S06 36C24623Q0642 Attachment II - Architectural and Structural.pdf
PDF 5 MB Posted
- Attached to
- 6515--OR Lighting System
- Solicitation number
- 36C24623Q0642
About this file
This solicitation is for an OR lighting system for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6. Key details include the solicitation number 36C24623Q0642 for opportunity 6515--OR Lighting System. The solicitation type is for an OR lighting system. The agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 6. No other salient information is provided in the document.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPUP
UP
DNDN
11 13 14 15 16 17 18
N
M
K
J
H
G
12 19
L
Ls
H.6
G.4
G.6
F.9
F.4
F.3
12' - 7 3/4" 9 5/8" 8' - 6 5/8" 22' - 0" 22' - 0" 22' - 0" 22' - 0" 22' - 0"
/1
/4
/8
N.4
12.6
A500
GENERAL OR
GENERAL OR
GENERAL OR
HYBRID OR
HYBRID
CONTROL
ELECTRICAL
CLOSET
2007A
EQUIPMENT
STORAGE
EQUIPMENT
STORAGE
ORTHO OR
SEMI-RESTRICTED
CORRIDOR
SEMI-RESTRICTED
CORRIDOR
SCRUB
SCRUB
SCRUB
SEMI-RESTRICTED
CORRIDOR
SEMI-RESTRICTED
CORRIDOR
SEMI-RESTRICTED
CORRIDOR
DS - 3
SCRUB
HYBRID
EQUIPMENT
RAMP
RAMP
CLEAN CORE
CLEAN CORE
RAMP
RAMP/CORRIDOR
DB206
DB205
D213DB212
DB214
DB221
DB217A
DB221A
DB222
DB281B
DB220A
DC2-B1
PROJECT
LIMITS / PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
COR FOR A RESOLUTION. ADJUSTMENTS TO DIMENSIONS AND CONDITIONS SHOWN MAY BE
REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS
OTHERWISE NOTED. DIMENSIONS ARE REFERENCED FROM FACE OF FINISH AT EXISTING
CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE
START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL
ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW
WORK FLUSH WITH EXISTING ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION
THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION
OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING AND ITS
OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA.
BARRIERS SHALL NOT INTERFERE WITH THE OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO
PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS
OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN ACCORDANCE WITH VAMC'S
EXISTING ROOF WARRANTY. COORDINATE ALL MODIFICATIONS TO THE ROOF WITH THE COR.
• ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE REFERENCED FROM SHEET A000.
GENERAL NEW WORK NOTES
NEW WORK NOTES
1. NOT USED
2. EXISTING PLUMBING PIPE.
3. EXISTING MECHANICAL EQUIPMENT.
4. EXISTING SKYLIGHT.
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A102
OVERALL NEW WORK PLAN -
SECOND FLOOR
RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JAS
1/8" = 1'-0"
OVERALL NEW WORK PLAN - SECOND FLOOR
NO. DESCRIPTION DATE
2 Life Safety Revision 1-10-2022
DNDN
13 14 15 16 17 18
N
M
K
L
Ls
A500
/2
/2
/4
/8
M6
M6
M6
M6_C
M6
M3
M3
M1B
M1B
M3
M1B
M1B
M1B
SW38_2
SW38_2
SW38_2
M3_1
M3_1
M3_1 M3_1
M1BM1B
M1B M1B
M1B
M1B M1B
M1B
M6
M1B
M1B
M3 L M3B M3
M3_CL
M3 L
M3B
M6_C
M3_1
M1B
M1B
M1B
M3_1
M6_1
GENERAL OR
GENERAL OR
GENERAL OR
SCRUB
SCRUB
SCRUB
HYBRID OR
CLEAN CORE
M3BL
M3BL
M3BL
M3_1
M3B
M3
A510
A510
H
M3_1
8' - 0 5/8" 9' - 7 1/8" 12' - 6 5/8"
3 5/8"
18' - 3 5/8" 3' - 1 7/8"
6 1/2"
1' - 0"
21' - 0" 4' - 8 3/4" 2' - 2" 7' - 0 1/2" 8' - 0 3/4" 10' - 0 1/4" 1' - 0" 2' - 3"
8' - 4 7/8"
/4
/4
/4
/1
SSC
ORT
SD1 SD1 SD1 SD1
SD1 SD1
M6_L
1:20
SLOPE
DOWN
A800
A800 6
S L O
P E
D O
W N
/4
/4
/1
/4
/2
/8
M3L_1
M6_L
M3_CL
BW
MS MS MS
A520
A520
A520
A520
N.4
12.6 8' - 9 5/8" 22' - 0" 22' - 0" 22' - 0" 22' - 0" 22' - 0"
14' - 6 5/8" 15' - 1"
1' - 5 3/4"
28' - 8 1/2"
HYBRID
CONTROL
SEMI-RESTRICTED
CORRIDOR
SEMI-RESTRICTED
CORRIDOR
A801 2
A8018 6
LC
LC
LC
EB
LB
LB
ORT
AC
MB
MTR
MB
/2
20202010 2030 2040A
2040B
2060B
2060C
EQUIPMENT
STORAGE
/2
2' - 0"
A202.1A
TYP.
