36C24619R0025-008.pdf
PDF 4 MB Posted
- Attached to
- Synopsis for Expand Parking Garage Bldg 33 Federal contract opportunity
- Solicitation number
- 36C24619R0025
About this file
36C24619R0025 Expand Parking Garage Bid Set_Structural #3.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24619R0025-0003000.docx | DOCX document | |
| 36C24619R0025-0002001.docx | DOCX document | |
| 36C24619R0025-0002000.docx | DOCX document | |
| 36C24619R0025-0001002.pdf | ||
| 36C24619R0025-0001001.docx | DOCX document | |
| 36C24619R0025-0001003.pdf | ||
| 36C24619R0025-0001000.docx | DOCX document | |
| 36C24619R0025-003.xlsx | XLSX spreadsheet | |
| 36C24619R0025-001.docx | DOCX document | |
| 36C24619R0025-004.pdf | ||
| 36C24619R0025-005.pdf | ||
| 36C24619R0025-010.pdf | ||
| 36C24619R0025-007.pdf | ||
| 36C24619R0025-012.pdf | ||
| 36C24619R0025-006.pdf | ||
| 36C24619R0025-014.docx | DOCX document | |
| 36C24619R0025-009.pdf | ||
| 36C24619R0025-002.pdf | ||
| 36C24619R0025-011.pdf | ||
| 36C24619R0025-013.docx | DOCX document | |
| 36C24619R0025-000.docx | DOCX document |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BEAM LEGEND
W18X40 C=1"
CAMBERBEAM SIZE
20K20K
BEAM REACTION,
TYP
(8) (8)(4)
QUANTITY OF SHEAR STUDS,
UNIFORMLY SPACED BETWEEN
ADJACENT FRAMING, TYP
(COMPOSITE CONSTRUCTION
ONLY)
NOTES:
1) REACTION VALUE IS ASD (KIPS), UNO.
2) WHERE NO VALUE IS SHOWN, DESIGN CONNECTION FOR A MINIMUM REACTION OF 10 KIPS.
3) SPACE STUDS PER TYPICAL SHEAR STUD PLACEMENT DETAIL. MINIMUM NUMBER OF STUDS
PER GENERAL NOTES.
4) "M" IN PLACE OF BEAM SIZE INDICATES W10X12 WITH MINIMUM CONNECTION.
5) HSS IN PLACE OF SHAPE INDICATES HSS10X4X5/16, UNO.
6) BEAMS ARE PRIMARY MEMBERS FOR FIREPROOFING UNLESS NOTED AS SECONDARY.
7) POSITIVE CAMBER UPWARDS, NEGATIVE CAMBER DOWNWARDS. CAMBER SHOWN
ON CANTILEVERS IS AT END OF CANTILEVER.
MOMENT CONNECTION
CANT BM, SAME SIZE AND
END REACTION AS
BACKSPAN, UNO
C=1/2" CAMBER
MISCELLANEOUS SYMBOLS
NORTH ARROW GRIDLINES
EARTH
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
A
ELEVATION
REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
C# COLUMN NOTATION
Z# PRECAST/ BRICK SUPPORT
L# LINTEL NOTATION
F ## COLUMN FOOTING NOTATION
GB ## GRADE BEAM NOTATION
P ## PIER NOTATION
B ## CONCRETE BEAM NOTATION
PB ## POST-TENSIONED CONCRETE
BEAM NOTATION
PC ## PILE CAP NOTATION
WF ## WALL FOOTING NOTATION
SHEAR WALL NOTATIONSW ##
BW ## BEARING WALL NOTATION
GRAVEL
Name
Elevation
WALL PIER NOTATIONWP ##
W ## WALL NOTATION
CONCRETE SYMBOLS
POST-TENSION TENDON
ANCHOR DEAD END
LOCATION
POST-TENSION TENDON
ANCHOR JACKING
LOCATION
REBAR
CHANGE OF SLAB
ELEVATION
SLOPING SLAB
CHANGE OF SLAB
THICKNESS
MECHANICAL COUPLER
REBAR SPLICE
LIMIT OF MEMBER OR
SPAN MARK
DIRECTION OF SPAN
OPENING
SELF-EXPANDING
WATERSTOP
CONTROL JOINT LOCATION
IN CONCRETE WALLS
REBAR TERMINATOR
INTENTIONALLY
ROUGHENED
CONSTRUCTION JOINT
TO 1/4" AMPLITUDE
WELDED WIRE FABRIC
PVC WATERSTOP
COLUMN CONTINUES
COLUMN TERMINATED
FORM-SAVER
SOG # SLAB ON GRADE MARK
CONNECTORS
HEADED STUD
CONNECTOR SECTION END/ALT VIEW
CAST-IN ANCHOR
ROD
POST-INSTALLED
MECHANICAL ANCHOR
BOLT
POST INSTALLED
ADHESIVE ANCHOR
STEEL MEMBERS
W-SHAPE BEAM
SHAPE SECTION PLAN VIEWELEVATION
CHANNEL
ANGLE
DOUBLE ANGLE
HOLLOW STRUCTURAL
SECTION
-RECTANGULAR
LLV LLH
HOLLOW STRUCTURAL
SECTION
-CIRCULAR (PIPE)
OPEN WEB STEEL
JOIST
STEEL SYMBOLS
STEEL DECK
STEEL DECK MARK AND
SPAN DIRECTION
BEAM SPLICE
CONNECTION
BEAM MOMENT CONNECTION
AT COLUMN
BEAM SHEAR CONNECTION
AT COLUMN
BEAM CONTINUOUS OVER
COLUMN
SLAB ON STEEL
DECK
SLAB ON STEEL
DECK
WWF
COLUMN STARTS HERE
DIAGONAL BRACING
BRACING
HANGER OR POST
HANGER OR POST
BELOW FLOOR
SLAB-ON-DECK MARK AND
SPAN DIRECTION
OR
D#
S#
PRECAST MEMBERS
DOUBLE TEE
SHAPE SECTION PLAN VIEWELEVATION
GIRDER
SPANDREL
PLANK
HOLLOW-CORE
MASONRY MEMBERS
CMU SECTION
CMU BOND BEAM SECTION
(FULLY GROUTED)
CMU LINTEL SECTION
(FULLY GROUTED)
SINGLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
DOUBLE REINFORCEMENT
(FULLY GROUT REINFORCED
CELLS)
PLAN
PLAN
NON-COATED REINFORCING BAR
DEVELOPMENT AND SPLICE LENGTHS
f 'c = 4000 PSI
BAR SIZE Ld Ldt Lt Ltt
15 20 20 26#3
19 25 25 33#4
24 32 32 41#5
29 38 38 50#6
42 55 55 71#7
48 63 63 82#8
54 71 71 92#9
60 78 78 102#10
66 86 86 112#11
ALL CONCRETE STRENGTHS
BAR SIZE Lb Lc Lcs
9 12 12#3
11 13 12#4
14 16 15#5
17 19 17#6
20 22 20#7
22 25 23#8
25 29 26#9
28 32 29#10
31 35 31#11
EPOXY COATED REINFORCING BAR
DEVELOPMENT AND SPLICE LENGTHS
f 'c = 4000 PSI
BAR SIZE Ld Ldt Lt Ltt
22 29 38#3
29 38 50#4
36 47 61#5
43 56 73#6
63 82 107#7
72 94 122#8
81 106 137#9
89 116 151#10
98 128 166#11
ALL CONCRETE STRENGTHS
BAR SIZE Lb Lc Lcs
9 12 12#3
11 13 12#4
14 16 15#5
17 19 17#6
20 22 20#7
22 25 23#8
25 29 26#9
28 32 29#10
31 35 31#11
NOTES:
1. db = NOMINAL BAR DIAMETER
Ld = TENSION DEVELOPMENT LENGTH Ldt = DEVELOPMENT LENGTH OF TOP BARS IN TENSION Lt = TENSION LAP SPLICE LENGTH Ltt = TENSION LAP SPLICE LENGTH OF TOP BARS Lb = COMPRESSION DEVELOPMENT LENGTH Lc = TIED COLUMN LAP SPLICE IN COMPRESSION Lcs = SPIRAL COLUMN LAP SPLICE IN COMPRESSION
2. REBAR DEVELOPMENT/SPLICE LENGTHS ARE BASED
ON ACI 318. REINFORCEMENT YIELD STRENGTH, Fy = 60 KSI.
