H.H. McGuire VA Medical Center 100% Bid Documents
Community Living Center Expansion January 26, 2018
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 1
SECTION 27 11 00
COMMUNICATIONS EQUIPMENT ROOM FITTINGS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This Section specifies the furnishing, installing, certification, testing, and guaranty of a complete and operating Voice and Digital
Cable Distribution System (here-in-after referred to as “the System”), and associated equipment and hardware to be installed in the VA Medical
Center, Out Patient Clinic, Nursing Home Care Unit, Domiciliary, here-in-after referred to as “the Facility”. The System shall include, but not be limited to: equipment cabinets, interface enclosures, and relay racks; necessary combiners, traps, and filters; and necessary passive devices such as: splitters, couplers, cable “patch”, “punch down”, and cross-connector blocks or devices, voice and data distribution sub-systems, and associated hardware. The System shall additionally include, but not be limited to: telecommunication closets (TC);
telecommunications outlets (TCO); copper and fiber optic, and analog radio frequency (RF) systems coaxial distribution cables, connectors, “patch” cables, and/or “break out” devices.
B. The System shall be delivered free of engineering, manufacturing, installation, and functional defects. It shall be designed, engineered and installed for ease of operation, maintenance, and testing.
C. The term “provide”, as used herein, shall be defined as: designed, engineered, furnished, installed, certified, and tested, by the
Contractor.
D. The Voice and Digital Telecommunication Distribution Cable Equipment and System provides the media which voice and data information travels over and connects to the Telephone System which is defined as an
Emergency Critical Care Communication System by the National Fire
Protection Association (NFPA). Therefore, since the System connects to or extends the telephone system, the System’s installation and operation shall adhere to all appropriate National, Government, and/or
Local Life Safety and/or Support Codes, which ever are the more stringent for this Facility. At a minimum , the System shall be installed according to NFPA, Section 70, National Electrical Code
(NEC), Article 517 and Chapter 7; NFPA, Section 99, Health Care
Facilities, Chapter 3-4; NFPA, Section 101, Life Safety Code, Chapters
7, 12, and/or 13; Joint Commission on Accreditation of Health Care
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 2
Organization (JCAHCO), Manual for Health Care Facilities, all necessary
Life Safety and/or Support guidelines; this specification; and the original equipment manufacturer's (OEM) suggested installation design, recommendations, and instructions. The OEM and Contractor shall ensure that all management, sales, engineering, and installation personnel have read and understand the requirements of this specification before the System is designed, engineered, delivered, and provided.
E. The VA Project Manager (PM) and/or if delegated, Resident Engineer (RE) are the approving authorities for all contractual and mechanical changes to the System. The Contractor is cautioned to obtain in writing, all approvals for system changes relating to the published contract specifications and drawings, from the PM and/or the RE before proceeding with the change.
F. System Performance:
1. At a minimum, the System shall be able to support the following voice and data operations for Category 6 Certified Telecommunication
Service:
a. Provide the following interchange (or interface) capabilities:
1) Basic Rate (BRI).
2) Primary Rate (PRI).
b. ISDN measured at:
1) Narrow Band BRI:
a) B Channel: 64 kilo-Bits per second (kBps), minimum.
b) D Channel: 16 kBps, minimum.
c) H Channel: 384 kBps, minimum.
2) Narrow Band PRI:
a) B Channel: 64 kBps, minimum.
b) D Channel: 64 kBps, minimum.
c) H Channel: 1,920 kBps, minimum.
3) Wide (or Broad) Band: All channels: 140 mega(m)-Bps, minimum, capable to 565 mBps at “T” reference.
c. System Sensitivity: Satisfactory service shall be provided for at least 3,000 feet for all voice and data and analog RF locations.
2. At a minimum the System shall support the following operating parameters:
a. EPBX connection:
1) System speed: 1.0 gBps per second, minimum.
2) Impedance: 600 Ohms.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 3
3) Cross Modulation: -60 deci-Bel (dB).
4) Hum Modulation: -55 dB.
5) System data error: 10 to the -10 Bps, minimum.
6) Loss: Measured at the frame output with reference Zero (0) deciBel measured (dBm) at 1,000 Hertz (Hz) applied to the frame input.
a) Trunk to station: 1.5 dB, maximum.
b) Station to station: 3.0 dB, maximum.
c) Internal switch crosstalk: -60 dB when a signal of + 10 deciBel measured (dBm), 500-2,500 Hz range is applied to the primary path.
d) Idle channel noise: 25 dBm “C” or 3.0 dBm “O” above reference (terminated) ground noise, whichever is greater.
e) Traffic Grade of Service for Voice and Data:
(1) A minimum grade of service of P-01 with an average traffic load of 7.0 CCS per station per hour and a traffic overload in the data circuits will not interfere with, or degrade, the voice service.
(2) Average CCS per voice station: The average CCS capacity per voice station shall be maintained at 7.0 CCS when the
EPBX is expanded up to the projected maximum growth as stated herein.
b. Telecommunications Outlet (TCO):
1) Voice:
a) Isolation (outlet-outlet): 24 dB.
b) Impedance: 600 Ohms, balanced (BAL).
c) Signal Level: 0 deciBel per mili-Volt (dBmV) + 0.1 dBmV.
d) System speed: 100 mBps, minimum.
e) System data error: 10 to the -6 Bps, minimum.
2) Data:
a) Isolation (outlet-outlet): 24 dB.
b) Impedance: 600 Ohms, BAL.
c) Signal Level: 0 dBmV + 0.1 dBmV.
d) System speed: 120 mBps, minimum.
e) System data error: 10 to the -8 Bps, minimum.