NCP
IM
WPH
MB
MTR
BW
ORT
AC
EB
LB
LB
LB
LB
NCP
MB
MB
IM
BW
MB
MB
IM
IM
NCP
MTR
MTR
M6_1
NCP
WPH
M3_CL
10' - 6 3/4" 10' - 7 1/8"
WPH
5 5
M3_1
B1
C2
B2
C1 MB
M3_CL
M1B
WPH
6 5/8" 11' - 9" 4' - 10" 8' - 4 5/8" 4' - 10" 2' - 0" 4' - 10" 7' - 9" 4' - 10" 7' - 9" 4' - 10" 2' - 0" 4' - 10" 8' - 9" 4' - 10" 8' - 9" 4' - 10" 2' - 0" 4' - 10" 7' - 7 3/8" 4' - 10" 3' - 1 1/8"
F
A
A
A
A A A A A A A A A A
M3B
2' - 0"
1' - 0 1/8"
/8
4' - 6"
/4
/1
/8
14' - 0 7/8" 1' - 0 1/8"
A500
M1B
M1B
M3B
M1BM1B M3B
M1B
M1B M3B
1 3
M3B
M3_C
M1B
M1B
/2
M3B M3B M3BM3B
M3B M3 M3_1
M6_1
M6_C
M3_1
M3_1
M3_1
AC
M6M6
OC
OC
OC
RAMP
135.00°
.0
/2
M1B
M3B
A520
A520
A520
OC
SSC
SSC
SSC
SSC
SSC
SSC
FEC
M3_C
/4
/1
/2
/1
8' - 1 1/4" 14' - 11 5/8" 1' - 4" 5' - 6 1/4" 1' - 3" 5' - 6 1/4" 1' - 9" 12' - 0 1/2" 1' - 0"
1' - 0 3/4" 21' - 4 7/8" 7 1/8" 1' - 2 3/8"
10' - 11 1/4" 9' - 0 3/8" 10" 3' - 7 7/8" 9' - 3 3/4" 8' - 4 7/8" 1' - 4 5/8"
2041B
M3_CL
FLAT
M3B
M3B
M3
/8
/4
M3_1
M6_1
S-3
ELECTRICAL
CLOSET
2007A
13'-5 5/8''
14'-0 5/8''
12'-10 5/8''
EXISTING STAIR
DS-3
M3_C
13'-5 5/8''
A900
12'-10 5/8'' 5
A900
13'-5 5/8''
M3B
M3BL
M3BL
M6_L
/4
/1
6" 8 1/8"
M1B
M1B
M1B
1' - 3 3/4"
TEMP DEAD SPACE
DUE TO PHASING
/8
2041A
HYBRID EQUIP
M3B
SEMI-
RESTRICTED
CORRIDOR
SEMI-RESTRICTED
CORRIDOR
NEW WORK NOTES
1. PROVIDE 1 1/2" FLOOR EXPANSION JOINT
2. PROVIDE 1 1/2" WALL EXPANSION JOINT TYPICAL
3. PROVIDE 1 1/2" FLOOR TO WALL EXPANSION JOINT TYPICAL
4. SEE HYBRID OR DRAWINGS FOR ADDITIONAL INFORMATION.
COORDINATE LEAD REQUIREMENTS WITH VA SUPPLIED
PHYSICIST'S REPORT
5. 4' HIGH STAINLESS STEEL CORNER GUARD.[CG#2]
6. FULL HEIGHT ACROVYN CORNER GUARD [CG#1]
7. FIRE EXTINGUISHER AND CABINET
8. NOT USED.
9. PROVIDE SPRINKLER DRAIN LINE DISCHARGE ON TO ROOF.
6" MINIMUM ABOVE EXISTING ROOF.
10. NOT USED.
11. EXISTING DOOR AND HARDWARE RELOCATED TO THIS
LOCATION.
12. PROVIDE 36'' HIGH STAINLESS STEEL HANDRAIL AT BOTH
SIDE OF RAMP.
13.PROVIDE CONCRETE LINTEL TO ACCOMMODATE WITH NEW
FLOOR HEIGHT. KEEP MIN 84'' HEAD CLEARANCES.
COORDINATE WITH EXISTING WALL AND DOOR SCHEDULE.
14. INFILL WALL TO MATCH EXISTING ADJACENT WALLS AND
ALIGN ALL SIDES.
15. FLOORING SHALL EXTEND DOWN OVER EXPOSED
CONCRETE. REMOVE STUDS BELOW OPENING AS REQUIRED
TO EXTEND FLOOR THRU THE OPENING. SEE FINISH
SCHEDULE FOR FLOOR FINISH.
16. PROVIDE 1/4'' GWB AND LAMINATE TO THIS PARTITION..
17. PROVIDE 1 HOUR RATED SHAFT WALL ON TOP OF
EXISTING WALL (1 1/2'' CH STUD @ 24'' O.C. MAX. 1'' GYPSUM
LINER ONE SIDE AND 1 LAYER OF 5/8" GWB OTHER SIDE.
EXTEND WALL ASSEMBLY TO DECK ABOVE.) REMOVE ALL
WALL MOUNTED ITEMS AND FIXTURES BEFORE SHAFT WALL
INSTALLATION. EXTEND ALL NECESSARY DEVICES THROUGH
SHAFT WALL.
PROJECT
LIMITS / PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND
CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE
ATTENTION OF THE COR FOR A RESOLUTION. ADJUSTMENTS
TO DIMENSIONS AND CONDITIONS SHOWN MAY BE REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT
NEW CONSTRUCTION UNLESS OTHERWISE NOTED.
DIMENSIONS ARE REFERENCED FROM FACE OF FINISH AT
EXISTING CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST
BE FIELD VERIFIED PRIOR TO THE START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO
INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR
SERVICES TO BE READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES
WHICH WILL REMAIN EXPOSED, ALIGN NEW WORK FLUSH WITH
EXISTING ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN
A WATER TIGHT CONDITION THROUGHOUT THE ENTIRE
CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY
CONSTRUCTION OPERATIONS. TAKE ALL PRECAUTIONS
NECESSARY TO PROTECT THE BUILDING AND ITS OCCUPANTS
DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY
TO THE CONSTRUCTION AREA. BARRIERS SHALL NOT
INTERFERE WITH THE OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN
THE AREA OF RENOVATION TO PREVENT THE SPREAD OF
DUST TO OCCUPIED AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET
ARE FOR THIS ONLY UNLESS OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE
IN ACCORDANCE WITH VAMC'S EXISTING ROOF WARRANTY.
COORDINATE ALL MODIFICATIONS TO THE ROOF WITH THE
COR.
• ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET
CAN BE REFERENCED FROM SHEET A000.
GENERAL NEW WORK NOTES
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A102.1A
NEW WORK PLAN - SECOND FLOOR -
PHASE 1 - AREA A
RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JHT
1/4" = 1'-0"
NEW WORK PLAN -SECOND FLOOR - PHASE 1 - AREA A
WALL TYPE SCHEDULE - PHASE 1
TYPE STC DESCRIPTION
FIRE
RATING UL REMARKS
M1B N/A 1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND GWB 4" ABOVE CEILING.
FASTEN STUD TO UNDERSIDE OF DECK.
M3 N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND GWB TO 4" ABOVE
FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48"
O.C. MAX
M3 L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR
STRUCTURE ABOVE AT 48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3 L_l N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" FIRERATED FIRERATED GWB ONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND PARTITION TO DECK ABOVE.
