMER. SEE TRANSFORMER SCHEDULE ON
SHEET E-EP7.002. SEE SHEET E-EP6.006 FOR GROUNDING DIAGRAM.
AUTOMATIC TRANSFER SWITCH.
AUTOMATIC TRANSFER SWITCH WITH CENTER OFF POSITION.
MULTI FUNCTION DIGITAL POWER CIRCUIT MONITOR.
KEY INTERLOCK
SURGE ARRESTOR WITH RATINGS INDICATED.
POWER TRANSFORMER WITH DELTA CONNECTED PRIMARY, WYE
CONNECTED SECONDARY AND RATING AS INDICATED.
FEEDER CONTINUATION SYMBOL
FEEDER REFERENCE
SHEET ON WHICH FEEDER IS CONTINUED
EQUIPMENT OR PANEL TO WHICH FEEDER IS CONNECTED
PANELBOARD
WHEN PRESENT, INDICATES PANELBOARD WITH MAIN CIRCUIT
BREAKER. SEE PANEL SCHEDULE FOR SIZE. IF NOT PRESENT,
PANELBOARD WITH MAIN LUGS ONLY.
WHEN PRESENT, INDICATES PANELBOARD WITH FEED THROUGH
LUGS.
100A 3P
C 100A 3P
100A 3P
T
N E
M
K
A1
EP602
1AHNDP
1AHN1
N E
MICROPROCESSOR BASED OVERCURRENT RELAY WITH THE
FOLLOWING FUNCTIONS:
PHASE OVERCURRENT (51) ELEMENT
PHASE INSTANTANEOUS (50) ELEMENT
GROUND TIME OVERCURRENT (51G) ELEMENT
GROUND INSTANTANEOUS (50) ELEMENT
INTEGRAL POWER MONITORING LOCK-OUT RELAY (86)
1200AF
200AT
52 DRAW-OUT TYPE, MEDIUM VOLTAGE, VACUUM CIRCUIT BREAKER.
FRAME RATING.
OVERCURRENT RELAY TRIP SETTING.
TC MEDIUM VOLTAGE CIRCUIT BREAKER TRIP COIL.
(3) CURRENT TRANSFORMERS WITH RATING AS INDICATED.600:5
MEDIUM VOLTAGE SWITCH WITH RATING. SUBSCRIPTS AS FOLLOWS:
SWITCH IS NORMALLY OPEN.
SWITCH IS NORMALLY CLOSED.
MEDIUM VOLTAGE FUSE WITH RATING.100A
C 200A
CIRCUIT BREAKER EQUIPPED WITH GROUND FAULT
MONITORING RELAY. BREAKER SHALL NOT TRIP ON
GROUND FAULT, BUT CAUSE ALARM ANNUNCIATION ONLY.
GFM -
CIRCUIT BREAKER EQUIPPED WITH GROUND FAULT
MONITORING RELAY. BREAKER SHALL NOT TRIP ON
GROUND FAULT, BUT CAUSE ALARM ANNUNCIATION ONLY.
GFM
CIRCUIT BREAKER EQUIPPED WITH GROUND FAULT
MONITORING RELAY. BREAKER SHALL NOT TRIP ON
GROUND FAULT, BUT CAUSE ALARM ANNUNCIATION ONLY.
GFM
MEDIUM VOLTAGE TERMINATION.
MICROPROCESSOR BASED OVERCURRENT RELAY WITH THE
FOLLOWING FUNCTIONS:
PHASE OVERCURRENT (51) ELEMENT
PHASE INSTANTANEOUS (50) ELEMENT
GROUND TIME OVERCURRENT (51G) ELEMENT (ANNUNCIATION
ONLY)
GROUND INSTANTANEOUS (50) ELEMENT (ANNUNCIATION ONLY)
INTEGRAL POWER MONITORING LOCK-OUT RELAY (86)
A
RELAY
RELAY ELECTRONIC TRIP SOLID STATE CIRCUIT BREAKER
WITH INTEGRAL POWER METERING AND BREAKER
STATUS. POWER METERING AND BREAKER STATUS
SHALL BE CONNECTED TO POWER MONITORING SYSTEM
VIA NETWORK CABLING.
ETM -
ELECTRONIC TRIP SOLID STATE CIRCUIT BREAKER
WITH INTEGRAL POWER METERING AND BREAKER
STATUS. POWER METERING AND BREAKER STATUS
SHALL BE CONNECTED TO POWER MONITORING SYSTEM
VIA NETWORK CABLING.
ETM -
ELECTRONIC TRIP SOLID STATE CIRCUIT BREAKER
WITH INTEGRAL POWER METERING AND BREAKER
STATUS. POWER METERING AND BREAKER STATUS
SHALL BE CONNECTED TO POWER MONITORING SYSTEM
VIA NETWORK CABLING.
ETM -
MOTOR CONTROL CENTER.EMCCE1
POTENTIAL TRANSFORMER
N.O N.C
AUTOMATIC POWER FACTOR CORRECTION SYSTEM.
THERMAL MAGNETIC CIRCUIT BREAKER.
MOTOR CONTROL CENTER LEGEND
MOTOR CIRCUIT PROTECTOR.MCP
NUMBER OF POLES.