3. "TOP BARS" = HORIZONTAL BEAM, MAT, OR SLAB REINFORCING WITH
MORE THAN12" CAST BELOW.
4. ALL SPLICES SHALL BE TENSION SPLICES, UNO.
TABLE VALUES SHALL BE MULTIPLIED BY 1.5 IF THE FOLLOWING
CRITERIA ARE NOT MET:
SLAB / WALL
MIN
3db d b
C
L R
M
IN
MIN
2db
MIN
2db
COLUMN / BEAM
d b C
L R
M
IN
TOP
BAR
TYPICAL REINFORCING BAR DEVELOPMENT / SPLICE DETAILS
S
S T
A G
G E
R
S
MECHANICAL
COUPLER
MECHANICAL
SPLICE STAGGER LAP DETAIL
T A
B L E
L A
P P
E R
(L t, L d t, L tt L c L c s
Lb
Ld
DEVELOPMENT LENGTH
DEDUCT ALTERNATES
# NOT ALL DEDUCT SYMBOLS WILL BE USED ON EACH SHEET
1. DEDUCT SILANE SEALER.
2. DEDUCT THINSET BRICK AT EXTERIOR SPANDRELS FROM SCOPE.
3. DEDUCT RE-STRIPING OF EXISTING GARAGE LEVELS.
4. DEDUCT TOP LEVEL BETWEEN COLUMN LINES 2 & 3, AND COLUMN LINES E & G.
5. DEDUCT ELEVATOR TO TOP LEVEL. ELEVATOR RUN TO EXTEND TO LEVEL 5.
6. DEDUCT TOP LEVEL BETWEEN COLUMN LINES 1 & 2, AND COLUMN LINES B & H.
7. DEDUCT TOP LEVEL BETWEEN COLUMN LINES 2 & 3, AND COLUMN LINES G & H.
8. DEDUCT TOP LEVEL BETWEEN COLUMN LINES 1 & 2, AND COLUMN LINES A & B. DEDUCT SW
STAIR TO TOP LEVEL.
JST JOIST
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABRATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSL LAMINATED STRAND LUMBER
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
LVL LAMINATED VENEER LUMBER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
OWJ PRE-MANUFACTURED OPEN WEB JOIST
PC PRECAST CONCRETE
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSL PARALLEL STRAND LUMBER
PT POST-TENSIONED
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
RTU ROOFTOP MECHANICAL UNIT
S SLOPE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TEMP TEMPERATURE
THRU THROUGH
TJI PREFABRICATED WOOD I-JOIST
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WH WEEP HOLE
WP WORK POINT
WT WEIGHT, STRUCTURAL T
WWF WELDED WIRE FABRIC
XS EXTRA STRONG (PIPE)
XXS DOUBLE EXTRA STRONG (PIPE)
& AND
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BD BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
BU BUILT UP
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GL GLUED LAMINATED TIMBER (GLULAM)
GRND GROUND
GT GIRDER TRUSS
HAS HEADED ANCHOR STUD
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HIP TRUSS
HVAC HEATING, VENTILATION, AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J/BRG JOIST BEARING
STRUCTURAL DRAWINGS ABBREVIATIONS
SHEET # SHEET NAME
SI001 ABBREVIATIONS AND SYMBOLS
SI002 STRUCTURAL GENERAL NOTES
SI003 SPECIAL INSP. NOTES AND TABLES
SI004 LOAD MAPS
SB101 FOUNDATION PLAN / EXISTING LEVEL LL2
SF101 EXISTING LEVEL LL1 SLAB ON GRADE PLAN
SF102 EXISTING LEVEL 1 FRAMING PLAN
SF103 EXISTING LEVEL 2 FRAMING PLAN
SF104 EXISTING LEVEL 3 FRAMING PLAN
SF105 LEVEL 4 FRAMING PLAN
SF106 LEVEL 5 FRAMING PLAN
SF107 LEVEL 6 FRAMING PLAN
SF201 SHEARWALL ELEVATIONS AND SCHEDULES
SF301 BUILDING SECTIONS AND ELEVATIONS
SF302 BUILDING SECTIONS AND ELEVATIONS
SF303 BUILDING SECTIONS AND ELEVATIONS
SF401 ENLARGED PLANS
SF501 FRAMING SECTIONS AND DETAILS
SF502 FRAMING SECTIONS AND DETAILS
SF503 FRAMING SECTIONS AND DETAILS
SF504 FRAMING SECTIONS AND DETAILS
SF901 AXONOMETRICS
STRUCTURAL INDEX
12/31/2014
028171
SEAL
N O
R
TH
CAROLIN
A
D O
N A L D G . C O R S
O
NE NG IN E E
R
P R
O
FESS ION
A L
Drawing TitleDrawing TitleDrawing TitleDrawing Title
Approved for Design Concept:Approved for Design Concept:Approved for Design Concept:Approved for Design Concept:
Project TitleProject TitleProject TitleProject Title
DateDateDateDate
LocationLocationLocationLocation
Checked By:Checked By:Checked By:Checked By:
Building NumberBuilding NumberBuilding NumberBuilding Number
Project NumberProject NumberProject NumberProject Number
Drawing NumberDrawing NumberDrawing NumberDrawing Number
Drawn By:Drawn By:Drawn By:Drawn By:
Revisions:Revisions:Revisions:Revisions: DateDateDateDate
PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:
Durham VAMCDurham VAMCDurham VAMCDurham VAMC
Bldg 33Bldg 33Bldg 33Bldg 33 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
1111 2222 3333 4444 5555 6666 7777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
OFFICE OFOFFICE OFOFFICE OFOFFICE OF
FACILITIESFACILITIESFACILITIESFACILITIES
MANAGEMENTMANAGEMENTMANAGEMENTMANAGEMENT
VA Project NumberVA Project NumberVA Project NumberVA Project Number
Structural
AMERICAN
STRUCTUREPOINT
7260 Shadeland Station Indianapolis, IN 46256
Tele: 317-547-5580
MEP Engineer
APOGEE
CONSULTING GROUP
7330 Chapel Hill Road, Suite 202 Raleigh, NC 27607
Tele: 919-858-7420
Civil Engineer
GUIDON DESIGN
INC.
905 N. Capitol Ave.
Suite 100 Indianapolis, IN 46204
Tele: 317-800-6388
Functional Design
CARL WALKER INC.