1 HR - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_1 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND WALL
ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE
COMPONENTS MEET DECK ABOVE.
M3_1SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND PARTITION TO
UNDERSIDE OF DECK ABOVE.
1 HR SMOKE
BARRIER
PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3_2 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB BOTH SIDES. EXTEND
WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR FIRE RATED
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE
COMPONENTS MEET DECK ABOVE.
M3_2S N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB BOTH SIDES. EXTEND
WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR SMOKE
BARRIER
U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR SMOKE BARRIER"
AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS
MEET DECK ABOVE.
M3_C N/A 3 5/8" METAL STUDSAT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND WALL ASSEMBLY TO
UNDERSIDE OF DECK ABOVE.
SMOKE
PARTITION
- PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS
MEET DECK ABOVE
M3_C L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWBONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE.
EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
SMOKE
PARTITION
- PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND PARTITION TO
UNDERSIDE OF DECK ABOVE.
SMOKE
BARRIER
PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3B N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL ASSEMBLY TO 4"
ABOVE FINISHED CEILING.
M3B L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" LEAD LINED GWB ONE SIDE. EXTEND GWB TO 4"
ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT
48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6 N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND GWB TO 4" ABOVE FINISHED
CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
M6_1 N/A 6" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND WALL ASSEMBLY
TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE
COMPONENTS MEET DECK ABOVE.
M6_C N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND WALL ASSEMBLY TO
UNDERSIDE OF DECK ABOVE.
SMOKE
PARTITION
- PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS
MEET DECK ABOVE
M6_L N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR
STRUCTURE ABOVE AT 48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6B N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL ASSEMBLY TO 4" ABOVE
FINISHED CEILING.
SW245_1 38 1 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 1 LAYERS 5/8" GWB OTHER
SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK ABOVE.
1 HR U 415
SYSTE
M B
SW_2 38 2 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 2 LAYERS 5/8" GWB OTHER
SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK ABOVE.
2 HR U 415
SYSTE
M B
EQUIPMENT SCHEDULE - PHASE 1
MARK NAME VAFCI VAFOI CFCI COMMENTS
AC ANESTHESIA COLUMN *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
B1 LIGHT BOOM 2 *** RELOCATED FROM EXISTING OR #7
B2 LIGHT BOOM 1 *** RELOCATED FROM EXISTING OR #7
BW BLANKET WARMER *** PROVIDE POWER
C1 EQUIPMENT BOOM 1 *** RELOCATED FROM EXISTING OR#7
C2 ANESTHESIA BOOM 1 *** RELOCATED FROM EXISTING OR#7
CRT CART *** EXISTING - RELOCATED THIS PHASE
EB EQUIPMENT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
IM INTEGRATION MONITOR *** PROVIDE POWER AND DATA
LB SURGICAL LIGHT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
LC LIGHT CONTROL *** PROVIDE POWER
MB MARKER BOARD *** *** PROVIDE BLOCKING AS REQUIRED
MS STAINLESS STEEL SHELVES ***
MTR MONITOR *** PROVIDE POWER AND DATA
NCP NITROGEN CONTROL PANEL *** PROVIDE POWER
OC MOBILE OMNI CELL *** PROVIDE POWER AND DATA
ORC OR CART *** EXISTING - RELOCATED THIS PHASE
ORT OR TABLE ***
SSC STAINLESS STEEL CART *** ***
WPH WALL PHONE *** PROVIDE POWER AND DATA
TOILET ACCESSORY SCHEDULE - PHASE 1
MARK DESCRIPTION MOUNTING HEIGHT VAFCI VAFOI VAFCI REMARKS
SD1 AUTOMATIC SOAP DISPENSER 38" A.F.F. TO BOTTOM ***
REFER TO SHEET A600 FOR WINDOW
TYPE AND WINDOW TYPE
ELEVATIONS AND DETAILS
A F
NO. DESCRIPTION DATE
1 Bulletin 1 7-28-2021
2 Life Safety Revision 1-10-2022
3 RFI 62, 63, 67, 68, 71, 72 Stairwell and Clean Core Revisions
2-24-2022
16 17 18
K
J
L
Ls
H.6
A500
EQUIPMENT
STORAGE
SEMI-RESTRICTED
CORRIDOR
ORTHO OR
M3_1
M6_1
M3_1
M3B
M3
M3B
M6
M3B
SW_1
M6_1
SW_1M1B
M3B
A501
6"
5' - 9 7/8" 1' - 0" 12' - 6 1/8" 2' - 2"
7 1/2"
21' - 4 1/2"
9 1/8"
13' - 11 1/4" 8' - 0 3/4" 13' - 3 1/4" 8' - 1 1/4" 7 1/2"
/8
/2
/8
/1
/1
/8
SD1 SD1
6 3/4"
7 1/2"
A802 2
LB
AC
LB
EB
LC
10' - 6 3/4" 2' - 0"
MB
MB
ORT
WPH
10' - 6 1/8" 10' - 11 1/4"
8 10 10 10
6 6
10 10
M3_1
1' - 7 1/2"
11' - 9 3/4" 2060C
2060B
2070 2060A
M3B
M3B
M3B
M1B
M1B
M1B M3 M3_1 M3_1
M1B
M1B
4' - 6" 4' - 6"
/8
1' - 0 1/8"
/8
/8
/2
OC
M1B
M6_C
M1B
M6B
M1B
M3B
E Q
R A
M P
D O
W N
:3 S
O L
ID
C O
N C
R E
T E
S
E E
S E
C T
IO
N
/A
TYP
M6_1 M6B
M3_2
M3_2
/8
/2
/2
/2
FLAT
/4
M3_C
M3_2
R A
M P
D O
W N
:3 S
O L
ID
C O
N C
R E
T E
S
E E
S E
C T
IO
N
/A
/2
M1B
9"
4 4
NEW WORK NOTES
1. PROVIDE 1 1/2" FLOOR EXPANSION JOINT & JOINT COVER.
2. PROVIDE 1 1/2" WALL EXPANSION JOINT & JOINT COVER.
3. FIRE EXTINGUISHER CABINET.
4. PROVIDE 1 1/2" FLOOR TO WALL EXPANSION JOINT TYPICAL
5. EDGE OF RAMP.
6. FULL HEIGHT ACROVYN CORNER GUARD (CG#1).
7. 4' HIGH STAINLESS STEEL CORNER GUARD (CG#2).