3) Fiber optic:
a) Isolation (outlet-outlet): 36 dB.
b) Signal Level: 0 dBmV + 0.1 dBmV.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 4
c) System speed: 540 mBps, minimum.
d) System data error: 10 to the -6 bps, minimum.
1.2 RELATED WORK
A. Specification Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND
SAMPLES.
B. Specification Section 27 05 11, REQUIREMENTS FOR COMMUNICATIONS
INSTALLATIONS.
C. Specification Section 27 05 33, RACEWAYS AND BOXES FOR COMMUNICATIONS
SYSTEMS.
D. Specification Section 27 10 00, STRUCTURED CABLING.
E. Specification Section 26 27 26, WIRING DEVICES.
F. Specification Section 27 05 26, GROUNDING AND BONDING FOR
COMMUNICATIONS SYSTEMS.
G. Specification Section 26 41 00, FACILITY LIGHTNING PROTECTION.
H. Specification Section 27 32 41, TWO-WAY RADIO EQUIPMENT.
I. Specification Section 27 31 00, VOICE COMMUNICATIONS SWITCHING AND
ROUTING EQUIPMENT.
J. Specification Section 27 31 31, VOICE COMMUNICATIONS SWITCHING AND
ROUTING EQUIPMENT - EXTENSION.
L. Specification Section 27 51 16, PUBLIC ADDRESS AND MASS NOTIFICATION
SYSTEMS.
M. Specification Section 27 41 31, MASTER ANTENNA TV EQUIPMENT AND
SYSTEMS.
N. H-088-C3, VA HANDBOOK DESIGN FOR TELEPHONE SYSTEMS
1.3 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in text by basic designation only. Except for a specific date given the issue in effect
(including amendments, addenda, revisions, supplements, and errata) on the date the system’s submittal is technically approved by VA, shall be enforced.
B. National Fire Protection Association (NFPA):
70 NATIONAL ELECTRICAL CODE (NEC)
75 Protection of Electronic Computer/Data Processing
Equipment
77 Recommended Practice on Static Electricity
Standard for Health Care Facilities
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 5
101 Life Safety Code
1221 Emergency Services Communication Systems
C. Underwriters Laboratories, Inc. (UL):
65 Wired Cabinets
96 Lightning Protection Components
96A INSTALLATION REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS
467 Grounding and Bonding Equipment
497/497A/497B PROTECTORS FOR PAIRED CONDUCTORS/
COMMUNICATIONS CIRCUITS/DATA COMMUNICATIONS
AND FIRE ALARM CIRCUITS
884 Underfloor Raceways and Fittings
D. ANSI/EIA/TIA Publications:
568B Commercial Building Telecommunications Wiring
Standard
569B Commercial Building Standard for
Telecommunications Pathways and Spaces
606A ADMINISTRATION STANDARD FOR THE
TELECOMMUNICATIONS INFRASTRUCTURE OF
COMMERCIAL BUILDINGS
607A Grounding and Bonding Requirements for
Telecommunications in Commercial Buildings
758 Grounding and Bonding Requirements for
Telecommunications in Commercial Buildings
E. Lucent Technologies: Document 900-200-318 “Outside Plant Engineering
Handbook”.
F. International Telecommunication Union – Telecommunication
Standardization Sector (ITU-T).
G. Federal Information Processing Standards (FIPS) Publications.
H. Federal Communications Commission (FCC) Publications: Standards for telephone equipment and systems.
I. United States Air Force: Technical Order 33K-l-lOO Test Measurement and
Diagnostic Equipment (TMDE) Interval Reference Guide.
J. Joint Commission on Accreditation of Health Care Organization (JCAHO):
Comprehensive Accreditation Manual for Hospitals.
K. National and/or Government Life Safety Code(s): The more stringent of each listed code.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 6
1.4 QUALITY ASSURANCE
A. The authorized representative of the OEM, shall be responsible for the design, satisfactory total operation of the System, and its certification.
B. The OEM shall meet the minimum requirements identified in Paragraph
2.1.A. Additionally, the Contractor shall have had experience with three or more installations of systems of comparable size and complexity with regards to coordinating, engineering, testing, certifying, supervising, training, and documentation. Identification of these installations shall be provided as a part of the submittal as identified in Paragraph 1.5.
C. The System Contractor shall submit certified documentation that they have been an authorized distributor and service organization for the
OEM for a minimum of three (3) years. The System Contractor shall be authorized by the OEM to certify and warranty the installed equipment.
In addition, the OEM and System Contractor shall accept complete responsibility for the design, installation, certification, operation, and physical support for the System. This documentation, along with the
System Contractor and OEM certification must be provided in writing as part of the Contractor’s Technical Submittal.
D. All equipment, cabling, terminating hardware, TCOs, and patch cords shall be sourced from the certifying OEM or at the OEM’s direction, and support the System design, the OEM’s quality control and validity of the OEM’s warranty.
E. The Contractor’s Telecommunications Technicians assigned to the System shall be fully trained, qualified, and certified by the OEM on the engineering, installation, and testing of the System. The Contractor shall provide formal written evidence of current OEM certification(s) for the installer(s) as a part of the submittal or to the RE before being allowed to commence work on the System.
1.5 SUBMITTALS
A. Provide submittals in accordance with Specification Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. The RE shall retain one copy for review and approval.
1. If the submittal is approved the RE shall retain one copy for
Official Records and return three (3) copies to the Contractor.
2. If the submittal is disapproved, three (3) copies will be returned to the Contractor with a written explanation attached that indicates
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 7
the areas the submittal deviated from the System specifications. The
RE shall retain one copy for Official Records.
B. Environmental Requirements: Technical submittals shall confirm the environmental specifications for physical TC areas occupied by the
System. These environmental specifications shall identify the requirements for initial and expanded system configurations for:
1. Floor loading for batteries and cabinets.
2. Minimum floor space and ceiling heights.
3. Minimum size of doors for equipment passage.
4. Power requirements: The Contractor shall provide the specific voltage, amperage, phases, and quantities of circuits required.
