36C24618R0711-0007003.pdf

PDF 694 KB Posted

Attached to
Renovate Building 2-Medical Surgical 659-17-101
Solicitation number
36C24618R0711
Issued by

About this file

36C24618R0711 0007 659.17.101_M601.pdf

View the file

Other files

File Type Posted
36C24618R0711-0007000.docx DOCX document
36C24618R0711-0007002.pdf PDF
36C24618R0711-0007004.pdf PDF
36C24618R0711-0007001.pdf PDF
36C24618R0711-0005000.docx DOCX document
36C24618R0711-0004002.pdf PDF
36C24618R0711-0004001.pdf PDF
36C24618R0711-0004000.docx DOCX document
36C24618R0711-0004003.pdf PDF
36C24618R0711-0003001.docx DOCX document
36C24618R0711-0002001.pdf PDF
36C24618R0711-0002002.pdf PDF
36C24618R0711-0002000.docx DOCX document
36C24618R0711-00001000.docx DOCX document
S02_-_Drawings_-_659-17-101.pdf PDF
36C24618R0711-014.pdf PDF
36C24618R0711-018.pdf PDF
36C24618R0711-016.pdf PDF
36C24618R0711-015.txt TXT text file
36C24618R0711-017.pdf PDF
36C24618R0711-013.docx DOCX document
36C24618R0711-000.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

www.atriaxgroup.com

Atriax, pllc

102 3rd Avenue, NE

PO Box 1629, Hickory, NC 28603

T: 828.315.9962

F: 828.315.9964

NC Engineering License No.: P-0214

NC Architectural License No.: 51254

8845 RED OAK BLVD.

CHARLOTTE, NC 28217-5593

PHONE: 704.523.2230

FAX: 704.523.2235

www.freemanwhite.com

LeGrand

Engineering, Inc.

215 PARK AVE SE

AIKEN, SC 29801

PHONE: 803.502.0657

FAX: 803.643.4648

www.legrandengineering.com

FINAL CONSTRUCTION DRAWINGS - FULLY SPRINKLERED

8701 RED OAK BLVD. SUITE 500

CHARLOTTE, NC 28217-5593

PHONE: 704.522.0495

FAX: 704.522.0499

www.lrspc.net

I

AIR TERMINAL UNIT SIZING SCHEDULE

SIZE

MIN ALLOWABLE

AIR FLOW

MAX ALLOWABLE

AIR FLOW DUCT INLET SIZE MAX APD

MAXIMUM SOUND POWER LEVEL (Re: 10 -12 WATTS)

FOR BOX DISCHARGE AT MAXIMUM INLET DUCT

STATIC

HOT WATER HEATING COIL

REMARKS

OCTAVE BANDS EAT EWT FLOW MAX WPD PIPE RUNOUT

SIZE TO COIL

CFM [L/s] CFM [L/s] IN [mm] IN WG [Pa] 2 3 4 5 6 7 °F [°C] °F [°C] GPM [L/m] FT [kPa] IN [mm]

A 60 [ 28 ] 170 [ 80 ] 4 [ 100 ] 0.4 [ 100 ] 69 65 58 52 51 47 55 [ 13 ] 140 [ 60 ] 0.5 [ 2 ] 3 [ 9 ] 0.75 [ 19 ] ----

B 90 [ 42 ] 260 [ 120 ] 5 [ 130 ] 0.4 [ 100 ] 69 63 59 52 51 47 55 [ 13 ] 140 [ 60 ] 0.5 [ 2 ] 3 [ 9 ] 0.75 [ 19 ] ----

C 130 [ 61 ] 380 [ 180 ] 6 [ 150 ] 0.4 [ 100 ] 69 67 61 55 52 49 55 [ 13 ] 140 [ 60 ] 0.7 [ 3 ] 4 [ 12 ] 0.75 [ 19 ] ----

D 160 [ 76 ] 490 [ 230 ] 7 [ 180 ] 0.4 [ 100 ] 70 68 63 57 53 49 55 [ 13 ] 140 [ 60 ] 0.7 [ 3 ] 4 [ 12 ] 0.75 [ 19 ] ----

