36C24619R0087-0002005.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24619R0087
About this file
36C24619R0087 0002 5 - B8_Elec_drwgs_for_Ref.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24619R0087-0005003.pdf | ||
| 36C24619R0087-0005000.docx | DOCX document | |
| 36C24619R0087-0005002.pdf | ||
| 36C24619R0087-0005001.pdf | ||
| 36C24619R0087-0004000.docx | DOCX document | |
| 36C24619R0087-0004001.pdf | ||
| 36C24619R0087-0003000.docx | DOCX document | |
| 36C24619R0087-0002001.pdf | ||
| 36C24619R0087-0002004.pdf | ||
| 36C24619R0087-0002006.pdf | ||
| 36C24619R0087-0002003.pdf | ||
| 36C24619R0087-0002000.docx | DOCX document | |
| 36C24619R0087-0002002.pdf | ||
| 36C24619R0087-0001000.docx | DOCX document | |
| 36C24619R0087-0001001.pdf | ||
| 36C24619R0087-010.docx | DOCX document | |
| 36C24619R0087-008.pdf | ||
| 36C24619R0087-012.docx | DOCX document | |
| 36C24619R0087-007.docx | DOCX document | |
| 36C24619R0087-009.pdf | ||
| 36C24619R0087-011.pdf | ||
| 36C24619R0087-006.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KW AMPS HP BY TYPE SIZE TRIP/FUSE CAN BY TYPE SIZE CAN SIZE TYPE
AHU-1R AIR HANDLING UNIT - 1 RETURN 208/3 10 MC - MC VFD QSB-2 3#10, 1#8G 1-1/2 EMT 1,3 AHU-1S AIR HANDLING UNIT - 1 SUPPLY 208/3 25 MC - MC VFD QSB-3 3#4/0, 1#4G 2 EMT 1,3
BAS BUILDING AUTOMATION PANEL 120/1 .5 EC TOG 1Q1-35 2#12, 1#12G 3/4 EMT 1
CP-1 CONDENSATE PUMP - 1 208/3 2 @ 1/2 MC 1Q1-20 3#12, 1#12G 3/4 EMT 1
CHWP-1 CHILLED WATER PUMP-1 208/3 1-1/2 EC NFS 30/3 - 1 MC VFD 1Q1-8 3#12, 1#12G 3/4 EMT 1,3
CHWP-2 CHILLED WATER PUMP-2 208/3 1-1/2 EC NFS 30/3 - 1 MC VFD 1Q1-14 3#12, 1#12G 3/4 EMT 1,3
EF-1 EXHAUST FAN-1 208/3 2 MC MC VFD 1Q1-2 3#12, 1#12G 3/4 EMT 1,3
EF-2 EXHAUST FAN-2 120/1 1/4 MC MC 1Q1-33 3#12, 1#12G 3/5 EMT 1
ELEVP3 ELEVATOR - P3 208/3 30 EC FS 200/3 175 1 QSB-15 3#3/0, 1#6G 2 EMT 1
ELEVP4 ELEVATOR - P4 208/3 30 EC FS 200/3 175 1 QSB-16 3#3/0, 1#6G 2 EMT 1
ELEVS1 ELEVATOR - S1 208/3 60 EC FS 400/3 350 1 QSB-17 2 - (3#3/0, 1#3G) 2 EMT 1
ELEVS2 ELEVATOR - S2 208/3 60 EC FS 400/3 350 1 QSB-18 3 - (3#3/0, 1#3G) 2 EMT 1
ELEVP3C ELEVATOR CONTROL - P3 120/1 15 EC FS 20/1 20 1Q1-17 2#12, 1#12G 3/4 EMT 1 ELEVP4C ELEVATOR CONTROL - P4 120/1 15 EC FS 20/1 20 1Q1-19 2#12, 1#12G 3/4 EMT 1 ELEVS1C ELEVATOR CONTROL - S1 120/1 15 EC FS 20/1 20 1Q1-21 2#12, 1#12G 3/4 EMT 1 ELEVS2C ELEVATOR CONTROL - S1 120/1 15 EC FS 20/1 20 1Q1-25 2#12, 1#12G 3/4 EMT 1
H-1 HUMIDIFIER 120/1 15 1.25 EC TOG 1Q1-23 2#12, 1#12G 3/4 EMT 1
HTP-1 HEAT TRANSFER PACKAGE - 1 208/3 2 @ 1 MC - MC 1Q1-26 3#12, 1#12G 3/4 EMT 1
RCP-1 RECIRCULATION PUMP - 1 120./1 1/6 EC TOG 1Q1-27 2#12, 1#12G 3/4 EMT 1
SP-1 SUMP PUMP - 1 120/1 1/2 1Q1-29 2#12, 1#12G 3/4 EMT 2
SP-2 SUMP PUMP - 1 120/1 1/2 1Q1-31 2#12, 1#12G 3/4 EMT 2
DISCONNECT TYPE STARTER TYPE RACEWAY TYPE BY
FS = FUSED SWITCH FVNR = FULL VOLTAGE, NON-REVERSING EMT = ELECTRIC METALLIC TUBING EC = ELECTRICAL NFS = NON-FUSED SWITCH FVN = FULL VOLTAGE, REVERSING IMC = INTERMEDIATE METALLIC CONDUIT MC = MECHANICAL TOG = 20A TOGGLE SWITCH RVAT = REDUCED VOLTAGE, AUTOTRANSFORMER RMC = RIGID METALLIC CONDUIT PC = PLUMBING MRS = MOTOR RATED SWITCH RVPW = REDUCED VOLTAGE, PART-WINDING PVC = NON-METALLIC CONDUIT MFR-MANUFACTURER
MCB = MAGNETIC CIRCUIT BREAKER WD = WYE-DELTA FMC = FLEXIBLE METALLIC CONDUIT
VFD = VARIABLE SPEED DRIVE LTFMC = LIQUID TIGHT FLEXIBLE METALLIC CONDUIT
CONDUCTORSITEM DESCRIPTION VOLT/Ø LOADS CIRCUITMOCP MCA
EQUIPMENT CONNECTION SCHEDULE
NOTES:
1. MAKE FINAL CONNECTION TO UNIT.
2. PROVIDE 5-20 GFCI RECEPTACLE WITH WEATHER-PROOF WHILE-IN-USE COVER.
3. EXTEND THE CIRCUIT AS NEEDED FROM THE VFD TO THE MOTOR.
DISCONNECT STARTER NOTESRACEWAY
SWITCHBOARD 'MSB' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: 3000A MCB TYPE: SWITCHBOARD
BUS AMPACITY: 3000 AMPERES A.I.C. RATING: 65,000 AMPERES MOUNTING: FLOOR
NEUTRAL BUS AMPACITY: 3000 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1
UNIT
NO. NAMEPLATE POLE FRAME(A) TRIP(A) # SIZE GND CONDUIT TOTAL PH. A PH. B PH. C NOTES ADDITIONAL COMMENTS
1 SWITCHBOARD - "QSB" 3 2000 2000 - - - - 361.7 121.4 120.3 120.0 2
2 PANEL 'DPC' 3 1000 1000 - - - - 29.3 10.3 10.2 8.8 2
3 PANEL '1N1' 3 225 225 - - - - 58.2 22.8 17.7 17.7 2
4 SPARE, FUTURE PANEL 3 225 225
5 SPARE, FUTURE PANEL 3 225 225
6 SPARE, FUTURE PANEL 3 225 225
7 SPARE, FUTURE PANEL 3 225 225
8 SPARE, FUTURE PANEL 3 225 225
9 SPARE, FUTURE PANEL 3 225 225
10 SPARE, FUTURE PANEL 3 225 225
11 SPARE 3 225
12 SPARE 3 225
13 SPARE 3 100
14 SPARE 3 100
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 154.5 KVA 23.7 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE POWER RISER DIAGRAM FOR CONDUCTOR AND RACEWAY SIZES. B = 148.3 KVA 58.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 146.5 KVA 13.9 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 53.9 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 1287 AMPERES 296.2 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS
7. - 1247 AMPERES 449.3 KVA TOTAL CONNECTED LOAD
DEVICE FEEDER/ BRANCH CIRCUIT LOAD (KVA)
PANELBOARD '1N1' (NEW) SECTION 1
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: NORMAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 LTG: A172, A173, A174 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: EWC 2
3 LTG: AC101,AC111,AC175,AC106,AC107 1.1 12 12 2 1 20 20 1 2 12 12 0.9 REC: 4
5 LTG: A171,A170,AS101,A103,A105,A107 1.4 12 12 2 1 20 20 1 2 12 12 1.3 REC: 6
7 LTG: A102,A104,A106,A155-163 1.6 12 12 2 1 20 20 1 2 12 12 1.1 REC: 8
9 LTG: AC102,A117,AC103,AC105,AC105 1.0 12 12 2 1 20 20 1 2 12 12 1.3 REC: 10
11 LTG: AC102, DIMMING AND DAY 1.5 12 12 2 1 20 20 1 2 12 12 0.9 REC: 12
13 LTG: AC103, DIMMING & DAY,A123,A12 1.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 14
15 LTG: A001 AND ELEV PIT 0.3 12 12 2 1 20 20 1 2 12 12 1.1 REC: 16
17 LTG: EXTERIOR 12 12 2 1 20 20 1 2 12 12 0.7 REC: 18
19 REC: AC001, A001 0.5 12 12 2 1 20 20 1 2 12 12 1.4 REC: 20
21 BOLLARDS 0.5 10 10 2 1 20 20 1 2 12 12 1.2 REC: MICROWAVE 22
23 SPARE 1 20 20 1 2 12 12 1.2 REC: COFFEE MAKER 24
25 REC: DAYROOM 0.2 12 12 2 1 20 20 1 2 12 12 1.4 REC: 26
27 REC: DAYROOM 0.2 12 12 2 1 20 20 1 2 12 12 1.1 REC: 28
29 REC: DAYROOM 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 30
31 REC: DAYROOM 0.5 12 12 2 1 20 20 1 2 12 12 0.9 REC: 32
33 REC: A117 (TV) 0.2 12 12 2 1 20 20 1 2 12 12 0.5 REC: 34
35 REC: A115 0.9 12 12 2 1 20 20 1 2 12 12 0.4 REC: 36
37 REC: A113 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 38
39 REC: A111 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 40
41 REC: A109 1.1 12 12 2 1 20 20 1 2 12 12 0.5 REC: 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 22.8 KVA 10.4 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. - B = 17.7 KVA 44.7 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 17.7 KVA 3.1 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 190 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 0.0 KVA MISCELLANEOUS
7. - 162 AMPERES 58.2 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '1N1' (NEW) SECTION 2
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
43 REC: A118 0.9 12 12 2 1 20 20 1 2 12 12 1.4 REC: 44
45 REC: A116 0.7 12 12 2 1 20 20 1 2 12 12 0.4 REC: 46
47 REC: A114 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 48
49 REC: A112 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 50
51 REC: A121 0.5 12 12 2 1 20 20 1 2 12 12 0.4 REC: 52
53 REC: A123 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: A134 54
55 REC: A107 0.9 12 12 2 1 20 20 1 2 12 12 0.9 REC: A133 56
57 WASHING MACHINE: A107 1.5 12 12 2 1 20 20 1 2 12 12 0.4 REC: A131 58
59 ELECTRIC DRYER: A107 2.1 2.1 10 10 2 2 30 20 1 2 12 12 0.7 REC: A122 60
20 1 2 12 12 0.7 REC: A124 62
63 REC: A105 0.9 12 12 2 1 20 20 1 2 12 12 0.9 REC: A126 64
65 SPARE 1 20 20 1 2 12 12 0.2 REC: TV 66
67 REC: A172 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: A129 68
69 LTG: A100 0.8 12 12 2 1 20 20 1 2 12 12 0.7 REC: A127 70
71 SPARE 1 20 20 1 2 12 12 0.7 REC: A125 72
73 SPARE 1 20 20 1 SPARE 74
75 SPARE 1 20 20 1 SPARE 76
77 SPARE 1 20 20 1 SPARE 78
79 SPARE 1 20 20 1 SPARE 80
81 SPARE 1 20 20 1 SPARE 82
83 SPARE 1 20 20 1 SPARE 84
WIRE DEVICE
PANELBOARD 'DPC' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 1000 AMPERES A.I.C. RATING: 65,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 1000 AMPERES BRANCH: NORMAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 PANEL '1C1' 12.3 12.2 10.9 2 3 225 225 3 SPARE, FUTURE PANEL 2
7 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 8
13 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 14
