STRUCTURAL NOTES
1. GENERAL
A. THE BUILDING IS DESIGNED UNDER THE PROVISIONS OF THE 2012 INTERNATIONAL
BUILDING CODE, ASCE 7-10, AND VA PG-18-10 DESIGN MANUAL.
B. THE FOLLOWING LIVE LOADS WERE USED IN THE DESIGN:
BUILDING RISK CATEGORY IV
FLOOR LIVE LOAD
PATIENT ROOMS (WARD ROOMS) 80 PSF
CORRIDORS AT LEVEL 1 100 PSF
CORRIDORS ABOVE LEVEL 1 80 PSF
KITCHEN AND DINING AREAS 100 PSF
LAUNDRY ROOMS 200 PSF
ADMINISTRATIVE SERVICES (OFFICES) 80 PSF
FUTURE LEVELS 100 PSF
INTERSTITIAL LEVELS 25 PSF
LOBBY AND COMMON AREAS 100 PSF
STAIRS AND EXITS 100 PSF
STORAGE 125 PSF
MECHANICAL 150 PSF
SUPERIMPOSED DEAD LOAD AS REQUIRED (20 PSF MIN. FOR PARTITIONS)
NOTE: LIVE LOAD REDUCTION IS UTILIZED AS ALLOWED BY CODE
ROOF LIVE LOAD
MINIMUM UNIFORM ROOF LIVE LOAD 30 PSF
ROOF SNOW LOAD
GROUND SNOW LOAD (Pg) 20 PSF FLAT-ROOF SNOW LOAD (Pf) 24 PSF SNOW EXPOSURE FACTOR (Ce) 1.0 SNOW IMPORTANCE FACTOR (Is) 1.20 THERMAL FACTOR (Ct) 1.0
NOTE: DRIFTING SNOW LOADS AS REQUIRED BY CODE
WIND LOAD
WIND SPEED (3 SECOND GUST)
VULT 120 MPH
VASD: (0.77*VULT) 93 MPH
WIND EXPOSURE B
INTERNAL PRESSURE COEFFICIENT +0.18, -0.18
EARTHQUAKE DESIGN
SEISMIC IMPORTANCE FACTOR (Ie) 1.50
SEISMIC DESIGN CATEGORY C
SITE CLASSIFICATION D
SEISMIC RESPONSE COEFFICIENTS (LOW SEISMICITY PER VA H-18-8)
Ss 0.225 S1 0.060 Sds 0.240 Sd1 0.096
DESIGN BASE SHEAR 470 KIPS
SEISMIC-FORCE RESISTING SYSTEM PER
ASCE 7-10 TABLE 12.2-1 TYPE H
R 3 Cd 3 Cs 0.116
TL 8
ANALYSIS METHOD ELFP
C. SEE ARCHITECTURAL DRAWINGS FOR ANGLES, CLIPS, PLATES, ETC., AND OTHER
MISCELLANEOUS ITEMS. VERIFY AND COORDINATE ALL FRAMES, OPENINGS, ETC. WITH THE
MECHANICAL AND ELECTRICAL CONTRACTORS.
D. SUBMIT SHOP DRAWINGS FOR THE FOLLOWING ITEMS. SUBMITTALS INCLUDE BUT MAY NOT
BE LIMITED TO:
--CONCRETE MIX DESIGN
--REINFORCING STEEL
--STRUCTURAL STEEL
--METAL DECKING
--LIGHT GAGE METAL FRAMING
DO NOT USE CONTRACT DRAWINGS AS A BASE FOR SHOPS. REVIEW IS LIMITED TO DESIGN
CONFORMANCE. CONTRACTOR IS RESPONSIBLE FOR DIMENSIONS.
E. CONTRACTOR SHALL COORDINATE WITH THE QUALIFIED AGENCY RETAINED BY THE OWNER
TO PERFORM INSPECTION AND TESTING. INSPECTIONS REQUIRED INCLUDE, BUT MAY NOT
BE LIMITED TO:
--SOILS AND FOUNDATIONS
--CONCRETE
--STRUCTURAL STEEL
--LIGHT GAGE METAL FRAMING
2. EARTHWORK
A. FOUNDATIONS AT LOWER LEVEL ARE DESIGNED TO BEAR ON AGGREGATE PIER IMPROVED
SOILS WITH A BEARING CAPACITY OF 6,000 PSF, PER THE RECOMMENDATIONS OF THE
GEOTECHNICAL ENGINEERING REPORT PREARED BY SCHNABEL ENGINEERING DATED
EBRUARY 19,2015. THIS VALUE IS TO BE VERIFIED IN THE FIELD BY THE BUILDING
INSPECTOR OR A QUALIFIED TESTING AGENCY.
B. BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE A MINIMUM OF 2 FOOT-6 INCH BELOW FINISH
EXTERIOR GRADE. WHERE REQUIRED, STEP FOOTINGS IN RATIO OF 2 HORIZONTAL TO 1
VERTICAL.
C. COMPACTED BACKFILL BELOW BUILDING SLABS AND FOOTINGS: ALL SOIL FILL MATERIAL
MUST BE APPROVED BY SOILS ENGINEER PRIOR TO PLACEMENT. PROOFROLL SUBGRADE
REMOVING AND REPLACING SOFT OR COMPRESSIVE MATERIALS. FILL MATERIAL SHALL BE
PLACED IN LAYERS NOT TO EXCEED 8INCH AND COMPACTED TO MIN. 95 PERCENT OF THE
DRY MAXIMUM DENSITY AS DETERMINED BY ASTM D698.
3. AGGREGATE PIERS
A. AGGREGATE PIERS SHALL CONSIST OF DENSELY COMPACTED AGGREGATE PIERS
CONSTRUCTED BY COMPACTING AGGREGATE IN AN EXCAVATED HOLE USING SPECIAL
HIGH-ENERGY IMPACT DENSIFICATION EQUIPMENT. THE AGGREGATE PIERS SHALL BE IN A
COLUMNAR TYPE CONFIGURATION AND SHALL BE USED TO PRODUCE AN INTERMEDIATE
FOUNDATION SYSTEM FOR THE SUPPORT FO THE BUILDING.
B. THE AGGREGATE PIER CONTRACTOR SHALL RETAIN AN ENGINEER TO ANALYZE THE SOIL
IMPROVEMENT REQUIREMENTS AND TO DESIGN THE AGGREGATE PIER SYSTEM. THE
SPECIALTY ENGINEER SHALL SUBMIT DESIGN CALCULATIONS AND CONSTRUCTION
DRAWINGS SIGNED AND SEALED BY A SPECIALTY ENGINEER REGISTERED IN THE STATE OF
THE PROJECT. AGGREGATE PIERS SHALL BE DESIGNED FOR THE LOADS NOTED ON THE
DRAWINGS. ANY SIZES NOTED IN THE DRAWINGS ARE FOR GENERAL INFORMATION ONLY.
C. INSTALLER MUST EXAMINE AREAS AND CONDITIONS UNDER WHICH AGGREGATE PIERS ARE
TO BE INSTALLED AND NOTIFY OWNER IN WRITING OF CONDITIONS DETRIMENTAL TO
PROPER AND TIMELY COMPLETION OF WORK.
D. THE AGGREGATE PIER DESIGN SHALL BE VERIFIED BY A SINGLE PIER LOAD TEST. TEST PIER
LOCATION TO BE SPECIFIED BY THE AGGREGATE PIER SPECIALTY ENGINEER AND SHALL BE
SAME DIAMETER AND LENGTH AS THE PRODUCTION PIERS.
4. DEMOLITION
A. PROVIDE ADEQUATE SHORING, BRACING AND OTHER TEMPORARY SUPPORT DURING
DEMOLITION. RETAIN THE SERVICES OF A QUALIFIED SPECIALTY ENGINEER TO DESIGN AND
MONITOR THE TEMPORARY SUPPORT. SUBMIT DRAWINGS FOR RECORD ONLY.
B. UNTIL PROPERLY SHORED, DO NOT CUT EXISTING STRUCTURAL MEMBER IN A MANNER
RESULTING IN A REDUCTION OF LOAD-CARRYING CAPACITY. DO NOT EXCEED THE CAPACITY
OF THE EXISTING STRUCTURE WITH SUPERIMPOSED LOADS.
C. IN GENERAL, SELECTIVE STRUCTURAL DEMOLITION IS TO BE PERFORMED WITH PHYSICAL
CUTTING ACTION (I.E. SAWING AND GRINDING INSTEAD OF HAMMERING AND CHOPPING). DO
NOT USE JACKHAMMERS ON STRUCTURALLY SUPPORTED MEMBERS.
D. CONTRACTOR SHALL VERIFY THAT EXISTING CONSTRUCTION CORRESPONDS TO THAT
SHOWN ON THE DRAWINGS. DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE
ATTENTION OF THE ARCHITECT/ENGINEER.
5. CONCRETE
A. CONCRETE CONSTRUCTION SHALL BE PER THE APPLICABLE BUILDING CODE, ACI 318 AND
ACI 301, LATEST EDITIONS.
B. CONCRETE SHALL ATTAIN THE FOLLOWING 28 DAY COMPRESSIVE STRENGTHS PER
ASTM A39.
--FOOTINGS, PIERS 3,000 PSI
--SLAB-ON-GRADE 3,500 PSI
--FOUNDATION WALLS (MAX W/C RATIO = 0.45) 4,000 PSI
--CONCRETE FILL OVER STEEL DECK 3,000 PSI
C. VERIFY CONCRETE STRENGTHS WITH A MINIMUM OF ONE SET OF SIX 6X12-INCH
COMPRESSION CYLINDERS (2 @ 7 DAYS, 2 @ 28, 2 SPARE) PER DAY PER MIX TYPE WITH AN
ADDITIONAL SET FOR EACH 100 YARDS OF CONCRETE. ALTERNATIVELY, 4X8-INCH
COMPRESSION CYLINDERS MAY USED, INCREASE TO 3 CYLINDERS PER TEST SAMPLE (3 @ 7
DAYS, 3 @ 28, 3 SPARE).