5. Air conditioning, heating, and humidity requirements. The Contractor shall identify the ambient temperature and relative humidity operating ranges required preventing equipment damage.
6. Air conditioning requirements (expressed in BTU per hour, based on adequate dissipation of generated heat to maintain required room and equipment standards).
7. Proposed floor plan, based on the expanded system configuration of the bidder's proposed EPBX for this FACILITY.
8. Conduit size requirement (between main TC, computer, and console rooms).
9. Main trunk line and riser pathways, cable duct, and conduit requirements between each MTC, TC, and TCO.
C. Documents: The submittal shall be separated into sections for each subsystem and shall contain the following:
1. Title page to include:
a. VA Medical Center.
b. Contractor’s name, address, and telephone (including FAX) numbers.
c. Date of Submittal.
d. VA Project No.
2. List containing a minimum of three locations of installations of similar size and complexity as identified herein. These locations shall contain the following:
a. Installation Location and Name.
b. Owner’s or User’s name, address, and telephone (including FAX) numbers.
c. Date of Project Start and Date of Final Acceptance by Owner.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 8
d. System Project Number.
e. Brief (three paragraphs minimum) description of each system’s function, operation, and installation.
3. Narrative Description of the system.
4. A List of the equipment to be furnished. The quantity, make, and model number of each item is required. Select the required equipment items quantities that will satisfy the needs of the system. Delete equipment items that are not required add additional items required, and renumber section as per system design. The following is the minimum equipment required by the system:
QUANTITY UNIT
As required Cabinet Assembly(s)
As required Environmental Cabinet
As required Distribution/Interface Cabinet
As required Equipment (Radio Relay) Rack
As required Cross Connection (CCS) Systems
As required Audio Alarm Panel
As required TROUBLE ANNUNCIATOR PANEL
As required Lightning Protection System
As required Wire Management System/Equipment
As required Telecommunications Outlets (TCO)
As Required Distribution Cables
As required TCO Connection Cables
As required System Connectors
As required Terminators
As required Distribution Frames
As required Telecommunications Closets (TC)
As required Environmental Requirements
1 ea. Installation Kit
As-required Separate List Containing Each Equipment
Spare(s)
5. Pictorial layouts of each MTC, IMTC, and RTCs; MCCS, IMCCS, VCCS, and HCCS termination cabinet(s), each distribution cabinet layout drawing, and TCO as each is expected to be installed and configured.
6. Equipment technical literature detailing the electrical and technical characteristics of each item of equipment to be furnished.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 9
7. Engineering drawings of the System, showing calculated signal levels at the EPBX output, each input and output distribution point, proposed TCO values, and signal level at each TCO multipin, fiberoptic, and coaxial cable jack.
8. List of test equipment as per paragraph 1.5.D. below.
9. Letter certifying that the Contractor understands the requirements of the SAMPLES Paragraph 1.5.E.
10. Letter certifying that the Contractor understands the requirements of Section 3.2 concerning acceptance tests.
D. Test Equipment List:
1. The Contractor is responsible for furnishing all test equipment required to test the system in accordance with the parameters specified. Unless otherwise stated, the test equipment shall not be considered part of the system. The Contractor shall furnish test equipment of accuracy better than the parameters to be tested.
2. The test equipment furnished by the Contractor shall have a calibration tag of an acceptable calibration service dated not more than 12 months prior to the test. As part of the submittal, a test equipment list shall be furnished that includes the make and model number of the following type of equipment as a minimum:
a. Spectrum Analyzer.
b. Signal Level Meter.
c. Volt-Ohm Meter.
d. Time Domain Reflectometer (TDR) with strip chart recorder (Data and Optical Measuring).
e. Bit Error Test Set (BERT).
f. Camera with a minimum of 60 pictures to that will develop immediately to include appropriate test equipment adapters. A video camera in VHS format is an acceptable alternate.
g. Video Waveform Monitor.
h. Video Vector Scope.
i. Color Video Monitor with audio capability.
j. 100 mHz Oscilloscope with video adapters
E. Samples: A sample of each of the following items shall be furnished to the RE for approval prior to installation.
1. TCO Wall Outlet Box 4" x 4"x 2.5" with:
a. One each telephone (or voice) rj45 jack installed.
b. Two each multi pin data rj45 jacks installed.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 10
c. Cover Plate installed.
d. Fiber optic ST jack(s) installed.
e. RF (F)/video (BNC)/audio (XL)jack(s) installed.
2. Data CCS patch panel, punch block or connection device with RJ45 connectors installed.
3. Telephone CCS system with IDC and/or RJ45 connectors and cable terminal equipment installed.
4. Fiber optic CCS patch panel or breakout box with cable management equipment and “ST” connectors installed.
5. 610 mm (2 ft.) section of each copper cable to be used with cable sweep tags as specified in paragraph 2.4.H and connectors installed.
6. 610 mm (2 ft.) section of each fiber optic cable to be used with cable sweep tags as specified in paragraph 2.4.H and connectors installed.
7. 610 mm (2 ft.) section of each analog RF, video coaxial and audio cable to be used with cable sweep tags as specified in paragraph
2.4.H and connectors installed.
8. Analog video CCS patch panel or breakout box with cable management equipment and “BNC” connectors installed.
9. Analog audio CCS patch panel or breakout box with cable management equipment and “XL” connectors installed.
10. Analog RF patch panel or breakout box with cable management equipment and “F” connectors installed.
F. Certifications:
1. Submit written certification from the OEM indicating that the proposed supervisor of the installation and the proposed provider of the contract maintenance are authorized representatives of the OEM.