CB
P
OC DEVICES (OVERCURRENT DEVICES):
STARTER:
STARTER SIZE (NEMA), "BLANK" INDICATES SIZE 0 STARTER.SIZE
TYPE OF STARTER, SEE DEFINITIONS BELOW. "BLANK"
INDICATES CIRCUIT BREAKER ONLY, NO STARTER REQUIRED.
TYPE
FULL VOLTAGE NON REVERSING STARTER.FVNR
REDUCED VOLTAGE, SOLID STATE "SOFT START" NON REVERSING STARTER.RVNR
TWO SPEED STARTER.2SPD
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS:
OFFICE OF
FACILITIES
MANAGEMENT
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot
6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
BUILDING IS FULLY SPRINKLERED
A NEW HOSPITAL FOR
VAMC ORLANDO, FLORIDA
Orlando, Florida
673-950
Professional Seals:
THESE RECORD DRAWINGS HAVE BEEN PREPARED
BY THE DESIGN PROFESSIONAL BASED ON
INFORMATION FURNISHED BY OTHERS. NO FIELD
VERIFICATION OF THEIR CORRECTNESS HAS
OCCURED. THE DESIGN PROFESSIONAL CANNOT
ASSURE THE ACCURACY OR INFORMATION
INCORPORATED INTO THESE RECORD DRAWINGS.
REFER TO SUPPLEMENTAL SHOP DRAWINGS
INCLUDED WITH THE RECORD DOCUMENT SET FOR
ADDITIONAL INFORMATION.
No. Description Date
RECORD DRAWINGS 12-01-2015
29 OCTOBER, 2009 KLM EB/RLF
CENTRAL ENERGY PLANT
E-EG0.002
ELECTRICAL LEGEND
D1 D2 D3 D4 D5 D6 D7 D8 D9 T1 D10 D11 D12 D13 D14 D15 D16 D17 D18
DAG23
CIRCUIT BREAKER
1200AF
DAG21
CIRCUIT BREAKER
1200AF
DAG15
CIRCUIT BREAKER
1200AF
DAG13
CIRCUIT BREAKER
1200AF
PT
ROLLOUT
PT
ROLLOUT
DAG24
CIRCUIT BREAKER
1200AF
DAG19
CIRCUIT BREAKER
1200AF
DAG17
CIRCUIT BREAKER
1200AF
DAG22
CIRCUIT BREAKER
1200AF
DAG20
CIRCUIT BREAKER
1200AF
DAG18
CIRCUIT BREAKER
1200AF
DAG16
CIRCUIT BREAKER
1200AF
PT
ROLLOUT
GA5
CIRCUIT BREAKER
1200AF
GA3
CIRCUIT BREAKER
1200AF
GA4
CIRCUIT BREAKER
1200AF
DAG14
CIRCUIT BREAKER
1200AF
PT
ROLLOUT
PT
ROLLOUT
DAG11
CIRCUIT BREAKER
1200AF
DAG9
CIRCUIT BREAKER
1200AF
DAG7
CIRCUIT BREAKER
1200AF
DAG6
CIRCUIT BREAKER
1200AF
DAG5
CIRCUIT BREAKER
1200AF
DAG4
CIRCUIT BREAKER
1200AF
DAG3
CIRCUIT BREAKER
1200AF
DAG1
CIRCUIT BREAKER
1200AF
BUS PT
ROLLOUT
TAG-1
CIRCUIT BREAKER
1200AF
GA1
CIRCUIT BREAKER
1200AF
GA2
CIRCUIT BREAKER
1200AF
DAG12
CIRCUIT BREAKER
1200AF
DAG10
CIRCUIT BREAKER
1200AF
DAG8
CIRCUIT BREAKER
1200AF
DAG2
CIRCUIT BREAKER
1200AF
TRANSITION
SECTION
DAN20
CIRCUIT
BREAKER
1200AF
DAN16
CIRCUIT
BREAKER
1200AF
D1
DAN14
CIRCUIT
BREAKER
1200AF
D2
DAN18
CIRCUIT
BREAKER
1200AF
D3 D4
DAN22
CIRCUIT
BREAKER
1200AF
DAN24
CIRCUIT
BREAKER
1200AF
D5
UM2
CIRCUIT
BREAKER
1200AF
D6
DAN23
CIRCUIT
BREAKER
1200AF
DAN19
CIRCUIT
BREAKER
1200AF
DAN21
CIRCUIT
BREAKER
1200AF
DAG13
CIRCUIT
BREAKER
1200AF
DAN15
CIRCUIT
BREAKER
1200AF
DAN17
CIRCUIT
BREAKER
1200AF
BUS PT
ROLLOUT
PT
ROLLOUT
D7 D8 T1
UM1
CIRCUIT
BREAKER
1200AF
D9 D10 D11 D12
DAN6
CIRCUIT
BREAKER
1200AF
DAN8
CIRCUIT
BREAKER
1200AF
DAN10
CIRCUIT
BREAKER
1200AF
TAN-1
CIRCUIT
BREAKER
1200AF
DAN12
CIRCUIT
BREAKER
1200AF
D13 D14 D15
DAN3
CIRCUIT
BREAKER
1200AF
DAN1
CIRCUIT
BREAKER
1200AF
DAN2
CIRCUIT
BREAKER
1200AF
DAN5
CIRCUIT
BREAKER
1200AF
DAN4
CIRCUIT
BREAKER
1200AF
DAN7
CIRCUIT
BREAKER
1200AF
DAN9
CIRCUIT
BREAKER
1200AF
DAN11
CIRCUIT
BREAKER
1200AF
PT
ROLLOUT
BUS PT
ROLLOUT
CC C3C2UTC - 1 C4UTC - 2 C5AUX.