8. 5/8" GWB GLUED TO FACE OF CONCRETE COLUMN.
9. ALIGN EDGE OF STUD TO FACE OF CONCRETE BEAM. GLUE 5/8" GWB TO FACE OF BEAM BELOW.
10. PROVIDE BUMPER GUARD (BG#1) AT 34" TO CENTERLINE AFF. BELOW BUMPER RAIL. PROVIDE
WAINSCOT (WS#1). TOP OF WAINSCOT TO TERMINATE AT CENTERLINE OF BUMPER GUARD.
11. SEE SECTION 2/A500 FOR WALL CONTINUATION OVER THE CEILING WHERE THE MECHANICAL
DUCT PASSES.
12. WALL IN THIS LOCATION IS A HALF WALL AND M3 TYPE OF WALL WITH AN EXCEPTION OF
HEIGHT. HEIGHT IS 3'-6" FROM SURGERY FLOOR.
PROJECT LIMITS /
PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
COR FOR A RESOLUTION. ADJUSTMENTS TO DIMENSIONS AND CONDITIONS SHOWN MAY BE
REQUIRED.
• ALL DIMENSIONS ARE REFERENCED FROM FACE OF STUD AT NEW CONSTRUCTION UNLESS
OTHERWISE NOTED. DIMENSIONS ARE REFERENCED FROM FACE OF FINISH AT EXISTING
CONSTRUCTION.
• ALL DIMENSIONS INDICATED +/- ARE APPROXIMATE AND MUST BE FIELD VERIFIED PRIOR TO THE
START OF CONSTRUCTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL
ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR ITS INTENDED USE.
• WHERE WORK ABUTS OR ADJOINS EXISTING SURFACES WHICH WILL REMAIN EXPOSED, ALIGN NEW
WORK FLUSH WITH EXISTING ADJACENT SURFACES.
• THE CONTRACTOR SHALL MAINTAIN THE EXISTING BUILDING IN A WATER TIGHT CONDITION
THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. REPAIR DAMAGE CAUSED BY CONSTRUCTION
OPERATIONS. TAKE ALL PRECAUTIONS NECESSARY TO PROTECT THE BUILDING AND ITS
OCCUPANTS DURING THE CONSTRUCTION PERIOD.
• CONTRACTOR SHALL PROVIDE BARRIERS TO PREVENT ENTRY TO THE CONSTRUCTION AREA.
BARRIERS SHALL NOT INTERFERE WITH THE OWNERS USE OF THE SITE.
• THE CONTRACTOR SHALL PROVIDE NEGATIVE PRESSURE IN THE AREA OF RENOVATION TO
PREVENT THE SPREAD OF DUST TO OCCUPIED AREAS OF THE BUILDING.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS ONLY UNLESS
OTHERWISE NOTED.
• ALL DOORS TO BE MOUNTED 4" FROM FACE OF FINISH UON.
• ALL MODIFICATIONS TO THE EXISTING ROOF SHALL BE MADE IN ACCORDANCE WITH VAMC'S
EXISTING ROOF WARRANTY. COORDINATE ALL MODIFICATIONS TO THE ROOF WITH THE COR.
• ALL SYMBOLS WHOSE TYPE IS NOT INDICATED ON THE SHEET CAN BE REFERENCED FROM SHEET A000.
GENERAL NEW WORK NOTES
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A102.1B
NEW WORK PLAN - SECOND FLOOR -
PHASE 1 - AREA B
RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JAS
1/4" = 1'-0"
NEW WORK PLAN -SECOND FLOOR - PHASE 1 AREA B
WALL TYPE SCHEDULE - PHASE 1
TYPE STC DESCRIPTION
FIRE
RATING UL REMARKS
M1B N/A 1 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND GWB 4" ABOVE CEILING.
FASTEN STUD TO UNDERSIDE OF DECK.
M3 N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND GWB TO 4" ABOVE
FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48"
O.C. MAX
M3 L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR
STRUCTURE ABOVE AT 48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3 L_l N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" FIRERATED FIRERATED GWB ONE SIDE AND 5/8" LEAD
LINED GWB ROOM SIDE. EXTEND PARTITION TO DECK ABOVE.
1 HR - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_1 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND WALL
ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE
COMPONENTS MEET DECK ABOVE.
M3_1SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND PARTITION TO
UNDERSIDE OF DECK ABOVE.
1 HR SMOKE
BARRIER
PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3_2 N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB BOTH SIDES. EXTEND
WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR FIRE RATED
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE
COMPONENTS MEET DECK ABOVE.
M3_2S N/A 3 5/8" METAL STUDS AT 16" O.C.MAX. 2 LAYERS 5/8" FIRE RATED GWB BOTH SIDES. EXTEND
WALL ASSEMBLY TO UNDERSIDE OF DECK ABOVE.
2 HR SMOKE
BARRIER
U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "2 HR SMOKE BARRIER"
AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS
MEET DECK ABOVE.
M3_C N/A 3 5/8" METAL STUDSAT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND WALL ASSEMBLY TO
UNDERSIDE OF DECK ABOVE.
SMOKE
PARTITION
- PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS
MEET DECK ABOVE
M3_C L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWBONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE.
EXTEND PARTITION TO UNDERSIDE OF DECK ABOVE.
SMOKE
PARTITION
- PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M3_SB 3 5/8" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND PARTITION TO
UNDERSIDE OF DECK ABOVE.
SMOKE
BARRIER
PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "SMOKE BARRIER"
M3B N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL ASSEMBLY TO 4"
ABOVE FINISHED CEILING.
M3B L N/A 3 5/8" METAL STUDS AT 16" O.C. MAX. 5/8" LEAD LINED GWB ONE SIDE. EXTEND GWB TO 4"
ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT
48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6 N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND GWB TO 4" ABOVE FINISHED
CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR STRUCTURE ABOVE AT 48" O.C. MAX
M6_1 N/A 6" METAL STUDS AT 16" O.C.MAX. 5/8" FIRE RATED GWB BOTH SIDES. EXTEND WALL ASSEMBLY
TO UNDERSIDE OF DECK ABOVE.