Include the individual's exact name and address and OEM credentials in the certification.
2. Submit written certification from the OEM that the wiring and connection diagrams meet National and/or Government Life Safety
Guidelines, NFPA, NEC, UL, this specification, and JCAHCO requirements and instructions, requirements, recommendations, and guidance set forth by the OEM for the proper performance of the
System as described herein. The VA will not approve any submittal without this certification.
3. Preacceptance Certification: This certification shall be made in accordance with the test procedure outlined in paragraph 3.2.B.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 11
G. Equipment Manuals: Fifteen (15) working days prior to the scheduled acceptance test, the Contractor shall deliver four complete sets of commercial operation and maintenance manuals for each item of equipment furnished as part of the System to the RE. The manuals shall detail the theory of operation and shall include narrative descriptions, pictorial illustrations, block and schematic diagrams, and parts list.
H. Record Wiring Diagrams:
1. Fifteen (15) working days prior to the acceptance test, the
Contractor shall deliver four complete sets of the Record Wiring
Diagrams of the System to the RE. The diagrams shall show all inputs and outputs of electronic and passive equipment correctly identified according to the markers installed on the interconnecting cables, Equipment and room/area locations.
2. The Record Wiring Diagrams shall be in hard copy and two compact disk (CD) copies properly formatted to match the Facility’s current operating version of Computer Aided Drafting (AutoCAD) system. The
RE shall verify and inform the Contractor of the version of AutoCAD being used by the Facility.
I. Surveys Required As A Part Of The Technical Submittal: The Contractor shall provide the following surveys that depict various system features and capacities are required in addition to the on site survey requirements described herein. Each survey shall be in writing and contain the following information (the formats are suggestions and may be used for the initial Technical Submittal survey requirements), as a minimum:
1. The required EPBX connections (each CSU shall be compatible with) shall be compatible with the following:
a. Initially connect:
EQUIPPED ITEM CAPACITY WIREDCAPACITY
Main Station Lines
Single Line
Multi Line (Equipped for direct input dial [DID])
Central Office (CO) Trunks
TWO WAY
DID
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 12
Two-way DRTL
Foreign Exchange (FX)
Conference
Radio Paging Access
Audio Paging Access
Off-Premise Extensions
CO Trunk By-pass
CRT w/keyboard
Printers
Attendant Consoles
T-1 Access/Equipment
Maintenance console
b. Projected Maximum Growth: The Contractor shall clearly and fully indicate this category for each item identified in Paragraph
1.4.H.1.a. as a part of the technical submittal. For this purpose, the following definitions and sample connections are provided to detail the system’s capability:
EQUIPPED ITEM CAPACITY WIRED CAPACITY
Servers
PC’s
Projected Maximum Growth
The Contractor shall clearly and fully indicate this category for each item identified in Paragraph 1.4.H.2.a. as a part of the technical submittal.
2. Cable Distribution System Design Plan: A design plan for the entire cable distribution systems requirements shall be provided with this document. A specific cable count shall coincide with the total growth items as described herein. It is the Contractor’s responsibility to provide the Systems entire cable requirements and engineer a distribution system requirement plan using the format of the following paragraph(s), at a minimum:
a. UTP (and/or STP) Requirements/Column Explanation:
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 13
Column Explanation
FROM BUILDING Identifies the building by number, title, or location, and main signal closet or intermediate signal closet cabling is provided from
BUILDING Identifies the building by number, title, or location cabling is to be provided in
TO BUILDING IMC Identifies building main terminal signal closet, by room number or location, to which cabling is provided too, in, and from
FLOOR Identifies the floor by number (i.e. 1st, 2nd, etc.) cabling and TCOs are to be provided
TC ROOM NUMBER Identifies the floor signal closet room, by room number, which cabling shall be provided
ROOM NUMBER Identifies the room, by number, from which cabling and TCOs shall be provided
NUMBER OF CABLE
PAIR
Identifies the number of cable pair required to be provided on each floor designated OR the number of cable pair (VA
Owned) to be retained
NUMBER OF STRANDS
USED/SPARE
Identifies the number of strands provided in each run
b. Fiber Optic Cabling Requirements/Column Explanation:
Column Explanation
FROM BUILDING Identifies the building by number, title, or location, and main signal closet or intermediate signal closet cabling is provided from
TO BUILDING IMC Identifies building, by number, title, or location, to which cabling is provided
FLOOR Identifies the floor by number (i.e. 1st, 2nd, etc.)
TC ROOM NUMBER Identifies the room, by number, from which cabling shall be installed
NUMBER OF STRANDS Identifies the number of strands in each run of fiber optic cable
INSTALLED METHOD Identifies the method of installation in accordance with as designated herein
NOTES Identifies a note number for a special feature or equipment
BUILDING MTC Identifies the building by number or title
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 14
3. Telecommunication Outlets: The Contractor shall clearly and fully indicate this category for each outlet location and compare the total count to the locations identified above as a part of the technical submittal. Additionally, the Contractor shall indicate the total number of spares.