14045 Ballantyne Corp.
Place, Suite 380 Charlotte, NC 28277
Tele: 704-716-8000
MICHAEL JAKUBIAKMICHAEL JAKUBIAKMICHAEL JAKUBIAKMICHAEL JAKUBIAK
PROJECT ENGINEERPROJECT ENGINEERPROJECT ENGINEERPROJECT ENGINEER
919-286-0411919-286-0411919-286-0411919-286-0411
Department of Veterans Affairs
558-318558-318558-318558-318
C R e v it \R e v it S tr u c tu re
\2
S
T V
A D u rh a m
P G
C
E N
T R
A L R
S T
R b c u rt s .r v t
BID SETBID SETBID SETBID SET
SI001SI001SI001SI001
BGCBGCBGCBGCJAPJAPJAPJAP
ABBREVIATIONSABBREVIATIONSABBREVIATIONSABBREVIATIONS
AND SYMBOLSAND SYMBOLSAND SYMBOLSAND SYMBOLS
12/31/201412/31/201412/31/201412/31/2014
2013.001882013.001882013.001882013.00188
A/E SERVICES PARKINGA/E SERVICES PARKINGA/E SERVICES PARKINGA/E SERVICES PARKING
STRUCTURESTRUCTURESTRUCTURESTRUCTUREVA Durham VAMCVA Durham VAMCVA Durham VAMCVA Durham VAMC
Dept. of Veterans AffairsDept. of Veterans AffairsDept. of Veterans AffairsDept. of Veterans Affairs 508 Fulton Street508 Fulton Street508 Fulton Street508 Fulton Street Durham, NC 27705Durham, NC 27705Durham, NC 27705Durham, NC 27705
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE
METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE
RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE
SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING
ERECTION. THIS INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL,
ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING DRAWINGS, AND PRECAST
CONCRETE DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH
THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A
DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE
MORE STRINGENT REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN
ON THE DRAWINGS, SHALL BE MADE WITHOUT THE APPROVAL OF THE STRUCTURAL
ENGINEER.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER
A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL
BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE
CONTRACTOR SHALL NOT VARY FROM THE MIX DESIGNS NOR USE ANY CONCRETE
OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE APPROVAL OF THE
STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE FOLLOWING
INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION
OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION,
AND NAME AND LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND
LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION
OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
9. DESIGN SLUMP RANGE.
10. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
11. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN
ACCORDANCE WITH "STANDARD DEVIATION" DETERMINATION OUTLINED IN
ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO COORDINATE
FABRICATION AND CONSTRUCTION OF ALL PARTS OF THE WORK IN ACCORDANCE
WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE
REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE
CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO
SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT
CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF SHOP DRAWINGS. FOR HARD
COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF SHOP DRAWINGS TO THE
STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED BY THE
STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT SHOP DRAWINGS IN
ADOBE PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT
IS CONSTRUCTED FOR ALL CONNECTIONS NOT SPECIFICALLY DETAILED ON
THE DRAWINGS)
3. STEEL DECK
4. PRECAST CONCRETE COMPONENTS (PRECAST LINTELS, ARCHITECTURAL
PRECAST)
5. HOLLOW CORE PRECAST PLANKS
6. GLASS CURTAIN WALL SYSTEM (INCLUDING DESIGN CALCULATIONS AND
CONNECTION DETAILS SEALED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE WHERE THE PROJECT IS CONSTRUCTED)
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC
ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE
SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF PRODUCT DATA. FOR HARD
COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF PRODUCT DATA TO THE
STRUCTURAL ENGINEER FOR REVIEW (ONE COPY SHALL BE RETAINED BY THE
STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT PRODUCT DATA IN
ADOBE PDF FORMAT.
1. CONCRETE CURING COMPOUND
2. CONCRETE JOINT SEALANT
3. WATER STOPS
4. EXPANSION ANCHORS
5. ADHESIVE ANCHORS
6. NON-SHRINK GROUT
RENOVATION (EXISTING CONDITIONS)
INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS
TAKEN FROM DRAWINGS THAT WERE PREPARED FOR DURHAM VA MEDICAL CENTER,
PREPARED BY BELK ARCHITECTURE, ENTITLED PARKING DECK, DATED 6/6/11.
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS
PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS
INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES,
MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO
VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY
THE STRUCTURAL ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK
ALL DIMENSIONS AND CONDITIONS IN THE FIELD, AND REPORT ANY ERRORS OR
DISCREPANCIES TO THE STRUCTURAL ENGINEER PRIOR TO THE FABRICATION AND
ERECTION OF ANY NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THIS PROJECT,
THAT BECOME DAMAGED, SHALL BE REPLACED WITH NEW MATERIAL OF EQUAL
QUALITY AND APPEARANCE, AT THE CONTRACTOR'S EXPENSE.
ALL WORK SHALL BE PERFORMED WITHOUT DAMAGE TO ADJACENT RETAINED WORK.
ADJACENT EXISTING CONSTRUCTION SHALL BE PROTECTED FROM DUST, DIRT AND
DEBRIS ACCUMULATION AT ALL TIMES.
FOUNDATIONS
FOUNDATION EXCAVATIONS AND SOIL RELATED WORK SHALL BE PERFORMED IN
ACCORDANCE WITH THE GEOTECHNICAL REPORT NUMBER 70135142 PREPARED
BY TERRACON DATED DECEMBER 18, 2013.
DESIGN NET SOIL PRESSURE:
SPREAD FOOTINGS: 9000 PSF
CONTINUOUS WALL FOOTINGS: 4000 PSF
FOUNDATIONS AND SOILS RELATED WORK SHALL BE INSPECTED BY A LICENSED
GEOTECHNICAL ENGINEER. WRITTEN FIELD REPORTS SHALL BE FORWARDED TO THE
STRUCTURAL ENGINEER AS SOON AS THEY BECOME AVAILABLE.
FOUNDATION CONDITIONS NOTED DURING CONSTRUCTION, WHICH DIFFER FROM
THOSE DESCRIBED IN THE GEOTECHNICAL REPORT, SHALL BE REPORTED TO THE
STRUCTURAL ENGINEER AND GEOTECHNICAL ENGINEER BEFORE FURTHER
CONSTRUCTION IS ATTEMPTED.
EXCAVATIONS FOR SPREAD FOOTINGS, COMBINED FOOTINGS, CONTINUOUS
FOOTINGS AND MAT FOUNDATIONS SHALL BE CLEANED AND HAND TAMPED TO
UNIFORM SURFACE AND SHALL BE PROTECTED AND MAINTAINED UNIFORM UNTIL
CONCRETE IS PLACED.
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING
CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318) AND COMMENTARY
(ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE
LATEST EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301).
READY-MIXED CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94.
IN CASE OF A DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT
(BY WEIGHT) OF FLY ASH TO TOTAL CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT
EXCEED 25 PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE
CERTIFIED BY THE MANUFACTURER TO BE COMPATIBLE WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN
0.1 PERCENT CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 306R, COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND
PROTECTION OF CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE
LATEST EDITION OF ACI 305R, HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON
THE DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL
HAVE THE PROPERTIES AS SHOWN BELOW:
FOOTINGS AND MATS
1. COMPRESSIVE STRENGTH (28 DAYS): 3000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 423 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING
ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH
2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.50
6. MAXIMUM COARSE AGGREGATE SIZE: 1-1/2 INCHES
7. AIR CONTENT: N/A
INTERIOR SLABS ON METAL DECK
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING
ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH
2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 1 INCH
7. AIR CONTENT: N/A
TOPPING SLABS
1. COMPRESSIVE STRENGTH (28 DAYS): 4000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 470 LB./CU. YD.
4. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING
ADMIXTURE: 8 INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH
2 TO 4 INCH SLUMP).
5. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.48
6. MAXIMUM COARSE AGGREGATE SIZE: 3/4 INCH
7. AIR CONTENT: N/A
WELDABLE REINFORCING STEEL
REINFORCING STEEL WHICH IS TO BE WELDED SHALL CONFORM TO ASTM A706.