D. EXTERIOR CONCRETE SHALL BE AIR-ENTRAINED TO PROVIDE AN AIR CONTENT OF 6+/-1.5
PERCENT BY VOLUME.
E. PROVIDE CLEAR DISTANCE TO OUTERMOST REINFORCING AS FOLLOWS:
CONCRETE CAST AGAINST EARTH 3 INCHES
CONCRETE EXPOSED TO EARTH OR WEATHER:
#5 OR SMALLER 1-1/2 INCHES
#6 OR LARGER 2 INCHES
OTHER CONCRETE:
SLABS & WALLS 3/4 INCHES
BEAMS & COLUMNS 1- 1/2 INCHES
F. CONCRETE TOPPING MIX: FOR TOPPINGS LESS THAN 2" IN THCKNESS, THE CONCRETE MIX SHALL ACHIEVE A COMPRESSIVE STRENGTH OF 4000 PSI AT 28 DAYS WITH A MAXIMUM WATER/CEMENT RATIO OF 0.50 AND A MAXIMUM SIZE OF COARSE AGGREGATE OF 3/8". THE MIX DESIGN SHALL BE
PROPORTIONED IN ACCORDANCE WITH SECTION 5.3 OF ACI 318.
F. NON-SHRINK GROUT FOR COLUMNS BASE PLATES SHALL ATTAIN A 28 DAY COMPRESSIVE
STRENGTH: F'c = 5,000 PSI.
G. REINFORCING STEEL SHALL CONFORM TO A615-GR60; MESH SHALL CONFORM TO ASTM A185
WITH MINIMUM LAPS OF 8 INCHES. PLACING PLANS AND SHOP FABRICATION DETAILS SHALL BE
IN ACCORDANCE WITH “THE MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED
CONCRETE STRUCTURES”. FURNISH SUPPORT BARS AND ACCESSORIES IN ACCORDANCE WITH
C.R.S.I. STANDARDS.
H. PROVIDE CORNER BARS TO MATCH HORIZONTAL REINFORCING IN WALLS AND FOOTINGS.
SPLICE LAPS SHALL BE A MINIMUM OF 36 BAR DIAMETERS, UNLESS NOTED OTHERWISE.
PROVIDE DOWELS BETWEEN FOOTINGS AND WALLS OR PIERS TO MATCH SIZE AND SPACING OF
VERTICAL REINFORCING.
I. WALLS WITH LATERAL EARTH PRESSURES SHALL BE ADEQUATELY SHORED OR FLOOR/ROOF
CONSTRUCTION SHALL BE IN PLACE AND SECURED PRIOR TO BACKFILLING.
J. CONCRETE SLABS ON STEEL FRAMING SHALL BE PLACED LEVEL TO THE ELEVATIONS
SPECIFIED ON THE DRAWINGS. PLACE THE CONCRETE USING AN APPROPRIATE METHOD, SUCH
AS A LASER TO SET THE TOP SURFACE ELEVATION. DO NOT SET THE SLAB THICKNESS BY
MEASURING OFF THE DECK.
K. THE SLAB THICKNESS SHOWN ON THE DRAWINGS IS THE THICKNESS AT THE COLUMNS. THE
THICKNESS WILL VARY ACROSS THE LENGTH OF THE BEAMS DEPENDING ON THE DEFLECTION
AND/OR CAMBER OF THE STEEL. THE CONTRACTOR IS RESPONSIBLE TO ACCOUNT FOR THIS
WHEN ESTIMATING CONCRETE QUANTITIES. THE WEIGHT OF THE ADDITIONAL CONCRETE HAS
BEEN ACCOUNTED FOR IN THE STRUCTURAL DESIGN OF THE BUILDING.
L. AFTER THE LOSS OF CAMBER, WHERE APPLICABLE, INDIVIDUAL STEEL BEAMS AND GIRDERS HAVE BEEN DESIGNED TO HAVE AN INITIAL DEFLECTION UNDER THE WET WEIGHT OF CONCRETE
GENERALLY LESS THAN L/300, (L IN INCHES).
M. WHEN PLACING WET CONCRETE OVER CAMBERED BEAMS, UNIFORMLY SPREAD THE CONCRETE
(10 TO 12 FEET WIDE) OVER THE FULL LENGTH OF THE BEAM PRIOR TO MOVING
PERPENDICULAR TO THE BEAMS. THIS WILL PROPERLY DEFLECT THE BEAMS SUFFICIENTLY TO
OBTAIN THE REQUIRED SLAB THICKNESS.
N. INSTALLATION OF ELECTRICAL CONDUIT WITHIN THE CONCRETE SLAB-ON-GRADE OR WITHIN
CONCRETE OVER METAL DECKING IS PROHIBITED.
6. MASONRY
A. MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE APPLICABLE BUILDING CODE
AND THE “BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES” TMS 402/ACI-530/ASCE
5 AND THE “SPECIFICATIONS FOR MASONRY STRUCTURES” TMS 602/ACI-530.1/ASCE 6, LATEST
EDITIONS.
B. MASONRY TO CONFORM TO THE FOLLOWING SPECIFICATIONS:
HOLLOW LOAD-BEARING C.M.U ASTM C90
CONCRETE BUILDING BRICK ASTM C55, GRADE A
MORTAR ASTM C270, TYPE M OR S
GROUT ASTM C476
C. MASONRY ASSEMBLIES SHALL HAVE COMPRESSIVE STRENGTH (F'M) GREATER THAN OR EQUAL
TO 1350 PSI.
D. WALLS SHALL BE CONSTRUCTED USING A FULL BED OF MORTAR. VERTICAL REINFORCING
SHALL BE GROUTED IN PLACE WITH 2500 PSI GROUT (GROUT SLUMP SHALL FALL BETWEEN 8
AND 11 INCHES) POUR HEIGHT AND LIFT HEIGHT SHALL NOT EXCEED 5 FEET - 0 INCHES.
E. PROVIDE CONTINUOUS HORIZONTAL JOINT REINFORCING IN MASONRY WALLS AT 16 INCHES O.C.
PROVIDE AT 8 INCHES O.C. AT PARAPETS.
F. CAVITY WALLS OF BRICK AND BLOCK SHALL BE CONSTRUCTED WITH JOINT REINFORCING IN
MASONRY AND ADJUSTABLE METAL ANCHORS TO BRICK.
G. UNLESS NOTED OTHERWISE, PROVIDE 16 INCH LONG BY 24 INCHES HIGH SOLID OR GROUTED
BLOCK UNDER BEARING ENDS OF BEAMS.
H. AT CONTINUOUS BOND BEAM, PROVIDE 4 FEET- 0 INCHES LAP AT BEAM STEPS.
I. MASONRY WALLS SHALL HAVE CONTROL JOINTS AT 30 FEET ON CENTER UNLESS NOTED
OTHERWISE.
J. REINFORCING STEEL SHALL CONFORM TO ASTM A615-GR60. LAP BARS A MINIMUM OF 48 BAR
DIAMETERS. GROUT ALL REINFORCED CORES SOLID.
K. UNLESS SHOWN ON PLAN, LINTELS FOR MASONRY WALLS SHALL BE AS FOLLOWS:
OPENINGS TO 3 FT, 0 IN 3-1/2 X 3-1/2 X 1/4
3 FT, 1 IN TO 5 FT, 0 IN 4 X 3-1/2 X 5/16 - 3-1/2 HORIZONTAL
5 FT, 1 IN TO 6 FT, 6 IN 5 X 3-1/2 X 5/16 - 3-1/2 HORIZONTAL
OVER 6 FT, 6 IN CONSULT ARCHITECT/ENGINEER
PROVIDE 1 ANGLE FOR EACH 4 INCHES OF WALL THICKNESS. LINTELS SHALL BEAR 6 INCHES
MINIMUM EACH END U.N.O.
L. PROVIDE TWO-PIECE ADJUSTABLE ANCHORS TO MASONRY AT 24 INCHES O.C. AT ALL VERTICAL
AND HORIZONTAL STRUCTURAL STEEL MEMBERS.
M. ALL NON-LOADBEARING MASONRY WALLS SHALL BE PROVIDED WITH VERTICAL SLIP
CONNECTIONS AT THE TOP OF THE WALL, U.N.O.
7. STEEL
A. STEEL CONSTRUCTION SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE APPLICABLE
BUILDING CODE AND SHALL CONFORM TO AISC 360. STRUCTURAL STEEL SHALL CONFORM TO
THE FOLLOWING ASTM STANDARDS:
WIDE FLANGE SHAPES A992 – GR50
STEEL PLATES, CHANNELS AND ANGLES A36
STRUCTURAL PIPES A53 OR A501
STRUCTURAL TUBES A500 - GR B
ANCHOR RODS (3/4” DIAM. OR LESS) F1554 – 36 KSI
ANCHOR RODS (7/8” DIAM. OR GREATER) F1554 – 55 KSI
HIGH-STRENGTH BOLTS A325
HEADED STUDS A108
B. BOLTED CONNECTIONS TO USE A325-TYPE N, HIGH STRENGTH BOLTS IN BEARING TYPE
CONNECTIONS TIGHTENED TO A SNUG TIGHT CONDITION IN ACCORDANCE WITH RCSC
SPECIFICATIONS.
C. BOLTS IN MOMENT CONNECTIONS AND WIND RESISTING FRAMES SHALL BE ASTM A325-TYPE SC
(SLIP CRITICAL). SLIP CRITICAL CONNECTIONS SHALL HAVE CONTACT SURFACES MEETING
CLASS A SURFACE CONDITIONS. BOLTS SHALL BE TENSIONED.
