BB Correct Patient Privacy Deficiencies 2N/2S Lake City, FL Project # 573A4-18-603
Solicitation number
36C24825R0067
Issued by

About this file

This document is a Pre-Bid Request for Information (RFI) dated June 2, 2025, for the Lake City VA Medical Center Patient Privacy Deficiencies Correction project. The RFI contains six technical inquiries from potential bidders and the corresponding architect/engineering (A/E) responses, addressing missing or unclear drawing sheets, electrical receptacle specifications, cross-section details, and signage specifications. The responses provide clarification by referencing specific sheet numbers (AE709, E001, AE503, AE302) and offering PDF copies of the requested documentation to ensure bidders have complete and accurate project information.

View the file

Other files

File Type Posted
573A418603 Visitor Registry.pdf PDF
36C24825R0067 0003.pdf PDF
RFIs 36C24825R0067 Correct Patient Privacy.pdf PDF
AE302.pdf PDF
AE709.pdf PDF
AE503.pdf PDF
SAM DBA 05_02_25.pdf PDF
36C24825R0067 0002.docx DOCX document
36C24825R0067 0001.docx DOCX document
36C24825R0067_1.pdf PDF
Specifications (2).zip ZIP file
S02-Solicitation Attachments.zip ZIP file
36C24825R0067_1.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Pre-Bid RFIs June 2, 2025 A/E Responses

573A4-18-603

CORRECT PATIENT PRIVACY DEFICIENCIES

Lake City VAMC

1. Sheet AE709 is missing from the drawing set. Will the VA please provide it?

RESPONSE

A PDF copy of Sheet AE709 is provided with this response.

2. Sheet EP-104 in Rooms 308 and 309, a receptacle symbol with a superscript "T". Please indicate the design intent for this symbol.

RESPONSE

Refer to Sheet E001 under “SYMBOL” and “DESCRIPTION”. These are the left-hand columns on the sheet.

The last sentence in the first note under POWER DEVICES reads: “ "T" INDICATES

TAMPER RESISTANT” .

3. Please provide cross-section details 1/A/503, 2/A503, 3/A503, 4/A503, 5/A503 & 6/A503 noted on sheet AE101.

A PDF copy of Sheet AE503 is provided with this response.

4. Please provide cross section detail 4/A302, 8/AE302, 9/AE302, 9A/A302 & 10/A302 noted on sheet AE101 next to the Equipment storage room A213 on the second floor. Sheet A302 is not included in the plans. Please review and advise.

A PDF copy of Sheet AE302 is provided with this response.

5. Sheet A503 is not included in the plans. Please review and advise.

A PDF copy of Sheet AE503 is provided with this response.

6. Please provide Signage specifications for Key notes: A, B, C, D,E & F noted on the signage plans. No information was provided.

RESPONSE

Sign Types A, B, C, D, E, and F are shown on Sheet AE709. Theses are sign type details 1,2,3,4,5 and 6/AE709.