WELDING OF REINFORCING STEEL, WHEN APPROVED BY THE STRUCTURAL ENGINEER,
SHALL CONFORM TO THE LATEST EDITION OF AMERICAN WELDING SOCIETY
STANDARD D1.4. ELECTRODES FOR SHOP AND FIELD WELDING OF REINFORCING
STEEL SHALL CONFORM TO ASTM A233, CLASS E90XX.
EPOXY-COATED REINFORCING STEEL
EPOXY COATED REINFORCING STEEL SHALL CONFORM TO ASTM A775 AND SHALL BE
USED ONLY WHERE SHOWN OR NOTED ON THE DRAWINGS.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185.
FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND LAPPED A MINIMUM OF ONE SPACE
PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED AS FOLLOWS, UNLESS NOTED OTHERWISE:
SLABS ON METAL DECK: 3/4 INCH DOWN FROM TOP OF SLAB.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH
UNIQUE MIX DESIGN ON EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS. EACH
SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT
28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION
OF THE STRUCTURAL ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS
AFTER CASTING UNLESS DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER.
THIS SET OF TEST CYLINDERS SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES
DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN
ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED.
THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED
UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL CURING BOXES
ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER,
READY-MIX SUPPLIER AND CONTRACTOR WITHIN 24 HOURS AFTER TESTING.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN
ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED,
NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA
SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS.
GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF 5,000 PSI IN
28 DAYS.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO
THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST
EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR
STEEL BUILDINGS AND BRIDGES, LATEST EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE
SHAPES SHALL CONFORM TO ASTM A36, UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED
OTHERWISE.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL
JOINTS USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL
ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED
CONNECTIONS FOR STRUCTURAL STEEL MEMBERS SHALL BE MADE WITH 3/4"
DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE. BOLTED CONNECTIONS SHALL BE
TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED CONNECTIONS IN
BRACE ELEMENTS ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN
WELDING SOCIETY'S STRUCTURAL WELDING CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE
WITH E70XX LOW HYDROGEN ELECTRODES. UNLESS OTHERWISE SHOWN OR NOTED
ON THE DRAWINGS, OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD
E70XX ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A
RUST-INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM
SPECIFIED BY THE ARCHITECT. COORDINATE FINISH PAINTING REQUIREMENTS
WITH THE ARCHITECT.
ALL STRUCTURAL STEEL SHALL BE SHOP PRIMED.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN
CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN
ARCHITECTURAL FINISH COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE.
FOR PAINTED STEEL, USE A PRIMER EQUIVALENT TO THE SHOP PAINT.
FOR GALVANIZED STEEL, USE A ZINC-RICH COLD-GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION
AND MANUAL OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE
DRAWINGS, DESIGN BEAM CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A
10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF
BOLTS, UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.
STEEL FLOOR DECK
PROVIDE AND ERECT STEEL DECK IN ACCORDANCE WITH THE LATEST EDITION OF THE
STEEL DECK INSTITUTE'S SPECIFICATIONS AND CODE OF STANDARD PRACTICE.
DECK MANUFACTURER SHALL PROVIDE ALL FLOOR DECK ACCESSORIES, SUCH AS
EDGE FORMS, CLOSURES, FILLERS AND POUR STOPS FOR A COMPLETE INSTALLATION,
WHETHER OR NOT SUCH ITEMS ARE DETAILED ON THE CONTRACT DOCUMENTS.
FASTEN FLOOR DECK TO STEEL SUPPORTS AS INDICATED ON THE DRAWINGS.
PERFORM WELDING IN ACCORDANCE WITH ANSI/AWS D1.3.
STEEL FLOOR DECK IS INTENDED TO BE INSTALLED IN AN UNSHORED CONDITION
UNLESS NOTED OTHERWISE. DECK SUPPLIER SHALL REVIEW ALL SPAN CONDITIONS
AND CONFIRM THAT THE SUPPLIED PRODUCT IS SUFFICIENT TO SAFELY SUPPORT THE
WET WEIGHT OF CONCRETE AND ASSOCIATED CONSTRUCTION LIVE LOADS WITHOUT
THE NEED FOR SHORING.
FLOOR DECK UNITS SHALL BE INSTALLED IN A MINIMUM THREE SPAN CONDITION WHERE
POSSIBLE.
PROVIDE INTERIOR STEEL FLOOR DECK WITH FINISH AS INDICATED ON THE DRAWINGS.
PROVIDE FLOOR DECK WITH A GALVANIZED FINISH IN ACCORDANCE WITH ASTM A924 G90.
ARCHITECTURAL PRECAST PANELS
SUPPLIER OF ARCHITECTURAL PRECAST PANELS IS RESPONSIBLE FOR THE DESIGN
AND DETAILING OF THE PANELS AND CONNECTIONS.
STEEL REQUIRED TO TRANSMIT THE GRAVITY AND/OR LATERAL LOADS TO THE
STRUCTURE NOT DETAILED ON THE STRUCTURAL DRAWINGS IS THE RESPONSIBILITY
OF THE PRECAST SUPPLIER TO DESIGN AND DETAIL.
GRAVITY CONNECTIONS SHALL NOT BE MADE TO BEAMS, JOISTS, OR JOIST GIRDERS
WITHOUT PERMISSION OF THE STRUCTURAL ENGINEER, UNLESS SPECIFICALLY
SHOWN ON THE DRAWINGS.
PRECAST CONCRETE SPANDREL PANELS SHALL NOT BE ERECTED AT ANY LEVEL
PRIOR TO PLACEMENT OF FLOOR OR ROOF DECK ON THAT LEVEL.
CONCRETE SLABS ON METAL DECK
UNLESS INDICATED OTHERWISE ON THE DRAWINGS, CONCRETE SLABS ON METAL
DECK SHALL BE PLACED AS REQUIRED TO MAINTAIN A CONSTANT
SLAB ELEVATION.
CONTRACTOR SHALL ALLOW FOR THE DEFLECTION OF THE FLOOR ASSEMBLY DUE TO
THE WET WEIGHT OF THE CONCRETE WHEN CALCULATING CONCRETE QUANTITIES
AND SHALL INCLUDE THE COST OF ALL REQUIRED SLAB-ON-DECK CONCRETE IN THE
BID PRICE.
PRIOR TO PLACEMENT OF CONCRETE SLABS ON METAL DECK, THE CONTRACTOR
SHALL CAREFULLY REVIEW THE ELEVATIONS OF THE STRUCTURAL STEEL FRAMING,
INCLUDING CAMBERED MEMBERS, FOR CONFORMANCE WITH THE CONSTRUCTION
DOCUMENTS. CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY
DISCREPANCIES (SUCH AS IMPROPER CAMBER, IMPROPER STEEL ELEVATIONS, ETC.)