D. SHOP CONNECTIONS TO BE WELDED OR BOLTED. FIELD CONNECTIONS TO BE BOLTED UNLESS OTHERWISE SHOWN. BOLT HOLES TO BE STANDARD ROUND HOLES (d+1/16 INCHES) UNLESS
OTHERWISE NOTED. SHORT SLOTS SHALL BE PERMITTED NORMAL TO THE LOAD DIRECTION IN
SLIP CRITICAL AND BEARING TYPE CONNECTIONS AS PER AISC REQUIREMENTS.
E. IF BEAM REACTIONS ARE DENOTED ON THE DRAWINGS, BEAM-WEB CONNECTIONS FOR SHEAR
AT EACH END SHALL BE DETAILED TO SUPPORT THE LOADS SHOWN OR PROVIDE THE
FOLLOWING MINIMUM NUMBER OF BOLTS, WHICHEVER IS GREATER. STIFFENED SEATS SHALL
BE DETAILED TO SUPPORT THE LOADS SHOWN ON THE DRAWINGS OR THE MINIMUM FACTORED
LOADS INDICATED BELOW, WHICHEVER IS GREATER.
BEAM/WEB STIFF. SEAT
W8 OR W10 2 BOLTS (24K)
W12 OR W14 3 BOLTS (36K)
W16 OR W18 4 BOLTS (48K)
W21 OR W24 5 BOLTS (60K)
F. STRUCTURAL STEEL SHALL BE GIVEN ONE SHOP COAT OF APPROVED SHOP PRIMER APPLIED
TO CLEAN AND DRY SURFACES. DO NOT PAINT STEEL THAT WILL BE FIREPROOFED OR
EMBEDDED IN CONCRETE.
G. STEEL BEAMS SHALL BE WELDED TO STEEL BEARING PLATES WITH 3 INCH LONG BY 3/16-INCH
FILLET WELD EACH SIDE OF FLANGE (MINIMUM).
H. CAMBERS SHOWN REFLECT THE IN-PLACE ERECTED, BEAM DEAD LOAD CONDITION. CAMBERS
SHALL BE INCREASED AS REQUIRED BY THE SUPPLIER TO ACCOUNT FOR LOSS OF CAMBER.
SINGLE POINT CAMBERING WILL NOT BE ALLOWED.
I. WELDING OF STRUCTURAL STEEL SHALL BE WITH E70XX ELECTRODES.
8. STEEL DECK
A. STEEL DECK SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE APPLICABLE BUILDING CODE
AND THE STEEL DECK INSTITUTE SPECIFICATIONS AND RECOMMENDATIONS.
B. COMPOSITE SLABS OF CONCRETE AND STEEL DECK SHALL BE CONSTRUCTED IN ACCORDANCE
WITH ASCE 3.
C. ROOF DECK SHALL BE 20 GAGE, 1 1/2 INCH DEEP, 33 KSI, TYPE B, WIDE RIB (I=0.201, Sp=0.234, Sn=0.247 PER FOOT OF WIDTH, U.N.O.) AND SHALL EXTEND A MINIMUM OF 3 SPANS, U.N.O. DECK
SHALL BE GALVANIZED.
D. MINIMUM REQUIREMENTS FOR ROOF DECK FASTENING SHALL BE 5/8 INCH DIAMETER PUDDLE WELDS USING A 36/5 OR 30/4 WELD PATTERN WITH #10 TEK SCREW SIDELAP FASTENER AT 18
INCHES O.C.
E. COMPOSITE FLOOR DECK SHALL BE 19 GAGE, 50 KSI, 2 INCH DEEP (I=0.409, Sp=0.341, Sn=0.346 PER FOOT OF WIDTH, U.N.O) AND SHALL EXTEND A MINIMUM OF 3 SPANS, U.N.O. DECK SHALL
HAVE PHOSPHATIZED TOP AND PAINTED BOTTOM. DECK SHALL BE GALVANIZED.
F. MINIMUM REQUIREMENTS FOR FLOOR DECK FASTENING SHALL BE 5/8 INCH DIAMETER PUDDLE WELDS USING A 36/4 OR 30/3 WELD PATTERN WITH 1-#10 TEK SCREW SIDELAP FASTENER AT 3
FEET ON CENTER.
9. LIGHT GAGE METAL FRAMING
A. LIGHT GAGE FRAMING SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE
APPLICABLE BUILDING CODE AND AISI, LATEST EDITION.
B. SUBMIT CALCULATIONS AND SHOP DRAWINGS SIGNED AND SEALED BY A SPECIALTY ENGINEER
REGISTERED IN THE STATE OF THE PROJECT. MEMBERS AND CONNECTIONS SHALL BE
DESIGNED FOR THE LOADINGS NOTED ABOVE. ANY SIZES NOTED IN THE DRAWINGS ARE FOR
GENERAL INFORMATION ONLY.
C. EXTERIOR WALL FRAMING SHALL BE DESIGNED FOR THE FOLLOWING MAXIMUM LATERAL
DEFLECTIONS, AT THE APPLICABLE DESIGN WIND:
AT MASONRY VENEER L/600 OR 0.3 INCH, WHICHEVER IS LESS
AT OTHER LOCATIONS L/360
D. SHOP DRAWINGS SHALL INCLUDE ERECTION DRAWINGS SHOWING MEMBER LAYOUT, SIZE AND
SPACING. PROVIDE CONNECTION DETAILS SUPPLEMENTAL BRACING, SPLICES, ACCESSORIES,
AND DETAILS AS MAY BE REQUIRED FOR PROPER INSTALLATION.
E. LIGHT GAUGE STUD CAPACITY SHALL BE REDUCED BY 20% AT 2 HOUR LOAD BEARING WALLS.
REFERENCE ARCHITECTURAL DRAWINGS FOR FIRE RATINGS AND UL DESIGN NUMBERS.
F. THE SPECIALTY ENGINEER SHALL VISIT THE JOBSITE DURING CONSTRUCTION TO VERIFY
CONFORMANCE TO THE SHOP DRAWINGS. AT THE COMPLETION OF THE PROJECT PROVIDE A
LETTER CERTIFYING THE CONSTRUCTION IS IN ACCORDANCE WITH THE DESIGN.
G. MATERIALS AND FINISHES:
FOR 16-GAGE AND HEAVIER UNITS, FABRICATE METAL FRAMING COMPONENTS OF STRUCTURAL
QUALITY STEEL SHEET WITH A MINIMUM YIELD POINT OF 50,000 PSI; ASTM A653, ASTM A875, ASTM A792, OR ASTM A463.
FOR 18-GAGE AND LIGHTER UNITS, FABRICATE METAL FRAMING COMPONENTS OF COMMERCIAL
QUALITY STEEL SHEET WITH A MINIMUM YIELD POINT OF 33,000 PSI; ASTM A653, ASTM A875, ASTM A792, OR ASTM A463.
PROVIDE GALVANIZED FINISH TO METAL FRAMING COMPONENTS COMPLYING WITH ASTM A924
FOR MINIMUM G60 COATING.
ALL STUDS SHALL BE STANDARD LOAD-BEARING STEEL STUDS OF SIZE, SHAPE, AND GAGE
INDICATED, WITH 1.625 INCH FLANGE AND FLANGE RETURN LIP.
STUDS MATERIAL USED TO BACKUP ON SUPPORT BRICK SHALL USE A MINIMUM 18 GAGE STUD
AND HAVE A G90 FINISH.
H. WELD STUD WORK USING E60XX ELECTRODES BY CERTIFIED WELDERS. FOR MECHANICAL
FASTENERS, USE ONLY POLYMER FINISHES, CHROMIUM PLATED, STAINLESS STEEL OR HOT DIP
GALVANIZED UNITS.
I. CONSTRUCT ALL NON-LOADBEARING WALLS WITH A VERTICAL SLIP CONNECTION AT THE TOP
OF THE WALL.
10. POST-INSTALLED ANCHORS IN CONCRETE AND MASONRY
A. GENERAL
INSTALL ANCHORS IN STRICT CONFORMANCE WITH THE MANUFACTURER’S PUBLISHED INSTALLATION INSTRUCTIONS AND PROCEDURES. ALL POST-INSTALLED ANCHORS IN CONCRETE SHALL HAVE ICC
APPROVAL FOR USE IN CRACKED CONCRETE.
SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE SUBMITTED FOR APPROVAL PRIOR TO
USE. CONTRACTOR SHALL PROVIDE LOAD CAPACITIES DEMONSTRATING THAT THE SUBSTITUTED
PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED PRODUCT.
PROVIDE STAINLESS STEEL FASTENERS FOR EXTERIOR USE OR WHEN PERMANENTLY EXPOSED TO
WEATHER. PROVIDE GALVANIZED CARBON STEEL ANCHORS AT OTHER LOCATIONS, UNLESS
OTHERWISE
NOTED.
B. PRODUCTS
ANCHORS IN CONCRETE:
-- EXPANSION ANCHORS SHALL BE HILTI KWIK BOLT TZ.
-- UNDERCUT ANCHORS SHALL BE HILTI HDA.
-- SCREW ANCHORS SHALL BE HILTI KWIK HUS-EZ.
-- ADHESIVE ANCHORS SHALL BE HILTI HIT-HY 200 SAFE SET SYSTEM WITH HILTI HIT-Z ROD
OR WITH HILTI HOLLOW DRILL BIT SYSTEM WITH HAS-E THREADED ROD.
ANCHORS IN MASONRY:
-- EXPANSION ANCHORS SHALL BE HILTI KWIK BOLT-3. GROUT MASONRY CELLS SOLID WITH
2500 PSI GROUT AT ANCHOR LOCATIONS.
-- SCREW ANCHORS SHALL BE HILTI KWIK HUS-EZ. GROUT MASONRY CELLS SOLID WITH
2500 PSI GROUT AT ANCHOR LOCATIONS.
-- ADHESIVE ANCHORS IN SOLID MASONRY SHALL BE HILTI HIT-HY 70 ADHESIVE ANCHORING
SYSTEM. STEEL ANCHOR ELEMENT SHALL BE HILTI HAS-E CONTINUOUSLY THREADED
ROD OR HILTI HIS-N INTERNALLY THREADED INSERT.
