ADDITIONAL QUESTIONS AND ANSWERS TO WATER CHILLER TREATMENT SOLICITATION 36C24725Q0026.docx
DOCX document 14 KB Posted
- Attached to
- J046--WATER TREATMENT AND CHILLER PLANT SERVICES
- Solicitation number
- 36C24725Q0026
About this file
This document appears to be a set of Additional Questions and Answers (Q&A) related to Solicitation 36C24725Q0026 for Water Chiller Treatment Services issued by the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 7.
The key details from the Q&A include:
- The solicitation is for 2 Marley cooling towers with 2 cells each, with Tower 1 cell dimensions of 14 ft x 22.5 ft and Tower 2 cell dimensions of 12 ft x 22.5 ft.
- The facility has 5 chillers - 3 at 750 tons and 2 at 500 tons.
- There are 4 chilled water loops, but no hot water loops.
- The facility has 4 steam boilers - 3 at 600 HP and 1 at 400 HP.
- The facility has a water softener, deaerator, and reverse osmosis (RO) system in the boiler plant.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24725Q0026 0003.docx | DOCX document | |
| QUESTIONS AND ANSWERS PAGE 2.docx | DOCX document | |
| 36C24725Q0026 0001.docx | DOCX document | |
| 36C24725Q0026.docx | DOCX document | |
| Wage Determination No. 2015-4429.docx | DOCX document | |
| VA Directive1061.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Please see below for RFIs with respect to the above referenced solicitation:
1. How many cooling tower systems? What are the tonnages? 2 Marley Towers
2. If cooling tower tonnage is not available, do you have annual water make up numbers? Annual water make up roughly 14,270,868-gals year.
3. How many cooling tower cells, and what are the dimensions of each cell? 2 Towers 2 Cells per tower, Tower 1 Cell Dimensions each Cell 14 Ft X 22.5 FT. Tower 2 Cell Dimensions each Cell 12 FT X 22.5 FT.
4. How many chillers? What are the tonnages? 5 3 750 Tons and 2 500 Tons.
5. How many chilled loops are present? How many hot water loops are present? 4 Loops leaving 1 manifold. No Hot water loop.
6. How many steam boilers are present? What is the horsepower of each boiler? 4 Steam Boilers 3 600 HP and 1 400 HP, 3 low pressure fire tubes.
7. Is there a water softener in the boiler plant for makeup? Yes, also DA and Condensate tanks have emergency make up auto valve. RO unit is 8 GPM.
8. Is there a Deaerator? YES