IMMEDIATELY AND SHALL NOT BEGIN CONCRETE PLACEMENT WITHOUT PRIOR
REVIEW BY THE STRUCTURAL ENGINEER.
ACTUAL CONCRETE SLAB THICKNESS SHALL NOT BE LESS THAN THE INDICATED
NOMINAL THICKNESS AT ANY LOCATION. IF ANY CONDITION IS DISCOVERED THAT
WOULD PREVENT PLACEMENT OF CONCRETE TO THE NOMINAL THICKNESS;
CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IMMEDIATELY AND SHALL
NOT PROCEED WITH CONCRETE PLACEMENT WITHOUT PRIOR REVIEW BY THE
STRUCTURAL ENGINEER.
SLABS ON METAL DECK SHALL RECEIVE A SMOOTH TROWEL FINISH, AND BE PLACED
TO ACHIEVE THE FOLLOWING MINIMUM TOLERANCES:
OVERALL VALUES: FF = 25
LOCAL VALUES: FF = 20
PLACE CONCRETE IN A MANNER SO AS TO PREVENT SEGREGATION OF THE MIX.
DELAY FLOATING AND TROWELING OPERATIONS UNTIL THE CONCRETE HAS LOST
SURFACE WATER SHEEN OR ALL FREE WATER. DO NOT SPRINKLE FREE CEMENT ON
THE SLAB SURFACE.
PROVIDE CURING OF CONCRETE SLABS IMMEDIATELY AFTER FINISHING USING A
SPRAYED ON DISSIPATING-RESIN LIQUID CURING COMPOUND CONFORMING TO
ASTM C309. ALL SCUFFS OR ABRASIONS TO THE CURING MEMBRANE SHALL BE
RECOATED DAILY. OTHER CURING METHODS MAY BE USED WITH APPROVAL BY THE
STRUCTURAL ENGINEER.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND
SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE
LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 301, ACI 315, ACI 318 AND
ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE
THE FOLLOWING MINIMUM CONCRETE COVER OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT
UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR APPROVED BY THE
STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE
STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT
CORNERS AND INTERSECTIONS OF ALL WALLS, WALL FOOTINGS AND GRADE BEAMS,
UNLESS NOTED OTHERWISE. LAP SPLICE CORNER BARS WITH STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE)
AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE
BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
DESIGN DATA
THE BUILDING STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE
2012 INTERNATIONAL BUILDING CODE.
SEE LOAD MAPS FOR FLOOR LOADING CRITERIA.
SNOW LOAD DESIGN DATA
1. GROUND SNOW LOAD (PG) = 15 PSF
2. LOW-SLOPE ROOF SNOW LOAD (PF) = 17.6 PSF (WITH 5 PSF RAIN-ON-SOW)
3. SNOW EXPOSURE FACTOR (CE) = 1.0
4. THERMAL FACTOR (CT) = 1.2
5. SNOW LOAD IMPORTANCE FACTOR (IS) = 1.0
WIND LOAD DESIGN DATA
1. BASIC WIND SPEED (3-SECOND GUST) = 115 MPH
2. WIND OCCUPANCY/RISK CATEGORY = II
3. WIND EXPOSURE = B
4. WIND DESIGN PRESSURE (P) = VARIES WITH HEIGHT AND LOCATION
EARTHQUAKE DESIGN DATA
1. SHORT PERIOD SPECTRAL RESPONSE (SS) = 0.152
2. 1-SECOND SPECTRAL RESPONSE (S1) = 0.076
3. SEISMIC OCCUPANCY/RISK CATEGORY = II
4. SEISMIC DESIGN CATEGORY = A
5. SITE CLASSIFICATION = C
6. SHORT PERIOD SPECTRAL RESPONSE COEFFICIENT (SDS) = 0.122
7. 1-SECOND SPECTRAL RESPONSE COEFFICIENT (SD1) = 0.086
8. BASIC STRUCTURAL SYSTEM / SEISMIC RESISTING SYSTEM: BEARING WALL /
INTERMEDIATE PRECAST SHEAR WALL
9. ANALYSIS PROCEDURE UTILIZED = EQUIVALENT LATERAL FORCE PROCEDURE
10. RESPONSE MODIFICATION COEFFICIENT (R) = 4.0
11. SEISMIC RESPONSE COEFFICIENT (CS) = 0.01
*SDC A BASED ON SECTION 11.6 OF ASCE 7-10. CS OF 0.01 BASED ON
SECTION 1.4 OF ASCE 7-10.
GLASS CURTAIN WALLS
SUPPLIER OF GLASS CURTAIN WALL IS RESPONSIBLE FOR THE DESIGN, DETAILING
AND INSTALLATION OF THE CURTAIN WALL SYSTEM.
STEEL REQUIRED TO TRANSMIT THE GRAVITY AND/OR LATERAL LOADS TO THE
STRUCTURE NOT DETAILED ON THE STRUCTURAL DRAWINGS IS THE RESPONSIBILITY
OF THE CURTAIN WALL SUPPLIER TO DESIGN, DETAIL AND INSTALL.
CONNECTIONS TO TRANSMIT LATERAL LOADS TO THE STRUCTURE SHALL NOT BE
MADE TO THE BOTTOM FLANGES OF BEAMS, BOTTOM CHORDS OF JOIST GIRDERS OR
BOTTOM CHORDS OF JOISTS WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER.
WHERE KNEE WALLS ARE PRESENT UNDER THE GLASS CURTAIN WALL SYSTEM THE
VERTICAL MULLIONS SHALL NOT STOP AT THE TOP OF THE KNEE WALL BUT SHALL
EXTEND DOWN TO THE STRUCTURE AND THE DESIGN SHALL NOT ASSUME THE KNEE
WALL BRACES THE CURTAIN WALL.
ELEVATORS
CONTRACTOR SHALL COORDINATE ELEVATOR PITS, SHAFTS, SLAB OPENINGS,
FRAMING LOCATIONS, GUIDE RAIL SUPPORTS, DIVIDER BEAMS, HOIST BEAMS AND
SUMP PITS WITH ELEVATOR SUPPLIER PRIOR TO CONSTRUCTION AS REQUIRED FOR
PROPER INSTALLATION AND OPERATION.
COORDINATE ANY REQUIRED STRUCTURAL MODIFICATIONS WITH THE STRUCTURAL
ENGINEER PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY STRUCTURAL
ELEMENTS.
12/31/2014
028171
SEAL
N O
R
TH
CAROLIN
A
D O
N A L D G . C O R S
O
NE NG IN E E
R
P R
O
FESS ION
A L
Drawing TitleDrawing TitleDrawing TitleDrawing Title
Approved for Design Concept:Approved for Design Concept:Approved for Design Concept:Approved for Design Concept:
Project TitleProject TitleProject TitleProject Title
DateDateDateDate
LocationLocationLocationLocation
Checked By:Checked By:Checked By:Checked By:
Building NumberBuilding NumberBuilding NumberBuilding Number
Project NumberProject NumberProject NumberProject Number
Drawing NumberDrawing NumberDrawing NumberDrawing Number
Drawn By:Drawn By:Drawn By:Drawn By:
Revisions:Revisions:Revisions:Revisions: DateDateDateDate
PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:
Durham VAMCDurham VAMCDurham VAMCDurham VAMC
Bldg 33Bldg 33Bldg 33Bldg 33 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
1111 2222 3333 4444 5555 6666 7777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
OFFICE OFOFFICE OFOFFICE OFOFFICE OF
FACILITIESFACILITIESFACILITIESFACILITIES
MANAGEMENTMANAGEMENTMANAGEMENTMANAGEMENT
VA Project NumberVA Project NumberVA Project NumberVA Project Number
Structural
AMERICAN
STRUCTUREPOINT
7260 Shadeland Station Indianapolis, IN 46256
Tele: 317-547-5580
MEP Engineer
APOGEE
CONSULTING GROUP
7330 Chapel Hill Road, Suite 202 Raleigh, NC 27607
Tele: 919-858-7420
Civil Engineer
GUIDON DESIGN
INC.