E 230 [ 110 ] 680 [ 320 ] 8 [ 200 ] 0.4 [ 100 ] 71 68 59 53 51 47 55 [ 13 ] 140 [ 60 ] 1 [ 4 ] 3 [ 9 ] 0.75 [ 19 ] ----

F 270 [ 130 ] 790 [ 370 ] 9 [ 230 ] 0.4 [ 100 ] 71 69 60 54 51 47 55 [ 13 ] 140 [ 60 ] 1.5 [ 6 ] 4 [ 12 ] 0.75 [ 19 ] ----

G 350 [ 170 ] 1050 [ 500 ] 10 [ 250 ] 0.4 [ 100 ] 74 68 61 57 54 52 55 [ 13 ] 140 [ 60 ] 1.5 [ 6 ] 4 [ 12 ] 0.75 [ 19 ] ----

H 500 [ 240 ] 1500 [ 710 ] 12 [ 300 ] 0.4 [ 100 ] 73 69 64 59 57 53 55 [ 13 ] 140 [ 60 ] 2.5 [ 10 ] 3 [ 9 ] 0.75 [ 19 ] ----

I 750 [ 350 ] 2250 [ 1100 ] 14 [ 350 ] 0.4 [ 100 ] 73 68 65 61 61 59 55 [ 13 ] 140 [ 60 ] 3.5 [ 13 ] 4 [ 12 ] 0.75 [ 19 ] ----

J 1000 [ 470 ] 3000 [ 1400 ] 16 [ 400 ] 0.4 [ 100 ] 73 68 66 60 58 55 55 [ 13 ] 140 [ 60 ] 4.5 [ 17 ] 4 [ 12 ] 1 [ 25 ] ----

NOTES

1. INLET STATIC BASED ON ARI 885-98.

2. THIS SCHEDULE IS USED WITH THE TERMINAL UNIT SCHEDULE.

3. CONTROL SEQUENCE SHALL BE AS INDICATED ON THE AIR TERMINAL UNIT SCHEDULE.

4. PROVIDE SOUND ATTENUATION AFTER-SECTION AS REQUIRED TO MEET ROOM NC LEVEL.

RADIANT CEILING PANEL SCHEDULE (ELECTRIC )

MARK ROOM

LOCATION

AREA

SERVED

PANEL SIZE CAPACITY POWER SUPPLY

REMARKS

IN [mm] BTUH [W] AMPS PHASE VOLT

2-ERP-1

3013A,3015A,3 017A,3019A,30

86A TLT 24 x 24 [ 610 x 610 ] 1280 [ 380 ] 3.2 1 120 ---

DUCTLESS SPLIT SYSTEM AIR CONDITIONER ELECTRIC SCHEDULE

MARK LOCATION

AREA

AND/OR

BLDG

SERVED

TYPE

TOTAL SUPPLY

AIR FLOW

MIN. OUTSIDE

AIR FLOW

EXT STATIC

PRESSURE

COOLING CAPACITY HEATING CAPACITY

AIR

FILTER

MARK NO

ELECTRICAL DATA

REMARKSMIN TOTAL

CAPACITY

MIN SENS

CAPACITY MIN

SEER

EAT OSA DESIGN

TEMP COMP Kw

GAS MIN. INPUT MIN. NET

OUTPUT

EAT

Db

LAT

Db INDOOR FAN OUTDOOR UNIT FAN

Db Wb CFM [L/s] CFM [L/s] IN [Pa] MBH [kW] MBH [kW] °F [°C] °F [°C] °F [°C] MBH [kW] MBH [kW] °F [°C] °F [°C] MCA [W] ELEC MCA [W] ELEC

2-CC1 CEILING MTD. IT/ELEC

CEILING

CASSETTE 406 [ 190 ] 0 [ ] 0 [ ] 10.8 [ 37 ] 8.4 [ 3 ] 20 80 [ 27 ] 67 [ 19 ] [ 95 ] [ 35 ] 7.5 NA #VALUE! 13.5 [ 4 ] 47 [ 8 ] 50 [ 10 ] NA 0.13 [ 97 ] 208/60/1 0.13 [ 97 ] 208/60/1 COND. UNIT ON 5TH FLR

ROOF

2-WMD1 WALL MTD. IT 3161 DUCTLESS

SPLIT 434 [ 200 ] 0 [ ] 0 [ ] 10.9 [ 37 ] 9.48 [ 3 ] 19 80 67 [ 95 ] [ 35 ] 1.42 NA #VALUE! NA #VALUE! NA NA NA 0.28 [ 210 ] 208/60/1 0.18 [ 130 ] 208/60/1 COND. UNIT ON 3RD FLR