19 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 20
25 SPARE 3 100 225 3 SPARE 26
31 SPARE 3 100 225 3 SPARE 32
37 SPARE 1 20 20 1 SPARE 38
39 SPARE 1 20 20 1 SPARE 40
41 SPARE 1 20 20 1 SPARE 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 12.3 KVA 13.3 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE POWER RISER DIAGRAM FOR CONDUCTOR, RACEWAY SIZES. B = 12.2 KVA 13.3 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 10.9 KVA 2.7 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 102 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 6.1 KVA MISCELLANEOUS
7. - 98 AMPERES 35.4 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '1C1' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: CRITICAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 LTG: A172, A173, A174 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 2
3 LTG: AC102-104,AC107,AC106,AC111 1.9 12 12 2 1 20 20 1 2 12 12 0.7 REC: 4
5 LTG: A171,A170,AS101,A103,A105,A107 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 6
7 LTG: A102,4,6,A155-163,A150-153 1.6 12 12 2 1 20 20 1 2 12 12 0.7 REC: 8
9 LTG: A120,A,B,C,A141,A142,A144,A,B 1.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 10
11 LTG: A121,A123,A125,A127,A129 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 12
13 LTG: A108,A110,A112,A114,A116,A118 1.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 14
15 LTG: A131,A133,A134,A122,A124,A126 1.6 12 12 2 1 20 20 1 2 12 12 0.7 REC: 16
17 LTG: AC001 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 18
19 LTG: EXTERIOR 0.6 12 12 2 1 20 20 1 2 12 12 0.4 REC: 20
21 LTG: A100 0.3 12 12 2 1 20 20 1 SPARE 22
23 MOTORIZED DOOR 1.1 12 12 2 1 20 20 1 SPARE 24
25 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.4 REC: 26
27 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.4 REC: 28
29 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: REFRIGERATOR 30
31 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 32
33 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 34
35 SPARE 1 20 20 1 2 12 12 0.7 REC: 36
37 REC: A141 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 38
39 REC: A120B 0.4 12 12 2 1 20 20 1 2 12 12 0.4 REC: 40
41 REC: A120C 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 12.3 KVA 13.3 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. - B = 12.2 KVA 13.3 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 10.9 KVA 2.7 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 102 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 6.1 KVA MISCELLANEOUS
7. - 98 AMPERES 35.4 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '1C1' (NEW) SECTION 2
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
43 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 44
45 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 46
47 SPARE 1 20 20 1 SPARE 48
49 SPARE 1 20 20 1 SPARE 50
51 SPARE 1 20 20 1 SPARE 52
53 SPARE 1 20 20 1 SPARE 54
55 SPARE 1 20 20 1 SPARE 56
57 SPARE 1 20 20 1 SPARE 58
59 SPARE 1 20 20 1 SPARE 60
61 SPARE 1 20 20 1 SPARE 62
63 SPARE 1 20 20 1 SPARE 64
65 SPARE 1 20 20 1 SPARE 66
67 SPARE 1 20 20 1 SPARE 68
69 SPARE 1 20 20 1 SPARE 70
71 SPARE 1 20 20 1 SPARE 72
73 SPARE 1 20 20 1 SPARE 74
75 SPARE 1 20 20 1 SPARE 76
77 SPARE 1 20 20 1 SPARE 78
79 SPARE 1 20 20 1 SPARE 80
81 SPARE 1 20 20 1 SPARE 82
83 SPARE 1 20
WIRE DEVICE
SWITCHBOARD 'QSB' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: SWITCHBOARD
BUS AMPACITY: 2000 AMPERES A.I.C. RATING: 65,000 AMPERES MOUNTING: FLOOR
NEUTRAL BUS AMPACITY: 2000 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1
UNIT
NO. NAMEPLATE POLE FRAME(A) TRIP(A) # SIZE GND CONDUIT TOTAL PH. A PH. B PH. C NOTES ADDITIONAL COMMENTS
1 PANEL '1Q1' 3 225 150 31.4 11.3 10.2 9.9 2
2 AHU-1R 3 100 70 11.1 3.7 3.7 3.7 3
3 AHU-1S 3 225 175 27.0 9.0 9.0 9.0 3
4 SPARE, FUTURE PANEL 3 225 225
5 SPARE, FUTURE PANEL 3 225 225
6 SPARE, FUTURE PANEL 3 225 225
7 SPARE, FUTURE PANEL 3 225 225
8 SPARE, FUTURE PANEL 3 225 225
9 SPARE, FUTURE PANEL 3 225 225
10 SPARE, FUTURE PANEL 3 225 225
11 SPARE 3 225 225
12 SPARE 3 225 225
13 SPARE 3 100 100
14 SPARE 3 100 100
15 ELEVATOR - P3 3 200 200 48.9 16.3 16.3 16.3 3
16 ELEVATOR - P4 3 200 200 48.9 16.3 16.3 16.3 3
17 ELEVATOR - S1 3 400 400 97.2 32.4 32.4 32.4 3
18 ELEVATOR - S2 3 400 400 97.2 32.4 32.4 32.4 3
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 121.4 KVA 0.0 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE POWER RISER DIAGRAM FOR CONDUCTOR, RACEWAY SIZES. B = 120.3 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. SEE EQUIPMENT CONNECTION SCHEDULE FOR CONDUCTOR, RACEWAY SIZES. C = 120.0 KVA 8.1 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 53.9 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 1012 AMPERES 296.2 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS
7. - 1004 AMPERES 361.7 KVA TOTAL CONNECTED LOAD
DEVICE FEEDER/ BRANCH CIRCUIT LOAD (KVA)
PANELBOARD '1Q1' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000 AMPERES MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.9 0.9 0.9 EF-1 2
3 TERMINAL BOXES 1.0 12 12 2 1 20
5 TERMINAL BOXES 1.0 12 12 2 1 20