42" MONITOR
ACTIVE ONE-LINE
DIAGRAM
17" TOUCH
PANEL FOR
ACTIVE CONTROLS
LOAD BANK
CONTROLLER
ENGINE
CONTROLLER
DIFFERENTIAL
CURRENT
TRANSFORMERS
ENGINE
BATTERY
CHARGER
DAY TANK
24VDC POWER
AND ALARMS
GENERATOR "X" (TYPICAL FOR 5)
EXTERIOR
LOAD
BANK
MAIN FUEL
STORAGE
INVENTORY
PANEL
UTILITY #1
TRANSFER
CONTROL CUBICLE
UTILITY #2
TRANSFER
CONTROL CUBICLE
AUXILIARY
CONTROL CUBICLE
MASTER
CONTROL CUBICLE
C1
GEN GA-1
CONTROL CUBICLE
GEN GA-2
CONTROL CUBICLE
GEN GA-3
CONTROL CUBICLE
GEN GA-4
CONTROL CUBICLE
GEN GA-5
CONTROL CUBICLE
DC DISTRIBUTION
PANEL "DC-EA"
RM 1A109A
SIMULATOR
WORK
STATION
RM 1A106C
NORMAL DISTRIBUTION SWITCHGEAR "A" (RM. 1A101)
PARALLELING SWITCHGEAR SWITCHGEAR "A" (RM. 1A109)
MASTER CONTROLS SYSTEM "A" (RM. 1A109A)
RM. 1A115
RM. 1A101RM. 1A109
S
GENERATOR ROOM 1A115B
TYPICAL DISCONNECT SERVING
GENERATOR JACKET HEATER
JB
EHE1EHE1B
JB
EMERGENCY SUBSTATION ROOM 1A105
1 2 3
1 1 1 1 1
2 3 8
3 3 4 2 3
RM. 1A115B
4 14
10 6
12 12
STATION
BATTERIES
STATION
BATTERIES
RM. 1A101RM. 1A109
JB
JB
16 16
DC DISTRIBUTION
PANEL "DC-NA"
15 15
SCADA WORK
STATION
SYSTEM "B"
SCADA WORK
STATION
SYSTEM "B"
SCADA WORK
STATION
SYSTEM "A"
SCADA WORK
STATION
SYSTEM "A"
FUEL
TRANSFER
PUMP
CONTROLLER
RM. 1A115
3 3
CONDUITS SHOWN ON THIS DRAWING ARE FOR BIDDING PURPOSES ONLY.
PROVIDE CONDUIT QUANTITIES, SIZES AND EXACT POINTS OF TERMINATION
IN ACCORDANCE WITH THE GENERATOR CONTROL SWITCHGEAR SUPPLIERS
APPROVED SHOP DRAWINGS AT NO ADDITIONAL COST TO THE GOVERNMENT.
A.
REFER TO SHEET E-EP5.012 FOR THE GENERATOR AND OVERALL SYSTEM
ALARM POINTS. REFER TO SPECIFICATION SECTION 26 13 00 FOR
SCADA SYSTEM ALARM POINTS.
B.
REFER TO SHEETS E-EP5.001 AND E-EP5.002 FOR AUTOMATIC TRANSFER SWITCH
CONNECTIONS AND SUBSTATION MONITORING CONNECTIONS TO THE MASTER
CONTROLLER.
C.
ANY WIRING THAT IS ROUTED BELOW FINISHED FLOOR SLAB OR OUTSIDE OF
THE BUILDING BELOW FINISHED GRADE SHALL BE UL LISTED FOR USE IN
WET LOCATIONS.
D.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS:
OFFICE OF
FACILITIES
MANAGEMENT
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot
6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
BUILDING IS FULLY SPRINKLERED
A NEW HOSPITAL FOR
VAMC ORLANDO, FLORIDA
Orlando, Florida
673-950
Professional Seals:
THESE RECORD DRAWINGS HAVE BEEN PREPARED
BY THE DESIGN PROFESSIONAL BASED ON
INFORMATION FURNISHED BY OTHERS. NO FIELD
VERIFICATION OF THEIR CORRECTNESS HAS
OCCURED. THE DESIGN PROFESSIONAL CANNOT
ASSURE THE ACCURACY OR INFORMATION
INCORPORATED INTO THESE RECORD DRAWINGS.
REFER TO SUPPLEMENTAL SHOP DRAWINGS
INCLUDED WITH THE RECORD DOCUMENT SET FOR
ADDITIONAL INFORMATION.