-- ADHESIVE ANCHORS IN HOLLOW OR MULTI-WYTHE MASONRY SHALL BE HILTI HIT-HY 70
ADHESIVE ANCHORING SYSTEM. STEEL ANCHOR ELEMENT SHALL BE HILTI HAS-E
CONTINUOUSLY THREADED ROD OR HILTI HIT-IC INTERNALLY THREADED INSERT. THE
APPROPRIATE SIZE SCREEN TUBE SHALL BE USED PER THE ADHESIVE MANUFACTURER’S
RECOMMENDATION.
C. INSTALLATION
ALL INSTALLATION PROCEDURES SHALL BE PER MANUFACTURERS RECOMMENDATIONS. COORDINATE
AND/OR PROVIDE FOR THIRD PART INSPECTION AS REQUIRED BY BUILDING CODE OR LOCAL
JURISDICTION.
ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF ANCHOR TO EDGE OF CONCRETE OR MASONRY. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE DISTANCE INDICATED ON THE DRAWINGS; IF NOT SHOWN, COMPLY WITH MINIMUM SPACING AND
EDGE DISTANCE FOR FULL ANCHOR CAPACITY, AS SPECIFIED BY MANUFACTURER.
EXISTING REINFORCING BARS IN THE CONCRETE OR MASONRY STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. DO NOT CUT OR DAMAGE REINFORCING BARS UNLESS SPECIFICALLY PERMITTED IN
THE DRAWINGS.
PRIOR TO DRILLING, THE CONTRACTOR SHALL LOCATE REINFORCING BAR POSITIONS IN THE IMMEDIATE VICINITY OF PROPOSED POST-INSTALLED ANCHORS USING GPR, X-RAY, OR OTHER NON-DESTRUCTIVE
MEANS.
WHEN CONFLICTS BETWEEN PROPOSED ANCHORS AND EXISTING REINFORCING BARS EXIST, SUBMIT RESULTS OF BAR LOCATIONS TO ARCHITECT / ENGINEER FOR REVIEW AND FURTHER DIRECTION.
11. FUTURE CONSTRUCTION
A. THE BUILDING STRUCTURE HAS BEEN DESIGNED FOR THE FUTURE CONSTRUCTION OF A 3RD
FLOOR, A ROOF, AND 2 INTERSTITIAL LEVELS.
B. THE LOADS CONSIDERED ARE SHOWN ON S-004.
WARNING: THE STRUCTURAL INTEGRITY OF THE BUILDING SHOWN ON THESE PLANS IS DEPENDENT UPON COMPLETION ACCORDING TO PLANS AND SPECIFICATIONS. STRUCTURAL MEMBERS ARE NOT SELF-BRACING UNTIL PERMANENTLY AFFIXED TO THE STRUCTURE. THE STRUCTURAL ENGINEERS
ASSUME NO LIABILITY FOR THE STRUCTURE DURING CONSTRUCTION.
ABBREVIATIONS & LEGEND
K
J
H
G
F
E
D
C
B
A
T
W
V
U
S
R
Q
P
O
N
M
L
I
BOTTOM OF FOOTING ELEVATION
GENERAL CONTRACT(OR)
JOIST BEARING ELEVATION
JST JOIST
KIP
JOINT
KNOCK-OUT
KIPS PER SQ. INCH
JT
KO
KSI
K
HIGH POINT
HEIGHT
HORIZONTAL
INSIDE FACE
INFORMATION
IF
INFO
JBE
HT
HP
HORIZ
BOTT BOTTOM
DBL DOUBLE
GALVANIZED
GAGE, GAUGEGA
GALV
GC
EACH SIDE
DEAD LOAD
EACH
EXTERIOR
EXPANSION
EXISTING
EACH WAY
ELEVATION
EQUAL
EL
EW
EQ
EXIST, EX
EXT
EXP
DL
ES
EA
DOWN
DRAWING
DIAGONAL
DIAMETER
DEFORMED BAR ANCHORS
DN
DIAM
DWG
DIAG
DBA
BETWEEN
BASEMENT
BEARING
BEARING PLATE MARKBP
BRG
BTWN
BSMT
ALTERNATE
ANCHOR BOLT
BEAM
BUILDING
BLOCKING
BEAM MARK
ARCHITECT(URAL)
BF
B
BM
BLDG
BLKG
AB
ARCH
ALT
TOP OF FOOTING ELEVATION
TOP OF CONCRETE
TOP OF PIER ELEVATION
TOP OF STEEL ELEVATION
TOP OF WALL ELEVATION
UNLESS NOTED OTHERWISE
WELDED WIRE FABRIC
UNDERSIDE METAL DECK ELEVATIONUMD
W/
WWF
WP
VERT
WORK POINT
VERTICAL
WITH
UNEXC
TOW
UNO
TYP
TOC
TOP
TOS
TEMP
TF
UNEXCAVATED
TYPICAL
TEMPORARY
MISCELLANEOUSMISC
PROJECTIONPROJ
POUNDS PER SQ. FOOT
POUNDS PER SQ. INCH
REVISION, REVISE(D)
REINFORCE(D), (ING)
STRUCT
SPA
SL
STD
STL
SIM
SB
SQ
REQ'D
STANDARD
STRUCTURAL
SNOW LOAD
SPACES
STEEL
REQUIRED
SOIL BORING
SIMILAR
SQUARE
QTY
REV
RD
REINF
RAD
PT
PSF
PSI
QUANTITY
ROOF DRAIN
RADIUS
POST TENSION/PRESSURE TREATED
MASONRY OPENING
NOT IN CONTRACT
PRECAST CONCRETE
POUNDS PER LINEAR FOOT
PRECAST PLANK MARK
P
PL
PLF
PP
PERIM
PC
OF
OPP
OPNG
OC
PIER MARK
PERIMETER
PLATE
OPPOSITE
OUTSIDE FACE
OPENING
ON CENTER(S)
NIC
NTS
NS
MTL
MATL
MO
NOT TO SCALE
NEAR SIDE
MATERIAL
METAL
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LP
MANUF
MAX
MAS
LLH
LL
LLV
L
LOW POINT
MAXIMUM
MASONRY
MMANUFACTURER(ED)
LINTEL MARK
LIVE LOAD
ELEVATORELEV
VIF VERIFY IN FIELD
WIND FRAMEWF
LAMINATED VENEER LUMBERLVL
BOD BOTTOM OF DECK
PEB PRE-ENGINEERED BUILDING
EACH END
THROUGH OUT
TJI
T0
WOOD I JOIST
EE
REM REMAINDER
SE SPECIALTY DESIGN ENGINEER
EF EACH FACE
PSL PARALLEL STRAND LUMBER COLUMN
SC SLIP CRITICAL
HS HIGH STRENGTH
AFF ABOVE FINISH FLOOR
CENTER OF MASONRY WALLCOM
COS CENTER OF STUD
COMP COMPOSITE
CAST IN PLACECIP
COLUMN MARK
COLUMN
CONNECTION
CONTINUOUS
CONCRETE
CONSTRUCTION
CONTROL JOINT
CLEAR(ANCE)
CONCRETE MASONRY UNIT
C
CLR
COL
CMU
CJ
CONN
CONT
CONST
CONC
JACK TRUSSJTR
HIP TRUSSHTR
GT GIRDER TRUSS
F FOOTING MARK
FUT
FS
FD
FDN
FTG
FLOOR DRAIN
FOOTING STEP
FUTURE
FOOTING
FOUNDATION
FACE OF STUD
FACE OF MASONRY WALL
FOS
FOM
BOTTOM OF STEELBOS
STAINLESS STEELSS
ADJACENTADJ
ADDITIONALADDL
APPROXIMATE(LY)APPROX
COORD COORDINATE(TION)
DETAILDTL
EDGE OF JOIST
EDGE OF SLAB
EDGE OF DECK
EOS
EOD
EOJ
EQUIPMENTEQUIP
FACE OF BUILDINGFOB
MIN MINIMUM
POWER DRIVEN FASTENERPDF
RTU ROOF TOP UNIT
SOG
SJI
SLAB ON GRADE
STEEL JOIST INSTITUTE
THK THICK(NESS), (ENED)
ENGINEERS PLANNERS LANDSCAPE ARCHITECTS SURVEYORS 3D LASER SCANNING
VIKA MARYLAND LLC
W W W . V I K A . C O M
(301) 916-4100 FAX (301) 916-2262
20251 CENTURY BOULEVARD SUITE 400 GERMANTOWN, MARYLAND 20874
1451 Dolley Madison Blvd. Suite 220 McLean VA 22101-3812 703-827-9552 www.ehlert-bryan.com Department of
Veterans Affairs
Drawing Title:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Approved: Project Director
Project Title: Project Number:
Building Number:
Drawing Number:Location:
Date: Checked: Drawn:
Office of Construction and Facilities Management
ARCHITECTS/ENGINEERS:CONSULTANTS:
FULLY SPRINKLERED
STAMP
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t th re e i n c h o n e fo o t
VA FORM 08-6231. Oct 1978
H D
H D
P ro je ct
X
X X
X X
X X
X
"C o n su lt.