1 HR U419 PROVIDE 1" STENCILED TEXT EVERY 8' O.C. READING "1 HR FIRE RATED
PARTITION" AS REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE
COMPONENTS MEET DECK ABOVE.
M6_C N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB BOTH SIDES. EXTEND WALL ASSEMBLY TO
UNDERSIDE OF DECK ABOVE.
SMOKE
PARTITION
- PROVIDE 1" STENCILED TEXT AT 8' O.C. MAX. READING "SMOKE PARTITION" AS
REQUIRED BY BUILDING CODE. PROVIDE INSULATION WHERE COMPONENTS
MEET DECK ABOVE
M6_L N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE AND 5/8" LEAD LINED GWB ROOM SIDE.
EXTEND GWB TO 4" ABOVE FINISHED CEILING. ANCHOR STUDS TO UNDERSIDE OF DECK OR
STRUCTURE ABOVE AT 48" O.C. MAX
- - PROVIDE 1/16" LEAD LINING TO 7'-0" A.F.F.
M6B N/A 6" METAL STUDS AT 16" O.C. MAX. 5/8" GWB ONE SIDE. EXTEND WALL ASSEMBLY TO 4" ABOVE
FINISHED CEILING.
SW245_1 38 1 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 1 LAYERS 5/8" GWB OTHER
SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK ABOVE.
1 HR U 415
SYSTE
M B
SW_2 38 2 1/2" CH STUDS AT 24" O.C. MAX. 1" GYPSUM LINER ONE SIDE AND 2 LAYERS 5/8" GWB OTHER
SIDE SIDE. EXTEND WALL ASSEMBLY TO DECK ABOVE.
2 HR U 415
SYSTE
M B
TOILET ACCESSORY SCHEDULE - PHASE 1
MARK DESCRIPTION MOUNTING HEIGHT VAFCI VAFOI VAFCI REMARKS
SD1 AUTOMATIC SOAP DISPENSER 38" A.F.F. TO BOTTOM ***
EQUIPMENT SCHEDULE - PHASE 1
MARK NAME VAFCI VAFOI CFCI COMMENTS
AC ANESTHESIA COLUMN *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
B1 LIGHT BOOM 2 *** RELOCATED FROM EXISTING OR #7
B2 LIGHT BOOM 1 *** RELOCATED FROM EXISTING OR #7
BW BLANKET WARMER *** PROVIDE POWER
C1 EQUIPMENT BOOM 1 *** RELOCATED FROM EXISTING OR#7
C2 ANESTHESIA BOOM 1 *** RELOCATED FROM EXISTING OR#7
CRT CART *** EXISTING - RELOCATED THIS PHASE
EB EQUIPMENT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
IM INTEGRATION MONITOR *** PROVIDE POWER AND DATA
LB SURGICAL LIGHT BOOM *** PROVIDE POWER, DATA, MEDICAL GAS, AND SUPPORT
LC LIGHT CONTROL *** PROVIDE POWER
MB MARKER BOARD *** *** PROVIDE BLOCKING AS REQUIRED
MS STAINLESS STEEL SHELVES ***
MTR MONITOR *** PROVIDE POWER AND DATA
NCP NITROGEN CONTROL PANEL *** PROVIDE POWER
OC MOBILE OMNI CELL *** PROVIDE POWER AND DATA
ORC OR CART *** EXISTING - RELOCATED THIS PHASE
ORT OR TABLE ***
SSC STAINLESS STEEL CART *** ***
WPH WALL PHONE *** PROVIDE POWER AND DATA
*SEE ALL NEW WORK SHEETS FOR EXTENT OF EQUIPMENT*
2 X 2 INDIRECT LED LIGHT FIXTURE
CEILING LEGEND
RETURN AIR DIFFUSER
SUPPLY AIR DIFFUSER
LINEAR DIFFUSER
2 X 4 INDIRECT LED LIGHT FIXTURE
RECESSED CEILING LIGHT
EXIT SIGN
STRIP LIGHTING
18"X18" GASKETED ACCESS PANEL
EQUIPMENT BOOM ESCUTCHEON
1 X 4 GASKETED LED LIGHT FIXTURE
2 X 4 GASKETED LED LIGHT FIXTURE
13 14 15 16 17 18
N
M
K
L
Ls
17.9
20042005
A510
N.4
12.6
A202.1A
A202.1A4
A202.1A
A202.1A
/8
/8
/8
/1
4' - 5 1/2" 6' - 0 3/4" 6' - 0 3/4" 4' - 5 1/2"
2 1
1 2 1 1
2 1
/1
5' - 11 3/16"
/8
0" 14' - 0 7/8" 13' - 1 1/8"
/8
/4
5 5
8' - 0"
7' - 0"
7' - 0" 7' - 0"
7' - 3" 8' - 3"
6' - 10"
/8
/4
2' - 2"
A202.2-ALT
A202.2-ALT
A202.2-ALT
/4
4' - 5 3/8" 4' - 5 3/8" 2' - 3 1/4"
8' - 0"
8' - 0"
8' - 7"
8' - 7"
8' - 4"
2nd FLOOR
8' - 2"
2nd FLOOR2nd FLOOR
2nd FLOOR
2nd FLOOR
9' - 2"
8' - 7"
2nd FLOOR
2nd FLOOR
14' - 0 7/8" 13' - 1 1/8"
10' - 7 3/8" 10' - 7 1/8"
TYP
8' - 7"
6' - 8" 7' - 0"
7' - 0"
10' - 0" 10' - 0"
10' - 0"
10' - 0"
8' - 0"
8' - 0"
8' - 0"
9' - 0"
8' - 2"
7' - 10" 7' - 10"
7' - 10"
8' - 0"
1. PROVIDE 1 1/2" CEILING EXPANSION JOINT.
2. PROVIDE 1 1/2" CEILING EXPANSION JOINT, ADJACENT TO
WALL.
3. PROVIDE INTEGRATED CEILING SYSTEM AS SPECIFIED.
4. PROVIDE UNISTRUT SYSTEM AS SPECIFIED.
5. ALIGN WALL WITH EDGE OF ADJACENT.
6. NOT USED.
7. NOT USED
8. PROVIDE 12''x12'' GASKETED ACCESS PANEL AT LOW
RETURN VOLUME DAMPERS ALL ORS. COORD W/ MECH.