905 N. Capitol Ave.
Suite 100 Indianapolis, IN 46204
Tele: 317-800-6388
Functional Design
CARL WALKER INC.
14045 Ballantyne Corp.
Place, Suite 380 Charlotte, NC 28277
Tele: 704-716-8000
MICHAEL JAKUBIAKMICHAEL JAKUBIAKMICHAEL JAKUBIAKMICHAEL JAKUBIAK
PROJECT ENGINEERPROJECT ENGINEERPROJECT ENGINEERPROJECT ENGINEER
919-286-0411919-286-0411919-286-0411919-286-0411
Department of Veterans Affairs
558-318558-318558-318558-318
C R e v it \R e v it S tr u c tu re
\2
S
T V
A D u rh a m
P G
C
E N
T R
A L R
S T
R b c u rt s .r v t
BID SETBID SETBID SETBID SET
SI002SI002SI002SI002
BGCBGCBGCBGCJAPJAPJAPJAP
STRUCTURALSTRUCTURALSTRUCTURALSTRUCTURAL
GENERAL NOTESGENERAL NOTESGENERAL NOTESGENERAL NOTES
12/31/201412/31/201412/31/201412/31/2014
2013.001882013.001882013.001882013.00188
A/E SERVICES PARKINGA/E SERVICES PARKINGA/E SERVICES PARKINGA/E SERVICES PARKING
STRUCTURESTRUCTURESTRUCTURESTRUCTUREVA Durham VAMCVA Durham VAMCVA Durham VAMCVA Durham VAMC
Dept. of Veterans AffairsDept. of Veterans AffairsDept. of Veterans AffairsDept. of Veterans Affairs 508 Fulton Street508 Fulton Street508 Fulton Street508 Fulton Street Durham, NC 27705Durham, NC 27705Durham, NC 27705Durham, NC 27705
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE HILTI “KWIK BOLT TZ” OR AN EQUIVALENT SUBSTITUTE
APPROVED BY THE STRUCTURAL ENGINEER, UNO.
ANCHOR FINISH SHALL BE CARBON STEEL FOR INTERIOR EXPOSURES AND AISI 316
STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER’S REPRESENTATIVE.
ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR MASONRY UNTIL IT HAS ATTAINED
ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE STRENGTH.
ADHESIVE ANCHORS FOR SOLID SUBSTRATES
ADHESIVE ANCHORS FOR SOLID SUBSTRATES SHALL BE HILTI "HIT-HY 200" OR AN
EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNO.
ANCHORS SHALL BE ASTM A36 THREADED RODS FOR INTERIOR EXPOSURES AND AISI 316
STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
ADHESIVE ANCHORS SHALL NOT BE INSTALLED IN CONCRETE OR MASONRY UNTIL IT HAS
ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE STRENGTH.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
ADHESIVE ANCHORS FOR HOLLOW SUBSTRATES
ADHESIVE ANCHORS FOR HOLLOW SUBSTRATES SHALL BE HILTI "HIT-HY 70" WITH HILTI
“HIT-SC” SCREEN TUBE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL
ENGINEER, UNO.
ANCHORS SHALL BE ASTM A36 THREADED RODS FOR INTERIOR EXPOSURES AND AISI 316
STAINLESS STEEL FOR EXTERIOR AND BELOW GRADE EXPOSURES, UNO.
ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
REQUIREMENTS BY INSTALLERS TRAINED BY THE MANUFACTURER'S REPRESENTATIVE.
SEPARATION OF DISSIMILAR METALS
DISSIMILAR METALS SHALL BE ELECTRICALLY ISOLATED TO PREVENT GALVANIC
CORROSION VIA NON-CONDUCTIVE WASHERS, GASKETS, COATINGS, OR EQUIVALENT
SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNO.
PRECAST PLANKS
DESIGN AND INSTALL PRECAST PLANKS IN ACCORDANCE WITH ACI 318
AND THE PCI DESIGN HANDBOOK, CURRENT EDITIONS. DESIGN FOR LOADS INDICATED
ON THE DRAWINGS.
PROVIDE OPENINGS (AND OPENING FRAMING WHERE REQUIRED) FOR ALL
PENETRATIONS. REFER TO THE MECHANICAL DRAWINGS FOR MECHANICAL
PENETRATIONS AND COORDINATE FINAL LOCATIONS AND SIZES WITH THE
MECHANICAL CONTRACTOR.
STRUCTURAL PRECAST CONCRETE (GENERAL)
SUPPLIER OF STRUCTURAL PRECAST CONCRETE IS RESPONSIBLE FOR THE DESIGN,
DETAILING, AND INSTALLATION OF THE PRECAST MEMBERS AND CONNECTIONS. DESIGN
AND INSTALL PANELS IN ACCORDANCE WITH ACI 318 AND THE PCI DESIGN HANDBOOK,
CURRENT EDITIONS. MANUFACTURE IN ACCORDANCE WITH MANUAL FOR QUALITY
CONTROL FOR PLANTS AND PRODUCTION OF STRUCTURAL PRECAST CONCRETE
PRODUCTS (PCI MNL 116).
THE PRECAST SUPPLIER SHALL ENGAGE A PROFESSIONAL ENGINEER LICENSED IN THE
STATE WHERE THE PROJECT IS CONSTRUCTED TO PERFORM THE DESIGN.
PRECAST SUPPLIER IS RESPONSIBLE FOR TEMPORARY BRACING, GUYS, TIEDOWNS,
DEADMEN, ETC. AS REQUIRED TO SUPPORT STRUCTURAL PRECAST UNTIL THE STRUCTURAL
FRAMING SYSTEM AND DECKING INSTALLATION ARE COMPLETE AND FINAL STABILITY IS
ACHIEVED.
CONTRACTOR SHALL DESIGN ALL PRECAST MEMBERS AND ERECTION ASSEMBLIES FOR
DESIGN AND TEMPORARY ERECTION FORCES, ERECTION SEQUENCING, GUY STAYING AND
SHORING. CONTRACTOR SHALL CONFIRM ALL APPROPRIATE CONNECTIONS ARE
COMPLETED AND REQUIRED GROUTING HAS OCCURRED TO ENSURE STABILITY DURING
CONSTRUCTION BEFORE ERECTING STRUCTURE VERTICALLY.
EMBEDS AND OTHER STEEL ITEMS TO BE EMBEDDED IN THE PRECAST ARE TO BE
PROVIDED AND INSTALLED BY THE PRECASTER, UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL ITEMS TO BE FIELD WELDED TO EMBEDDED ITEMS IN THE PRECAST
ARE TO BE PROVIDED AND INSTALLED BY THE STEEL FABRICATOR, UNLESS NOTED
OTHERWISE.
EMBEDS AND OTHER ITEMS TO BE EMBEDDED IN CAST-IN-PLACE CONCRETE SHALL BE
SUPPLIED BY THE PRECASTER AND INSTALLED BY THE CONCRETE CONTRACTOR, UNLESS
NOTED OTHERWISE.
