36C24618R0711-0004003.pdf
PDF 19 MB Posted
- Attached to
- Renovate Building 2-Medical Surgical 659-17-101
- Solicitation number
- 36C24618R0711
About this file
36C24618R0711 0004 659.174.101_FINAL Drawings Vol 3.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24618R0711-0007000.docx | DOCX document | |
| 36C24618R0711-0007002.pdf | ||
| 36C24618R0711-0007003.pdf | ||
| 36C24618R0711-0007004.pdf | ||
| 36C24618R0711-0007001.pdf | ||
| 36C24618R0711-0005000.docx | DOCX document | |
| 36C24618R0711-0004002.pdf | ||
| 36C24618R0711-0004001.pdf | ||
| 36C24618R0711-0004000.docx | DOCX document | |
| 36C24618R0711-0003001.docx | DOCX document | |
| 36C24618R0711-0002001.pdf | ||
| 36C24618R0711-0002002.pdf | ||
| 36C24618R0711-0002000.docx | DOCX document | |
| 36C24618R0711-00001000.docx | DOCX document | |
| S02_-_Drawings_-_659-17-101.pdf | ||
| 36C24618R0711-014.pdf | ||
| 36C24618R0711-018.pdf | ||
| 36C24618R0711-016.pdf | ||
| 36C24618R0711-015.txt | TXT text file | |
| 36C24618R0711-017.pdf | ||
| 36C24618R0711-013.docx | DOCX document | |
| 36C24618R0711-000.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC DESIGN DATA
DESIGN CONDITIONS
SUMMER WINTER LOWEST
AVERAGE
ANNUAL
DEWPOINTTEMP WET BULB TEMP
% HUMIDITY
TEMP DEWPOINT TEMP
% HUMIDITY
°F [°C] °F [°C] °F [°C] °F [°C] °F [°C]
OUTDOOR DESIGN
CONDITIONS 92.4 [ 34 ] 77 [ 25 ] 46 18.2 [ -8 ] NA NA NA
INDOOR AREA DESIGN CONDITIONS
SUPPORT SPACES 75 [24] 62 [ 17 ] 50 70 [ 21 ] 37 [ 3 ] 30
PATIENT ROOM 70 [ 21 ] 58 [ 14 ] 50 75 [ 24 ] 41 [ 5 ] 30
OFFICE 75 [ 24 ] 62 [ 17 ] 50 70 [ 21 ] 37 [ 3 ] 30
CORRIDORS 75 [ 24 ] 62 [ 17 ] 50 70 [ 21 ] 37 [ 3 ] 30
MECHANICAL GENERAL NOTES
AND SYMBOL LEGEND
M001
HAS GLR
M001 MECHANICAL GENERAL NOTES, ABBREVIATIONS AND LEGEND
MD103_D THIRD FLOOR PLAN: DEMOLITION DUCTWORK
MD103_P THIRD FLOOR PLAN: DEMOLITION PIPING
MD104 THIRD FLOOR ROOF: DEMOLITION
MH103 THIRD FLOOR PLAN: DUCTWORK
MH104 THIRD FLOOR ROOF: NEW WORK
MP103 THIRD FLOOR PLAN: PIPING
M501 MECHANICAL DETAILS
M502 MECHANICAL DETAILS
M503 MECHANICAL DETAILS
M504 MECHANICAL DETAILS
M505 AIR HANDLING UNIT PLAN - 2-AHU4
M601 MECHANICAL SCHEDULES
M602 MECHANICAL SCHEDULES
M603 MECHANICAL SCHEDULES
MI701 MECHANICAL INSTRUMENTATION AND CONTROLS
MI702 MECHANICAL INSTRUMENTATION AND CONTROLS
01 17
A12
A13
A14
A14 A16
A17
A17
A19
A19
A15
A15
A22
A22
A24 A27A21
A25 A28 A34 A37
A37
A36
A36
A30
A30
A31
A31
A35
A11
A11
A8
A8
A9
A9
A20
A20
337 SF
DAY ROOM
202 SF
OFFICE
168 SF
EXAM
165 SF
OFFICE
109 SF
BREAK
ROOM
51 SF
UTIL
149 SF
OFFICE
193 SF
OFFICE
139 SF
OFFICE
158 SF
OFFICE
130 SF
OFFICE
122 SF
OFFICE
185 SF
CONF. ROOM
121 SF
OFFICE
69 SF
GEN.
STORAGE
256 SF
OFFICE
138 SF
OFFICE
144 SF
OFFICE
106 SF
BREAK
ROOM
75 SF
SUPP
57 SF
CORR
38 SF
ICE
36 SF
EKG
24 SF
SOIL LIN
192 SF
STAIR #5
211 SF
NURSE
STATION
45 SF
STO. 68 SF
STO.
39 SF
TLT. 23 SF
M TLT.
14 SF
STO.
114 SF
LINL
STORAGE
33 SF
F. TLT.
37 SF
MOP
39 SF
ELEC.
35 SF
M TLT.
210 SF
NURSE
STATION
21 SF
L. CHUTE
44 SF
MOP CLOS.
44 SF
MEDICATION.
175 SF
MSCU ISOL
34 SF
TLT.57 SF
STOR
67 SF
STOR
36 SF
F. TLT.
21 SF
TELE
21 SF
LAB STOR. 132 SF
WAITING
41 SF
MOP
27 SF
TLT
6 SF
ELEC.
2 SF
FAC24 SF
ALCOVE
79 SF
DIST. ROOM
200 SF
STAIR #6
145 SF
1-BED
43 SF
TLT.
149 SF
1-BED
42 SF
TLT.
128 SF
1-BED
46 SF
TLT.
184 SF
LOCKER
ROOM
48 SF
TLT 3014
46 SF
TLT
138 SF
1-BED
46 SF
STOR.
136 SF
1-BED
146 SF
1-BED
37 SF
STOR.
41 SF
TLT.
152 SF
1-BED
139 SF
1-BED
46 SF
TLT. 142 SF
1-BED
42 SF
TLT
43 SF
TLT.
396 SF
DIALYSIS
101 SF
STOR.
50 SF
STOR.
145 SF
1-BED 37 SF
CL. UTILITY
148 SF
PAT. RM.
45 SF
PAT. TLT.
178 SF
PAT. RM.
314 SF
WORK ROOM
55 SF
HAC
95 SF
MECH
244 SF
PAT. RM.
54 SF
PAT. TLT
148 SF
EQUIPMENT
STORAGE
130 SF
CLEAN
LINEN
68 SF
STORAGE
EMS
118 SF
NOURISHMENT
STORAGE
260 SF
BARIATRIC
RM.
66 SF
PAT. BATH
54 SF
PAT. BATH
101 SF
EQUIP.
STORAGE
56 SF
HAC
30 SF
CHASE69 SF
BARIATRIC
BATH
245 SF
BARIATRIC
RM.
364 SF
5 BED MSCU
172 SF
STAFF
LOCKER
8 SF
CHARTING
12 SF
FAC
4 SF
FAC
PLAN
NORTH
KEY PLAN
THIRD FLOOR PLAN - DEMOLITION
DUCTWORK
MD103_D
HAS GLR 02 17
A13
A14
A14 A16
A17
A17
A19
A19
A15
A15
A22
A22
A24 A27A21
A25 A28 A34 A37
A37
A36
A36
A30A31 A35
A11
A11
A8
A8
A9
A9
A20
A20
337 SF
DAY ROOM
202 SF
OFFICE
168 SF
EXAM
165 SF
OFFICE
109 SF
BREAK
ROOM
51 SF
UTIL
149 SF
OFFICE
193 SF
OFFICE
139 SF
OFFICE
158 SF
OFFICE
130 SF
OFFICE
122 SF
OFFICE
185 SF
CONF. ROOM
121 SF
OFFICE
69 SF
GEN.
STORAGE
256 SF
OFFICE
138 SF
OFFICE
144 SF
OFFICE
106 SF
BREAK
ROOM
75 SF
SUPP
57 SF
CORR
38 SF
ICE
36 SF
EKG
24 SF
SOIL LIN
192 SF
STAIR #5
211 SF
NURSE
STATION
45 SF
STO. 68 SF
STO.
39 SF
TLT. 23 SF
M TLT.
14 SF
STO.
114 SF
LINL
STORAGE
33 SF
F. TLT.
37 SF
MOP
39 SF
ELEC.
35 SF
M TLT.
210 SF
NURSE
STATION
21 SF
L. CHUTE
44 SF
MOP CLOS.
44 SF
MEDICATION.
175 SF
MSCU ISOL
34 SF
TLT.57 SF
STOR
67 SF
STOR
36 SF
F. TLT.
21 SF
TELE
21 SF
LAB STOR. 132 SF
WAITING
41 SF
MOP
27 SF
TLT
6 SF
ELEC.
2 SF
FAC24 SF
ALCOVE
79 SF
DIST. ROOM
200 SF
STAIR #6
145 SF
1-BED
43 SF
TLT.
149 SF
1-BED
42 SF
TLT.
128 SF
1-BED
46 SF
TLT.
184 SF
LOCKER
ROOM
48 SF
TLT 3014
46 SF
TLT
138 SF
1-BED
46 SF
STOR.
136 SF
1-BED
146 SF
1-BED
37 SF
STOR.
41 SF
TLT.
152 SF
1-BED
139 SF
1-BED
46 SF
TLT. 142 SF
1-BED
42 SF
TLT
43 SF
TLT.
396 SF
DIALYSIS
101 SF
STOR.
50 SF
STOR.
145 SF
1-BED 37 SF
CL. UTILITY
148 SF
PAT. RM.
45 SF
PAT. TLT.
314 SF
WORK ROOM
55 SF
HAC
95 SF
MECH
244 SF
PAT. RM.
52 SF
PAT. TLT.
PAT. TLT
148 SF
EQUIPMENT
STORAGE
130 SF
CLEAN
LINEN
68 SF
STORAGE
EMS
118 SF
NOURISHMENT
96 SF
STORAGE
57 SF
ISO PAT.
BATH
260 SF
BARIATRIC
RM.
66 SF
PAT. BATH
54 SF
PAT. BATH
101 SF
EQUIP.
STORAGE
56 SF
HAC
30 SF
CHASE69 SF
BARIATRIC
BATH
245 SF
BARIATRIC
RM.
364 SF
5 BED MSCU
172 SF
STAFF
LOCKER
8 SF
CHARTING
12 SF
FAC
CHARTING
4 SF
FAC
THIRD FLOOR PLAN - DEMOLITION
PIPING
MD103_P
HAS GLR
PLAN
NORTH
KEY PLAN
03 17
Roof
THIRD FLOOR ROOF PLAN -
DEMOLITION
MD104
HAS GLR
PLAN
NORTH
04 17
EQUIPMENT
TLT.
MED GAS
3013A
PAT. RM.
3015A
TLT
TLT
PAT. RMPAT. RM3014A
TLT
PAT. RM PAT. RM.