No. Description Date
RECORD DRAWINGS 12-01-2015
29 OCTOBER, 2009 KLM EB/RLF
CENTRAL ENERGY PLANT
E-EP5.013
WIRING DIAGRAM SYSTEM "A"
NOT TO SCALE
1 CONTROL WIRING SYSTEM "A"
KEY NOTES:
NOTES:
SHEET NOTES:
14 TYPICAL DISCONNECT SWITCH SERVING THE GENERATOR
JACKET WATER HEATER. PROVIDE MONITORING
CONNECTION TO THE DISCONNECT SWITCH "OFF" POSITION
AUXILIARY CONTACT. ALL MONITORING WIRING WITHIN THE
DISCONNECT SWITCH SHALL HAVE INSULATION RATED FOR
600V.
15 PROVIDE JUNCTION BOX AS REQUIRED.
16 CONDUIT AND WIRING AS REQUIRED.
17 PANELBOARD SERVING THE GENERATOR FUEL-OIL
TRANSFER PUMPS. PROVIDE MONITORING CONNECTION TO
THE CIRCUIT BREAKER "OFF" POSITION AUXILIARY CONTACT.
WIRING SHALL HAVE INSULATION RATED FOR 600V.
10 SEE 8/E-ET5.001 FOR DETAIL.
11 SEE 4/E-ET5.001 FOR DETAIL.
12 (2) 1" CONDUITS WITH DC POWER WIRING AS REQUIRED.
13 PANELBOARD SERVING GENERATOR JACKET WATER
HEATERS. PROVIDE MONITORING CONNECTION TO THE
CIRCUIT BREAKER "OFF" POSITION AUXILIARY CONTACT FOR
EACH BREAKER SERCING A JACKET WATER HEATER. ALL
MONITORING WIRING WITHIN THE PANELBOARD SHALL HAVE
INSULATION RATED FOR 600V.
1 1 1/2" CONDUIT WITH WIRING AS REQUIRED.
2 2" CONDUIT WITH WIRING AS REQUIRED.
3 1" CONDUIT WITH WIRING AS REQUIRED.
4 3/4" CONDUIT WITH WIRING AS REQUIRED.
5 3/4" CONDUIT WITH (2) 4 PAIR CATEGORY 6 RATED CABLES.
6 1" CONDUIT WITH (3) 4 PAIR CATEGORY 6 RATED CABLES.
7 3/4" CONDUIT WITH (1) 4 PAIR CATEGORY 6 RATED CABLE TO
SYSTEM "B" MASTER CONTROL CUBICLE.
8 1" CONDUIT WITH (2) 4 PAIR CATEGORY 6 RATED CABLES.
9 (2) 2" CONDUITS TO SYSTEM "B" MASTER CONTROL CUBICLE.
SEE SHEET E-EP5.014 FOR CONTINUATION
SCADA NETWORK
TYPICAL UTILITY
SWITCHGEAR
TYPICAL
GENERATOR
SWITCHGEAR
TYPICAL
GENERATOR
SET
POWER MONITORING SYSTEM NETWORK (VA LAN)
Router/ Switch
TYPICAL
SCADA
WORKSTATION
TO VA VISN
ENERGY
MANAGEMENT
PMS
SERVER
RM 1A106C
TYPICAL
PMS
WEB
CLIENT
CENTRAL
ENERGY
PLANT
COMMUNITY
LIVING
CENTER DOMICILIARY
PARKING
STRUCTURES WAREHOUSE HOSPITAL CLINIC
TYPICAL
SWITCHGEAR
METERS/TRIP
UNITS/ATS
TYPICAL
SWITCHGEAR
METERS/TRIP
UNITS/ATS
TYPICAL
SWITCHGEAR
METERS/TRIP
UNITS/ATS
TYPICAL
SWITCHGEAR
METERS/TRIP
UNITS/ATS
TYPICAL
SWITCHGEAR
METERS/TRIP
UNITS/ATS
TYPICAL
SWITCHGEAR
METERS/TRIP
UNITS/ATS
TYPICAL
SWITCHGEAR
METERS/TRIP
UNITS/ATS12
11 10
M4 5 8
SUBSTATION SS-CH1/2
RELAY
E-CH-2
E-CH-1
M
E-ATS-CH1/2
RELAY
ETM ETM ETM
ETM ETM
M
ETM
M
SUBSTATION SS-EN1 SUBSTATION SS-EG1
5 52 2
1 1
EHN1 E-ATS-E10
E-ATS-S2 E-ATS-E6
E-ATS-E3
M M M
E-ATS-E4 E-ATS-E5 E-ATS-E6
ETM
ETM
E-ATS-E5
E-ATS-E4
7 7
ETM ETM
ETM ETM
E-ATS-E10
E-ATS-S2 E-ATS-E6
E-ATS-E3
ETM
ETM
E-ATS-E5
E-ATS-E4
E-FP-1
M
E-ATS-E3
M M M
E-ATS-E10 E-ATS-S2 E-FP-1
7 7 76 6 6 6 6
M4 5 8
SUBSTATION SS-CH3/4
RELAY
E-CH-4
E-CH-3
M
E-ATS-CH3/4
RELAY
M4 5 8