IF THE DETAILS INDICATED ON THESE DRAWINGS NEED TO BE MODIFIED TO
ACCOMMODATE THE PRECAST SUPPLIER'S FABRICATION OR INSTALLATION STANDARDS,
THE PRECASTER MUST INFORM THE STRUCTURAL ENGINEER AND ALL AFFECTED
FABRICATORS AND CONTRACTORS PRIOR TO FABRICATION OF AFFECTED MATERIALS.
MODIFICATIONS REQUESTED BY THE PRECASTER AFTER THE AFFECTED ITEMS ARE
FABRICATED SHALL BE SOLELY THE RESPONSIBILITY OF THE PRECASTER (INCLUDING
ENGINEERING, MATERIAL AND INSTALLATION) AND SHALL BE PROVIDED AT NO ADDITIONAL
COST TO THE PROJECT.
COORDINATE ALL OPENINGS, REVEALS, DRIP EDGES, BLOCKOUTS, INSERTS, ETC TO BE
CAST INTO PRECAST MEMBERS WITH STRUCTURAL, ARCHITECTURAL, MECHANICAL, AND
ELECTRICAL DRAWINGS. AS PART OF THE SUBMITTAL PROCESS COORDINATION OF EXACT
SIZES IS REQUIRED AND SHALL BE PERFORMED BY THE CONTRACTOR.
PRECASTER SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION TO
ENSURE PROPER FIT UP OF NEW CONSTRUCTION WITH EXISTING CONSTRUCTION.
LOAD BEARING PRECAST CONCRETE WALL PANELS
LOAD BEARING PRECAST WALL PANELS ARE USED TO SUPPORT GRAVITY AND
LATERAL LOADS. PRECAST PANELS ARE TO BE DESIGNED FOR THE REACTIONS
AND LOAD INFORMATION INDICATED ON THE DRAWINGS AND IN ACCORDANCE WITH
THE GOVERNING BUILDING CODE.
CONCRETE CONSTRUCTION SPECIAL INSPECTION REQUIREMENTS
INSPECTION REQUIREMENTS
1. INSPECTION OF REINFORCING STEEL, INCLUDING
PRESTRESSED TENDONS, AND PLACEMENT.
FREQUENCY
OF
INSPECTION
REFERENCE
STANDARD
CODE (IBC)
REFERENCE
PERIODIC ACI 318: 3.5, 7.1-7.7 1913.4
2. INSPECTION OF REINFORCING STEEL WELDING.
SEE IBC TABLE
1704.3, ITEM 5B
AWS D1.4, ACI 318: 3.5.2 ___
3. INSPECT BOLTS TO BE INSTALLED IN CONCRETE PRIOR
TO AND DURING PLACEMENT OF CONCRETE WHERE
ALLOWABLE LOADS HAVE BEEN INCREASED.
CONTINUOUS ___ 1911.5
4. VERIFYING USE OF REQUIRED DESIGN CONCRETE MIX. PERIODIC ACI 318: CH. 4, 5.2-5.4 1904.2.2, 1913.2, 1913.3
5. AT THE TIME FRESH CONCRETE IS SAMPLED TO
FABRICATE SPECIMENS FOR STRENGTH TESTS, PERFORM
SLUMP AND AIR CONTENT TESTS, AND DETERMINE
THE TEMPERATURE OF THE CONCRETE.
CONTINUOUS
ASTM C31, ASTM C172,
ACI 318: 5.6, 5.8
1913.10
6. INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT
FOR PROPER APPLICATION TECHNIQUES.
CONTINUOUS ACI 318: 5.9, 5.10 1913.6, 1913.7, 1913.8
7. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES.
PERIODIC ACI 318: 5.11-5.13 1913.9
8. INSPECTION OF PRESTRESSED CONCRETE.
A. APPLICATION OF PRESTRESSING FORCES.
B. GROUTING OF BONDED PRESTRESSING TENDONS
IN THE SEISMIC-FORCE RESISTING SYSTEM.
CONTINUOUS ACI 318: 18.20
ACI 318: 18.18.4
9. ERECTION OF PRECAST CONCRETE MEMBERS. PERIODIC ACI 318: CH. 16 ___
11. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR
TO STRESSING OF TENDONS IN POST-TENSIONED
CONCRETE AND PRIOR TO REMOVAL OF SHORES AND
FORMS FROM BEAMS AND STRUCTURAL SLABS.
PERIODIC ACI 318: 6.2 ___
12. INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED.
PERIODIC ACI 318: 6.1.1 ___
10. INSPECTION OF EMBEDED ITEMS (FOR PRECAST ATTACHMENT)
PRIOR TO CAST-IN-PLACE CONCRETE PLACEMENT.
CONTINUOUS ACI 318: CH. 16 ___
INSPECTION REQUIREMENTS
STEEL CONSTRUCTION
SPECIAL INSPECTION REQUIREMENTS
FREQUENCY
OF INSPECTION
REFERENCED
STANDARD
CODE (IBC)
REFERENCE
1. MATERIAL VERIFICATION OF HIGH-STRENGTH
BOLTS, NUTS, AND WASHERS.
PERIODIC
PERIODIC
APPLICABLE ASTM
MATERIAL SPECS
AISC 360
SECTION A3.3
A. VERIFY IDENTIFICATION MARKS CONFORM
TO ASTM STANDARDS SPECIFIED IN THE
APPROVED CONSTRUCTION DOCUMENTS
B. MANUFACTURER'S CERTIFICATE
OF COMPLIANCE
2. INSPECTION OF HIGH-STRENGTH BOLTING
A. BEARING-TYPE CONNECTIONS
B. SLIP-CRITICAL CONNECTIONS
PERIODIC
CONTINUOUS
AISC 360
SECTION M2.5
AISC 360
SECTION M2.5
1704.3.3
1704.3.3
3. MATERIAL VERIFICATION OF STRUCTURAL
STEEL.
A. VERIFY IDENTIFICATION MARKS CONFORM
TO ASTM STANDARDS SPECIFIED IN THE
APPROVED CONSTRUCTION DOCUMENTS
B. MANUFACTURER'S CERTIFIED MILL TEST
REPORTS
ASTM A6 OR A568
ASTM A6 OR A568
1708.4
1708.4
4. MATERIAL VERIFICATION OF WELD FILLER
MATERIALS.
A. VERIFY IDENTIFICATION MARKS CONFORM
TO AWS SPECIFICATION INDICATED IN THE
APPROVED CONSTRUCTION DOCUMENTS
B. MANUFACTURER'S CERTIFICATE
OF COMPLIANCE
---AISC 360
SECTION A3.5
5. INSPECTION OF WELDING:
A. STRUCTURAL STEEL
1. COMPLETE AND PARTIAL
PENETRATION GROOVE WELDS
3. SINGLE-PASS FILLET WELDS
(GREATER THAN 5/16")
2. MULTI-PASS FILLET WELDS
4. SINGLE-PASS FILLET WELDS
(NOT TO EXCEED 5/16")
5. DECK WELDS
B. REINFORCING STEEL
1. VERIFICATION OF WELDABILITY OF
REINFORCING STEEL OTHER THAN
ASTM A706.