TLT3017A
TLT
PAT. RM.
3019A
3018A
PAT. RM.
3020A
TOILET
CLEAN
CORR
TLT
TLT
IT & ELEC.
NURSE
MANAGER
3190J
NURSE
MANAGER
CHIEF
NURSE
3190I
3190H
3190G
CHIEF
UNASSIGNED
ASST CHIEF
NURSE
UM NURSES
3190E3190F
3190D
SOCIAL
WORKERS
3190B
PHARM/
PHARM
TECH
3190A
COPY/FAX
STAFF TLT
ELEC.
3088A
ELEC.
3100A
PAT. RM
TLT
3086A
3087A PAT. RM
TLT
STOR.
SUPPLY
STOR.
STAIR #6
STAIR #5
OFFICE
3102 3101 3101A
EXISTING
CONFERENCE
EXISTING
BREAK
3016A
TLT
MED GAS
CORR
CORR
LINEN
HALL
3014 3017 3018
3190C
EDUCATOR
OFC
3190L
TLT
HAC
IT
PLAN
NORTH
KEY PLAN
THIRD FLOOR PLAN - NEW
DUCTWORK
MH103
HAS GLR 05 17
Roof
PLAN
NORTH
KEY PLAN
THIRD FLOOR ROOF PLAN - NEW
WORK
MH104
HAS GLR 06 17
EQUIPMENT
TLT.
MED GAS
PAT. RM
3013A
PAT. RM.
3015A
TLT
TLT
PAT. RMPAT. RM3014A
TLT
PAT. RM PAT. RM.
TLT
3017A
TLT
PAT. RM.
3019A
3018A
PAT. RM.
3019 3020A
TOILET
CLEAN
CORR
TLT
TLT
IT & ELEC.
EQUIP.
2 PERSON
OFFICE
3190K
NURSE
MANAGER
3190J
NURSE
MANAGER
CHIEF
NURSE
3190I
3190H
3190G
CHIEF
UNASSIGNED
ASST CHIEF
NURSE
UM NURSES
3190E
3190F
3190D
2 PERSON
OFFICE
3190B
2 PERSON
OFFICE
3190A
PT/OT EQUIP
STAFF TLT
WAITING
ELEC.
3088AELEC.
3100A
PAT. RM
TLT
3086A
3087A
PAT. RM
TLT
CORRIDOR
STOR.
SUPPLY
STOR.
STAIR #6
STAIR #5
OFFICE
3101 3101A
EXISTING
CONFERENCE
SOILED
EXISTING
BREAK
3016A
TLT
MED GAS
CORR
CORR
LINEN
HALL
3017 3018
HAC
HAC
PLAN
NORTH
KEY PLAN
THIRD FLOOR PLAN -
PIPING
MP103
HAS GLR 07 17
MECHANICAL DETAILS
M501
HAS GLR 08 17
M502
HAS GLR 09 17
M503
HAS GLR 10 17
Firestop System -
Packing Material -
Fill, Void or Cavity Material* -Sealant -
SPECIFIED TECHNOLOGIES INC
Metal Jacket -
System No. W-L-5014
Wall Assembly -
Studs -
Gypsum Board* -
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
Metallic Sleeve -
Through Penetrants -
Steel Pipe -
Iron Pipe -
Copper Tubing -
Copper Pipe -
Pipe Coverings* -
Pipe and Equipment Covering Materials* -
Pipe and Equipment Covering-Materials*
Pipe Covering Materials* -
IIG MINWOOL L L C
Sheathing Material* -
Sheathing Materials
Fill, Void or Cavity Material* - Sealant -
SPECIFIED TECHNOLOGIES INC
1B
1A
A
Section A-A
A
4A
4C
4A
4B
4D 4C
4B
1B
1A
Section A-A
A
A
MECHANICAL DETAILS
M504
HAS GLR 11 17
AIR HANDLING UNIT 2-AHU4 PLAN
M505
HAS GLR 12 17
AIR TERMINAL UNIT SIZING SCHEDULE
SIZE
MIN ALLOWABLE
AIR FLOW
MAX ALLOWABLE
AIR FLOW DUCT INLET SIZE MAX APD
MAXIMUM SOUND POWER LEVEL (Re: 10 -12 WATTS)
FOR BOX DISCHARGE AT MAXIMUM INLET DUCT
STATIC
HOT WATER HEATING COIL
REMARKS
OCTAVE BANDS EAT EWT FLOW MAX WPD PIPE RUNOUT
SIZE TO COIL
CFM [L/s] CFM [L/s] IN [mm] IN WG [Pa] 2 3 4 5 6 7 °F [°C] °F [°C] GPM [L/m] FT [kPa] IN [mm]
A 60 [ 28 ] 170 [ 80 ] 4 [ 100 ] 0.4 [ 100 ] 69 65 58 52 51 47 55 [ 13 ] 140 [ 60 ] 0.5 [ 2 ] 3 [ 9 ] 0.75 [ 19 ] ----
B 90 [ 42 ] 260 [ 120 ] 5 [ 130 ] 0.4 [ 100 ] 69 63 59 52 51 47 55 [ 13 ] 140 [ 60 ] 0.5 [ 2 ] 3 [ 9 ] 0.75 [ 19 ] ----
C 130 [ 61 ] 380 [ 180 ] 6 [ 150 ] 0.4 [ 100 ] 69 67 61 55 52 49 55 [ 13 ] 140 [ 60 ] 0.7 [ 3 ] 4 [ 12 ] 0.75 [ 19 ] ----
D 160 [ 76 ] 490 [ 230 ] 7 [ 180 ] 0.4 [ 100 ] 70 68 63 57 53 49 55 [ 13 ] 140 [ 60 ] 0.7 [ 3 ] 4 [ 12 ] 0.75 [ 19 ] ----
E 230 [ 110 ] 680 [ 320 ] 8 [ 200 ] 0.4 [ 100 ] 71 68 59 53 51 47 55 [ 13 ] 140 [ 60 ] 1 [ 4 ] 3 [ 9 ] 0.75 [ 19 ] ----
F 270 [ 130 ] 790 [ 370 ] 9 [ 230 ] 0.4 [ 100 ] 71 69 60 54 51 47 55 [ 13 ] 140 [ 60 ] 1.5 [ 6 ] 4 [ 12 ] 0.75 [ 19 ] ----
G 350 [ 170 ] 1050 [ 500 ] 10 [ 250 ] 0.4 [ 100 ] 74 68 61 57 54 52 55 [ 13 ] 140 [ 60 ] 1.5 [ 6 ] 4 [ 12 ] 0.75 [ 19 ] ----
H 500 [ 240 ] 1500 [ 710 ] 12 [ 300 ] 0.4 [ 100 ] 73 69 64 59 57 53 55 [ 13 ] 140 [ 60 ] 2.5 [ 10 ] 3 [ 9 ] 0.75 [ 19 ] ----
I 750 [ 350 ] 2250 [ 1100 ] 14 [ 350 ] 0.4 [ 100 ] 73 68 65 61 61 59 55 [ 13 ] 140 [ 60 ] 3.5 [ 13 ] 4 [ 12 ] 0.75 [ 19 ] ----
J 1000 [ 470 ] 3000 [ 1400 ] 16 [ 400 ] 0.4 [ 100 ] 73 68 66 60 58 55 55 [ 13 ] 140 [ 60 ] 4.5 [ 17 ] 4 [ 12 ] 1 [ 25 ] ----