PART 2 - PRODUCTS
2.1 EQUIPMENT AND MATERIALS
A. System Requirements:
1. The System shall provide the following minimum services that are designed in accordance with and supported by an Original Equipment
Manufacturer (OEM), and as specified herein. The System shall provide continuous inter and/or intra-Facility voice and data, service. The System shall be capacity sized so that loss of connectivity to external telephone systems shall not affect the
Facilities operation in specific designated locations. The System shall:
a. Be capable of inter-connecting and functioning fully with the existing Local Telephone Exchange (LEC) Network(s), Federal
Telephone System (FTS) Inter-city Network(s), Inter-exchange
Carriers, Integrated Services Digital Network (ISDN), Electronic
Private Branch Exchange (EPBX) switches, asynchronous/synchronous data terminals and circuits including Automatic Transfer Mode
(ATM), Frame Relay, and local area networks (LAN), at a minimum.
b. Be compatible with and able to provide direct digital connection to trunk level equipment including, but, not limited to: directly accessing trunk level equipment including the telephone system, audio paging, Industry Standard “T” and/or “DS” carrier services and external protocol converters. Additionally, connections to
“T” and/or “DS” access/equipment or Customer Service Units (CSU) that are used in FTS and other trunk applications shall be included in the System design. Provide T-1 access/equipment (or
CSU), as required for use, in FTS and other trunk applications by system design if this equipment is not provided by the existing telephone system and/or will be deactivated by the installation of the System. The Contractor shall provide all T-1 equipment necessary to terminate and make operational the quantity of circuits designated. The CSU's shall be connected to the System’s
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 15
emergency battery power supply. The System shall be fully capable of operating in the Industry Standard “DS” protocol and provide that service when required.
c. Where the System connects to an existing or future telephone system, refer to specification Section 27 31 00, VOICE
COMMUNICATIONS SWITCHING AND ROUTING EQUIPMENT OR specification
Section 27 31 31, VOICE COMMUNICATIONS SWITCHING AND ROUTING
EQUIPMENT - EXTENSION for specific telephone equipment and system operational performance standards.
2. Specific Subsystem Requirements: The System shall consist, as a minimum, of the following independent sub-systems to comprise a complete and functional voice and digital telecommunications cabling system: “Main” (MTC), “intermediate” (IMTC), and “riser” (RTC) TC’s;
“vertical” (or “riser”) trunk cabling system; vertical cross-connection (VCC) cabling systems, and TCO’s with a minimum of three
(3) RJ-45 jacks for the appropriate telephone, Data connections, and additional jacks, connectors, drop and patch cords, terminators, and adapters provided.
a. Telecommunication Closet (TC):
1) There shall be a minimum of one TC for the MTC, each building
IMTC, and each RTC per building floor location. However, in large building(s), where the horizontal distance to the farthest voice and digital work area may exceed 90 Meters (M)
(or 295 feet [ft]), additional TC’s shall be provided as described herein. The maximum DC resistance per cable pair shall be no more than 28.6 Ohms per 305 M (1,000 feet). Each
TC shall be centrally located to cover the maximum amount of local floor space. The TC’s house in cabinets or enclosures, on relay racks, and/or on backboards, various telecommunication data equipment, controllers, multiplexers, bridges, routers, LAN hub(s), telephone cross-connecting, active and passive equipment.
2) Additionally, the TC’s may house fire alarm, nurses call, code one (or blue), video, public address, radio entertainment, intercom, and radio paging equipment. Regardless of the method of installation, mounting, termination, or cross-connecting used, all vertical copper and fiber optic cables shall be terminated on appropriate cross-connection systems (CCS)
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 16
containing patch panel(s), punch blocks, and/or breakout devices provided in enclosures and tested as described herein.
A cable and/or wire management system shall be a part of each
CCS.
a) A minimum of three 110-120 VAC active quad outlets shall be provided, each with “U” grounded receptacles at a minimum of one outlet for each front, side and back wall. These outlets shall be separately protected by an AC circuit breaker provided in the designated Government Emergency
Critical Care AC power panel, that is connected to the
Facilities Emergency AC Power Distribution System. For larger building TC applications, a minimum of one additional quad AC outlet shall be provided for every 800M²
(or 8,000 ft²) of useable floor space. Additional outlets shall be equally spaced along the wall.
b) Climate control shall be provided in each TC 24 hours a day, seven days per week and 52 week per year to prevent failure of electronic components and for mission critical functional applications. The RE are responsible for informing the Contractor regarding the minimum climate control requirements. In identified hostile TC locations where it has been determined (by the RE or Facility Chief
Engineer) that proper TC climate or external signal radiation cannot be properly maintained or controlled, the
Contractor may, at his/her option, provide a minimum of two individual and properly sized self contained climate controlled equipment cabinet enclosures; one designated for voice, and one designated for data , and one additional cabinet designated for analog RF service, in each TC location identified on the drawings, in lieu of providing additional required TC air handling capability.
B. System Performance:
1. At a minimum, the System shall be able to support the following voice and data operations for Category 6 Certified Telecommunication
Service:
a. Provide the following interchange (or interface) capabilities:
1) Basic Rate (BRI).
2) Primary Rate (PRI).
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 17
b. ISDN measured at:
1) Narrow Band BRI.
a) B Channel: 64 kilo-Bits per second (kBps), minimum.
b) D Channel: 16 kBps, minimum.
c) H Channel: 384 kBps, minimum.
2) Narrow Band PRI:
a) B Channel: 64 kBps, minimum.
b) D Channel: 64 kBps, minimum.
c) H Channel: 1,920 kBps, minimum.
3) Wide (or Broad) Band:
a) All channels: 140 mega (m)-Bps, minimum, capable to 565 mBps at “T” reference.
c. ATM operation and interface: ATM 155 mBps measured at VA
Standard.
d. Frame Relay: All stated compliance’s measured at VA Standard.
e. Integrated Data Communications Utility (IDCU) operation and interface: Measured at VA Standard.
f. Government Open Systems Interconnection Profile (GOSSIP) compliant: Measured at VA Standard.
g. Fiberoptic Distributed Data Interface (FDDI): A minimum 100 mBps to a maximum of 1.8 giga(g)-Bps data bit stream speed measured at
VA Standard (shall be Synchronous Optical Network [Sonet] compliant).
h. System Sensitivity: Satisfactory service shall be provided for at least 3,000 feet for all voice and data and analog RF locations.