2. REINFORCING STEEL RESISTING
FLEXURAL AND AXIAL FORCES IN
INTERMEDIATE AND SPECIAL
MOMENT FRAMES, AND BOUNDARY
ELEMENTS OF SPECIAL REINF
CONCRETE SHEAR WALLS, AND
SHEAR REINFORCEMENT.
3. SHEAR REINFORCEMENT
4. OTHER REINFORCING STEEL
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
CONTINUOUS
PERIODIC
PERIODIC
PERIODIC
PERIODIC
AWS D1.1 (UNO)
AWS D1.3
AWS D1.4
ACI 318: 3.5.2
1704.3.1
6. INSPECTION OF STEEL FRAME JOINT DETAILS
FOR COMPLIANCE WITH APPROVED
CONSTRUCTION DOCUMENTS.
A. BRACING AND STIFFENER DETAILS
B. MEMBER LOCATIONS
C. APPLICATION OF JOINT DETAILS AT EACH
CONNECTION
PERIODIC
PERIODIC
PERIODIC
--- 1704.3.2
12/31/2014
028171
SEAL
N O
R
TH
CAROLIN
A
D O
N A L D G . C O R S
O
NE NG IN E E
R
P R
O
FESS ION
A L
Drawing TitleDrawing TitleDrawing TitleDrawing Title
Approved for Design Concept:Approved for Design Concept:Approved for Design Concept:Approved for Design Concept:
Project TitleProject TitleProject TitleProject Title
DateDateDateDate
LocationLocationLocationLocation
Checked By:Checked By:Checked By:Checked By:
Building NumberBuilding NumberBuilding NumberBuilding Number
Project NumberProject NumberProject NumberProject Number
Drawing NumberDrawing NumberDrawing NumberDrawing Number
Drawn By:Drawn By:Drawn By:Drawn By:
Revisions:Revisions:Revisions:Revisions: DateDateDateDate
PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:PROJECT LEADER/ARCHITECT:
Durham VAMCDurham VAMCDurham VAMCDurham VAMC
Bldg 33Bldg 33Bldg 33Bldg 33 o n e e ig h th in c h o n e fo o t 1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
BBBB
AAAA
CCCC
DDDD
EEEE
FFFF
1111 2222 3333 4444 5555 6666 7777 9999
FFFF
EEEE
DDDD
CCCC
BBBB
AAAA
99997777 8888666655554444333322221111
905 N. CAPITOL AVE. SUITE 100 INDIANAPOLIS, IN 46204
317.800.6388 WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
OFFICE OFOFFICE OFOFFICE OFOFFICE OF
FACILITIESFACILITIESFACILITIESFACILITIES
MANAGEMENTMANAGEMENTMANAGEMENTMANAGEMENT
VA Project NumberVA Project NumberVA Project NumberVA Project Number
Structural
AMERICAN
STRUCTUREPOINT
7260 Shadeland Station Indianapolis, IN 46256
Tele: 317-547-5580
MEP Engineer
APOGEE
CONSULTING GROUP
7330 Chapel Hill Road, Suite 202 Raleigh, NC 27607
Tele: 919-858-7420
Civil Engineer
GUIDON DESIGN
INC.
905 N. Capitol Ave.
Suite 100 Indianapolis, IN 46204
Tele: 317-800-6388
Functional Design
CARL WALKER INC.
14045 Ballantyne Corp.
Place, Suite 380 Charlotte, NC 28277
Tele: 704-716-8000
MICHAEL JAKUBIAKMICHAEL JAKUBIAKMICHAEL JAKUBIAKMICHAEL JAKUBIAK
PROJECT ENGINEERPROJECT ENGINEERPROJECT ENGINEERPROJECT ENGINEER
919-286-0411919-286-0411919-286-0411919-286-0411
Department of Veterans Affairs
558-318558-318558-318558-318
C R e v it \R e v it S tr u c tu re
\2
S
T V
A D u rh a m
P G
C
E N
T R
A L R
S T
R b c u rt s .r v t
BID SETBID SETBID SETBID SET
SI003SI003SI003SI003
BGCBGCBGCBGCJAPJAPJAPJAP
SPECIAL INSP.SPECIAL INSP.SPECIAL INSP.SPECIAL INSP.
NOTES ANDNOTES ANDNOTES ANDNOTES AND
TABLESTABLESTABLESTABLES
12/31/201412/31/201412/31/201412/31/2014
2013.001882013.001882013.001882013.00188
A/E SERVICES PARKINGA/E SERVICES PARKINGA/E SERVICES PARKINGA/E SERVICES PARKING
STRUCTURESTRUCTURESTRUCTURESTRUCTUREVA Durham VAMCVA Durham VAMCVA Durham VAMCVA Durham VAMC
Dept. of Veterans AffairsDept. of Veterans AffairsDept. of Veterans AffairsDept. of Veterans Affairs 508 Fulton Street508 Fulton Street508 Fulton Street508 Fulton Street Durham, NC 27705Durham, NC 27705Durham, NC 27705Durham, NC 27705
SPECIAL INSPECTION
SPECIAL INSPECTION IS A MANDATORY REQUIREMENT OF THE GENERAL
CONTRACTOR FOR VERIFYING CONFORMANCE OF THE INDICATED CONSTRUCTION.
SPECIAL INSPECTION IS REQUIRED IN ADDITION TO ALL MATERIAL TESTS AND
INSPECTIONS IDENTIFIED ELSEWHERE IN THE CONSTRUCTION DOCUMENTS.
THE CONTRACTOR SHALL EMPLOY INDEPENDENT AGENCY(IES) OR
INDIVIDUAL(S) TO PROVIDE SPECIAL INSPECTION FOR ITEMS AS INDICATED ON THE
DRAWINGS.
THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON, WHO SHALL
DEMONSTRATE COMPETENCE, TO THE SATISFACTION OF THE BUILDING OFFICIAL AND
THE STRUCTURAL ENGINEER, FOR INSPECTION OF EACH PARTICULAR TYPE OF
CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION.
“PERIODIC” SPECIAL INSPECTION IS DEFINED AS “THE PART-TIME OR INTERMITTENT
OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL
INSPECTOR WHO IS PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS BEING
PERFORMED AND AT THE COMPLETION OF THE WORK.”
“CONTINUOUS” SPECIAL INSPECTION IS DEFINED AS “THE FULL-TIME OBSERVATION OF
WORK REQUIRING SPECIAL INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO
IS PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.”
THE CONTRACTOR SHALL SUBMIT TO THE STRUCTURAL ENGINEER FOR
REVIEW A MINIMUM OF 14 DAYS PRIOR TO COMMENCEMENT OF CONSTRUCTION OF
ELEMENTS REQUIRING SPECIAL INSPECTION THE FOLLOWING:
1. NAME(S), ADDRESS(ES), TELEPHONE NUMBER(S), EMAIL ADDRESS(ES), AND
STATEMENT(S) OF QUALIFICATIONS OF ALL SPECIAL INSPECTOR(S) TO BE
ENGAGED ON THE PROJECT.
2. A LISTING OF ALL ITEMS TO RECEIVE SPECIAL INSPECTION, DESIGNATION
WHETHER INSPECTION WILL BE CONTINUOUS OR PERIODIC AND THE NAME OF
THE INDIVIDUAL THAT WILL BE PERFORMING INSPECTION FOR EACH ITEM.
THE CONTRACTOR SHALL COORDINATE WITH THE SPECIAL INSPECTOR SUFFICIENTLY
IN ADVANCE OF WORK REQUIRING SPECIAL…