CEILING NOTES
L Ls
1 1/2" CEILING
EXPANSION JOINT
2 1/2" MTL STUD AT 16" OC. 5/8"
GWB ON ONE SIDE. FASTEN
STUDS TO EXISTING CONCRETE
STRUCTURE
CEILING HEIGHT AND MATERIAL AS
SCHEDULED, SEE FINISH SCHEDULE
FOR MORE INFORMATION
1' - 6"
8' - 2"
8' - 0" 9' - 0"
ABOVE SURGERY
FLOOR
ABOVE SECOND
FLOOR
ABOVE
SECOND
FLOOR
L Ls
CEILING HEIGHT AND MATERIAL AS
SCHEDULED, SEE FINISH SCHEDULE.
TYP
1 1/2" CEILING
EXPANSION JOINT
2 1/2" MTL STUDS AT 16" OC.
PHASE 1
1' - 6 1/2" 6 3/8" 9 3/8"
7' - 0"
ABOVE SURGERY
FLOOR
EXISTING CMU WALL TO BE
DEMOLISHED AT THE END OF
PHASE 2
2 1/2" MTL STUDS AT 16" OC.
PHASE 2
/8
L Ls
1 1/2" CEILING
EXPANSION JOINT
CEILING HT AND MATERIAL
AS SCHEDULED, SEE FINISH
SCHEDULE
2 1/2" MTL STUDS AT 16" OC.
5/8" GWB ON ONE SIDE.
ANCHOR TO STRUCTURE
ABV.
1' - 2 1/2" 6" 9 1/2"
1' - 9 3/4"
TYP.
8' - 2"
8' - 7"
8' - 0"
ABOVE SECOND
FLOOR
ABOVE SURGERY
FLOOR
ABOVE SECOND
FLOOR
L Ls
CEILING HEIGHT AND
MATERIAL AS
SCHEDULED, SEE FINISH
SCHEDULE, TYP
1 1/2" CEILING
EXPANSION JOINT
FOR PARTITION TYPE,
SEE FLOOR PLAN
T Y
P
2 1/2" MTL STUD AT 16"
OC
8" 7 3/8" 7' - 0"
ABOVE SURGERY
FLOOR
PROJECT
LIMITS / PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.
• CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION.
• EACH SUBCONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A
RESOLUTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR
ITS INTENDED USE.
• CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND CHASES FOR OWNER FURNISHED OWNER INSTALLED EQUIPMENT WITH
THE OWNER.
• CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER SEPARATE CONTRACT BY OWNER.
• SEE FIRE PLAN FOR FIRE WALL AND SMOKE PARTITION LOCATIONS.
• ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH ADJACENT MATERIALS.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.
• ALL DIMS ON CEILING PLAN ARE TAKEN FROM FACE OF FINISH
• ALL SOFFITS TO BE PNT#1
GENERAL CEILING NOTES
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A202.1A
REFLECTED CEILING PLAN - SECOND
FLOOR - PHASE 1 - AREA A
RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JAS
ROOM LEGEND - PHASE 1
NUMBER NAME
2000 SEMI- RESTRICTED CORRIDOR
2001 SEMI-RESTRICTED CORRIDOR
2002 SEMI-RESTRICTED CORRIDOR
2003 SCRUB
2004 SCRUB
2005 SCRUB
2007 RAMP
2007A ELECTRICAL CLOSET
2009 SEMI-RESTRICTED CORRIDOR
2010 GENERAL OR
2016 SCRUB
2020 GENERAL OR
2030 GENERAL OR
2040 HYBRID OR
2041 HYBRID EQUIP
2050 HYBRID CONTROL
2060 EQUIPMENT STORAGE
2070 ORTHO OR
2080 CLEAN CORE
2090 EQUIPMENT STORAGE
1/4" = 1'-0"
REFLECTED CEILING PLAN - SECOND FLOOR - PHASE 1 - AREA A
A202.1A 1 1/2" = 1'-0"
1 CEILING DETAIL ROOM 2000
A202.1A 1 1/2" = 1'-0"
3 DETAIL
A202.1A 1 1/2" = 1'-0"
4 DETAIL
A202.1A 1 1/2" = 1'-0"
2 DETAIL
NO. DESCRIPTION DATE
2 Life Safety Revision 1-10-2022
3 RFI 62, 63, 67, 68, 71, 72 Stairwell and Clean Core Revisions
2-24-2022
16 17 18
K
J
L
Ls
H.6
17.9
A501
1' - 0"
4' - 5 3/8" 6' - 0 3/4" 6' - 0 3/4"
/4
/8
/8
/8
1 2 2 2
A202.2-ALT
1' - 9"
/8
/4
TYP
10' - 0"
9' - 0"
7' - 10"
8' - 0"
8' - 0"
2 X 2 INDIRECT LED LIGHT FIXTURE
CEILING LEGEND
RETURN AIR DIFFUSER
SUPPLY AIR DIFFUSER
LINEAR DIFFUSER
2 X 4 INDIRECT LED LIGHT FIXTURE
RECESSED CEILING LIGHT
EXIT SIGN
STRIP LIGHTING
18"X18" GASKETED ACCESS PANEL
EQUIPMENT BOOM ESCUTCHEON
1 X 4 GASKETED LED LIGHT FIXTURE
2 X 4 GASKETED LED LIGHT FIXTURE
1. 1 1/2" CEILING EXPANSION JOINT
2. 1 1/2" CEILING EXPANSION JOINT, ADJACENT TO
WALL
3. INTEGRATED CEILING SYSTEM
4. PROVIDE 12''x12'' ACCESS PANEL WHERE INDICATED.
CEILING NOTES
PROJECT LIMITS /
PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
• ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.
• CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION.
• EACH SUBCONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A
RESOLUTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR
ITS INTENDED USE.
• CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND CHASES FOR OWNER FURNISHED OWNER INSTALLED EQUIPMENT WITH
THE OWNER.
• CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER SEPARATE CONTRACT BY OWNER.
• SEE FIRE PLAN FOR FIRE WALL AND SMOKE PARTITION LOCATIONS.
• ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH ADJACENT MATERIALS.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.