7 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.8 0.8 0.8 CHWP-1 8
9 TERMINAL BOXES 1.0 12 12 2 1 20
11 TERMINAL BOXES 1.0 12 12 2 1 20
13 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.8 0.8 0.8 CHWP-2 14
15 TERMINAL BOXES 1.0 12 12 2 1 20
17 ELEVATOR CONTROL - P3 1.0 2 1 20
19 ELEVATOR CONTROL - P4 1.0 2 1 20 15 3 2 0.6 0.6 0.6 CP - 1 20
21 ELEVATOR CONTROL - S1 1.0 2 1 20
23 HUMIDIFIER - H1 0.1 2 1 20
25 ELEVATOR CONTROL - S2 1.0 2 1 20 15 3 2 1.1 1.1 1.1 HTP - 1 26
27 RCP-1 0.3 2 1 20
29 SP-1 1.1 2 1 20
31 SP-2 1.1 2 1 20 20 1 SPARE 32
33 EF-2 0.7 2 1 20 20 1 SPARE 34
35 BAS 0.5 2 1 20 20 1 SPARE 36
37 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 38
39 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 40
41 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 11.3 KVA 0.0 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE EQUIPMENT CONNECTION SCHEDULE FOR CONDUCTOR, RACEWAY SIZES. B = 10.2 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 9.9 KVA 8.1 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 15.8 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 94 AMPERES 4.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS
7. - 87 AMPERES 31.4 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD 'DPLS' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 200 AMPERES A.I.C. RATING: 65,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 200 AMPERES BRANCH: LIFE SAFETY ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 EGRESS LTG. 0.8 12 12 2 1 20 20 1 2 12 12 0.5 FACP 2
3 EGRESS LTG. 1.3 12 12 2 1 20 20 1 2 12 12 0.1 SPRINKLER BELL 4
5 EGRESS LTG. 1.0 12 12 2 1 20 20 1 SPARE 6
7 SPARE 1 20 20 1 SPARE 8
9 SPARE 1 20 20 1 SPARE 10
11 SPARE 1 20 20 1 SPARE 12
13 SPARE 1 20 100 3 FUTURE, PANEL "3LS" 14
15 SPARE 1 20
17 SPACE ONLY
19 SPACE ONLY SPACE ONLY 20
21 SPACE ONLY SPACE ONLY 22
23 SPACE ONLY SPACE ONLY 24
25 SPACE ONLY SPACE ONLY 26
27 SPACE ONLY SPACE ONLY 28
29 SPACE ONLY SPACE ONLY 30
31 SPACE ONLY SPACE ONLY 32
33 SPACE ONLY SPACE ONLY 34
35 SPACE ONLY SPACE ONLY 36
37 SPACE ONLY SPACE ONLY 38
39 SPACE ONLY SPACE ONLY 40
41 SPACE ONLY SPACE ONLY 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 1.3 KVA 3.1 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. - B = 1.4 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 1.0 KVA 0.0 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 12 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 0.6 KVA MISCELLANEOUS
7. - 10 AMPERES 3.7 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
SWITCHBOARD 'MSB' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: 3000A MCB TYPE: SWITCHBOARD
BUS AMPACITY: 3000 AMPERES A.I.C. RATING: 65,000 AMPERES MOUNTING: FLOOR
NEUTRAL BUS AMPACITY: 3000 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1
UNIT
NO. NAMEPLATE POLE FRAME(A) TRIP(A) # SIZE GND CONDUIT TOTAL PH. A PH. B PH. C NOTES ADDITIONAL COMMENTS
1 SWITCHBOARD - "QSB" 3 2000 2000 - - - - 361.7 121.4 120.3 120.0 2
2 PANEL 'DPC' 3 1000 1000 - - - - 29.3 10.3 10.2 8.8 2
3 PANEL '1N1' 3 225 225 - - - - 58.7 22.8 17.7 18.2 2
4 SPARE, FUTURE PANEL 3 225 225
5 SPARE, FUTURE PANEL 3 225 225
6 SPARE, FUTURE PANEL 3 225 225
7 SPARE, FUTURE PANEL 3 225 225
8 SPARE, FUTURE PANEL 3 225 225
9 SPARE, FUTURE PANEL 3 225 225
10 SPARE, FUTURE PANEL 3 225 225
11 SPARE 3 225
12 SPARE 3 225
13 SPARE 3 100
14 SPARE 3 100
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 154.5 KVA 23.7 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE POWER RISER DIAGRAM FOR CONDUCTOR AND RACEWAY SIZES. B = 148.3 KVA 58.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 147.0 KVA 13.9 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 53.9 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 1287 AMPERES 296.2 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 4.0 KVA MISCELLANEOUS
7. - 1248 AMPERES 449.8 KVA TOTAL CONNECTED LOAD
DEVICE FEEDER/ BRANCH CIRCUIT LOAD (KVA)
PANELBOARD '1N1' (NEW) SECTION 1
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: NORMAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 LTG: A172, A173, A174 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: EWC 2
3 LTG: AC101,AC111,AC175,AC106,AC107 1.1 12 12 2 1 20 20 1 2 12 12 0.9 REC: 4
5 LTG: A171,A170,AS101,A103,A105,A107 1.4 12 12 2 1 20 20 1 2 12 12 1.3 REC: 6
7 LTG: A102,A104,A106,A155-163 1.6 12 12 2 1 20 20 1 2 12 12 1.1 REC: 8
9 LTG: AC102,A117,AC103,AC105,AC105 1.0 12 12 2 1 20 20 1 2 12 12 1.3 REC: 10
11 LTG: AC102, DIMMING AND DAY 1.5 12 12 2 1 20 20 1 2 12 12 0.9 REC: 12
13 LTG: AC103, DIMMING & DAY,A123,A12 1.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 14
15 LTG: A001 AND ELEV PIT 0.3 12 12 2 1 20 20 1 2 12 12 1.1 REC: 16
17 LTG: EXTERIOR 12 12 2 1 20 20 1 2 12 12 0.7 REC: 18
19 REC: AC001, A001 0.5 12 12 2 1 20 20 1 2 12 12 1.4 REC: 20
21 BOLLARDS 0.5 10 10 2 1 20 20 1 2 12 12 1.2 REC: MICROWAVE 22
23 SPARE 1 20 20 1 2 12 12 1.2 REC: COFFEE MAKER 24
25 REC: DAYROOM 0.2 12 12 2 1 20 20 1 2 12 12 1.4 REC: 26
27 REC: DAYROOM 0.2 12 12 2 1 20 20 1 2 12 12 1.1 REC: 28
29 REC: DAYROOM 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 30