2. At a minimum the System shall support the following operating parameters:
a. EPBX connection:
1) System speed: 1.0 gBps per second, minimum.
2) Impedance: 600 Ohms.
3) Cross Modulation: -60 deci-Bel (dB).
4) Hum Modulation: -55 Db.
5) System data error: 10 to the -10 Bps, minimum loss measured at the frame output with reference Zero (0) deciBel measured
(dBm) at 1,000 Hertz (Hz) applied to the frame input.
a) Trunk to station: 1.5 dB, maximum.
b) Station to station: 3.0 dB, maximum.
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 18
c) Internal switch crosstalk: -60 dB when a signal of + 10 deciBel measured (dBm), 500-2,500 Hz range is applied to the primary path.
d) Idle channel noise: 25 dBm “C” or 3.0 dBm “O” above reference (terminated) ground noise, whichever is greater.
e) Traffic Grade of Service for Voice and Data:
(1) A minimum grade of service of P-01 with an average traffic load of 7.0 CCS per station per hour and a traffic overload in the data circuits will not interfere with, or degrade, the voice service.
(2) Average CCS per voice station: The average CCS capacity per voice station shall be maintained at 7.0 CCS when the
EPBX is expanded up to the projected maximum growth as stated herein.
b. Telecommunications Outlet (TCO):
1) Voice:
a) Isolation (outlet-outlet): 24 dB.
b) Impedance: 600 Ohms, balanced (BAL).
c) Signal Level: 0 deciBel per mili-Volt (dBmV) + 0.1 dBmV.
d) System speed: 100 mBps, minimum.
e) System data error: 10 to the -6 Bps, minimum.
2) Data:
a) Isolation (outlet-outlet): 24 dB.
b) Impedance: 600 Ohms, BAL.
c) Signal Level: 0 dBmV + 0.1 dBmV.
d) System speed: 120 mBps, minimum.
e) System data error: 10 to the -8 Bps, minimum.
3) Fiber optic:
a) Isolation (outlet-outlet): 36 dB.
b) Signal Level: 0 dBmV + 0.1 dBmV.
c) System speed: 540 mBps, minimum.
d) System data error: 10 to the -6 BPS, minimum.
C. General:
1. All equipment to be supplied under this specification shall be new and the current model of a standard product of an OEM or record. An
OEM of record shall be defined as a company whose main occupation is the manufacture for sale of the items of equipment supplied and which:
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 19
a. Maintains a stock of replacement parts for the item submitted.
b. Maintains engineering drawings, specifications, and operating manuals for the items submitted.
c. Has published and distributed descriptive literature and equipment specifications on the items of equipment submitted at least 30 days prior to the Invitation for Bid.
2. Specifications of equipment as set forth in this document are minimum requirements, unless otherwise stated, and shall not be construed as limiting the overall quality, quantity, or performance characteristics of items furnished in the System. When the
Contractor furnishes an item of equipment for which there is a specification contained herein, the item of equipment shall meet or exceed the specification for that item of equipment.
3. The Contractor shall provide written verification, in writing to the
RE at time of installation, that the type of wire/cable being provided is recommended and approved by the OEM. The Contractor is responsible for providing the proper size and type of cable duct and/or conduit and wiring even though the actual installation may be by another subcontractor.
4. The Telephone Contractor is responsible for providing interfacing cable connections for the telephone, PA, Radio Paging, systems with the System.
5. The telephone equipment and PA interface equipment Radio interface equipment shall be the interface points for connection of the PA
Radio interface cabling from the telephone switch via the system telephone interface unit.
6. Active electronic component equipment shall consist of solid state components, be rated for continuous duty service, comply with the requirements of FCC standards for telephone equipment, systems, and service.
7. All passive distribution equipment shall meet or exceed -80 dB radiation shielding specifications.
8. All interconnecting twisted pair, fiber-optic or coaxial cables shall be terminated on equipment terminal boards, punch blocks, breakout boxes, splice blocks, and unused equipment ports/taps shall be terminated according to the OEM’s instructions for telephone cable systems without adapters. The Contractor shall not leave
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 20
unused or spare twisted pair wire, fiber-optic, or coaxial cable unterminated, unconnected, loose or unsecured.
9. Color code all distribution wiring to conform to the Telephone
Industry standard, EIA/TIA, and this document, which ever is the more stringent. At a minimum, all equipment, cable duct and/or conduit, enclosures, wiring, terminals, and cables shall be clearly and permanently labeled according to and using the provided record drawings, to facilitate installation and maintenance. Reference
Specification Section 27 10 00, STRUCTURED CABLING and Section 27 31
00, VOICE COMMUNICATIONS SWITCHING AND ROUTING EQUIPMENT.
10. Connect the System’s primary input AC power to the Facility’
Critical Branch of the Emergency AC power distribution system as shown on the plans or if not shown on the plans consult with RE regarding a suitable circuit location prior to bidding.
11. Plug-in connectors shall be provided to connect all equipment, except coaxial cables and interface points. Coaxial cable distribution points and RF transmission lines shall use coaxial cable connections recommended by the cable OEM and approved by the
System OEM. Base- band cable systems shall utilize barrier terminal screw type connectors, at a minimum. Crimp type connectors installed with a ratchet type installation tool are and acceptable alternate as long as the cable dress, pairs, shielding, grounding, and connections and labeling are provided the same as the barrier terminal strip connectors. Tape of any type, wire nuts, or solder type connections are unacceptable and will not be approved.
12. All equipment faceplates utilized in the System shall be stainless steel, anodized aluminum, or UL approved cycolac plastic for the areas where provided.
13. Noise filters and surge protectors shall be provided for each equipment interface cabinet, switch equipment cabinet, control console, local, and remote active equipment locations to ensure protection from input primary AC power surges and noise glitches are not induced into low Voltage data circuits.
