36C24618R0096-00002004.pdf

PDF 394 KB Posted

Attached to
Expand and Renovate CLC, Bldg 500, 1st Floor (minor construction)
Solicitation number
36C24618R0096
Issued by

About this file

36C24618R0096 00002 ELECTRICAL-EP103.pdf

View the file

Other files

File Type Posted
36C24618R0096-00004002.pdf PDF
36C24618R0096-00004001.docx DOCX document
36C24618R0096-00004003.pdf PDF
36C24618R0096-00004000.docx DOCX document
36C24618R0096-00003000.docx DOCX document
36C24618R0096-00002003.pdf PDF
36C24618R0096-00002000.docx DOCX document
36C24618R0096-00002002.pdf PDF
36C24618R0096-00002001.pdf PDF
36C24618R0096-00001009.pdf PDF
36C24618R0096-00001004.pdf PDF
36C24618R0096-00001000.docx DOCX document
36C24618R0096-00001005.pdf PDF
36C24618R0096-00001006.pdf PDF
36C24618R0096-00001008.pdf PDF
36C24618R0096-00001001.pdf PDF
36C24618R0096-00001002.pdf PDF
36C24618R0096-00001010.pdf PDF
36C24618R0096-00001011.pdf PDF
36C24618R0096-00001007.pdf PDF
36C24618R0096-00001003.pdf PDF
36C24618R0096-017.pdf PDF
36C24618R0096-016.pdf PDF
36C24618R0096-003.docx DOCX document
36C24618R0096-005.docx DOCX document
36C24618R0096-014.pdf PDF
36C24618R0096-008.pdf PDF
36C24618R0096-012.pdf PDF
36C24618R0096-004.docx DOCX document
36C24618R0096-011.pdf PDF
36C24618R0096-010.pdf PDF
36C24618R0096-018.pdf PDF
36C24618R0096-007.pdf PDF
36C24618R0096-013.pdf PDF
36C24618R0096-009.pdf PDF
36C24618R0096-015.pdf PDF
36C24618R0096-019.pdf PDF
36C24618R0096-002.docx DOCX document
36C24618R0096-001.docx DOCX document
36C24618R0096-006.pdf PDF
36C24618R0096-020.pdf PDF
36C24618R0096-000.docx DOCX document
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

125A 3P

100A 3P

200A 3P

200A 3P

600A 3P

NEW DISTRIBUTION PANEL "DP"

(277/480V, 3ɸ-4W, 600AMP BUS)

600A 3P

EXISTING SWITCHBOARD (LOCATED IN VAULT NO. 1 IN LOWER LEVEL OF AREA M - SEE SHEET EP100) (277/480V, 3Ø-4W)

SPARE

(FUTURE 2ND FLR.)

TVSS

SPARE

(FUTURE 3RD FLR.)

TRANS. "TXLA"

(75 KVA)

ONE-LINE DIAGRAM NOTES/FEEDERS

INSTALL NEW CIRCUIT BREAKER IN EXISTING SWITCHBOARD SPARE

SPACE. NEW BREAKER SHALL BE COMPATIBLE WITH EXISTING

SWITCHBOARD. MATCH KAIC RATING OF EXISTING SWITCHBOARD.

NEW CIRCUIT BREAKER SHALL HAVE POWER MONITORING AND

METERING DEVICE THAT SHALL RECORD, STORE AND TREND THE

FOLLOWING:

a) VOLTAGE

b) CURRENT

c) KW

d) KWh

e) KVAR

f) POWER FACTOR

g) VOLTAGE ND CURRENT TOTAL HARMONIC DISTORTION

(2) 3" CONDUITS, EACH CONTAINING 4 - #350MCM, 1 - #1 GND.

3-#8, 1-#8GND IN A 3/4"C.

4 - #1, 1 - #8 GND IN A 1-1/2" C.

4 - #4/0, 1 - #2 GND IN A 2 1/2" C.

4 - #2, 1 - #8 GND IN A 1 1/2" C.

3 - #10, 1 - #10 GND IN A 3/4" C.