31 REC: DAYROOM 0.5 12 12 2 1 20 20 1 2 12 12 0.9 REC: 32
33 REC: A117 (TV) 0.2 12 12 2 1 20 20 1 2 12 12 0.5 REC: 34
35 REC: A115 0.9 12 12 2 1 20 20 1 2 12 12 0.4 REC: 36
37 REC: A113 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 38
39 REC: A111 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 40
41 REC: A109 1.1 12 12 2 1 20 20 1 2 12 12 0.5 REC: 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 22.8 KVA 10.4 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. - B = 17.7 KVA 44.7 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 18.2 KVA 3.1 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 190 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 0.5 KVA MISCELLANEOUS
7. - 163 AMPERES 58.7 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '1N1' (NEW) SECTION 2
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
43 REC: A118 0.9 12 12 2 1 20 20 1 2 12 12 1.4 REC: 44
45 REC: A116 0.7 12 12 2 1 20 20 1 2 12 12 0.4 REC: 46
47 REC: A114 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 48
49 REC: A112 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 50
51 REC: A121 0.5 12 12 2 1 20 20 1 2 12 12 0.4 REC: 52
53 REC: A123 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: A134 54
55 REC: A107 0.9 12 12 2 1 20 20 1 2 12 12 0.9 REC: A133 56
57 WASHING MACHINE: A107 1.5 12 12 2 1 20 20 1 2 12 12 0.4 REC: A131 58
59 ELECTRIC DRYER: A107 2.1 2.1 10 10 2 2 30 20 1 2 12 12 0.7 REC: A122 60
20 1 2 12 12 0.7 REC: A124 62
63 REC: A105 0.9 12 12 2 1 20 20 1 2 12 12 0.9 REC: A126 64
65 SPARE 1 20 20 1 2 12 12 0.2 REC: TV 66
67 REC: A172 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: A129 68
69 LTG: A100 0.8 12 12 2 1 20 20 1 2 12 12 0.7 REC: A127 70
71 ELEV PIT LTG AND REC 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: A125 72
73 SPARE 1 20 20 1 SPARE 74
75 SPARE 1 20 20 1 SPARE 76
77 SPARE 1 20 20 1 SPARE 78
79 SPARE 1 20 20 1 SPARE 80
81 SPARE 1 20 20 1 SPARE 82
83 SPARE 1 20 20 1 SPARE 84
WIRE DEVICE
PANELBOARD 'DPC' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 1000 AMPERES A.I.C. RATING: 65,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 1000 AMPERES BRANCH: NORMAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 PANEL '1C1' 12.3 12.5 11.4 2 3 225 225 3 SPARE, FUTURE PANEL 2
7 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 8
13 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 14
19 SPARE, FUTURE PANEL 3 225 225 3 SPARE, FUTURE PANEL 20
25 SPARE 3 100 225 3 SPARE 26
31 SPARE 3 100 225 3 SPARE 32
37 SPARE 1 20 20 1 SPARE 38
39 SPARE 1 20 20 1 SPARE 40
41 SPARE 1 20 20 1 SPARE 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 12.3 KVA 13.3 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE POWER RISER DIAGRAM FOR CONDUCTOR, RACEWAY SIZES. B = 12.5 KVA 13.3 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 11.4 KVA 2.7 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 105 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 6.9 KVA MISCELLANEOUS
7. - 101 AMPERES 36.2 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '1C1' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: CRITICAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 LTG: A172, A173, A174 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 2
3 LTG: AC102-104,AC107,AC106,AC111 1.9 12 12 2 1 20 20 1 2 12 12 0.7 REC: 4
5 LTG: A171,A170,AS101,A103,A105,A107 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 6
7 LTG: A102,4,6,A155-163,A150-153 1.6 12 12 2 1 20 20 1 2 12 12 0.7 REC: 8
9 LTG: A120,A,B,C,A141,A142,A144,A,B 1.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 10
11 LTG: A121,A123,A125,A127,A129 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 12
13 LTG: A108,A110,A112,A114,A116,A118 1.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 14
15 LTG: A131,A133,A134,A122,A124,A126 1.6 12 12 2 1 20 20 1 2 12 12 0.7 REC: 16
17 LTG: AC001 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 18
19 LTG: EXTERIOR 0.6 12 12 2 1 20 20 1 2 12 12 0.4 REC: 20
21 LTG: A100 0.3 12 12 2 1 20 20 1 2 12 12 0.3 INTERCOM 22
23 MOTORIZED DOOR 1.1 12 12 2 1 20 20 1 SPARE 24
25 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.4 REC: 26
27 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.4 REC: 28
29 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: REFRIGERATOR 30
31 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 32
33 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 34
35 SECURITY CAMERA PWR SUPPLY 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 36
37 REC: A141 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 38
39 REC: A120B 0.4 12 12 2 1 20 20 1 2 12 12 0.4 REC: 40
41 REC: A120C 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 12.3 KVA 13.3 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. - B = 12.5 KVA 13.3 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 11.4 KVA 2.7 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 105 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 6.9 KVA MISCELLANEOUS
7. - 101 AMPERES 36.2 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '1C1' (NEW) SECTION 2