SUBSTATION SS-CH5/6
RELAY
E-CH-5
M
E-ATS-CH5/6
ETM ETM
ETM ETM
M
ETM
M
SUBSTATION SS-EN2 SUBSTATION SS-EG2
5 2
1 1
E-ATS-E9
E-ATS-S1 E-ATS-E7
E-ATS-E1
M M M
E-ATS-E2 E-ATS-E7 E-ATS-E8
ETM
ETM
E-ATS-E8
E-ATS-E2
7 7
ETM ETM
ETM ETM
ETM
ETM
E-FP-2
M
E-ATS-E1
M M M
E-ATS-E9 E-ATS-S1 E-FP-2
7 7 76 6 6 6 6
E-ATS-E9
E-ATS-S1 E-ATS-E7
E-ATS-E1
E-ATS-E8
E-ATS-E2
M
NORMAL DISTRIBUTION SWITCHGEAR A
8 RELAY
DAN1
M
UA4UA3
RELAY
DAN2
RELAY
DAN3
RELAY
DAN4
RELAY
DAN8
RELAY
DAN7
RELAY
DAN6
RELAY
DAN5
RELAY
DAN9
RELAY
DAN10
RELAY
DAN11
RELAY
DAN12
RELAY
DAN16
RELAY
DAN15
RELAY
DAN14
RELAY
DAN13
M
NORMAL DISTRIBUTION SWITCHGEAR B
8 RELAY
DBN1
M
UB2UB1
RELAY
DBN2
RELAY
DBN3
RELAY
DBN4
RELAY RELAY RELAY RELAY
RELAY
DBN9
RELAY
DBN10
RELAY
DBN11
RELAY
DBN12
RELAY
DBN14
RELAY
DBN13
PARALLELLING SWITCHGEAR A
8 RELAY
DAG1
5 RELAY
DAG2
RELAY
DAG3
RELAY
DAG4
RELAY RELAY RELAY RELAY
RELAY
DAG9
RELAY
DAG10
RELAY
DAG11
RELAY
DAG12
RELAY
DAG14
RELAY
DAG13
6 8 RELAY
DBG1
RELAY
DBG2
RELAY
DBG3
RELAY
DBG4
RELAY
DBG8
RELAY
DBG7
RELAY
DBG6
RELAY
DBG5
RELAY
DBG9
RELAY
DBG10
RELAY
DBG11
RELAY
DBG12
RELAY
DBG14
RELAY
DBG13
PARALLELLING SWITCHGEAR B
M4 9
GA-1
M
GA-2
M
GA-3
M
GA-4
DAG8 DAG7 DAG6 DAG5
RELAY
DBG16
RELAY
DBG15
DBN8 DBN7 DBN6 DBN5
M4 9
GB-1
M
GB-2
M
GB-3
M
GB-4
RELAY
DBG16
RELAY
DBG15
1 1
RELAY
DAN17
RELAY
DAN18
RELAY
DAN19
RELAY
DAN20
DAN24 DAN23 DAN22 DAN21
RELAY RELAY RELAY RELAY
RELAY
DAG16
RELAY
DAG15
RELAY
DAG17
RELAY
DAG18
RELAY
DAG19
RELAY
DAG20
RELAY
DAG22
RELAY
DAG21
RELAY
DAG24
RELAY
DAG23
M
GA-5
RELAY
DBN17
RELAY
DBN18
RELAY
DBN19
RELAY
DBN20
RELAY
DBN22
RELAY
DBN21
RELAY
DBG24
RELAY
DBG23
RELAY
DBG17
RELAY
DBG18
RELAY
DBG19
RELAY
DBG20
RELAY
DBG22
RELAY
DBG21
RELAY
DBG24
RELAY
DBG23
M
GB-5
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS:
OFFICE OF
FACILITIES
MANAGEMENT
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot
6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
BUILDING IS FULLY SPRINKLERED
A NEW HOSPITAL FOR
VAMC ORLANDO, FLORIDA
Orlando, Florida
673-950
NOTES:
KEY NOTES:
Professional Seals:
THESE RECORD DRAWINGS HAVE BEEN PREPARED
BY THE DESIGN PROFESSIONAL BASED ON
INFORMATION FURNISHED BY OTHERS. NO FIELD
VERIFICATION OF THEIR CORRECTNESS HAS
OCCURED. THE DESIGN PROFESSIONAL CANNOT
ASSURE THE ACCURACY OR INFORMATION
INCORPORATED INTO THESE RECORD DRAWINGS.
REFER TO SUPPLEMENTAL SHOP DRAWINGS
INCLUDED WITH THE RECORD DOCUMENT SET FOR
ADDITIONAL INFORMATION.
No. Description Date
RECORD DRAWINGS 12-01-2015
29 OCTOBER, 2009 KLM EB/RLF
CENTRAL ENERGY PLANT
E-EP5.021
POWER MONITORING WIRING DIAGRAMS
NOT TO SCALE
2 POWER MONITORING SYSTEM LAYOUT
1 MULTI-FUNCTION POWER CIRCUIT MONITOR AT MAIN
CIRCUIT BREAKER.
2 ELECTRONIC TRIP CIRCUIT BREAKER WITH
INTEGRAL POWER MONITOR (TYPICAL).