• ALL DIMS ON CEILING PLAN ARE TAKEN FROM FACE OF FINISH
• ALL SOFFITS TO BE PNT#1
GENERAL CEILING NOTES
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A202.1B
REFLECTED CEILING PLAN - SECOND
FLOOR - PHASE 1 - AREA B
RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JHT
1/4" = 1'-0"
REFLECTED CEILING PLAN - SECOND FLOOR - PHASE 1 - AREA B
ROOM LEGEND - PHASE 1
NUMBER NAME
2000 SEMI- RESTRICTED CORRIDOR
2001 SEMI-RESTRICTED CORRIDOR
2002 SEMI-RESTRICTED CORRIDOR
2003 SCRUB
2004 SCRUB
2005 SCRUB
2007 RAMP
2007A ELECTRICAL CLOSET
2009 SEMI-RESTRICTED CORRIDOR
2010 GENERAL OR
2016 SCRUB
2020 GENERAL OR
2030 GENERAL OR
2040 HYBRID OR
2041 HYBRID EQUIP
2050 HYBRID CONTROL
2060 EQUIPMENT STORAGE
2070 ORTHO OR
2080 CLEAN CORE
2090 EQUIPMENT STORAGE
13 14 15 16 17 18
N
M
K
J
H
L
Ls
H.6
G.4
G.6
17.9
N.4
12.6
NIC
NIC
NIC
NIC
NIC
2007A
S-3
20042005
2070 2000
NIC
PROJECT
LIMITS / PHASE
KEY PLAN
1A
1B2A
12 13 14 15 16 17 18 19
N
M
Ls
L
K
J
H.6
H
G
F.9
F.1
F 17.915W14W14E13E
F.3
F.4
G.4
G.6PLAN NORTH
ACTUAL
NORTH
2 X 2 INDIRECT LED LIGHT FIXTURE
CEILING LEGEND
RETURN AIR DIFFUSER
SUPPLY AIR DIFFUSER
LINEAR DIFFUSER
2 X 4 INDIRECT LED LIGHT FIXTURE
RECESSED CEILING LIGHT
EXIT SIGN
STRIP LIGHTING
18"X18" GASKETED ACCESS PANEL
EQUIPMENT BOOM ESCUTCHEON
1 X 4 GASKETED LED LIGHT FIXTURE
2 X 4 GASKETED LED LIGHT FIXTURE
• ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL, STATE AND LOCAL CODES AND ORDINANCES.
• CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A RESOLUTION.
• EACH SUBCONTRACTOR SHALL REVIEW THE CONSTRUCTION DOCUMENTS AND EVALUATE THE SCOPE OF WORK REQUIRED BY THEIR RESPECTIVE TRADE AND ANY CONFLICTS WITH OTHER TRADES. ANY CONFLICTS WILL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR FOR A
RESOLUTION.
• PROVIDE SHALL MEAN TO SUPPLY, TO FURNISH AND TO INSTALL COMPLETE WITH ALL ACCESSORIES, PARTS AND/OR SERVICES TO BE READY FOR
ITS INTENDED USE.
• CONTRACTOR SHALL COORDINATE ALL REQUIRED CONDUIT, PIPING AND CHASES FOR OWNER FURNISHED OWNER INSTALLED EQUIPMENT WITH
THE OWNER.
• CONTRACTOR SHALL COORDINATE WITH WORK BEING PERFORMED UNDER SEPARATE CONTRACT BY OWNER.
• SEE FIRE PLAN FOR FIRE WALL AND SMOKE PARTITION LOCATIONS.
• ALL ABUTTING DISSIMILAR MATERIALS ARE TO BE SEALED. COLOR TO MATCH ADJACENT MATERIALS.
• ALL NOTES, REMARKS AND/OR SCHEDULES ON THIS SHEET ARE FOR THIS SHEET ONLY UNLESS OTHERWISE NOTED.
• ALL DIMS ON CEILING PLAN ARE TAKEN FROM FACE OF FINISH
• ALL SOFFITS TO BE PNT#1
GENERAL CEILING NOTES
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A202
OVERALL REFLECTED CEILING PLAN
- SECOND FLOOR
RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JAS
1/8" = 1'-0"
OVERALL REFLECTED CEILING PLAN - SECOND FLOOR
ROOM LEGEND
WT NAME
2000 SEMI-RESTRICTED CORRIDOR
2001 SEMI-RESTRICTED CORRIDOR
2002 SEMI-RESTRICTED CORRIDOR
2003 SCRUB
2004 SCRUB
2005 SCRUB
2006 SEMI-RESTRICTED CORRIDOR
2007 RAMP/CORRIDOR
2007A ELECTRICAL CLOSET
2009 SEMI-RESTRICTED CORRIDOR
2010 GENERAL OR
2016 SCRUB
2020 GENERAL OR
2030 GENERAL OR
2040 HYBRID OR
2041 HYBRID EQUIP
2050 HYBRID CONTROL
2060 EQUIPMENT STORAGE
2070 ORTHO OR
2080 CLEAN CORE
2081 CLEAN CORE
2082 RAMP
2090 EQUIPMENT STORAGE
DS - 3 EXISTING STAIR
T Y
P
6" EPOXY BASE TYP.
LOW RETURN
SS CORNER GUARD TYP.
LIGHT SWITCH
POWER
GROUND
MODULE
CODE BLUE
FUTURE MONITOR
4' W x 3' H MARKER BOARD
LOW RETURN
POWER GROUND
MODULE
M
IN8
LIGHT CONTROL
POWER MODULE
LIGHT CONTROL
WALL PHONE TYP.
INTEGRATION
MONITOR
LIGHT SWITCH
CODE BLUE
OMNI CELL
POWER GROUND
MODULE
ISOLATED POWER
PANEL
SS CABINETS WITH
GLASS DOORS
4' W x 3' H
MARKER
BOARD
LOW RETURN
NITROGEN
CONTROL PANEL
4' - 0"
POWER GROUND
MODULE
LIGHT SWITCH
CODE BLUE
POWER GROUND
MODULE
LOW RETURN
4' W x 3' H
MARKER
BOARD
FUTURE
MONITOR
ISOLATED
POWER PANEL
POWER
GROUND
MODULE
4' - 0"
INTEGRATION
MONITOR
LIGHT CONTROL
WALL PHONE
LOW RETURN
LIGHT CONTROL
POWER MODULE
/2
LIGHT SWITCH
CODE BLUE
OMNI CELL
POWER
GROUND
MODULE
4' - 0"
4' W x 3' H MARKER BOARD
LOW RETURN
NITROGEN CONTROL PANEL
POWER
GROUND
MODULE
SS CABINET
W/ GLASS
DOORS
ISOLATION
PANEL
PRIOR TO ROUGH-IN OF ALL UTILITIES, CONTRACTOR SHALL USE ROOM 2020 AS A MOCK UP.