NOTES
1. INLET STATIC BASED ON ARI 885-98.
2. THIS SCHEDULE IS USED WITH THE TERMINAL UNIT SCHEDULE.
3. CONTROL SEQUENCE SHALL BE AS INDICATED ON THE AIR TERMINAL UNIT SCHEDULE.
4. PROVIDE SOUND ATTENUATION AFTER-SECTION AS REQUIRED TO MEET ROOM NC LEVEL.
RADIANT CEILING PANEL SCHEDULE (ELECTRIC )
MARK ROOM
LOCATION
AREA
SERVED
PANEL SIZE CAPACITY POWER SUPPLY
REMARKS
IN [mm] BTUH [W] AMPS PHASE VOLT
2-ERP-1
3013A,3015A,3 017A,3019A,30
86A TLT 24 x 24 [ 610 x 610 ] 1280 [ 380 ] 3.2 1 120 ---
DUCTLESS SPLIT SYSTEM AIR CONDITIONER ELECTRIC SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
TYPE
TOTAL SUPPLY
AIR FLOW
MIN. OUTSIDE
AIR FLOW
EXT STATIC
PRESSURE
COOLING CAPACITY HEATING CAPACITY
AIR
FILTER
MARK NO
ELECTRICAL DATA
REMARKSMIN TOTAL
CAPACITY
MIN SENS
CAPACITY MIN
SEER
EAT OSA DESIGN
TEMP COMP Kw
GAS MIN. INPUT MIN. NET
OUTPUT
EAT
Db
LAT
Db INDOOR FAN OUTDOOR UNIT FAN
Db Wb CFM [L/s] CFM [L/s] IN [Pa] MBH [kW] MBH [kW] °F [°C] °F [°C] °F [°C] MBH [kW] MBH [kW] °F [°C] °F [°C] MCA [W] ELEC MCA [W] ELEC
2-CC1 CEILING MTD. IT/ELEC
CEILING
CASSETTE 406 [ 190 ] 0 [ ] 0 [ ] 10.8 [ 37 ] 8.4 [ 3 ] 20 80 [ 27 ] 67 [ 19 ] [ 95 ] [ 35 ] 7.5 NA #VALUE! 13.5 [ 4 ] 47 [ 8 ] 50 [ 10 ] NA 0.13 [ 97 ] 208/60/1 0.13 [ 97 ] 208/60/1 COND. UNIT ON 5TH FLR
ROOF
2-WMD1 WALL MTD. IT 3161 DUCTLESS
SPLIT 434 [ 200 ] 0 [ ] 0 [ ] 10.9 [ 37 ] 9.48 [ 3 ] 19 80 67 [ 95 ] [ 35 ] 1.42 NA #VALUE! NA #VALUE! NA NA NA 0.28 [ 210 ] 208/60/1 0.18 [ 130 ] 208/60/1 COND. UNIT ON 3RD FLR
ROOF
MECHANICAL SCHEDULES
M601
HAS GLR
SINGLE DUCT AIR TERMINAL UNIT SCHEDULE
MARK LOCATION
AREA
AND/OR
ROOM
SERVED
SYSTEM AIR
HANDLING SIZE
AIR FLOW ADDITIONAL
SOUND
ATTUNATION
REQUIRED
CONTROL
TYPE
CONTROL
SEQUENCE
REHEAT PERIMETER
SUPPLEMENTAL
HEAT LINK
REMARKSMAX MIN
CFM [L/s] CFM [L/s] HW
(GPM) ELEC NONE
2-TU-4-30 CORRIDOR 3190D 2-AHU4 A 160 [ 76 ] 80 [ 38 ] NONE VAV 5 DEGREE
DEADBAND 0.5 N/A ----
2-TU-4-31 3190G 3190G, 3190H 2-AHU4 C 300 [ 140 ] 150 [ 71 ] NONE VAV 5 DEGREE
DEADBAND 0.5 N/A
2-TU-4-32 CORRIDOR 3190E 2-AHU4 D 420 [ 200 ] 210 [ 99 ] NONE VAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-33 CORRIDOR 3190F, 3190L 2-AHU4 E 540 [ 250 ] 270 [ 130 ] NONE VAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-34 3190J 3190I, 3190J 2-AHU4 C 300 [ 140 ] 190 [ 90 ] NONE VAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-35 3190C 3190C,
3190B, 3091A 2-AHU4 D 405 [ 190 ] 205 [ 97 ] NONE VAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-36 3190K 3190K 2-AHU4 A 135 [ 64 ] 70 [ 33 ] NONE VAV 5 DEGREE
DEADBAND 0.5 N/A
2-TU-4-37 3088 3088, 3089 2-AHU4 C 310 [ 150 ] 155 [ 73 ] NONE VAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-38 CORRIDOR CORRIDOR 2-AHU4 C 350 [ 170 ] 350 [ 170 ] NONE CAV 5 DEGREE
DEADBAND 1.5 N/A
2-TU-4-39 3100 3100 2-AHU4 A 150 [ 71 ] 75 [ 35 ] NONE VAV 5 DEGREE
DEADBAND 0.5 N/A
2-TU-4-40 CORRIDOR 3156, 3154,
CORRIDOR 2-AHU4 C 325 [ 150 ] 325 [ 150 ] NONE CAV 5 DEGREE
DEADBAND 1.5 N/A
2-TU-4-41 3166 3166, 3169,
CORRIDOR 2-AHU4 D 385 [ 180 ] 385 [ 180 ] NONE CAV 5 DEGREE
DEADBAND 1.5 N/A
2-TU-4-42 3087 3087 2-AHU4 B 250 [ 120 ] 250 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-43 3086 3086 2-AHU4 C 270 [ 130 ] 270 [ 130 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-44 3015 3015 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-45 3014 3014 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-46 3013 3013 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-47 3016 3016 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-48 3017 3017 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-49 3018 3018 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-50 3019 3019 2-AHU4 B 245 [ 120 ] 245 [ 120 ] NONE CAV 5 DEGREE
DEADBAND 1 N/A
2-TU-4-51 3020 3020 2-AHU4 C 315 [ 150 ] 315 [ 150 ] NONE CAV 5 DEGREE
DEADBAND 1.5 N/A
AIR DEVICE SCHEDULE (SUPPLY)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
IN x IN [mm x mm] IN [mm ] CFM [L/s] CFM [L/s]
IN WG
[Pa]
SD-11 LOUVERED FACE 40 [ 19 ] 160 [ 76 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 6 ø
[152 ø] 19 NONE WHITE ----
SD-12 LOUVERED FACE 70 [ 33 ] 280 [ 130 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 8 ø
[203 ø] 23 NONE WHITE -----
SD-13 LOUVERED FACE 110 [ 52 ] 380 [ 180 ] 0.090 [ 23 ] CEILING 24 x 24 [ 600 x 600 ] 10 ø
[254 ø] 22 NONE WHITE -----
SD-14 LOUVERED FACE 160 [ 76 ] 470 [ 220 ] 0.080 [ 20 ] CEILING 24 x 24 [ 600 x 600 ] 12 ø
[305 ø ] 19 NONE WHITE -----
SD-15 LOUVERED FACE 220 [ 100 ] 640 [ 300 ] 0.090 [ 23 ] CEILING 24 x 24 [ 600 x 600 ] 14 ø [356 ø ] 21 NONE WHITE -----
SD-16 LOUVERED FACE 250 [ 120 ] 740 [ 350 ] 0.100 [ 25 ] CEILING 24 x 24 [ 600 x 600 ] 16 ø [406 ø ] 22 NONE WHITE -----
SD-51 SUPPLY REGISTER 80 [ 38 ] 120 [ 57 ] 0.100 [ 25 ] CEILING/WALL 8 x 8 [203 x 203] 6 x 6 [152 x 152] 25 OBD WHITE -----
NOTES
1. SEE FLOOR PLAN FOR THROW PATTERN.
2. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.
3. PROVIDE SQUARE TO ROUND ADAPTER.
AIR DEVICE SCHEDULE (LINEAR)
MARK TYPE
AIR FLOW
MAX APD MIN THROW MAX THROW # OF
SLOT
S
SLOT
WIDTH
PANEL/FRAME
SIZE NECK SIZE
THROW
PATTER
N
THROW
TYPE NC DAMPE
R
FINIS
H REMARKS
IN [mm] IN [mm]
MIN MAX
CFM [L/s] CFM [L/s] IN
WG
[Pa] FT [M] FT [M]
IN
[mm]
SD-31 LINEAR 180 [ 85 ] 580 [ 270 ] 0.27 66.70 4 - 7
-15
2.0 - 3.1 - 4.9
17 - 21 -
5.3 - 6.5 -
9.2 2 2 [ 50 ] 24 x 5 [ 600 x 127
] 10 ø [254 ø] 2 WAY VERTICAL 41 NONE WHITE -----
SD-310 LINEAR 50 [ 24 ] 350 [ 170 ] 0.26 63.80 4 - 5 -
1.1 - 1.6 - 3.3
23 - 28 -
6.9 - 8.4 -
11.9 2 1 [ 25 ] 48 x 5 [ 1219 x
127 ] 10 ø [254 ø] 1 WAY VERTICAL 32 NONE WHITE -----
NOTES
1. SEE DETAIL FOR DAMPER IN BRANCH DUCT SERVING EACH DIFFUSER.
2. PROVIDE COLLAR AND TRANSITION AS REQUIRED.
AIR DEVICE SCHEDULE (RETURN & EXHAUST)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
CFM [L/s] CFM [L/s] IN WG [Pa] IN x IN [mm x mm] IN x IN [mm x mm] RG-21 PERFORATED 60 [ 28 ] 100 [ 47 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 6 DIAM [ 152 DIAM ] 13 NONE WHITE -----
RG-22 PERFORATED 110 [ 52 ] 170 [ 80 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 8 DIAM [ 203 DIAM ] 13 NONE WHITE -----
RG-23 PERFORATED 170 [ 80 ] 250 [ 120 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 10 DIAM [ 254 DIAM ] 14 NONE WHITE -----
RG-24 PERFORATED 240 [ 110 ] 400 [ 190 ] 0.088 22.000 CEILING 24 x 24 [ 600 x 600 ] 12 DIAM [ 305 DIAM ] 12 NONE WHITE -----
RG-25 PERFORATED 320
[ 150 ]
[ 240 ] 0.087 22.000 CEILING 24 x 24 [ 600 x 600 ] 14 DIAM [ 356 DIAM ] 14 NONE WHITE -----
RG-26 PERFORATED 420
[ 200 ]
[ 330 ] 0.087 22.000 CEILING 24 x 24 [ 600 x 600 ] 16 DIAM [ 406 DIAM ] 16 NONE WHITE -----
RR-51 RETURN
REGISTER 50 [ 24 ] 160 [ 76 ] 0.078 20.000 CEILING/WALL 8 x 8 [ 203 x 203 ] 6 x 6 [ 152 x 152 ] 12 OBD WHITE -----
RR-52 RETURN
REGISTER 130 [ 61 ] 210 [ 99 ] 0.078 20.000 CEILING/WALL 10 x 10 [ 254 x 254 ] 8 x 8 [ 203 x 203 ] 13 OBD WHITE -----
RR-53 RETURN
REGISTER 200 [ 94 ] 330 [ 160 ] 0.078 20.000 CEILING/WALL 12 x 12 [ 305 x 305 ] 10 x 10 [ 254 x 254 ] 15 OBD WHITE -----
RR-54 RETURN
REGISTER 270 [ 130 ] 440 [ 210 ] 0.078 20.000 CEILING/WALL 14 x 14 [ 356 x 356 ] 12 x 12 [ 305 x 305 ] 17 OBD WHITE -----
RR-55 RETURN
REGISTER 250 [ 120 ] 610 [ 290 ] 0.082 21.000 CEILING/WALL 16 x 16 [ 406 x 406 ] 14 x 14 [ 356 x 356 ] 18 OBD WHITE -----
NOTE
"EG or ER" IS USED IN PLACE OF "RG or RR" FOR AIR DEVICES USED ON EXHAUST SYSTEMS
PROVIDE SQUARE TO ROUND ADAPTER.
SMOKE AND COMBINATION FIRE/SMOKE DAMPER SCHEDULE
MARK LOCATION FAN SYSTEM
SYSTEM
AND/OR
SERVICE
DUCT SIZE DUCT PRESSURE
CLASS
REMARKSIN [mm] IN WG [Pa]
A 3RD FLR ROOF 2-SAF 1&2 2-AHU4 53X20 4 [ 1000 ] SMOKE DAMPER
B 3RD FLR ROOF 2-RAF 1&2 2-AHU-4 53X20 2 [ 500 ] SMOKE DAMPER
C 3RD FLOOR 2-RAF 1&2 2-AHU-4 14X10 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
D 3RD FLOOR 2-SAF 1&2 2-AHU-4 36X12 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER
E 3RD FLOOR 2-RAF 1&2 GENERAL
EXHAUST 30X12 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
F 3RD FLOOR 2-SAF 1&2 2-AHU-4 12X8 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER
G 3RD FLOOR EX. EF-3 2-AHU-4 14X10 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
H 3RD FLOOR 2-SAF 1&2 2-AHU-4 16X14 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER
I 3RD FLOOR 2-SAF 1&2 2-AHU-4 9" ROUND 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER
J 3RD FLOOR 2-RAF 1&2 2-AHU-4 7" ROUND 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
K 3RD FLOOR EX EF-3 GENERAL
EXHAUST 6" ROUND 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
L 3RD FLOOR 2-SAF 1&2 2-AHU-4 8X8 4 [ 1000 ] COMBINATION FIRE/SMOKE DAMPER
M 3RD FLOOR 2-SAF 1&2 2-AHU-4 6" ROUND 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
N 3RD FLOOR EX. EF-1 GENERAL
EXHAUST 8X6 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
O 3RD FLOOR EX. EF-1 GENERAL
EXHAUST 18X14 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
P 3RD FLOOR EX. EF-1 GENERAL
EXHAUST 18X14 2 [ 500 ] COMBINATION FIRE/SMOKE DAMPER
13 17
AIR HANDLING UNIT SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
TYPE AIR FLOW
AIR FLOW SUPPLY
FAN
MARK
RETURN OR
RELIEF FAN
MARK
EXHAUST
FAN MARK
PREFILTER
MARK
AFTER
FILTER
MARK
FINAL
FILTER
MARK
HEAT
RECOVERY
MARK
PREHEAT
COIL MARK
COOLING
COIL MARK
REHEAT
COIL
HUMIDIFIER
MARK REMARKSSUPPLY MIN OA RETURN
CFM [L/s] CFM [L/s] CFM [L/s]
2-AHU4 THIRD FLR.