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
43 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 44
45 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 46
47 SPARE 1 20 20 1 SPARE 48
49 SPARE 1 20 20 1 SPARE 50
51 SPARE 1 20 20 1 SPARE 52
53 SPARE 1 20 20 1 SPARE 54
55 SPARE 1 20 20 1 SPARE 56
57 SPARE 1 20 20 1 SPARE 58
59 SPARE 1 20 20 1 SPARE 60
61 SPARE 1 20 20 1 SPARE 62
63 SPARE 1 20 20 1 SPARE 64
65 SPARE 1 20 20 1 SPARE 66
67 SPARE 1 20 20 1 SPARE 68
69 SPARE 1 20 20 1 SPARE 70
71 SPARE 1 20 20 1 SPARE 72
73 SPARE 1 20 20 1 SPARE 74
75 SPARE 1 20 20 1 SPARE 76
77 SPARE 1 20 20 1 SPARE 78
79 SPARE 1 20 20 1 SPARE 80
81 SPARE 1 20 20 1 SPARE 82
83 SPARE 1 20
WIRE DEVICE
SWITCHBOARD 'QSB' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: SWITCHBOARD
BUS AMPACITY: 2000 AMPERES A.I.C. RATING: 65,000 AMPERES MOUNTING: FLOOR
NEUTRAL BUS AMPACITY: 2000 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1
UNIT
NO. NAMEPLATE POLE FRAME(A) TRIP(A) # SIZE GND CONDUIT TOTAL PH. A PH. B PH. C NOTES ADDITIONAL COMMENTS
1 PANEL '1Q1' 3 225 150 31.4 11.3 10.2 9.9 2
2 AHU-1R 3 100 70 11.1 3.7 3.7 3.7 3
3 AHU-1S 3 225 175 27.0 9.0 9.0 9.0 3
4 SPARE, FUTURE PANEL 3 225 225
5 SPARE, FUTURE PANEL 3 225 225
6 SPARE, FUTURE PANEL 3 225 225
7 SPARE, FUTURE PANEL 3 225 225
8 SPARE, FUTURE PANEL 3 225 225
9 SPARE, FUTURE PANEL 3 225 225
10 SPARE, FUTURE PANEL 3 225 225
11 SPARE 3 225 225
12 SPARE 3 225 225
13 SPARE 3 100 100
14 SPARE 3 100 100
15 ELEVATOR - P3 3 200 200 48.9 16.3 16.3 16.3 3
16 ELEVATOR - P4 3 200 200 48.9 16.3 16.3 16.3 3
17 ELEVATOR - S1 3 400 400 97.2 32.4 32.4 32.4 3
18 ELEVATOR - S2 3 400 400 97.2 32.4 32.4 32.4 3
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 121.4 KVA 0.0 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE POWER RISER DIAGRAM FOR CONDUCTOR, RACEWAY SIZES. B = 120.3 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. SEE EQUIPMENT CONNECTION SCHEDULE FOR CONDUCTOR, RACEWAY SIZES. C = 120.0 KVA 8.1 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 53.9 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 1012 AMPERES 296.2 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS
7. - 1004 AMPERES 361.7 KVA TOTAL CONNECTED LOAD
DEVICE FEEDER/ BRANCH CIRCUIT LOAD (KVA)
PANELBOARD '1Q1' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000 AMPERES MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.9 0.9 0.9 EF-1 2
3 TERMINAL BOXES 1.0 12 12 2 1 20
5 TERMINAL BOXES 1.0 12 12 2 1 20
7 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.8 0.8 0.8 CHWP-1 8
9 TERMINAL BOXES 1.0 12 12 2 1 20
11 TERMINAL BOXES 1.0 12 12 2 1 20
13 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.8 0.8 0.8 CHWP-2 14
15 TERMINAL BOXES 1.0 12 12 2 1 20
17 ELEVATOR CONTROL - P3 1.0 2 1 20
19 ELEVATOR CONTROL - P4 1.0 2 1 20 15 3 2 0.6 0.6 0.6 CP - 1 20
21 ELEVATOR CONTROL - S1 1.0 2 1 20
23 HUMIDIFIER - H1 0.1 2 1 20
25 ELEVATOR CONTROL - S2 1.0 2 1 20 15 3 2 1.1 1.1 1.1 HTP - 1 26
27 RCP-1 0.3 2 1 20
29 SP-1 1.1 2 1 20
31 SP-2 1.1 2 1 20 20 1 SPARE 32
33 EF-2 0.7 2 1 20 20 1 SPARE 34
35 BAS 0.5 2 1 20 20 1 SPARE 36
37 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 38
39 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 40
41 SPARE FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 11.3 KVA 0.0 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE EQUIPMENT CONNECTION SCHEDULE FOR CONDUCTOR, RACEWAY SIZES. B = 10.2 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 9.9 KVA 8.1 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 15.8 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 94 AMPERES 4.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS
7. - 87 AMPERES 31.4 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD 'DPLS' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 200 AMPERES A.I.C. RATING: 65,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 200 AMPERES BRANCH: LIFE SAFETY ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 EGRESS LTG. 0.8 12 12 2 1 20 20 1 2 12 12 0.5 FACP 2
3 EGRESS LTG. 1.3 12 12 2 1 20 20 1 2 12 12 0.1 SPRINKLER BELL 4
5 EGRESS LTG. 1.0 12 12 2 1 20 20 1 SPARE 6
7 SPARE 1 20 20 1 SPARE 8
9 SPARE 1 20 20 1 SPARE 10
11 SPARE 1 20 20 1 SPARE 12
13 SPARE 1 20 100 3 FUTURE, PANEL "3LS" 14
15 SPARE 1 20
17 SPACE ONLY
19 SPACE ONLY SPACE ONLY 20
21 SPACE ONLY SPACE ONLY 22
23 SPACE ONLY SPACE ONLY 24
25 SPACE ONLY SPACE ONLY 26
27 SPACE ONLY SPACE ONLY 28
29 SPACE ONLY SPACE ONLY 30
31 SPACE ONLY SPACE ONLY 32
33 SPACE ONLY SPACE ONLY 34
35 SPACE ONLY SPACE ONLY 36
37 SPACE ONLY SPACE ONLY 38
39 SPACE ONLY SPACE ONLY 40
41 SPACE ONLY SPACE ONLY 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 1.3 KVA 3.1 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. - B = 1.4 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 1.0 KVA 0.0 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 12 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 0.6 KVA MISCELLANEOUS
7. - 10 AMPERES 3.7 KVA TOTAL CONNECTED LOAD
PANELBOARD '3N1' (NEW) SECTION 1