P ro je ct
X
X X
X X
X
635 S. Fairfax Street Alexandria, VA 22314 703.838.8414 www.healingdesign.com
Virginia
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.com317.464.9090
220 North College Avenue
Indianapolis, Indiana 46202
EB#1450072
DWG. OF
:2 :4
A M
C U s e rs a s c h m it t\ D o c u m e n ts J o b s s tr u c
R ic h m o n d
V A M C a s c h m it t.
rv t
S-001
1201 BROAD ROCK BLVD. RICHMOND, VA 23249
COMMUNITY LIVING CENTER
EXPANSION AND RENOVATION
STRUCTURAL NOTES AND ABBREVIATIONS
APS SLSAPRIL 14, 2017
VA 246 14R 0013
100% CONSTRUCTION DOCUMENTS
ENGINEERS PLANNERS LANDSCAPE ARCHITECTS SURVEYORS 3D LASER SCANNING
VIKA MARYLAND LLC
W W W . V I K A . C O M
(301) 916-4100 FAX (301) 916-2262
20251 CENTURY BOULEVARD SUITE 400 GERMANTOWN, MARYLAND 20874
1451 Dolley Madison Blvd. Suite 220 McLean VA 22101-3812 703-827-9552 www.ehlert-bryan.com Department of
Veterans Affairs
Drawing Title:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Approved: Project Director
Project Title: Project Number:
Building Number:
Drawing Number:Location:
Date: Checked: Drawn:
Office of Construction and Facilities Management
ARCHITECTS/ENGINEERS:CONSULTANTS:
FULLY SPRINKLERED
STAMP
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e i n c h o n e fo o t
VA FORM 08-6231. Oct 1978
H D
H D
P ro je ct
X
X X
X X
X X
X
"C o n su lt.
P ro je ct
X
X X
X X
X
635 S. Fairfax Street Alexandria, VA 22314 703.838.8414 www.healingdesign.com
Virginia
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.com317.464.9090
220 North College Avenue
Indianapolis, Indiana 46202
EB#1450072
DWG. OF
:2 :4
A M
C U s e rs a s c h m it t\ D o c u m e n ts J o b s s tr u c
R ic h m o n d
V A M C a s c h m it t.
rv t
S-002
1201 BROAD ROCK BLVD. RICHMOND, VA 23249
COMMUNITY LIVING CENTER
EXPANSION AND RENOVATION
SPECIAL INSPECTIONS
Checker SLSAPRIL 14, 2017
VA 246 14R 0013
100% CONSTRUCTION DOCUMENTS
SCHEDULE OF SPECIAL INSPECTIONS
VERIFICATION AND INSPECTION Y/N FREQUENCY CONTINUOUS
FREQUENCY
PERIODIC REFERENCED STANDARD IBC REFERENCE SCOPE OF SERVICE
RESPONSIBLE
PARTY
A. APPLICATION OF PRESTRESSING FORCES. N - - ACI 318 1705.3 - -
B. GROUTING OF BONDED PRESTRESSING TENDONS IN THE
SEISMIC-FORCE-RESISTING SYSTEM.
N - - ACI 318 1705.3 - -
10 ERECTION OF PRECAST CONCRETE MEMBERS. N - - ACI 318 1705.3 - -
11 VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO
STRESSING OF TENDONS IN POSTTENSIONED CONCRETE & PRIOR
TO REMOVAL OF SHORES & FORMS FROM BEAMS & STRUCTURAL
SLABS.
N - - ACI 318 1705.3 - -
12 INSPECT FORMWORK FOR SHAPE, LOCATION & DIMENSIONS OF
THE CONCRETE MEMBER BEING FORMED.
Y - X ACI 318 1705.3 VERIFY IN ACCORDANCE WITH APPROVED FORMWORK SHOP DRAWINGS. SIER
MASONRY
LEVEL A QUALITY ASSURANCE: RISK CATEGORY I, II, OR III
STRUCTURES DESIGNED IN ACCORDANCE WITH CHAPTER 5, 6, OR
7.
N 1705.4 -
LEVEL B QUALITY ASSURANCE: RISK CATEGORY IV STRUCTURES
DESIGNED IN ACCORDANCE WITH CHAPTERS 6 OR 7 & RISK
CATEGORY I, II, OR III STRUCTURES DESIGNED IN ACCORDANCE
WITH CHAPTERS OTHER THAN 5, 6, OR 7.
N 1705.4 -
LEVEL C QUALITY ASSURANCE: RISK CATEGORY IV STRUCTURES
DESIGNED IN ACCORDANCE WITH CHAPTERS OTHER THAN 5, 6, OR
7.
N 1705.4 -
1 COMPLIANCE WITH REQUIRED INSPECTION PROVISIONS OF THE
CONSTRUCTION DOCUMENTS & THE APPROVED SUBMITTALS
SHALL BE VERIFIED.
N - - ACI530.1 1705.4 - -
2 VERIFICATION OF F’M & F’AAC PRIOR TO CONSTRUCTION (AND
FOR EVERY 5,000 SQUARE FEET DURING CONSTRUCTION FOR
LEVEL C).
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
3 VERIFICATION OF PROPORTIONS OF MATERIALS IN PREMIXED OR
PREBLENDED MORTAR, PRESTRESSING GROUT, & GROUT OTHER
THAN SELF-CONSOLIDATING GROUT AS DELIVERED TO THE SITE.
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
4 VERIFICATION OF SLUMP FLOW & VSI AS DELIVERED TO THE SITE
FOR SELF-CONSOLIDATING GROUT.
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
5 THE FOLLOWING SHALL BE VERIFIED TO ENSURE COMPLIANCE: -
A. PROPORTIONS OF SITE-PREPARED MORTAR, GROUT, &
PRESTRESSING GROUT FOR BONDED TENDONS.
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
B. PLACEMENT OF MASONRY UNITS & CONSTRUCTION OF MORTAR
JOINTS.
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
C. GRADE, TYPE, & SIZE OF REINFORCEMENT, ANCHOR BOLTS,
PRESTRESSING TENDONS, & ANCHORAGES
N - - TMS 402/ACI
530/ASCE 5/TMS 602/ACI
530.1/ASCE 6
1705.4 - -
D. PLACEMENT OF REINFORCEMENT, CONNECTORS & PRESTRESSING
TENDONS & ANCHORAGES.
N - - TMS 402/ACI
530/ASCE 5/TMS 602/ACI
530.1/ASCE 6
1705.4 - -
E. GROUT SPACE PRIOR TO GROUTING. N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
F. PLACEMENT OF GROUT & PRESTRESSING GROUT FOR BONDED
TENDONS.
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
G. SIZE & LOCATION OF STRUCTURAL ELEMENTS. N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
H. TYPE, SIZE & LOCATION OF ANCHORS, INCLUDING OTHER DETAILS
OF ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS,
FRAMES OR OTHER CONSTRUCTION.
N - - TMS 402/ACI
530/ASCE 5
1705.4 - -
I. WELDING OF REINFORCEMENT. N - - TMS 402/ACI
530/ASCE 5
1705.4 - -
J. PREPARATION, CONSTRUCTION & PROTECTION OF MASONRY
DURING COLD WEATHER (TEMPERATURE BELOW 40°F) OR HOT
WEATHER (TEMPERATURE ABOVE 90°F).
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
K. APPLICATION & MEASUREMENT OF PRESTRESSING FORCE. N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
L. PLACEMENT OF AAC MASONRY UNITS & CONSTRUCTION OF
THIN-BED MORTAR JOINTS.
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
M. PROPERTIES OF THIN-BED MORTAR FOR AAC MASONRY. N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
N. VERIFY PRE-STRESSING TECHNIQUE IS IN COMPLIANCE AS
CONSTRUCTION BEGINS
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 -
6 OBSERVE PREPARATION OF GROUT SPECIMENS, MORTAR
SPECIMENS, AND/OR PRISMS.
N - - TMS 602/ACI
530.1/ASCE 6
1705.4 - -
WOOD CONSTRUCTION
1 INSPECTION OF FABRICATORS & FABRICATION PROCEDURES FOR
PREFABRICATED WOOD STRUCTURAL ELEMENTS.
N - - 1705.5 - -
2 HIGH-LOAD DIAPHRAGMS DESIGNED IN ACCORDANCE WITH
SECTION 2306.2
N - - 1705.5 - -
3 METAL PLATE CONNECTED WOOD TRUSSES SPANNING 60 FEET OR
MORE
N - - 1705.5 - -
SOILS -
1 VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE
ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY.
Y - X Geotechnical Report 1705.6 - SIER
2 VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH & HAVE
REACHED PROPER MATERIAL.
Y - X Geotechnical Report 1705.6 - SIER
3 PERFORM CLASSIFICATION & TESTING OF COMPACTED FILL
MATERIALS.
Y - X Geotechnical Report 1705.6 - SIER
4 VERIFY USE OF PROPER MATERIALS, DENSITIES, & LIFT
THICKNESSES DURING PLACEMENT & COMPACTION OF
COMPACTED FILL.
Y X - Geotechnical Report 1705.6 TEST FREQUENCY PER SPECIFICATIONS, BUT NOT LESS THAN ONE TEST EVERY 2,000
SQUARE FEET FOR EACH LAYER OF FILL OR PROOF-ROLLING
SIER
5 PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE
& VERIFY THAT SITE HAS BEEN PREPARED PROPERLY.
Y - X Geotechnical Report 1705.6 - SIER
DRIVEN DEEP FOUNDATIONS
1 VERIFY ELEMENT MATERIALS, SIZES, & LENGTHS COMPLY WITH
THE REQUIREMENTS.
N - - 1705.7 - -
2 DETERMINE CAPACITIES OF TEST ELEMENTS & CONDUCT
ADDITIONAL LOAD TESTS, AS REQUIRED.
N - - 1705.7 - -
3 OBSERVE DRIVING OPERATIONS & MAINTAIN COMPLETE &
ACCURATE RECORDS FOR EACH ELEMENT.
N - - 1705.7 - -
4 VERIFY PLACEMENT LOCATIONS & PLUMBNESS, CONFIRM TYPE &
SIZE OF HAMMER, RECORD NUMBER OF BLOWS PER FOOT OF
PENETRATION, DETERMINE REQUIRED PENETRATIONS TO ACHIEVE
DESIGN CAPACITY, RECORD TIP & BUTT ELEVATIONS, & DOCUMENT
ANY DAMAGE TO FOUNDATION ELEMENT.
N - - 1705.7 - -
5 PERFORM ADDITIONAL INSPECTIONS FOR STEEL ELEMENTS PER
STEEL INSPECTION REQUIREMENTS.