ROOF
BUILDING 2
-3RD FLR
CENTER
PRE-ENGINEERI
NG VAV 7000 [ 3300 ] 2100 [ 990 ] 4900 [ 2300 ] 2-SF1 & 2 2-RF1 & 2 NA 2-PF4 2-AF4 2-FF4 N/A 2-PHC4 2-CC4 NA 2-H4 -----
STEAM HEATING COIL SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
SYSTEM
AND/OR
SERVICE
APPLICATION
AIR FLOW MAX FACE
VELOCITY APD
TEMPERATURES TOTAL MIN
CAPACITY
STEAM
REMARKSEAT LAT ENT CONT VALVE ENT COIL FLOW STEAM TRAP
CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] MARK LBS/HR [kg/HR]
1-SHC16 G1100 CLINICAL
ADDITION 1-AHU7 PREHEAT 10000 [ 4700 ] 500 [2.54] 0.2 [ 50 ] 45 [ 7 ] 90 [ 32 ] 480 [ 1600 ] 15 [ 100 ] 5 [ 35 ] 500 [ 230 ] 1-TP7 1200 [ 540 ] ----
CHILLED WATER COOLING COIL SCHEDULE
MARK LOCATION
AREA
AND/OR BLDG
SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW MAX FACE
VELOCITY APD
EAT LAT
TOTAL CAPACITY SENSIBLE
CAPACITY
CHILLED WATER
REMARKSDb Wb Db Wb FLOW EWT LWT WPD CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] °F [°C] °F [°C] MBH [kW] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [M]
7-CWCC5 B1100AA OUTPATIENT
ADDITION 7-AHU5 10000 [ 4700 ] 450 [ 2 ] 0.65 [ 160 ] 80 [ 27 ] 67 [ 19 ] 55 [ 13 ] 54 [ 12 ] 380 [ 110 ] 270 [ 79 ] 47 [ 3 ] 42 [ 6 ] 58 [ 14 ] 6 [ 2 ] -----
NOTE
THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT [400 FINS PER METER].
FAN SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW TSP
FAN MOTOR ELECTRICAL
CONTROL
SEQUENCE REMARKS
TYPE WHEEL CLASS
ARRANGEMENT,
ROTATION, AND
DISCHARGE
DIAMETER MIN %
EFF DRIVE
FAN
MAX
RPM
NOMINAL POWER
PHASE VOLT RPM SPEED
CONTROLCFM [L/s] IN [Pa] IN [mm] BHP HP [kW]
2-SF1 THIRD FLOOR
ROOF
BUILDING 2 -
3RD FLR.
CENTER
2-AHU4 3500 [ 1700 ] 6 [ 1500 ] PLENUM AIRFOIL II CW, HORIZONTAL 24.5 [ 610 ] 75% DIRECT 2269 5 7.5 [ 6 ] 3 208 1750 VARIABLE 2 FAN ARRAY
2-SF2 THIRD FLOOR
ROOF
BUILDING 2 -
3RD FLR.
CENTER
2-AHU4 3500 [ 1700 ] 6 [ 1500 ] PLENUM AIRFOIL II CW, HORIZONTAL 24.5 [ 610 ] 75% DIRECT 2269 5 7.5 [ 6 ] 3 208 1750 VARIABLE 2 FAN ARRAY
2-RF1 THIRD FLOOR
ROOF
BUILDING 2 -
3RD FLR.
CENTER
2-AHU4 2450 [ 1200 ] 2 [ 500 ] PLENUM AIRFOIL II CW, HORIZONTAL 22 [ 550 ] 75% DIRECT 2454 2 5 [ 4 ] 3 208 1750 VARIABLE 2 FAN ARRAY
2-RF2 THIRD FLOOR
ROOF
BUILDING 2 -
3RD FLR.
CENTER
2-AHU4 2450 [ 1200 ] 2 [ 500 ] PLENUM AIRFOIL II CW, HORIZONTAL 22 [ 550 ] 75% DIRECT 2454 2 5 [ 4 ] 3 208 1750 VARIABLE 2 FAN ARRAY
NOTE
ALL SELECTIONS ARE BASED ON AN ALTITUDE OF 971 FT..
AIR FILTER SCHEDULE
MARK LOCATION AREA AND/OR BLDG
SERVED
SYSTEM
AND/OR
SERVICE
MERV
RATING
AIR FLOW
APD
HOUSING
TYPE
CARTRIDGES
INITIAL CHANGEOVER
SIZE
ARRANGEMENT REMARKS
CFM [L/s] IN [mm] IN [mm] IN [mm]
2-PF1 3RD FLR ROOF BLDG. 2 - 3RD FLR.
CENTER 2-AHU4 7 7000 [ 3300 ] 0.25 [ 6 ] 0.5 [ 13 ] SIDE 2
20 x 20 x 2
24x20x2 [508X508X.50]
[609X508X.50] 3 WIDE BY 2 HIGH -----
2-PF2 3RD FLR ROOF BLDG. 2 - 3RD FLR.
CENTER 2-AHU4 11 7000 [ 3300 ] 0.65 [ 16 ] 1.3 [ 33 ] SIDE 2
20 x 20 x 2
24x20x2 [508X508X.50]
[609X508X.50] 3 WIDE BY 2 HIGH ----
2-FF1 3RD FLR ROOF BLDG. 2 - 3RD FLR.
CENTER 2-AHU4 14 7000 [ 3300 ] 1 [ 25 ] 2 [ 50 ] SIDE 2
20 x 20 x 12
24x20x12 [508X508X305]
[609X508X305] 3 WIDE BY 2 HIGH ----
STEAM HUMIDIFER SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SEVICE
HUMIDIFIER TYPE
AIR FLOW # OF
MANIFOLDS
EAT LAT
SOURCE
STEAM
CONTROL
TYPE
TRAP
REMARKSDb DEWPOINT
%RH
DEWPOINT PRESS ENT VALVE PRESS ENT
HEATER FLOW
MARK
CAPACITY
CFM [L/s] °F [°C] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] LBS/HR [kg/HR]
2-SH1 ROOF 2-AHU4 UNIT-MOUNTED
DISPERSION TUBE 7000 [ 3300 ] 3 55 [ 13 ] 21 [ -6 ] [ 55 ] 52 [ 11 ] PLANT
STEAM 15 [ 100 ] 5 [ 35 ] 67 [ 30 ] MODULATING 2-TRP1 170 [ 77 ]
BUILDING · STEAM TRAP SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SERVICE
CAPACITY AT MIN DIFF
PRESS MIN DIFF PRESS MIN INLET PRESS
TRAP TYPE
TRAP SIZE
REMARKS
LBS/HR [kg/HR] PSI [kPa] PSI [kPa] IN [mm]
2-ST1 CEILING RM
3190 MAIN DRIP 220 [ 100 ] .25 [ 2 ] 15 [ 100 ] F&T .75 [ 19 ] TRAP SIZED ON SAFETY FACTOR OF 2.0
2-ST2 ROOF MAIN DRIP 220 [ 100 ] .25 [ 2 ] 15 [ 100 ] F&T .75 [ 19 ] TRAP SIZED ON SAFETY FACTOR OF 2.0
2-ST3 2-AHU4 PREHEAT
COIL 110 [ 50 ] .25 [ 2 ] 5 [ 35 ] F&T .75 [ 19 ] TRAP SIZED ON SAFETY FACTOR OF 2.0
AIR FLOW MEASURING DEVICE SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SERVICE
AIR FLOW DUCT SIZE
APD
REMARKSMIN MAX WIDTH HEIGHT
CFM [L/s] CFM [L/s] IN [mm] IN [mm] IN [mm]
2-AFMD1 RETURN FAN
INLET 2-AHU-4 525 [ 250 ] 1050 [ 500 ] NA #VALUE! NA #VALUE! 0.01 [ ] PIEZOMETER RING ON FAN INLET
2-AFMD1A RETURN FAN
INLET 2-AHU-4 525 [ 250 ] 1050 [ 500 ] NA #VALUE! NA #VALUE! 0.01 [ ] PIEZOMETER RING ON FAN INLET
2-AFMD2 SUPPLY FAN
INLET 2-AHU-4 1750 3500 NA NA 0.01 PIEZOMETER RING ON FAN INLET
2-AFMD2A SUPPLY FAN
INLET 2-AHU-4 1750 [ 830 ] 3500 [ 1700 ] NA #VALUE! NA #VALUE! 0.01 [ ] PIEZOMETER RING ON FAN INLET
MECHANICAL SCHEDULES
M602
HAS RW 14 17
MECHANICAL SCHEDULES
M603
HAS RW
ROOM AIR BALANCE SCHEDULE
ROOM
NO
ROOM
NAME
AIR
HANDLING
UNIT NO
TERMINAL
UNIT
INDIVIDUAL
ROOM TEMP
CONTROL
SUPPLY RETURN OR EXHAUST ROOM AIR
FLOW
ROOM AIR
BALANCE
NET
INFILTRATION
NET
EXFILTRATION
ROOM AIR FLOW
# OF AIR
DEVICES
AIR
DEVICE
MARK
SUPPLY
FAN
RETURN OR
EXHAUST
(R/E)
ROOM AIR FLOW
# OF AIR
DEVICES
AIR
DEVICE
MARK
RETURN OR
EXHAUST
FAN
REMARKSCFM L/S CFM L/S CV VAV CFM [L/s] CFM [L/s]
3012 MED GAS 2-AHU-4 2-TU-4-40 N 100 [ 47 ] 1 SD-51 2-SF-1 & 2 E 150 [ 71 ] 1 OPEN
DUCT EX-F-8 X N -50 [ -20 ] 0 [ ] 50 CFM FROM CORR.