ROOF

MECHANICAL SCHEDULES

M601

HAS GLR

AIR DEVICE SCHEDULE (SUPPLY)

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC DAMPER FINISH REMARKSMIN MAX

IN x IN [mm x mm] IN [mm ] CFM [L/s] CFM [L/s]

IN WG

[Pa]

SD-11 LOUVERED FACE 40 [ 19 ] 160 [ 76 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 6 ø

[152 ø] 19 NONE WHITE ----

SD-12 LOUVERED FACE 70 [ 33 ] 280 [ 130 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø

[203 ø] 23 NONE WHITE -----

SD-13 LOUVERED FACE 110 [ 52 ] 380 [ 180 ] 0.090 [ 23 ] CEILING 24 x 24 [ 600 x 600 ] 10 ø

[254 ø] 22 NONE WHITE -----

SD-14 LOUVERED FACE 160 [ 76 ] 470 [ 220 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 12 ø

[305 ø ] 19 NONE WHITE -----

SD-15 LOUVERED FACE 220 [ 100 ] 640 [ 300 ] 0.090 [ 23 ] CEILING 24 x 24 [ 600 x 600 ] 14 ø [356 ø ] 21 NONE WHITE -----

SD-16 LOUVERED FACE 250 [ 120 ] 740 [ 350 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 16 ø [406 ø ] 22 NONE WHITE -----

SD-51 SUPPLY REGISTER 80 [ 38 ] 120 [ 57 ] 0.100 [ 25 ] CEILING/WALL 8 x 8 [203 x 203] 6 x 6 [152 x 152] 25 OBD WHITE -----

NOTES

1. SEE FLOOR PLAN FOR THROW PATTERN.

2. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.

3. PROVIDE SQUARE TO ROUND ADAPTER.

AIR DEVICE SCHEDULE (LINEAR)

MARK TYPE

AIR FLOW

MAX APD MIN THROW MAX THROW # OF

SLOT

S

SLOT

WIDTH

PANEL/FRAME

SIZE NECK SIZE

THROW

PATTER

N

THROW

TYPE NC DAMPE

R

FINIS

H REMARKS

IN [mm] IN [mm]

MIN MAX

CFM [L/s] CFM [L/s] IN

WG

[Pa] FT [M] FT [M]

IN

[mm]

SD-31 LINEAR 180 [ 85 ] 580 [ 270 ] 0.27 66.70 4 - 7

-15

2.0 - 3.1 - 4.9

17 - 21 -

5.3 - 6.5 -

9.2 2 2 [ 50 ] 24 x 5 [ 600 x 127

] 10 ø [254 ø] 2 WAY VERTICAL 41 NONE WHITE -----

SD-310 LINEAR 50 [ 24 ] 350 [ 170 ] 0.26 63.80 4 - 5 -

1.1 - 1.6 - 3.3

23 - 28 -

6.9 - 8.4 -

11.9 2 1 [ 25 ] 48 x 5 [ 1219 x

127 ] 10 ø [254 ø] 1 WAY VERTICAL 32 NONE WHITE -----

NOTES

1. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.

2. PROVIDE COLLAR AND TRANSITION AS REQUIRED.

AIR DEVICE SCHEDULE (RETURN & EXHAUST)

MARK TYPE

AIR FLOW

MAX APD

MOUNTING

PANEL/FRAME SIZE NECK SIZE

NC DAMPER FINISH REMARKSMIN MAX

CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm] RG-21 PERFORATED 60 [ 28 ] 100 [ 47 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 6 DIAM [ 152 DIAM ] 13 NONE WHITE -----

RG-22 PERFORATED 110 [ 52 ] 170 [ 80 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 8 DIAM [ 203 DIAM ] 13 NONE WHITE -----

RG-23 PERFORATED 170 [ 80 ] 250 [ 120 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 10 DIAM [ 254 DIAM ] 14 NONE WHITE -----

RG-24 PERFORATED 240 [ 110 ] 400 [ 190 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 12 DIAM [ 305 DIAM ] 12 NONE WHITE -----

RG-25 PERFORATED 320

[ 150 ]

[ 240 ] 0.087 22.000 CEILING 24 x 24 [ 600 x 600 ] 14 DIAM [ 356 DIAM ] 14 NONE WHITE -----

RG-26 PERFORATED 420

[ 200 ]