N - - 1705.7 - -
6 PERFORM ADDITIONAL INSPECTIONS FOR CONCRETE &
CONCRETE-FILLED ELEMENTS PER CONCRETE INSPECTION
REQUIREMENTS.
N - - 1705.7 - -
7 PERFORM ADDITIONAL INSPECTIONS FOR SPECIALTY ELEMENTS
AS DETERMINED BY THE REGISTERED DESIGN PROFESSIONAL IN
CHARGE.
N - - 1705.7 - -
CAST-IN-PLACE DEEP FOUNDATIONS
1 OBSERVE DRILLING OPERATIONS & MAINTAIN COMPLETE &
ACCURATE RECORDS FOR EACH ELEMENT.
N - - 1705.8 - -
2 VERIFY PLACEMENT LOCATIONS & PLUMBNESS, CONFIRM
ELEMENT DIAMETERS, BELL DIAMETERS (IF APPLICABLE),
LENGTHS, EMBEDMENT INTO BEDROCK (IF APPLICABLE), &
ADEQUATE END-BEARING STRATA CAPACITY. RECORD CONCRETE
OR GROUT VOLUMES.
N - - 1705.8 - -
3 PERFORM ADDITIONAL INSPECTIONS FOR CONCRETE ELEMENTS
PER CONCRETE INSPECTION REQUIREMENTS.
N - - 1705.8 - -
HELICAL PILE FOUNDATIONS
1 RECORD INSTALLATION EQUIPMENT USED, PILE DIMENSIONS, TIP
ELEVATIONS, FINAL DEPTH, & FINAL INSTALLATION TORQUE.
N - - GEOTECHNICAL REPORT &
APPROVED SHOP DRAWINGS
1705.9 - -
SPRAYED FIRE-RESISTANT MATERIALS -
1 CONDITIONS OF SUBSTRATES N - - APPROVED FIRE-RESISTANCE
DESIGN
1705.13 - -
2 THICKNESS OF APPLICATION N - - APPROVED FIRE-RESISTANCE
DESIGN
1705.13 - -
3 DENSITY IN POUND PER CUBIC FOOT N - - APPROVED FIRE-RESISTANCE
DESIGN
1705.13 - -
4 BOND STRENGTH ADHESION /COHESION N - - APPROVED FIRE-RESISTANCE
DESIGN
1705.13 - -
5 CONDITION OF FINISHED APPLICATION N - - APPROVED FIRE-RESISTANCE
DESIGN
1705.13 - -
6 FIRE-RESISTANT PENETRATIONS & JOINTS N - - APPROVED FIRE-RESISTANCE
DESIGN
1705.16 - -
LIGHT GAGE METAL FRAMING Y - X APPROVED SHOP DRAWINGS - REVIEW FOR CONFORMANCE WITH APPROVED SHOP DRAWINGS & PROVIDE FINAL
CERTIFICATION LETTER
SE
MASTIC & INTUMESCENT FIRE-RESISTANT COATINGS N - - AWCI-12B & APPROVED
FIRE-RESISTANCE DESIGN
1705.14 - -
EXTERIOR INSULATION & FINISH SYSTEMS (EIFS) Y - - - 1705.15 - SIER
GEOPIERS Y REVIEW FOR COMPLIANCE WITH APPROVED SHOP DRAWINGS AND SPECIFICATIONS.
PROVIDE FINAL CERTIFICATION REPORT.
SE &SER
* INSPECTION AGENTS NAME COMPANY ADDRESS
1. SPECIAL INSPECTION ENGINEER OF RECORD (SIER) 1. 1. 1.
2. INSPECTION & TESTING AGENCY (ITA) 2. 2. 2.
3. GEOTECHNICAL ENGINEER OF RECORD (GER) 3. 3. 3
4. SPECIALTY ENGINEER (SE) 4. 4. 4.
5. STRUCTURAL ENGINEER OF RECORD (SER) 5. ALEXANDER P. SALMIN, PE 5. EHLERT BRYAN 5. 1451 DOLLEY MADISON BLVD, SUITE 220, MCLEAN, VA 22101
SCHEDULE OF SPECIAL INSPECTIONS
VERIFICATION AND INSPECTION Y/N FREQUENCY CONTINUOUS
FREQUENCY
PERIODIC REFERENCED STANDARD IBC REFERENCE SCOPE OF SERVICE
RESPONSIBLE
PARTY
STRUCTURAL STEEL 1705.2
1 HIGH-STRENGTH BOLTING: INSPECTION TASKS PRIOR TO BOLTING
A. MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER
MATERIALS.
Y X - - 1705.2 - SIER
B. FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS Y - X AISC 360 & APPLICABLE ASTM
MATERIAL STANDARDS
1705.2 - SIER
C. PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE,
TYPE, BOLT LENGTH IF THREADS ARE TO BE EXCLUDED FROM
SHEAR PLANE).
Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS ONLY SIER
D. PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL. Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS ONLY SIER
E. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING
SURFACE CONDITION & HOLE PREPARATION, IF SPECIFIED, MEET
APPLICABLE REQUIREMENTS
Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS ONLY SIER
F. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION
PERSONNEL OBSERVED & DOCUMENTED FOR FASTENER
ASSEMBLIES & METHODS USED.
Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS ONLY SIER
G. PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS, &
OTHER FASTENER COMPONENTS.
Y - X AISC 360 1705.2 - SIER
2 HIGH-STRENGTH BOLTING: INSPECTION TASKS DURING BOLTING
A. FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL
HOLES & WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED.
Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS USING CALIBRATED WRENCH METHOD
OR TURN-OF-NUT WITHOUT MATCHMARKING ONLY
SIER
B. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO
PRETENSIONING OPERATION.
Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS USING CALIBRATED WRENCH METHOD
OR TURN-OF-NUT WITHOUT MATCHMARKING ONLY
SIER
C. FASTENER COMPONENT NOT TURNED BY THE WRENCH
PREVENTED FROM ROTATING.
Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS USING CALIBRATED WRENCH METHOD
OR TURN-OF-NUT WITHOUT MATCHMARKING ONLY
SIER
D. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC
SPECIFICATION, PROGRESSING SYSTEMATICALLY FROM THE MOST
RIGID POINT TOWARD THE FREE EDGES.
Y - X AISC 360 1705.2 FOR PRETENSIONED & SLIP CRITICAL JOINTS USING CALIBRATED WRENCH METHOD
OR TURN-OF-NUT WITHOUT MATCHMARKING ONLY
SIER
3 HIGH-STRENGTH BOLTING: INSPECTION TASKS AFTER BOLTING
A. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED
CONNECTIONS.
Y X - AISC 360 1705.2 - SIER
4 WELDING: INSPECTION TASKS PRIOR TO WELDING
A. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE. Y X X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 ESTABLISH THE JOINT WELDING PROCEDURES ARE PREQUALIFIED OR TEST IN
ACCORDANCE WITH AWS D1.1 QUALIFICATION PROCEDURES
SIER
B. MANUFACTURER'S CERTIFICATIONS FOR WELDING CONSUMABLES
AVAILABLE.
Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
C. MATERIAL IDENTIFICATION (TYPE/GRADE). Y - X AISC 360 1705.2 - SIER
D. FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY):
1) JOINT PREPARATION Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
2) DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL) Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
3) CLEANLINESS (CONDITION OF STEEL SURFACES) Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
4) TACKING (TACK WELD QUALITY & LOCATION) Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
5) BACKING TYPE & FIT (IF APPLICABLE) Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
E. CONFIGURATION & FINISH OF ACCESS HOLES Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
F. FIT-UP OF FILLET WELDS:
1) DIMENSIONS (ALIGNMENT, GAPS AT ROOT) Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
2) CLEANLINESS (CONDITION OF STEEL SURFACES) Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
3) TACKING (TACK WELD QUALITY & LOCATION) Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
5 WELDING: INSPECTION TASKS DURING WELDING
A. USE OF QUALIFIED WELDERS Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 WELDERS MUST BE CURRENTLY CERTIFIED UNDER AMERICAN WELDING SOCIETY
QUALIFICATION PROCEDURES.
SIER
B. CONTROL & HANDLING OF WELDING CONSUMABLES INCLUDING
PACKAGING & EXPOSURE CONTROL
Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
C. ENVIRONMENTAL CONDITIONS: WIND SPEED WITHIN LIMITS,
PRECIPITATION, & TEMPERATURE.
Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
D. WPS FOLLOWED: SETTINGS ON WELDING EQUIPMENT, TRAVEL
SPEED, SELECTED WELDING MATERIALS, SHIELDING GAS
TYPE/FLOW RATE, PREHEAT APPLIED, INTERPASS TEMPERATURE
MAINTAINED (MIN./MAX.), PROPER POSITION (F,V,H,OH).
Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
E. WELDING TECHNIQUES: INTERPASS & FINAL CLEANING, EACH PASS
WITHIN PROFILE LIMITATIONS, EACH PASS MEETS QUALITY
REQUIREMENTS.
Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
6 WELDING: INSPECTION TASKS AFTER WELDING
A. WELDS CLEANED Y - X AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
B. SIZE, LENGTH, & LOCATION OF WELDS Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
C. WELDS MEET VISUAL ACCEPTANCE CRITERIA: CRACK
PROHIBITION, WELD/BASE-METAL FUSION, CRATER CROSS
SECTION, WELD PROFILES, WELD SIZE, UNDERCUT, POROSITY
Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 PERFORM ULTRASONIC TESTING OF ALL FULL PENETRATION FIELD & SHOP WELDS TO
COMPLY WITH ASTM E 164 PER PROJECT SPECIFICATIONS.
SIER
D. ARC STRIKES Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
E. K-AREA Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 WHEN WELDING DOUBLER PLATES, CONTINUITY PLATES, OR STIFFENERS HAS BEEN
PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA FOR CRACKS
WITHIN 3 IN. OF THE WELD.