3013 PAT. ROOM 2-AHU-4 2-TU-4-46 Y 245 [ 120 ] 2 SD-31 2-SF-1 & 2 R 165 [ 78 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3013A TLT. 2-AHU-4 NA Y (2-ERP-1) 0 [ ] 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-8 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3013
3014 PAT. ROOM 2-AHU-4 2-TU-4-45 Y 245 [ 120 ] 1 SD-310 2-SF-1 & 2 R 165 [ 78 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3014A TLT. 2-AHU-4 NA N 0 [ ] 0 NA NA E 801 [ 380 ] 1 ER-56 EX-F-8 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3014
3015 PAT. ROOM 2-AHU-4 2-TU-4-44 Y 245 [ 120 ] 1 SD-310 2-SF-1 & 2 R 165 [ 78 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3015A TLT. 2-AHU-4 NA Y (2-ERP-1) 0 [ ] 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-8 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3015
3016 PAT. ROOM 2-AHU-4 2-TU-4-47 Y 245 [ 120 ] 1 SD-310 2-SF-1 & 2 R 165 [ 78 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3016A TLT. 2-AHU-4 NA N 0 [ ] 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-8 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3016
3017 PAT. RM. 2-AHU-4 2-TU-4-48 Y 245 [ 120 ] 2 SD-31 2-SF-1 & 2 R 165 [ 78 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3017A TLT. 2-AHU-4 NA Y (2-ERP-1) 0 [ ] 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-5 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3017
3018 PAT. RM. 2-AHU-4 2-TU-4-49 Y 245 [ 120 ] 1 SD-310 2-SF-1 & 2 R 165 [ 78 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3018A TLT. 2-AHU-4 NA N 0 [ ] 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-5 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3018
3019 PAT. RM. 2-AHU-4 2-TU-4-50 Y 245 [ 120 ] 2 SD-31 2-SF-1 & 2 R 165 [ 78 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3019A TLT. 2-AHU-4 NA Y (2-ERP-1) 0 [ ] 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-5 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3019
3020 PAT. RM. 2-AHU-4 2-TU-4-51 Y 315 [ 150 ] 2 SD-31&
SD-310 2-SF-1 & 2 R 235 [ 110 ] 1 RG-23 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3020A TLT. 2-AHU-4 NA N 0 N/A 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-5 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3020
3086 PAT. RM. 2-AHU-4 2-TU-4-43 Y 270 [ 130 ] 2 SD-31 2-SF-1 & 2 R 190 [ 90 ] 1 RG-23 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3086A TLT. 2-AHU-4 NA Y (2-ERP-1) 0 NA 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-5 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3086
3087 PAT. RM. 2-AHU-4 2-TU-4-42 Y 250 [ 120 ] 2 SD-31 2-SF-1 & 2 R 170 [ 80 ] 1 RG-23 2-RF-1&2 X E 0 [ ] 80 [ 38 ] 80 CFM TO TOILET EXHAUST
3087A TLT. 2-AHU-4 NA N 0 [ ] 0 NA NA E 80 [ 38 ] 1 ER-56 EX-F-5 X N 80 [ 38 ] 0 [ ] 80 CFM FROM PAT. RM. 3087
3088 WAITING 2-AHU-4 2-TU-4-37 Y 280 [ 130 ] 2 SD-11 2-SF-1 & 2 R 280 [ 130 ] 1 RG-23 2-RF-1&2 X E 0 [ ] 0 [ ]
3088A ELEC. RM 2-AHU-4 2-TU-4-52 N 50 [ 24 ] 1 SSG-1 2-SF-1 & 2 NA 0 [ ] NA NA NA X P 0 [ ] 50 [ 24 ] 50 CFM TO CORR/3162
3089 TLT. 2-AHU-4 2-TU-4-37 N 30 [ 14 ] 1 SD-51 2-SF-1 & 2 E 80 [ 38 ] 1 ER-56 EX-F-5 X N 50 [ 24 ] 0 [ ] 50 CFM TO CORR/3162
3090 HALL 2-AHU-4 2-TU-353 Y 175 [ 83 ] 1 SD-12 2-SF-1 & 2 R 175 [ 83 ] 2 RG-11 2-RF-1&2 X E 0 [ ] 0 [ ]
3100 EXIST OFC 2-AHU-4 2-TU-4-39 Y 150 [ 71 ] 1 SD-12 2-SF-1 & 2 R 150 [ 71 ] 1 RG-22 2-RF-1&2 X E 0 0
3153 MED GAS 2-AHU-4 2-TU-4-40 N 100 [ 47 ] 1 SD-51 2-SF-1 & 2 E 150 [ 71 ] 1 OPEN
DUCT EX-F-8 X N 50 [ 24 ] 0 [ ] 50 CFM FROM CORR/3162
3154 EQUIP. RM. 2-AHU-4 2-TU-4-40 N 75 [ 35 ] 1 SD-11 2-SF-1 & 2 E 75 [ 35 ] 1 EG-21 EX-F-8 X E 0 0
3156 CLEAN
SUPPLY 2-AHU-4 2-TU-4-40 N 75 [ 35 ] 1 SD-11 2-SF-1 & 2 NA 0 [ ] NA NA NA X 3162 0 [ ] 75 [ 35 ] 75 CFM TO CORR/3162
3162 CORR. 2-AHU-4 2-TU-4-38 &
2-TU-4-52 Y 175 [ 83 ] 3 SD-11 2-SF-1 & 2 R 445 [ 210 ] 2 RG-23 &
RG-24 2-RF-1&2 X P 300 [ 140 ] 255 [ 120 ]
3164 CORR. 2-AHU-4 2-TU-4-40 &
2-TU-4-41 Y 350 [ 170 ] 2 SD-11 2-SF-1 & 2 R 210 [ 99 ] 2 RG-21 2-RF-1&2 X P 0 [ ] 100 [ 47 ]
3166 CLEAN STOR. 2-AHU-4 2-TU-4-41 N 75 [ 35 ] 1 SD-11 2-SF-1 & 2 NA 0 [ ] NA NA NA X P 0 [ ] 75 [ 35 ] 75 CFM TO CORR/3162
3167 TLT 2-AHU-4 NA N 30 [ 14 ] 1 SD-51 2-SF-1 & 2 E 80 [ 38 ] 1 ER-56 EX-F-5 X N 50 [ 24 ] 0 [ ] 50 CFM FROM CORR/3162
3168 TLT 2-AHU-4 NA N 30 [ 14 ] 1 SD-51 2-SF-1 & 2 E 80 [ 38 ] 1 ER-56 EX-F-5 X E 50 [ 24 ] 0 [ ] 50 CFM FROM CORR/3162
3169 SOILED 2-AHU-4 2-TU-2-41 Y 75 [ 35 ] 1 SD-11 2-SF-1 & 2 E 135 [ 64 ] 1 ER-22 EX-F-5 X N 50 [ 24 ] 0 [ ] 50 CFM FROM CORR/3162
3170 HAC 2-AHU-4 50 N 0 1 ER-56 EX-F-5 X N 50 [ 24 ] 0 [ ] 50 CFM FROM CORR/3162
3172 IT/ELEC 2-CC1 NA Y 268/406 1 NA 2-CC1 R 268/406 1 NA 2-CC1 X E 0 [ ] 0
3185 IT CLOSET 2-WMD1 NA Y 247/434 1 NA 2-WMD1 R 247/434 1 NA 2-WMD1 X E 0 [ ] 0
3190A COPY/FAX 2-AHU-4 2-TU-4-35 N 85 [ 40 ] 1 SD-11 2-SF-1 & 2 R 85 [ 40 ] 1 RG-11 2-RF-1&2 X E 0 [ ] 0
3190B PHARM/PHAR
M TECH 2-AHU-4 2-TU-4-35 Y 160 [ 76 ] 1 SD-12 2-SF-1 & 2 R 160 [ 76 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
3190C SOCIAL
WORKERS 2-AHU-4 2-TU-4-35 N 160 [ 76 ] 1 SD-12 2-SF-1 & 2 R 160 [ 76 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
3190D ASST CHIEF
NURSE 2-AHU-4 2-TU-4-30 Y 160 [ 76 ] 1 SD-12 2-SF-1 & 2 R 160 [ 76 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
3190E UM NURSES 2-AHU-4 2-TU-4-32 Y 420 [ 200 ] 3 SD-11 &
SD-12 2-SF-1 & 2 R 420 [ 200 ] 1 RG-25 2-RF-1&2 X E 0 [ ] 0
3190F UNASSIGNED 2-AHU-4 2-TU-4-33 Y 400 [ 190 ] 2 SD-12 2-SF-1 & 2 R 400 [ 190 ] 1 RG-24 2-RF-1&2 X E 0 [ ] 0
3190G CHIEF 2-AHU-4 2-TU-4-31 Y 150 [ 71 ] 1 SD-11 2-SF-1 & 2 R 150 [ 71 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
3190H CHIEF NURSE 2-AHU-4 2-TU-4-31 Y 150 [ 71 ] 1 SD-11 2-SF-1 & 2 R 150 [ 71 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
3190I NURSE
MANAGER 2-AHU-4 2-TU-4-34 Y 150 [ 71 ] 1 SD-11 2-SF-1 & 2 R 150 [ 71 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
3190J NURSE
MANAGER 2-AHU-4 2-TU-4-34 N 150 [ 71 ] 1 SD-11 2-SF-1 & 2 R 150 [ 71 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
3190K CONSULT 2-AHU-4 2-TU-4-36 Y 135 [ 64 ] 1 SD-11 2-SF-1 & 2 R 150 [ 71 ] 1 RG-22 2-RF-1&2 X E 0 [ ] 0
NOTE
ROOMS OR AREAS DO NOT HAVE INDIVIDUAL HUMIDITY CONTROL UNLESS NOTED.
15 17
MECHANICAL
INSTRUMENTATION
AND CONTROLS
MI701
HAS GLR 16 17
MECHANICAL
INSTRUMENTATION
AND CONTROLS
MI702
HAS GLR 17 17
GENERAL NOTESABBREVIATIONSSYMBOLS DRAWING INDEX
ELECTRICAL SYMBOL
SCHEDULE AND NOTES
E001
RAH SUB 1 13
R R R R R
R
R
R RR
R R R
R
R
R
R
R
R
A35A13
A16 A17
A19A15 A22
A24 A27A21
A25 A28 A34
A34
A30
A30
A31
A31
A11
A20
A26
A12 A14
A8
A8
A9
A9
5'-2" 10 1/2"
R R R
R
R R
"2C1A1C" "2L1A1C"
"2DC2"
"2DC-1"
"2DC"
ALTERNATE BID
DEDUCT #1
THIRD FLOOR PLAN - DEMOLITION
ED103
RAH SUB
A. THIS PROJECT IS TO BE ACCOMPLISHED IN PHASES AS
INDICATED ON THE ARCHITECTURAL PLANS, AND IT IS THE
INTENT OF THESE DOCUMENTS THAT THE ELECTRICAL
WORK FOLLOW, WHERE POSSIBLE, THIS PRESCRIBED
PHASING.
B. ALL ELECTRICAL CIRCUITS OR SYSTEMS WHICH PASS
THROUGH OR ARE AFFECTED BY THIS WORK SHALL BE
MAINTAINED IN A COMPLETE AND FULLY OPERATIONAL
CONDITION. PROVIDE TEMPORARY WIRING AND OR
CONNECTIONS, IN COMPLETE CONDUIT SYSTEMS, AS
REQUIRED TO MAINTAIN FULL OPERATION OUTSIDE THE
AREA OF CONSTRUCTION. PROVIDE PERMANENT
CONNECTIONS ON THOSE ITEMS WHICH ARE RELOCATED
TO ACCOMMODATE NEW CONSTRUCTION. ANY CIRCUITS
THAT ARE LIBERATED AS A RESULT OF THIS DEMOLITION
SHALL BECOME SPARE.