Underground warning tape shall be standard, 4-Mil polyethylene 76 mm
(3 inch) wide tape detectable type, red with black letters imprinted with “CAUTION BURIED ELECTRIC LINE BELOW”, orange with black letters imprinted with “CAUTION BURIED TELEPHONE LINE BELOW” or orange with
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 21
black letters imprinted with “CAUTION BURIED FIBER OPTIC LINE
BELOW”, as applicable.
D. Equipment Functional Characteristics:
FUNCTIONS CHARACTERISTICS
Input Voltage 105 to 130 VAC
POWER LINE FREQUENCY 60 HZ ±2.0 HZ
Operating Temperature O to 50 degrees () Centigrade (C)
Humidity 80 percent (%) minimum rating
E. Equipment Standards and Testing:
1. The System has been defined herein as connected to systems identified as Critical Care performing Life Support Functions.
Therefore, at a minimum, the system shall conform to all aforementioned National and/or Local Life Safety Codes (which ever are the more stringent), NFPA, NEC, this specification, JCAHCO Life
Safety Accreditation requirements, and the OEM recommendations, instructions, and guidelines.
2. All supplies and materials shall be listed, labeled or certified by
UL or a nationally recognized testing laboratory where such standards have been established for the supplies, materials or equipment. See paragraph minimum requirements Section 27 05 11, REQUIREMENTS FOR COMMUNICATIONS INSTALLATIONS, and the guidelines listed in paragraph 2.J.2.
3. The provided active and passive equipment required by the System design and approved technical submittal must conform with each UL standard in effect for the equipment, as of the date of the technical submittal (or the date when the RE approved system equipment necessary to be replaced) was technically reviewed and approved by VA. Where a UL standard is in existence for equipment to be used in completion of this contract, the equipment must bear the approved UL seal.
4. Each item of electronic equipment to be provided under this contract must bear the approved UL seal or the seal of the testing laboratory that warrants the equipment has been tested in accordance with, and conforms to the specified standards.
2.2 EQUIPMENT ITEMS
A. Cabinet with Internal Equipment Mounting Rack:
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 22
1. The provided equipment cabinet shall be lockable, fabricated of heavy 16 gauge (ga) steel, and have fully adjustable internal equipment mounting racks or rails that allows front panel equipment mounting and access. It shall have baked-on iron phosphate primer and baked enamel paint finish in a color to be selected by the using
Facility Service Chief. It shall be floor or wall mounted with knock-out holes for cable entrance and conduit connection, contain ventilation ports and a quiet fan with non disposable air filter for equipment cooling. Two keys shall be provided to the RE for each lock when the VA accepts the System.
2. A minimum of one cabinet shall be provided with blank rack space, for additional equipment. Blank panels shall be installed to cover any open or unused rack space. In addition, provide two 120 VAC power strips connected to surge protectors, a ventilation fan with non-disposable air filter, and a conduit or cable duct interfaced to adjacent cabinet(s), as part of this cabinet.
3. Blank panels shall be color matched to the cabinet, 3.175 mm
(1/8in.) aluminum with vertical dimensions in increments of one rack unit 45 mm (or 1.75in.) with mounting holes spaced to correspond to
EIA 480 mm (or 19in.) rack dimensions. Single standard size blank panels shall be used to fill unused panel or rack spaces in lieu of numerous 45 mm (1.75in.) types. One blank 45 mm (1.75in.) high blank panel shall be installed between each item of equipment.
4. Technical Characteristics:
Overall Height 2180 mm (85 7/8in.), maximum
Overall Depth 650 mm (25 1/2in.), maximum
Overall Width 535 mm (21 1/16in.), maximum
Front Panel Opening Width 480 mm (19in.), EIA horizontal
Hole Spacing per EIA and Industry Standards
5. Internal Cabinet Components (minimum required):
a. AC power outlet strip(s):
1) Power outlet strip(s) shall be provided as directed by the RE or the IRM. The additional equipment cabinet with no installed items in the cabinet, shall contain strip(s) with a minimum of
12 ea. AC power outlets. Each strip shall be mounted inside and at the rear of the cabinet. It shall contain “U” grounded
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 23
AC outlets for distributing AC power to the installed electronic equipment. The strip shall be self-contained in a metal enclosure and may be provided with a 2 M (6 ft.) long
(maximum) connecting cord with three prong plug.
2) Technical Characteristics:
a) Power capacity20 Ampere (AMP), 120 VAC continuous duty.
b) Wire gauge: Three conductor, #12 AWG copper.
b. Cabinet AC Power Line Surge Protector and Filter:
1) Each cabinet shall be equipped with a AC Surge Protector and
Filter. The Protector and Filter shall be housed in one single enclosure. The Protector and Filter shall perform instantaneous regulation of the AC input voltage and isolate and filter any noise present on the AC input line. The unit shall be equipped with AC voltage and current surge protectors to prevent damage to the electronic equipment from power line induced voltage spikes, surges, lightning, etc. It shall be cabinet mounted and the cabinet AC power strip (maximum of two strips) may be connected to it as long as the system design is met.
2) Technical Characteristics:
Input Voltage range 120 VAC + 15%
Power capacity 20 AMP, 120 VAC
Voltage output regulation
+3.0%
Circuit breaker 15 AMP, may be self contain
Noise filtering Greater than -45 dB
AC outlets Four duplex grounded types, minimum
Response time 5.0 ns
Surge suppression 10,000 AMPS
Noise suppression
Common -40 dB
Differential -45 dB
3) Specific requirements for current and surge protection shall include:
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 24
a) Voltage protection threshold, line to neutral, starts at no more than 220 Volts peak. The transient voltage shall not exceed 300 volts peak. The Contractor shall furnish documentation on peak clamping voltage as a function of transient AMP.
b) Peak power dissipation minimum 35 Joules per phase, as measured for l.0 mS at sub branch panels, l00 Joules per phase at branch panels and 300 Joules per phase at service entrance panels. The Contractor shall furnish an explanation of how the ratings were measured or empirically derived.
c) Surge protector must not short circuit the AC power line at any time.