SIER
F. BACKING REMOVED & WELD TABS REMOVED (IF REQUIRED) Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
G. REPAIR ACTIVITIES Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
H. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR
MEMBER
Y X - AISC 360 & APPLICABLE AWS
DOCUMENTS
1705.2 - SIER
7 STEEL ELEMENT OF COMPOSITE CONSTRUCTION PRIOR TO
CONCRETE PLACEMENT
A. PLACEMENT & INSTALLATION OF STEEL DECK Y X - AWS D1.3
AISC 360
1705.2 - SIER
B. PLACEMENT & INSTALLATION OF STEEL HEADED STUD ANCHORS Y X - AWS D1.1
AISC 360
1705.2 - SIER
C. DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS Y X - AISC 360 1705.2 - SIER
8 INSPECTION OF FABRICATORS & FABRICATION PROCEDURES Y - X AISC 360 1704.2.5 RESPONSIBLE AGENT SHALL VISIT THE FABRICATOR'S PLANT & VERIFY QC
PROCEDURES ARE AISC COMPLIANT & CURRENT, UNLESS FABRICATOR IS
REGISTERED & APPROVED BY THE JURISDICTION.
SIER
STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL
1 MATERIAL VERIFICATION OF COLD-FORMED STEEL DECK:
A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARDS
SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS
Y - X APPLICABLE ASTM MATERIAL
STANDARDS
1705.2.2 - SIER
B. MANUFACTURER'S CERTIFIED TEST REPORTS. Y - X - 1705.2.2 - SIER
2 INSPECTION OF WELDING:
A. COLD-FORMED STEEL DECK: - -
1) FLOOR & ROOF DECK WELDS. Y - X AWS D1.3 1705.2.2 - SIER
B. REINFORCING STEEL:
1) VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER
THAN ASTM A 706.
N - - AWS D1.4
ACI 318
1705.2.2 - -
2) REINFORCING STEEL RESISTING FLEXURAL & AXIAL FORCES IN
INTERMEDIATE & SPECIAL MOMENT FRAMES, & BOUNDARY
ELEMENTS OF SPECIAL STRUCTURAL WALLS OF CONCRETE &
SHEAR REINFORCEMENT.
N - - AWS D1.4
ACI 318
1705.2.2 - -
3) SHEAR REINFORCEMENT. N - - AWS D1.4
ACI 318
1705.2.2 - -
4) OTHER REINFORCING STEEL. N - - AWS D1.4
ACI 318
1705.2.2 - -
CONCRETE
1 INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING
TENDONS, & PLACEMENT.
Y - X ACI 318 1705.3 VERIFY SIZE, LOCATION, SPACING ORIENTATION, COVER, SPLICING, & CONFORMANCE
WITH THE CONTRACT DOCUMENTS, AS SUPPLEMENTED WITH APPROVED SHOP
DRAWINGS OR OTHER SUBMITTALS. CONFIRM THAT THE SURFACE OF THE
REINFORCING STEEL IS FREE OF FORM RELEASE OIL OR OTHE
SIER
2 INSPECTION OF REINFORCING STEEL WELDING.
A. VERIFICATION OF WELDABILITY OF REINFORCING STEEL OTHER
THAN ASTM A 706.
N - - AWS D1.4
ACI 318
1705.3 - -
B. REINFORCING STEEL RESISTING FLEXURAL & AXIAL FORCES IN
INTERMEDIATE & SPECIAL MOMENT FRAMES, & BOUNDARY
ELEMENTS OF SPECIAL STRUCTURAL WALLS OF CONCRETE &
SHEAR REINFORCEMENT.
N - - AWS D1.4
ACI 318
1705.3 - -
C. SHEAR REINFORCEMENT. N - - AWS D1.4
ACI 318
1705.3 - -
D. OTHER REINFORCING STEEL. N - - AWS D1.4
ACI 318
1705.3 - -
3 INSPECTION OF BOLTS TO BE INSTALLED IN CONCRETE PRIOR TO &
DURING PLACEMENT OF CONCRETE WHERE ALLOWABLE LOADS
HAVE BEEN INCREASED OR WHERE STRENGTH DESIGN IS USED.
Y - X ACI 318 1705.3 PRECISE LOCATION OF ANCHOR RODS IS NOT EXPECTED BUT VERIFY THE
CONTRACTOR HAS TAKEN APPROPRIATE STEPS TO CORRECTLY POSITION THEM
SUCH AS ENGAGING A SURVEYOR OR SETTING UP A SYSTEM OF STRING LINES &
BATTER BOARDS & THAT CORRECT GRADE & SIZE OF ANCHORS IS
SIER
4 INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED
CONCRETE.
Y - X ACI 318 1705.3 INSPECT IN ACCORDANCE WITH MANUFACTURER'S REQUIREMENTS. SIER
5 VERIFYING USE OF REQUIRED DESIGN MIX. Y - X ACI 318 1705.3 VERIFY APPROVED MIX DESIGN SIER
6 AT THE TIME FRESH CONCRETE IS SAMPLED TO FABRICATE
SPECIMENS FOR STRENGTH TESTS, PERFORM, SLUMP & AIR
CONTENT TESTS, & DETERMINE THE TEMPERATURE OF THE
CONCRETE.
Y X - ASTM C 172/ASTM C 31/ACI 318 1705.3 TEST IN ACCORDANCE WITH PROJECT SPECIFICATIONS, BUT NOT LESS THAN ONCE
PER DAY PER CLASS OF CONCRETE OR ONCE PER 150 CUBIC YARDS PER DAY OR
ONCE PER 5,000 SQUARE FEET OF SLAB OR WALL PER DAY. CYLINDERS MUST BE
PROPERLY HANDLED & STORED ON SITE UNTIL TRANS
SIER
7 INSPECTION OF CONCRETE & SHOTCRETE PLACEMENT FOR
PROPER APPLICATION TECHNIQUES.
Y X - ACI 318 1705.3 VERIFY CONFORMANCE WITH PROJECT SPECIFICATIONS. INSPECTOR SHALL BE
WHERE THE CONCRETE IS BEING PLACED RATHER THAN WHERE CONCRETE TRUCKS
ARE DISCHARGING THEIR LOADS. INSPECTOR NEEDS TO BE PRESENT WHILE SLAB IS
BEING FLOATED & POWER TROWELED.
SIER
8 INSPECTION FOR MAINTENANCE OF SPECIFIED CURING
TEMPERATURE & TECHNIQUES.
Y - X ACI 318 1705.3 VERIFY CONFORMANCE WITH PROJECT SPECIFICATIONS & ACI SIER
9 INSPECTION OF PRESTRESSED CONCRETE:
F E D C
B
C13
C10
H
L K
J
G
C11
C12
A
LINE OF FUTURE
LOBBY & BUILDING
C10.2
F E D C
B
C13
C10
H
L K
J
G
C11
C12
A
LINE OF FUTURE
LOBBY & BUILDING
C10.2
F E D C
B
C13
C10
H
L K
J
G
C11
C12
A
LINE OF FUTURE
LOBBY & BUILDING
C10.2
25 PSF
30 PSF
80 PSF
100 PSF
125 PSF
150 PSF
200 PSF
LIVE LOAD DIAGRAM KEY
ENGINEERS PLANNERS LANDSCAPE ARCHITECTS SURVEYORS 3D LASER SCANNING
VIKA MARYLAND LLC
W W W . V I K A . C O M
(301) 916-4100 FAX (301) 916-2262
20251 CENTURY BOULEVARD SUITE 400 GERMANTOWN, MARYLAND 20874
1451 Dolley Madison Blvd. Suite 220 McLean VA 22101-3812 703-827-9552 www.ehlert-bryan.com Department of
Veterans Affairs
Drawing Title:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Approved: Project Director
Project Title: Project Number:
Building Number:
Drawing Number:Location:
Date: Checked: Drawn:
Office of Construction and Facilities Management
ARCHITECTS/ENGINEERS:CONSULTANTS:
FULLY SPRINKLERED
STAMP
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e i n c h o n e fo o t
VA FORM 08-6231. Oct 1978
H D
H D
P ro je ct
X
X X
X X
X X
X
"C o n su lt.
P ro je ct
X
X X
X X
X
635 S. Fairfax Street Alexandria, VA 22314 703.838.8414 www.healingdesign.com
Virginia
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.com317.464.9090
220 North College Avenue
Indianapolis, Indiana 46202
EB#1450072
DWG. OF
:2 :4
A M
C U s e rs a s c h m it t\ D o c u m e n ts J o b s s tr u c
R ic h m o n d
V A M C a s c h m it t.
rv t
S-003
1201 BROAD ROCK BLVD. RICHMOND, VA 23249
COMMUNITY LIVING CENTER
EXPANSION AND RENOVATION
LIVE LOAD DIAGRAMS
Checker SLSAPRIL 14, 2017
VA 246 14R 0013
100% CONSTRUCTION DOCUMENTS
SCALE: NOT TO SCALES-003
LIVE LOAD DIAGRAM - LEVEL 1A
SCALE: NOT TO SCALES-003
LIVE LOAD DIAGRAM - INTERSTITIAL FRAMINGB
SCALE: NOT TO SCALES-003
LIVE LOAD DIAGRAM - ROOF/FUTURE LEVEL 2C
F E D C
B
C13
C10
H
L K
J
G
C11
C12
A
LINE OF FUTURE
LOBBY & BUILDING
C10.2
F E D C
B
C13
C10
H
L K
J
G
C11
C12
A
LINE OF FUTURE
LOBBY & BUILDING
C10.2
F E D C
B
C13
C10
H
L K
J
G
C11
C12
A
LINE OF FUTURE
LOBBY & BUILDING
C10.2
NOTES:
1. INTERSTITIAL SPACES ARE TAKEN AS LOCATED BELOW THE FUTURE ROOF AND
FUTURE LEVEL 3 FRAMING.