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: NORMAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 LTG: A372 (AND OTHER ROOMS) 0.3 12 12 2 1 20 20 1 2 12 12 0.7 REC: EWC 2
3 LTG: A374 (AND OTHER ROOMS) 0.6 12 12 2 1 20 20 1 2 12 12 0.9 REC: 4
5 LTG: A309 (AND OTHER ROOMS) 0.9 12 12 2 1 20 20 1 2 12 12 1.1 REC: 6
7 LTG: A302 (AND OTHER ROOMS) 0.4 12 12 2 1 20 20 1 2 12 12 1.1 REC: 8
9 LTG: AC302 (AND OTHER ROOMS) 2.1 12 12 2 1 20 20 1 2 12 12 1.3 REC: 10
11 LTG: AC302A (AND OTHER ROOMS) 1.4 12 12 2 1 20 20 1 2 12 12 0.9 REC: 12
13 LTG: A321 (AND OTHER ROOMS) 1.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 14
15 REC 0.9 12 12 2 1 20 20 1 2 12 12 1.1 REC: 16
17 ROOF RECEPTACLE 0.2 12 12 2 1 20 20 1 2 12 12 0.7 REC: 18
19 SPARE 1 20 20 1 2 12 12 1.4 REC: 20
21 SPARE 1 20 20 1 2 12 12 1.1 REC: 22
23 SPARE 1 20 20 1 2 12 12 0.5 REC: 24
25 REC 0.2 12 12 2 1 20 20 1 2 12 12 0.5 REC: 26
27 REC 0.2 12 12 2 1 20 20 1 2 12 12 1.1 REC: 28
29 REC 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC: 30
31 REC 0.5 12 12 2 1 20 20 1 2 12 12 0.9 REC: 32
33 REC 0.2 12 12 2 1 20 20 1 2 12 12 0.5 REC: 34
35 REC 0.9 12 12 2 1 20 20 1 2 12 12 0.4 REC: 36
37 REC 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 38
39 REC 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 40
41 REC 1.1 12 12 2 1 20 20 1 2 12 12 0.5 REC: 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 20.8 KVA 7.4 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SPARE BREAKERS SHALL BE IN THE "OFF" POSITION. B = 20.0 KVA 45.5 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 17.7 KVA 5.5 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE A: 173 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 0.0 KVA MISCELLANEOUS
7. - 162 AMPERES 58.4 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '3C1' (NEW) SECTION 1
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: CRITICAL ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 LTG: A372 (AND OTHER ROOMS) 0.4 12 12 2 1 20 20 1 2 12 12 0.5 REC: 2
3 LTG: AC302 (AND OTHER ROOMS) 1.8 12 12 2 1 20 20 1 2 12 12 0.7 REC: 4
5 LTG: A309 (AND OTHER ROOMS) 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 6
7 LTG: A302 (AND OTHER ROOMS) 1.1 12 12 2 1 20 20 1 2 12 12 0.7 REC: 8
9 LTG: A320 (AND OTHER ROOMS) 1.6 12 12 2 1 20 20 1 2 12 12 0.7 REC: 10
11 LTG: A321 (AND OTHER ROOMS) 1.4 12 12 2 1 20 20 1 2 12 12 0.7 REC: 12
13 LTG: A308 (AND OTHER ROOMS) 1.5 12 12 2 1 20 20 1 2 12 12 0.7 REC: 14
15 LTG: A322 (AND OTHER ROOMS) 1.7 12 12 2 1 20 20 1 2 12 12 0.4 REC: 16
17 SPARE 1 20 20 1 2 12 12 0.4 REC: 18
19 SPARE 1 20 20 1 2 12 12 0.5 SECURITY CAMERA POWER SUPPLY 20
21 SPARE 1 20 20 1 0.3 SPARE 22
23 SPARE 1 20 20 1 SPARE 24
25 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.4 REC: 26
27 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.5 REC: 28
29 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: REFRIGERATOR 30
31 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 32
33 CARD READERS 1.0 12 12 2 1 20 20 1 2 12 12 0.7 REC: 34
35 SECURITY CAMERA PWR SUPPLY 12 12 2 1 20 20 1 2 12 12 0.7 REC: 36
37 REC: A241 12 12 2 1 20 20 1 SPARE 38
39 REC: A220B 12 12 2 1 20 20 1 SPARE 40
41 REC: A220C 12 12 2 1 20 20 1 2 12 12 0.7 REC: 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 9.6 KVA 10.9 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SPARE BREAKERS SHALL BE IN THE "OFF" POSITION. B = 11.4 KVA 9.9 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 7.8 KVA 2.7 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 95 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 5.3 KVA MISCELLANEOUS
7. - 80 AMPERES 28.8 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '3Q1' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 225 AMPERES A.I.C. RATING: 22,000 AMPERES MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 225 AMPERES BRANCH: EQUIPMENT ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 2 0.9 0.9 0.9 EF-7 2
3 TERMINAL BOXES 1.0 12 12 2 1 20
5 TERMINAL BOXES 1.0 12 12 2 1 20
7 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 SPARE 8
9 TERMINAL BOXES 1.0 12 12 2 1 20
11 TERMINAL BOXES 1.0 12 12 2 1 20
13 TERMINAL BOXES 1.0 12 12 2 1 20 15 3 SPARE 14
15 TERMINAL BOXES 1.0 12 12 2 1 20
17 MTR OP SMOKE CONTROL DOOR 0.5 12 12 2 1 20
19 SSCU-1 0.7 0.7 12 10 3 2 15 15 3 SPARE 20
23 HUMIDIFIER - H3 0.1 2 1 20
25 SPARE 1 20 15 3 2 1.1 1.1 1.1 HTP - 2 26
27 RCP-3 0.3 2 1 20
29 SPARE 1 20
31 EF-6 0.3 2 1 20 20 1 SPARE 32
33 EF-5 0.7 2 1 20 20 1 SPARE 34
35 BAS 3 0.5 2 1 20 20 1 SPARE 36
37 FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 38
39 FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 40
41 FOR MECHANICAL USE 1.0 12 12 2 1 20 20 1 SPARE 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 7.0 KVA 0.0 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE EQUIPMENT CONNECTION SCHEDULE FOR CONDUCTOR, RACEWAY SIZES. B = 7.7 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. SPARE BREAKERS SHALL BE IN THE "OFF" POSITION. C = 6.1 KVA 8.6 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 8.7 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 64 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 3.5 KVA MISCELLANEOUS