INSTALL NEW 100A-3P CIRCUIT

BREAKER IN EXISTING PANEL

FOR FEED TO NEW EMERGENCY

PANEL. NEW BREAKERS SHALL

BE SIMILAR TO 'G.E.' TYPE THED

BREAKERS AND SHALL BE

COMPATIBLE WITH EXISTING

PANEL.

65K A.I.C.

GENERAL NOTES:

1. ALL CONDUCTORS SHALL BE COPPER

2. ALL PANELBOARDS AND WIRING SHOWN ON THIS PLAN ARE NEW,

UNLESS OTHERWISE INDICATED.

50A 3P

30A 3P

NEW "T-EQ"

30 KVA

480V DELTA PRI.

120/208V WYE SEC.

NEW "T-LS"

30 KVA

480V DELTA PRI.

120/208V WYE SEC.

NEW "T-CB"

30 KVA

480V DELTA PRI.

120/208V WYE SEC.

30A 3P

SPARE

M

100/3

ONE-LINE DIAGRAM

(EMERGENCY CRITICAL BRANCH)

NOT TO SCALE

ONE-LINE DIAGRAM

(EMERGENCY LIFE SAFETY)

NOT TO SCALE

100/3

EXISTING BREAKERS ARE 'EATON' TYPE MAGNUM DS.

CONTRACTOR SHALL PROVIDE COORDINATION STUDY AND

COORDINATE ALL BREAKERS.

SPARE

3 - #1, 1 - #8 GND IN A 1-1/2" C.10

CONTACT JOHN COOLEY WITH

'EATON' AT (804) 301-0494 FOR

ADDITIONAL INFORMATION.

ENGINEERS PLANNERS LANDSCAPE ARCHITECTS SURVEYORS 3D LASER SCANNING

VIKA MARYLAND LLC

W W W . V I K A . C O M

(301) 916-4100 FAX (301) 916-2262

20251 CENTURY BOULEVARD SUITE 400 GERMANTOWN, MARYLAND 20874

1451 Dolley Madison Blvd. Suite 220 McLean VA 22101-3812 703-827-9552 www.ehlert-bryan.com Department of

Veterans Affairs

Drawing Title:

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

A

B

C

D

E

F

Approved: Project Director

Project Title: Project Number:

Building Number:

Drawing Number:Location:

Date: Checked: Drawn:

Office of Construction and Facilities Management

ARCHITECTS/ENGINEERS:CONSULTANTS:

FULLY SPRINKLERED

STAMP

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e r in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h o n e fo o t th re e in c h o n e fo o t

VA FORM 08-6231. Oct 1978

HD

HD

P ro je ct

XX

XX

XX

XX

"C on su lt.

" P ro je ct

X1

635 S. Fairfax Street Alexandria, VA 22314 703.838.8414 www.healingdesign.comVirginia

DESIGN-AIRE ENGINEERING, INC.

www.daengineering.com317.464.9090 220 North College Avenue Indianapolis, Indiana 46202

EB#1450072

DWG. OF

1201 Broad Rock Blvd. Richmond, VA 23249

COMMUNITY LIVING CENTER

EXPANSION AND RENOVATION

EWB DAEAPRIL 14, 2017

VA 246 14R 0013

100% CONSTRUCTION DOCUMENTS

Lic. No. 13101

EARL WADE BOULWAREC

OM

MO NWE A LT H O F VI RG I N I A

P

RO

F E S S I O N A L E N G I N E E R EP103

ELECTRICAL ONE LINE DIAGRAM

NO SCALE1 ELECTRICAL ONE - LINE DIAGRAM

P

M

AutoCAD SHX Text

PROPER GROUNDING CONNECTIONS.