C. EXISTING SMOKE DETECTORS SHALL BE MAINTAINED IN
OPERATION AND SHALL BE TEMPORARILY MOUNTED AS
REQUIRED. APPROVED COVERS MAY BE USED DURING
WORKING HOURS WHEN THE CONSTRUCTION AREA IS
STAFFED BY THE CONTRACTOR AND DUST OR SMOKE
PRODUCING OPERATIONS ARE TAKING PLACE (TO REDUCE
THE NUMBER OF FALSE ALARMS) BUT THESE COVERS
SHALL BE REMOVED IMMEDIATELY AFTER THE COMPLETION
OF THESE OPERATIONS OR WHENEVER THE
CONSTRUCTION AREA IS NOT STAFFED BY THE
CONTRACTOR.
D. IN EXISTING WALLS INDICATED FOR DEMOLITION, EXISTING
FIRE ALARM DEVICES AND RELATED CONDUIT AND WIRING
ARE TO BE REMOVED. ALL FIRE ALARM DEVICES SHALL BE
TURNED OVER TO THE OWNER UNLESS INDICATED TO BE
RELOCATED.
E. WHERE AN EXISTING FIXTURE OR DEVICE IS REMOVED BUT
THE CIRCUIT(S) AND BOX ARE TO REMAIN TO MAINTAIN
CIRCUIT CONTINUITY, THEN THE CONTRACTOR IS TO
PROVIDE AN APPROPRIATE BLANK COVER PLATE ON THE
BOX TO MATCH THE COVER PLATES ON ADJACENT DEVICES
IN THE AREA.
F. EXISTING PAGING SYSTEM SPEAKERS AND ASSOCIATED
CONDUIT AND WIRING ARE TO BE REMOVED AS REQUIRED
IN CEILINGS BEING REPLACED. CLEAN SPEAKER COVERS
AND REINSTALL ALL SYSTEM RELATED DEVICES REQUIRED
IN NEW CEILINGS. PROVIDE TEMPORARY WIRING AS
REQUIRED TO MAINTAIN SYSTEM OPERATION DURING
CONSTRUCTION. EXISTING SPEAKER LOCATIONS ARE
INDICATED ON THIS DRAWING.
G. EXISTING RACEWAY AND BOXES MAY BE REUSED IF THEY
MEET THE REQUIREMENTS FOR NEW WORK.
H. ALL RELATED WIRING AND CONDUIT ASSOCIATED WITH
EXISTING FIXTURES OR DEVICES TO BE REMOVED SHALL
ALSO BE REMOVED WHERE NOT REUSED IN NEW
CONSTRUCTION. WIRING SHALL BE REMOVED TO THE NEXT
DEVICE OR TO THE OVERCURRENT PROTECTIVE DEVICE, AS
APPLICABLE. ALL UNUSED CONDUITS ABOVE THE CEILING
SHALL BE REMOVED, BUT UNUSED CONDUITS WITHIN
NONACCESSIBLE WALLS MAY BE ABANDONED.
I. EXISTING FIXTURES AND DEVICES ARE SHOWN ON THE
DEMOLITION AND NEW WORK DRAWINGS USING DASHED
STANDARD SYMBOLS:
NO SUBSCRIPT - ITEM TO REMAIN
R - ITEM TO BE REMOVED
REMOVE ALL EXISTING ELECTRICAL FIXTURES, DEVICES,
BOXES, CONDUIT, WIRING FROM ALL SECTIONS OF EXISTING
WALLS OR PARTITIONS BEING REMOVED. ALL EXISTING LED
LIGHT FIXTURES SHALL BE SALVAGED AND TURNED OVER TO
THE OWNER.
REMOVE ALL EXISTING LIGHT FIXTURES, SPEAKERS, FIRE
ALARM, NURSE CALL & SECURITY DEVICES, FROM ALL
SECTIONS OF EXISTING CEILINGS BEING REMOVED. ALL WIFI
DEVICES AND CCTV CAMERAS SHALL BE TURNED OVER TO
THE OWNER.
REMOVE ALL EXISTING RECEPTACLES, COMMUNICATION
OUTLETS, NURSE CALL, AND ALL ASSOCIATED WIRING FROM
ALL SECTIONS OF EXISTING WALLS OR PARTITIONS THAT ARE
TO REMAIN.
NO WORK REQUIRED IN THIS ROOM OR AREA.
EXISTING DATA EQUIPMENT IN THIS ROOM TO REMAIN.
EXISTING DATA EQUIPMENT RACK TO REMAIN.
EXISTING ELECTRICAL PANELS IN THIS ROOM TO REMAIN.
2 13
PLAN
NORTH
L32
L22
W2
L23
L23 L22
L33 L33
L22
L22 L22
L22
L22
L32
L32
L32
L32
L32 L32
L32 L32
L32 L32
L6 L6
L32 L32
L32
L32
W2
L33 L33
L33 L33
L22 L22
L33 L33
L33 L33
L33 L33
L33 L33
L33 L33
L32
L32
W2
L34
L34 L34
L34 L34 L34 L34 L34 L34
L34
L34 L34 L34 812101210 10
L34
L34 L34 L34 L34
L34
C4
C4
L34
L24
L24
L24
L24
L24
L34 L34 L34
L34
L34
L34
L34
L34
L24
L24
L34
L34
L34
L34
2DC-1
2DC-3
2DEM-16
2DEM-18
2DEM-20
2DEM-22
2DEM-24
2DC-30
2DC1-18 2DC1-20
2DC1-22
2DC1-24
2EM9-7
12 10
"2DC"
2DC1
"2L1A1C"
"2DEM"
ELEV.
EQUIPMENT
ELEC.
OFFICE3177
ELEV. 3185
IT
HAC
SOILED
CLEAN
SUPPLY
MED GAS
EDUCATOR OFC.
3190L
LINEN
HALL
CORR
STAIR #6
CORR
FAC
STAIR #5
3162A
FAC
OFFICE
EXISTING
CONFERENCE
3101A
EXISTING
BREAK
TOILET
3020A
STAFF TLT
3100A
ELEC.
UM NURSE
UM NURSE
UM NURSE
SOILED
LINEN
EQUIPMENT
EQUIP.
PAT. RM
TLT
3086A
PAT. RM
IT & ELEC.
PAT. RM
TLT
3015A
CORR
MED GAS
ASST CHIEF NURSE
3190D
PHARM/PHARM TECH
3190B
SOCIAL WORKERS
3190C
UM NURSES
3190E
NURSE MANAGER
3190J
CHIEF
3190G
CHIEF NURSE
3190H
UNASSIGNED
3190F
STAFF
LOCKER
PAT. TLT
54 SF
PAT. RM.
MECH
HAC
CLEAN
LINEN
STORAGE
NOURISHMENT
STOR.
STOR.
PAT. RM.
PAT. TLT.
PAT. RM.
STAFF
WORKROOM
NURSE
STATION
NURSE MANAGER
3190I
COPY/FAX SUPLIES
3190A
CONSULT
3190K
3088A
ELEC.
NURSE
STATION
TLT
3087A
WAITING
TLT
3018A
TLT
3019A
TLT
3016ATLT
3014A
TLT.
3013A
PAT. RM.
PAT. RM.
3018PAT. RM
3017PAT. RM
PAT. RM.
PAT. RM
TLT
TLT
TLT
3017A
ALTERNATE BID
DEDUCT #1
"2C1A1C"
EXISTING LIGHTING TO REMAIN.
NOT USED.
CONNECT TO FAUCET/ TOILET SENSORS. SEE SHEET EP103
PLAN '1' FOR CONTINUATION.
KEYED NOTES
GENERAL NOTES
A. FOR DRAWING CLARITY, CONDUIT ROUTING FOR
EGRESS/LIFE SAFETY LIGHTING IS NOT SHOWN. ALL LIFE
SAFETY BRANCH LIGHTING FIXTURES AND EXIT SIGNS ON
THE DRAWING SHALL ORIGINATE FROM PANEL '2L1A1C'.
THE NUMBER ADJACENT TO EACH FIXTURE AND EXIT SIGN
INDICATES THE CIRCUIT NUMBER.
B. THIS PROJECT IS TO BE ACCOMPLISHED IN PHASES AS
INDICATED ON THE ARCHITECTURAL PLANS, AND IT IS THE
INTENT OF THESE DOCUMENTS THAT THE ELECTRICAL
WORK FOLLOW, WHERE POSSIBLE, THIS PRESCRIBED
PHASING.
THIRD FLOOR PLAN -
LIGHTING
EL103
RAH SUB
PLAN
NORTH
3 13
LIGHTING DETAILS
EL701
RAH SUB 4 13
2EM4 (4TH FL)
208V, 125A
FEED FROM ATS 2-2
2EM2 (4TH FL)
208V, 125A
FED FROM ATS 2-1
GFI
GFI
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
CRCR
CR
CR
CR
CR
CR
CR
CR
CR CR
CR
CR
CR
CR
S
S S
S
CR
CR
CR
CR
GFI
2DEM-25,27
2DEM-21,232DEM-17,192DEM-13,152DEM-9,112DEM-5,72DEM-1,3
2DEM-33,35
2DEM-37,39
FTS
FTS
FTS
7 FTS
FTS
FTS
FTS
FTS
FTS
FTS
FTS
FTS
FTS
FTS
2DEM-29,31
FTS
FTS
FTS
FTS
FTS
FTS
FTS
FTS
FTS
CR
2DC-5
2DC-7 2DC-9
2DC-11
2DC-13
2DC-15
2DC-17
2DC-19
2DC-212DC-23
2DC-25
2DC-27
2DC-29
2DC-37
2DC-39
2DC-47
2DC-452DC-43
2DC-18
E 2DEM-8
2DC-20
2ERP-1: 3.2A
120V, 1ɸ
2ERP-1: 3.2A
120V, 1ɸ
2ERP-1: 3.2A
120V, 1ɸ
2ERP-1: 3.2A
120V, 1ɸ
2ERP-1: 3.2A
120V, 1ɸ
FTS
MG
2L1A1C-6
2DC-22
2DC-24
2DC-26
2DC-28
2DC1-7
2DC1-9
2DC1-14 2DC1-17 2DC1-19
2DC1-21
2DC1-23
2DC1-16
2DC-32
2DC-34
ALTERNATE BID
DEDUCT #1
GFI
GFI3161
ELEV.
EQUIPMENT
ELEC.
OFFICE3177
ELEV.
IT
HAC
SOILED
CLEAN3156
SUPPLY
MED GAS
EDUCATOR OFC.
3190L
LINEN
HALL
CORR
STAIR #63163
CORR
FAC
STAIR #5
3162A
FAC
OFFICE
EXISTING
CONFERENCE
3101A
EXISTING
BREAK
TOILET
3020A
STAFF TLT
3100A
ELEC.
UM NURSE
UM NURSE
UM NURSE
SOILED
LINEN
EQUIPMENT
EQUIP.
PAT. RM
3087 TLT
3086A
PAT. RM
IT & ELEC.