[ 330 ] 0.087 22.000 CEILING 24 x 24 [ 600 x 600 ] 16 DIAM [ 406 DIAM ] 16 NONE WHITE -----

RR-51 RETURN

REGISTER 50 [ 24 ] 160 [ 76 ] 0.078 20.000 CEILING/WALL 8 x 8 [ 203 x 203 ] 6 x 6 [ 152 x 152 ] 12 OBD WHITE -----

RR-52 RETURN

REGISTER 130 [ 61 ] 210 [ 99 ] 0.078 20.000 CEILING/WALL 10 x 10 [ 254 x 254 ] 8 x 8 [ 203 x 203 ] 13 OBD WHITE -----

RR-53 RETURN

REGISTER 200 [ 94 ] 330 [ 160 ] 0.078 20.000 CEILING/WALL 12 x 12 [ 305 x 305 ] 10 x 10 [ 254 x 254 ] 15 OBD WHITE -----

RR-54 RETURN

REGISTER 270 [ 130 ] 440 [ 210 ] 0.078 20.000 CEILING/WALL 14 x 14 [ 356 x 356 ] 12 x 12 [ 305 x 305 ] 17 OBD WHITE -----

RR-55 RETURN

REGISTER 250 [ 120 ] 610 [ 290 ] 0.082 21.000 CEILING/WALL 16 x 16 [ 406 x 406 ] 14 x 14 [ 356 x 356 ] 18 OBD WHITE -----

NOTE

"EG or ER" IS USED IN PLACE OF "RG or RR" FOR AIR DEVICES USED ON EXHAUST SYSTEMS

PROVIDE SQUARE TO ROUND ADAPTER.

SMOKE AND COMBINATION FIRE/SMOKE DAMPER SCHEDULE

MARK LOCATION FAN SYSTEM

SYSTEM

AND/OR

SERVICE

DUCT SIZE DUCT PRESSURE

CLASS

REMARKSIN [mm] IN WG [Pa]

A 3RD FLR ROOF 2-SAF 1&2 2-AHU4 53X20 4 [ 1000 ] SMOKE DAMPER

B 3RD FLR ROOF 2-RAF 1&2 2-AHU-4 53X20 2 [ 500 ] SMOKE DAMPER

C 3RD FLOOR 2-RAF 1&2 2-AHU-4 14X10 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

D 3RD FLOOR 2-SAF 1&2 2-AHU-4 36X12 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER

E 3RD FLOOR 2-RAF 1&2 GENERAL

EXHAUST 30X12 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

F 3RD FLOOR 2-SAF 1&2 2-AHU-4 12X8 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER

G 3RD FLOOR EX. EF-3 2-AHU-4 14X10 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

H 3RD FLOOR 2-SAF 1&2 2-AHU-4 16X14 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER

I 3RD FLOOR 2-SAF 1&2 2-AHU-4 9" ROUND 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER

J 3RD FLOOR 2-RAF 1&2 2-AHU-4 7" ROUND 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

K 3RD FLOOR EX EF-3 GENERAL

EXHAUST 6" ROUND 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

L 3RD FLOOR 2-SAF 1&2 2-AHU-4 8X8 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER

M 3RD FLOOR 2-SAF 1&2 2-AHU-4 6" ROUND 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

N 3RD FLOOR EX. EF-1 GENERAL

EXHAUST 8X6 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

O 3RD FLOOR EX. EF-1 GENERAL

EXHAUST 18X14 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

P 3RD FLOOR EX. EF-1 GENERAL

EXHAUST 18X14 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER

13 17

SINGLE DUCT AIR TERMINAL UNIT SCHEDULE

MARK LOCATION

AREA

AND/OR

ROOM

SERVED

SYSTEM AIR

HANDLING SIZE

AIR FLOW ADDITIONAL

SOUND

ATTUNATION

REQUIRED

CONTROL

TYPE

CONTROL

SEQUENCE

REHEAT PERIMETER

SUPPLEMENTAL

HEAT LINK

REMARKSMAX MIN

CFM [L/s] CFM [L/s] HW (GPM) ELEC NONE

2-TU-4-30 CORRIDOR 3190D 2-AHU4 A 160 [ 76 ] 80 [ 38 ] NONE VAV 5 DEGREE

DEADBAND 0.5 N/A ----

2-TU-4-31 3190G 3190G, 3190H 2-AHU4 C 300 [ 140 ] 150 [ 71 ] NONE VAV 5 DEGREE

DEADBAND 0.5 N/A

2-TU-4-32 CORRIDOR 3190E 2-AHU4 D 420 [ 200 ] 210 [ 99 ] NONE VAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-33 CORRIDOR 3190F, 3190L 2-AHU4 E 540 [ 250 ] 270 [ 130 ] NONE VAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-34 3190J 3190I, 3190J 2-AHU4 C 300 [ 140 ] 190 [ 90 ] NONE VAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-35 3190C 3190C,