3 ETHERNET COMMUNICATIONS CARD.
4 3/4" CONDUIT WITH (1) 4 PAIR CATEGORY 6 RATED
NETWORK CABLE TO PATCH PANEL IN
COMMUNICATIONS ROOM 1A114.
5 POWER MONITORING SYSTEM COMMUNICATION
CABLE WITHIN SWITCHGEAR ENCLOSURE (TYPICAL).
6 3/4" CONDUIT WITH POWER MONITORING SYSTEM
COMMUNICATIONS WIRING AS REQUIRED.
7 MULTI-FUNCTION POWER CIRCUIT MONITOR
MOUNTED ON THE LOAD SIDE OF THE AUTOMATIC
TRANSFER SWITCH. MOUNT MONITOR WITHIN THE
AUTOMATIC TRANSFER SWITCH ENCLOSURE. THIS
MONITOR SHALL BE USED FOR THE EMERGENCY
POWER SUPPLY SYSTEM (EPSS) TEST REPORTING
FUNCTIONS. REFER TO SPECIFICATIONS SECTION
262411 FOR CIRCUIT MONITOR REQUIREMENTS.
8 MICROPROCESSOR BASED MULTIFUNCTION
OVERCURRENT RELAY WITH INTEGRAL POWER
MONITORING FUNCTIONS, TYPICAL.
9 MULTI-FUNCTION POWER CIRCUIT MONITOR AT
GENERATOR MAIN CIRCUIT BREAKER IN
SWITCHGEAR (TYPICAL).
10 DEVICE PROVIDED WITH THE POWER MONITORING
SYSTEM (PMS).
11 3/4" CONDUIT WITH (1) 4 PAIR, CATEGORY 6 RATED
CABLE.
12 CONNECTION AS REQUIRED FOR REMOTE
REPORTING OF ENERGY USAGE DATA TO THE
VETERAN INTEGRATED SERVICE NETWORKS (VISN).
NOT TO SCALE
1 POWER MONITORING WIRING DIAGRAM
PARALLELING SWITCHGEAR "A"
1200A
AUTOMATIC
TIE BREAKER
1200AF
150AT
52TC
RELAY 300:5
1200AF
50AT
52TC
100:5
1200AF
150AT
52TC
300:5
1200AF
60AT
52TC
100:5
1200AF
150AT
52TC
300:5
1200AF
150AT
52TC
300:5
AAAA A
2250KW, 12.47KV,
3Ø, 3W
PRIME RATED
GEN "GA-1"
NORMAL DISTRIBUTION SWITCHGEAR "A"
1200A N.O.
AUTOMATIC
TIE BREAKER
1200AF
540AT
52TC
RELAY 600:5
1200AF
160AT
52TC
200:5
1200AF
160AT
52TC
200:5
1200AF
150AT
52TC
300:5
1200AF
160AT
52TC
RELAY 200:5
1200AF
540AT
52TC
600:5
1200A, 12.47KV, 3 PHASE, 3 WIRE, 36KAIC, 750MVA (SECTION 2) 1200A, 12.47KV, 3 PHASE, 3 WIRE, 36KAIC, 750MVA (SECTION 1)
1200A, 12.47KV, 3 PHASE, 3 WIRE, 36KAIC, 750MVA (SECTION 1)
TC
300:5 A
1200AF
270AT
52TC
300:5 A
1200AF
270AT
52TC
300:5 A
1200AF
270AT
52TC
300:5
1200AF
270AT
52TC
300:5
N.O.
CIRCUIT #1 TO
OUC SUBSTATION #32
(PREFERRED CIRCUIT)
720A RELAY
OUC PAD
MOUNTED
SWITCH #3
OUC PAD MOUNTED
SWITCH #2
OUC PAD MOUNTED
SWITCH #1
M
OUC PAD MOUNTED
PRIMARY METERING
CABINET #4
OUC PAD MOUNTED
PRIMARY METERING
CABINET #3
MMMM
EQUIPMENT PROVIDED BY UTILITY
COMPANY UNLESS NOTED
OTHERWISE
E3
E-EP6.003
CEP
SUBSTATION
SS-EG1
E4
E-EP6.005
CEP CHILLER
SUBSTATION
SS-CH1/2
N2
E-EP6.001
NORMAL DIST
SWITCHGEAR "B"
SECTION 1
N1
E-EP6.001
NORMAL DIST
SWITCHGEAR "B"
SECTION 2
N5
E-EP6.003
CEP
SUBSTATION
SS-EN1
MMMM M
OUC PAD MOUNTED
PRIMARY METERING
CABINET #1
OUC PAD MOUNTED
PRIMARY METERING
CABINET #2
RELAYRELAY RELAY RELAY RELAY
RELAY
RELAY RELAYRELAY RELAY RELAYRELAY RELAY
AUTOMATIC N.O.
TIE BREAKER
AUTOMATIC N.O.