AutoCAD SHX Text

E.C. SHALL FOLLOW THIS DETAIL FOR

AutoCAD SHX Text

SWITCHBOARD (MSB)

AutoCAD SHX Text

AT MAIN

AutoCAD SHX Text

AutoCAD SHX Text

3/O CU

AutoCAD SHX Text

3/O CU

AutoCAD SHX Text

CONCRETE FOUNDATION

AutoCAD SHX Text

TO RE-STEEL IN

AutoCAD SHX Text

WATER SYSTEM

AutoCAD SHX Text

CONNECT TO COLD

AutoCAD SHX Text

NEUTRAL BUS

AutoCAD SHX Text

GROUND BUS

AutoCAD SHX Text

EQUIPMENT

AutoCAD SHX Text

SURGE ARRESTOR

AutoCAD SHX Text

3/0 CU

AutoCAD SHX Text

3/0 CU

AutoCAD SHX Text

CONNECTION TO STRUCTURAL STEEL OF BLDG.

AutoCAD SHX Text

COLD WATER PIPE

AutoCAD SHX Text

WATER METER

AutoCAD SHX Text

3/O CU SHUNT

AutoCAD SHX Text

AROUND WATER METER

AutoCAD SHX Text

TO WATER METER

AutoCAD SHX Text

3/O CU

AutoCAD SHX Text

DISC. LINK

AutoCAD SHX Text

FIELD.)

AutoCAD SHX Text

4 ROD GROUNDING

AutoCAD SHX Text

(TYP. FOR 3 OR

AutoCAD SHX Text

10' MIN.

AutoCAD SHX Text

3/0 CU

AutoCAD SHX Text

TO DRY TRANSFORMER(S)

AutoCAD SHX Text

3/0 CU

AutoCAD SHX Text

MAIN BONDING

AutoCAD SHX Text

CODE SIZED

AutoCAD SHX Text

JUMPER

AutoCAD SHX Text

%%UGROUNDING DETAIL

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

3/O CU

AutoCAD SHX Text

3/O CU

AutoCAD SHX Text

3/O CU

AutoCAD SHX Text

(3) 3/4" COPPERWELD 10' LONG GROUND RODS (TYPICAL)

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"LB"

AutoCAD SHX Text

225A MCB

AutoCAD SHX Text 120/208V

AutoCAD SHX Text

22 KAIC

AutoCAD SHX Text

(DOUBLE TUB)

AutoCAD SHX Text 30A 3P

AutoCAD SHX Text 15A

AutoCAD SHX Text

AHU-1

AutoCAD SHX Text 30A 3P

AutoCAD SHX Text 15A

AutoCAD SHX Text

SIZE 1

AutoCAD SHX Text

EF-1

AutoCAD SHX Text

SEE GROUNDING DETAIL

AutoCAD SHX Text

PROVIDE SUB-METERING

AutoCAD SHX Text

EXIST. INCOMING FEEDER

AutoCAD SHX Text

EXIST. PANEL 'ECPDOZ' (CRITICAL)

AutoCAD SHX Text

EXIST. INCOMING FEEDER

AutoCAD SHX Text

EXIST. PANEL 'ESPDOZ' (LIFE SAFETY)

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"HA"

AutoCAD SHX Text

100A MCB

AutoCAD SHX Text 277/480V

AutoCAD SHX Text

22 KAIC

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"LA"

AutoCAD SHX Text

225A MCB

AutoCAD SHX Text 120/208V

AutoCAD SHX Text

22 KAIC

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"ELEQ"

AutoCAD SHX Text

100A MCB

AutoCAD SHX Text 120/208V

AutoCAD SHX Text

22 KAIC

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"EHLS"

AutoCAD SHX Text

100A MCB

AutoCAD SHX Text 277/480V

AutoCAD SHX Text

22 KAIC

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"ELLS"

AutoCAD SHX Text

100A MCB

AutoCAD SHX Text 120/208V

AutoCAD SHX Text

22 KAIC

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"EHCB"

AutoCAD SHX Text

100A MCB

AutoCAD SHX Text 277/480V

AutoCAD SHX Text

22 KAIC

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

"ELCB"

AutoCAD SHX Text

100A MCB

AutoCAD SHX Text 120/208V

AutoCAD SHX Text

22 KAIC

Sheets and Views
EP103

File details come from the government source that posted it.