3190B, 3091A 2-AHU4 D 405 [ 190 ] 205 [ 97 ] NONE VAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-36 3190K 3190K 2-AHU4 A 135 [ 64 ] 70 [ 33 ] NONE VAV 5 DEGREE

DEADBAND 0.5 N/A

2-TU-4-37 3088 3088, 3089 2-AHU4 C 310 [ 150 ] 155 [ 73 ] NONE VAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-38 CORRIDOR CORRIDOR 2-AHU4 C 350 [ 170 ] 350 [ 170 ] NONE CAV 5 DEGREE

DEADBAND 1.5 N/A

2-TU-4-39 3100 3100 2-AHU4 A 150 [ 71 ] 75 [ 35 ] NONE VAV 5 DEGREE

DEADBAND 0.5 N/A

2-TU-4-40 CORRIDOR 3156, 3154,

CORRIDOR 2-AHU4 C 325 [ 150 ] 325 [ 150 ] NONE CAV 5 DEGREE

DEADBAND 1.5 N/A

2-TU-4-41 3166 3166, 3169,

CORRIDOR 2-AHU4 D 385 [ 180 ] 385 [ 180 ] NONE CAV 5 DEGREE

DEADBAND 1.5 N/A

2-TU-4-42 3087 3087 2-AHU4 B 250 [ 120 ] 250 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-43 3086 3086 2-AHU4 C 270 [ 130 ] 270 [ 130 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-44 3015 3015 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-45 3014 3014 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-46 3013 3013 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-47 3016 3016 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-48 3017 3017 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-49 3018 3018 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-50 3019 3019 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-51 3020 3020 2-AHU4 C 315 [ 150 ] 315 [ 150 ] NONE CAV 5 DEGREE

DEADBAND 1.5 N/A

2-TU-4-52 CORRIDOR 3088A,

CORRIDOR 2-AHU4 B 225 [ 110 ] 225 [ 110 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

2-TU-4-53 CORRIDOR CORRIDOR 2-AHU4 B 175 [ 83 ] 175 [ 83 ] NONE CAV 5 DEGREE

DEADBAND 1 N/A

ADDENDUM A 8/08/18

A

AutoCAD SHX Text Drawing Title

AutoCAD SHX Text Approved: Project Director

AutoCAD SHX Text Project Title

AutoCAD SHX Text Date

AutoCAD SHX Text Location

AutoCAD SHX Text Checked

AutoCAD SHX Text Building Number

AutoCAD SHX Text Project Number

AutoCAD SHX Text Drawing Number

AutoCAD SHX Text Drawn

AutoCAD SHX Text Dwg. of

AutoCAD SHX Text Revisions:

AutoCAD SHX Text Date

AutoCAD SHX Text

CONSULTANTS:

AutoCAD SHX Text

ARCHITECT/ENGINEERS:

AutoCAD SHX Text one eighth inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three inches = one foot

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text one and one half inches = one foot

AutoCAD SHX Text one inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 6"

AutoCAD SHX Text 6"

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three quarters inch = one foot

AutoCAD SHX Text one half inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text three eighths inch = one foot

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text one quarter inch = one foot

AutoCAD SHX Text

VA FORM 08-6231

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Office of Construction and Facilities Management

AutoCAD SHX Text 659-17-101

AutoCAD SHX Text

AutoCAD SHX Text

W.G. HEFNER VAMC

AutoCAD SHX Text

SALISBURY,

AutoCAD SHX Text

NC

AutoCAD SHX Text

RENOVATE BUILDING 2

AutoCAD SHX Text

FOR MEDICAL SURGICAL

AutoCAD SHX Text

MODERNIZATION

AutoCAD SHX Text

MAY 1, 2018

AutoCAD SHX Text

SEAL

AutoCAD SHX Text

SEAL

AutoCAD SHX Text 025013

Sheets and Views