TIE BREAKER
DAG1 DAG2 DAG3 DAG4 DAG14 DAG15 DAG16 DAG24
TAG1
DAN1 DAN2 DAN3 DAN4 DAN5 DAN6 DAN12
TAN1
DAN13-
DAN16
DAN17 DAN18 DAN19 DAN20 DAN21 DAN24DAN22
1200AF
160AT
52TC
200:5 A
RELAY
DAG17-
DAG20
1200AF
160AT
52TC
200:5 A
RELAY
DAG11
A
DAG21
1200AF
120AT
52TC
RELAY 300:5
DAN7-
DAN10
DAN23
10 9 2
2250KW, 12.47KV,
3Ø, 3W
PRIME RATED
GEN "GA-2"
2250KW, 12.47KV,
3Ø, 3W
PRIME RATED
GEN "GA-3"
2250KW, 12.47KV,
3Ø, 3W
PRIME RATED
GEN "GA-4"
FUTURE
2250KW, 12.47KV,
3Ø, 3W
PRIME RATED
GEN "GA-5"
CONTINUOUS GROUND BUS
TC
200:5
TC
200:5
TC
200:5
1200AF
200AT
52TC
200:5 200:5
1200AF
200AT
1200AF
200AT
1200AF
200AT
RELAY RELAYRELAY RELAY RELAY
GA1 GA2 GA3 GA4 GA5
G G G G G
1 1 1 1 3
SPACE 6
NGR-A1
NGR-A2
NGR-A3
NGR-A4
GARAGE
SUBSTATION
SS-PG1
CLINIC
SUBSTATION
SS-CG2
TYPICAL
FOR 4
SPACE
A
RELAY
CONTINUOUS GROUND BUS
DOM
SUBSTATION
SS-DN1
CLINIC
SUBSTATION
SS-CN4
CLINIC
SUBSTATION
SS-CN3
5 5
1200AF
60AT
52TC
100:5RELAY
GARAGE
SUBSTATION
SS-PN1
1200AF
150AT
52TC
RELAY 300:5
N6
E-EP6.005
CEP
SUBSTATION
SS-CH1/2
A
CIRCUIT #2 TO
OUC SUBSTATION #32
(ALTERNATE CIRCUIT)
720A RELAY
N.C.
N.C.N.C.
N.O.N.C.
N.C.N.C.
N.C.N.O.
N.C.N.C.
2,500KW
LOAD BANK
TYPICAL
FOR 6
SPACE
300:5 A
RELAY
DAG5-
DAG10
1200AF
160AT
52TC
200:5 A
RELAY
DAG12
TC
300:5 A
E6
E-EP6.005
CEP CHILLER
SUBSTATION
SS-CH3/4
RELAY
DAG13
1200AF
150AT
E7
E-EP6.005
CEP CHILLER
SUBSTATION
SS-CH5/6
CLINIC
SUBSTATION
SS-CG1
SPACE
A
RELAY
TYPICAL
FOR 4
DOM
SUBSTATION
SS-DG1
1200AF
150AT
52TC
RELAY
A
DAG22
1200AF
160AT
52TC
200:5 A
RELAY
DAG23
A
E5
E-EP6.003
CEP
SUBSTATION
SS-EG1
1200AF
150AT
52TC
RELAY 300:5
1200AF
160AT
52TC
200:5RELAY
CLINIC
SUBSTATION
SS-CN1
1200AF
160AT
52TC
200:5RELAY
CLINIC
SUBSTATION
SS-CN2
1200AF
150AT
52TC
RELAY 300:5
TYPICAL
FOR 4
SPACE
300:5RELAY
DAN11
1200AF
150AT
52TC
RELAY 300:5
1200AF
160AT
52TC
200:5
N7
E-EP6.003
CEP
SUBSTATION
SS-EN1
RELAY
1200AF
150AT
52TC
300:5
N8
E-EP6.005
CEP
SUBSTATION
SS-CH3/4
RELAY
SEE SHEET E-EP5.007 FOR ELEVATION
SEE SHEET E-EP5.008 FOR ELEVATION
1200A, 12.47KV, 3 PHASE, 3 WIRE, 36KAIC, 750MVA (SECTION 2)
SPARE SPARE
SPARE SPARE 9
UA3UA4
TCRELAY
TCRELAY
13 1313 13
12KV 12KV 12KV 12KV 12KV
12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV
12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV 12KV
MMMMM
M M
SPARE
N9
E-EP6.005
CEP
SUBSTATION
SS-CH5/6
A A A A A
14 14 14 14
12KV 12KV
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT/ENGINEERS:
OFFICE OF
FACILITIES
MANAGEMENT
on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot
6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r in ch o ne fo ot
VA FORM 08-6231, OCT 1978
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Department of Veterans Affairs
BUILDING IS FULLY SPRINKLERED
A NEW HOSPITAL FOR
VAMC ORLANDO, FLORIDA
Orlando, Florida
673-950
NOTES:
SHEET NOTES:
Professional Seals:
THESE RECORD DRAWINGS HAVE BEEN PREPARED
BY THE DESIGN PROFESSIONAL BASED ON
INFORMATION FURNISHED BY OTHERS. NO FIELD
VERIFICATION OF THEIR CORRECTNESS HAS
OCCURED. THE DESIGN PROFESSIONAL CANNOT
ASSURE THE ACCURACY OR INFORMATION
INCORPORATED INTO THESE RECORD DRAWINGS.