7. - 58 AMPERES 20.8 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD 'DPLS' (EXISTING)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 200 AMPERES A.I.C. RATING: 65,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 200 AMPERES BRANCH: LIFE SAFETY ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 EGRESS LTG, 1ST FLOOR 0.8 3 12 12 2 1 20 20 1 2 12 12 3 0.5 FACP, 1st FLOOR 2
3 EGRESS LTG, 1ST FLOOR 1.3 3 12 12 2 1 20 20 1 2 12 12 3 0.1 SPRINKLER BELL 4
5 EGRESS LTG, 1ST FLOOR 1.0 3 12 12 2 1 20 20 1 3 SPARE 6
7 SPARE 3 1 20 20 1 3 SPARE 8
9 SPARE 3 1 20 20 1 3 SPARE 10
11 SPARE 3 1 20 20 1 3 SPARE 12
13 SPARE 3 1 20 100 3 2,3 PANEL "3LS" 14
15 SPARE 3 1 20
17 SPACE ONLY
19 SPACE ONLY SPACE ONLY 20
21 SPACE ONLY SPACE ONLY 22
23 SPACE ONLY SPACE ONLY 24
25 SPACE ONLY SPACE ONLY 26
27 SPACE ONLY SPACE ONLY 28
29 SPACE ONLY SPACE ONLY 30
31 SPACE ONLY SPACE ONLY 32
33 SPACE ONLY SPACE ONLY 34
35 SPACE ONLY SPACE ONLY 36
37 SPACE ONLY SPACE ONLY 38
39 SPACE ONLY SPACE ONLY 40
41 SPACE ONLY SPACE ONLY 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 1.3 KVA 3.1 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SEE POWER RISER DIAGRAM FOR CONDUCTOR AND RACEWAY SIZES. B = 1.4 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. EXISTING BREAKER SHALL REMAIN. C = 1.0 KVA 0.0 KVA RECEPTACLES (EQUIPMENT)
4. SPARE BREAKERS SHALL BE IN THE "OFF" POSITION. HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 12 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 0.6 KVA MISCELLANEOUS
7. - 10 AMPERES 3.7 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '3LS' (NEW)
SUPPLY VOLTAGE: 208/120 VOLT, 3 PHASE, 4 WIRE MAIN DEVICE: MLO TYPE: LIGHTING / APPLIANCE
BUS AMPACITY: 100 AMPERES A.I.C. RATING: 22,000A MOUNTING: SURFACE
NEUTRAL BUS AMPACITY: 100 AMPERES BRANCH: LIFE SAFETY ENCLOSURE: NEMA 1
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
1 EGRESS LTG, 2nd FLOOR 0.8 12 12 2 1 20 20 1 2 12 12 0.5 FACP2 2 3 EGRESS LTG, 2nd FLOOR 1.3 12 12 2 1 20 20 1 2 12 12 0.5 FACP3 4 5 EGRESS LTG, 2nd FLOOR 1.0 12 12 2 1 20 20 1 SPARE 6 7 EGRESS LTG, 3rd FLOOR 0.7 12 12 2 1 20 20 1 SPARE 8 9 EGRESS LTG, 3rd FLOOR 0.9 12 12 2 1 20 20 1 SPARE 10
11 EGRESS LTG, 3rd FLOOR 0.9 12 12 2 1 20 20 1 SPARE 12
13 SPARE 1 20 SPACE ONLY 14
15 SPARE 1 20 SPACE ONLY 16
17 SPACE ONLY SPACE ONLY 18
19 SPACE ONLY SPACE ONLY 20
21 SPACE ONLY SPACE ONLY 22
23 SPACE ONLY SPACE ONLY 24
25 SPACE ONLY SPACE ONLY 26
27 SPACE ONLY SPACE ONLY 28
29 SPACE ONLY SPACE ONLY 30
31 SPACE ONLY SPACE ONLY 32
33 SPACE ONLY SPACE ONLY 34
35 SPACE ONLY SPACE ONLY 36
37 SPACE ONLY SPACE ONLY 38
39 SPACE ONLY SPACE ONLY 40
41 SPACE ONLY SPACE ONLY 42
NOTES: CONNECTED PHASE TOTALS CONNECTED LOAD SUMMARY
1. WITH EQUIPMENT GROUND BUS. A = 2.0 KVA 5.7 KVA LIGHTING (INTERIOR AND EXTERIOR)
2. SPARE BREAKERS SHALL BE IN THE "OFF" POSITION. B = 2.7 KVA 0.0 KVA RECEPTACLES (GENERAL PURPOSE)
3. - C = 1.9 KVA 0.0 KVA RECEPTACLES (EQUIPMENT)
4. - HIGHEST CONNECTED PHASE(S) 0.0 KVA HVAC (HEATING, A/C, AHU'S & EXH. FANS)
5. - PHASE B: 23 AMPERES 0.0 KVA OTHER (ELEV., WATER HTR., KIT. EQUIP.)
6. - TOTAL CONNECTED LOAD 1.0 KVA MISCELLANEOUS
7. - 19 AMPERES 6.7 KVA TOTAL CONNECTED LOAD
WIRE DEVICE
PANELBOARD '3N1' (NEW) SECTION 2
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
43 REC 0.9 12 12 2 1 20 20 1 2 12 12 1.4 REC: 44
45 REC 0.7 12 12 2 1 20 20 1 2 12 12 0.4 REC: 46
47 REC 0.7 12 12 2 1 20 20 1 2 12 12 0.5 REC: 48
49 REC 0.7 12 12 2 1 20 20 1 2 12 12 0.7 REC: 50
51 REC 0.5 12 12 2 1 20 20 1 2 12 12 0.4 REC: 52
53 REC 0.5 12 12 2 1 20 20 1 2 12 12 0.7 REC 54
55 REC 0.7 12 12 2 1 20 20 1 2 12 12 0.9 REC 56
57 WASHING MACHINE 1.5 12 12 2 1 20 20 1 2 12 12 0.4 REC 58
59 ELECTRIC DRYER 2.1 2.1 10 10 2 2 30 20 1 2 12 12 0.7 REC 60
20 1 2 12 12 0.7 REC 62
63 REC 0.9 12 12 2 1 20 20 1 2 12 12 0.9 REC 64
65 SPARE 1 20 20 1 2 12 12 0.2 REC: TV 66
67 REC 0.5 12 12 2 1 20 20 1 2 12 12 0.9 REC 68
69 EXERCISE EQUIPMENT 1.2 12 12 2 1 20 20 1 2 12 12 0.7 REC 70
71 EXERCISE EQUIPMENT 1.2 12 12 2 1 20 20 1 2 12 12 0.7 REC 72
73 EXERCISE EQUIPMENT 1.2 12 12 2 1 20 20 1 SPARE 74
75 EXERCISE EQUIPMENT 1.2 12 12 2 1 20 20 1 SPARE 76
77 SPARE 1 20 20 1 SPARE 78
79 SPARE 1 20 20 1 SPARE 80
81 SPARE 1 20 20 1 SPARE 82
83 SPARE 1 20 20 1 SPARE 84
WIRE DEVICE
PANELBOARD '3C1' (NEW) SECTION 2
CKT. LOAD (KVA) DEVICE WIRE LOAD (KVA) CKT.
NO. LOAD DESCRIPTION / LOCATION PH. A PH. B PH. C NOTES GND SIZE # P AMP AMP P # SIZE GND NOTES PH. A PH. B PH. C LOAD DESCRIPTION / LOCATION NO.
43 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 44
45 SPARE 1 20 20 1 2 12 12 1.0 REC: PYXIS 46
47 SPARE 1 20 20 1 SPARE 48
49 SPARE 1 20 20 1 SPARE 50
51 SPARE 1 20 20 1 SPARE 52
53 SPARE 1 20 20 1 SPARE 54
55 SPARE 1 20 20 1 SPARE 56
57 SPARE 1 20 20 1 SPARE 58
59 SPARE 1 20 20 1 SPARE 60
61 SPARE 1 20 20 1 SPARE 62
63 SPARE 1 20 20 1 SPARE 64
65 SPARE 1 20 20 1 SPARE 66
67 SPARE 1 20 20 1 SPARE 68
69 SPARE 1 20 20 1 SPARE 70
71 SPARE 1 20 20 1 SPARE 72
73 SPARE 1 20 20 1 SPARE 74
75 SPARE 1 20 20 1 SPARE 76
77 SPARE 1 20 20 1 SPARE 78
79 SPARE 1 20 20 1 SPARE 80
81 SPARE 1 20 20 1 SPARE 82
83 SPARE 1 20