PAT. RM
TLT
3015A
CORR
MED GAS
ASST CHIEF NURSE
3190D
PHARM/PHARM TECH
3190B
SOCIAL WORKERS
3190C
UM NURSES
3190E
NURSE MANAGER
3190J
CHIEF
3190G
CHIEF NURSE
3190H
UNASSIGNED
3190F
STAFF
LOCKER
MECH
HAC
CLEAN
LINEN
NOURISHMENT
STOR.
STOR.
PAT. RM.
PAT. TLT.
PAT. RM.
STAFF
WORKROOM
NURSE
STATION
NURSE MANAGER
3190I
COPY/FAX SUPLIES
3190A
CONSULT
3190K
3088A
ELEC.
NURSE
STATION
TLT
3087A
WAITING
TLT
3018A
TLT
3019A
TLT
3016A
TLT
3014A
TLT.
3013A
PAT. RM.
PAT. RM.
PAT. RM
3017PAT. RM
PAT. RM.
PAT. RM
TLT
TLT
TLT
3017A
"2DEM"
2-WMD1-.23FLA
208V, 1Ø
30A F15A
2-CC1: .28 FLA
208V, 1Ø
2DEM-2
2DEM-4
E
2DEM-10
30A F15A
"2DC"
2DC1
"2C1A1C" "2L1A1C"
DUPLEX RECEPTACLE FOR WALL MOUNTED CONDENSATE
PUMP. EXACT LOCATION SHALL BE FIELD DETERMINED WITH
MECHANICAL CONTRACTOR.
CONNECT TO CRITICAL LIGHTING CIRCUIT SERVING THIS
AREA. SEE SHEET EL103 PLAN '1' FOR CONTINUATION .
CONNECTION TO CEILING MOUNTED RADIANT HEATING
PANEL. PROVIDE 20A 1P TOGGLE SWITCH FOR
DISCONNECTION MEANS. RADIANT PANEL BY DIVISION 23.
PROVIDE NEW 20A, 1P CIRCUIT BREAKER IN EXISTING SPACE
2L1A1C-6 TO SERVE NEW MED GAS ALARM PANEL. AIC
RATING TO MATCH EXISTING PANELBOARD RATING.
COORDINATE MOUNTING HEIGHT OF DEVICE WITH OWNER.
KEYED NOTES
GENERAL NOTES
A. ALL DEVICES SHOWN DASHED ARE EXISTING TO REMAIN
UNLESS OTHERWISE NOTED.
B. THIS PROJECT IS TO BE ACCOMPLISHED IN PHASES AS
INDICATED ON THE ARCHITECTURAL PLANS , AND IT IS THE
INTENT OF THESE DOCUMENTS THAT THE ELECTRICAL
WORK FOLLOW, WHERE POSSIBLE, THIS PRESCRIBED
PHASING.
THIRD FLOOR PLAN -
POWER
EP103
RAH SUB
PLAN
NORTH
5 13
EXIST'G
PNL. "GA"
EXIST'G
PNL.
"2EMGA"
EXIST'G
ATS 2-8
EXIST'G
PNL.
"2EM8"
NEW PNL. "2EM8A"
MOUNTED ON UNI-STRUT
NEW MECHANICAL AHU
LOCATED ON THE FOURTH
FLOOR ROOF
2EM8A- 1,3,5
3#6,1#10G,1"C
2EM8A- 7,9,11
3#6,1#10G,1"C
2EM8A- 2,4,6
3#8,1#10G,1"C
2EM8A- 8,10,12
3#8,1#10G,1"C
WP/GFI
HARDWIRED
CONNECTION FOR
AHU LIGHTING AND
CONTROLS
(2)SAF: 7.5HP
208V, 3Ø
(2)RAF: 5HP
208V, 3Ø
2EM8A-16
2#10,1#10G, 3/4"C
2EM8A-14
2#10,1#10G, 3/4"C
2-ACC2: 7.5 RLA
208V, 1Ø
30A F15A
2EM8A-13,15
2#10,1#10G, 3/4"C
EXISTING
3RD FLOOR ROOF
EXISTING
3RD FLOOR ROOF
EXISTING
PENTHOUSE
2-ACC2: 7.5 RLA
208V, 1Ø
30A F15A
2EM8A-17,19
2#10,1#10G, 3/4"C
EXISTING
5TH FLOOR ROOF
GENERAL NOTES
A. ALL DEVICES SHOWN DASHED ARE EXISTING TO REMAIN
UNLESS OTHERWISE NOTED.
B. ALL DEVICES SHOWN SOLID ARE NEW.
ROOF/PENTHOUSE FLOOR
PLAN - POWER
EP104
RAH SUB
PLAN
NORTH
6 13
ELECTRICAL DETAILS
EP701
RAH SUB 7 13
ELEV.
EQUIPMENT
ELEC.
OFFICE3177
ELEV. 3185
IT
HAC
3170SOILED
CLEAN
SUPPLY
MED GAS
EDUCATOR OFC.
3190L
LINEN
HALL
CORR
STAIR #63163
CORR
FAC
STAIR #5
3162A
FAC
OFFICE
EXISTING
CONFERENCE
3101A
EXISTING
BREAK
TOILET
3020A
STAFF TLT
3100A
ELEC.
UM NURSE
UM NURSE
UM NURSE
SOILED
LINEN
EQUIPMENT
EQUIP.
PAT. RM
TLT
3086A
PAT. RM
IT & ELEC.
PAT. RM
TLT
3015A
CORR
MED GAS
ASST CHIEF NURSE
3190D
PHARM/PHARM TECH
3190B
SOCIAL WORKERS
3190C
UM NURSES
3190E
NURSE MANAGER
3190J
CHIEF
3190G
CHIEF NURSE
3190H
UNASSIGNED
3190F
STAFF
LOCKER
PAT. TLT
54 SF
PAT. RM.
MECH
HAC
CLEAN
LINEN
STORAGE
NOURISHMENT
STOR.
STOR.
PAT. RM.
PAT. TLT.
PAT. RM.
STAFF
WORKROOM
NURSE
STATION
NURSE MANAGER
3190I
COPY/FAX SUPLIES
3190ACONSULT
3190K
3088A
ELEC.
NURSE
STATION
TLT
3087A
WAITING
TLT
3018A
TLT
3019A
TLT
3016ATLT
3014A
TLT.
3013A
PAT. RM.
PAT. RM.
3018PAT. RM
3017PAT. RM
PAT. RM.
3014PAT. RM
TLT
TLT
TLT
3017A
3153 3156
31563154
31723169
ALTERNATE BID
DEDUCT #1
THIRD FLOOR PLAN -
AUXILIARY SYSTEMS
EY103
RAH SUB
PLAN
NORTH
8 13
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED LIPPED
STEEL MOUNTING
CHANNEL
REFER TO PLANS FOR QUANTITY
& SIZE OF CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL LONGER THAN 915mm
(36") SHALL BE INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER
SPECIFICATION 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS. FIELD
VERIFY EXACT CONDITIONS.
3. REFER TO SPECIFICATION SECTION 13 05 41 FOR SEISMIC RESTRAINT
REQUIREMENTS .
LENGTH AS REQUIRED
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN GALVANIZED
THREADED ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
CONDUIT, TYP MINERAL WOOL
(FIRMLY PACKED)
PROVIDE FIRE-STOP SEALANT PER
SECTION 07 84 00 FIRESTOPPING
(3/8") MAX
9.52mm
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT FITTING
SPRING
NUT, TYP
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL,
TYP.
FLOOR SLAB, TYP. STEEL EXPANSION ANCHOR, TYP
PROVIDE ANGLE TO WALL TO
PREVENT LATERAL
MOVEMENT
EZ PATH OR EQUIVALENT
FIRE RATED PATHWAY
FIRE RATED WALL;
REFER TO
ARCHITECTURAL PLANS
FOR LOCATIONS
4" SLEEVE WITH
CONNECTORS
AND BUSHINGS
NOTES:
1. ALL DATA AND COMMUNICATIONS CABLING SHALL UTILIZE EITHER A 4" SLEEVE FOR NON RATED
WALLS OR A FIRE RATED INTUMESCENT PATHWAY DEVICE WHEREVER CABLES PASS THROUGH
FIRE RATED WALLS. SEE SPECIFICATIONS FOR ADDITIONAL FIRE RATED DEVICES REQUIREMENTS.
GYPBOARD WALL
SECURE J-HOOK CABLE
HANGER TO WALL STUDS
WITH SHEET METAL SCREWS (TYP)
CABLE SAG NO
GREATER THAN
12"
METAL WALL STUD (TYP)
CABLE HANGERS
SPACED NO MORE THAN
48" ON CENTER
COMMUNICATIONS
DETAILS
EY701
RAH SUB 9 13
TLT
3015A
TLT
3014A PAT. RM
PAT. RM.
D4 D4
W2
L6
NL
L42
L42
L6 L6
L6
L6
L6
L42
L42
L6
NLL6
D4 D4
W2
L6
L6 L6
L6
#1
#2
#2
#1
TOILET
3020A
PAT. RM.
NL
L6
D4
L6
W2
L42
L42
L6
L6
L6
L6
L6
L6 a a a b
#1
#2
SEE DETAIL 8
THIS SHEET
(TYPICAL)
TLT
3015A
TLT
3014A PAT. RM
PAT. RM.
CC
NN
TLT
3015A
TLT
3014A PAT. RM
PAT. RM.
NC
TD
NURSE CALL
CONNECTION TO
OWNER FURNISHED
HEADWALL SYSTEM
TELEDATA
CONNECTION TO
OWNER FURNISHED
HEADWALL SYSTEM
NC
TD
NURSE CALL
CONNECTION TO
OWNER FURNISHED
HEADWALL SYSTEM
TELEDATA
CONNECTION TO
OWNER FURNISHED
HEADWALL SYSTEM
TOILET
3020A
PAT. RM.
C
N
TOILET
3020A
PAT. RM.
NC
TD
NURSE CALL
CONNECTION TO
OWNER FURNISHED
HEADWALL SYSTEM
TELEDATA
CONNECTION TO
OWNER FURNISHED
HEADWALL SYSTEM
MED GASES
E1 E1 E1
N1 N1
E2 E2
E2
CONNECTION FOR
PATIENT LIFT
E1
E2
LIGHTING IN
HEADWALL SYSTEM
PATIENT LIFT
RECEPTACLES
(TYPICAL)
DATA OUTLET
LIGHT SWITCHES
NURSE CALL
CODE BLUE
KP
#2
KP
#1
LOW VOLTAGE WIRING TO NURSE
CALL FOR PILLOW SPEAKER CONTROL
LOW VOLTAGE WIRING FOR AMBIENT
AND EXAM LIGHT DIMMING
LIGHT MASTER CONTROLLER
LOCATED ABOVE CEILING
120V - 277V
POWER SOURCE
OVER BED
PATIENT LIGHT
LM
AMICO LIGHT MASTER.