REFER TO SUPPLEMENTAL SHOP DRAWINGS
INCLUDED WITH THE RECORD DOCUMENT SET FOR
ADDITIONAL INFORMATION.
No. Description Date
RECORD DRAWINGS 12-01-2015
29 OCTOBER, 2009 KLM EB/RLF
CENTRAL ENERGY PLANT
E-EP6.002
SINGLE LINE DIAGRAM
1 4" C - (3) #2/0 (15 KV, MV-105,TYPE EPR, SHEILDED) + (1)
#2/0 XHHW GROUND. ROUTE FEEDER BELOW FLOOR
SLAB, CONDUIT SHALL BE SCHEDULE 80 PVC.
2 SEE SHEET E-EP6.007 FOR GROUNDING REQUIREMENTS.
3 4" SCHEDULE 80 PVC CONDUIT FOR FUTURE USE. SEE
SHEET E-ES1.008 FOR ROUTING.
4 (3) #4/0 (15KV, MV-105, TYPE EPR, SHIELDED) + (1) #4/0
XHHW GROUND. ROUTE CONDUCTORS THROUGH THE 5"
CONCRETE ENCASED DUCT BANK AND MANHOLE
SYSTEM. REFER TO SITE PLAN FOR DUCT BANK LAYOUT.
5 4" C - (3) #1 (15KV, MV-105, TYPE EPR,SHIELDED) + (1) #1
XHHW GROUND. ROUTE FEEDER BELOW FLOOR SLAB,
CONDUIT SHALL BE SCHEDULE 80 PVC.
6 FULLY EQUIPPED SPACE INCLUDING CRADLE, RELAY,
CONTROL WIRING AND ALL COMPONENTS AS REQUIRED
TO RECEIVE FUTURE CIRCUIT BREAKER.
7 NEUTRAL GROUNDING RESISTOR RATED FOR 8,000V
LINE TO GROUND, 10A CONTINUOUS DUTY, 800 OHMS,
NEMA TYPE 3R ENCLOSURE. SEE SHEET E-EP6.007 FOR
CONNECTIONS.
8 ALL OF THE CIRCUIT BREAKERS IN THIS SWITCHGEAR
ARE AUTOMATICALLY CONTROLLED FROM THE
GENERATOR PARALLELING SWITCHGEAR MASTER
CONTROLLER SERVING SYSTEM "A". SEE 1/E-EP5.013
FOR CONTROL WIRING CONNECTION DIAGRAM.
9 (3) #1/0 (15KV, MV-105, TYPE EPR, SHIELDED) + (1) #1/0
XHHW GROUND. ROUTE CONDUCTORS THROUGH THE 5"
CONCRETE ENCASED DUCT BANK AND MANHOLE
SYSTEM. REFER TO SITE PLAN FOR DUCT BANK LAYOUT.
10 4" C - (3) #4/0 (15 KV, MV-105,TYPE EPR, SHEILDED) + (1)
#4/0 XHHW GROUND. ROUTE FEEDER BELOW FLOOR
SLAB, CONDUIT SHALL BE SCHEDULE 80 PVC.
11 TO PARALLELING SWITCHGEAR "B", SEE SHEET
E-EP6.001 FOR CONTINUATION.
12 2,500KW PERMANENT LOAD BANK WITH 12,470V, 3
PHASE, 3 WIRE INPUT.
13 6"C - (3)#750 KCMIL (15KV, MV-105, TYPE EPR, SHIELDED)
+ (1)#4/0 XHHW GROUND.
14 MAKE CONNECTIONS TO THE PRIMARY METERING
CABINET UNDER DIRECT SUPERVISION FROM THE
ORLANDO UTILITIES COMMISSION (OUC).
THIS PACKAGE REQUIRES WORK WITHIN EACH BUILDING ON
THE CAMPUS. EXTEND THE MEDIUM VOLTAGE
CONDUCTORS TO THE SUBSTATIONS INDICATED. PROVIDE
MEDIUM VOLTAGE CABLE TERMINATIONS AT BOTH ENDS IN
ACCORDANCE WITH THE SPECIFICATIONS. THE
CONDUCTORS SHALL BE ROUTED THROUGH THE
CONCRETE ENCASED DUCT BANKS FROM THE CENTRAL
ENERGY PLANT TO EACH BUILDING, REFER TO THE SITE
PLANS FOR THE DUCT BANK ROUTING. IN MULTI-STORY
BUILDINGS WHERE SUBSTATION(S) ARE LOCATED ON THE
UPPER FLOORS (CLINIC, HOSPITAL AND DOMICILIARY), THE
CONDUCTORS SHALL BE ROUTED THROUGH THE RISER
CONDUITS THAT WILL BE PROVIDED UNDER THE SPECIFIC
BUILDING PACKAGE.
REFER TO SHEET E-EP6.006 FOR CAMPUS WIDE SUBSTATION
CONNECTION DIAGRAM.
REFER TO SITE PLANS FOR LOCATIONS OF SUBSTATIONS IN
THE CLINIC, HOSPITAL, WAREHOUSE, PARKING GARAGE, DOM
AND CLC BUILDINGS.
A.
B.
KEY NOTES:
C.