2. DEAD LOAD FOR INTERSTITIAL SPACE IS TAKEN AS A UNIFORM 55 PSF.
25 PSF
30 PSF
80 PSF
100 PSF
125 PSF
150 PSF
200 PSF
LIVE LOAD DIAGRAM KEY
ENGINEERS PLANNERS LANDSCAPE ARCHITECTS SURVEYORS 3D LASER SCANNING
VIKA MARYLAND LLC
W W W . V I K A . C O M
(301) 916-4100 FAX (301) 916-2262
20251 CENTURY BOULEVARD SUITE 400 GERMANTOWN, MARYLAND 20874
1451 Dolley Madison Blvd. Suite 220 McLean VA 22101-3812 703-827-9552 www.ehlert-bryan.com Department of
Veterans Affairs
Drawing Title:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Approved: Project Director
Project Title: Project Number:
Building Number:
Drawing Number:Location:
Date: Checked: Drawn:
Office of Construction and Facilities Management
ARCHITECTS/ENGINEERS:CONSULTANTS:
FULLY SPRINKLERED
STAMP
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e i n c h o n e fo o t
VA FORM 08-6231. Oct 1978
H D
H D
P ro je ct
X
X X
X X
X X
X
"C o n su lt.
P ro je ct
X
X X
X X
X
635 S. Fairfax Street Alexandria, VA 22314 703.838.8414 www.healingdesign.com
Virginia
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.com317.464.9090
220 North College Avenue
Indianapolis, Indiana 46202
EB#1450072
DWG. OF
:2 :4
A M
C U s e rs a s c h m it t\ D o c u m e n ts J o b s s tr u c
R ic h m o n d
V A M C a s c h m it t.
rv t
S-004
1201 BROAD ROCK BLVD. RICHMOND, VA 23249
COMMUNITY LIVING CENTER
EXPANSION AND RENOVATION
FUTURE LIVE LOAD DIAGRAMS
Checker SLSAPRIL 14, 2017
VA 246 14R 0013
100% CONSTRUCTION DOCUMENTS
SCALE: NOT TO SCALES-004
LIVE LOAD DIAGRAM - FUTURE INTERSTITIAL SPACEA
SCALE: NOT TO SCALES-004
LIVE LOAD DIAGRAM - FUTURE LEVEL 3B
SCALE: NOT TO SCALES-004
LIVE LOAD DIAGRAM - FUTURE ROOFC
L=COLUMN BAY LENGTH
SPLICE
CLASS B
NO SPLICE
0.2L
NO SPLICE
0.2L
ALLOWABLE SPLICE ZONE
0.6L
REINF. TIE
NOTE: TIE SPLICES ARE ONLY PERMITTED IN THE MIDDLE 60%
OF THE BAY, IN THE DIRECTION OF THE TIE.
ALLOWABLE SPLICE ZONE FOR
INTERNAL & PERIPHERAL TIES
SEE PLAN
EOS 8"
BAR Ø MAX.
SPACED @ 4 4" MAX.
1ST INTERNAL TIE BAR
METAL DECK,
ORIENTATION VARIES
PERIPHERAL TIE BARS
(MAY BE DOUBLE
STACKED)
INTERNAL TIE W/ 135°
SEISMIC HOOK
STEEL BEAM
TYPICAL ADD'L SLAB REINF. @ PERIMETER
AND SLAB OPENINGS
SEE 2/S-303 FOR
TYPICAL REINF.
@ POUR STOP
3'-0" MAX.
8" 8"
BAR Ø MAX.
SPACED @ 4 4" MAX.
INTERNAL TIE W/ 135°
SEISMIC HOOK
1ST INTERNAL TIE BAR
PERIPHERAL TIE BARS
INTERNAL TIE W/ 135°
SEISMIC HOOK
STEEL BEAM
PERIPHERAL TIE
BARS
4" MAX.
BAR Ø MAX.
SPACED @ 4
1ST INTERNAL
TIE BAR
TYPICAL ADD'L SLAB REINF. @ SLAB STEP
3'-0" MAX. 3'-0" MAX.
TYPICAL SLAB REINFORCING
/4
/4
C L E
A R
/4
WELDED WIRE FABRIC.
SEE PLAN
CONC. SLAB ON
2" METAL DECK.
SLAB REINF. SEE S.001
CHAIR AS REQ'D TO
ACHIEVE 3/4" CLEAR ON
WELDED WIRE FABRIC.
REF. FIN FLOOR
TYPICAL SLAB REINFORCING NOTES
1. SLAB REINFORCING DETAILS TO COMPLY W/ TIE FORCE REQUIREMENTS
OF UFC 4-023-03 (14 JULY 2009).
2. TERMINATE ENDS OF TIES AT SLAB EDGES W/ SEISMIC HOOKS W/ 135 BEND, TYP.
3. SPLICES AND DEVELOPMENT LENGTHS FOR SLAB REINFORCEMENT SHALL BE AS
FOLLOWS:
BAR SIZE CLASS 'B' SPLICE DEVELOPMENT LENGTH
LENGTH (FEET) 'L' (FEET)
#6 4'-2" 3'-4" #7 6'-10" 5'-4"
4. SEE 1/S-005 FOR ALLOWABLE SPLICE ZONES FOR INTERNAL & PERIPHERAL TIES.
5. SEE SLAB REINFORCEMENT SCHEDULE FOR TIES MAKERD WITH A LETTER.
6. SEE 2/S-005 FOR TYPICAL SLAB REINF. SECTION.
7. ADJUST REINFORCEMENT LAYOUT AS NECESSARY TO WORK AROUND PIPE
SLEEVES. AVOID CORE DRILLING SLAB.
PERIPHERAL TIE SLAB
REINFORCING SCHEDULE
MARK
P1
TIES
6-#6ROOF
INTERNAL TIE SLAB
REINFORCING SCHEDULE
T1 #6 @ 12" O.C.ROOF
P2 4-#6ROOF
F E D C
B
C13
C10
H
L K
J
G
C11
C12
P1
P1
P1
P
T1
T
P1
P
P
P1
P
P1
P
T1
T
P
P
T1
T1
T
P1
P1
P 1P
A
P2
P2
P 1P
T
P
T
P1
P1
C10.2
P2
P2
6'-0" 6'-0"
6'-0"
6'-0"
FUTURE STAIR
SHAFT OPENING
HOOK T1 BARS
FUTURE ELEVATOR
SHAFT OPENING
NOTES:
1. DEDUCT ALTERNATE #8: EXTEND PERIPHERALTIE SLAB
REINFORCING P1 ALONG GRID B BETWEEN GRIDS 6 & 7.
REMOVE PERIPHERAL TIE SLAB REINFORCEMENT P1
ALONG GRID A, 5.8 & 7.2.
ENGINEERS PLANNERS LANDSCAPE ARCHITECTS SURVEYORS 3D LASER SCANNING
VIKA MARYLAND LLC
W W W . V I K A . C O M
(301) 916-4100 FAX (301) 916-2262
20251 CENTURY BOULEVARD SUITE 400 GERMANTOWN, MARYLAND 20874
1451 Dolley Madison Blvd. Suite 220 McLean VA 22101-3812 703-827-9552 www.ehlert-bryan.com Department of
Veterans Affairs
Drawing Title:
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
A
B
C
D
E
F
Approved: Project Director
Project Title: Project Number:
Building Number:
Drawing Number:Location:
Date: Checked: Drawn:
Office of Construction and Facilities Management
ARCHITECTS/ENGINEERS:CONSULTANTS:
FULLY SPRINKLERED
STAMP
o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t n e in c h o n e fo o t n e a n d o n e h a lf in c h o n e fo o t re e i n c h o n e fo o t
VA FORM 08-6231. Oct 1978
H D
H D
P ro je ct
X
X X
X X
X X
X
"C o n su lt.
P ro je ct
X
X X
X X
X
635 S. Fairfax Street Alexandria, VA 22314 703.838.8414 www.healingdesign.com
Virginia
DESIGN-AIRE ENGINEERING, INC.
www.daengineering.com317.464.9090
220 North College Avenue
Indianapolis, Indiana 46202
EB#1450072
DWG. OF
:2 :4
A M
C U s e rs a s c h m it t\ D o c u m e n ts J o b s s tr u c
R ic h m o n d
V A M C a s c h m it t.
rv t
S-005
1201 BROAD ROCK BLVD. RICHMOND, VA 23249
COMMUNITY LIVING CENTER
EXPANSION AND RENOVATION
SLAB REINFORCING PLAN
Checker SLSAPRIL 14, 2017
VA 246 14R 0013
100% CONSTRUCTION DOCUMENTS
SECTION
SCALE: 1/8" = 1'-0" S-005
1SECTION
SCALE: 3/4" = 1'-0" S-005
SECTION
SCALE: 3/4" = 1'-0" S-005
3SECTION
SCALE: 1 1/2" = 1'-0" S-005
SCALE: 3/32" = 1'-0" S-005
ROOF SLAB REINFORCING PLAN A
F E
B
C13
C10
H
L
K
K
EXISTING HOSPITAL
S-201
TYP.
S-201
S-201
J
G
APPROXIMATE
LOCATION OF EXIST
UNDERGROUND
TUNNEL w/ TOS=80'
F6 F1
F5
F3
F3
F4
EXIST CONC WALLS
F3
P3
P1
P1
P1
P1
P1
P1
P1
P1
P1
TOP= 99'-0
TF= 96'-8
TOP= 99'-0
TF= 97'-8
TOP= 99'-0
TF= 97'-8
TOP= 99'-0
TF= 97'-8
"TOP= 99'-0
TF= 97'-8
TOP= 98'-8
TF= 82'-0
TF= 99'-0
TF=
'-0
F8
SEE S101b
9'-1 1/2"
F.S.
P1
TOP= 99'-0
TF= 82'-0
F4
F5
6'-0" 6'-0"
F4
TO
P= 9
9'- 0"
TF= 9
4'-
0"
P5
P3
P3
P4
P1
S-202
F4
P1
TO
P= 99'-0"
TF= 90'-0"
P1
T F
'-0
T F
'-0
T F
'-0
T F
'-0
T F
'-0
T F
'-8
T F
'-8
T F
'…