MULTIFUNCTION DIMMING SWITCH
BASIS OF DESIGN:
NURSE CALL
PATIENT STATION
ENLARGED PLANS
E401
RAH SUB
KEYED NOTES:
120V NORMAL POWER LIGHTING CIRCUIT. SEE SHEET EL103 PLAN '1' FOR CIRCUITING INFORMATION.
120V CRITICAL POWER LIGHTING CIRCUIT. SEE SHEET EL103 PLAN '1' FOR CIRCUITING INFORMATION.
JUNCTION BOX FOR LIGHTING IN PREFABRICATED FURNISHED HEADWALL SYSTEM.
KEYED NOTES:
120V NORMAL POWER LIGHTING CIRCUIT. SEE SHEET EL103 PLAN '1' FOR CIRCUITING INFORMATION.
120V CRITICAL POWER LIGHTING CIRCUIT. SEE SHEET EL103 PLAN '1' FOR CIRCUITING INFORMATION.
JUNCTION BOX FOR LIGHTING IN PREFABRICATED FURNISHED HEADWALL SYSTEM.
KEYED NOTES:
120V NORMAL POWER CIRCUIT. SEE SHEET EP103 PLAN '1' FOR CIRCUITING INFORMATION.
120V CRITICAL POWER CIRCUIT. SEE SHEET EP103 PLAN '1' FOR CIRCUITING INFORMATION.
POWER CONNECTION TO PREFABRICATED HEADWALL SYSTEM.
COORDINATE MOUNTING HEIGHT OF DEVICE WITH OWNER.
SEE DETAIL 8
THIS SHEET
(TYPICAL)
KEYED NOTES:
120V NORMAL POWER CIRCUIT. SEE SHEET EP103 PLAN '1' FOR CIRCUITING INFORMATION.
120V CRITICAL POWER CIRCUIT. SEE SHEET EP103 PLAN '1' FOR CIRCUITING INFORMATION.
POWER CONNECTION TO PREFABRICATED HEADWALL SYSTEM.
COORDINATE MOUNTING HEIGHT OF DEVICE WITH OWNER.
N1 = DENOTES NORMAL CIRCUIT 1
E1 = DENOTES EMERGENCY CIRCUIT 1
E2 = DENOTES EMERGENCY CIRCUIT 2
KEYED NOTES:
COORDINATE MOUNTING HEIGHT OF DEVICE WITH OWNER.
KEYED NOTES:
COORDINATE MOUNTING HEIGHT OF DEVICE WITH OWNER.
6 13
POWER RISER DIAGRAM
E501
RAH SUB
"2C1A1C"
EXISTING ELECTRICAL ROOM 3177
THIRD LEVEL
EXISTING ELECTRICAL ROOM 3165A EXISTING ELECTRICAL ROOM 3162
EXISTING ELECTRICAL ROOM
EXIST'G
PNL.
120/208V
EMERGENCY BR.
(200k SCAR)
PANEL
"2DEM"
225A
"2DC2"
EXIST'G
PNL.
120/208V
NORMAL BR.
(22k SCAR)
225A
"2DC"
EXIST'G
PNL.
120/208V
NORMAL BR.
(22k SCAR)
225A MLO
"2DC1"
EXIST'G
PNL.
120/208V
NORMAL BR.
(10k SCAR)
100A
FOURTH LEVEL
GROUND LEVEL
EXISTING ELECTRICAL ROOM G040
"2AY"
EXIST'G
PNL.
120/208V
NORMAL BR.
(22k SCAR)
600A
"2EM4"
EXIST'G
PNL.
120/208V
LIFE SAFETY BR.
125A
TO ATS 2-2
ELECTRICAL ROOM G032
120/208V
EMERGENCY BR.
100A
PENTHOUSE
"2GA"
EXIST'G
PNL.
PANEL
"2EM8A"
225A MLO
120/208V
EQUIPMENT
BR.
PROVIDE NEW 100A 3P CIRCUIT BREAKER TO EXISTING
PANEL. AIC RATING SHALL MATCH EXISTING PANEL RATING.
REMOVE EXISTING 150A 3P BREAKER AND ASSOCIATED
CONDUIT AND WIRING AND REPLACE WITH NEW 225A 3P
BREAKER. AIC RATING TO MATCH EXISTING PANEL RATING.
CONTRACTOR TO FIELD VERIFY PANEL AIC RATING.
REMOVE EXISTING 100A 3P BREAKER AND ASSOCIATED
CONDUIT AND WIRING AND REPLACE WITH NEW 225A 3P
BREAKER. AIC RATING TO MATCH EXISTING PANEL RATING.
CONTRACTOR TO FIELD VERIFY PANEL AIC RATING.
REMOVE EXISTING FEEDER CONDUIT AND WIRING.
ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE DESIGN
ENGINEER A MINIMUM OF 7 DAY LOAD RECORDING FOR THIS
PANEL PRIOR TO ANY WORK BEING DONE. THE RECORDING
SHALL INCLUDE THE AMPERAGE, AND VOLTAGE OF ALL (3)
THREE FEEDER PHASES SERVING THE PANEL.
A. ALL ITEMS SHOWN DASHED ARE EXISTING TO REMAIN
UNLESS OTHERWISE NOTED.
B. ALL ITEMS SHOWN SOLID ARE NEW.
C. ALL WIRE SIZES SHOWN ON EXISTING FEEDERS WERE
OBTAINED FROM THE HOSPITAL'S MASTER RISER SINGLE
LINE DIAGRAMS.
EXIST'G
ATS 2-8
EQUIP. BR.
120/208V
NORMAL BR.
(22k SCAR)
EXIST'G
GEN.DIST.
120/208V (10k SCAR)
120/208V
EQUIPMENT
BR.
(10k SCAR)
"2EM8"
100A MLO
600A MLO
225A 4P
600A MLO
"2EMGA"
EXIST'G
PNL.
EXISTING NORMAL
SWBD
"2N2"
3,000A (100k SCAR)
500A
EXISTING ELECTRICAL ROOM G032
"2EMB"
EXIST'G
PNL.
120/208V
NORMAL BR.
(10k SCAR)
600A400A
3#4/0,1#4G, 2"C 3#4/0,1#4G, 2"C
3#1,1#8G, 1-1/4"C 3#4/0,1#4G, 2"C
200A
4#1,1#8G, 1-1/2"C
(2) #300
(2) #300
(1) #3/0
(1) #3
(1) #6
EXISTING
70A/3P C/B
EXISTING
100A/3P C/B
"2C1A"
EXIST'G
PNL.
120/208V
NORMAL BR.
(200k SCAR)
600A 300A
(1)#400
FEEDER
RISER
(1)#4/0
11 13
LIGHTING FIXTURE SCHEDULE
E601
RAH SUB
GENERAL NOTES
1. ALL UNDERCABINET LIGHT FIXTURES SHALL HAVE SOLID
FRONTS WITH ACRYLIC PRISMATIC DIFFUSERS. UNLESS
OTHERWISE NOTED ON FIXTURE SCHEDULE.
2. ALL LED DOWNLIGHTS SHALL HAVE A COLOR TEMPERATURE
OF 40K AND 80 CRI. UNLESS OTHERWISE NOTED ON
FIXTURE SCHEDULE.
3. ALL STRIP AND INDUSTRIAL LIGHTING FIXTURES SHALL BE
PROVIDED WITH WIREGUARDS AND HAVE 10% UPLIGHT.
4. THE INTERIOR OF ALL TROFFERS SHALL BE FINISHED WHITE
IN COLOR UTILIZING BAKED DRY POLYESTER POWDER
PAINT.
5. ALL RECESSED DOWNLIGHTS SHALL HAVE WHITE TRIMS
UNLESS OTHERWISE NOTED ON THE LIGHTING FIXTURE
SCHEDULE.
6. ALL EXIT SIGNS SHALL HAVE DIE CAST ALUMINUM HOUSINGS
WITH STENCIL FACE OF DIE FORMED ALUMINUM WITH RED
BACKPLATE OF HIGH IMPACT RESISTANT PLASTIC. EXIT
SIGNS SHALL HAVE DOWNLIGHT PANELS AND DIRECTIONAL
ARROWS WHERE SHOWN ON THE PLANS. WHERE SELF
CONTAINED BATTERY UNITS ARE SPECIFIED ON THE
FIXTURE SCHEDULE, PROVIDE 90 MINUTE MINIMUM LEAD
CALCIUM BATTERY WITH TEST SWITCH ON THE EXIT SIGN.
7. CATALOG NUMBERS LISTED ON THE FIXTURE SCHEDULE DO
NOT NECESSARILY INCLUDE ACCESSORIES SPECIFIED IN
THE FIXTURE DESCRIPTION. THE CONTRACTOR SHALL
PROVIDE ALL SPECIFIED FEATURES WHETHER THEY ARE
INCLUDED IN THE CATALOG NUMBER OR NOT.
8. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING
LIGHTING FIXTURES THAT FIT THE ACTUAL CEILING BEING
PROVIDED. VERIFY WITH THE GENERAL CONTRACTOR THAT
FIXTURES SPECIFIED WILL FIT CEILINGS PRIOR TO
SUBMITTING THE SHOP DRAWINGS AND MAKE
ADJUSTMENTS AS REQUIRED. NO EXTRA PAYMENT WILL BE
PROCESSED FROM CHANGES DERIVED FOR FAILURE TO
COMPLY WITH THIS REQUIREMENT.
9. THE MANUFACTURERS AND CATALOG NUMBERS OF THE
LIGHTING FIXTURES SPECIFIED ARE INTENDED TO
ESTABLISH THE LEVEL OF FIXTURE QUALITY AND FUNCTION
DESIRED. LIGHTING FIXTURES OF EQUAL OR BETTER
QUALITY MAY BE SUBMITTED SUBJECT TO PRIOR APPROVAL
BY THE A/E.
10. NOT ALL LIGHTING FIXTURES SHOWN ON THE LIGHTING
FIXTURE SCHEDULE MAY APPEAR ON THE CONTRACT
DOCUMENTS.
11. WHERE ONLY ONE MANUFACTURER IS LISTED, ANY
SUBSTITUTION TO BE CONSIDERED MUST MEET BOTH THE
CONSTRUCTION AND PERFORMANCE SPECIFICATIONS OF
THE LISTED MANUFACTURER, 10 DAYS PRIOR TO BID DATE.
ANY SUBSTITUTION MUST BE SIMILAR IN SIZE AND
APPEARANCE TO THE LISTED MANUFACTURER'S PRODUCT.
12 13
PANEL SCHEDULES
E602
RAH SUB
2L1A1C 2C1A1C 2DEM
2DC 2DC1 2EM8A
NOTE: CONTRACTOR SHALL INCLUDE FINAL ROOM NAME(S) AND NUMBER(S) ASSOCIATED
WITH EACH CIRCUIT BEING PROVIDED IN THE PANEL SCHEDULE (I.E. LIGHTING - PAT RM
3013, ETC…).
13 13