(1) The primary surge protection components must be silicon semiconductors. Secondary stages, if used, may include other types of devices.
(2) Surge protectors shall incorporate a visual device which indicates whether the surge suppression component(s) is
(are) functioning.
(3) Surge protection devices shall be UL listed.
(4) Voltage and current surge protectors shall be provided on all ancillary equipment provided by the Contractor.
d) Power dissipation 12,000 Watts (W) for l.0 mS (or l2
Joules).
e) Voltage protection threshold starts at not more than 100
VAC.
B. Environmental Cabinet (if selected):
1. The Contractor shall provide this enclosure in lieu of a standard equipment cabinet identified in Paragraph 2.3.A to meet system design in hostile TC locations as identified on the drawings. The enclosure shall fully sustain the installed, including electronic, equipment in the same manner as the standard cabinet identified in
Paragraph 2.3.A. Additionally, the enclosure shall fully support all installed equipment as if they were in a stand alone air handling area regardless of the local area’s air handling capabilities. The enclosure shall be a OEM’s fully assembled unit. If more than two enclosures are required in any system location, those enclosures shall be OEM assembled for consolidating or combining two or more
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 25
enclosures in a single unit to meet system space and equipment handling designs.
2. Technical Characteristics:
Environmental control Automatic, heating and/or cooling, as required
Temperature conditions (rated at 1,300 W of install equipment heat generation):
Internal Range Maintains 80° to 105° of internal heat conditions, maximum
External Range 100° + 25°, maximum
Forced air unit Required with non disposable air filter unobstructed and uninterruptible
Air conditioning As required, fully internal mounted
Heater As required, fully internal mounted
Uninterruptible power supply
As required, fully internal mounted
Front door Full length, see through, EMI resistant, and lockable
Rear door Full length, non-see through, EMI resistant, and lockable
Conduit wiring entrance TOP AND/OR BOTTOM, FULLY SEALED
Input power 2 ea. minimum 120 VAC @ 20A, maximum, independent circuit, conduit for fixed or armored cable for moveable installations
Dimensions:
Height 1980 mm (78in.), maximum
Width 635 mm (25in.), maximum
Depth 965 mm (38in.), maximum
Front panel opening 480 mm (19in.), w/ EIA mounting hole spacing
C. Distribution or System Interface Cabinet:
1. The cabinet shall be constructed of heavy 16 gauge cold rolled steel, have top and side panels and hinged front and rear (front door only if wall mounted) doors. It shall have baked-on iron phosphate primer and baked enamel paint finish in a color to be selected by the using Facility Service Chief or the RE, contain integral and adjustable predrilled rack mounting rails or frame that allows front panel equipment mounting and access. When all
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 26
equipment, doors and panels are installed, snap-in-place chrome trim strip covers are required to be installed that will cover all front panel screw fasteners. It shall be equipped the same as the equipment cabinet.
Overall height 2180 mm (85 7/8in.), maximum
Overall depth 650 mm (25 1/2in.), maximum
Overall width 535 mm (21 1/16in.), maximum
Equipment vertical mounting space
1960 mm (77 1/8in.), maximum
Front panel horizontal 484 mm (19 1/16in.), maximum width
D. Stand Alone Equipment (or sometimes called Radio Relay) Rack:
1. The rack shall be constructed of heavy 16 gauge cold rolled steel and have fully adjustable equipment front mounting rails that allows front panel equipment mounting and access. It shall have baked-on iron phosphate primer and baked enamel paint finish in a color to be selected by the using Facility Service Chief or the RE. It shall be floor or wall mounted or mounted on casters as directed by the RE.
Overall Height 2180 mm (85 7/8in.), maximum
Overall Depth 650 mm (25 1/2in.), maximum
Overall Width 535 mm (21 1/16in.), maximum
Front Panel Opening 480 mm (19in.), EIA horizontal width
Hole Spacing per EIA and Industry Standards
E. Cross-Connection System (CCS) Equipment Breakout, Termination Connector
(or Bulkhead), and Patch Panels:
1. The connector panel(s) shall be made of flat smooth 3.175 mm (1/8 in.) thick solid aluminum, custom designed, fitted and installed in the cabinet. Bulkhead equipment connectors shall be mounted on the panel to enable all cabinet equipment’s signal, control, and coaxial cables to be connected through the panel. Each panel shall be color matched to the cabinet installed.
a. Voice (or Telephone):
1) The CSS for voice or telephone service shall be Industry
Standard type 110 (minimum) punch blocks for voice or telephone, and control wiring in lieu of patch panels, each
COMMUNICATIONS EQUIPMENT ROOM FITTINGS 27 11 00 - 27
being certified for category six service. IDC punch blocks
(with internal RJ45 jacks) are acceptable for use in all CCS and shall be specifically designed for category six telecommunications service and the size and type of UTP cable used as described herein. As a minimum, punch block strips shall be secured to an OEM designed physical anchoring unit on a wall location in the MTC, IMTC, RTC, and TC. However, console, cabinet, rail, panel, etc. mounting is allowed at the
OEM recommendation and as approved by the RE. Punch blocks shall not be used for Class II or 120 VAC power wiring.
Number of horizontal rows 100, MINIMUM
Number of terminals per row 4, minimum
Terminal protector required for each used or unused terminal
Insulation splicing required between each row of…