REFER TO SPECIFICATION SECTION 01 00 00 GENERAL REQUIREMENTS FOR ADDITIONAL INFORMATION
CONTRACTOR'S NOTE
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A800
INTERIOR ELEVATIONS RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JHT
3/8" = 1'-0"A102.1A
1 ELEVATION ROOM 2010
3/8" = 1'-0"A102.1A
2 ELEVATION ROOM 2010
3/8" = 1'-0"A102.1A
3 ELEVATION ROOM 2010
A800
4 ELEVATION ROOM 2010
3/8" = 1'-0"A102.1A
5 ELEVATION ROOM 2020
3/8" = 1'-0"A102.1A
6 ELEVATION ROOM 2020
3/8" = 1'-0"A102.1A
7 ELEVATION ROOM 2020
3/8" = 1'-0"A102.1A
8 ELEVATION ROOM 2020
6" EPOXY BASE
TYP.
STAINLESS STEEL
CORNER GUARD
TYP.
LOW RETURN
LIGHT SWITCH
POWER GROUND
MODULE
4' W x 3' H MARKER
BOARD
LOW RETURN
FUTURE MONITOR
POWER GROUND
MODULE
LIGHT CONTROL
INTEGRATION
MONITOR
POWER AND
DATA IN
CABINET
LIGHT SWITCH
WALL PHONE
M
IN8
OMNI CELL
CODE BLUE
LIGHT CONTROL
POWER MODULE
POWER
GROUND
MODULE
STAINLESS
STEEL CABINETS
W/ GLASS DOORS
4' W x 3' H MARKER
BOARD
LIGHT SWITCH
LOW RETURN
NITROGEN CONTROL PANEL
4' - 0" 4' - 0"
POWER GROUND MODULE
ISOLATED POWER PANEL
LOW RETURN
LIGHT SWITCH
CODE BLUE
POWER GROUND MODULE
STAINLESS
STEEL CABINETS
W/ GLASS
DOORS
4' W x 3' H
MARKER BOARD
4' - 0" 4' - 0" 4' - 0"
LOW RETURN
LIGHT CONTROL
POWER MODULE
LIGHT
CONTROL
LIGHT SWITCH
INTEGRATION
MONITOR
WALL PHONE
LOW
RETURN
POWER GROUND MODULE
CODE BLUE
POWER
GROUND
MODULE
ISOLATED POWER PANEL
NITROGEN CONTROL PANEL
4' W x 3' H MARKER BOARD
LOW RETURN
FUTURE MONITOR
POWER GROUND MODULE
OMNI CELL
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A801
INTERIOR ELEVATIONS RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT JHT
3/8" = 1'-0"A102.1A
1 ELEVATION ROOM 2030
3/8" = 1'-0"A102.1A
2 ELEVATION ROOM 2030
3/8" = 1'-0"A102.1A
3 ELEVATION ROOM 2030
3/8" = 1'-0"A102.1A
4 ELEVATION ROOM 2030
3/8" = 1'-0"A102.1A
5 ELEVATION ROOM 2040
3/8" = 1'-0"A102.1A
6 ELEVATION ROOM 2040
3/8" = 1'-0"A102.1A
7 ELEVATION ROOM 2040
3/8" = 1'-0"A102.1A
8 ELEVATION ROOM 2040
LIGHT CONTROL
POWER MODULE
6" EPOXY BASE TYP.
/2
LIGHT CONTROL
WALL PHONE
CODE BLUE
LIGHT SWITCH
OMNI CELL
4' W x 3' H MARKER BOARD
POWER GROUND MODULE
SS CORNER GUARD
POWER GROUND MODULE
LIGHT SWITCH
CODE BLUE
LOW RETURN
STAINLESS STEEL CORNER GUARD
ISOLATION POWER PANEL
POWER GROUND MODULE
FUTURE MONITOR
4'W X 3'H MARKERBOARD
STAINLESS STEEL CABINETS
WITH GLASS DOORS
LOW RETURN
STAINLESS STEEL
CORNER GUARD
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Project Number
Building Number
Drawing Number
Project Title
Location
Checked Drawn
Drawing Title
Approved:
ARCHITECT / ENGINEERS:
PF&A DESIGN
ARCHITECTURE,PLANNING,INTERIORCONSULTANTS:
FULLY SPRINKLERED
REVISED CONSTRUCTION SET
Date
637-315
A802
INTERIOR ELEVATIONS RENOVATE AND
EXPAND OPERATION
ROOMS
CHARLES GEORGE VAMC
ASHEVILLE, NC
05/27/2022
JHT RW
3/8" = 1'-0"A102.1B
1 ELEVATION ROOM 2070
3/8" = 1'-0"A102.1B
2 ELEVATION ROOM 2070
3/8" = 1'-0"A102.1B
3 ELEVATION ROOM 2070
3/8" = 1'-0"A102.1B
4 ELEVATION ROOM 2070
N
M
K
J
L
Ls
N.4
N
M
K
J
L
Ls
N.4
13 14 15 16 17 1812 12.6 13 14 15 16 17 1812 12.6
RENOVATE AND
EXPAND OPERATING
ROOMS
637-315
NO. DESCRIPTION DATE
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
REVISED CONSTRUCTION SET
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
8815 CENTRE PARK DRIVE, SUITE 200 COLUMBIA, MD 21045
410-750-2246 (BALT) 410-750-2588 (FAX)
KA PROJECT NUMBER: M023-08
R
KEY PLAN
PLAN NORTH
ACTUAL
NORTH
PROJECT LIMITS / PHASE
TTI ENVIRONMENTAL, INC.
1253 NORTH CHURCH STREET
MOORESTOWN, NJ 08057
MR PROJECT #: 0499-0055
STRUCTURAL
NEW ROOF FRAMING PLAN
2ND FLOOR
S103
ST/DSST
File details come from the government source that posted it. Updated .